DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS

Size: px
Start display at page:

Download "DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS"

Transcription

1 Date : 09/09/2013 revised 26/09/2013 Auteur : MMT Destinataires pour action : UNICLIMA Document de travail DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS The document exclusively includes technical comments on the wording of the draft regulation. 1. DRAFT ECODESIGN REGULATION 1.1. Chapter 2 Definitions 9) p6 Comfort chiller shall not be defined by a maximum outlet temperature. In case of chiller used with floor cooling, the delivery temperature is 23 C. Remove the water temperature range 10) p6 The definition of fan coil unit is not understood as it is made reference to nor an outdoor unit. It shall be specified that the fan coil unit includes a heat exchanger between water and air. The definition given in the standard EN1397 shall be used, as follows: hydronic fan-coil unit factory-made single assembly which provides one or more of the functions of forced circulation of air, heating, cooling, dehumidification and filtering of air, but which does not include the source of heating or cooling Note 1 to entry: This device includes at least a liquid-to-air heat exchanger and a fan, and may be designed for free or ducted intake air and/or for free or ducted delivery of supply air.

2 11) c) p6 The outlet temperature at standard rating conditions is 7 C and not 6 C, to be in line with EN standard and refrigeration chillers in ENTR Lot1 11) d) p6 The draft regulation does not include any requirements nor specification for process chiller with remote condenser the chiller shall always integrate the condenser Modify d) 19) p7 It shall be specified if the definition applies to comfort and/or high temperature process chillers. 2. ANNEX I 2.1. Generic definitions 8) and 9) p11 η s,h and η s,c are used while the transitional method makes reference to η s,heat and η s,cool Tables 11 to 13 make reference to η s and SEER while Table 15 makes reference to η s only Harmonisation is required. 21) p11 The definition shall be a general one as it applies to all products and is duplicated under definition 80) on page Definitions related to heat pumps. 26) p12 The definition can be simplified by not repeating partially the general definition on a heat pump in 25) air-to-air heat pump means a heat pump [which has a heat generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (evaporator) allows heat transfer from ambient air; The term ambient air is not defined. Delete it or replace it by outdoor air

3 27) p12 The definition can be simplified by not repeating partially the general definition on a heat pump under 25) water/brine-to-air heat pumps means a heat pump [which has a heat generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (condenser) allows heat transfer from water or brine; In this case the outdoor heat exchanger is the evaporator and not condenser. 29) p12 Delete in in that provides in space cooling and: 30) p12 The definition can be simplified by not repeating partially the general definition on an air conditioner in 29) air-to-air air conditioner means an air conditioner [which has a cooling generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (condenser) allows heat transfer to air; 31) p12 The definition can be simplified by not repeating partially the general definition on an air conditioner in 29) water/brine-to-air air conditioner means an air conditioner [which has a cooling generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (condenser) allows heat transfer to water or brine; 33) p13 The definition can be simplified by not repeating partially the general definition on a comfort chiller under 9) air-to-water chiller means a comfort chiller [that has a cooling generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (condenser) [of the cooling generator] allows heat

4 transfer to air, including heat transfer that is based on evaporation into this air of externally added water; 34) - p13 The definition can be simplified by not repeating partially the general definition on a comfort chiller under 9) water/brine-to-water chiller means a comfort chiller [that has a cooling generator that uses a vapour compression cycle driven by an electric motor or fuel combustion engine and] whereby the outdoor heat exchanger (condenser) [of the cooling generator] allows heat transfer to water or brine, excluding heat transfer that is based on evaporation of externally added water; The last part of the definition excluding heat transfer that is based on evaporation of externally added water shall be deleted as it does not apply to water cooled chillers. 37) p13 A condensing unit only includes part of the cooling generator as the evaporator is not included in this cooling product It is a product that requires an additional evaporator to form a cooling generator. Furthermore it is not in the scope of this draft regulation. It is used nowhere else in the draft regulation definition shall be deleted Definitions related to the calculation method 40) p13 The definition shall be given by referring to the rated heating output as it is the correct term defined in 17) page 7 and not rated capacity for heating. 41) p13 The definition shall be given by referring to the rated cooling output as it is the correct term defined in 18) page 7 and not rated capacity for cooling. 47) p14 It is preferable, in order to be consistent with the other ErP regulations, to define heating and cooling season for the different climates

5 Proposal: heating/cooling season means a set of operating conditions for average, colder and warmer climate conditions, describing per bin the combination of outdoor temperatures and the number of hours these temperatures occur per season; 54) p14 QC and HCE to be replaced by Q C and H CE respectively. 60) and 61) p15 SEERon and SCOPon shall be defined as weighted average EER and COP. same definition as in regulation n 813/2013 for lot1 for the cooling season shall be replaced by for the designated cooling season 62) p15 The supplementary capacity for heating is defined by the symbol sup(tj) and the symbol P sup shall be then deleted. Reference to the temperature bin Tj is necessary Proposal: supplementary capacity for heating (sup(tj)) means the rated heat output [Psup] of a supplementary heater that supplements the declared capacity for heating to meet the part load for heating in case the declared capacity for heating is less than the part load for heating for the bin temperature Tj, expressed in kw; 66) p15 The definition shall be corrected to apply to chillers as follows: declared capacity for cooling (Pdc(Tj)) means the capacity of the vapour compression cycle of the air conditioner or chiller, pertaining to an outdoor temperature Tj and indoor air or water/brine temperature (Tin), as declared by the manufacturer, expressed in kw; 67) p15 and 113) p19 The definition shall be identical to that in regulation 206/2012, i.e. as follows: capacity control means the ability of the unit to change its capacity by changing the volumetric flow rate. Units are to be indicated as fixed if the unit can not change its volumetric flow rate, 'staged' if the volumetric flow rate is changed or varied in series of not

6 more than two steps, or 'variable' if the volumetric flow rate is changed or varied in series of three or more steps; The definition in the draft regulation for ENER Lot1 products shall also be revised to be consistent with the other regulations. The definition shall be a general one as it applies to all products and is duplicated. 68) and 69) p15 Both definitions shall used the corrected terms; rated heating output and rated cooling output 76) p16 The regulation is dealing with products that provide either air or water cooling. For units that provide air heating or air cooling, the degradation coefficient has a default value of 0.25 (definition of Cd in EN 14825) For units that provide water cooling, the degradation coefficient has a default value of 0.9 (definition of Cc in EN 14825) In addition, the degradation coefficient in cooling mode and in heating mode shall be differentiated by the symbols: Cdh, Cdc as in regulation n 206/2012 and as used in the Tables of Annex II Definitions related to high temperature process chillers 95) p18 Brine-cooled high temperature process chillers seem not to be in the scope of the draft regulation? 105) and 106) p18 The adjective ambient is generally used to described air temperature. Here the term ambient temperature is also used to describe the water temperature for water-cooled process chillers. cannot we use the term heat source temperature? 112) p18 The degradation coefficient shall be named Cdc and not Cc for consistency with other regulations.

7 3. ANNEX II 6) a) vi) p23 It is mentioned that for fan coil units, the information shall be measured in accordance with Annex III. However Annex III does not prescribe any procedure for fan coil units. Table 11 p26 o Indication of NOx emissions shall be removed. o Indication of combination heater : Yes/no shall be removed Table 12 p27 o Indication of combination heater : Yes/no shall be removed o Delete For air-to-water units: before the indication of the outdoor rated air flow rate as the Table is dealing with air-to-air conditioners. o The default degradation coefficient shall be Cdc=0.25 Table 13 p28 o Indication of combination heater : Yes/no shall be removed o The default degradation coefficient shall be Cdc=0.25 Table 14 p29 o Sensible and latent cooling outputs are not defined need for definitions of latent cooling output and sensible cooling output o The same symbol, P rated is used for the two outputs declaration identify P rated,sens and P rated, latent for example. o The temperature conditions, fan speed settings, for which information about cooling outputs and electrical consumption is required are not specified in the draft regulation, or the conditions for measurement of sound power level. Table 15 p30 and p31 o Replace air conditioner by heat pump 2 occurrences in the table o Replace air-to-water by air-to-air 4 occurrences in the table o Replace water/brine-to-water by water/brine-to-air o Indication of NOx emissions shall be removed. o Indication of combination heater : Yes/no shall be removed and delete information required fro combination heater

8 o Delete the information about WTOL which does not apply to water/brine-to-air heat pumps o The default degradation coefficient shall be Cdc=0.25 Table 16 p32 o The information required about refrigerant fluid(s) is not understood as the energy efficiency requirements of high temperature process chillers are not related to GWP of the refrigerant. o On the contrary the information about the refrigerant(s) to be used for other products shall be indicated in Tables 11 to 15 as the energy efficiency requirements are dependent on GWP values. o The operating temperature (t)shall be indicated ; however this temperature is not defined nor found somewhere else in the draft regulation o Harmonisation of the symbol for the degradation factor is needed o Definition 113) on page 19 does not define staged capacity control 4. ANNEX III There is no standard rating conditions for fan coil units 2) - e) and f) p33 Not understood 4) - a) p33 o The wet bulb temperature (19 C) associated with the dry bulb temperature of 27 C shall be indicated. o Chillers are not provided any cooled air, a water temperature of 7 C shall be indicated o Reference to point 5 is wrong and not understood. 4) - b) p33 water/brine cooled comfort chillers to be added 4) - c) iv) p34 H HE to be replaced by H CE Reference to Table 6 shall be Table 29 4) - c) v) (2) p34

9 standby consumption is missing. 5) c) iv) p34 HHE to be replaced by H HE 5) - c) v) (2) p35 standby consumption is missing. 5) p35 o This point shall be numbered 6) and not 5) o The adjective ambient is generally used to described air temperature. Here the term reference ambient temperature is also used to describe the water temperature for water-cooled process chillers delete ambient in reference ambient temperature see comment on p18 105) and 106) Table 18 p36 Are water-to-brine chillers in the scope of the regulation? If not, delete the corresponding test conditions given in Table 18. If yes, the efficiency requirements shall be differentiate from those of water-to-water chillers because of the less efficient heat exchange when using brine. If water to-brine chillers are in the scope, then air-to-brine chillers shall also be included (which seems to be the case with Table 19) and again efficiency requirements shall be different from those stated for air-to-water chillers. Why is the * only referring to one test condition of the Table? It can be helpful to refer to regulation n 813/2013 for finding the standard rating conditions in heating mode from which the flow rate shall be obtained. Table 19 p37 The footnote * is not refer to in the Table 19. Table 20 p37 The same footnote * or a shall be used. Explanation is required for this setting of the flow rate in cooling mode. In Tables 18 and 19 for chillers, the reference flow rate is in heating mode.

10 Table 21 p37 As the table is indicating standard rating conditions, all references to part load ratio shall be deleted the table can be simplified and have then the same format as the above tables. Reference to T A and T D are not understood. Table 22 p38 o Test conditions shall be indicated as A/B/C or D in order to better understand the use of this Table 22 with Table 27. o For accuracy in the calculations, part load ratio shall be also expressed with the equation, as follows : (Tj-16)/(Tref-16) o Water-to-air air conditioners can used dry coolers as outdoor heat exchanger with other temperature levels than the ones already indicated complete the table with additional test conditions according to EN o Water-to-water chillers can used dry coolers as outdoor heat exchanger with other temperature levels than the ones already indicated complete the table with additional test conditions according to EN o Footnote * is not understood. o Footnote ** shall be deleted and reference to EN test method made as this is part of the test procedure and is under improvement in the standard revision Table 25 p40 Reference design conditions are provided for warmer and colder climates for heating but these climates are not described and not used in the rest of the draft regulation. Only average climate is described in Table 26. The Table shall also identifies warmer and colder cooling seasons as they are used in Table 27. Table 26 p41 The average climate for high temperature process chillers (HTPC) has not the same bin temperatures as the average climate for comfort chillers, heat pumps and AC units in terms of range of temperature. Average climate (for both heating and cooling) includes bin temperatures from -10 C to +35 C, while the average climate of HTPC is extended down to -19 C and up to 38 C. It is not either consistent with colder climate temperature range Harmonisation is required. Table 29 p44

11 It shall be specified that Table 29 applies to air conditioners, heat pumps and comfort chillers. Set of hours to be used for reversed cycle units, i.e. units that can operate in cooling mode and heating mode shall be specified. 5. WORKING DOCUMENT ON TRANSITIONAL METHODS No mention is made to any European standard for fan coil units. EN 1397 shall be indicated. references p8 Degradation coefficient is named Cc while in the draft regulation, the symbol Cd or Cc or even Cdc are used indifferently. Harmonisation is required. 3.1 b) - p12 SCOP and SPER heat are not seasonal energy efficiency in active mode delete in active mode p14 The use of Cc shall again be harmonised with the definitions and symbols.

ANNEXES. to the. COMMISSION REGULATION (EU) No /..

ANNEXES. to the. COMMISSION REGULATION (EU) No /.. EUROPEAN COMMISSION Brussels, 30.11.2016 C(2016) 7769 final ANNEXES 1 to 5 ANNEXES to the COMMISSION REGULATION (EU) No /.. implementing Directive 2009/125/EC of the European Parliament and of the Council

More information

The products covered by the Regulation can be classified as follows:

The products covered by the Regulation can be classified as follows: Table of Contents 1. Purpose of the guidelines and disclaimer... 3 1.1. The Regulation... 3 2. Scope... 3 3. Product environmental impacts... 4 4. State of play of legislation... 4 4.1. History of the

More information

Draft COMMUNICATION FROM THE COMMISSION

Draft COMMUNICATION FROM THE COMMISSION EUROPEAN COMMISSION Brussels, XXX [ ](2012) XXX draft Draft COMMUNICATION FROM THE COMMISSION in the framework of the implementation of Commission Regulation (EU) No / implementing Directive 2009/125/EC

More information

(Non-legislative acts) REGULATIONS

(Non-legislative acts) REGULATIONS 20.12.2016 L 346/1 II (Non-legislative acts) REGULATIONS COMMISSION REGULATION (EU) 2016/2281 of 30 November 2016 implementing Directive 2009/125/EC of the European Parliament and of the Council establishing

More information

Delegated Regulation (EU) 626/2011 of 4 May 2011 supplementing Directive 2010/30/EU with regard to energy labelling of air conditioners

Delegated Regulation (EU) 626/2011 of 4 May 2011 supplementing Directive 2010/30/EU with regard to energy labelling of air conditioners Delegated Regulation (EU) 626/2011 of 4 May 2011 supplementing Directive 2010/30/EU with regard to energy labelling of air conditioners Incorporated and adapted by Ministerial Council Decision 2011/03/MC-EnC

More information

COMMISSION REGULATION (EU)

COMMISSION REGULATION (EU) 10.3.2012 Official Journal of the European Union L 72/7 COMMISSION REGULATION (EU) No 206/2012 of 6 March 2012 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard

More information

Official Journal of the European Union L 239/1. (Non-legislative acts) REGULATIONS

Official Journal of the European Union L 239/1. (Non-legislative acts) REGULATIONS 6.9.2013 Official Journal of the European Union L 239/1 II (Non-legislative acts) REGULATIONS COMMISSION DELEGATED REGULATION (EU) No 811/2013 of 18 February 2013 supplementing Directive 2010/30/EU of

More information

PART I ENERGY EFFICIENCY ACQUIS / DELEGATED REGULATION (EU) 811/2013

PART I ENERGY EFFICIENCY ACQUIS / DELEGATED REGULATION (EU) 811/2013 Delegated Regulation (EU) 811/2013 of 18 February 2013 supplementing Directive 2010/30/EU with regard to the energy labelling of space heaters, combination heaters, packages of space heater, temperature

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2013) XXX draft COMMISSION REGULATION (EU) No /.. of XXX implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2014) XXX draft COMMISSION REGULATION (EU) No /.. of XXX implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2013) XXX draft COMMISSION REGULATION (EU) No /.. of XXX implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign

More information

OJ L 239, , p. 1. OJ L 239, , p. 83, OJ L 239, , p. 136.

OJ L 239, , p. 1. OJ L 239, , p. 83, OJ L 239, , p. 136. 2 This document reflects the opinion of the European Commission and does not provide a legally binding interpretation of the regulations. Only the European Court of Law can provide a legally binding interpretation

More information

Ecodesign for Energy Related products. State of play ASERCOM/EPEE SYMPOSIUM E. Baert-

Ecodesign for Energy Related products. State of play ASERCOM/EPEE SYMPOSIUM E. Baert- Ecodesign for Energy Related products State of play ASERCOM/EPEE SYMPOSIUM 2012 -E. Baert- What is is Ecodesign Requirements for Energy Related Products? (Referred to to as as ERP, or or Ecodesign,, formerly

More information

2. SCOPE. OJ L 239, , p. 1. OJ L 239, , p. 83, OJ L 239, , p OJ L 239, , p. 162.

2. SCOPE. OJ L 239, , p. 1. OJ L 239, , p. 83, OJ L 239, , p OJ L 239, , p. 162. 2 Table of Contents 1. Purpose of the guidelines and disclaimer... 4 1.1. The Regulations... 4 2. Scope... 4 2.1. Space Heaters and Combination Heaters... 5 2.2. Water Heaters... 5 3. Product environmental

More information

COMMISSION REGULATION (EU) No /.. of

COMMISSION REGULATION (EU) No /.. of EUROPEAN COMMISSION Brussels, 30.11.2016 C(2016) 7769 final COMMISSION REGULATION (EU) No /.. of 30.11.2016 implementing Directive 2009/125/EC of the European Parliament and of the Council establishing

More information

The test items passed the test specification(s).

The test items passed the test specification(s). Report NO.: NTRE20170442 Test Report No.: NTRE20170442 age 1 of 17 Applicant Name: Test item: Gree Electric Appliances Inc. of Zhuhai West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070 Split Air

More information

Official Journal of the European Union

Official Journal of the European Union 8.7.2015 L 177/19 COMMISSION REGULATION (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional

More information

ErP. ErP READY. The Eco-Design Directive ErP for refrigerator systems and heat pumps. READY

ErP. ErP READY. The Eco-Design Directive ErP for refrigerator systems and heat pumps. READY ErP READY The Eco-Design Directive ErP for refrigerator systems and heat pumps. The EU-Regulation 2281/2016/EU defines the new requirements for refrigerator systems and heat pumps and focuses on the new

More information

Council of the European Union Brussels, 14 July 2014 (OR. en)

Council of the European Union Brussels, 14 July 2014 (OR. en) Council of the European Union Brussels, 14 July 2014 (OR. en) 11898/14 ENER 354 ENV 676 COVER NOTE From: European Commission date of receipt: 11 July 2014 To: No. Cion doc.: D033491/02 Subject: General

More information

103776HV1241 NOVELAN LAV 8-HV kw kw db 50 db

103776HV1241 NOVELAN LAV 8-HV kw kw db 50 db NOVELAN 44 50 103776HV1241 5 7 6 7 6 4 NOVELAN 103776HV1241 package (heat pumps and combination heater with heat pump) Seasonal space heating energy efficiency of heat pump (ηs) of the heat pump (Prated

More information

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance DRAFT INTERNATIONAL STANDARD ISO/DIS 15042 ISO/TC 86/SC 6 Voting begins on: 2005-07-11 Secretariat: ANSI Voting terminates on: 2005-12-12 INTERNATIONAL ORGANIZATION FOR STANDARDIZATION МЕЖДУНАРОДНАЯ ОРГАНИЗАЦИЯ

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL DTW_1SP005E_01 DESIGN & TECHNICAL MANUAL Comfort series ( Single phase type ) INNOVATIVE SOLUTION OF DOMESTIC HEATING Air to Water Split type 111OUTDOOR UNIT CONTENTS SINGLE PHASE TYPE : WO A060LFCA, WO

More information

White paper: New Ecodesign rules and energy labelling for space and water heaters

White paper: New Ecodesign rules and energy labelling for space and water heaters White paper: New Ecodesign rules and energy labelling for space and water heaters White paper: New Ecodesign rules and energy labelling for space and water heaters The Ecodesign Regulation is one of the

More information

Template for comments Date: Document: Eurovent Association Comments on

Template for comments Date: Document: Eurovent Association Comments on TABLE FOR COMMENTS Name of submitr: Francesco Scuderi Affiliad organization of the submitr (if any): Eurovent Association Contact email of submitr: francesco.scuderi@eurovent.eu 1 NA NA There is not any

More information

Heating Nom. dba 50 (5) 50 (5) 50 (5) Cooling Nom. dba 50 (5) 50 (5) 50 (5) Anti freeze heater (optional) W Expansion vessel Volume l 6 6 6

Heating Nom. dba 50 (5) 50 (5) 50 (5) Cooling Nom. dba 50 (5) 50 (5) 50 (5) Anti freeze heater (optional) W Expansion vessel Volume l 6 6 6 EWYQ005ADVP EWYQ006ADVP EWYQ007ADVP Sound pressure level Heating Nom. dba 50 (5) 50 (5) 50 (5) Cooling Nom. dba 50 (5) 50 (5) 50 (5) Hydraulic components Anti freeze heater (optional) W 75 75 75 Expansion

More information

Model and/or type reference... : COPMAX GS 15 JORDVARMEPUMPE Rating(s)... : V 3N~; 50Hz; other rating refer to page 6

Model and/or type reference... : COPMAX GS 15 JORDVARMEPUMPE Rating(s)... : V 3N~; 50Hz; other rating refer to page 6 age 2 of 42 Test sample.....: Type of test object... : Trademark... : Heat ump Heat ump Hiseer Model and/or type reference... : COMAX GS 15 JORDVARMEUME Rating(s)... : 380-415 V 3N~; 50Hz; other rating

More information

Applications of Thermodynamics: Heat Pumps and Refrigerators

Applications of Thermodynamics: Heat Pumps and Refrigerators Applications of Thermodynamics: Heat Pumps and Refrigerators Bởi: OpenStaxCollege Almost every home contains a refrigerator. Most people don t realize they are also sharing their homes with a heat pump.

More information

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE: ABOUT THE i-chiller RANGE The fully packaged, EcoDesign compliant, air-cooled i-chiller range is designed specifically for reliable and efficient process cooling. The unique evaporator is immersed within

More information

AS10S-DPNHE. Rating(s)... : V 3N~; 50Hz; other rating refer to page 6. Guangzhou Hiseer Air conditioning Co,. LTD

AS10S-DPNHE. Rating(s)... : V 3N~; 50Hz; other rating refer to page 6. Guangzhou Hiseer Air conditioning Co,. LTD age 2 of 42 Test sample.....: Type of test object... : Trademark... : Model and/or type reference... : Heat ump Heat ump Hiseer AS10S-DNHE Rating(s)... : 380-415 V 3N~; 50Hz; other rating refer to page

More information

Page 2 of 42 Test report no. HS Rev.00

Page 2 of 42 Test report no. HS Rev.00 age 2 of 42 Test sample.....: Type of test object... : Trademark... : Heat ump Heat ump Hiseer Model and/or type reference... : AS14S-DNHE Rating(s)... : 380-415 V 3N~; 50Hz; other rating refer to page

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 00 m /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

Smart Rules - Smart Application. Introduction to Ecodesign & Energy Labelling

Smart Rules - Smart Application. Introduction to Ecodesign & Energy Labelling Smart Rules - Smart Application Introduction to Ecodesign & Energy Labelling Ecodesign Directive 2009/125/EC Evaluation resulted in no changes to the Directive Work Plan Study 2015-2017 Work Plan available

More information

Energy Efficiency Requirements for Air Conditioners, Chillers and Close Control Units

Energy Efficiency Requirements for Air Conditioners, Chillers and Close Control Units Energy Efficiency Requirements for Air Conditioners, Chillers and Close Control Units Simone Tiele, Assistant Director Appliance Energy Efficiency Section DEWHA AIRAH 21 April 2009 Air Conditioners Air

More information

AHRI Certification Program Scopes - COOLING

AHRI Certification Program Scopes - COOLING Air-to-Air Energy Recovery Ventilators (AHRI Std. 1060) Automatic Commercial Ice-Cube Machines and Ice Storage Bins (AHRI Stds. 810 & 820) Central Station Air-Handling Units (AHRI Std. 430) Commercial

More information

This FAQ list is intended to be used only for facilitating the implementation of Regulation (EU) 2015/1095 and Regulation (EU) 2015/1094.

This FAQ list is intended to be used only for facilitating the implementation of Regulation (EU) 2015/1095 and Regulation (EU) 2015/1094. This FAQ list is intended to be used only for facilitating the implementation of Regulation (EU) 2015/1095 and Regulation (EU) 2015/1094. They are not intended to replace the regulations nor to provide

More information

GEOTHERMAL DESIGN GUIDE

GEOTHERMAL DESIGN GUIDE GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX D028689/03 [ ](2013) XXX draft COMMISSION REGULATION (EU) No /.. of XXX implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to

More information

ENTE CERTIFICAZIONE MACCHINE

ENTE CERTIFICAZIONE MACCHINE ENTE CERTIFICAZIONE MACCHINE Organismo di Certificazione e di Ispezione - unto GS Ente di Formazione n. 6737 - Laboratorio di rova ISO/IEC 17025 Test Report EN 14825:2013 COMMISSION REGULATION (EU) No

More information

EHPA Testing Regulation

EHPA Testing Regulation EHPA Testing Regulation Testing of Heat Pumps for Domestic Hot Water Production Terms, Test Conditions and Test Method based on EN 16147 Additional requirements for granting the international quality label

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING AND TESTING REQUIREMENTS FOR LOW CAPACITY WINDOW TYPE AND SINGLE-SPLIT

AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING AND TESTING REQUIREMENTS FOR LOW CAPACITY WINDOW TYPE AND SINGLE-SPLIT SAUDI ARABIAN STANDARD SASO 2663/2017 والجودة الھيئة السعودية للمواصفات والمقاييس Saudi Standards, Metrology and Quality Org (SASO) SASO 2663:2017 (Draft) AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2013) XXX draft COMMISSION DELEGATED REGULATION (EU) No /.. of XXX supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to

More information

WPL 17 IKCS classic 55 C 35 C A ++ A ++ A ++ A + A B C D E F G kw kw. 50 db. 44 db

WPL 17 IKCS classic 55 C 35 C A ++ A ++ A ++ A + A B C D E F G kw kw. 50 db. 44 db 55 C 35 C A A A B C D E F G A A 50 db 13 7 4 kw 13 9 5 kw 44 db 2015 811/2013 Product datasheet: Room heater to regulation (EU) no. 811/2013 Energy efficiency class for central heating in moderate climates

More information

WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW)

WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW) WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW) Table of Contents Explanatory Notes... 2 Form of the implementing measures... 2 Scope... 3 Market

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

(Text with EEA relevance)

(Text with EEA relevance) L 193/76 21.7.2015 COMMISSION REGULATION (EU) 2015/1188 of 28 April 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for local

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 16494 First edition 2014-11-01 Heat recovery ventilators and energy recovery ventilators Method of test for performance Ventilateurs-récupérateurs de chaleur et ventilateurs-récupérateurs

More information

Compendium DES July 2016, CARN

Compendium DES July 2016, CARN Compendium DES July 2016, CARN 1 Contents Contents... 2 1. Energy balance... 4 Using Energy Balance for analyzing energy systems... 4 Energy Balance definition... 4 Steady state, steady flow... 4 Methodology...

More information

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2012) XXX draft COMMISSION DELEGATED REGULATION (EU) No /.. of XXX supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to

More information

FACT SHEET 9 Large Air-Conditioning (air-to-air)

FACT SHEET 9 Large Air-Conditioning (air-to-air) FACT SHEET 9 Large Air-Conditioning (air-to-air) UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material for on HFC HFC Workshop, management: 205 technical issues Bangkok, 20 and 2 April

More information

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - TF N 530 Rev.2 2012-04-13 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 Drafting

More information

Air conditioning products regulations based on Ecodesign directive (> 12 kw)

Air conditioning products regulations based on Ecodesign directive (> 12 kw) Air conditioning products regulations based on Ecodesign directive (> 12 kw) Philippe Rivière, CEP, Mines ParisTech / Armines on Buildings Related EU Regulations and Projects 27 Oct 2011, Bruxelles Ecodesign

More information

A Step by Step Guide to Energy Labelling of Gaseous Fuel Local Space Heaters (Part 1)

A Step by Step Guide to Energy Labelling of Gaseous Fuel Local Space Heaters (Part 1) A Step by Step Guide to Energy Labelling of Gaseous Fuel Local Space Heaters (Part 1) What do the new regulations require? The Energy Related Products (ErP) Regulations require that: From the 1 st January

More information

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES Poster P.6.13-1 - EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES Markus Lindahl, MSc, SP Technical Research Institute of Technology, Energy Technology, Box 857, 501 15 Borås, Sweden; Caroline,

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

WP2 European Product Analysis, Task 2.1 Determining energy efficiency criteria, D 2.1 Periodic Criteria Papers (first set)

WP2 European Product Analysis, Task 2.1 Determining energy efficiency criteria, D 2.1 Periodic Criteria Papers (first set) Topten ACT Criteria Paper Air conditioners 14.Juli 2015 Anette Michel Bush Energie GmbH anette.michel@topten.eu Topten ACT aims at transforming the European market of energy-using products towards higher

More information

ANNEXES TO WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW)

ANNEXES TO WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW) ANNEXES TO WORKING DOCUMENT ON POSSIBLE ECODESIGN AND ENERGY LABELLING REQUIREMENTS FOR SOLID FUEL BOILERS (< 500 KW) Table of Contents Annex I Definitions applicable for the purposes of Annex II to IV...

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,

More information

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

HVAC product labelling and certification

HVAC product labelling and certification 1/ 2011 HVAC product labelling and certification Sylvain COURTEY s.courtey@eurovent-certification.com Eurovent Certification Company (ECC) www.eurovent-certification.com Summary 2/ 2011 1. Labelling directives

More information

FACT SHEET 9 Large Air-Conditioning (air-to-air)

FACT SHEET 9 Large Air-Conditioning (air-to-air) UNEP Ozone Secretariat UNEP Ozone Secretariat Background Material on HFC Management Fact Sheets on HFCs and Low GWP Alternatives October 205 FACT SHEET 9 Large Air-Conditioning (air-to-air). Description

More information

Nicolas Doré Service Bâtiment ADEME Tel : Mail : European normative and regulative context for Gas Heat Pumps

Nicolas Doré Service Bâtiment ADEME Tel : Mail : European normative and regulative context for Gas Heat Pumps Nicolas Doré Service Bâtiment ADEME Tel : 04 93 95 72 62 Mail : nicolas.dore@ademe.fr European normative and regulative context for Gas Heat Pumps Contents 1. About ADEME 2. GHP in the Energy Related Products

More information

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel. DEHUMIDIFICATION 9 CDS 80 FUNCTION The CDS 80 works in accordance with the condensation principle. A fan draws the humid air into the dehumidifier and through an evaporator coil. When passing through the

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

COMMISSION DELEGATED REGULATION (EU) No /.. of

COMMISSION DELEGATED REGULATION (EU) No /.. of EUROPEAN COMMISSION Brussels, 18.2.2013 C(2013) 818 final Part 1/6 COMMISSION DELEGATED REGULATION (EU) No /.. of 18.2.2013 supplementing Directive 2010/30/EU of the European Parliament and of the Council

More information

Chilled Water system

Chilled Water system Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller. The usual package consists of

More information

AIR CONDITIONER PERFORMANCE RATING

AIR CONDITIONER PERFORMANCE RATING HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER

More information

High efficiency air to water Heat pumps LZT series

High efficiency air to water Heat pumps LZT series High efficiency air to water Heat pumps LZT series 01/2009 THE COMPANY HIDROS was born in 1993 as a trading company involved in the market of dehumidification and humidification of the air. Quite soon

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Room air conditioners: Recommendations for policy design May 2011

Room air conditioners: Recommendations for policy design May 2011 Room air conditioners: Recommendations for policy design May 2011 1. Summary Split variable speed (inverter) air conditioners are today s best available technology (BAT). The most efficient models on the

More information

Technical Data Sheet. Brine/Water Heat Pumps 8 12kW - single phase 230V. Heliotherm Basic Comfort. Basic Comfort Advantages

Technical Data Sheet. Brine/Water Heat Pumps 8 12kW - single phase 230V. Heliotherm Basic Comfort. Basic Comfort Advantages Technical Data Sheet Air Ground Water Brine Cooling PV-ready Modulation Brine/Water Heat Pumps 8 12kW - single phase 230V Heliotherm Basic Comfort A fully modulating Brine/Water heat pump with leading-edge

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Performance Rating of Computer and Data Processing Room Air Conditioners

Performance Rating of Computer and Data Processing Room Air Conditioners ANSI/AHRI Standard 1360 (I-P) with Addendum 1 2013 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners Approved by ANSI on November 8, 2013 WITH ADDENDUM 1, PERFORMANCE

More information

WPL 23 E 55 C 35 C A ++ A + A B C D E F G A + A kw kw. 58 db. 65 db

WPL 23 E 55 C 35 C A ++ A + A B C D E F G A + A kw kw. 58 db. 65 db 55 C 35 C A A A B C D E F G A A 58 db 20 18 16 kw 18 17 16 kw 65 db 2015 811/2013 Energy efficiency class for central heating in moderate climates for medium Energy efficiency class for central heating

More information

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING MODULE 6 HUMIDIFICATION AND AIR CONDITIONING LECTURE NO. 3 6.3 Humidification and dehumidification operations and design calculations Humidification operations: In this operation, water transfers from

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative A U.S. Environmental Protection Agency survey released in 2007 concluded that IT data centers consumed 61 billion kw of electricity at a total cost of $4.5 billion in 2006. As energy costs continue to

More information

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX

COMMISSION DELEGATED REGULATION (EU) No /.. of XXX COMMISSION DELEGATED REGULATION (EU) No /.. of XXX supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to the energy labelling of water heaters, hot water storage

More information

Chapter 10. Refrigeration and Heat Pump Systems

Chapter 10. Refrigeration and Heat Pump Systems Chapter 10 Refrigeration and Heat Pump Systems Learning Outcomes Demonstrate understanding of basic vaporcompression refrigeration and heat pump systems. Develop and analyze thermodynamic models of vapor-compression

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Set No. 1 IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec - 2014 REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI Standard 1230 with Addendum 1 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI STANDARD 1230-2014 WITH ADDENDUM 1,

More information

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems 2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path

More information

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat

More information

Report Reference No...:

Report Reference No...: TEST REORT COMMISSION REGULATION (EU) No 206/2012 of 6 March 2012 implementing Directive 2009/125/EC of the European arliament and of the Council with regard to ecodesign requirements for air conditioners

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

WPL C 35 C A ++ A + A B C D E F G A + A kw kw. 69 db

WPL C 35 C A ++ A + A B C D E F G A + A kw kw. 69 db 55 C 35 C A B C D E F G 33 33 32 kw 32 31 30 kw 69 db 2015 811/2013 Product datasheet: Room heater to regulation (EU) no. 811/2013 Energy efficiency class for central heating in moderate climates for medium

More information

COMMISSION REGULATION (EU) / of

COMMISSION REGULATION (EU) / of EUROPEAN COMMISSION Brussels, 30.11.2016 C(2016) 7767 final COMMISSION REGULATION (EU) / of 30.11.2016 amending Regulations (EC) No 1275/2008, (EC) No 107/2009, (EC) No 278/2009, (EC) No 640/2009, (EC)

More information

Prices and technical information for Applied Systems. Pricelist Applied Systems

Prices and technical information for Applied Systems. Pricelist Applied Systems Prices and technical information for Applied Systems Pricelist 2018-2019 Applied Systems NEW NEW NEW NEW NEW NEW NEW NEW NEW NEW Table of contents Type Refrigerant Compressor Material Capacity Page Key

More information

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06) C 416/16 EN Official Journal of the European Union 11.11.2016 Commission communication in the framework of the implementation of Commission Regulation (EU) No 1253/2014 implementing Directive 2009/125/EC

More information

COMMISSION DELEGATED REGULATION (EU) No /.. of

COMMISSION DELEGATED REGULATION (EU) No /.. of EUROPEAN COMMISSION Brussels, 24.4.2015 C(2015) 2638 final COMMISSION DELEGATED REGULATION (EU) No /.. of 24.4.2015 supplementing Directive 2010/30/EU of the European Parliament and of the Council with

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

Teknik Data NIBE F2120 8, 12, 16, 20

Teknik Data NIBE F2120 8, 12, 16, 20 Teknik Data NIBE F21, 12, 1, Havadan Suya Isı Pompası LEK F21 F21 Teknik Data Ebatlar F21 Ø2 30 0 0 0 1 10 F2112, 1, Ø2 10 1 0 0 0 1 12 1 LEK Ses basıncı seviyeleri F21 is usually placed next to a house

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS - 1 - COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS W. Mittelbach, Managing Director, SorTech AG, Weinbergweg 23, 06120 Halle, Germany T. Büttner, Head of R&D / production, SorTech AG,

More information

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by

More information

Heat pump & cooling unit in one

Heat pump & cooling unit in one + + Heat pump & cooling unit in one The reversible ThermoCooler HP heat pump can be integrated in our Envistar Flex units. All parts of the cooling/heating pump are incorporated in a module section, which

More information

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais INTERNATIONAL STANDARD ISO 7183 Second edition 2007-12-15 Compressed-air dryers Specifications and testing Sécheurs à air comprimé Spécifications et essais Reference number ISO 7183:2007(E) ISO 2007 PDF

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information