Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration
|
|
- Bartholomew Ford
- 5 years ago
- Views:
Transcription
1 Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration Unit.
2 Acknowledgements Thanks to the following companies for supplying the refrigerant samples tested: - Chemours To those who performed the work: - Michal Hegar - Michal Kolda - Vladimír Šulc - Prague Lab Team 2
3 Purpose & Some Evaluation Details Evaluate the soft optimized test results of next generation alternative refrigerant R452A in a R404A trailer refrigeration unit. Soft Optimization Changes - Adjustment of expansion device (1/4 turn open) - Refrigerant charge unchanged (4 kgs) Results are compared to the same trailer refrigeration unit running on R404A tested at same ambient temperature / box temperature / compressor speed conditions. 3
4 R452A Properties & Safety GWP 2140 (AR4) 1945 (AR5) Blend- ASHRAE Class A1: 11% R32/59% R125/30% R1234yf Temperature Glide = 4ºC (7.2ºF) vs. R404A = 0.8ºC (1.4ºF) Compressor Discharge Temperature = up 3.3ºC (6ºF) vs R404A R452A is a Close Property Match to R-404A 4
5 Test Setup Application: Trailer refrigeration unit sized for 15 meter European Trailer 5
6 Test Conditions - Unit run at high diesel engine speed mode (HS) and at electric stand-by (stand-by) mode under the temperature conditions shown below. Condenser Air Inlet Temperature (CAIT) Evaporator Air Inlet Temperature (EAIT) [ C] [ F] [ C] [ F] Note: AHRI condition AHRI condition Added condition ATP condition ATP condition 6
7 Test Results Cooling Capacity at 30.0 ºC (86ºF) Capacity Equal at Fresh & Frozen Conditions 7
8 Test Results Cooling Capacity at 37.8 ºC (100ºF) Capacity Close Match at Fresh Conditions Small Decreases at Frozen & Deep Frozen Conditions 8
9 Test Results COP at 30.0 ºC (86ºF) COP Basically the Same at Fresh & Frozen Conditions 9
10 Test Results COP at 37.8 ºC (100ºF) COP Basically the Same at Fresh & Frozen Conditions Small Decrease at Deep Frozen 10
11 Test Results Compressor Discharge Temperature at 30.0 ºC (86ºF) Discharge Temps as Predicted Up Max 3.3ºC (6ºF) 11
12 Test Results Compressor Discharge Temperature at 37.8 ºC (100ºF) Discharge Temps as Predicted Up Max 3.3ºC (6ºF) 12
13 Test Results Compressor Discharge Pressure at 30.0 ºC (86ºF) Discharge Pressures as Predicted 13
14 Test Results Compressor Discharge Pressure at 37.8 ºC (100ºF) Discharge Pressures as Predicted 14
15 Conclusions R452A (DR34) is comparable to R404A in capacity and efficiency at fresh conditions at both ambients with only small drops in capacity (-5.5% max) and efficiency (-3.3% max) were seen at the frozen and deep frozen conditions Compressor discharge temperatures and pressures were as predicted and acceptable for use in these types of products. Soft optimization consisted of; - Small expansion device adjustment to accommodate a minor change in mass flow rate (1/4 turn open). 15
16 Other R452A References KUJAK S.(*), BERGE J.(**), MAJURIN J.(*), KOLDA M., CROMBIE D. (*) Ingersoll Rand, United States, (**) Thermo King, United States, Assessment of Next Generation Refrigerant R452A to Replace R404A for Transport Refrigeration, ICR th IIR International Congress of Refrigeration. ZILIO C.(*), MANCIN S.(*), BROWN S. J.(**), LONGO G. A.(*) (*), New Refrigerant Options for R404A Replacement in Truck Refrigeration Systems, University of Padova, Department of Management and Engineering, Italy, (**) The Catholic University of America, School of Engineering, United States, ICR th IIR International Congress of Refrigeration. 16
17 Lubricant Compatibility Existing POEs found acceptable with the R452A Miscibility Solubility Viscosity Stability PVE s found to be chemical unstable with R452A New additives proposed to allow increased stability Existing POEs Found Compatible - Slightly Better Viscosity 17
18 R452A Chemical Stability & Materials Compatibility Good industry experience with R32 and R125 R1234yf knowledge base growing YF been found compatibility to HFCs Stability less than R- 134a, but acceptable Compatibility of Materials with R-452A Similar To R-404A 18
19 Field Trials & Experiences Marine Container Netherlands to Australia No issues Trailer have been shipped to date Issues Seen? ZERO! 19
20 Steve Kujak
21 APPENDIX 21
22 Test Setup Unit basic description: - Compressor: 4 cylinder reciprocating open shaft, 30 in 3 displacement - Lubricant: 35 cst, POE - Refrigeration system schematic diagram: 22
23 Test Setup, Cont. Monitored quantities: 23
24 Test Setup, Cont. Test chamber: Calorimeter cell with determined heat losses (gains) + measured heat input per ANSI/AHRI Standard 1110 Measurement uncertainty = ± 2 % (From ANSI/AHRI Standard 1110) 24
Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning
Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units
More informationR-404A Alternative with Low Compressor Discharge Temperature
2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA
More informationTEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationUpdate on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research
Update on Next Generation Low GWP Refrigerants for Chillers Products Steve Kujak Director, Next Generation Refrigerant Research The International Symposium on New Refrigerants and Environmental Technology
More informationTEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationTEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A
More informationLower GWP Refrigerants Compared to R404A for Economizer Style Compressors
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm
More informationReference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.
GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant
More informationBehavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationSystematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential
More informationANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS
ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS YANA MOTTA, S. (*), SPATZ, M., VERA BECERRA, E. (*) Honeywell International, 2 Peabody Street, Buffalo, NY 1421, Samuel.YanaMotta@honeywell.com
More informationSeminar 34 Refrigerants Today, Tomorrow, and Beyond
m Bianca W. Hydutsky, Ph.D. DuPont Chemicals & Fluoroproducts bianca.hydutsky@dupont.com Seminar 34 Refrigerants Today, Tomorrow, and Beyond Thermal Stability Studies to Evaluate Low-GWP Refrigerants 1
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationAHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)
AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) 2014 Purdue Conferences Xudong Wang and Karim Amrane Air Conditioning, Heating, and Refrigeration Institute (AHRI) Low GWP AREP Introduction
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationSystem Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationTEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,
More informationSustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn
Sustainable Refrigerant Solutions for HVAC-R Laurent Abbas, Wissam Rached, Brett Van Horn 2014 ASHRAE Annual Conference Seattle, WA July 1, 2014 Learning Objectives 1. Design refrigeration and air-conditioning
More informationJanuary 16 th, 2014 New York City
Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January
More informationTEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
More information2016 Annual Conference
2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance
More informationThe R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard
Opteon Refrigerants The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard Mark Hughes Business Development Manager Opteon Refrigerants Agenda Intro Chemours The Chemical
More informationPREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17
PREPARE FOR CHANGE LOW GWP ALTERNATIVES November 17 F-GAS PHASE DOWN Where we are now F-Gas regulation places restrictions on the use of some HFC refrigerants of high GWP. This is indirectly achieved by
More informationTEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,
More informationThe lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator
The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator Vicente Guilabert HUAYI COMPRESSOR BARCELONA, S.L The Company Huayi Compressor Barcelona, S.L.
More informationDEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
Thomas Leck, PhD DuPont Fluorochemicals 2010 NEXT ACR Tokyo International Exchange Center 17 Feb 2010 DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
More informationGWP Alternative Refrigerants
Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum
More informationNew Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA
New Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA 5 th March 2014 Honeywell $39-39.5B in sales* 54% sales outside U.S. 1,300 sites, 70 countries 132,000 employees Morristown,
More informationTEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and
More informationAmmonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member
Ammonia Refrigeration & Scenario in Industrial Refrigeration By Ramesh Paranjpey ASHRAE Fellow Life member 5 th March 2014 Basic Components Of A Refrigeration System Refrigerant Flow Path Refrigerant?
More informationTEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source
More informationGary Parker Refrigerants Product Manager
Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance
More informationAIR CONDITIONING COMPRESSOR OIL
AIR CONDITIONING COMPRESSOR OIL PAG, PAO AND POE OILS THERE ARE LOTS OF OILS AVAILABLE, WHICH ONE IS RECOMMENDED? Oil plays an important role in the air-conditioning system, no matter whether it's required
More informationUnderstanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies
Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants
More informationChapter 2. Alternatives to HCFCs and their Characteristics
Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid
More informationDevelopment of centrifugal chiller and heat pump using low GWP refrigerant
Development of centrifugal chiller and heat pump using low GWP refrigerant Ryosuke Suemitsu 1*, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy
More informationPerformance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in
More informationThe Current Path of Refrigerants
The Current Path of Refrigerants Rick Wentling NA Market Development Manager Opteon Stationary Refrigerants November 9, 2017 Prediction is very difficult; especially if it s about the future. - Neils Bohr
More informationREFRIGERANT CHANGEOVER
Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants
More informationStudy of R161 Refrigerant for Residential Airconditioning
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen
More informationScroll Chillers Transition from HCFC-22 to HFCs
Scroll Chillers Transition from HCFC-22 to HFCs An HVAC Manufacturer s Perspective Todd Brown McQuay International Business Development Manager Chillers todd.brown@mcquay.com ICF Workshop, Montreal Canada,
More informationComparative assessment for drop in replacement of R134a in domestic refrigerator.
Comparative assessment for drop in replacement of R134a in domestic refrigerator. Pravin K. Katare Research Scholar, Department of Mechanical Engineering, G.H.Raisoni College of Engineering Digdoh Hill,
More informationGary Parker Refrigerants Product Manager
Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance
More informationR32 Compressor for Air conditioning and Refrigeration applications in China
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua
More informationPerformance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for
More informationV Series. Superior Temperature Control. Small trucks and vans
V Series Superior Temperature Control Small trucks and vans Modern compact platform User friendly Direct Smart Reefer Increased reliability Easy maintenance, service and installation Content Introduction
More informationOil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Oil Return Measurements In A Unitary Split System Air Conditioner Using
More informationEffects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 0 Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of
More informationStandard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units
ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed
More informationCO 2 transcritical FTE System Full Transcritical Efficiency
CO 2 transcritical FTE System Full Transcritical Efficiency FRANCESCO MASTRAPASQUA Marketing Manager Refrigeration Systems Francesco.Mastrapasqua@eptarefrigeration.com www.eptarefrigeration.com HFC refrigerants
More informationDue to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.
TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there
More informationRefrigerant Dryers DRY with PDP Indicator
Refrigerant Dryers DRY with PDP Indicator Refrigerant dryers range From 333 lt./min up to 21.000 lt./min PDP: 5 C at reference conditions Whole range with the PDP indicator Max. working pressure: 16 bar
More informationScroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C
Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C McQuay International (A Member of the DAIKIN Group) Hydrofluorocarbon (HFC) refrigerants are critical to the safe and cost-effective phase-out
More information(12) Patent Application Publication (10) Pub. No.: US 2016/ A1
(19) United States US 2016O13 0490A1 (12) Patent Application Publication (10) Pub. No.: US 2016/0130490 A1 KUJAK et al. (43) Pub. Date: May 12, 2016 (54) REFRIGERANT COMPOSITIONS AND Publication Classification
More informationA: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.
1/1/12 RS-45 (R434A): Q & A 1 Q: What is RS-44? 1.Q: What is RS-45 A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-45 contain? A: RS-45 is
More informationEmbraco Position Paper: Light Commercial Refrigeration
Embraco Position Paper: Light Commercial Refrigeration Refrigerants Outlook 2018 www.embraco.com Introduction The global community, with Kigali Amendment to Montreal Protocol, made another important step
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationA study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion
A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion Prepared for the Public Commenting Meeting of Ph.D program February 28,
More informationZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS
ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS Per the EPA: Retail food refrigeration, or commercial refrigeration, includes equipment designed to store and display chilled
More informationRefrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan
More informationPerformance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION
2597, Page 1 Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump Ian H. BELL 1 *, James E. BRAUN 2 1 Bell Thermal Consultants ian.h.bell@gmail.com 2 Purdue
More informationAIRAH Victoria Refrigerants Update
AIRAH Victoria Refrigerants Update 20 th October 2014 Agenda R22 Phase down Legislation and options Interim replacements and considerations New HFO refrigerants Legislation as a driver for change New HFO
More informationDirect Drive Truck Units. A complete line of refrigeration units for a wide variety of vehicle chassis and applications.
Direct Drive Truck Units A complete line of refrigeration units for a wide variety of vehicle chassis and applications. CLEAN, EFFICIENT, RELIABLE. THERMO KING DIRECT DRIVE VEHICLE-POWERED UNITS FOR A
More informationBRA FACT FINDER Number 19
BRA FACT FINDER Number 19 Issue: 1 Date: March 2017 A practical guide to using refrigerants with a temperature glide This document is the second in a series of bulletins produced by the BRA following the
More informationV-Series. Superior Temperature Control for Small Trucks and Vans
V-Series Superior Temperature Control for Small Trucks and Vans Modern compact platform User-friendly Direct Smart Reefer Increased reliability Easy maintenance, service and installation Enhanced performance
More informationDirect Drive Truck Units. A complete line of refrigeration units for a wide variety of vehicle chassis and applications.
Direct Drive Truck Units A complete line of refrigeration units for a wide variety of vehicle chassis and applications. CLEAN, EFFICIENT, RELIABLE. THERMO KING DIRECT DRIVE VEHICLE-POWERED UNITS FOR A
More informationEvaluation and Development of Air-conditioners using Low GWP Refrigerant
th IEA Heat Pump Conference 07 Rotterdam Evaluation and Development of Air-conditioners using Low GWP Refrigerant Shigeharu TAIRA, Tomoyuki HAIKAWA *, Tomoatsu MINAMIDA DAIKIN INDUSTRIES, LTD. 6th, May,
More informationDuPont Refrigerants. John McCormack Business Manager DuPont Chemicals and Fluoroproducts. R22 market and the ISCEON retrofit options
DuPont Refrigerants R22 market and the ISCEON retrofit options Airefrig November 2010 John McCormack Business Manager DuPont Chemicals and Fluoroproducts HCFC Regulations & ISCEON 3 Actions Impacting Fluorochemicals
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Chicago, IL October 5, 2017 Jason Prenger Director of Engineering Emerson Disclaimer This presentation is intended to highlight changing
More informationMarch 2014 AHRI Presents Research Findings at Low-GWP AREP Conference
March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference In addition to its regular research activities, AHRI is conducting the Low-Global Warming Potential Alternative Refrigerants Evaluation
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties
More informationFACT SHEET 6 Transport Refrigeration
UNEP Ozone Secretariat Fact Sheets on HFCs and Low GWP Alternatives UNEP Ozone Secretariat Background Material on HFC Management October 205 FACT SHEET 6 Transport Refrigeration. Description of market
More informationTERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION
TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION Kazimierz MACZEK Jaros aw MÜLLER Kazimierz WOJTAS TECHNICAL UNIVERSITY of CRACOW Institute of Thermal Engineering and Air Protection
More informationMarch 10, 2016 San Joaquin Valley RETA Meeting
March 10, 2016 San Joaquin Valley RETA Meeting Refrigerant Selection Peter Thomas, P.E., CSP Resource Compliance, Inc. Background and History Simple, dangerous Compounds Safer, more complex refrigerants
More informationAN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS
AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore
More informationAPS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017
APS Chiller Seminar Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 Agenda for today Refrigeration Cycle Chiller Types and Refrigerants Compressor Styles Chilled Water Pumping Systems
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationNew High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 New High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration
More informationFull and Partial Load Performances of RAC and CAC Heat Pump using R-32
Paper O.1.2.4-1 - Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Sungjin In, Graduate student, Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Keumnam Cho, Professor,
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationHoneywell Refrigerants. Retrofit Guidelines. R-404A/R-507A to: R-448A Solstice N40
Honeywell Refrigerants Retrofit Guidelines R-404A/R-507A to: R-448A Solstice N40 Table of Contents Introduction... 1 Solstice Refrigerants... 1 R-448A is not a Drop-in Replacement... 1 Retrofit Procedures...
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationDEEPAK PALIWAL, S.P.S.RAJPUT
International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,
More informationPERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS
Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK
More informationASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER
University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou
More informationPublication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration
More informationThe Changing State of Refrigerants. Gary Parker Refrigerants Product Manager
The Changing State of Refrigerants Gary Parker Refrigerants Product Manager The Changing State of Refrigerants Acronyms you may want to know CARB California Air Resources Board GWP Global Warming Potential
More informationSolstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units
Low- and MediumTemperature Refrigeration Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units Solstice 452A (R-452A) Characteristics Solstice 452A (R-452A) is
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor(SJIF): 3.134 e-issn(o): 2348-4470 p-issn(p): 2348-6406 International Journal of Advance Engineering and Research Development Volume 02,Issue 06, JUNE -2015 COMPARATIVE
More informationVolume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation
Thermodynamic Comparison Using HFO-1234yf and HFO-1234ze in the Refrigeration s and in Applications R. S. Mishra Department of Mechanical Engineering, Delhi Technological University, Delhi, India Article
More information*Corresponding author;
PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU
More informationEvaluation of HCFC Alternative Refrigerants
Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in
More informationSystem Design, Commissioning, Operation
PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares
More information