TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Size: px
Start display at page:

Download "TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)"

Transcription

1 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a, DR-7, L-20, LTR4X, LTR6A, and D52Y) in a 5-RT Air-Cooled Water Chiller (Cooling Mode) Ken Schultz Steve Kujak Trane / Ingersoll Rand 3600 Pammel Creek Rd La Crosse, WI January 25, 2013 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

2 List of Tested Refrigerants Compositions (Mass%) ARM-32a R-32/R-125//R-134a/R-1234yf (25/30/25/20) DR-7 R-32/R-1234yf (36/64) L-20 R-32/R-152a/R-1234ze(E) (45/20/35) LTR4X R-32/R-125/R-134a/R-1234ze(E) (28/25/16/31) LTR6A R-32/R-744/R-1234ze(E) (30/7/63) D52Y R-32/R-125/R-1234yf (15/25/60)

3 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 2 of 13 INTRODUCTION This report documents tests run on a small air cooled water chiller / heat pump in Trane s La Crosse, Wisconsin, Laboratory. Tests were run only in cooling mode; the facility we ended up using did/could not control ambient humidity. The refrigerants tested are listed below: name order begin testing end testing number of runs DR Aug Aug ARM 32a 2 20 Aug Aug L Aug Aug LTR4X 4 04 Sep Sep LTR6A 5 11 Sep Sep R Sep Sep D52Y 7 28 Sep Oct This same equipment and facility were used for the tests reported earlier on R410A alternate refrigerants. 1 The only changes involved replacing the compressor and TXV with components sized for R22. TEST SETUP The equipment being tested is a Koolman air cooled water chiller / heat pump, model CGAR It has a nominal design cooling capacity of 4.4 RT (15.6 kw). The product is designed to provide chilled or hot water to apartments, offices, or small retail stores. In cooling mode, the evaporator is a brazed plate heat exchanger (BPHE); the condenser is a copper tube/aluminum fin coil (RTPF coil). The production design employs R22 or R407C as the refrigerant (depending on country of use). 2 Following completion of testing with alternate refrigerants proposed as replacements for R410A, the compressor and TXV were replaced with standard production R22 components and testing continued with alternate refrigerants projected to be closer to R22. The unit came to us containing a POE 160SZ oil. This oil will be used when testing all refrigerants. The mineral oil contained in the replacement R22 compressor was drained prior to installation and replaced with a POE 160SZ oil. See Figure 1 for photos of the Koolman unit set up in the laboratory. A schematic diagram of the system with locations of instrumentation is shown in Figure 2. Key measurements include chilled water flow rate along with inlet and outlet temperatures (RTD s) and pressures, mixed air temperature, and power input to the compressor and total power to the unit. Pressure sensors are mounted along the refrigerant circuit; thermocouples are surface mounted at corresponding locations. A list of instrumentation along with sensor accuracies is attached as Appendix A. METHOD OF TEST The method of test is consistent with Appendix C of AHRI Standard 550/ with operating conditions generally held within tighter tolerances. Performance is reported here as measured; no adjustments are made for fouling allowance or elevation. The cooling capacities reported are computed from the measured chilled 1 TEST REPORT #SD001, SYSTEM DROP IN TEST OF R410A ALTERNATIVE FLUIDS (ARM 32, ARM 70, DR 5, HPR1D, L 41a, L 41b, and R32) IN A 5 RT AIR COOLED WATER CHILLER (COOLING MODE), 20 Aug 2012, AHRI Low GWP Alternative Refrigerants Evaluation Program. 2 Catalogs were not readily available for making a direct comparison of performance with R407C and R22. TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

4 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 3 of 13 water flow rate and the difference between the entering and leaving chilled water enthalpies. The enthalpies are computed from the measured water temperatures and pressures. Therefore, the capacity reported here corresponds to the gross refrigerating capacity defined in AHRI Standard 550/ Thermodynamic properties of water are computed using Trane s internal code, which is consistent with the 550/590 equations to well within experimental accuracy. Tests in cooling mode consist of: 1. Refrigerant charge sweep at nominal operating (boundary) conditions of: leaving chilled water temperature = 45 ±0.1 chilled water flow rate = 14.0 gpm ±0.1 gpm ambient air temperature = 95 ±0.15 compressor suction superheat ~ (TXV adjusted as needed) The charge for further testing was selected at maximum EER (0.5 lbm resolution). 2. Variation in leaving chilled water temperature while holding air temperature fixed at 95: 41 TChWo Variation in ambient air temperature while holding leaving water temperature fixed at 45: 75 Tair 115 (unless limited by high pressure cutout switch set at 415 psia) This test matrix produces several measurements at the nominal operating condition to check repeatability. The Koolman product is designed for international markets and is rated at the following conditions in cooling mode: ambient air temperature = 35 C = 95 leaving chilled water temperature = 7 C = 44.6 entering chilled water temperature = 12 C = 53.6 chilled water temperature change = 5 C = 9 These conditions are slightly different than those listed in AHRI Standard 550/ To expedite execution of the test matrix, several simplifications to the operating conditions were made. First, the rating point leaving water temperature (7 C) was rounded up to an integer value (45). Second, the chilled water flow rate was set at a fixed value of 14 gpm which produced a 7.1 change in chilled water temperature for the baseline R22 runs (same flow rate as used for the R410A tests). Adjusting chilled water flow rate for a fixed temperature change is an iterative process and can become time consuming in the laboratory. Although a fixed flow rate, variable entering water temperature can affect the potential refrigerant superheat leaving the evaporator 3, a fixed water flow rate does maintain a nearly constant water side heat transfer coefficient in the heat exchanger. These simplifications were considered to be minor compromises to maintaining conditions per a formal rating standard and are expected to have negligible impact on the ultimate comparisons of the alternate refrigerants to the baseline. RESULTS Overall performance results (capacity and EER), along with the key state points obtained at the nominal operating condition using the charge that maximizes EER are attached as Appendix B for each refrigerant tested. This information is also compiled in a companion Excel file. A summary of the capacities, EER s, and refrigerant charges relative to performance with the baseline R22 are shown in Figure 3, Figure 4, and Figure 5, respectively. The refrigerants are listed in the order that they were run. Also shown are values for the capacity and EER (COP) predicted by a simple thermodynamic cycle model. The simple model ignores line pressure drops and so assumes the evaporator pressure equals the compressor 3 The refrigerant superheat leaving the evaporator is relatively small here roughly only half of the compressor suction superheat maintained by the TXV. The second portion of the compressor suction superheat is added by heat transfer in the four way mode switching valve TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

5 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 4 of 13 suction pressure and the condenser pressure equals the compressor discharge pressure. The model inputs (compressor suction pressure evaporator saturation temperature, compressor suction superheat, compressor discharge pressure condenser saturation temperature, condenser subcooling, and compressor adiabatic efficiency) were set to match those for the R22 baseline experimental data. The switching valve for cooling or heating model is assumed to behave as a heat exchanger with a temperature effectiveness of 5% (from the R410A test data). Measured capacities ranged from 10% higher (DR 7) to 5.5% lower (D52Y) than with R22. The capacities with DR 7 and D52Y were about 5.5% higher than predicted by the simple model; ARM 32a was up about 2%. The capacity with LTR6A was ~10% lower than predicted; as discussed further below, LTR6A has a very large glide of 25+d. All of the alternate refrigerants had measured EER s significantly lower than with R22, ranging from 5% for L 20 to 20% for LTR6A. Measured EER s ranged from 2 5% lower than predicted, except the measured EER for LTR6A was nearly 18% lower than predicted. Refrigerant charges ranged from a nearly 10% reduction with L 20 to a 14% increase for LTR6A, with most of the others requiring a small 5% increase in charge. Figure 6 shows the superheats measured at the evaporator outlet and at the compressor suction (the difference is caused by heat transfer in the four way mode switching valve). Most tests were held within the 10 12d target band, although the LTR4X and LTR6A superheats proved a bit difficult to adjust and maintain. The condenser exit subcooling obtained at the nominal operating condition with optimum charge is shown in Figure 7. Subcooling generally ranged between 9 14d. The R22 alternate subcoolings are slightly smaller than for the R410A alternates. Determining the approach temperatures between the water and refrigerant in the evaporator (BPHE) is somewhat problematic. The water and refrigerant are in counter flow. On the refrigerant side, restrictions internal to the heat exchanger create a large pressure drop between the evaporator inlet pressure measurement point and the heat exchanger channels (to promote uniform flow rates through the channels). Therefore, the true pressure of the refrigerant entering the heat exchanger channels is unknown. It is estimated here by assuming that 85% of the total pressure drop across the BPHE occurs across the entrance restrictions (same assumption used for R410A data analysis). The resulting evaporator approach temperatures are shown in Figure 8. The Twtr,lvg Tsat,ent approach temperatures measured during the R22 alternate testing are 5 8d higher than in the R410A testing. 4 The approach temperatures between the entering water and leaving refrigerant are shown by the second and third columns in Figure 8. The difference between these two columns is the evaporator exit superheat. These two approach temperatures are similar between the R22 and R410A testing. Figure 9 compares the water and refrigerant temperature glides for each of the refrigerants tested. As with the HPR1D in the R410A testing, the excessively large glide associated with LTR6A is likely having a negative impact on performance. The refrigerant glides associated with the R22 alternates are somewhat larger than for the R410A alternates. Figure 10 provides measures of condenser performance. The entering refrigerant dew point temperatures (an indication of the excess pressure needed to achieve the condenser heat rejection) of all the alternate refrigerants are slightly higher than the baseline R22 case. The significantly higher entering dew point for LTR6A is again likely attributable to its large glide and might contribute to the degraded performance relative to the simple model prediction. 4 The fractional pressure drop across the BPHE entering orifice has to be dropped to ~50% to make the Twtr,lvg Tsat,ent s for the R22 tests match the R410A tests at 85%. However, this would result in a large negative glide for R22 because of the relatively large pressure drop across the refrigerant channels. TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

6 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 5 of 13 The pressure drops along the evaporator to compressor suction and compressor discharge to condenser lines are shown in Figure 11. The line pressure drops range from slightly higher to somewhat lower for the alternate refrigerants compared with the R22 baseline. The pressure drops correlate with the refrigerant mass flow rates shown in Figure 12 (computed from the measured evaporator water side heat transfer rate, the refrigerant enthalpy leaving the evaporator as determined from the measured temperature and pressure, and the refrigerant enthalpy entering the evaporator as determined from the measured temperature and pressure at the condenser outlet assuming adiabatic flow through the expansion device). Figure 13 shows the compressor adiabatic efficiencies computed from the suction and discharge measurements and the fluid properties as provided by the refrigerant suppliers. Some of variation can be attributed to uncertainties in fluid properties, in particular, the ideal gas specific heat (likely estimated, not measured for most blends). Some of the variation can be attributed to the pressure ratios seen by the compressor; see Figure 14. For example, the low compressor efficiency seen for LTR6A might be a consequence of significantly higher pressure ratio experienced. Figure 15 shows the compressor discharge temperatures reached for each refrigerant. The experimental results match the predictions reasonably well the measured discharge temperatures range from 0 (R22) to 8d (DR 7) higher than modeled, with LTR4X ( 12d) and LTR6A ( 16d) being exceptions. Finally, Figure 16 shows the ratio of refrigerant volume flow rate to the swept volume of the compressor stated by the manufacturer. The refrigerant volume flow rate is computed from the mass flow rate as computed above (Figure 12) and the refrigerant specific volume as determined from the measured temperature and pressure entering the compressor. The ratios vary from 2% (LTR6A) to 3% (DR 7) relative to R22. The variation could come from the range of compression ratios experienced, along with any errors/uncertainties there might be in the gas region PVT equations of state. REMARKS In general, the test results were similar between the R410A like and R22 like refrigerants. The short fall in EER of the R22 refrigerants is greater than for the R410A refrigerants. The discrepancies between the measured results and the simple model predictions were a little larger for the R22 alternates than the R410A alternates. It appears that the majority of the candidates considered here could successfully be used in high pressure HVAC&R equipment with varying levels of design modifications. It also appears that large refrigerant glide can negatively impact performance, at least for the equipment and operating conditions tested here. TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

7 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 6 of 13 NOMENCLATURE BPHE Brazed Plate Heat Exchanger CAP Capacity [RT or Btu/hr or W] Chrg refrigerant charge [lbm or kg] CiDP Condenser inlet Dew Point (dew point temperature of refrigerant entering condenser) CoBP Condenser outlet Bubble Point (bubble point temperature of refrigerant leaving condenser) COP Coefficient of Performance [ ] dpent ratio of the refrigerant pressure drop across the distributor entering the evaporator channels to the total pressure drop across the evaporator EER Energy Efficiency Ratio = cooling capacity measured from water side of evaporator divided by electrical power input [Btu/W hr] EERc EER based on power input to compressor only EERt EER based on total power input (compressor, fans, and controls) RT Refrigeration Tons RTPF Tair TCo Tdew,lvg Tref,lvg Tsat,ent Twi Two Twtr,ent Twtr,lvg Round Tube Plate Fin heat exchanger (condenser coil ) temperature of the ambient air entering the condenser subcooled refrigerant temperature leaving condenser saturation temperature (dew point) at the refrigerant pressure leaving the evaporator temperature of the superheat refrigerant vapor leaving the evaporator saturation temperature of the refrigerant entering the evaporator channels (after the inlet distributor ) temperature of the chilled water entering the evaporator temperature of the chilled water leaving the evaporator temperature of the chilled water entering the evaporator temperature of the chilled water leaving the evaporator TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

8

9 Low GWP AREP High Pressure Test Summary Final Report (Cooling Mode) created: 19 November 2012 last edited: 19 November 2012 page 8 of 13 cooling: evaporator inlet (check Tsat) heating: condenser outlet (subcooling) T cooling: evaporator inlet P heating: condenser outlet cooling: evaporator outlet P T cooling: evaporator outlet (superheat) heating: condenser inlet heating: condenser inlet (superheat) T P Koolman Chiller/Heat Pump Test of Alternate Refrigerants LO Instrumentation Refrigerant Circuit (v1) HP LP HP LP 1 EVAP TFi filter or P F city water TFo expansion tank T 13 2 LP 12 HP 11 "T" "Tsat(P)" Flow T P accum Flow 10 control panel variable control discharge superheat control box Tdischarge 6 COOLING MODE liquid injection for discharge superheat control Twell (empty) P T P T cooling: condenser outlet (subcooling) heating: evaporator inlet (check Tsat) cooling: condenser inlet (superheat) heating: evaporator outlet (superheat) 8 9 COND TC's Measure T's at outlet of each circuit to check for maldistribution? (cmpr discharge) T T air (cmpr discharge) P Schrader valves Phi cut-out switch CMPR Plo cut-out switch T (cmpr suction) 7 P (compressor power) W (cmpr suction) (unit power) W Figure 2. Schematic diagram of Koolman system showing locations of measurement points. printed 6 Jul, 2012 Drawing1 Page-1 TraneHP_Report#3_ docx Ken Schultz Thermal Systems Group

10

11

12

13

14

15 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix A: Instrumentation List ID # ** Description Units Stated Sensor Accuracy Measurement Accuracy 1 BPHX Water Flow GPM SI: m³/h ± 0.5% of Rdg ± 0.5% of Rdg 2 BPHX Waterside Delta P psid SI: kpa diff 0.2% of Span ± PSID 3 Ent BPHX Water Pressure psia SI: kpa abs 0.05% of FS ± PSIA 4 Lvg BPHX Water Pressure psia SI: kpa abs 0.05% of FS ± PSIA 5 Entering BPHX Water Temp SI: C ± 0.1 F 6 Leaving BPHX Water Temp SI: C ± 0.1 F 7 Outdoor Air DB Temp SI: C ± 0.1 F 8 Outdoor Air WB Temp SI: C ± 0.5 F 9 Barometric Pressure psia SI: kpa abs 0.1% of FS ± PSIA 10 Compressor Discharge Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 11 RTPF Vapor Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 12 RTPF Liquid Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 13 Entering TXV Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 14 BPHX Liquid Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 15 BPHX Vapor Refr Pressure psia SI: kpa abs 0.05% of FS ± PSIA 16 Compressor Suction Pressure psia SI: kpa abs 0.05% of FS ± PSIA 20 Compressor Discharge Refr Temp SI: C ± 1.0 F 21 RTPF Vapor Refr Temp SI: C ± 1.0 F 22 RTPF Liquid Refr Temp SI: C ± 1.0 F 23 Entering TXV Refr Temp SI: C ± 1.0 F 24 BPHX Liquid Refr Temp SI: C ± 1.0 F 25 BPHX Vapor Refr Temp SI: C ± 1.0 F 26 Compressor Suction Temp SI: C ± 1.0 F 30 Ent RTPF Circuit Temp #1 (cooling) SI: C ± 1.0 F 31 Ent RTPF Circuit Temp #2 (cooling) SI: C ± 1.0 F 32 Ent RTPF Circuit Temp #3 (cooling) SI: C ± 1.0 F 33 Ent RTPF Circuit Temp #4 (cooling) SI: C ± 1.0 F 34 Ent RTPF Circuit Temp #5 (cooling) SI: C ± 1.0 F 35 Ent RTPF Circuit Temp #6 (cooling) SI: C ± 1.0 F 36 Ent RTPF Circuit Temp #7 (cooling) SI: C ± 1.0 F 37 Ent RTPF Circuit Temp #8 (cooling) SI: C ± 1.0 F 40 Lvg RTPF Circuit Temp #1 (cooling) SI: C ± 1.0 F 41 Lvg RTPF Circuit Temp #2 (cooling) SI: C ± 1.0 F 42 Lvg RTPF Circuit Temp #3 (cooling) SI: C ± 1.0 F 43 Lvg RTPF Circuit Temp #4 (cooling) SI: C ± 1.0 F 44 Lvg RTPF Circuit Temp #5 (cooling) SI: C ± 1.0 F 45 Lvg RTPF Circuit Temp #6 (cooling) SI: C ± 1.0 F 46 Lvg RTPF Circuit Temp #7 (cooling) SI: C ± 1.0 F 47 Lvg RTPF Circuit Temp #8 (cooling) SI: C ± 1.0 F 50 Liquid Refrigerant Flow GPM SI: m³/h ± 0.5% of Rdg ± 0.5% of Rdg 51 Compressor Liquid Injection Flow GPM SI: m³/h ± 0.5% of Rdg ± 0.5% of Rdg 60 Compressor Voltage AB V SI: V 0.2% of Rdg + ± 0.1% of Range 61 Compressor Voltage BC V SI: V 0.2% of Rdg + ± 0.1% of Range 62 Compressor Voltage AC V SI: V 0.2% of Rdg + ± 0.1% of Range 63 Compressor Current A A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 64 Compressor Current B A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 65 Compressor Current C A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 66 Compressor Power W SI: W 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 70 Total Unit Voltage AN V SI: V 0.2% of Rdg + ± 0.1% of Range 71 Total Unit Voltage BN V SI: V 0.2% of Rdg + ± 0.1% of Range 72 Total Unit Voltage AN V SI: V 0.2% of Rdg + ± 0.1% of Range 73 Total Unit Current A A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 74 Total Unit Current B A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 75 Total Unit Current C A SI: A 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 76 Total Unit Power W SI: W 0.2% of Rdg + ± 0.1% of Rang ~0.5% of Rdg w/ CTs 90 Ent RTPF Air Temp #1 SI: C ± 1.0 F 91 Ent RTPF Air Temp #2 SI: C ± 1.0 F 92 Ent RTPF Air Temp #3 SI: C ± 1.0 F 93 Ent RTPF Air Temp #4 SI: C ± 1.0 F 94 Ent RTPF Air Temp #5 SI: C ± 1.0 F 95 Ent RTPF Air Temp #6 SI: C ± 1.0 F 96 Ent RTPF Air Temp #7 SI: C ± 1.0 F 97 Ent RTPF Air Temp #8 SI: C ± 1.0 F 98 Ent RTPF Air Temp #9 SI: C ± 1.0 F 99 Ent RTPF Air Temp #10 SI: C ± 1.0 F 100 Ent RTPF Air Temp #11 SI: C ± 1.0 F 101 Ent RTPF Air Temp #12 SI: C ± 1.0 F 102 Ent RTPF Air Temp #13 SI: C ± 1.0 F 103 Ent RTPF Air Temp #14 SI: C ± 1.0 F 104 Ent RTPF Air Temp #15 SI: C ± 1.0 F

16 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 12 Oct 2012 Alternative Refrigerant DR 7 DuPont Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 16,203 W 50,329 55,287 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 6,961 W 5,700 6,961 W Power to Compressor 5,369 6,623 W 5,369 6,623 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF DR 7

17 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 12 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: DR 7 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , DR 7

18 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 12 Oct 2012 Alternative Refrigerant ARM 32a Arkema Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 15,612 W 50,329 53,269 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 6,775 W 5,700 6,775 W Power to Compressor 5,369 6,431 W 5,369 6,431 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF ARM 32a

19 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 12 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: ARM 32a Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , ARM 32a

20 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 12 Oct 2012 Alternative Refrigerant L 20 Honeywell Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 14,857 W 50,329 50,695 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 6,052 W 5,700 6,052 W Power to Compressor 5,369 5,718 W 5,369 5,718 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF L 20

21 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 12 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: L 20 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , L 20

22 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 12 Oct 2012 Alternative Refrigerant LTR4X Mexichem Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 14,790 W 50,329 50,464 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 6,297 W 5,700 6,297 W Power to Compressor 5,369 5,955 W 5,369 5,955 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF LTR4X

23 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 12 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: LTR4X Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , LTR4X

24 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 12 Oct 2012 Alternative Refrigerant LTR6A Mexichem Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 14,971 W 50,329 51,082 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 7,112 W 5,700 7,112 W Power to Compressor 5,369 6,765 W 5,369 6,765 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF LTR6A

25 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 12 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: LTR6A Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , LTR6A

26 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 1 Manufacturer: Basic Information Trane 15 Oct 2012 Alternative Refrigerant D52Y Daikin Alternative Lubricant Type and ISO Viscosity POE 160SZ Baseline Refrigerant R22 Baseline Lubricant Type and ISO Viscosity POE 160SZ Make and Model of System Koolman CGAR 0605 Air Cooled Water Chiller / Heat Pump Nominal Capacity and Type of System 15.6 kw cooling / 17.7 kw heating (4.4 tons / 5.0 tons) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) cooling Compressor Type scroll compressor (Copeland ZR81KC TFD 50 Hz, 3φ, 380V) Compressor Displacement 18.7 m³/hr 662 ft³/hr Nominal Motor Size not listed by Copeland kw not listed by Copeland hp Motor Speed (50 Hz) not listed by Copeland Hz Expansion Device Type TXV (Danfoss, TDEX6, 068H4103) Lubricant Charge 1.8 L 1.9 qt Refrigerant Charge kg lbm Composition (at Cmpr Suct) Chilled Leaving Temp 7.2 C 45 Water Flow rate 53.0 L/min 14.0 gpm Outdoor Dry Bulb 35 C 95 Air Wet Bulb n/a C n/a Total Capacity 14,750 13,954 W 50,329 47,612 Btu/hr Sensible Capacity n/a n/a W n/a n/a Btu/hr n/a Total System Power Input 5,700 5,926 W 5,700 5,926 W Power to Compressor 5,369 5,597 W 5,369 5,597 W COP or EER (total) [] Btu/W hr COP or EER (compressor only) [] Btu/W hr Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was returned to original production by replacing the compressor and TXV with original equipment. The evaporator remains the one used during R410A testing. System Data Base Alt. Ratio Degradation Coefficient Seasonal Energy Efficiency Ration SEER Heating Seasonal Performance Factor HSPF D52Y

27 Trane Koolman Tests of "HP" Alternate Refrigerants Appendix B: Experimental Results at Nominal Operating Condition Low GWP AREP SYSTEM DROP IN TEST DATA FORM page 2 15 Oct 2012 Type of System: Koolman CGAR 0605 Alternate Refrigerant: D52Y Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio Diff Evaporator (BPHE) fluid flow rate water L/hr gpm T entering C T leaving C Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd gpm T entering C T leaving not msrd C not msrd Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet , , outlet , , outlet subcooling Expansion Device (TXV) inlet , , inlet subcooling Evaporator (water to refrig BPHE) inlet outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet , , HP outlet , , D52Y

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32

More information

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

January 16 th, 2014 New York City

January 16 th, 2014 New York City Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January

More information

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Progra (Low-GWP AREP) TEST REPORT #68 Syste Drop-in Test of (R-448a) in a R04A Low and Mediu Teperature

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

More information

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units

More information

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) 2014 Purdue Conferences Xudong Wang and Karim Amrane Air Conditioning, Heating, and Refrigeration Institute (AHRI) Low GWP AREP Introduction

More information

GWP Alternative Refrigerants

GWP Alternative Refrigerants Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum

More information

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Low GWP Refrigerants for Air Conditioning and Chiller Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Low GWP Refrigerants for Air Conditioning and Chiller Applications Ankit

More information

Refrigerant Glide and Effect on Performances Declaration

Refrigerant Glide and Effect on Performances Declaration Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential

More information

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and

More information

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Figure 1: Schematic of internal heat exchanger vapor-injection cycle Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor

More information

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down

More information

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration Marquette University e-publications@marquette Mechanical Engineering Faculty Research and Publications Mechanical Engineering, Department of 1-1-2013 Modeling and Testing of an R-23/R-134a Mixed Refrigerant

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes ME 410 - Mechanical Engineering Systems Laboratory Experiment 3 - Mass and Energy Balances in Psychrometric Processes Assist.Prof.Dr. Özgür BAYER, A-123 AIR-CONDITIONING (A/C) Goal: Control temperature

More information

R4H4. Product Specifications

R4H4. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI Standard 1230 with Addendum 1 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI STANDARD 1230-2014 WITH ADDENDUM 1,

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Application of a hybrid control of expansion valves to a 3-ton large room cooling system 2123, Page 1 Application of a hybrid control of expansion valves to a 3-ton large room cooling system Christian K. Bach*, Eckhard A. Groll, James E. Braun Ray W. Herrick Laboratories, Purdue University,

More information

R4H4. Product Specifications

R4H4. Product Specifications R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on

More information

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment HVAC&R Research ISSN: 1078-9669 (Print) 1938-5587 (Online) Journal homepage: http://www.tandfonline.com/loi/uhvc20 Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor-

More information

Air Cooled Packaged Systems AIRAH Back to Basics

Air Cooled Packaged Systems AIRAH Back to Basics Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM Hantz, D., Gulyas, G., Bensafi, A. Centre Technique des Industries Aéraulique et Thermique (CETIAT) BP 2042

More information

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature. Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Evaluation of Heat pump System using and ed Refrigerant in

More information

Refrigeration/Troubleshooting Manual

Refrigeration/Troubleshooting Manual Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 P/N: 2300100910 Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Executive Summary. Number of Low Number of High Number of Faults , Number of OK Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes

More information

Steady and Cyclic Performance Testing of Packaged R-410A Units

Steady and Cyclic Performance Testing of Packaged R-410A Units Prepared by: Bo Shen, James E. Braun, and Eckhard A. Groll Ray W. Herrick Laboratories The School of Mechanical Engineering Purdue University Steady and Cyclic Performance Testing of Packaged R-410A Units

More information

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration Marquette University e-publications@marquette Master's Theses (2009 -) Dissertations, Theses, and Professional Projects Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator

More information

R-404A Alternative with Low Compressor Discharge Temperature

R-404A Alternative with Low Compressor Discharge Temperature 2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA

More information

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON 7D- -A EVOLUTIONr 15 SEER SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONr (R-410A) REFRIGERANT SINGLE PHASE 2-5 NOMINAL TONS (SIZES 24-) Fig. 1 - Unit 7D - -A Product Data A09032 Single-Packaged Products

More information

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using

More information

Oxyvap Evaporative Cooling Applications

Oxyvap Evaporative Cooling Applications Oxyvap Evaporative Cooling Applications Oxycom Fresh Air BV March 9th, 2015 Abstract This paper shows two highly efficient applications of the Oxyvap direct evaporative cooling technology, developed by

More information

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research Update on Next Generation Low GWP Refrigerants for Chillers Products Steve Kujak Director, Next Generation Refrigerant Research The International Symposium on New Refrigerants and Environmental Technology

More information

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential

More information

R-407A R-448A R-449A

R-407A R-448A R-449A GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

The Current Path of Refrigerants

The Current Path of Refrigerants The Current Path of Refrigerants Rick Wentling NA Market Development Manager Opteon Stationary Refrigerants November 9, 2017 Prediction is very difficult; especially if it s about the future. - Neils Bohr

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Numbers of Abstract/Session (given by NOC) - 1 - DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Richard W. Murphy Van D. Baxter Edward A. Vineyard Randall L.

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Paper O.1.2.4-1 - Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Sungjin In, Graduate student, Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Keumnam Cho, Professor,

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

System Considerations for Refrigerant Blends with Temperature Glide

System Considerations for Refrigerant Blends with Temperature Glide System Considerations for Refrigerant Blends with Temperature Glide Theory and Practical Retrofit Guidance Table of Contents 1 2 3 4 5 Blend and Glide Basics... 3 1.1 Superheat and Subcooling of Refrigerant

More information

AIR CONDITIONER PERFORMANCE RATING

AIR CONDITIONER PERFORMANCE RATING HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

10/4/2013. The Changing State of Refrigerants

10/4/2013. The Changing State of Refrigerants 10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

N4H4. Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase, 208/230 Volt 3- phase, 460 Volt 3- phase; 60 Hz REFRIGERATION CIRCUIT S Scroll compressors

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

HFO-1234yf Performance in a Beverage Cooler

HFO-1234yf Performance in a Beverage Cooler 2422 Page 1 HFO-1234yf Performance in a Beverage Cooler Barbara MINOR 1 *, Carlos MONTOYA 2, Francisco Sandoval KASA 3 1 DuPont Fluoroproducts, Wilmington, DE, USA Phone: 302-999-2802, E-mail: barbara.h.minor@usa.dupont.com

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

of the liquid prior to it entering the expansion device. By doing so, the capacity for

of the liquid prior to it entering the expansion device. By doing so, the capacity for of the liquid prior to it entering the expansion device. By doing so, the capacity for refrigeration is increased. Refrigerator evaporator Capillary tube T Subcooler 2 T 1 Suction-line heat exchanger Refrigerator

More information

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total. 1. State 2 75 o F Exhaust M amb T amb State 3 Room Q chiller State 1 60 o F M total A room at steady state has a supply air stream of cool air entering at 60 o F. The lights, office appliances and people

More information

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1 Week 4 Gas-vapor mixtures Air conditioning processes ME 300 Thermodynamics II 1 Today s Outline Gas-vapor mixtures Key definitions and measures ME 300 Thermodynamics II 2 Gas-vapor Mixtures At temperatures

More information

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information