1 Johnson Controls Denmark ApS Christian X's Vej Højbjerg Denmark Phone Fax CVR No Technical Information 2015/01 14 January 2015 A newsletter from Sabroe Factory Quality requirements for ammonia used in refrigeration systems IMPORTANT: When working with refrigerants, ALWAYS observe safety precautions as stated in service manuals. Scope This Technical Information deals with ammonia as a refrigerant. Requirements for: - halogenated refrigerants (HFC, i.e. R134a) - hydrocarbon refrigerants (HCs, i.e. R290 and R-600a) - CO2 (R744) must comply with the AHRI standard. For CO2, see also Sabroe Technical Information 2004/05. Background Recent experience shows that it is crucial to ensure proper quality of refrigerants when installing and servicing refrigeration systems. This is especially important when it comes to ammonia as this is used for many different purposes and is therefore available in many different grades. Insufficient quality of ammonia when used as a refrigerant may lead to: Reduced performance of a system, approximately 2% reduction per 1% water content Increased energy consumption, approximately 1% increase per 1% water content Corrosion inside the system Breakdown of lubrication oil Sludge formation blocking small pipe runs Damage of compressor bearings and other parts Increased oil carry-over due to fouling of coalescers Page 1 of 3
2 Johnson Controls Denmark ApS Christian X's Vej Højbjerg Denmark Phone Fax CVR No Quality requirements It is necessary to distinguish between the requirements in different situations and for various system types: 1. New ammonia to be charged 2. Assessment of ammonia sample taken out from an installation a. Systems with oil return to compressor, e.g. chillers b. Systems without oil return, typically distributed ammonia installations Refrigerant Ammonia (R717) Quality requirements for refrigeration ammonia Samples from installation Max. contamination Systems with Systems without new refrigerant oil return oil return Contaminant (1) (2.a) (2.b) Purity 99.98% Water <200 ppm <2000 ppm <5000 ppm Oil <5 ppm Non-condensable <0.2 ml/g Charging new ammonia For ammonia there is no generally accepted standard covering it as a refrigerant, R717. Requirements in this specification are based on ASHRAE Ammonia Data Book, IIAR bulletin no. 108 as well as various data sheets from ammonia manufacturers. Use only a suitable grade of ammonia from acknowledged vendors Check that the refrigerant certificate meets the above requirements for refrigeration grade ammonia Perform evacuation and charging according to instructions given in manuals For chillers, make an analysis of ammonia taken from the evaporator/pump separator according to the commissioning checklist. An ammonia sample kit is available from AfterMarket Solutions, part number See appendix. It should be noted that the widely available commercial/agricultural ammonia grade should NEVER be used in ammonia refrigeration systems as the water content is usually very high. The purchase specification for refrigeration ammonia should include: Refrigerant grade ammonia water content maximum 200 ppm. Certificate with water content stated must be delivered together with the ammonia. The ammonia sample referred to in the certificate shall be taken from the liquid phase of the ammonia Chillers Factory built chillers are carefully evacuated to remove any ammonia and water before shipment. However, during transportation and installation humid air may enter the system. To remove this, a best practice at the end of commissioning is to perform a pump down of the evaporator to evacuate the ammonia. Oil and water will then remain in the evaporator and should be drained off the evaporator. This procedure should be repeated whenever oil samples shows elevated water content. Page 2 of 3
3 Johnson Controls Denmark ApS Christian X's Vej Højbjerg Denmark Phone Fax CVR No Systems with oil return to compressor Water has a very low vapour pressure and will not evaporate at a rate proportional to ammonia. This means that water will accumulate in the evaporator or the pump separator. In order to return oil from these places to the compressor, the water content must be kept low to avoid elevated water content in the oil. For large systems, installation of a water purger is strongly recommended to keep the system dry. A water purger, type CPW-15, is available from AfterMarket Solutions. Systems without oil return to compressor Whenever major installation work has been done or ammonia is being recharged, an ammonia analysis should be performed. It is recommended to carry out an oil analysis every 6 month. If this oil sample shows a water content above the limits in our oil recommendation, a supplementary ammonia analysis should be made as well. In any case, it is recommended to carry out an ammonia analysis at least once a year. It is the obligation of the plant operator to ensure continuous quality of the refrigerant charges. In case a failure on a Sabroe product is suspected to be caused by water, oil as well as ammonia should be analysed before the equipment is put back into operation. If failure is caused by contamination of refrigerant or oil, coverage under warranty may be denied. Appendices: Ammonia water test instruction Water purger CPW-15 leaflet Erhardt Nielsen Manager, Compressor Development Technical Support and Development Direct no.: Fax no.: erhardt.nielsen@jci.com Page 3 of 3
4 19 Oct 01, Rev 1 CAF/jmd Ammonia water test Customer: Plant: Date: Order no: Supervisor: Procedure: Use only approved test tubes part no , gloves and mask must be used when draining refrigerant. The sample must be taken from the evaporator side. That is, from the separator, pump forward, or oil draining on the evaporator, after the oil has been drained. Sampling from the receiver is unsuitable, as the water content is several times higher on the evaporator side. The plant must be running in normal operation when the sample is taken. There must be no ice or condensation at the drain valve as the sample will then show too high water content. The test tube is filled with 50 ml ammonia and placed securely for evaporation to prevent unauthorised persons getting injured. No water/moisture must access the test tube during evaporation as ammonia easily absorbs moisture and makes the test misleading. Evaporation takes 3 or 4 hours and should not be accelerated by increased heat induction to the test tube, as excessive boiling of the ammonia sample will generate ammonia vapours, which will entrain part of the water content from the sample. Increase of heat induction by means of a piece of welding rod placed in the test tube is, however, possible. After drainage the ammonia colour and clarity are observed to estimate impurity and decomposition content. After evaporation the glass sides are checked for deposits. Brown deposits indicate decomposition products in the ammonia refrigerant. After evaporation the water content in ml is read and the water content determined. Water content is calculated according to the following formula: Readings of water content in ml x water density in g / cm3 x 100 % water content Sample amount in ml x ammonia density in g / cm3 Example: 0.3 ml water reading after evaporation: ml x 1.0 g / cm 50 ml x 0.65 g / cm 3 x % water. Rule-of-thumb: Readings of water content in ml x 3 = % water content
5 Water sample taken from: Before evaporation, amount: 50 ml After evaporation, amount: ml Clarity Colour Clarity Colour Clear Muddy Colourless Light yellow Yellow Light brown Brown Dark Clear Muddy Colourless Light yellow Yellow Light brown Brown Dark Result, water content = % Result under 0.5% water content is satisfactory. Result over 1.0% water content is not acceptable as it results in increased energy consumption, increased wear, possible break down, corrosion and impurities/decomposition products. Notes: YORK Refrigeration, After-Market Service
6 REMANU- FACTURING Sustain your installed base using the Industrial Compressor Service and Remanufacturing Water Purger (CPW-15) External version Consequences of water in ammonia systems Increased power consumption Reduced refrigeration capacity Lower evap pressure at the same temperature Oil is broken down and creates nitro compounds Nitro compounds can dissolve in the NH 3 and colour it Leaks due to embrittlement of O-rings and gaskets Leaks due to galvanic corrosion Wear and tear on valves and controls Sludge in the system. Avoid water in your ammonia Easy installation Self regulating Minimum maintenance No electrical installation No adjustments once installed. PUBL-7415EN Johnson Controls Denmark ApS Industrial Compressor Service & Remanufacturing Chr. X s Vej Højbjerg Denmark Phone: Fax: cg-eur-dk-ycsr@jci.com
Effective Handling of Air, Water, and Oil in Ammonia Refrigeration Systems to Conserve Energy
Sustainable Management of Refrigeration Technologies in Marine and Off-Shore Fisheries Sectors, 6-8 April 2017, Bangkok Effective Handling of Air, Water, and Oil in Ammonia Refrigeration Systems to Conserve
More informationEnergy Saving & Eco-Friendly Refrigerant
Technical Seminar Energy Saving & Eco-Friendly Refrigerant Presented By Eva Yim Business Development Director Stephen Cheung Engineering Director Date : Oct 16, 2012 Others 25% Lighting 15% Air Conditioning
More informationProviding Solutions. Simplifying Regulation. IIAR Standards. Peter Thomas, P.E., CSP Resource Compliance, Inc.
Providing Solutions. Simplifying Regulation. IIAR Standards Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Providing Solutions. Simplifying Regulation. Providing Solutions. Simplifying
More informationSpecifications for Fluorocarbon Refrigerants
AHRI Standard 700 with Addendum 0 Standard for Specifications for Fluorocarbon Refrigerants WITH ADDENDUM, Specifications for Fluorocarbon Refrigerants June 0 AHRI Standard 700-0 with Addendum, Specifications
More informationSpecifications for Fluorocarbon Refrigerants
ANSI/AHRI Standard 700 with Addenda 1 and 2 2006 Standard for Specifications for Fluorocarbon Refrigerants Approved by ANSI on 8 August 2011 WITH ADDENDUM 1, Specifications for Fluorocarbon Refrigerants
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationThe Design Flaw in HVAC
The Design Flaw in HVAC www.powertronglobal.com The Design Flaw in HVAC You may know that HVAC accounts for up to 70% of a total power bill for any building. What you may not know is there is a design
More informationInstruction Manual for Reciprocating Compressors SBO 21, 22, 41, 42, 43
Instruction Manual for Reciprocating Compressors SBO 21, 22, 41, 42, 43 28/01/2005 REV. 03 Sabroe Refrigeration A/S, Marine Division 1 Preface The aim of this instruction manual is to provide the operators
More informationlmprovin Industrial Refrigeration -!nergy Efficiency
lmprovin Industrial Refrigeration -!nergy Efficiency R efvigeration systems consume a large portion of the total energy used in food processing and food storage industries. There are a number of simple
More informationReference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.
GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant
More informationPublication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration
More informationA: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.
1/1/12 RS-45 (R434A): Q & A 1 Q: What is RS-44? 1.Q: What is RS-45 A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-45 contain? A: RS-45 is
More informationPresentation Title. Energy Efficiency for Cold Warehouse Industrial Refrigeration Systems
Presentation Title Energy Efficiency for Cold Warehouse Industrial Refrigeration Systems Presented by: Hasan S. Al-Harahsheh Regional Business Development Manager IR MEA Johnson Controls Founded 1885 130,000
More informationReview Article. compressors on the market. He has in-depth experience in the sale, design, installation and commissioning of the first CO 2
ENGLISH REVIEW ARTICLE Alexander Cohr Pachai is employed by Johnson Controls Denmark. Since 1995, his main working area has been natural refrigerants. He was extensively involved in the promotion of hydrocarbons
More informationChapter 2. Alternatives to HCFCs and their Characteristics
Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid
More informationDue to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.
TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there
More informationINVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS
INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported
More informationRS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:
TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation
More informationUse Of Ammonia for Air Conditioning Applications
[Home] Search CD: Go Theme: Select one Issue : April-June 1999 Use Of Ammonia for Air Conditioning Applications By Ramesh Paranjpey Chief Executive Voltas - AIG Ltd., Pune Paranjpey is an M-Tech. (Refrigeration)
More informationScroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C
Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C McQuay International (A Member of the DAIKIN Group) Hydrofluorocarbon (HFC) refrigerants are critical to the safe and cost-effective phase-out
More informationOptimization of Cooling Systems
Optimization of Cooling Systems Basic principles Compressors and other power consumers The simple refrigeration system - refrigerants Svenn Hansen Refrigeration and Heat Pump Technology sha@teknologisk.dk
More informationPreventive Maintenance
Preventive Maintenance Preventive Maintenance for MHI Cen Preventive Maintenance Programs by Mitsubishi Heavy Industries Thermal Systems, Ltd. (MTH) keep your centrifugal chiller running with efficiency
More informationSpecifications for Refrigerants
AHRI Standard 700 2016 Standard for Specifications for Refrigerants IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components
More informationCOLD. Basic Training Course II. November ESSE - Wilhelm Nießen
COLD Basic Training Course II 1 Temperature What is cold? 2 Temperature The expression cold is not correct physically. We are talking about heat. Heat is a form of energy. Every material has got more or
More informationSafe Handling of Ammonia & Reporting Leaks. Andrew Keeley, Senior Project Professional
Safe Handling of Ammonia & Reporting Leaks MECHANICAL October 17, INTEGRITY 2013 Andrew Keeley, Senior Project Professional Ammonia is used as a refrigerant at a large number of industrial facilities.
More informationSERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS
Classification: Reference: Date: HA94-005 NTB94-091 September 26, 1994 SERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS APPLIED VEHICLE(S): All models except Quest equipped with a retrofitted A/C system SERVICE
More informationINSTRUCTIONS RHS 700. Recovery, Recycling, Evacuation and Charging Station RHS 700
A GRAMKOW A/S Augustenborg Landevej 19 DK-6400 Sønderborg Denmark A/S Reg. No. 17 12 31 Telephone: 45 74 12 36 36 Telefax: 45 74 43 36 46 Telex: 5 23 18 Bank: Den Danske Bank, No. 32 27 INSTRUCTIONS Recovery,
More informationMECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS
By Joe Fazzari, P.E, Vice President of Colmac Coil Manufacturing, Inc. MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS Owners should perform periodic mechanical integrity inspections on air coolers to
More informationAHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves
AHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee
More informationSpecifications for Refrigerants
AHRI Standard 700 with Addendum 1 2017 Standard for Specifications for Refrigerants Price $10.00 (M) $20.00 (NM) Printed in U.S.A. Copyright 2017, by Air-Conditioning, Heating, and Refrigeration Institute
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationSabroe Factory profile. For further information go to
Sabroe Factory profile For further information go to www.sabroe.com Company: About Johnson Controls History Johnson Controls businesses Revenues If the you can read this Click on the icon to choose a picture
More informationHybrid Conversion Kit Procedure Guide
Automotive Air Conditioning Hybrid Conversion Kit Procedure Guide TM autoclimate COPYRIGHT INFRINGEMENT NOTICE Autoclimate Limited. All rights reserved. No part of this manual, publication or text may
More informationREFRIGERANT CHANGEOVER
Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants
More informationStandard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units
ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed
More informationTel: Fax: Website:
Vacuum Dehydration Oil Purification System(Oil Purifier) The water and particles contamination in lubrication, hydraulic and dielectric oils badly affect the oils performance and threaten system reliability.
More informationFALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Paul Mueller Company s Other applications include
More informationPRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008
PRICE CHOPPER SARATOGA, NY First cascade supermarket system in North America Installed and Started March of 2008 Why did we choose CO2? Meets Corporate sustainability initiatives Looking for ways to reduce
More informationc Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2013) 2 / 25 T270 COP R = Q L
Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd http://teacher.buet.ac.bd/zahurul/
More informationwe will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.
Refrigeration Cycle Reading Problems 10-1 10-5, 10-7, 10-9 10-11, 10-14, 10-39 Definitions a refrigeration system removes thermal energy from a low-temperature region and transfers heat to a high-temperature
More informationRefrigeration Cycles. Refrigerators, Air-conditioners & Heat Pumps. Refrigeration Capacity/Performance. Dr. Md. Zahurul Haq
Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd http://teacher.buet.ac.bd/zahurul/
More informationCarbon Monoxide (CO) Gas Detector March 15 GCO 300
GCO Carbon Monoxide (CO) Gas Detector March 15 Features Output 4-20 ma or 2-10 Vdc Power supply 24 Vdc Ranges 0-100 ppm or 0-300 ppm IP65 enclosure with quick locking screws Digital measurement value processing
More informationT270 COP R = Q L. c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2017) 2 / 23 T354
Refrigerators, Air-conditioners & Heat Pumps Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000,
More informationRefrigeration Technology in Building Services Engineering
Unit 70: Unit code: T/600/0459 QCF Level: 3 Credit value: 10 Guided learning hours: 60 Unit aim Refrigeration Technology in Building Services Engineering This unit develops an understanding of the principles,
More informationFilter Driers with Replaceable Core
STANDARD Filter Driers with Replaceable Core The filter driers with replaceable core (HTG series) are used in liquid line and suction line of refrigerating, freezing and air conditioning system. The filter
More informationAlternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration
Alternatives in the AC & Chiller Sectors Sukumar Devotta and Lambert Kuijpers OORG Refrigeration 1 Outline ASHRAE position paper summary which marks a difference in the US approach dealing with various
More informationThe cold chain in the fishery sector. Refrigeration Technology Review
The cold chain in the fishery sector. Refrigeration Technology Review Paul de Larminat Johnson Controls MOP-27 Side Event Dubai 01 Nov. 2015 «Fishing Industry» is highly diversified Catches Conservation
More informationSystem Design, Commissioning, Operation
PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares
More informationThe Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.
The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties
More informationEvaporators. Direct Expansion Flooded Recirculated Over Feed
Evaporators Purpose: Liquid Refrigerant is Boiled from a Low Pressure Liquid to a Low Pressure Gas by Absorbing Heat from the Medium that is being Cooled Types: Direct Expansion Flooded Recirculated Over
More informationCall us today! (800)
150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,
More informationRefrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016
Refrigeration System Overview ASTI 32 Hour Managing Ammonia Course September 27 30, 2016 A refrigeration system is a mechanical heat transport system. The system absorbs heat energy from an area it is
More informationSUBJECT Model ASH218SV-C8LU SPECIFICATION ASH218SV-C8LU. 1. SCOPE This specification is applied to SHANGHAI HITACHI rotary compressor.
ASH218SV-C8LU SUBJECT Model ASH218SV-C8LU SPECIFICATION ASH218SV-C8LU PAGE:1/23 1. SCOPE This specification is applied to SHANGHAI HITACHI rotary compressor. 2. SPECIFICATION OF COMPRESSOR 2.1 Model ASH218SV-C8LU
More informationAir Conditioning & Duracool Emery Stora
Air Conditioning & Duracool Emery Stora X Low refrigerant Clutch cut off switch * *Leaves compressor as High pressure gas **Leaves condenser as High pressure liquid ** Changes from a high Pressure liquid
More informationUser manual Flushing device VAS 6337/1a
User manual Flushing device VAS 6337/1a 2 Content Safety warnings 3 Flushing with R134a refrigerant 4 1.0 Preparing the Vehicle AC System 4 1.1 Connecting the recovery recharge Unit 6 1.2 Flush procedure
More informationAIC Brazed Plate Heat Exchanger Operating and Instruction Manual
AIC Brazed Plate Heat Exchanger Operating and Instruction Manual Advanced Industrial Components Page 1 of 8 Customer Service Call: 1-888-738-1350 1.0 Installation 1.1 Mounting/support unit: a) On a shelf
More informationPage 1 of Relevant Provincial Jurisdictional legislation.
Page 1 of 15 1. Act, Regulations and Codes (6.7%): To locate information relating to the staffing, operation, maintenance, inspection, and testing of the refrigeration plant and its equipment using reference
More informationAmmonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member
Ammonia Refrigeration & Scenario in Industrial Refrigeration By Ramesh Paranjpey ASHRAE Fellow Life member 5 th March 2014 Basic Components Of A Refrigeration System Refrigerant Flow Path Refrigerant?
More informationOPERATION & MAINTENANCE MANUAL RHS680
OPERATION & MAINTENANCE MANUAL RHS680 Refrigerant Handling System 4075 East Market Street York, PA 17402 800-468-2321 tech@rtitech.com Manual P/N 035-80740-00 (Rev 1- May 22, 2001) TABLE OF CONTENTS Startup
More informationReduce energy usage by 25-50%
Reduce energy usage by 25-50% Drive significant energy savings by reducing HVAC energy consumption. INTRODUCING HVAC Portfolio With each purchase from RAISE Energy you participate in a donation of energy
More informationICEU 36 SPARE PARTS LIST REV. 07/2016
ICEU 36 ~ SPARE PARTS LIST REV. 07/2016 ICEU 36 1 UNIT PANELS UP TO S.N. 02594 2 UNIT PANELS FROM S.N. 02595 3 REFRIGERANT SYSTEM AIR COOLED UP TO S.N. 02413 4 REFRIGERANT SYSTEM AIR COOLED - FROM S.N.
More informationResidential Duct Mount Builder s Box Media Air Cleaner
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Residential Duct Mount Builder s Box Media Air Cleaner Part Numbers: P102-BB14A, P102-BB20 IMPORTANT: Read entire instructions before installing the
More informationSabroe Factory NetTraining COMP1 and sales tools
SABROE FACTORY Sabroe Factory NetTraining COMP1 and sales tools By Michael A. Jensen Sabroe Factory NetTraining COMP1 Select and templates 2 Johnson Controls PowerPoint Guidelines February 8, 2008 - basics
More informationGeneral Guidance. The easiest way to establish the amount of refrigerant in the system is to use data supplied by the manufacturer:
Information Sheet GEN 5 Refrigerant Quantity General Guidance 1. How much refrigerant is in the system? If you have established that you are using an HFC refrigerant in a refrigeration system, the next
More informationRefrigerant Transfer and Compressor Damage
Refrigerant Transfer and Compressor Damage While a piston or scroll compressor refrigeration system with a low-side oil sump is shut down, all is not at rest in the refrigerant circuit. Cutaway views of
More informationFrigi Tech International, Inc Prairie Wind Lane,. Houston, Texas T: F:
Education at your fingertips There is the misconception that t an air conditioner blows cold air when actually it removes the heat from the conditioned space. Let s start trtwithwhtwe re what we re all
More informationA/C-Service Unit 7KG-MOBIL Art.-No
Art.-No. 0764 98 Instruction manual 1 WÜRTH reserves the right to discontinue, or change at any time specifications or designs without notice and without incurring obligations according to her policy of
More informationXL
Vacuum Machine 7004.0005 - Smooth Mini 7004.0010 - Smooth Plus 7004.0015 - Smooth 30 7004.0020 - Smooth 35 7004.0025 - Smooth 42 7004.0030 - Smooth 42 L User Manual CONTENT 1 Preamble... 4 2 Safety...
More informationFundamentals of Refrigeration Part 2 Refrigeration 1
Fundamentals of Refrigeration Part 2 Refrigeration 1 We have established in the first part of this training session that cooling in a DX coil is the result of the latent heat of vapourisation which is
More informationEnergy Use in Refrigeration Systems
2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is
More informationKCC Centrifugal Fan Air Cooled Condensers
PRODUCT DATA & INSTALLATION Bulletin K50-KCC-PDI-10 KCC Centrifugal Fan Air Cooled Condensers Air Cooled Models from 103 Thru 164 Four to ninety Ton 1064435 We are on the Internet www.keepriterefrigeration.com
More informationSafety concerns for A2L refrigerants in AC service procedures
Safety concerns for A2L refrigerants in AC service procedures Alternative Refrigerants for High-Ambient Countries; Risk Assessment of Future Refrigerants in Production, Installation, and Service 28 October
More informationControl of refrigerant gases during manufacture, installation, servicing
The Australian automotive code of practice 2008 Control of refrigerant gases during manufacture, installation, servicing or de-commissioning of motor vehicle air conditioners Motor Trades Association of
More informationAIR CONDITIONING COMPRESSOR OIL
AIR CONDITIONING COMPRESSOR OIL PAG, PAO AND POE OILS THERE ARE LOTS OF OILS AVAILABLE, WHICH ONE IS RECOMMENDED? Oil plays an important role in the air-conditioning system, no matter whether it's required
More informationINSTRUCTION MANUAL HETO CBN 8 / 18 / C Cooling Baths ID: IM.doc Revision 1
Revision 1 INSTRUCTION MANUAL HETO CBN 8 / 18 / 28-30 - 30 C Cooling Baths ID: 88872215 Page 2 / 9 INSTRUCTION MANUAL CBN 8 / 18 / 28-30 Important user information Please read this entire manual to fully
More informationCommercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications
Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.
More informationChapter 10 Lyes KADEM [Thermodynamics II] 2007
Refrigeration Cycles The objective of refrigeration cycles is to transfer the heat from a low temperature region to a high temperature region. - if the objective of the cycle is to decrease the lowest
More informationNZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a
Page 1 of 5 Title Convert an automotive air conditioning system from R-12 to R-134a Level 3 Credits 2 Purpose This unit standard is for people in the automotive repair industry. People credited with this
More informationThe Problem of Counterfeit Refrigerants
The Problem of Counterfeit Refrigerants James K Carson President, Commission C2, International Institute of Refrigeration Senior Lecturer, School of Engineering, University of Waikato j.carson@waikato.ac.nz
More informationIntroducing a New Ammonia/CO 2 Cascade Concept for Large Fishing Vessels
Introducing a New Ammonia/CO 2 Cascade Concept for Large Fishing Vessels Per Skærbæk Nielsen Thomas Lund YORK Refrigeration, arine & Controls 2003 IIAR ammonia refrigeration conference, Albuquerque, New
More information2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)
2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment AHRI Guideline T (I-P) IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the
More informationSunny Hills. HVAC Maintenance Checklist Template. conducted for. Conducted on 31 Oct :40 PM. Prepared by Jon Nieve
HVAC Maintenance Checklist Template conducted for Sunny Hills Conducted on 31 Oct 2018 03:40 PM Prepared by Jon Nieve Location 102 S Mendel St, Fort Stockton, TX 79735, USA Completed on 31 Oct 2018 04:11
More informationFlammability and the Low GWP Refrigerant Challenge
Flammability and the Low GWP Refrigerant Challenge A Presentation to the BSRA Presentation On Guy Fawkes Night 5 th November 2015 Presented by Dewi Garcia MSc, MInstR Technical Manager Harp International
More informationPURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN
VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems
More informationMarch 2014 AHRI Presents Research Findings at Low-GWP AREP Conference
March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference In addition to its regular research activities, AHRI is conducting the Low-Global Warming Potential Alternative Refrigerants Evaluation
More informationAPPLICATION & SERVICE GUIDE
APPLICATION & SERVICE GUIDE HFC Refrigerant R410a Used In GeoMax2 Geothermal Heat Pump Systems Although the bulk of this manual is information regarding R410a, R407c will also be discussed for purposes
More informationHigh Profile Evaporator
PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature
More informationEvaporative Cooling products
user manual Evaporative Cooling products OPERATION - MAINTENANCE Z0582995_A ISSUED 06/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT general information Note Recold
More informationThe Electronic Newsletter of The Industrial Refrigeration Consortium Vol. 14 No. 3, 2014
chan The Electronic Newsletter of The Industrial Refrigeration Consortium Vol. 14 No. 3, 2014 OIL MANAGEMENT DO S AND DON TS Oil management is one area of major difference between ammonia refrigeration
More informationAutomotive Air Conditioning systems
Automotive Air Conditioning systems Basic understanding of the system, the components and the roles they play. Budi Waluyo, MT. Understanding the system. Your A/C system is nothing more than a heat exchanger.
More informationUEE11 Electrotechnology. Training Package. UEENEEJ108A Recover, pressure test, evacuate, charge and leak test refrigerants SAMPLE.
UEE11 Electrotechnology Training Package UEENEEJ108A Recover, pressure test, evacuate, charge and leak test refrigerants Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank
More informationAir conditioning 23XRV
High-Efficiency ChillerS with screw compressors Air conditioning Control CCN - Carrier Comfort Network Features The Evergreen range offers superior solutions with record capacities from 970 to 1880 kw,
More informationCaresaver Universal Refrigerant Recovery Unit
Operation Manual Caresaver Universal Refrigerant Recovery Unit 2 CONTENTS CHAPTER 1 INTRODUCTION AND OVERVIEW Specifications 3 Health and Safety 4-5 Component Location and Identification 6-9 CHAPTER 2
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationTechnical manual 2G-TA 04 - Gas
Technical manual 2G-TA 04 - Gas Combined Heat and Power Plants of 2G-Biogas, 2G-Natural gas and 2G-agenitor Series G-Box 50 2G-KWK-EG 2G-KWK-BGG 2G-agenitor G-BOX 50 2G-KWK-70EG 2G-KWK-100EG 2G-KWK-140EG
More informationImproving the Effectiveness of Air Conditioning and Refrigeration Systems. White Paper
Improving the Effectiveness of Air Conditioning and Refrigeration Systems White Paper Tom VanZeeland Chief Technology Officer Raise Energy Solutions, LLC, 1059 Triad Court, Suite 1, Marietta, GA 30062
More informationDevelopment of centrifugal chiller and heat pump using low GWP refrigerant
Development of centrifugal chiller and heat pump using low GWP refrigerant Ryosuke Suemitsu 1*, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy
More informationPerformance Rating of Heat Pump Pool Heaters
ANSI/AHRI Standard 1161 (SI) 2014 Standard for Performance Rating of Heat Pump Pool Heaters Approved by ANSI on 20 November 2014 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does
More informationSPECIFICATIONS MODEL E859C MINI DEHYDRATOR
SPECIFICATIONS MODEL E859C MINI DEHYDRATOR 1 DEHYDRATION TECHNOLOGY This proposal describes the equipment which shall be supplied by ENERVAC for a system for processing (dehydrating, de-aerating, purifying
More information