1 t ACKNOWLEDGEMENT The success of the 15th Annual Meeting of the International Institute of Ammonia Refrigeration is due to the work of the authors whose technical papers appear in this book. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry. --IIAR Board NOTICE The views expressed in the papers contained in this book are those of the individual authors. They do not constitute the official views of IIAR and are not endorsed by it Connecticut Avenue, N.W. Suite #700 Washington, D. C / FAX: 202/

2 ARTICLE 80 OF THE UNIFORM FIRE CODE: COMPLIANCE CASE STUDY FOR AMMONIA REFRIGERATION SYSTEMS By : Ellis Norton The Facility Group Atlanta, Georgia Presented at: IIAR 15th Annual Meeting March 21-24, 1993 Vancouver, British Columbia, Canada

3 - I. INTRODUCTION The hiform Fire Code (UFC) was initially deve,aped by the California Fire Chiefs Association and was first published by the Western Fire Chiefs Association (WFCA) and the International Conference of Building Officials (ICBO) in The Code is revised at 3-year intervals, and is currently sponsored by the International Fire Code Institute (IFCI). This code has been adopted in California and in most of the states west of the Mississippi River. Generally, the Uniform Building Code (UBC) and the Uniform Mechanical Code (UMC) are used in conjunction with the UFC. The 1988 revision of the UFC incorporated a complete re-write of Article 80, Hazardous Materials. Because ammonia is covered by the definition of hazardous materials in the UFC, ammonia refrigeration systems are subject to Article 80. Ammonia is considered by some fire officials as both a "toxic compressed gas" and a "corrosive" under Article 80. The author does not agree that ammonia refrigeration systems should be included in Article 80 which is a view shared by many in our industry. Ammonia refrigeration systems should be included in Article 63 of the UFC, under Mechanical Refrigeration. Article 63 needs to be revised to include appropriate requirements from ASHRAE and IIAR standards, and Article 80 should refer to Article 63 for coverage of refrigeration systems. IIAR has made significant progress towards instituting these changes. Until these changes are actually accomplished, and Ellis Norton is the Refrigeration Design Manager of The Facility Group in Smyrna, Georgia. 71

4 ammonia refrigeration systems are remosved from Article 80, we must comply with its requirements. This paper is offered as a guideline to help the members of our industry comply with the requirements of Article GENERAL DESIGN REQUIREMENTS Experience with Article 80 on recent projects has been that the following sections of the UFC are usually required by fire code officials and emphasized for ammonia refrigeration systems: Sec , General Storage Requirements - Division 111 Sec , Compressed Gases Sec , Corrosives Sec , General Dispensing, Use and Handling - Division IV Sec , Dispensing and Use Compliance with these sections impacts the refrigeration system design, and requires that we look at our system from a different standpoint than we have in the past. Some major design issues to consider are: 0 Minimize the refrigerant charge 0 Utilize the evaporative condenser as a scrubber for the engine room ventilation 0 Eliminate fugitive emissions from relief valves, control valves, and hand valves 0 Utilize the ammonia dilution tank (required by Article 63) to dilute ammonia concentration in the condenser pan Develop calculations that predict ammonia discharge (ppm) from the compressor room ventilatiodscrubber system In addition to refrigeration system design, the building design is also impacted. Generally, the owner will have a more expensive building as a result of Article 80. Some of the major building design issues to consider are: 0 0 A sprinkler system is required in the engine room A special occupancy rating is required in locations where ammonia is stored: fire walls are required and explosion venting may be required 72

5 0 0 0 Secondary containment requirements dictate special floor design and treatment in the engine room Electrical emergency power (generator or other source) is required for the scrubber, ventilation, control and alarm systems Smoke detectors are required in the compressor room In working with various fire departments in California, we have found that a similar attitude exists among most individuals, and they take similar approach to Article 80 enforcement. The typical attitudes encountered are: 0 Code enforcement personnel are concerned with the external impact of ammonia releases. What happens to the community as a result of a release is more important to them than the safety and protection of people inside. Generally, 0 OSHA is responsible for the safety of the workers inside the facility Code enforcement officials in general do not understand ammonia refrigeration systems, and they have no understanding of how compliance with the code impacts design, performance and safety 0 Interpretation of the code is not consistent, even among personnel in the same fire department. The reason being that no one has a back log of experience. 0 Department personnel in general do not (can not) offer suggestions on compliance. Their attitude is to wait for a submittal and then make a ruling on a specific submittal. In general, there is considerable turn-over of personnel within the code, and this creates problems due to inconsistent code interpretation. It is best to work with the same individual throughout a project so that this problem is minimized. Our projects were grocery distribution centers having ammonia refrigeration systems that contained approximately 10,000 lbs. of ammonia. The configuration for each system is a central machinery room containing the compressors, vessels, refrigerant pumps, and electrical equipment. One or more evaporative condensers are located on the roof above the compressor room. Piping and control valves are on the roof. A brine chiller located in the machinery room provides refrigeration for banana rooms in some instances. A computer control system was 73

6 installed in each case. The contractors who installed the system were local in each case, and in general they were familiar with Article 80, but in no case did they know exactly how to comply with all the provisions. The methods used to comply with Article 80 are not the only way that this can be done. There are better ways in many cases than these methods. However, the methods described have been approved by various jurisdictions, and the comments and descriptions are offered as a starting point for a system design STORAGE REOUIREMENTS-GENERAL (80.301) The General provision for storage requirements in Section must be adhered to if there is not a specific requirement in other (following) sections. Specific areas of interest are: 0 Spill Control, Drainage, and Containment (1). This is also required under Section , Corrosives, and the requirements will be discussed under that section. Ventilation (m). This is also required under Section (a)(6), and the requirements will be discussed in that section. Fire-extinguishing Systems (p). The machinery room must be protected by an automatic sprinkler system with a basis of design as Ordinary Hazard Group 3 under the UBC. Acceptable specifications for the system are described below: Type: Density : Remote area: Head Type: Head Spacing: Wet, Schedule 40 pipe.20 gpin per sq. ft. 3,000 sq. ft. Brass Upright; 17/32" orifice; 286 F 130 sq.ft. A sprinkler system in the machinery room presents some problems. Some things that 74

7 must be considered are: Protection of electrical equipment, such as the control panel and the motor control center. Accidental release during operation: water will be released at a rate of 1" every 3 minutes. 0 Explosion Venting or Suppression, (4). Explosion venting is u t required under Article 80. Insurance carriers have requested, however, this on some projects, with an assumption that ammonia is a flammable gas. These requests should be firmly resisted on the grounds that ammonia is not classified as flammable by DOT, and venting is not required by the code. 0 Standby Power, (s). Standby power is defined as "Legally Required Standby Systems" in the National Electric Code (NEC). It differs from "Emergency Power" as specified in Section (a)(7) of the UFC. The major difference between the two is that emergency power systems are essential for safety to human life, whereas standby systems are intended to provide power for fire fighting, rescue operations, control of health hazards, and similar operations. Both require an automatic transfer switch, but the emergency system must come on in 10 seconds, whereas the standby system must come on within 60 seconds. Generally, unless the express approval of the fire marshal1 is obtained, an emergency power system is required under Article 80 for operating the following equipment: 1. Machinery room ventilation fan 2. Ventilation air scrubber system 3. Ammonia detector 4. Emergency alarm system Emergency power can come from one of three sources: 75

8 1. Generator Set. Generator service, and as stated above, switch that operates within 10 be provided. system. The generator must have automatic start upon failure of normal it must be equipped with an automatic transfer seconds. Normally, a two-hour fuel supply must must be supplied with a self-contained cooling 2. Separate Service. This requires a completely separate supply, widely separated electrically and physically, and requires a separate transformer, in most instances. Most utilities will resist supplying this service, and will cite code requirements as a reason. However, the National Electric Code (NEC) allows this as an exception in the case of emergency power for legally required standby. It is best to get started on this service early, and to get the client active in discussions with the local utility. 3. Connection Ahead of Service Disconnecting Means. This connection cannot be within the confines of the main disconnect. In order to make the connection, main power must be shut off by the utility and the connection made at a location far enough away from the main so that any occurrence inside the building will not interrupt the emergency service. Source (3) is normally the most economical option for emergency power, and as above, it is best to get started on this service early and to get the client involved in discussions with the utility. - IV. COMPRESSED GASES (80.303) Section , covering compressed gases, is normally applied to ammonia, and is the main section governing ammonia refrigeration systems especially when fire officials consider ammonia to be a "toxic compressed gas." Important areas are: 0 Exempt Amounts, (a)(2) This section requires that any amount of ammonia (stored) in excess of 40 cubic feet at normal temperature and pressure (approximately 2 lbs.) be in a room conforming to H-7 occupancy under the Uniform Building Code (UBC). This requires a 4-hour rated fire wall between the machinery room and the rest of the plant in most instances. 76

9 0 Exhaust Ventilation, (a)(6). The exhaust ventilation system must be capable of absorbing or scrubbing ammonia vapors from the ventilation air in the event of a spill. Discharge from the scrubber must. be less than one-half the IDLH (Immediately Dangerous to Life and Health) value, or 250 ppm for ammonia. In all instances the evaporative condenser served as the scrubber. Calculations had to be submitted to show both the maximum release rate and the expected scrubber discharge in ammonia ppm. The exhaust fan must be sized in accordance with the Uniform Mechanical Code (UMC) for 12 air changes per hour (minimum). The exhaust air must be ducted to the condenser inlet so that it is captured by the entering air. The condenser drain must also be diverted automatically to a holding tank when the concentration of ammonia gets to a pre-determined level. At the same time, the drain pan must be diluted with fresh water on a rise in concentration. The water dilution tank (required by Article 63) can be used to collect the diverted drain water. Dilution water is furnished from the dilution tank or from water make-up. Controls must be such that an ammonia detector in the machinery room compels the exhaust fan and condenser fans and pumps to run, and a ph sensor in the condenser pan initiates the drain diverting and pan water dilution cycle. 0 Gas Detection, (a)(9). Although it is standard practice to provide ammonia detectors in the machinery room as a minimum, and in refrigerated rooms in most instances, Exception (2) in this section states that, "if the physiological warning properties for the gas are below the accepted 77

10 permissible exposure limit," for that gas, "a continuous gas detection system need not be provided." As we all know, ammonia, known as the self-alarming refrigerant, fits this requirement. However, a detector is required in the machinery room for the operation of the ventilation fan to qualify as a non-hazardous location under the National Electric Code (NEC). In one instance, detectors were required at each air unit to satisfy a B-2 occupancy requirement for the building under the UBC. Smoke Detection, (a)(10). A smoke detector is required in the machinery room, and it must be tied into a local alarm. - V. CORROSIVES, Section , covering corrosives, requires secondary containment for certain areas. The important part of this section is section (a)@), Containment, which states: I' Secondary containment shall be provided for the storage of corrosive liquids in accordance with the requirements of Section (1)(4). This requires secondary containment for the vessels in the machinery room. The machinery room floor can either be recessed or containment curbs can be constructed around the vessels to provide secondary containment. In either case, provisions must be made to seal the floor or curbs to make the containment liquid-tight. No drains are permitted unless they extend up far enough to stay clear of 20 minutes of fire sprinkler water plus the volume of the largest vessel. Provisions must be made to dispose of the ammoniawater solution. A sump pump can be used to transfer it to either the water dilution tank or to other approved areas. 78

11 - VI. DISPENSING, USE AND HANDLING-GENERAL (80.401) Section covers the General requirements for dispensing, use and handling. The section requires excess flow valves in pipes carrying ammonia liquid or gas at pressures over 15 psig. This is an area of serious concern because excess flow valves large enough to meet the requirements in this section are not available through traditional suppliers. Even if these valves could be located, the pressure drops are prohibitive in some instances. For these reasons, we must provide "alternative means and methods" to accomplish the intent of this section. One alternative that has been accepted is the installation of emergency solenoid valves in the main liquid supply and hot gas line(s), with controls to close automatically when ammonia is detected at valve groups or air units. The fact that solenoid valves close on power failure contributed to the acceptance of this alternative. This section also requires seismic protection. The details and guidelines found in the SMACNA publication, Seismic Restraint Manual: Guidelines for Mechanical Systems can be used for most piping supports. However, a review of vessel and machinery foundations must be made by a qualified structural engineer. VTI. DISPENSING AND USE (80.402) Section cwers dispensing and use, and requires secondary containment for roof-top piping. Because the Risk Management and Prevention Program (RMPP), required by the State of California, showed that a worst case release did not constitute a serious threat to life or safety at the nearest sensitive receptor, secondary containment was required only for valve groups, not 79

12 for the entire rooftop piping system. One arrangement that was approved is containment "boxes" that enclose the valve groups. The boxes are connected in series with 12" round duct, and air is continuously drawn through the system by a fan discharging into the condenser air inlet. An ammonia detector is mounted in this duct. The detector activates an alarm and initiates procedures such as closing solenoid valves. It also initiates the scrubber cycle in the condenser. An RMPP report is required on every large refrigeration project in California. In most instances it will show that ammonia releases do not constitute a serious hazard. It is to our advantage to have this report done early and to use the results in discussions with code officials. VIII. CONCLUSION IIAR and other refrigeration industy groups are working with ICBO and IFCI to remove ammonia refrigeration systems from Article 80. This will not happen immediately, however, and in the meantime we must comply. The methods presented in this discussion are designed to meet the requirements in Article 80 with a minimum impact on refrigeration system safety operation and cost. 80

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s PART 2 Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s Occupancy Classifications Y A - Assembly Y B - Business Y E - Educational Y F - Factory/Industrial Y H - Hazardous

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code SECTION 606 MECHANICAL REFRIGERATION [M] 606.1 Scope. Refrigeration systems shall be installed in Code. [M] 606.2 Refrigerants. The use and purity of new, recovered and reclaimed refrigerants shall be

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

FIRE PREVENTION STANDARDS

FIRE PREVENTION STANDARDS DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable

More information

Safety Standard for Refrigeration Systems

Safety Standard for Refrigeration Systems BSR/ASHRAE Addendum a ANSI/ASHRAE Standard 15-2016 First Public Review Draft Safety Standard for Refrigeration Systems First Public Review (April 2017) (Draft shows Proposed Changes to Current Standard)

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Hazard Zone Locations: HAZARD ZONE CHECKLIST

Hazard Zone Locations: HAZARD ZONE CHECKLIST LOGO HAZARD ZONE CHECKLIST Hazards, Risks, and Threats Levels of Concern Fire Control Measures Defensive Action Objectives Reference: SIMPLE Playbook and SOP s Hazard Zone Locations: Generally Applied

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

(h) Pesticide Application.

(h) Pesticide Application. Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.

More information

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room?

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room? Machinery Room Requirements & Best Practices Design Todd Jekel, Assistant Director, IRC Feb. 8, 2007 Standard Definition What is a machinery room? ASHRAE 15-2004 3 states: a space, meeting the requirements

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

Laboratories and Hazardous Materials. Company Overview

Laboratories and Hazardous Materials. Company Overview Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering

More information

A2L Refrigerants. Objectives 14/09/2017

A2L Refrigerants. Objectives 14/09/2017 A2L Refrigerants RMC HRAI Quebec City August 17, 2017 Greg Scrivener greg.scrivener@colddynamics.com Objectives 1) Learn the current state of codes and standards in relation to A2L refrigerants 2) Examine

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

***DRAFT - NOT FOR FILING***

***DRAFT - NOT FOR FILING*** ACTION: Original ***DRAFT - NOT FOR FILING*** DATE: 09/29/2017 1:14 PM 1301:7-7-27 Semiconductor fabrication facilities. (A) Section 2701 General (1) 2701.1 Scope. Semiconductor fabrication facilities

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

Part I Extraction Process Equipment

Part I Extraction Process Equipment 745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this

More information

FIRE PROTECTION PROGRAM

FIRE PROTECTION PROGRAM Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented

More information

Diesel Fuel System Report

Diesel Fuel System Report Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical

More information

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT

More information

SCALES NW EMERGENCY ACTION PLAN

SCALES NW EMERGENCY ACTION PLAN Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.

More information

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods.

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods. ANSI/IIAR 2-2014 Addendum A Standard for Safe Design of Closed-Circuit Ammonia Refrigeration Systems Public Review Draft #3 Reviewers of Addendum A are welcome to comment on the changes in the standard,

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications January 15, 2018 Revision 6 Ammonia detection system codes and design specifications Following is a discussion of ammonia detection system design

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc.

Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc. Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc. Commonwealth Scaffold, LLC Effective Date: 12/14/2012 Revision Number: 1 TABLE OF CONTENTS 1. Fire Prevention Plan Program 1 2.

More information

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.: Hot Work Permit Can this job be avoided? Is there a safer alternative? Permit No.: A Hot Work Permit is required for any non-production or maintenance operation involving cutting, welding, grinding, open

More information

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L ) NCEHSA Conference Carbon Monoxide Detector Regulations for Lodging Establishments (S.L. 2013-413) 1 Purpose of this session The purpose of this session is to review the provisions of Session Law 2013-413

More information

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum RAGAGEP UPDATE Douglas Reindl, Director, IRC 2016 IRC R&T Forum What s the point? Process safety information (d)(3)(ii) The employer shall document that equipment complies with recognized and generally

More information

Fire Prevention Plan Program

Fire Prevention Plan Program Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure

More information

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19 PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Dave Rule, President Eric Smith, Vice President and Technical Director

Dave Rule, President Eric Smith, Vice President and Technical Director Dave Rule, President Eric Smith, Vice President and Technical Director Technical Society for Industrial Refrigeration ANSI Accredited Standards Writer Advocacy for Natural Refrigerants Educational Resource

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

Understanding Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) for the Ammonia Industry

Understanding Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) for the Ammonia Industry Understanding Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) for the Ammonia Industry Daniel Dettmers Industrial Refrigeration Consortium University of Wisconsin Madison Overview

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

FIRE EMERGENCY POLICY

FIRE EMERGENCY POLICY University Policies and Procedures 11-01.01 FIRE EMERGENCY POLICY I. Policy Statement: This is a statement of official University policy for the reporting of fire emergencies and for the evacuation of

More information

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION DuPont Formacel Z-2 FOAM EXPANSION AGENT TECHNICAL INFORMATION Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications Flammability of Formacel Z-2 and Other Alternative

More information

Fire Protection. A Health and Safety Guideline for Your Workplace. Introduction. Fire Prevention and Control. Workplace Assessment

Fire Protection. A Health and Safety Guideline for Your Workplace. Introduction. Fire Prevention and Control. Workplace Assessment A Health and Safety Guideline for Your Workplace Fire Protection Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

FIRE PREVENTION AND PROTECTION*

FIRE PREVENTION AND PROTECTION* Chapter 30 (Replaced old ordinance September10, 2012) FIRE PREVENTION AND PROTECTION* * Cross References: Buildings and building regulations, ch. 14; environment, ch. 26; manufactured homes and trailers,

More information

BSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD

BSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD (This foreword is for information only and is not part of this addendum) FORWORD Changes in this addendum to ANSI/ASHRAE 15-1994 are made to add water as a refrigerant, include absorption refrigeration

More information

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS High-Hazard This document shall apply to all Group H, High-Hazard occupancies. GENERAL Scope Reporting of emergencies, coordination with emergency response

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

Fire Safety Plan Information. For Construction and Demolition Sites

Fire Safety Plan Information. For Construction and Demolition Sites Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions

More information

Plant Processing and Extraction Facilities

Plant Processing and Extraction Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Plant Processing and Extraction Facilities Guideline G-16 Serving the

More information

REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC

REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC Jean-Paul Lacoursière, P.E. University of Sherbrooke jpla@sympatico.ca Claude Dumas, P.E. Ville de Montréal cdumas@ville.montreal.qc.ca

More information

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone Medicine Hat Fire Service Construction Site Fire Safety Plan ABC Part 9 Buildings 1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone 403-529-8282 Email fireprevention@medicinehat.ca Small Buildings

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

Fire Plan Review and Inspection Guidelines

Fire Plan Review and Inspection Guidelines Fire Plan Review and Inspection Guidelines 2009 Edition Mike Thrapp Fire Plan Review and Inspection Guidelines ISBN: 978-1-58001-881-4 Cover Design: Publications Manager: Manager of Development: Illustrator/Interior

More information

DUST COLLECTION TRAINING. Revision 2013

DUST COLLECTION TRAINING. Revision 2013 DUST COLLECTION TRAINING Revision 2013 TOPICS 1. Why does a school need a dust collector? 2. What is a dust collection system? 3. What are the maintenance requirements? 4. What are the hazards? WHY NFPA

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES BACKGROUND INFORMATION Alberta Fire Code 2014: FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES Alberta Fire Code (AFC) 2014, Division B, Section 5.6. requires a Fire Safety Plan for

More information

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS Town of Brighton Office of the Fire Marshal October 2018 Carbon Dioxide Systems for Beverage Dispensing Requirements Scope The intent

More information

Process Safety Management

Process Safety Management Process Safety Management Benefits of PSM Flexible Comprehensive Adaptive Creative Designed to be the root elements of the Industrial process safety effort. 05/18/17 Ammonia Safety Training Institute 1

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 California Conference of Directors of Environmental Health I. Background Proper venting and capture of the gases, heat, grease,

More information

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS Last Updated: April 28, 2008 FIRE REGULATIONS The purpose of fire regulations is to maintain an acceptable level of fire safety within CGS facilities.

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

1. PURPOSE This standard specifies safe design, construction, installation, and operation of refrigeration systems.

1. PURPOSE This standard specifies safe design, construction, installation, and operation of refrigeration systems. ants. Over the next 11 years, representatives from the American Gas Association, American Institute of Electrical Engineers, American Institute of Refrigeration, American Chemical Society, American Society

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

Use of Dispersion Modeling Software In Ammonia Refrigeration Facility Design. By: Martin L. Timm, PE Corporate Process Safety Manager

Use of Dispersion Modeling Software In Ammonia Refrigeration Facility Design. By: Martin L. Timm, PE Corporate Process Safety Manager Use of Dispersion Modeling Software In Ammonia Refrigeration Facility Design By: Martin L. Timm, PE Corporate Process Safety Manager For the UW-Madison IRC R&T Forum, May 8-9, 2013 Introduction My IIAR

More information

POLICY STATEMENT: Policy Number: Section 600 Physical Plant. Date Adopted: May 7, Date(s) Revised: September 4, 2012

POLICY STATEMENT: Policy Number: Section 600 Physical Plant. Date Adopted: May 7, Date(s) Revised: September 4, 2012 Policy Number: 600.8 Policy Title: Subject: Hot Work Program Section 600 Physical Plant Date Adopted: May 7, 2009 Date(s) Revised: September 4, 2012 Approved by: Daniel J. Bingham Dean/CEO Helena College

More information

REFERENCES TO ICC ELECTRICAL CODE - ADMINISTRATIVE PROVISIONS IN THE INTERNATIONAL BUILDING CODE

REFERENCES TO ICC ELECTRICAL CODE - ADMINISTRATIVE PROVISIONS IN THE INTERNATIONAL BUILDING CODE REFERENCES TO ICC ELECTRICAL CODE - ADMINISTRATIVE PROVISIONS IN THE INTERNATIONAL BUILDING CODE 101.4.1 Electrical. The provisions of the ICC Electrical Code shall apply to the installation of electrical

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

Hospitals and Major Medical Centers

Hospitals and Major Medical Centers Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 10/17) HOT WORK PERMIT OPERATIONS Authority In recognition of the inherent hazards posed by certain hot work processes, the National Fire Protection Agency adopted Standard

More information

BUILDING/FIRE CODE REFERENCES 2006 EDITION

BUILDING/FIRE CODE REFERENCES 2006 EDITION BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire The IBC references the IFC in 97 Code sections. This document

More information

Fire Sprinklers Working Group Final Report

Fire Sprinklers Working Group Final Report Introduction The Building Act received Royal Assent on March 25, 2015. The Act aims to establish more consistent building requirements across British Columbia and create a more robust and modern building

More information

Guidelines for Fire Safety Plans at Construction or Demolition Sites

Guidelines for Fire Safety Plans at Construction or Demolition Sites Guidelines for Fire Safety Plans at Construction or Demolition Sites Sun Peaks Fire Rescue P.O. Box 1000, Sun Peaks, V0E 5N0 Phone 250-578-8985 Fax 250-578-8905 Guidelines for Fire Safety Plans at Construction

More information

REFRIGERATION CHAPTER 11

REFRIGERATION CHAPTER 11 CHAPTER 11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Exhaust Systems Chapter 7 Combustion Air Chapter 9 Specific Appliances Chapter 11 Refrigeration Chapter 13 Fuel Oil Piping POLICY Table

More information

2010 FIRE CODE OF NEW YORK STATE

2010 FIRE CODE OF NEW YORK STATE 2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,

More information

The Cannabis Industry: Fire Department Requirements

The Cannabis Industry: Fire Department Requirements The Cannabis Industry: Fire Department Requirements RVFD Standard 4.1 Rio Vista Fire Department 350 Main St. Rio Vista, CA. 94571 By: Jeff Armstrong, Fire Chief Updated December 2018 1 The purpose of this

More information

Ships and marine technology Fireextinguishing. of galley cooking equipment

Ships and marine technology Fireextinguishing. of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction

More information

Center for Life Safety Education

Center for Life Safety Education Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National

More information

Special Occupancy Requirements

Special Occupancy Requirements Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the

More information

Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS. A. Regulations, Standards and References 2. B. Scope 3. C. Approvals and Listings 3

Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS. A. Regulations, Standards and References 2. B. Scope 3. C. Approvals and Listings 3 Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS A. Regulations, Standards and References 2 B. Scope 3 C. Approvals and Listings 3 D. Design 4 E. Venting Cabinets 4 Page F. General Installation

More information

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope 1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

I. INTRODUCTION Codes, Rules, Laws, & Requirements

I. INTRODUCTION Codes, Rules, Laws, & Requirements I. INTRODUCTION 1.03 Codes, Rules, Laws, & Requirements A. Buildings and sites are to be designed in conformance to the applicable requirements of the following: 1. The Texas Engineering Practice Act and

More information

analysis ASHRAE : Implications for Mechanical Room Design

analysis ASHRAE : Implications for Mechanical Room Design analysis HVAC VOLUME ONE NUMBER ONE I S S U E S A N D A N S W E R S F O R T H E C O N S U L T I N G / S P E C I F Y I N G C O M M U N I T Y In this issue... What standards should be adhered to when designing

More information

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: Mech Code 601 Effective: 2-07-79 DOCUMENT NO. P/BC 2002-018 Revised: 9-25-03 Previously Issued As: RGA 2-79, MGD101 INSTALLATION OF ACCESS FLOOR

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information