MS Routine Monitoring and Maintenance

Size: px
Start display at page:

Download "MS Routine Monitoring and Maintenance"

Transcription

1 MS Routine Monitoring and Maintenance PT100 and EM controls incubators and hatchers ventilation checklists specifications for ventilation and fan blade spacing

2 The Jamesway multi-stage incubator system is an efficient material handling and incubation system, producing strong, healthy, active chicks. Nevertheless, in order to obtain optimal production, management should establish and implement regular monitoring and regular maintenance schedules. Maximum benefit will not be obtained if one is implemented without the other. Adapt a monitoring and maintenance program tailored to your specific needs using this manual and Note: The monitoring and maintenance information contained with this chapter is the basic requirement for good performance. To further enhance performance, refer to Chapter 7, Optimizing Performance on page 143. the manual for your control system. BASIC GUIDELINES FOR MONITORING EQUIPMENT Jamesway recommends that personnel from maintenance take and record the following readings using a checklist and the time schedule as suggested below. Assess each item. Is it operating satisfactorily? Unsatisfactory would include variance between set points and actual readings, equipment not functioning or showing excessive wear, dirt build up or any other potential problem. All problems should be investigated and corrected prior to further use. Check Space Saver Intake Duct after each set. to prepare and follow a checklist suited to your hatchery. TEMPERATURE AND HUMIDITY READINGS Record the temperature and humidity readings. Note any variance between actual and set points. Make necessary corrections. MONITORING INCUBATORS It is important to assess the general machine condition as well as the temperature and humidity at prescribed times. This time schedule varies. General machine condition which includes such items as the position of the eggs rack, baffles, curtains, etc. should be checked immediately after every set. Spray nozzles and audible alarms should be checked daily. Also, temperature and humidity should be read, recorded and compared on a twice daily basis. Check the egg turn mechanism every three hours. A table for monitoring incubators, including items and time schedules, is on page 103. Use this table, SPACE SAVER INTAKE DUCT Mixing of incoming fresh air with re-circulating air is important to proper machine function. To ensure that fresh air is correctly mixed, an intake duct has been installed on the centre post between the entrance end doors. The duct includes an upper section attached to the roof and a lower section attached to the centre post. The lower portion is easily removable for cleaning purposes. Since the duct is not permanently attached and protrudes into the entrance end slightly, care must be taken when loading eggs. Check the intake duct

3 after each set. Make sure it is in the proper position and if required, reposition. The correct spacing is 5/8 inches (15.5 mm) and the duct should be parallel with the centre post on both sides. MONITORING HATCHERS It is equally important to monitor hatchers. Assess the general machine condition as well as the temperature and humidity at prescribed times. This time schedule varies. General machine condition which includes such items as fan blades, heat elements, etc. should be checked prior to transfer. Spray nozzles should be checked daily. Also, temperature and humidity should be read, recorded and compared on a twice daily basis. A table for monitoring hatchers, including items and time schedules, is on page 104. Use this table, to prepare and follow a checklist suited to your hatchery. TEMPERATURE AND HUMIDITY Record the temperature and humidity readings. Note any variance between actual and set points. Make necessary corrections. MONITORING VENTILATION EQUIPMENT ENVIRONMENTAL CONDITIONS Install magnehelic gauges to assist you in monitoring the incubator and hatcher environments. Mount them in a stationary position in the vicinity of the pressure controllers, making sure they are level. Install a tee on the tube running from the exterior to the controller low pressure port. Connect a tube from the low pressure port of the magnehelic gauge to the tee. Both the controller and magnehelic should have similar readings. Establish a program to monitor and record their readings, as well as the temperature and humidity readings of each room. Readings should be recorded twice daily and twice nightly. With this type of program, you should be able to pick up any malfunction of the ventilation equipment. A table for monitoring the ventilation system is on page 105. Jamesway recommends all hatcheries maintain a Note: In some instances the pressure controller may be mounted externally to the room. In these cases the monitoring instrument must be connected to the low pressure (external reference) and room high pressure tubes. A tee on both lines is required. Monitoring Schedule for Incubators All of the items mentioned below should be checked, as scheduled. Refer to page 101 for additional notes. Actual readings should be recorded and compared with the optimum. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. A) Temperature Calibration 1. Display reading F or C 2. Check reading F or C 3. Set point F or C B) Humidity Calibration 1. Display reading RH FWB or CWB 2. Check reading RH FWB or CWB 3. Set point RH FWB or CWB C) General Machine 1. Position of egg rack against the venturi 2. Rubber baffle condition 3. Curtain condition 4. Curtain position 5. Heat rods 6. Fan rotation 7. Motor off switches 8. Doors seal properly 9. Doors latch properly 10. Door gasket condition 11. Threshold gasket condition 12. Threshold position 13. Space Saver intake duct position 14. Egg turning mechanism 15. Audible alarms 16. Spray nozzles, no excessive dripping 17. Spray nozzle pattern 60 Immediately After Every Set Every 3 Hours After Set Twice Daily Daily

4 Monitoring Schedule for Hatchers All of the items mentioned below should be checked, as scheduled. Refer to page 102 for additional notes. Actual readings should be recorded and compared with the optimum. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. A) Temperature Calibration 1. Display reading F or C 2. Check reading F or C 3. Set point F or C B) Humidity Calibration 1. Display reading RH FWB or CWB 2. Check reading RH FWB or CWB 3. Set point RH FWB or CWB C) General Machine 1. Fan blade condition 2. Fan blade spacing 3. Fan rotation 5. Heat rings 6. Hatcher rack track condition 7. Hatcher rack track position 8. Doors seal properly 9. Doors latch properly 10. Door gasket condition 11. Threshold gasket condition 12. Threshold position 13. Spray nozzles, no excessive dripping 14. Spray nozzle pattern 60 Pre-Transfer Twice Daily Daily Monitoring Schedule for Ventilation All of the items mentioned below should be checked, as scheduled. Refer to page 102 for additional notes. Actual readings should be recorded and compared with the optimum. Investigate any inconsistent readings. Record in each plenum A) Magnehelic Gauge 1. Display reading in.w.g or Pa 2. Check reading in.w.g or Pa 3. Optimum pressure in.w.g or Pa B) Temperature 1. Display reading F or C 2. Check reading F or C 3. Optimum temperature F or C C) Humidity 1. Display reading RH FWB or CWB 2. Check reading RH FWB or CWB 3. Optimum humidity RH FWB or CWB Twice Daily and Twice Nightly

5 catalogue of the ventilation equipment, as well as the components of that equipment, including motor size, pulley and belt size, etc. It is also important to become familiar with the operations of the ventilation equipment. From this information, you can establish both a spare parts list and a routine preventive maintenance program. ROUTINE MAINTENANCE FOR INCUBATOR PT100 CONTROLS Refer to the checklist on page 115. WEEKLY Reservoir Clean the water reservoir with detergent and a bottle brush to minimize the build-up of mineral deposits. If necessary, add distilled water to the reservoir. (Filling the reservoir with distilled water may also be required between weekly cleaning.) Wick Replace the wick every seven (7) days or more frequently, depending upon the mineral content of the water. Mineral deposits can build up in the wick, resulting in false readings. To Install a Wick Hold the top of the wicking with one hand. Gently slide over the extended end of the probe. Seat the wicking firmly around the probe. Place the free end of the wicking into the reservoir, Make sure it does not twist or bend. Any twists or bends will interrupt the flow of water through the wicking. The wicking should be 12 in. (30 cm) in length. other mild acid solvent; rinse thoroughly with water. Failure to do so may result in probe deterioration. If water quality is poor, probes may require more frequent cleaning. Make sure that the temperature probe baffle is not out of position or damaged. The baffle should be on a horizontal plane to protect the probe from coming into direct contact with the spray or stray water particles. Calibration - placement of the electro-therm (HA1071) next to the PT100 sensor Calibration Check the accuracy of the temperature and readings. It is important that the electro-therm (HA1071) be positioned correctly next to the PT100 probe. Allow the shaft of the electro-therm to bend. Fit the tip of the shaft into the plastic sleeve and as close to the PT100 sensor as possible. They should not touch. For the testing procedure and calibration refer to The PT100SMT Controls and System Manual, page 85. Display Panel Check the PT100 display panel during normal incubator operation. Dial the temperature or humidity thumbwheel switches up or down to simulate various machine conditions. Dial the humidity thumbwheel up 2 degrees or more. The low humidity LED should flash. Note: Remember to turn the thumbwheel switches back to their original set points once the check is completed. High Temperature Dial the temperature thumbwheel down 1 degree. The high temperature LED and alarm should flash, the damper should start opening, water should spray, and the audible alarm should ring. Alternatively, press and hold the Test button on the display panel until a 1 appears. This will activate the audible alarm. Low Temperature Dial the temperature thumbwheel switch up 2 degrees. The low temperature LED should flash. Fan Motor Off Switch Turn off the fans and unplug one motor. Then, turn the fans back on. The fan failure LED should flash and the audible alarm should ring. Repeat the process, switching off the fans each time before each motor is unplugged. This checks each fan motor off switch for correct function. Turn Failure Disconnect the turn cables at any location. The turn failure LED should flash after 5 to 7 minutes. If selected, the audible alarm also should ring. Power Off Turn off the power to the incubator. All of the LEDs on the display panel should go out, causing the au- Note: On the PT100SMT display, all digits and LEDs will light up when the Reset button is pushed. On the PT100 display, all digits and most of the LEDs will light up. In the System Status, only the Damper Open and Damper Closed LEDs will light. The heat, spray and egg turn LEDs will not light up unless they were already lit before the Reset button was pushed. dible alarm to ring. Alarms Warning: The PT100 controller should only be serviced by qualified maintenance personnel. Do not attempt to service the controller while it is turned on. Some circuits are energized with 220 or 380 volts ac. They will cause serious shocks, injury or death if touched. Before servicing the control box, ensure that CB1, CB2 and CB3 are turned off. If the audible alarm bell does not ring for high temperature, fan off or power off, check the battery, battery connections or alarm circuit. Display Panel LEDs Press the Reset button for less than 3 seconds to turn on LEDs. (See Note.) If a digit segment or LED does not work, replace the display panel. EVERY THREE MONTHS Probes Hard water causes the probes to develop lime and calcium deposits. To clean the probes remove the probe baffle. Wash the probes in white vinegar or High Humidity Dial the humidity thumbwheel down 2 degrees or more. The high humidity LED and alarm lamp should flash. Alternatively, remove the wick from the probe; remember to replace the wick after testing. Low Humidity PT100 Display Panel

6 Control Box Turn the fans off. Turn the power off - CB1, CB2 and CB3. Refer to page 56. Open the control box, and examine the PT100 boards Incubator Thermostat Board and wiring, wiring connections and relay contacts for obvious faults such as discoloured wiring, and burned or blackened areas. Pay special attention to terminals, connections and relay points. Vacuum the interior if dust, chick down or metal shavings have accumulated. After vacuuming, ensure plug connections are snug. In older models, check that the boards are firmly seated. Turn the power back on. Turn the fans back on. ROUTINE MAINTENANCE FOR INCUBATOR ELECTRO-MECHANICAL CONTROLS Refer to the checklist on page 116. WEEKLY Reservoir Clean the water reservoir with detergent and a bottle brush to minimize the build-up of mineral deposits. If necessary, add distilled water to the reservoir. Wick Replace the wick every seven (7) days or more frequently, depending upon the mineral content of the water. Mineral deposits can build up in the wick, resulting in false readings. Warning: The thermostat contacts are electrically live. Therefore, open the control panel and disconnect the power to the thermostats before removing. Failure to do so could result in injury. To Install a Wick Hold the top of the wicking with one hand. Gently slide over the extended end of the probe. Seat the wicking firmly around the probe. Place the free end of the wicking into the reservoir, Make sure it does not twist or bend. Any twists or bends will interrupt the flow of water through the wicking. The wicking should be 12 in. (30 cm) in length. EVERY THREE MONTHS Thermostats Hard water will cause lime deposits to form on the thermostats. Wash the thermostats in white vinegar or other mild solvent. Rinse thoroughly in cold water. The clips also should be cleaned with a fine emery cloth to remove mineral deposits. If water quality Warning: In order to test the following circuits, switch the power on. Jamesway recommends that you use an insulated jumper wire with insulated alligator clips or probes to perform the following checks. Make sure all personnel are clear of the fans before switching on. is poor, thermostats may require more frequent cleaning. Information Panel Check for burned wires, defective relays and burned out bulbs. Control Box The best time to check the control box is after complete clean-out. Wires, Connections and Bulbs Turn the power off. Open the control box, the cover interlock switch will disconnect the power to fans. Check the wiring, wiring connections and relay contacts for obvious faults, such as discoloured wiring, or burned or blackened areas. Pay special attention to relays points, connections and terminals. Check for burnt out bulbs. Close the Control Box Cover, the fans will switch on. High Temperature Circuit Using the insulated jumper wire, connect one clip to bottom contact of one of the thermostats. Attach the other clip to the top contact of the High Temperature thermostat (middle thermostat). The high temperature light on the Information Panel comes on, the audible alarm will sound, and the damper starts opening. If the heat and auxiliary heat pilot light are on they will turn off during this test. Remove jumper wire from both contacts when test is complete. Heat Circuit Main Heat Attach jumper wire to the bottom contact of a thermostat. Connect the other insulated alligator clip to the top contact of the Heat thermostat (5th from left) once the heat pilot light illuminates. The heat pilot light should turn off and the damper starts to open. Remove jumper wire from both contacts, the heat pilot light illuminates and the damper starts to close. pilot light illuminates. The auxiliary heat pilot light should turn off. Remove jumper wire from both contacts when test is complete. Low Temperature Circuit. The Low Temperature circuit can be tested for proper function immediately after fresh eggs have been loaded into the machine. Using an insulated jumper wire, connect one clip to bottom contact of one of the thermostats. Attach the other clip to the top contact of the Low Temperature thermostat (2nd from left). The Low Temperature light on the Information Panel should go out and the humidity spray will come on. Remove the jumper wire, the Note: If the bell does not ring to indicate high temperature, motor off and/or power off, check the battery, the battery connections or the alarm circuit. Replace pilot lights as required. Be careful during this examination of the control box since the power has not have been disconnected. Warning: If rewiring or relay replacement is required, turn off the power. Failure to do so could result in injury. Auxiliary Heat Attach jumper wire to the bottom contact of a thermostat. Connect the other insulated alligator clip to the top contact of the Auxiliary Heat thermostat (4th from left) once the auxiliary heat

7 spray will stop and the Low Temperature light will come on. Humidity Circuit To check the High Humidity Light on the Information Panel remove the wick from the humidistat. Replace the wick once the test has been completed. The Low Humidity light on the Information Panel should be checked following each set of fresh eggs. Motor Off Circuit Turn off the fans and unplug one motor. Then, turn the fans back on. The Motor Off light on the Warning: The tray frames will turn when air lines are connected, possibly causing injury. Therefore, ensure that no one is working within the tray frames or any other component of the incubator racks when you are connecting the air lines. information panel should illuminate and the audible alarm should ring. Repeat the process, switching off the fans each time before each motor is unplugged. This checks each fan motor off switch for correct function. Power Off Check Turn off the power to the incubator. All the lights for the machine being tested should go out on the Information Panel causing the audible alarm to ring. ROUTINE MAINTENANCE FOR INCUBATORS Refer to the checklist on page 117. BEFORE EVERY SET Egg Tray Frames Before loading egg racks, check the egg tray frame turning mechanism. Connect the air lines to the compressed air supply. If any rubbing or binding occurs, locate and fix the problem. Check the turn sensors and cables by using a battery-operated tester. Space Saver Intake Duct Check the spacing of the intake duct. The correct spacing is 5/8 inches (15.5 mm) and the duct should be parallel with the centre post on both sides. Replace or repair damaged parts as required. AFTER EVERY TRANSFER Incubator Racks Grease all castor wheels and plate bearings after sanitizing the incubator racks. One or two pumps of a grease gun should suffice. Any more will result in forcing grease out through the rubber seals. WEEKLY Spray Nozzles Clean the spray nozzles. After cleaning, check the water nozzle spray pattern. It should be a 60 degrees fan pattern and there should be no excessive dripping. If the nozzles are not producing the correct spray pattern, they may need to be replaced or the water pressure may be too low. Check the water spray nozzles for correct distance from the ceiling and correct positioning. Refer to page 136 for specific measurements. Dismantle the spray nozzle for cleaning. Spray Nozzle Condition Both water pressure and nozzle condition affect droplet size and number, which in turn, affects how efficiently moisture is absorbed into the air. Inevitably, some water droplets injected into the air stream are deposited on surfaces or objects in the flow path. When water is laden with minerals, the solids are left behind as the water evaporates. Note: The spray nozzles are located in front of the fans. To avoid injury, turn off the fans before removing the nozzles. Use a small, narrow stiletype stepladder to stand upon when disconnecting the nozzles. Nozzles block or partially block. The spray pattern is disrupted and excessive dripping occurs. Drip pans, rack tops, extrusions, panels and sensors quickly become encrusted with these deposits. Not only is this unsightly, but cleaning becomes difficult, protective coatings rapidly diminish and corrosion is accelerated. Routine maintenance becomes unpleasant and machine performance is reduced. Low water pressure, partially blocked nozzles, or poor spray pattern can result in uneven temperature distribution, measured at the exit end of the machine, e.g., top section temperature is highest while the bottom section is lowest. Therefore, maintain the spray nozzles to specifications for optimum performance. Refer to page 42 for water pressure and water quality specifications. To Clean Spray Nozzles Disconnect the nozzles at the Kwik coupler. Remove the nozzles from the body and dismantle. Clean the nozzle components in an ultrasonic cleaner. Alternatively, soak the parts in pure white vinegar or other mild solvent; thoroughly rinse. Do not use a wire to clean the orifice. This could result in damage and an incorrect spray pattern. To Check the Water Pressure Check the water pressure at the nozzles by inserting a gauge fitted for the Kwik connect into the coupling. The pressure should be at least 65 psi (5 bars). Water Pan Check the water pan level. Water pans should remain relatively dry. If not, excessive spraying probably has occurred. If one pan is full and the other empty, check for blocked nozzles on the empty side. Otherwise, check for poor incubator room conditions. The optimum room temperature is 80.0 F (26.6 C), with a relative humidity of 50 to 60 percent. Door Seals Check door seals for torn or missing door gaskets. Threshold Gasket. Replace if worn. Gaskets on rack baffle, side wall and venturi. Check both sides. Air Compressor Regulator

8 Replace missing or worn gaskets. Damaged door gaskets can result in poor air flow. Threshold Gaskets Check the threshold gasket for wear. If it is damaged, replace it. Curtains Check incubator rack curtains and brackets for damage. Any split or damaged curtains should be replaced. Rubber Gaskets Check all rubber gaskets on the rack baffle, side wall and venturi for damage. Replace any gaskets that are torn or damaged. Check the amperage of each heater. be between 11 and 14 amperes. If not, replace the heater element. Procedures on page 93. Avoid splashing water on motors and electrical connections. All motors and electrical connections must be dry before the incubator is restarted and warmed. Once the incubator has reached the appropriate temperature and humidity, the egg-filled racks can be returned in their correct order to the incubator. Proceed to check the following systems. (The best Note: If fan motors are repaired or rewound, it is recommended that revolutions per minute (rpm) be checked when the motors are reinstalled in an incubator. Use motors of similar rpm (± 2.5%) in each incubator. Do not mix low rpm motor with high rpm motors and vice versa. should be identical. The damper openings should be 1/2 in. (13 mm) when the damper is in the fully closed position. Fan Motors, Switches and Blades Clean fan motor off switches, blades and motors during complete clean-out and sanitation. Refer to Chapter 5 - Cleaning Procedures on page 93. Fan Blade Spacing and Motor RPM Compressor Drain the water from the air compressor and filter/ Note: To avoid injury, turn off the fans and turn off power before unplugging or working with fans. Before switching the fans on again, allow them to stop completely. If you do not, some of the fans may run backwards, upsetting the air flow. All fans should run in a counter-clockwise direction when viewed from behind the motor. If a fan does run backwards, simply switch it off, allowing it to stop before turning it on. trap regularly. Older air compressor regulators are mounted near the entrance of the incubator. The compressed air moisture trap is not self-draining. On newer models, drain the air compressor regulator by opening the petcock at the base of the automatic drain trap; closing it when all water has been drained. All compressor tanks have a drain petcock located on the underside. Open the petcock and drain until the escaping air is clear of water or water vapour. MONTHLY Heat Rods Use an ampere clamp (or amp probe) to check the amperage of each heater. The reading should Fans Check for excessive fan vibration. If you are unable to read the nameplate on the motor clearly or the motor frame assembly is rattling, the fan is vibrating too much. Before determining the cause of the excessive vibration, turn off the fans and turn off the power to the incubator. Inspect the motor mounts for loose bolts and connections, the motor for worn bearings, and the fan blade for correct pitch or distortion. See pages 138 to 142 for fan specifications. If vibration continues, replace the motor or fan blade. EVERY THREE MONTHS Wash and Sanitize Thoroughly clean the interior of the incubator. There is no need to leave one incubator empty for this purpose, although some hatcheries prefer to do so. Eggs can be held in other incubators (position 6) or grouped together in a warm hallway. The inside of the incubator can be washed and sanitized using a team of three or four people. Organized properly, it should take no longer than 45 minutes to one hour to complete. Refer to Chapter 5 - Cleaning time to check these components is after eggs have been loaded into the incubator.) Damper System Checked for proper opening and closing. The arrow on the knob on the drive box will indicate if the damper is closing or opening. Check for the following potential problems: If the damper opens when the main heat is on, check for reversed wiring (EM Controls only). If the incubator calls for main heat, and the damper is not moving and is open more than 1/2 in. (13 mm) the damper drive motor may need replacing. If the knob on the drive box is turning but the damper is not moving, replace the plastic drive block on the threaded rod in the damper drive. The drive motor should be turning at 5-1/2 to 6 revolutions per minute. Both the intake and exhaust damper slides should move freely without binding. Also, the size of both openings Note: If the fan blade does not appear to be static, i.e., the mark appears, disappears, reappears, the strobe light flash rate may be set x2, x3, x4. (multiple of desired rpm) too high or too low. Adjust flash rate to rpm value on the nameplate. Water Line Strainer Upon completion, check the fan spacing. See page 138 to 142 for fan spacing for current motor mount PB4723 as well as older motor mounts. Procedure for Checking RPM Jamesway suggests the use of a strobe light to check rpm, as no physical contact with the motor is required and all motors can be checked at one time. With Note: practice Close fit the of strobe all racks light is essential can also for be proper used to air flow. Incubator racks must never have a space between them of more than 1/4 inch (6.35 mm) top or bottom. If shifting of the floors or a loose levelling screw pushes the tracks out of level, adjust the tracks.

9 identify fan blade defects. Check the rpm when the motor is under load, i.e., when incubator is in normal operation and filled with eggs. Plug strobe light into power source. Stand Maintenance Schedule for PT100 Incubator Controls All of the items mentioned below should be checked, as scheduled. Refer to page 106 and your control manual for additional notes. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. Weekly Every 3 in the entrance end of incubator. Switch on strobe light and switch off incubator lights. Adjust the strobe flash rate to a value similar to rpm marked on motor nameplate, e.g., Motor PB5146: 1625 rpm at 60 Hz, 1325 rpm at 50 Hz. Fine-tune until fan blades appear to stop. Focus on a blade that is easily identifiable (small scratch or Racks must fit closely and evenly for proper air flow. If shifting of the floors or a loose levelling screw pushes the tracks out of level, adjust the tracks. Switch Plate for Side-Door Incubators A) Sensor 1. Reservoir - clean and fill as required 2. Wick - replace 3. Probes - clean B) Calibration (See PT100SMT Controls Manual, page 86.) C) Display Panel - check the following LEDs 1. High Humidity 2. Low Humidity 3. High Temperature 4. Low Temperature 5. Fan Motor Off Switch 6. Turn Failure 7. Power Off 8. Alarms D) Control Box 1. Clean, vacuum if required 2. Wire condition 3. Terminal condition 4. Relay condition 5. Boards - position firmly (older models) Warning: The PT100 controller should only be serviced by qualified maintenance personnel. Do not attempt to service the controller while it is turned on. Some circuits are energized with 220 or 380 volts ac. They will cause serious shocks, injury or death if touched. Before servicing the control box, ensure that CB1, CB2 and CB3 are turned off. Turn the fans off. Voltage Checkpoints. If required, refer to page 88 in The PT100SMT Control and System Manual.

10 Maintenance Schedule for Electro-Mechanical Incubator Controls All of the items mentioned below should be checked, as scheduled. Refer to page 108 and your control manual for additional notes. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. Maintenance Schedule for Incubators All of the items mentioned below should be checked, as scheduled. Refer to pages All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. Weekly Every 3 Months Before Every Set After Every Transfer Weekly Monthly Every 3 Months Every 6 Months A) Thermostat Board 1. Reservoir - clean and fill as required 2. Wick - replace 3. Thermostats - clean B) Information Panel 1. Wire condition 2. Relays and connections condition 3. Bulb condition C) Control Box 1. Clean, vacuum if necessary 2. Wire condition 3. Relays and connections condition 4. Bulb condition D) Check the following circuits 1. High Temperature 2. Heat 3. Humidity 4. Motor Off 5. Power Off Warning: 1. The thermostat contacts are electrically live. Therefore, before cleaning the thermostats, open the control panel and disconnect the power to the thermostats. Failure to do so could result in injury. 2. Before working on the Information Panel or Control Box, disconnect the fans and heater. 3. In order to check circuitry, switch the power on. Jamesway recommends that you use an insulated jumper wire with insulated alligator clips or probes to perform the following checks. Switch the power off after each test procedure. A) Egg Turning Mechanism 1. Turn operation condition 2. Air cylinder and fittings condition 3. Turn sensor and cable condition 4. Air lines condition 5. Air connections condition 6. Turning drop cords condition B) Space Saver Incubator 1. Intake duct position (5/8 inch or 15.5 mm) C) Incubator Racks 1. Wash and sanitize 2. General condition 3. Castors and bearing plate - grease D) Spray Nozzles 1. Clean, replace if required 2. Check spray pattern 3. Check position E) Water Pan 1. Check water level F) Doors 1. Doors seal properly 2. Doors latch properly 3. Door gasket condition 4. Threshold gasket condition Note: The air cylinders should be checked for leaks including damaged or worn parts. When checking racks and turning operation, look for excessive wear, binding or rubbing of any parts. For circuit checks, refer to page 109.

11 Maintenance Schedule for Incubators (continued) G) Rubber Gaskets 1. Baffles condition 2. Side wall condition Before Every Set After Every Transfer Weekly Monthly Every 3 Months Every 6 Months mark) and ensure that its location does not change. If the blade in the chosen position appears to be static, record the strobe flash rate. The recorded value is the revolutions per minute of the motor or motors. The reading taken with strobe light should be within ± 2.5% of rpm specified on motor nameplate. EVERY SIX MONTHS programs. Frequently cleaning with a high pressure washer subjects the hatcher to harsh conditions. ROUTINE MAINTENANCE FOR PT100 HATCHER CONTROLS Refer to the checklist on page Venturi condition H) Compressor 1. Reading 2. Water build-up? 3. Tank drain I) Heat Rods 1. Check amperage (11 to 14 amp) J) Fans 1. Fan condition (vibration?) 2. Switches, blades and motors - clean 3. Blade spacing - check 4. Motor rpm - check K) Damper 1. Opening and closing properly 2. Slides move freely 3. Damper openings equal 4. Closed position correct 5. Damper motor (5-1/2 to 6 rpm) L) General Machine 1. Wash and sanitize (See Chapter 5.) 2. Check joint, caulk as required Water Line Strainer Clean the water line strainer, which is generally located within the incoming water line and before the first incubator. Turn off the water, loosen the retaining nut, and remove the strainer screen. Flush and rinse the screen to remove debris. Replace the screen, insert and tighten the retaining nut, and turn the water back on. The frequency of cleaning will depend upon the mineral content of the water. V-Groove Tracks Check the level of the V-groove tracks if the space between any two incubator racks exceeds 1/4 in. (6.35 mm), top or bottom. If the space between two racks is greater at the top, then the track may be high at this point or low at the space between the preceding or following racks. To Level Tracking To raise tracking, turn levelling screws clockwise. To lower tracking, turn levelling screws counter-clockwise. Make sure that all wheels are in contact with the track. TWICE-WEEKLY Water Reservoir Clean the water reservoir with detergent and a bottle brush to remove chick down. Fill the water reservoir with distilled water only. This will help minimize the build-up of mineral deposits inside the reservoir. Wick Change the wick after each hatch, and after cleaning the reservoir. Mineral deposits build up in the wicking and can cause false readings. To Install a Wick Hold the top of the wicking with one hand. Gently slide over the extended end of the probe. Seat the wicking firmly around the probe. Place the free end of the wicking into the reservoir, Make sure it does not twist or bend. Any twists or bends will interrupt the flow of water through the wicking. The wicking should be 12 in. (30 cm) in length. M) Water Strainer 1. Clean N) V-Groove Tracking 1. Level as required O) Side-Door Incubators 1. Align switch plates Switch Plates In side-door entry/exit incubators, the proper alignment of the switch plates also should be checked. Careless handling of incubator racks, such as pushing too fast, can cause the switch plates to become miss-aligned. Realign all switch plates to prevent the wheels from jamming. HATCHERS Routine maintenance of hatchers, while similar to that of incubators, includes additional concerns because of the twice-weekly cleaning and sanitizing Calibration -placement of the electro-therm (HA1071) next to the PT100 sensor

12 EVERY THREE MONTHS Probes Hard water will cause a build-up of calcium and lime on the probes. Wash them in white vinegar or other mild solvent, and rinse thoroughly with water. Failure to do so may result in deterioration. If water quality is poor, you may have to clean the probes more often. Make sure that the temperature probe baffle is not out of position or damaged. The baffle should be on a horizontal plane to protect the probe from coming into direct contact with the spray or stray water particles. Calibration Note: Remember to move the thumbwheel dials back to their original set points once the check is completed. Check the accuracy of the temperature and readings. It is important that the electro-therm (HA1071) be positioned correctly next to the PT100 probe. Allow the shaft of the electro-therm to bend. Fit the tip of the shaft into the plastic sleeve and as close to the PT100 sensor as possible. They should not touch. For the testing procedure and calibration refer to The PT100SMT Controls and System Manual, page 85. Low Humidity The low humidity LED should be flashing since the actual humidity is below normal set point. If it is not, dial the humidity thumbwheel up 2 degrees or more above the actual humidity read-out. The low humidity LED should flash. High Temperature Dial the temperature thumbwheel down one degree PX Hatcher Air Cylinder Assembly or more below the actual temperature read-out. The high temperature LED and alarm lamp should flash, the damper should start opening, the blower(s) should come on, the auxiliary damper should start to lift, the spray usually should come on, and the audible alarm should ring. Alternatively, press and hold the Test button on the display panel until a 1 appears and the audible alarm is activated. dial the temperature thumbwheel switch up two degrees or more above the actual read-out. The low temperature LED should flash. Warning: The PT100 controller should only be serviced by qualified maintenance personnel. Do not attempt to service the controller while it is turned on. Some circuits are energized with 220 or 380 Vac. They will cause serious shocks, injury or death if touched. Before servicing the control box, ensure that CB1, CB2 and CB3 are turned off. Power Off Alarms Turn off the power to the hatcher. All LEDs on the display panel should go out and the audible alarm should ring. Fan Motor Off and Door Open Alarms Turn off the fans. The alarm should ring until a door is opened. Close the door and open the other. The alarm should ring momentarily. Wait Display Panel When the hatcher is empty, check the display panel. Follow the procedures normally implemented following clean-up, such as hooking up the fans and heat ring, locating the tracking, and installing the thresholds. Do not load the hatcher racks. Close the doors and switch on the machine. Wait for the hatcher to warm up to about 90 to 95 F (32 to 35 C). Dial the temperature or humidity thumbwheel switches up or down, to simulate various machine conditions. Low Temperature The low temperature LED should be flashing since the actual temperature is below set point. If not, PT100 Control Box showing CB1, CB2 and CB3 High Humidity Dial the humidity thumbwheel down 2 degrees or more below the actual humidity read-out. The high humidity LED and alarm lamp should flash. Alternatively, remove the wick from the probe.

13 until the fans stop rotating and unplug one motor. Close the door or hold down the door switch arm to simulate a closed door. Then turn the fan back on. The motor off LED should flash and the audible alarm should ring. Repeat the process, switching off the fan before reconnecting the first motor and unplugging another. This will check each motor off current sensing device for correct functioning. For PX Hatchers Air Cylinder Check the air cylinder function by dialling the temperature down 2 degrees or more (see the High Temperature check.) The 1-inch (25 mm) primary auxiliary cooling cylinder will be activated first, followed by the 2-inch (5 cm) secondary auxiliary cooling cylinder. For 2-Door Hatchers Blowers Check blowers by dialling the temperature down 2 degrees or more (see High Temperature). The blower(s) should come on. Auxiliary Damper Check the auxiliary damper operation (see High Temperature ). When the high temperature alarm rings, open the hatcher door and visually check that the auxiliary damper lifts clear of the slide. Electro-Mechanical Hatcher Thermostat Board ROUTINE MAINTENANCE FOR ELECTRO-MECHANICAL HATCHER CONTROLS Refer to the checklist on page 130. AFTER EVERY HATCH Thermostat Board Clean after every hatch. Do not use a high pressure Warning: The thermostat contacts are electrically live. Therefore, open the control panel and disconnect the power to the thermostats before removing. Failure to do so could result in injury. mixture with a paint brush. Do not get the electrical connections wet. Check the rubber grommets that seal the angle thermometers. The foam gasket on the thermostat assembly should be inspected and replaced if necessary. If the gasket is installed on the centre post, check it before installing the thermostat assembly. If the thermostat board assembly is plugged in correctly, the bulb will illuminate when the hatcher is switched on. If it does not light up, replace the assembly immediately. Warning: For the following procedure, switch the power on. Jamesway recommends that you use an insulated jumper wire with insulated alligator clips or probes to perform the following checks. Switch the power off after each test procedure. TWICE WEEKLY Water Reservoir Clean the water reservoir with detergent and a bottle brush to remove chick down. Fill the water reservoir with distilled water only. This will help minimize the build-up of mineral deposits inside the reservoir. Wick Change the wick after each hatch, and after cleaning the reservoir. Mineral deposits build up in the wicking and can cause false readings. To Install a Wick Thermostats Hard water will cause lime deposits to form on the thermostats. Wash the thermostats in white vinegar or other mild solvent. Rinse thoroughly in cold water. The clips also should be cleaned with a fine emery cloth to remove mineral deposits. If water quality is poor, thermostats may require more frequent cleaning. The best time to clean the thermostats is after a hatch when the thermostat board is removed for cleaning. Control Box The best time to check the control box is after washing, but before transfer. (The hatcher is empty.) Note: If the bell does not ring to indicate high temperature, motor off and/or power off, check the battery, the battery connections or the alarm circuit. Replace pilot lights as required. Be careful during this examination of the control box since the power has not have been disconnected. Warning: If rewiring or relay replacement is required, turn off the power. Failure to do so could result in injury. Control Box Turn the fans off. Turn the power off. Open the control box, and examine the PT100 boards and wiring, wiring connections and relay contacts for obvious faults such as discoloured wiring, and burned or blackened areas. Pay special attention to terminals, connections and relay points. Vacuum the interior if dust, chick down or metal shavings have accumulated. After vacuuming, ensure plug connections are snug. In older models, check that the boards are firmly seated. Turn the power back on. Turn the fans back on. washer on thermostats. Instead, use compressed air to remove fluff from all parts of the thermostat board. To sanitize, hold the thermostat board over a basin of water with disinfectant and apply the Warning: Turn off the power. Disconnect the fans and heater. Hold the top of the wicking with one hand. Gently slide over the extended end of the thermostat. Seat the wicking firmly around the bulb. Place the free end of the wicking into the reservoir, Make sure it does not twist or bend. Any twists or bends will interrupt the flow of water through the wicking. The wicking should be 12 in. (30 cm) in length. EVERY THREE MONTHS

14 Vacuum the box if dust or down has accumulated. Wires, Connections and Bulbs The check can be made with or without the thermostat board installed. Unlatch the control box cover and swing it down gently. If the thermostats are installed, be careful that the latch does not damage the angle thermometers. Check the wiring, wiring connections and relay contacts for obvious faults, such as discoloured wiring, or burned or blackened areas. Pay special attention to relays points, connections and terminals. Check for burnt out bulbs. High Temperature Circuit Using the jumper wire, connect one clip to Terminal 38 on TB2. Attach the other clip to Terminal 5 on TB1. The high temperature pilot light should come on, the damper should start opening, the auxiliary damper should lift, and the alarm should ring. The heat pilot light should stay on. Blower Circuit Leave the clip connected to Terminal 38 on TB2 and attach the other clip to Terminal 7 on TB1. The blower light and motor (Big J) or motors (Super J) should come on. The heat pilot light should stay on. alarm should ring. If one door is opened, the alarm should stop ringing. When the door is closed, the alarm should ring. Open the other door. This should cause the alarm to stop ringing. The heat pilot light should stay on. Power Off Check Close the doors. Turn off the power to the hatcher. All of the pilot lights on the control box should go out, and the alarm should ring. ROUTINE MAINTENANCE FOR HATCHERS Refer to the checklist on page 131. AFTER EVERY HATCH Wash and Sanitize Thoroughly wash and sanitize hatcher racks, dollies and the interior of the hatcher. Refer to Chapter 5 - Spray Nozzle Condition Both water pressure and nozzle condition affect droplet size and number, which in turn, affects how efficiently moisture is absorbed into the air. Inevitably, some water droplets injected into the air stream are deposited on surfaces or objects in the flow path. When water is laden with minerals, the solids are left behind as the water evaporates. Nozzles block or partially block. The spray pattern is disrupted and excessive dripping occurs. Drip pans, rack tops, extrusions, panels and sensors quickly become encrusted with these deposits. Not only is this unsightly, but cleaning becomes difficult, protective coatings rapidly diminish and corrosion is accelerated. Routine maintenance becomes unpleasant and machine performance is reduced. Low water pressure, partially blocked nozzles, or poor spray pattern can result in uneven temperature distribution, measured at the exit end of the machine, e.g., top section temperature is highest while the bottom section is lowest. Therefore, maintain the spray nozzles to specifications for optimum performance. Refer to page 42 for water pressure and water quality specifications. Threshold Gasket After clean-up, reseal joints as required. Heat Circuit Connect the jumper wire to Terminal 38 on TB2 and Terminal 11 on TB1. The heat pilot light should go out, the damper should start opening, and the spray should come on. Dismantle the spray nozzle for cleaning. Cleaning Procedures on page 93 for this procedure. Avoid splashing water on motors and electrical connections. All motors and electrical connections must be dry before the hatcher is restarted and warmed. To Clean the Spray Nozzles Remove the exhaust duct at the back of the hatcher. Disconnect the Kwik connect coupler from the Humidity Circuit Using a second jumper wire, bridge Terminals 38 on TB2 and 12 on TB1. The spray should stop, and the pilot light should go out. TWICE-WEEKLY Spray Nozzles Use only one or two pumps when greasing the castor wheels. Motor Off Circuit Close the doors. Connect the alligator clips to Terminal 36 or 36A on TB2 and Terminal 2 on TB1. The motor off pilot light should come on, and the Clean the spray nozzles. After cleaning, check the water nozzle spray pattern. It should be a 60 degrees fan pattern and there should be no excessive dripping. If the nozzles are not producing the correct spray pattern, they may need to be replaced or the water pressure may be too low. Clean and sanitize the area around the damper slide.

15 spray nozzle assembly, loosen the wing nuts, and lift to remove. Unfasten the nozzles from the body and dismantle. Use an ultrasonic cleaner to clean the spray nozzle components. Alternatively, they can be soaked in pure white vinegar or other mild acid solvent. Thoroughly rinse with water. Do not use a wire to clean the orifice as it is likely to cause damage. This will result in an incorrect spray pattern. When reassembling the hatcher after clean-up, centre the spray nozzles on the fan shafts and fastened securely. To Check the Water Pressure Check the water pressure at the nozzles by inserting a gauge fitted for the Kwik connect into the coupling. The pressure should be at least 65 psi (4.5 bars). Warning: To avoid injury, turn off the fans and turn off power before unplugging or working with fans. Note: Before switching the fans on again, allow them to stop completely. If you do not, some of the fans may run backwards, upsetting the air flow. All fans should run in a counter-clockwise direction when viewed from behind the motor. If a fan does run backwards, simply switch it off, allowing it to stop before turning it on. Exhaust Duct Check for torn or missing gaskets before installing. Replace any gaskets if necessary. joints. If new sealant is required, warm the inside of the cabinet to remove moisture from the crevices. Using a dry clean cloth or paper towel, remove any residue with alcohol. Re-caulk with silicone sealant. Hatcher Racks Grease all castor wheels and plate bearings after sanitizing the hatcher racks. One or two pumps of a grease gun should suffice. Any more will result in forcing grease out through the rubber seals. For 2-Door Hatchers Blower Unplug, unlatch and remove the blower box. Clean and sanitize the area around the damper slide. Using an air hose clean the fins of the blower fan. Replace the box and plug in the blower(s). MONTHLY Fans Check for excessive fan vibration. If you are unable to read the nameplate on the motor clearly or the motor frame assembly is rattling, the fan is vibrating too much. Before determining the cause of the excessive vibration, turn off the fans, turn off the power to the hatcher and unplug the motor. Inspect the fan stand or motor mounts for loose bolts and connections, the motor shaft for worn bearings, and the fan blade for correct pitch or distortion. See page 140 for fan specifications. If vibration continues, replace the motor or fan blade. Heat Rings Note: If fan motors are repaired or rewound, it is recommended that revolutions per minute (rpm) be checked when the motors are reinstalled. Use motors of similar rpm (± 2.5%) in each hatcher. Do not mix low rpm motor with high rpm motors and vice versa. Use an ampere clamp (or amp probe) to check the amperage of each heater. The reading should be between 6 and 8 amperes. If not, replace the heater element. Check the heater for correct operation. The best time to do this is immediately after transfer, when the hatcher is calling for heat. Use an ampere clamp to check the amperage of the heater. Note: If the fan blade does not appear to be static, i.e., the mark appears, disappears, reappears, the strobe light flash rate may be set x2, x3, x4. (multiple of desired rpm) too high or too low. Adjust flash rate to rpm value on the nameplate. olds are considered normal. If other light is visible, such as along the top or bottom corners of the doors, adjust the door latches. For PX Hatchers Air Cylinder Control Assembly After clean-up, check all air cylinders and air cylinder control assembly fittings and fasteners. Adjust and tighten any that are loose. If air pressure is high, above 25 psi (1.7 bars), the extreme, rapid, back and forth movement of the piston in each cylinder can cause buddy nuts, jam nuts and socket set screws to loosen. The air pressure should be lowered to the recommended 20 psi (1.4 bars) by adjusting the regulator on the filter assembly. See the PX Hatcher installation and parts manual. EVERY THREE MONTHS Fan Motors and Blades Door Seals Check for torn or missing door gaskets. Replace any gaskets if necessary. Damaged gaskets will result in poor air flow. Threshold Gaskets Check the threshold gaskets for tears. Torn or missing threshold seals will result in poor hatching conditions in the lower trays. Therefore, keep all threshold seals in good order. Switch off the power, lift the cover off the control box, clamp around one of the heat ring wires (either number 10 or 50), and switch the power back on. The reading should be between 6 and 8 amperes. If it is not, replace the heat ring. Remember that with electro-mechanical controls only, if the damper slide is open more than 1/8 in. (3.175 mm), the heat ring will not draw any current. With PT100 controls, the heat rings will operate regardless of damper opening. WEEKLY All Joints After clean-up, check the silicone sealant used on all Use an ampere clamp to check the amperage of the heater. Cabinet Finally, inspect the cabinet for signs of penetrating light. Stand inside the cabinet with the threshold installed and the doors closed. Small areas of light around door switch arms and at the ends of thresh-

16 Clean fan motor during complete clean-out and sanitation. See pages 94 to 96. Turn off the fan motors, Clean the blades and motors with a damp sanitized cloth or brush. Be careful not to bend the blades when cleaning. Do not use a high pressure washer on the motors. Check the fan spacing upon completion. Turn the hatcher back on. Fan Blade Spacing and Motor RPM Upon completion, check the fan spacing. See page 140 for fan spacing for current motor mounts. Procedure for Checking RPM Jamesway suggests the use of a strobe light to check rpm, as no physical contact with the motor is required and all motors can be checked at one time. With practice the strobe light can also be used to identify fan blade defects. Check the rpm when the motor is under load, i.e., when hatcher is in normal operation and filled with eggs. Plug strobe light into power source. Stand in the entrance end of the hatcher. Switch on strobe light and switch off hatcher lights. Adjust the strobe flash rate to a value similar to rpm marked on motor nameplate, e.g., Motor PB5146: 1625 rpm at 60 Hz, 1325 rpm at 50 Hz. Fine-tune until fan blades appear to stop. Focus on a blade that is easily identifiable (small scratch or mark) and ensure that its location does not change. If the blade in the chosen position appears to be static, record the strobe flash rate. The recorded value is the revolutions per minute of the motor or motors. The frequency of cleaning the water line strainer will depend upon the mineral content of the water. Maintenance Schedule for PT100 Hatcher Controls All of the items mentioned below should be checked, as scheduled. Refer to page 119 and your control manual for additional notes. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. A) Sensor 1. Reservoir - clean and fill as required 2. Wick - replace 3. Probes - clean B) Calibration (See PT100SMT Controls Manual, page 86.) C) Display Panel - check the following LEDs 1. High Humidity 2. Low Humidity 3. High Temperature 4. Low Temperature D) Alarms 1. Power Off Alarm 2. Fan Motor Off and Door Open Alarms E) PX Hatcher 1. Air Cylinder condition F) 2-Door Hatchers 1. Blowers condition 2. Auxiliary Damper condition G) Control Box 1. Clean, vacuum as required 2. Wire condition 3. Terminal condition 4. Relay condition 5. Boards - position firmly (older models) Twice Weekly Every 3 Warning: The PT100 controller should only be serviced by qualified maintenance personnel. Do not attempt to service the controller while it is turned on. Some circuits are energized with 220 or 380 volts ac. They will cause serious shocks, injury or death if touched. Before servicing the control box, ensure that CB1, CB2 and CB3 are turned off. Turn the fans off. Voltage Checkpoints. If required, refer to page 88 in The PT100SMT Controls and System Manual.

17 Maintenance Schedule for Electro-Mechanical Hatcher Controls Maintenance Schedule for Hatchers All of the items mentioned below should be checked, as scheduled. Refer to pages 122 and your control manual for additional notes. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. All of the items mentioned below should be checked, as scheduled. Refer to pages 124 to 128. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. A) Thermostat Board 1. Wash and sanitize 2. Grommet condition 3. Gasket condition 4. Operating properly 5. Reservoir - clean and fill as required 6. Wick - replace 7. Thermostats - clean B) Control Box and Information Panel 1. Wire condition 2. Relays and connections condition 3. Bulb condition C) Check the following circuits 1. High Temperature 2. Blower 3. Heat 4. Humidity 5. Motor Off 6. Power Off After Every Hatch Twice Weekly Every 3 Months A) Hatcher Racks and Dollies 1. Wash and sanitize 2. General condition 3. Castors and bearing plate - grease (racks only) B) General Machine 1. Wash and sanitize (See Chapter 5.) 2. Check joints, caulk as required 3. Check for light penetration C) Spray Nozzles 1. Clean, replace if required 2. Check spray pattern 3. Check position 4. Check pressure - 65 psi (4.5 bars) D) Exhaust Duct 1. Gasket condition E) Doors 1. Doors seal properly 2. Doors latch properly 3. Door gasket condition 4. Threshold gasket condition After Every Hatch Twice Weekly Weekly Monthly Every 3 Months Warning: 1. The thermostat contacts are electrically live. Therefore, before cleaning the thermostats, open the control panel and disconnect the power to the thermostats. Failure to do so could result in injury. 2. Before working on the Control Box and Information Panel, disconnect the fans and heater. 3. In order to check circuitry, switch the power on. Jamesway recommends that you use an insulated jumper wire with insulated alligator clips or probes to perform the following checks. Switch the power off after each test procedure. F) Damper 1. Opening and closing properly 2. Slides move freely 3. Damper openings equal (PX Hatcher only) 4. Closed position correct 5. Damper motor (5.5 to 6 rpm) G) PX Hatcher 1. Air cylinder For circuit checks, refer to page 123.

18 Maintenance Schedule for Hatchers (continued) H) 2-Door Hatcher 1. Blower clean and sanitize 2. Blower thorough cleaning and sanitizing 3. Check auxiliary damper I) Heat Rings 1. Check amperage (6 to 8 amp) J) Fans 1. Fan condition (vibration?) 2. Switches, blades and motors - clean 3. Blade spacing - check 4. Motor rpm - check K) Water Strainer 1. Clean After Every Hatch Twice Weekly Weekly Monthly Every 3 Months The reading taken with strobe light should be within ± 2.5% of rpm specified on motor nameplate. Damper System The arrow on the knob of the drive box will indicate whether the damper is closing when the machine calls for heat. The damper should be opening when the heat pilot light is off. After clean-up and before egg transfer, while the hatcher is warming, check for the following potential problems: If the knob on the drive box is turning but the damper is not moving, replace the plastic drive block on the threaded rod in the damper drive. The drive motor always should turn at 5-1/2 to 6 revolutions per minute. The intake damper slide should move freely, without binding. Also, the opening should be set at 1/8 in. (3.2 mm) in the fully closed position. the gasket, if necessary. Blower Remove the blower box and thoroughly clean the inside of the blower. Remove dirt from hard to reach areas using compressed air. Clean dirt from the blower blades using a paint brush dipped in disinfectant. After thoroughly cleaning the blower and box, check the gasket around the base. Replace it if necessary. Reinstall the blower box, oil the bearings, plug in and check. Water Line Strainer Clean the water line strainer, which is generally located within the incoming water line and before the first hatcher. Turn off the water, loosen the retaining nut, and remove the strainer screen. Flush and rinse the screen to remove debris. Replace the screen, insert and tighten the retaining nut, and turn the water back on. The frequency of cleaning will depend upon the mineral content of the water. If the damper is not moving but open more than 1/8 in. (3.2 mm), the sigma relay (EM Controls only) or damper motor should be replaced. ROUTINE MAINTENANCE FOR VENTILATION EQUIPMENT For 2-Door Hatchers Check for the following potential problem: If the damper is opening when the heat light is on, the wiring may be reversed (EM Controls only). Auxiliary Damper Lift the auxiliary damper, check the gasket around the opening, then release. The lid should be under pressure from the spring in the motor and compress the gasket slightly. If not, remove the damper lid from the crank arm. Adjust the arm so it is more or less parallel with the angle of the motor mount bracket. Reattach the lid and test again. Scratch marks on the roof of the blower box also could mean incorrect assembly. See the installation and parts manual for more details. Replace A routine maintenance program is an integral part in keeping incubator and hatcher circulation problems to a minimum. A suggested maintenance schedule for ventilation equipment includes: AS REQUIRED Humidifiers Service the humidifiers according to geographical and climatic conditions. Furnaces Clean or replace filters. Cooling Units Clean or replace the filters.

19 Maintenance Schedule for Ventilation All of the items mentioned below should be checked, as scheduled. Refer to the preceding page. All other items should be assessed as to their operating condition either satisfactory or unsatisfactory. Unsatisfactory would include not operating properly, excessive wear, dirt or any potential problem. Items, not in satisfactory condition, should be repaired or replaced, and/or cleaned prior to further use. A) Humidifiers 1. Service for climatic conditions B) Furnaces 1. Clean filters, replace as required 2. Check belt tension and condition 3. Grease and inspect bearings 4. Check damper actuation 5. Inspect vents 6. Clean and lubricate motor 7. Tighten mounting hardware 8. Inspect and tighten electrical connections 9. Clean blower C) Cooling Units 1. Clean filters, replace as required 2. Check belt condition and tension 3. Grease and inspect bearings 3. Check damper actuation 4. Inspect vents, if combination heating/cooling unit D) Evaporative Coolers (during cooling season) 1. Float and water level 2. Water distribution 3. Belt tension and condition 4. Pulley alignment 5. Pad condition and placement 6. Grease and inspect bearings 7. Inspect cowlings 8. Tighten mounting hardware 9. Inspect and tighten electrical connections 10. Clean blowers As Required Weekly Monthly Every 6 Months Maintenance Schedule for Ventilation (continued) E) Exhaust Fans 1. Belt tension and condition 2. Grease and inspect bearings 3. Inspect pulley alignment 4. Clean blades 5. Check damper actuation 6. Inspect and tighten electrical connections 7. Tighten mounting hardware As Required Weekly Monthly Every 6 Months

20 SPECIFICATIONS FOR VENTILATION COMPONENTS INCUBATOR DAMPER POSITIONS HATCHER DAMPER POSITIONS PX Hatcher Note: When the damper is in fully closed position, there is a spatial opening of 1/8 inch (3 mm). Note: When the damper is in fully closed position, there is a spatial opening of 1/2 inch (13 mm). Fully closed damper position for PT100 controls Fully closed damper position for PT100 controls 2-Door Hatcher Note: When the damper is in fully closed position, there is a spatial opening of 1/8 inch (3 mm). Fully closed damper position for EM controls POSITIONING OF SPRAY NOZZLES Note: To prevent dripping, keep the nozzle tip slightly higher than the elbow centre. Fully closed damper position Correct measurements for locating angle of spray nozzle assembly SPACE SAVER INTAKE DUCT For correct spacing of the Space Saver intake duct, refer to page 101.

21 GENERAL CONSIDERATIONS FOR FAN BLADE SPACING FAN BLADE SPACING FOR 50 HZ AREA - OLDER MOTOR MOUNT 1. When adjusting the fan blade spacing, use the specifications for you particular blade and motor mount. These specifications can be found on the following pages. 2. Irrespective of the blade or the motor mount, all fans should be almost centred in the venturi, i.e., half of the fan blade depth should be located slightly under half of the venturi depth. See illustration. 3. All motor mounts in a machine should be the same. Do not mix and match motor mounts. Note: When the blades are correctly spaced, the solid red line and the dotted red line should meet on the same vertical plane. Correct spacing between fan blades and older motor mount Blade rotation for 50 Hz fans

22 FAN BLADE SPACING FOR 60 HZ AREA - OLDER MOTOR MOUNT FAN BLADE SPACING FOR 50 HZ AREA - NEW MOTOR MOUNT Correct spacing between fan blades and new motor mount FAN BLADE SPACING FOR 60 HZ AREA - NEW MOTOR MOUNT Correct spacing between fan blades and older motor mount Blade rotation for 60 Hz fans Correct spacing between fan blades and new motor mount

23 FAN BLADE SPACING FOR HATCHERS PX Hatcher Correct spacing between fan and motor mount 2-Door Hatcher Correct spacing between fan and motor mount

HATCHERY. ROSS TECH Hatchery Maintenance. August 2011

HATCHERY. ROSS TECH Hatchery Maintenance. August 2011 HATCHERY ROSS TECH Hatchery Maintenance August 2011 Hatchery Maintenance: Introduction Introduction A good hatchery maintenance program is an essential part of maximizing hatchery performance. Maintenance

More information

BLAST-IT-ALL BUMPER BLASTER

BLAST-IT-ALL BUMPER BLASTER LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL BUMPER BLASTER SUCTION BLAST CABINET NOTE: It is the responsibility

More information

ICED CAPPUCCINO MACHINE Taylor MODEL: 390

ICED CAPPUCCINO MACHINE Taylor MODEL: 390 4.8.6.3 ICED CAPPUCCINO MACHINE Taylor MODEL: 390 LOCATION: Front of House WHEN CLEANED: Daily, Weekly, Monthly, Seasonal TOOLS/SUPPLIES REQUIRED: Salmon Cloth 2 or 3-Compartment Sink Sink Detergent Sanitizer

More information

READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS. Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14

READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS. Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14 READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS Type Installed: Maintenance page: Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14 Includes Safety, Operating

More information

CC-2222C-PL, CC-2222C-PRL, CC-2222C-PR-2, CC-2222C-PL-2,

CC-2222C-PL, CC-2222C-PRL, CC-2222C-PR-2, CC-2222C-PL-2, Rev. 14 (10/08) Page 1 of 16 INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor Models: CC-2222C-PR, CC-2222C-PL, CC-2222C-PRL, CC-2222C-PR-2, CC-2222C-PL-2, and CC-2222C-PRL-2 Rev. 14 (10/08)

More information

TECHNICAL INFORMATION T1500 Series Clothes Dryers

TECHNICAL INFORMATION T1500 Series Clothes Dryers TECHNICAL INFORMATION T1500 Series Clothes Dryers 2003 Miele - Table of Contents 1.0 CONSTRUCTION & DESIGN 1.1 Appliance Overview - Vented 1 1.2 Appliance Overview Condenser Models 2 1.3 Controls Overview

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

BLAST-IT-ALL PRESSURE BLAST CABINET

BLAST-IT-ALL PRESSURE BLAST CABINET LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL PRESSURE BLAST CABINET NOTE: It is the responsibility of

More information

MANUAL COVER. To expedite parts ordering or technical questions, please include your Model and Serial Number listed below in all correspondence.

MANUAL COVER. To expedite parts ordering or technical questions, please include your Model and Serial Number listed below in all correspondence. MANUAL COVER We at Larry Hess & Associates, Inc. would like to take this opportunity to thank you for your patronage. The machine you have purchased has been manufactured and assembled in the USA with

More information

Before using your machine, you must familiarize yourself with all of its components.

Before using your machine, you must familiarize yourself with all of its components. USE AND MAINTENANCE MANUAL FOR THE FOAMTEC 1800 NOTE: As with all electrical equipment, care and attention must be exercised at all times during its use, in addition to ensure that routine and preventative

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual TORNADO INDUSTRIES 7401 W. LAWRENCE AVENUE CHICAGO, IL 60706 (708) 867-5100 FAX (708) 867-6968 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99690 BD 22/14, 99720 BD 26/14 L9722

More information

PRO 2000i LOW LEVEL DEPOSITOR

PRO 2000i LOW LEVEL DEPOSITOR DEPOSITORS AND AUTOMATED CAKE PRODUCTION SYSTEMS PRO 2000i LOW LEVEL DEPOSITOR OPERATION AND SPARE PARTS MANUAL Serial No. PR2L- (Please quote this number when ordering spares, and making service calls)

More information

Owner s Manual CMC100 Dehumidifier

Owner s Manual CMC100 Dehumidifier Owner s Manual CMC100 Dehumidifier DRI-EAZ PRODUCTS, INC. 15180 Josh Wilson Road, Burlington, WA 98233 Phone: 800-932-3030 Fax: (360) 757-7950 http://cmc-100.dri-eaz.com The CMC100 automatically controls

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents IAQ HUMIDIFIERS Litho U.S.A. 2007 Dallas, Texas, USA 505,289M 08/2007 Supersedes 02/2007 KAZ # C.6046 HCWB2 & HCWP2 SERIES USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS Table Of Contents Introduction....................................

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Owner s Manual CMC100 Dehumidifier

Owner s Manual CMC100 Dehumidifier Owner s Manual CMC100 Dehumidifier DRI-EAZ PRODUCTS, INC. 15180 Josh Wilson Road, Burlington, WA 98233 Phone: 800-932-3030 Fax: (360) 757-7950 http://cmc-100.dri-eaz.com The CMC100 automatically controls

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,1,_2008 Lennox Industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS CR33 Series Coils EVAPORATOR COILS _ Technical 505,056M LL.L[ Publications 04108 Litho U.S.A. Supersedes 05/05 CR33 Series Coils...

More information

AHPO-6/18 GOLD PROOFER OVEN

AHPO-6/18 GOLD PROOFER OVEN AHPO-6/18 GOLD PROOFER OVEN For information or technical assistance, call: TOLL FREE 1(800) 735-DUKE (3853) or 1(314) 231-1130 PN 156081R 1 of 25 TABLE OF CONTENTS MANUFACTURER S INTRODUCTION...3 INSTALLATION...4

More information

Control Panel For Water Wash Hoods AM2

Control Panel For Water Wash Hoods AM2 Control Panel For Water Wash Hoods AM2 For further information Call: (919) 554-1025 Or Fax: (919)554-1525 Aqua-Matic 117 Franklin Park Ave. Youngsville, NC 27506 TABLE OF CONTENTS AQUA-MATIC LIMITED WARRANTY

More information

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER Room Air Conditioner Installation and Operation Manual UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER (VOLTS) MIN. MAX. MIN. F ( C) MAX. F ( C) WAC060K7A 127-1-60 114.3 139.7 70(20.1)

More information

Heat Exchanger Block Replacement Instructions

Heat Exchanger Block Replacement Instructions Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement

More information

NO LONGER IN PRODUCTION

NO LONGER IN PRODUCTION M7-00 thru -00 Service and Parts Manual Self-Contained Steam Sterilizer Serial Number Prefixes: RB, CR, CP, CS, FM, FN -00 M7 thru -00 NO LONGER IN PRODUCTION Some service parts may not be available for

More information

HEALTHY CLIMATE HUMIDIFIER

HEALTHY CLIMATE HUMIDIFIER Humidifiers 0,880M /00 HEALTHY CLIMATE HUMIDIFIER OPERATING INSTRUCTIONS FOR MODELS WB-, WB-7, WB-7A, WP-8 & WP-8A Includes Safety, Operating, and Maintenance Instructions Introduction Thank you for your

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

π H-2268 SANITAIRE UPRIGHT VACUUM SAFETY uline.com

π H-2268 SANITAIRE UPRIGHT VACUUM SAFETY uline.com π H-2268 SANITAIRE UPRIGHT VACUUM 1-800-295-5510 uline.com SAFETY PAGE 1 OF 7 NOTE: When using an electrical appliance, basic precautions should always be followed, including the following: READ ALL INSTRUCTIONS

More information

AIR CONDITIONER ELECTRONIC CONTROL

AIR CONDITIONER ELECTRONIC CONTROL READ AND SAVE THESE INSTRUCTIONS AIR CONDITIONER ELECTRONIC CONTROL ROOM AIR CONDITIONER WARRANTY Your product is protected by this warranty Your appliance is warranted by Electrolux. Electrolux has authorized

More information

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE - SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN VC3ED ML-137013 - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly

More information

MODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H)

MODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H) Order Number: PMMA091040CE Vacuum Cleaner MC-UL592/MC-UL594 SPECIFICATION MODEL MC-UL592 MC-UL594 POWER SOURCE 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H) 1200-1300

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

Power Washer Maintenance

Power Washer Maintenance Power Washer Maintenance Purpose The maintenance of your MART Power Washer. In general, the washer is not maintenance-intensive. A few key items, however, need regular, scheduled care: Use the information

More information

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents IAQ HUMIDIFIERS Litho U.S.A. 2007 Dallas, Texas, USA 505,289M 09/2008 Supersedes 08/2007 KAZ # C.6046 HCWB2 & HCWP2 SERIES USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS Table Of Contents Introduction....................................

More information

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5 Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to

More information

Maintenance 5-1. Good maintenance is essential for cleaning results, and long economical life of the washer.

Maintenance 5-1. Good maintenance is essential for cleaning results, and long economical life of the washer. Maintenance 5-1 5 Maintenance Purpose This chapter discusses the maintenance of your StingRay Parts Washer. In general, the washer is not maintenance-intensive. A few key items, however, need regular,

More information

GRIND PRO DUAL OR DISC SANDER. Operator Manual

GRIND PRO DUAL OR DISC SANDER. Operator Manual GRIND PRO DUAL OR DISC SANDER Operator Manual 2 GRIND PRO DUAL OR DISC ORTHO-SANDER INTRODUCTION The Grind Pro Dual or Disc Sander is a compact, durable machine designed for fast, complete finishing work.

More information

* * English. Operator Manual. Carpet Cleaner Rev. 01 ( ) Model V

* * English. Operator Manual. Carpet Cleaner Rev. 01 ( ) Model V R3 Carpet Cleaner English Operator Manual Model 9004199-230V R For the latest Parts manuals and other language Operator manuals, visit: www.tennantco.com/manuals 9003707 Rev. 01 (07-2016) *9003707* OPERATION

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

TECHNICAL INFORMATION T 15xx Dryers

TECHNICAL INFORMATION T 15xx Dryers TECHNICAL INFORMATION T 15xx Dryers 2010 Miele USA Table of Contents 1.0 2.0 3.0 T 15xx Dryers Construction and Design... 5 1.1 Appliance Overview Vented Models... 5 1.2 Appliance Overview Condenser Models...

More information

BYPASS AND POWER HUMIDIFIER OWNER S MANUAL

BYPASS AND POWER HUMIDIFIER OWNER S MANUAL ResearchPr 57 Bypass v2 4/15/03 10:22 AM Page 1 READ AND SAVE THESE INSTRUCTIONS BYPASS AND POWER HUMIDIFIER OWNER S MANUAL Includes Safety, Operating, and Maintenance Instructions and Warranty ResearchPr

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

ASTRO ENVELOPE FEEDER AMC FOR HEIDELBERG PRINTMASTER INSTALLATION AND OPERATING INSTRUCTIONS

ASTRO ENVELOPE FEEDER AMC FOR HEIDELBERG PRINTMASTER INSTALLATION AND OPERATING INSTRUCTIONS ASTRO ENVELOPE FEEDER AMC-2000-17 FOR HEIDELBERG PRINTMASTER INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION Thank you for purchasing the Astro Envelope Feeder. It is fast, efficient, reliable, and

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

690 and Power Fishing Systems

690 and Power Fishing Systems INSTRUCTION MANUAL 690 and 690-22 Power Fishing Systems Includes Serial Number AAR 3800 and higher (120 volt model) Includes Serial Number AAT 00500 and higher (220 volt model) Read and understand all

More information

PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650

PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650 USER GUIDE PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650 AB0039 FOR RESIDENTIAL USE ONLY!! MODELS SFDB-DQ, SFDB-DR AND SFDB-DS 30042509E IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

More information

Installation & Operating Guide

Installation & Operating Guide 5-036 HOT WATER TANK Installation & Operating Guide Read all instructions thoroughly. Keep this guide for future reference. Proof of purchase is required for Warranty. Staple receipt or proof of purchase

More information

Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ

Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ CS6-50-VD Operation & Maintenance Manual Table of Contents: 1.0 Introduction 1 2.0 Unpacking your COOL- SPACE 1 3.0 Set-up of COOL-SPACE

More information

SuperKlean Washdown Products

SuperKlean Washdown Products February 2012 DURAMIX 8000 INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** WARNING HIGH PRESSURE AND HOT

More information

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6 INTRODUCTION This service manual covers the installation, operation, maintenance and service of this ice machine. Table of Contents SPECIFICATIONS Page 2 FOR THE INSTALLER Page 3 FOR THE PLUMBER Page 4

More information

ROTARY CONTROL AIR CONDITIONER

ROTARY CONTROL AIR CONDITIONER USE & CARE MANUAL NOTE: This USE & CARE MANUAL provides specific operating instructions for your model. Use the room air conditioner only as instructed in this USE & CARE MANUAL. These instructions are

More information

T1 SCRUBBER DRYER OPERATOR MANUAL

T1 SCRUBBER DRYER OPERATOR MANUAL T1 SCRUBBER DRYER OPERATOR MANUAL Clemas & Co. Unit 5 Ashchurch Business Centre, Alexandra Way, Tewkesbury, Gloucestershire, GL20 8NB. Tel: 01684 850777 Fax: 01684 850707 Email: info@clemas.co.uk Web:

More information

Operation and Maintenance Manual 120V/60HZ

Operation and Maintenance Manual 120V/60HZ Operation and Maintenance Manual 120V/60HZ GLACIER CS5-16-VD CS5-16-VD-TB CS5-18-VD CS5-18-VD-TB AVALANCHE CS6-36-1D CS6-36-VD BLIZZARD CS6-50-VD Operation & Maintenance Manual 60HZ Models Table of Contents:

More information

OPERATING and MAINTENANCE INSTRUCTIONS Models: H138NPSCLCMCQRL Merchandising Hot Cabinets

OPERATING and MAINTENANCE INSTRUCTIONS Models: H138NPSCLCMCQRL Merchandising Hot Cabinets Rev. (/) Page of 0 OPERATING and MAINTENANCE INSTRUCTIONS Models: H8NPSCLCMCQRL Merchandising Hot Cabinets Cabinet model number: Cabinet serial number: Authorized Service Agency: Ph: Fax: Keep this manual

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE

More information

TK-1001, 1101, 1201, 1301, 1601

TK-1001, 1101, 1201, 1301, 1601 TK-1001, 1101, 1201, 1301, 1601 Pneumatic Room Thermostats General Instructions DEVICE INFORMATION Identification Thermostats of this family may be easily identified by referring to the part number located

More information

IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS Suncourt recommends professional installation of the Airiva (or by an accomplished DIY person) Please read and save these entire instructions before starting

More information

OPERATING & SERVICE PARTS MANUAL HDS-215 COMBINATION SHRINK SYSTEM

OPERATING & SERVICE PARTS MANUAL HDS-215 COMBINATION SHRINK SYSTEM OPERATING & SERVICE PARTS MANUAL HDS-215 COMBINATION SHRINK SYSTEM FOR HOT KNIFE AND IMPULSE MACHINES READ ALL INSTRUCTIONS CAREFULLY BEFORE OPERATING EQUIPMENT TABLE OF CONTENTS Electrical Requirements

More information

Glass and Dishwashers 402/452/502. (original instructions) (incl. Australian /502) Starting from Serial No.:

Glass and Dishwashers 402/452/502. (original instructions) (incl. Australian /502) Starting from Serial No.: Glass and Dishwashers ECOMAX 402/452/502 (incl. Australian 452-90/502) INSTALLATION AND OPERATION INSTRUCTIONS (original instructions) Starting from Serial No.: 8663 4000 REV. 05.10.2015 EN IMPORTANT NOTES

More information

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Ovens Service Manual Models OMFP6010 CONTENTS This document has been published to be used for service only. The contents

More information

Installation Manual UNIVERSAL C-750 PRE-MIX DISPENSER

Installation Manual UNIVERSAL C-750 PRE-MIX DISPENSER IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (612) 422-3246 Installation Manual UNIVERSAL C-750 PRE-MIX DISPENSER Part No. 185211000 January 25, 1984 Revised:

More information

PRESSURE WASHER MODEL NO: JETSTAR 1750 OPERATION & MAINTENANCE INSTRUCTIONS. WARNING Read the instructions before using the machine PART NO:

PRESSURE WASHER MODEL NO: JETSTAR 1750 OPERATION & MAINTENANCE INSTRUCTIONS. WARNING Read the instructions before using the machine PART NO: WARNING Read the instructions before using the machine PRESSURE WASHER MODEL NO: JETSTAR 1750 PART NO: 7333230 OPERATION & MAINTENANCE INSTRUCTIONS LS0711 INTRODUCTION Thank you for purchasing this CLARKE

More information

CBT LW MAINTENANCE GUIDE

CBT LW MAINTENANCE GUIDE CBT LW MAINTENANCE GUIDE PICTOGRAMS Each Signifier displayed here is specific to this User Manual. Menu Previous Advance Note Tip Example Powder Feeder Mixing Bowl Weigh Scale CBP Tanks Control Panel PSD

More information

Installation Manual PS-225 & PS-275

Installation Manual PS-225 & PS-275 Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

MERCHANT POPCORN MACHINE SERVICE MANUAL

MERCHANT POPCORN MACHINE SERVICE MANUAL 3243 North California Avenue, Chicago, IL 60618 MERCHANT POPCORN MACHINE SERVICE MANUAL 120 Volt, Single Phase, 60 Hz 230 Volt, Single Phase, 50 Hz READ and UNDERSTAND this servicing, and safety instructions

More information

Daily maintenance and checks

Daily maintenance and checks 5 Daily maintenance and checks This chapter explains about daily maintenance and checks. The information herein is very important towards keeping the equipment regularly in proper working order. 5-1 5.1

More information

Glass and Dishwashers. BarAid 500/800. Installation and. Starting from Serial No.:

Glass and Dishwashers. BarAid 500/800. Installation and. Starting from Serial No.: Glass and Dishwashers BarAid 500/800 Installation and operation Instructions Starting from Serial No.: 8652 0001 REV. 19.01.2009 1617-A-01-09 Content Page 1 Important Notes... 4 2 Installation... 5 2.1

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

Operating Instructions

Operating Instructions Operating Instructions BA-003 Read and understand this manual before use. Keep this manual for future reference. CONFORMS TO UL STD.No.1017 Certified to CSA STD C22.2 No.243-10 For questions or concerns

More information

SLIDER CASEMENT AIR CONDITIONER

SLIDER CASEMENT AIR CONDITIONER OWNER S GUIDE READ AND SAVE THESE INSTRUCTIONS SLIDER CASEMENT AIR CONDITIONER ROTARY CONTROL P/N 309000854 (11/03) ROOM AIR CONDITIONER WARRANTY Your product is protected by this warranty Your appliance

More information

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER G-Series Cooler GCG-10 UPRIGHT COOLER Manual is for the following models: GCG-10-N33EB G-10-N33EB Instruction Manual Manual is for the following models: GCG-10-N33EB G-10-N33EB Instruction Manual GCG-10

More information

Installation Manual PS-200 & PS-201

Installation Manual PS-200 & PS-201 Installation Manual PS-200 & PS-201 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the Bill of Lading to ensure all crates

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor AQUATEMP TM HUMIDITY CONVECTION and RETHERM OVENS with MICROPROCESSOR CONTROLS

INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor AQUATEMP TM HUMIDITY CONVECTION and RETHERM OVENS with MICROPROCESSOR CONTROLS 9 Heisley Road Mentor, OH 0- Rev. (6/0) Page of INSTALLATION, OPERATION and MAINTENANCE MANUAL for Cres Cor AQUATEMP TM HUMIDITY CONVECTION and RETHERM OVENS with MICROPROCESSOR CONTROLS ROFWB-Q COFWUAB-Q

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

1 ESMA, Inc. P. O. BOX 734 * SOUTH HOLLAND, IL * (800) * FAX (708)

1 ESMA, Inc. P. O. BOX 734 * SOUTH HOLLAND, IL * (800) * FAX (708) 1 2 Instructions for Ultrasonic Washer E789 (U.L. Approved) 1. INTRODUCTION The E789 Automatic Ultrasonic Washer automatically performs a cleaning cycle, the major steps of which are: Ultrasonic cleaning

More information

Automatic Temperature Control (ATC) is a system that operates the broiler at two different energy rates. 1. High energy input - for initial warm-up and periods of high volume. 2. Low energy input - for

More information

TCUT10UL 2.5 HP 10 Tile Saw Assembly & Operating Instructions

TCUT10UL 2.5 HP 10 Tile Saw Assembly & Operating Instructions TCUT10UL 2.5 HP 10 Tile Saw Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information on proper operation and maintenance.

More information

Water Distiller Service Manual

Water Distiller Service Manual Water Distiller Service Manual Water Distiller Service Manual L70478WT 2008 Regal Ware, Inc. Table of Contents RECOMMENDED TOOLS... 2 GENERAL INSPECTION...3 BOILING CHAMBER TROUBLESHOOTING & REPAIRS Description...

More information

Pocket Hardmount. Preventative Maintenance.

Pocket Hardmount. Preventative Maintenance. Pocket Hardmount Preventative Maintenance www.comlaundry.com Part No. 7-04-49 November 2005 Table of Contents Daily...2 Beginning of the Day...2 End of the Day...4 Weekly...6 Monthly...7 Quarterly...11

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL T Edition 0 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 88 STRATFORD, CT 0665

More information

Installation and Operation Manual For Hunter Ceiling Fans

Installation and Operation Manual For Hunter Ceiling Fans Installation and Operation Manual For Hunter Ceiling Fans 1 2 CONGRATULATIONS! Your new Hunter ceiling fan is an addition to your home or office that will provide comfort and performance for many years.

More information

BarAid 400. Installation and. Starting from Serial No.:

BarAid 400. Installation and. Starting from Serial No.: Glasswasher BarAid 400 Installation and operation Instructions Starting from Serial No.: 8649 1065 REV. 19.01.2009 DE 1618-A-01-09 Content Page 1 Important Notes... 4 2 Installation... 5 2.1 Location...

More information

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS FOR USE WITH ALL FORCED AIR SYSTEMS SEQUENCE OF OPERATION The AUTOFLO Model s 200P, 800BP and 97 Humidifiers use the evaporative by-pass principal to add moisture into the return air duct of your central

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual Tornado Industries, LLC 333 Charles Court West Chicago, IL 60185 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99414 Form No. L9740AB Tornado Industries, LLC. All rights reserved

More information

Operator s Manual. Wet/Dry Vacuum with Detachable Blower 12 Gallon Model No. VBV1210 FOR YOUR SAFETY

Operator s Manual. Wet/Dry Vacuum with Detachable Blower 12 Gallon Model No. VBV1210 FOR YOUR SAFETY Wet/Dry Vacuums Operator s Manual Wet/Dry Vacuum with Detachable Blower 12 Gallon Model No. VBV1210 FOR YOUR SAFETY Read and understand this manual before use Keep this manual for future reference www.vacmaster.com

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

SuperKlean Washdown Products

SuperKlean Washdown Products DURAREEL DR8 & DR8S INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** GENERAL WARNINGS High pressure and hot

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

E32 CONVECTION OVEN SERVICE MANUAL -1- Revision 1/F3508

E32 CONVECTION OVEN SERVICE MANUAL -1- Revision 1/F3508 E32 CONVECTION OVEN SERVICE MANUAL -1- WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY. -2- CONTENTS This manual is designed to take a more in depth look

More information

TECHNICAL INFORMATION Touchtronic Clothes Dryers

TECHNICAL INFORMATION Touchtronic Clothes Dryers TECHNICAL INFORMATION Touchtronic Clothes Dryers Includes: T1302, T1303, T1322, T1329ci T1403 & T1405 2004 Miele This page intentionally left blank. Table of Contents GENERAL INFORMATION A. Warning and

More information

READ AND SAVE THESE INSTRUCTIONS HUMIDIFIERS USER S INFORMATION GUIDE. For Models *HUMD200ABM00B *HUMD300ABA00B *HUMD500APA00B

READ AND SAVE THESE INSTRUCTIONS HUMIDIFIERS USER S INFORMATION GUIDE. For Models *HUMD200ABM00B *HUMD300ABA00B *HUMD500APA00B READ AND SAVE THESE INSTRUCTIONS HUMIDIFIERS USER S INFORMATION GUIDE For Models *HUMD200ABM00B *HUMD300ABA00B *HUMD500APA00B Includes Safety & Operating Instructions and Warranty Information * May be

More information

OPERATOR S MANUAL FOR YOUR SAFETY. 4 Gallon / Liter Part No. PB408SV

OPERATOR S MANUAL FOR YOUR SAFETY. 4 Gallon / Liter Part No. PB408SV 120 VOLT WET / DRY VAC 4 Gallon / 15.14 Liter Part No. PB408SV FOR YOUR SAFETY Read and understand this manual before use. Keep this manual for future reference. OPERATOR S MANUAL TABLE OF CONTENTS SECTION

More information

E32M CONVECTION OVEN SERVICE MANUAL. Revision 1/F

E32M CONVECTION OVEN SERVICE MANUAL. Revision 1/F E32M CONVECTION OVEN SERVICE MANUAL -- WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY. -2- CONTENTS This manual is designed to take a more in depth look

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Models KM-900MAH50 KM-900MRH50 A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 6-25-2008 IMPORTANT Only qualified service technicians

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

Multi-Cyclonic Vacuum USER GUIDE

Multi-Cyclonic Vacuum USER GUIDE Multi-Cyclonic Vacuum USER GUIDE MODEL CJTG00499B-120 Thank you for purchasing a BENNETT READ POWER UP PET vacuum. Your POWER UP PET vacuum incorporates the latest technological advances in home cleaning

More information

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging

More information

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / 27-009, 27-010, 27-015, 27-020 IMPORTANT INFORMATION UNATHORIZED CHANGES OR ALTERATIONS TO ANY LINCOLN PORTABLE VACUUM SYSTEM WILL AUTOMATICALLY

More information