1 ISO 9001:2008 CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-16F Private enterprise "ARTON" 6 Prutska street OPERATIONAL Chernivtsi Ukraine MANUAL EN 54-2 EN 54-4 For further information please contact us:

2 CONTENTS 1. INTRODUCTION FUNCTIONS TECHNICAL SPECIFICATIONS ITEMS SUPPLIED WITH THE PANEL DESIGN AND FUNCTIONING Design Functions and interactions of the panel s units General information PSU functions I/O functions BKI functions MC functions Operation principles General overview Alarm loops (zones) Outputs Users Power supply Boards Communicator Remote indicator Event log Tamper contact Main modes of operation General overview FIRE mode FAULT mode DISABLEMENT mode ALARM mode TEST mode User interface General overview Zone status window Schematic diagram of screen windows, menus and control functions SAFETY ISSUES HOW TO PREPARE THE PANEL FOR OPERATION WIRING AND INSTALLATION Installation AL wiring Sounder/beacon wiring Connecting outputs to CMS Connecting real-time clock power supply Mains wiring Battery wiring Wiring and usage of I/O outputs OUT1.. OUT USER GUIDE General information Zone disablement/ enablement Resetting all zones, FIRE, FAULT and ALARM modes Sounder disablement

3 9.5. FIRE output disablement FAULT output disablement Event log view Checking alphanumeric display, LED indicators and internal buzzer PROGRAMMING GUIDE How to enter programming mode How to program the panel How to program OUTPUT How to program USER How to set system date and time How to reset engineer password to factory defaults How to reset values of ZONE and OUTPUT to factory defaults How to autoconfigure the panel How to exit programming mode Factory defaults MAINTENANCE GUARANTEE COMPLIANCE/PACKING CERTIFICATE SPARE PARTS AND ACCESSORIES...36 ANNEX 1. ARTON-16F FRONT PANEL...37 ANNEX 2. DIMENSIONS...39 ANNEX 3. LOCATION OF PCBs, UNITS AND COMPONENTS INSIDE THE CABINET...40 ANNEX 4. LAYOUT OF MAIN CONTROL PCB AND INPUT/OUTPUT PCB...41 ANNEX 5. TYPICAL WIRING DIAGRAMS

4 1. INTRODUCTION 1.1 This manual describes the functions, technical specifications, installation, configuration and operation of the ARTON-16F fire alarm control panel. 1.2 You should peruse this manual prior to installation, adjustment, programming and use of the unit. 1.3 Only authorized persons or organizations are allowed to carry out the appropriate installation, adjustment and programming. 1.4 The following abbreviations apply in this manual: BAT rechargeable battery; AL fire alarm loop; Zone, ZN fire alarm zone (for the purpose of the manual AL equals to Zone); MCU main control PCB; BKI keyboard and indications PCB; I/O input/output PCB; PSU power supply PCB; SM standby mode; I norm AL current in standby mode; Charger back-up power charger; SC short circuit; Panel fire alarm control panel "ARTON-ХХF" series; CMS central monitoring station; Active detector a detector increasing AL current when going to the FIRE status; Passive detector a detector decreasing AL current when going to the FIRE status. 2. FUNCTIONS 2.1 The panel is designed to arrange centralized and stand-alone protection of various applications against fires by continuous monitoring of up to 16 fire alarm loops, receiving of fault and alarm signals, issue of alarm notifications (fire, emergency, fault, unauthorized opening) to sound and light alarm devices, CMS. The unit issues control signals for 14 output lines (fire fighting devices, smoke removal, and ventilation system). 2.2 The unit complies with EN54-2:2003 and EN 54-4: The ARTON-16F will operate under the following ambient conditions: ambient temperature from minus 5 to 40 С; relative air humidity at 40 С - to 95 %; atmosphere pressure from 84 to 107 kpa. 2.4 The unit identifies and indicates the following general statuses with optical indicators as well as on the digital display: - Fire mode; - Fault mode; - Disablement mode; - Test mode; 2.5 The unit identifies and indicates the following statuses with optical indicators as well as on the digital display: - disablement of FIRE output; - fault of FIRE output; - transmission of FIRE signal; - disablement of FAULT output; - fault of FAULT output; - transmission of FAULT signal; - transmission of DISABLEMENT signal; - transmission of TESTING signal; 4

5 - disablement of sounder outputs; - fault of sounder outputs; - enablement of sounder outputs; - disablement of CMS connection channels; - fault of CMS connection channels; - system error; - output activation delay; 2.6 The unit identifies and displays the AL statuses: - «Standby mode»; «NORM» - «Attention»; - «Fire»; - «Short-circuit»; - «Open-circuit»; - «AL disabled»; - «AL test»; 2.7 The unit identifies and displays the following statuses of outputs: - «SC in load»; - «Load break»; - «Enablement delay»; - «Activation»; - «Disablement»; - «Test»; 2.8 The unit identifies and displays the statuses of BAT and PSU: - «BAT disconnection»; - «BAT charge»; - «BAT critical discharge»; - «BAT in norm»; - «Mains power» or «Mains failure»; - «Fault of charger»; 2.9 The unit is designed as tamperproof (against opening and break of the enclosure). The tamper button triggers when the cover gets open and the panel goes to the ALARM mode The panel provides signalling with monitored outputs located on MC: «FAULT» monitored output for Fault signal transmission to CMS; «FIRE» monitored output for Fire signal transmission to CMS; «ALARM» - monitored output for Alarm signal transmission to CMS; «NORM» monitored NORM external indicator output; «LIGHT» monitored external beacon output (light alarm device); «SOUND» monitored external sounder output (sound alarm device); 2.11 The panel provides monitoring of auxiliary (programmable by user) outputs. The outputs are located on the Input/Output PCB-16 (8 outputs on each board) The panel is designed for 2-wire connections and allows setting loop voltage rated at 15 or 24 V (toggle between 12/24V on the I/O PCB-16 tumbler) Active, passive and combined detectors (devices) can be wired to a loop Any loop can be independently disabled/enabled. All loops can be reset for a short time The panel provides automatic recharging of the battery and protection against improper connecting (mispoling) The panel provides protection of all outputs against short-circuit with automatic reset upon S/C clearance The panel maintains line continuity for all outputs Multilevel control is available on the panel The following functions and parameters can be programmed using buttons on the front panel: 5

6 - view and setting loop parameters просмотр и установка параметров ШС; - fixation of the basic loop currents (standby loop current); - setting character names of loops; - view and setting parameters of outputs; - setting character names of outputs; - change of user and engineer passwords; - setting user rights to loop control; - setting user rights to output control; - resetting of event log; - resetting of all parameters to defaults; 2.20 The following controls are available to users: - resetting of Fire or Fault status; - disablement/enablement of loops; - resetting loops; - view loop statuses; - disablement/enablement of loop test mode; - muting/restoring outputs; - disablement/enablement of output test mode; - overriding output delay; - view output statuses; - view event log; - disablement of internal sounder; - testing of LCD indicator, LEDs and internal buzzer. 3. TECHNICAL SPECIFICATIONS 3.1 The panel is 220( )V AC mains powered with (50±1) Hz. 3.2 The back-up power is 12V non-spillable sealed lead-acid rechargeable battery (BAT) rated at 14.4 V full charge voltage, nominal capacity from 16 to 18 Ah and 10,5 V terminal long discharge voltage (not supplied with the panel). 3.3 Max mains power consumption 40 W. 3.4 Standby mains power consumption 12 W max. 3.5 Max BAT current consumption 2,5 А. 3.6 Max standby BAT current consumption 0,55 А. 3.7 Max BAT current consumption at mains failure and BAT voltage <(10,5-1)V ma. 3.8 Total outputs load <0,8 А. 3.9 Open output contact voltage (at max total output load) 8,8 15V Open output double pulse amplitude - <0,5V AL contact voltage at load absence: in 12V AL mode 15±0,5V; in 24V AL mode 24±0,5V Total resistance of signalling lines (wires) of loops not considering EOL resistor - <470 Ohm Leakage resistance between AL lines as well as between each AL line and enclosure - >50 kohm AL modes for detector types (AL type): - AL with active fire detectors (FD) (active AL); - AL with passive fire detectors (passive AL); - AL with both active and passive detectors (combined AL); 3.15 AL modes for decision type (AL operation algorithm) about FIRE status: - going to FIRE status when one or more detectors triggered (one FD); - going to FIRE status when two or more FD triggered (two FD); - going to FIRE status when one or more FD with verification triggered (verification); 6

7 3.16 Current growth value for first active detector relative to basic standby loop current is programmed by user and selected within the range 0,5 8 mа in increments of 0, Current decrease value for first active detector relative to basic standby loop current is programmed by user and selected within the range 0,5 8 mа in increments of 0, Open-circuit current <3 ma Short-circuit current >24 ma The panel is short-circuit-proof in AL/output circuits with fault indication Automatic reset time in Verification status is set by a user within the range 1 20 sec in increments of Wait-to-ready time after reset in Verification status is set by a user within the range 1 20 sec in increments of Wait-to-trigger time after reset in Verification status is set by a user within the range sec in increments of The panel is guaranteed to change a status effected longer than 100 msec and not to change a status effected for less than 50 msec Up to 32 active detectors can be connected to each loop (SPD-3.1M, SPD-3.5, SPD-3.10, SPT-2B, SPT-3 etc.), so max current consumption by all active fire detectors in the line does not exceed 3 ma Activation delay time for outputs is set by a user within the range sec in increments of Active state time for outputs is set by a user within the range sec in increments of Active period time in passive state is set by user within the range 0 25,5 sec in increments of 0, Passive period time in passive state is set by user within the range 0 25,5 sec in increments of 0, Active period time in active state is set by user within the range 0 25,5 sec in increments of 0, Passive period time in active state is set by user within the range 0 25,5 sec in increments of 0, Output transient time from active to passive state sec in increments of 0, Inverse mode can be set for each output Max output load current <300 ma Number of users 9. (8 authorized users and 1 engineer) 3.36 User password length 0 16 characters Technical readiness time upon powering <30 sec Meantime-between-failures >40000 h Average service life >10 years Dimensions 410 х 610 х 120 mm Weight (excluding battery) 10 kg Power supply parameters: - AC mains voltage 220( ) V; - mains frequency 50(±1) Hz; - output voltage +12V power supply from 9,5 to 15,5V; - output voltage +5V power supply from 4,75 to 5,25V; - max channel load current +12V <1,3 А; - max channel load current +5V <0,4A; - double pulse amplitude of +12V supply <1,0V; - double pulse amplitude of +5V supply <0,4V; - battery charge current 0,9(±0,1) A; - battery end-of-charge voltage 14,0(±0,1)V. 7

8 4. ITEMS SUPPLIED WITH THE PANEL 4.1 Having unpacked the panel check the exterior to make sure it is not mechanically damaged and check the contents for completeness that should correspond to Table 4.1. Table 4.1 Item Quantity Note ARTON-16F fire alarm control panel 1 Operational manual 1 Spare parts and accessories 1 Please refer to Section 14 Note. In accordance with your order the package may contain auxiliary devices expanding the panel s functions. 5. DESIGN AND FUNCTIONING 5.1 Design The panel consists of the following units: Main control PCB (MC); Input/Output PCB (I/O); Keyboard and Indications PCB (BKI); Power supply PCB (PSU); rechargeable battery (BAT); terminal block with fuse holder for connection to 220VAC supply; The panel s view is shown in Annex For the enclosure s and mounting dimensions refer to Annex The layout of units and PCBs inside the enclosure is shown in Annex The layout and function of connector block terminals is shown in Annex You can mount auxiliary units and PCBs, e.g. module PCB, blocking relays, remote indicator PCB etc. The functions of the units and how to handle them are indicated in the manuals for the appropriate units. 5.2 Functions and interaction of the units General information The panel has the unit-type structure allowing to get various performances. When you add a new unit or replace a unit out of service you should carry out auto-configuring of the panel The interunit interface is based on highspeed anti-interference industrial bus CAN 2.0В The control panel is an intellectual, distributed, event monitored, data collecting/processing as well as online system objects monitoring system The system objects are AL, Output, User, Power supply, PCB, Communicator, Tamper contact, Event log, Remote indicator, Logical expression Each object has statuses, functions and parameters suites An object goes from one status to another either by calling a function from its suite or as the object s response to external object monitored factor change (a physical value usually), and the object action in different statuses can be set using parameter values The system event is an object going from one status to another The panel performs interconnection of objects calling functions of some objects on status change of the others (reaction to event or/and to event combination). 8

9 The order of system response to events can be set using the special system object suite logical expressions A change of logical expression parameter is only possible on level 4 using special hardware and software reasoned by complexity and labour content PSU functions PSU transforms 220V AC voltage to voltages required for the panel to properly operate, the battery to charge, battery back-up power to be applied in the event of mains failure I/O functions I/O processes statuses and monitors 16 loops and 8 outputs, issues events when AL and/or output change their statuses I/O provides loop voltage stabilization I/O allows a user to set 15/24 V for loops using jumpers BKI functions BKI displays the panel s statuses and presents the interface for users to view information about object conditions, view and set object parameters, view the event log, monitor objects BKI contains groups of optical indicators, 4x40 alphanumeric display and multifunctional keypad MC functions MC is designed to generally synchronize all the panel s units, process logical expressions, issue an object function call, monitor the BAT, maintain the event log, control the obligatory outputs (according to EN54-2:2003) Fire, Fault, Alarm, Norm, Light, Sound MC has a capability to connect auxiliary boards to expand the panel s functions. 5.3 Operation principles General overview The panel monitors system object statuses (e.g. AL, Power supply and others) and depending on status combinations, program settings and configurations, calls other objects control functions of the internal sounder (e.g. outputs, light indicators etc.), external sounders enablement, transmission of notifications to CMS The following modes are available on the panel: Standby mode, ALARM, FIRE, FAULT, DISABLEMENT, AUTHORIZED USER, PROGRAMMING, TEST. The panel can operate in several modes simultaneously The indicator lights are located on the front of the enclosure giving an overview of the Panel s current status (see Annex 1) The 4 access levels are available on the panel. Level 1. - general user controls. Available functions: - testing the indicator lights and internal buzzer (called by pressing the TEST button); - muting the internal sounder in FIRE, FAULT, ALARM modes (by pressing the button Buzzer OFF ); - view of object current conditions; - view of event log; - output delay override (by pressing the Disable button). Level 2 authorized user controls. The access is limited by actions not requiring special tools. The level can be accessed by entering the user s number and his password. Each user has his unique number and password. The password is drawn from [0] to [9] numbers, from 0 to 8 characters long. Enter buttons [0] [9] and confirm entering by pressing the [ENTER] button. For default passwords for all users please refer to Table

10 Each authorized user can access controls under one or a few objects (AL and outputs). Several users can access the same objects. The following controls are available on this level: - enablement/ disablement of certain ALs, available to the user; - muting and restoration of outputs available to the user; - view of all system objects conditions; - view of event log; - resetting all ALs (by pressing the RESET button); Level 3 engineer controls (programming mode). To gain access to the mode enter the engineer access code. It is from [0] to [9] symbol combination from 8 to 16 character long. The following controls are available to engineers: - view and setting of each AL type and parameter; - basic AL current fixation; - view and setting of each output parameters; - setting of user rights on each AL; - setting of user rights on each output; - change of access codes of users and engineer; - enablement of autoconfiguration function when replacing or adding the panel s units. Note. For full description of the panel s controls refer to Section 7. To read the complete information about programming mode refer to Section 8. Level 4 maintenance level. Special auxiliary hardware and software are involved here (used at the factory, service centers, installation companies) Alarm loops (Zones) Outputs as AL objects are components of I/O boards with the following parameters: (below a text fragment typed in semibold with the «*» mark means that the text is displayed on the alpha numeric display). - AL name Name*; - AL mode by the detector type (AL type*): AL with active fire detectors Active *; AL with passive fire detectors Passive *; AL with active and passive detectors Active@Passive*; AL with linear beam detectors ARTON-DL type ARTON-DL; - AL mode by decision making type about Fire condition (Algorythm*): One or more detectors triggering General*; Two or more detectors triggering Two detectors *; One or more detectors triggering with verification With verification*; - standby current (I norm ) Standby current*; - AL drawing current (I cur ); - first detector current increment (I 1+ ) Increm I1+ *; - first detector current decrease (I 1- ) Decrem I1+*; - second detector current increment (I 2++ ) Increm I2+ *; - second detector current decrease (I 2-- ) Decrem I2+ *; - AL reset time (t rst ) ResetTime*; - AL wait-to-ready time (t rdy ) ReadyTime*; - AL wait-to-repeated-trigger time (t ver ) VerifTime*; 10

11 AL objects can be in the following conditions: - «Disabled»; - «Norm»; - «SC»; - «OC»; - «Attention»; - «Fire»; The following functions can be invoked for AL: - «Enable»; - «Disable»; - «Reset»; - «Set norm»; - «Enable Test mode»; - «Disable Test mode» AL operational principle Alarm loops of the panel are monitored transistor outputs with commutation of positive load power potential relative to the general panel s cable with current physical restriction. Rated voltage on AL leading-out terminals can be set on I/O board using jumpers «15/24V CH01 08», «15/24V CH09 16» for 8 AL group. AL continuously monitors current in the circuit (I cur ) and depending on the value of the current deviation from standby current (I norm ) goes to various conditions. Power application (enablement procedure) on AL load circuit occurs upon receiving the Enable command. AL applies power and during the time t rdy monitors circuits for SC and OC. On expiring the time the processing will start on other conditions presence. If AL circuit current is less than OC current, then the AL goes to OC condition. Upon the circuit restoring, the AL goes from the OC status to another condition within 10 sec. If AL load current is greater than SC current then AL deenergises the circuit load for 10 sec and goes to SC condition. When this time will expire the power is applied again and AL circuit current will be less SC level, then AL will perform enablement procedure and goes from the SC condition to another status. If AL circuit current has remained greater than SC current then AL will be deenergised again for 10 sec. When you select the Active mode, AL current will be monitored only for I norm.. When you select the Passive mode AL current will be monitored only for drop lower than I norm. When you select the Combined mode AL current will be monitored for both exceeding and dropping lower I norm. With the combination Active zone plus General algorithm if I cur exceeds I norm for the value greater than I s+, the AL goes to the Fire status. With the combination Passive zone plus General algorithm In the, one detector mode if I cur goes lower I norm for the value greater than I s-, the AL goes to the Fire status. With the combination Active@Passive zone plus General algorithm the AL will operate the same as in the combinations Active, General and Passive, General. With the combination Active zone plus With verification algorithm if I cur exceeds I norm for the value greater than I s+, the AL goes to the Attention status with AL load deenergising for t rst time, then the enablement procedure will occur, and if within t ver time I cur exceeds I norm for the value greater than I s+ again or SC condition occurs, then the AL goes to the Fire status. Otherwise, when t ver time expires the AL goes from the Attention status to the Norm condition. With the combination the Passive zone plus With verification algorithm if I cur gets lower I norm for the value greater than I s-, the AL goes to the Attention status with AL load deenergising for t rst time, then the enablement procedure will occur, and if within t ver time I cur gets lower I norm for the value greater than I s- again or OC condition occurs, then the AL goes to the Fire 11

12 status. Otherwise, when t ver time expires the AL goes from the Attention status to the Norm condition. With the combination Active@Passive zone plus With verification algorithm the AL will operate the same as in the combinations Active, With verification and Passive, With verification. With the combination Active AL plus Two detectors algorithm if I cur exceeds I norm for the value greater than I s+, the AL goes to the Attention status, and if within t ver time I cur exceeds I norm for the value greater than I s+ + I s++, then the AL goes to the Fire status. Otherwise, when t ver time expires the AL deenergises for t rst time, the enablement procedure is performed and the AL goes from the Attention status to the Norm condition. With the combination Passive AL plus Two detectors algorithm if I cur gets lower I norm for the value greater than I s-, the AL goes to the Attention status, and if within t ver time I cur gets lower I norm for the value greater than I s- + I s--, then the AL goes to the Fire status. Otherwise, when t ver time expires the AL deenergises for t rst time, the enablement procedure is performed and the AL goes from the Attention status to the Norm condition. With the combination Active@Passive AL plus Two detectors algorithm the AL will operate the same as in the combinations Active, Two detectors and Passive, Two detectors. When you carry out the Disable function, the AL deenergises loads in its circuits, goes to the Disabled status and doesn t process the circuit currents. When you carry out the Reset function, if the AL is in a status different from Norm or Disabled, then it deenergises the circuit loads for t rst time, performs the Enablement procedure and goes to the Norm status. If you enable the TEST mode, the AL object will react the same way as in the normal mode, indication in the window AL status will correspond to the TEST condition, the actual indication of AL status occurs in the box AL list by adding the word TEST to the real AL status (e.g. TEST Fire, TEST Norm etc.). In the TEST mode the AL status change will not lead to the output status change Outputs Outputs pertain to I/C and MC and have the following parameters: - Name Name*; - Output type - Output type*; - «Inversion» (Algorithm*): With inversion Inversion*; Without inversion Normal*; - «Active status time» (t On ) Active time*; - «Activation delay time» (t OnDly ) Delay time*; - «Automatic restoration after muting» (t arest ) Mute time*; - «Authorized enablement at SC» Perm ON in SHORT *; - «Active time in active status» (t OnAPr ) Та1 (ON/act),0.1s*; - «Passive time in active status» (t OffAPr ) Та2 (OFF/act),0.1s*; - «Active time in passive status» (t OnPPr ) Тp1 (ON/pas),0.1s*; - «Passive time in passive status» (t OffPPr ) Тp2 (OFF/pas),0.1s*; The Outputs can be in the following statuses: - «Passive»; - «Delayed»; - «Active»; - «Cleared»; - «Muted»; - «Passive SC»; - «Delayed SC»; - «Active SC»; 12

13 - «Cleared SC»; - «Muted SC»; - «Passive OC»; - «Delayed OC»; - «Active OC»; - «Cleared OC»; - «Muted OC»; The following functions can be called for Outputs : - «Cancel»; - «Enable»; - «Mute»; - «Restore»; - «Delay override»; - «TEST mode enablement»; - «TEST mode disablement; Note. The full list of an object functions is stated in the description of objects here and further in the manual. For the functions available for users please refer to Section How outputs operate The panel s outputs are monitored transistor outputs with load power positive potential commutation relative to the general cable with physical current restriction. An Output reaction depends on the parameters set for it. When you call the Enable function the output object starts to perform the operation scenario. The operation scenario consists of temporal phases: enablement delay, active status, cleared status. The object transition from one phase to another is accompanied with its status change that evokes an event in the system. The durability of each scenario phase can be set using the corresponding object parameter. Physical object status open/closed in active and passive logical states can be defined with the parameter Operation algorithm*. With the meaning With inversion* of the parameter Operation algorithm* in logical states «Passive», «Delayed», «Cleared» the output shall be closed, in the «Active» state - open. The object Output allows to fulfil dynamic load control using non-zero values of parameters t OnAPr, t OnPPr for the «Active» state and t OffAPr, t OffPPr for the «Passive», «Delayed», «Cleared» states. Each parameter pair defines for how long the output will be output periodically enabled then disabled in the corresponding state. The output s state is defined by two factors physical state of the output load circuit (norm, short-circuit, open-circuit), and the current logical scenario phase of the output operation (passive, delayed, active, cleared, muted). Outputs continuously monitor the load line integrity and in the closed status define Opencircuit when load resistance exceeds 20 kohm, and in the open status define Short-circuit when the load resistance is less than 4 Ohm. When the output goes from open to closed status and vice versa, the output load is not monitored during t FltSkip time, that is necessary in the event of capacity or inductive load that can cause surges at transitions. The load circuit is limited at 350 ma that s why short surges do not cause the output failure. When short-circuit is being determined in the load circuit the output goes to SC status, the output gets closed for 10 sec. In the event if the parameter Permit ON in SHORT* is not set, then it gets open again and monitored for short-circuit and so on. If short-circuit is absent the output goes from SC to normal condition. 13

14 Note: Recurring output s enablement is likely not to occur if the AL has not gone to the second scenario phase within the indicated time. When open-circuit is being detected in the load circuit the output goes to OC status, the output gets blocked for 10 sec., then the recurring monitoring for open-circuit occurs and so on. If open-circuit is absent the output goes from OC to normal condition. When you call the Mute function the object will go to the Muted status which is passive one. The output s reaction in the status shall correspond to the Passive phase of the scenario. When you call the Restore function the scenario implementation will proceed from the interrupted phase. Note: If the Reset function will be called in the Muted condition, then at the next call of the Restore function the output shall go to the Passive condition. The reaction of the Output object will the same as normal in the TEST mode: the obect logical status change will occur in accordance with the set parameters, with the word TEST being added to the object status (e.g., «ТЕSТ Delay», «ТЕSТ Passive Open-circuit» and so on) in the box Output list Users User is one of the system s components. Nine users support is realized in the system. They are divided into authorized users and engineers by the access type. The authorized users can access the control level 1 and 2. Engineers have access access levels 1, 2 and 3. The user is identified by access code. The user with number 1 is engineer. The users with numbers 2 9 are authorized users. «User» has the following parameters: - list of loops accessible to control; - list of outputs accessible to control; - access code; «User» can be in the following statuses: - «UserIn» (the user is in the system); - «LogOut» ((the user is out of the system); The identification procedure is carried out by entering a user s access code on the keypad The identification procedure is initiated by the user from the «UserIn» point of the main menu or automatically when the user (not passed identification) tries to invoke functions of level 2 and If the user is under identification procedure, then it goes to «UserIn» status and gains access to function calling for objects accessible to him If the user in the «UserIn» status is not active within 1 minute (user activity time-out), he automatically logs off A user can log out independently from «LogOut» in the main menu The event «UserIn» of any user automatically resets the Alarm mode of the panel caused by tamper contact triggering Power supply Power supply is a system s object pertaining to MC board or I/O board The «Power supply» object has the following parameters: - board voltage; - battery charge current; The «Power supply» object can be in the following statuses: - «battery in norm, AC in norm»; - «battery fault, AC in norm»; 14

15 - «charger fault»; - «battery charge, AC in norm»; - «battery discharge», AC in norm»; - «Low battery, AC fault»; - «Critical battery voltage, AC fault»; The board connected to PSU is responsible for transmission of information to the system about Power status When the «Power» status is changed, events occur in the system that lead to status change of outputs, keyboard and indications PCB etc. When the Power object goes to the «Critical battery voltage, AC fault» status, boards powered by it («Boards» objects) go to low power consumption mode, securing battery storage Boards A board in the system is an electronic board containing hardware/software to maintain one object or a group of various system objects Board is an object providing identification of compound and periodical monitoring for the system integrity The «Board» object has the following parameters: - unique serial number of the board; - version of integrated software; - version of hardware; - manufacturing date; - type; - boards logical number in the system The «Board» can be in the following statuses: - «Disabled»; - «Enablement»; - «Enabled»; - «Disablement»; The «Board» object has the following functions: - «Start»; - «Stop»; - «Setting of system time»; The following types of the Board object are defined in the panel s structure: - input/output board (I/O); - indication and controls board (BKI); - main control board (MC); - GSM communicator (BSKM-2); - phone communicator (BSKT-2); - remote indicators (RI); Each «Board» type can have a range of specific parameters MC monitors the system integrity and synchronizes boards The system must be configured at first to properly function that is you should set logical numbers and the required values of specific parameters of boards in the system. The panel can be configured on access level 4 with special hardware/software facilities at the factory or by an installation company When power is applied all boards are in the Disabled condition. MC monitors compound and settings of the system and when correct date were detected it issues the Start command to all boards. Boards go to the Enablement condition where internal memory of the program and data are monitored. If the monitoring was successful the boards go to the Enabled condition and begin to fulfil the system object maintenance program. 15

16 If as result of monitoring of the compound and correctness of the system non-compliance was detected then the Start command is not given and the panel goes to the System error condition If non-compliance was detected by a board in the Enablement condition as a result of internal program memory and data monitoring, then the Board object goes to the Disabled condition, the panel goes to the System error state Communicators Communicator is a system s object providing notifications transmission about the panel s state on different communication channels in different formats Communicators can be several types depending on the notification transmission channel type For parameters, statuses and functions of different communicators please refer to the relevant manuals Remote indicator Remote indicator is an object indicating statuses of different system objects For parameters, statuses and functions of the remote indicator please refer to the relevant manual Event log Event log is an object providing recording and issue on demand the information about all events occurred in the system Information about the object type, its new status, and time of transition to the status is saved in the event log The event log is capable of storing up to 60 thousand events in the nonvolatile memory of MC The «Event log» object has the following parameters: - size; - record; - last record; The «Event log» object can be in the following statuses: - «Norm»; - «Overflow»; The «Event log» object has the following functions: - «Clearance»; - «Record index setting»; If an event occurs from any system s object this event is recorded in the event log, and the last record index is incremented by one When the event log is overflowed the object goes to the Overflow condition, whilst new events are recorded to the place of the oldest The event log s review is available on access level The event log s clearance is possible on access level Tamper contact Tamper contact is an object monitoring unauthorized opening of the panel s lid The tamper contact can be in the following statuses: - «Initialization»; - «Norm»; - «Alert»; The tamper contact has the following functions: 16

17 - «Reset»; When the panel is switched on, the tamper contact goes to the Initialization status and remains in this condition while the enclosure s lid is open. When the enclosure s lid gets closed the tamper contact goes to the Norm condition When the lid gets open the tamper contact goes to the Alert status The panel will automatically call the Reset function of the tamper contact when the Entering the system event occurs from any User object whilst, if the tamper contact was in the Alert condition it will go to the Initialization status. 5.4 Main modes of operation General overview The panel can be simultaneously in the FIRE, FAULT, DISABLEMENT, ALARM, TEST modes indicated by various illuminations of LED indicators of the BKI, internal buzzer sounding and outputs statuses The internal buzzer will sound in a different tone in FIRE, FAULT, ALARM modes FIRE mode The red indicator Fire flashes, the internal buzzer generates the Fire signal, the Fire output is activated (enabled) sending the signal to CMS, the Light LED and sounders are on, the Norm output goes to passive state, on alphanumeric display in the AL status box the Fire field pops up indicating the number of the first and the last AL in the Fire status, the number of loops in the Fire status, number and name of the current loop being scanned in the Fire condition The FIRE mode can be reset on access level 2 by pushing the [Reset] button or from the Reset item of the context menu of the relevant AL FAULT mode The panel defines the following faults and statuses: SC and OC of AL, SC and OC of any output, 220 V failure, critical discharge or BAT absence, charger fault, system error, disconnection with CMS In the FAULT mode the general Fault indicator flashes, the internal buzzer issues the Fault signal, the «Fault» activates sending the signal to CMS, the «Norm» output goes to passive state The following indicators flash yellow depending on the fault type: ««Fire» output fault»; «Fault output fault»; «Sounder fault»; «CMS connection fault ; «System error»; Upon detecting a fault of any AL, AL fault field pops up on the alphanumeric display in AL status box indicating the first and the last AL in the fault status, number of AL in the Fault status, number and name of the current AL being scanned in Fault status When detecting a fault it is feasible to scroll the list of all current faults including those without an indicator The FAULT mode resets automatically (on fault clearance) or on access level 2 by pressing the Reset button. If after resetting the fault is not cleared then the Fault condition shall occur again DISABLEMENT mode The DISABLEMENT mode activates as a result of the following actions in the authorized user mode: AL disablement; light alarm device muting («LIGHT»); 17

18 sound alarm device muting («SOUND»); «Fire» outcoming signal muting («FIRE»); «Fault» outcoming signal muting («FAULT»); muting of outputs OUT1 OUT8; The mode is displayed with continuous light of the general indicator Disablement, as well as indicators: ««Fire» output disablement»; ««Fault» output disablement»; «Sounder disablement»; «CMS disconnection»; In this mode «FAULT» output activates, «NORM» output goes to passive state On disabling an AL on the LCD display in the AL status box the DISABLED field automatically pops up indicating number of the first and the last AL in the Disabled status, number and name of the current AL being scanned in the Disabled condition. Note: If the «Fault» output is in the Muted state, then the «Fault» output activation shall not occur in the Disablement mode ALARM mode On opening the enclosure s lid in standby mode the tamper button shall trigger and the panel goes to the ALARM mode In the mode on the alphanumeric display in the navigation bar the TAMPER message pops up, the «ALARM» output activates sending the signal to CMS, the «Norm» output goes to passive state The ALARM mode resets after authentication of a user TEST mode The panel goes to the TEST mode after any AL or Output object has been transferred to the TEST mode by a user on access level The Test indicator continuously is lit yellow on the front panel of the enclosure in the mode Object status change in the TEST mode does not lead to output status change The «ТЕSТ» mode is reset by a user individually for each object on access level User interface General overview The panel can be controlled by a user by means of controls and multifunctional alphanumeric keypad. Current statuses of objects are displayed ob alphanumeric display, service information, notifications about events. Alphanumeric display contains 4 lines by 40 characters and conditionally divided into 3 main zones. System line (top), two informative lines and search line (bottom). The system line divided into 3 fields: The current box name is displayed in the left part, and commonly corresponds to the selected menu item or submenu (e.g.: «Disablement», «AL status», «AL list», «Output list», «Fault list».) The message about the current user in the system is displayed in the centre. For instance, «User2» reports the actions in the system are being implemented and registered on behalf of User 2. Absence of the current user name reports that none of users has been authenticated in the system. System date and time is displayed in the right part. The functions of system line fields differ in programming mode. For detailed information please refer to Section 8 Programming guide. 18

19 Information lines. It is the main display zone for object statuses and number of objects in the indicated status. The functions of system line fields in programming mode differs. For detailed information please refer to Section 8 Programming guide. Navigation bars. Information about events (FIRE, FAULT, DISABLEMENT), action list for the selected object (object context menu) or links to menus (main menu) are displayed in the bar. All messages of the navigation bar, object context menu and main menu consist of four fields connected to function keys [F1], [F2], [F3], [Menu] and located directly above keys. Example: < Zone status > User2 02/03/12 09:52 FAULT ZN01..02(2) ZN01:Cellar DISABL ZN03..05(3) ZN03:Garage (FAULT-2) (DISBL-3) The messages of the system line: the panel is in the main mode «<Zone status>», none of users in the system has been authenticated. The information line message: (FAULT AL02..04(2) AL02:Cellar) indicates the fault in AL (the number of loops in the status is indicated in brackets) There are two messages in the navigation line (FAULT-2) and (DISABL-2). The messages inform two ALs are in the DISABLEMENT status, and 2 ALs arein the DISABLED status. These messages are also items of the context menu. Pressing [F2] you shall go to the screen menu FAULTS, pressing [F3] «DISABLEMENTS». Control and review of object statuses, their parameters and modes can be made from different screen menus. The main display box is AL Status menu, where information about current statuses of all ALs, assorted by statuses is displayed. The priority is taken into account while assorting, the AL in FIRE status is first to be displayed, then FAULT, DISABLED and NORM. The number of first and last AL, the number of ALs in the status in brackets (2), as well as pointer and name of current AL in the status are displayed in the field of each status. The panel automatically goes to AL Status menu from all menus upon user activation timeout expiring. A user automatically goes to AL Status menu upon leaving the menu of access level 1 or 2 by pressing [Esc] key. A user automatically goes to AL Status menu upon leaving the Configuration menu of access level 3 by pressing [Esc] key. [F1], [F2], [F3] keys control invoking various functions of the selected object in the context object menu in the control mode. When the number of functions that can be invoked for the selected object is large, pops up above [Menu] key that signals about possibility to scroll the list of available functions by pressing [Menu] for one more time. While pressing [Menu] the cyclic change functions for [F1], [F2], [F3] occurs. All menus available for a user have the navigation system of the same type. Selection of objects or scrolling lines in the menu can be made using arrow keys: [ ], [ ], [ ], [ ], whilst the object selection mark is shifting. Upon pressing [Enter] the mark is indicating becomes active, the words starts flashing, and the context menu for the object pops up in the navigation line. 19

20 To make an object inactive you should either press [Esc] (in status/parameter review mode) or press [Enter] (in the parameter value entering mode). If there are no active objects pressing [Menu] shall cause the main menu display. Some boxes can contain big number of lines. In this case the presence of additional lines in the box is indicated with the symbols, which are in the extreme right positions of line 2 and 3. You can scroll using the keys [ ] [ ]. When an additional line is displayed one of lines on the screen disappears, the other line moves to its place, and the additional one is displayed in its place. You can access the system with authentication procedure entering your number and password in the separate box. The authentication procedure is invoked automatically when trying to call functions of the object context menu (available on access level 2) or by a user from «UserIn» in the main menu. Example 1: From Zone status menu enter the Zone list menu and scroll functions of ZN01 control. < Zone status > User2 02/03/12 09:52 DISABL ZN17..32(16) ZN17:Seventeenth NORM ZN01..16(16) ZN01:First Loop - invoke the main menu by pressing [Menu]: < Zone status > User2 02/03/12 09:52 DISABL ZN17..32(16) ZN17:Seventeenth NORM ZN01..16(16) ZN01:First Loop ( Zones ) ( Outs ) ( Fault )... - enter Zone list menu by pressing [F1]: <Zone list> User2 02/03/12 09:52 ZN01:First loop :NORM ZN02:Second loop :NORM - activate ZN01 by pressing [Enter].This procedure requires user authentication. Therefore in this case authentication procedure is automatically invoked, as no user has been logged in for this moment. Enter access code: ( Ок ) (Cancel) - in series enter numbers of the user s access code. Enter access code: **** ( Ок ) (Cancel) 20

21 - press [Enter] or [F1] (confirmation of password entering). Consequently the back-off to the previous box occurs (< Zone >): <Zone list> User2 02/03/12 09:52 ZN01:First Loop :NORM ZN02:Second Loop :NORM - press [Enter], activate ZN01, while the context menu of the object pops up in the navigation line, the selected object ZN-1 starts flashing: <Zone list> User2 02/03/12 09:52 ZN01:First loop :NORM ZN02:Second loop :NORM ( Reset ) ( Enable ) (Disable)... You can invoke AL reset function in the menu pressing [F1], [F2] - «AL enablement», [F3] - «AL disablement»; the function list will be changed when pressing [Menu] and you will see on the display: < Zone list > User2 02/03/12 09:52 ZN01:First loop :NORM ZN02:Second loop :NORM (Res All) (Test ON) (TestOFF)... In the menu pressing [F1] you can invoke Reset all zones», [F2] - «Zone test mode enablement», [F3] - «Zone test mode disablement»; function list will be changed when pressing [Menu] and you will see on the display: < Zone list > User2 02/03/12 09:52 ZN01:First Loop :NORM ZN02:Second Loop :NORM ( Reset ) ( Enable ) (Disable)... - quit the context menu of ZN01 object pressing [Esc], the object s line stops flashing: <Zone list> User2 02/03/12 09:52 ZN01:First Loop :NORM ZN02:Second Loop :NORM 21

22 - quit the Zone List menu and go to the main menu Zone status pressing [Esc]: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth Example 2. View the list of the main menu items: < Zone status > User2 02/03/12 09:52 NORM ZN01..16(16) AL01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth - invoke the main menu by pressing [Menu]: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First loop DISBL ZN17..32(16) ZN17:Seventeenth (Warning) (Faults) (Zone list)... In the menu pressing [F1] you can invoke the menu Warning, [F2] menu «Faults», [F3] - «Zone List» menu; pressing [Menu] the following menu items will be displayed: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth (Outs) (Commun) (Config.)... In that case pressing [F1] you can invoke the Outputs menu, [F2] - «Comminicators» menu, [F3] - «Configuration» menu; pressing [Menu] the following items will be displayed: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth (Log ) (UserIn ) (UserOut)... In this menu pressing [F1] you can invoke Log box, [F2] User authentication, F3 - UserOut ; pressing [Menu] the following items will be displayed: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth (Warning) (Faults) (Zone list)... 22

23 - quit the main menu pressing [Esc]: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth Example 3. You need to reset ZN04 from the «Zone list» menu: < Zone list > User2 02/03/12 09:52 ZN01:First Loop :NORM ZN02:Second Loop :NORM - press [ ], then set the marker on the relevant zone: < Zone list > User2 02/03/12 09:52 ZN01:First Loop :NORM ZN02:Second Loop :NORM - invoke the context menu pressing [Enter], you will see ZN04 line flashing: < Zone list > User2 02/03/12 09:52 ZN03:Third Loop :NORM ZN04:Forth Loop :NORM ( Reset ) ( Enable ) (Disable)... - press [F1] to reset the selected zone: < Zone list > User2 02/03/12 09:52 ZN03:Third Loop :NORM ZN04:Forth Loop :NORM ( Reset ) ( Enable ) (Disable)... - to go to the main box press [Esc] twice on the display: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth ( Zones ) ( Outs ) ( Fault ) The fields containing the object list can be in the status box. These fields can be changed with the arrow keys [ ] and [ ]. 23

24 Example 4. In the menu «Zone Status», view numbers of zones in the Norm mode: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth - pressing [ ], [ ] set the marker in the Norm field line, you will see on the display: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth - pressing the arrow keys [ ] and [ ] view numbers of zones in the Norm status: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN02:Second Loop DISBL ZN17..32(16) ZN17:Seventeenth There are fields in the object parameter setting menu containing the list of possible parameter values. You can change the values after selection and activation of the necessary parameter. Select the parameter by setting the marker opposite to the name of the relevant parameter with the arrow keys [ ], [ ]. To activate the parameter press [Enter], you shall see the field of parameter value flashing, the parameter s context menu shall appear in the navigation line. You can change the parameter s value using [ ], [ ]. To save the parameter press [Enter]. To cancel changing the parameter press [Esc]. The panel will return to the parameter selection mode when you save or cancel the parameter change. Example 5. You need to change operation algorithm of ZN03 With verification to General in the zone configuration box: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN02:Second Loop DISBL ZN17..32(16) ZN17:Seventeenth - invoke the main menu pressing [Menu]: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Zone DISBL ZN17..32(16) ZN17:Seventeenth (Warning) (Faults) (Zone list)... 24

25 - press [Menu] key, the following items of the main menu will be displayed: <Zone status> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Zone DISBL ZN17..32(16) ZN17:Seventeenth (Outs) (Commun) (Config.)... - call the configuration menu pressing [F3]: Enter engineer s access code: - enter the engineer password (by default ) and press [Enter]: «Аrton-ХХF» - Configuration ( Zones ) ( Outs ) ( User )... Nu - invoke the zone configuration menu pressing [F1]: <Config> ZN:01 Name:First Loop Zone Type : Active&Passive Algorithm : With verification ( Help ) ( Edit ) ( Save ) Nu - if necessary set the marker opposite to the «ZN:» using [ ], [ ]; - press the [Enter] button make the field «ZN:» active, the number of zone starts flashing («01»); - using [ ], [ ] set the number of the relevant zone, «03» in that case; - to confirm the zone choice press [Enter]: <Config> ZN:03 Name:Third Loop Type : Active&Passive Algorithm : With verification ( Help ) ( Edit ) ( Save ) - using [ ], [ ] set the marker opposite to the «Operation Algorithm»: <Config> ZN:03 Name:Third Loop Type : Active&Passive Algorithm : With verification ( Help ) ( Edit ) ( Save ) 25

26 - press [Enter], make the «Operation Algorithm:» field active, the parameter value With verification shall flash; - using [ ], [ ] set the necessary parameter value, in that example General ; - to confirm your choice press [Enter]: <Config> ZN:03 Name:Third Loop Type : Active&Passive Algorithm : General ( Help ) ( Edit ) ( Save ) - to save changes in nonvolatile memory of the panel press the [F3] button (Save). There are fields in the parameter value setting menu containing digital or character parameter values which require entering the line of text (e.g., name of AL) or numerical value (e.g., time of output s active status). A user can change the fields after choosing and activation of the relevant parameter. When you enter a text the cursor shall be flashing on the display. The user can enter Cyrillic or Roman characters to some fields. In that case you can toggle between active layouts using «Alt» key, as a result the active layout indicator on the extreme right changes. The two-character active layout indicator indicates: «EN» - to enter Roman capital letters, «en» Roman lowercase letters, «RU» Cyrillic capital letters, «ru» Cyrillic lowercase letters, «Nu» numerical data. You can enter characters in the selected layout from the numerical keypad by single or multiple pressing a necessary key. In Cyrillic/Roman character entering mode the [0] key is for entering characters Space, «.», «,», «!», and [1] to enter «+», «-», «(», «)». When you hold down [Shift] the entered character changes the case (lowercase to capital and vice versa). The characters of the layouts are coated on keys in alphabetical order. You should multiply press keys with an interval of not more than 0,5 sec. If you exceed the interval the character is considered to be entered and the cursor is located to the next point. You can delete any character to the left of the cursor by pressing the key «Zone Status» window The Zone status window is displayed in the main mode: <ZoneStatus> User2 02/03/12 09:52 NORM ZN01..16(16) ZN01:First Loop DISBL ZN17..32(16) ZN17:Seventeenth In the bottom line (navigation line) the information about the active user and a tip about user actions are displayed if the menu is not activated and no faults were detected in the system. If there are any faults in the system then the navigation line contains reference to the Faults menu item. In the top line the information about the selected box AL Status, system time and date is displayed Second and third lines contain information about all AL statuses, assorted on the following descending statuses: FIRE, Attention, Fault, Norm, Test, Disabled. In each status line the information about the name of status, number of the first and the last AL in this status, and total number of AL in that status. 26

27 Schematic diagram of screen windows, menus and control functions The full schematic diagram of screen windows, menus and control functions available to a user is shown in Figure Fig

28 6. SAFETY ISSUES 6.1 Attention! All operations with the panel must be made by operators (users) with the closed panel s lid. 6.2 The installation, mounting, connection and maintenance must be performed by the competent service personnel. 6.3 It should be kept in mind that the 220 V mains voltage in operating state is connected to input terminals that is dangerous for human life. 6.4 The installation, removing, wiring and repair of the panel should be made when the A.C. mains is off. 6.5 The mounting works with the panel should be done using an electrical tool with the voltage not more than 42 V and power not more than 40 W that has healthy isolation of current leading circuits from the electrical tool housing. 6.6 The fire safety rules should be kept when performing works with the panel. 6.7 The use of the panel without earthing its enclosure is forbidden. 6.8 The use of the panel in premises with aggressive admixtures causing corrosion is prohibited. 7. HOW TO PREPARE THE PANEL FOR OPERATION 7.1 Please keep the following sequence of wiring and configuration for proper operation of the panel. After the panel has been installed: - Connect the alarm loops. Short the inputs not in use with resistors supplied with the panel. - Wire sounders and beacons. - Wire outputs to CMS. - Wire the auxiliary outputs «OUT1» «OUT8». Short the outputs not in use with resistors supplied with the panel. - Enable the lithium battery for real time clock. - Install and wire the rechargeable battery. - Wire the mains power. After switching on the mains power supply check the LED indicators on the front panel of the enclosure. Two green indicators of the primary power and back-up power should be lit. If they are not, ensure all devices on the circuits are correctly connected, check for presence and integrity of safety fuses. - Record the basic current of all connected loops in the configuration mode. - Configure the panel. - In the end, clear the event log before commissioning. The function of clearing the event log is in submenu LOG of the system menu. 8. WIRING AND INSTALLATION 8.1 Installation The panel should be mounted at a height convenient for operating and maintenance The panel can be mounted vertically. The marking on the panel should be made according to the installation dimensions (Appendix 1) To prevent the panel going to the fault mode if the panel has been switched on without loads connect 3,3 kohm resistors (supplied with the panel) in parallel to terminals of AL and outputs The connection of wires and cables should be made through the holes at the panel s bottom. (see Appendix 3) AL wiring Connect alarm loops to contacts «Ch1»...«Ch16» and of I/O PCB (see Appendix 4). To ease the mounting screw joints are made in a way that allows to remove contact batch from the I/O board, connect to them alarm loops, and then fix them back to the I/O board. To remove the screw joint batch from the I/O, insert a thin screwdriver between the PCB and contact batch and hook them with slight effort. Pull the contact batch and remove from pillars. On connecting alarm loops to the screw joints fit the contact batch back on the pillars Max AL resistance not considering EOL resistor should not exceed 470 Ohm. 28

29 Two jumpers «12/24 Ch1-8» and «12/24 Ch9-16» are fitted on the I/O. Set the zone supply voltage using the jumpers. Please note that each jumper sets the voltage for each group Zone1 Zone8 and Zone9 Zone For wiring diagrams for various zones (active, passive, combined) please refer to Annex To prevent the panel from going to the FAULT mode, connect 3,3 kohm load resistors (supplied with the panel) to the inputs not in use Record the basic current of the zone for each new connected zone in the programming mode Sounder/beacon wiring Connect sounder and beacon to terminals «LIGHT»- and «SOUND»- (see Annex 4) V 300 ma sounders (bells, sirens)/beacons (strobe lights) can be connected to the panel To control the sounder line continuity fit a 2-10 kohm resistor from the load side parallel to sounder terminals You can set modes of the outputs «LIGHT» and «SOUND» when programming the panel Connecting outputs and CMS Outputs «FAULT», «FIRE», «ALARM» control the CMS communication equipment Connect communication devices to terminals «FAULT»-, «FIRE»-, «ALARM»- (see Annex 4) To control the line continuity fit a 2-10 kohm resistor parallel to CMS output load terminals You can set modes of the outputs «FAULT», «FIRE», «ALARM» when programming the panel Connecting real-time clock power supply There is a compartment on the MCU with a connected lithium battery powering the real-time clock. The battery is deactivated for the time of storage and transportation. Set the jumper «BAT OFF» into the «ON» position (to the extreme right) to activate the battery CAUTION! It is advisable to deactivate the battery while storing, transporting, or for durable inactivity. Detach the jumper «ВАТ» and shift it to the position «OFF» (to the extreme left). Before commissioning the panel, detach the jumper «ВАТ» and shift it to the position «ON» (to the extreme right). Then set the real time clock on activating the battery (see the Programming guide) To replace a lithium battery you must disconnect the battery. Remove the BAT jumper and set it to the «OFF» position (to the extreme left). Swing the fixing flag on the holder out of the way and remove the battery. Install a new battery keeping the polarity. Remove the BAT jumper and set it to the «ON» position (to the extreme right). You should set the real time clock on switching the battery (see the Programming guide) Mains wiring Attention! The mains supply must be connected to the panel only by a qualified and technically experienced person The panel can be wired to the mains supply only using the diagram with differential protective relay in the main distribution board Connect the terminal of the terminal block to grounding mat rated at not greater than 4 Ohm Check for presence and proper operation of 1.0 А fuse in the terminal block Connect the dead power cable to terminals «220 V» so that the phase wire is connected to «L» terminal and the neutral wire - to terminal «N» Fix the cable using a clip Apply power to the panel. If after applying the mains supply none of the indicators are not lit check for presence and correct operation of 1.0 A fuse in the terminal block Battery wiring Locate the rechargeable battery as shown in the figure in Annex 3. Connect black wire with the minus terminal, red wire with the plus terminal of the battery. 29

30 You must keep the polarity while connecting the battery. Incorrect polarity leads to outage of the «Fuse1» on PSU Wiring and usage of outputs «OUT1».. «OUT8» on I/O It is allowable to connect a load rated at not greater than 300 ma to each output «OUT1» «OUT8». Make sure that the total current consumption of all outputs «OUT1» «OUT8» does not exceed 0.8A. If you need to connect more powerful loads use blocking relays To prevent the panel going to the FAULT mode you should fit 3.3 kohm resistors provided in the panel s accessory pack to the outputs not in use To control circuit integrity you should fit a resistor from 1 kohm to 10 kohm to each output «OUT1»..«OUT8» from the load side The outputs «OUT1»..«OUT8» of I/O boards are intended for performing of various user functions User can program output operation logics by the way of setting of system object parameters logical expressions on the 4 th access level using special software and tools By default outputs «OUT1»..«OUT8» are activated on detecting the Fire condition in two adjacent loops by logical operation AND to arrange fire fighting systems The output «OUT1» is linked to the pair: AL1 (zone 1), AL2; «OUT2» AL3, AL4; output «OUT8» - AL15, AL USER GUIDE 9.1. General information You can access to the panel controls after authentication of the user. Nine users are predefined in the system: one engineer (user 1), and 8 authorised users. Each user has rights to control one or several zones, that allows to delimit responsibilities for guarded objects between users. The authorized user controls can be accessed by calling «UserIn» and in the authentication window you should enter the user access code. After that, if the access code is correct, the inscription in the navigation line will be changed to «UserN» where N is the user s number. To exit the authorised user mode call the «LogOut» of the main menu or automatically if no key has been pressed within 1 min. For factory default user access codes please refer to p Controls available for an authorized user: disabling or enabling zones; resetting of the modes FIRE, FAULT, ALARM; resetting of all zones; disabling or enabling sounders; disabling or enabling the fire output; disabling or enabling the fault output; testing the indicator lights and internal buzzer; calling any object function; 9.2. Zone disablement/enablement To disable a zone invoke Disable item of the context menu in the authorized user mode in windows Zone status and Zone list. As a result of disablement the zone will be physically disabled, the FAULT output gets activated (disabled), the general indicator Disablement starts continuously illuminating and zone goes to the DISABLED state. After deenergizing the panel and then applying the power the disabled zone statuses retain. Zones are enabled in the authorized user menu by calling the Disable item of the context menu of thee Zone object in windows Zone status and Zone list. It is impossible to disable/enable zones by a user who is not entitled to control the zone. User rights can be set in the programming mode. 30

31 9.3. Resetting all zones, FIRE, FAULT and ALARM modes Resetting of the modes can be made in the authorized user mode by pressing the RESET button Sounder disablement Sounders can be disabled through the Warning menu. Disablement of sounders (outputs «LIGHT» and «SOUND») is implemented in the authorized user mode by calling the Silence item of the context menu of objects «OUT5 Light» and «OUT6 Sound» in the Output list window. Disablement of sounders is indicated with continuous yellow light of general indicators Disablement and Disable sounder Disablement of FIRE output The FIRE output is automatically disabled when resetting the FIRE mode. To temporally disable the signal in the FIRE mode activate the SILENCE item of the context menu of object «OUT3 Fire» in the window Output list. Disablement of the Fire output is indicated with continuous yellow light of general indicators Disablement and Disable Fire output Disablement of FAULT output The FAULT output is automatically disabled when the fault has been cleared or after resetting the FAULT mode. To temporally disable the signal in the FAULT mode activate the SILENCE item of the context menu of object «OUT3 Fault» in the window Output list. Disablement of the Fault output is indicated with continuous yellow light of general indicators Disablement and Disable Fault output Event log view You can view the event log in the authorized user mode by calling the LOG of the main menu. Information about total number of records, number and contents of the current record is displayed in the event log view box. The record includes information about the object, its new state and time that the event occurred. A user can successively view records in the event log box by clicking Back and Next, or point to the last recorded event or to the indicated by the user by clicking End and Go to Checking alphanumeric display, light indicators and internal buzzer for proper operation To check alphanumeric display, all light indicators and internal buzzer for proper operation press the TEST button. After that all indicators shall flash 5 times, at the same time all character cells of the alphanumeric display shall successively be filled with numbers 1 to 5, and buzzer shall sound. The test is available both on the access level two (authorized user mode) and on the level one (before user authentication). 31

32 10. PROGRAMMING GUIDE How to enter programming mode You can gain access to the programming mode from any dialog box through Programming of the main menu. After that enter the engineer password (engineer factory default - [1][2][3][4][4][3][2][1]). The programming menu items become available upon entering the correct password How to program the panel You can change object parameters by programming the panel. As a rule, programming menu items correspond to object types (e.g., Zone, Outputs, Users ). The marker is located in the object parameter setting window, pointing to the current field or parameter. Use [ ], [ ] buttons to move between fields (parameters). To activate the current field (parameter) change option press [Enter] or functional button «Edit». The field (parameter) change process can be 2 types: - choice from the list of available values (use [ ], [ ]), with a field that includes the parameter value flashing. - entry of character number from the keypad, with the vertical bar (cursor) in enter position on the screen flashing. To confirm changes press [Enter] or the functional key «ОК». To cancel changes press [Esc], or the functional key «Cancel». The confirmed changes are saved to panel s non-volatile memory the when you activate «Save» in the context menu for the current object How to program ZONE To activate the zone programming window use AL item of the programming menu. The display will look like the below: <Config> AL:01 Name:Zone one AL type : Combined Operation algorithm : With verification ( Help ) ( Edit ) ( Save ) You can change the following parameters in the window: Name of zone (Name). Defines the character name of the zone, which will be displayed in status windows AL status and AL list. The name may contain capital and small Latin or Cyrillic letters, numbers, space, brackets etc. Maximum number is 14 characters. AL type. Defines the way of zone current change processing. The following values of the parameter are available: Combined; Active; Passive. AL operation algorithm. Sets the way of the FIRE condition detecting in a zone. The following values of the parameter are available: With verification; Without verification; Two detectors activation (2 det. activation). Standby current. Sets the primary zone current through which zone current change is calculated. When the parameter is activated by pressing [Enter], the context menu item Store in memory becomes available through which the actual current in zone is stored in memory. Threshold activation current of the first active detector (Curr Thres. Up1). Sets the value of threshold (current raise) of first active detector relative to the primary standby current of a zone (standby zone current). The value can be set from 0,5 до 8,0 mа in increments of 0,5mА. 32

33 Threshold activation current of the first passive detector (Curr Thres. Dn1). Sets the value of threshold (current drop) of first passive detector relative to the primary standby current of a zone (standby zone current). The value can be set from 0,5 до 8,0 mа in increments of 0,5mА. Threshold activation current of the second active detector (Curr Thres. Up2). Sets the value of threshold (current raise) of second active detector relative to the first activated detector. The value can be set from 0,5 до 8,0 mа in increments of 0,5mА. Threshold activation current of the second passive detector (Curr Thres. Dn2). Sets the value of threshold (current drop) of the second passive detector relative to the first activated detector. The value can be set from 0,5 до 8,0 mа in increments of 0,5mА. AL reset time. Sets the reset period for a zone. The value can be set within 0 and 99 seconds. Waiting-to-ready time (Wait time). Sets the time of zone waiting-to-ready after applying power supply or AL reset. The value can be set within 0 and 99 seconds. Verification time (Verif time). Sets the time of reactivation or activation of second detector in the zone depending on the effective zone operation algorithm. The value can be set within 1 and 255 seconds. ( Value 0 waiting till deenergizing) How to program OUTPUT To activate the output programming window use the Outputs item of the programming menu. The display will look like the below: <Config> Output:01 Name:Fault Operation algorithm : With inversion Active period,s : 0 ( Help ) ( Edit ) ( Save ) You can change the following parameters of outputs in the window: Output name (Name). Defines the character output name which will be displayed in status windows Output list. The name may contain capital and small Latin or Cyrillic letters, numbers, space, brackets etc. Maximum number is 14 characters. Output type. The following values of the parameter are available: - standard; - 4 wire zone power supply; - +12V not disabled output; - FIRE1; - FIRE2; - FIRE3; - Disabled. Operation algorithm. Designates direct or inverse mode for an output. The following options of the parameter are available: - With inversion; Without inversion. Active period. Sets the time of output active status. The value can be set within 1 and seconds (0 non limited active time). Delay period. Sets the delay time for output active period. The value can be set within 0 to 255 seconds. Automatic restore time (Disabl time). Sets the time in that the output goes from disabled to actual state. The value can be set within 1 to 255 seconds (0 switch off the auto restore mode). Allow to enable at SC (Allow ON at SC). Sets the permission to activate output at SC in its load. The following options of the parameter are available: 33

34 Yes; No. Active period in active state (Та1 act/act). Sets the time of output s active period in active state. The value can be set within 0,1 to 25,5 seconds (0 switch off the dynamic mode). Passive period in active state (Та2 pas/act). Sets the time of output s passive period in active state. The value can be set within 0,1 to 25,5 seconds (0 switch off the dynamic mode). Active period in passive state (Тp1 act/pas). Sets the time of output s active period in passive state. The value can be set within 0,1 to 25,5 seconds (0 switch off the dynamic mode). Passive period in passive state (Та2 pas/pas). Sets the time of output s passive period in passive state. The value can be set within 0,1 to 25,5 seconds (0 switch off the dynamic mode) How to program USER To activate the user programming window use the User item of the programming menu. The display will look like the below: <Config> User 1 (Engineer) Level 3 AL: ( Help ) ( Edit ) ( Save ) You can change the following parameters of users in the window: Allow to control AL (AL). Sets the list of AL available to control for the user. Available ALs are marked with «+», non available - with «-». On activation of the parameter with [Enter], the choice of the relevant AL is made with the keys [ ] [ ], and setting of permissions with [ ], [ ]. User access code (Access code). The password is a line from 0 to 15 characters for users 2 9 and from 8 to 15 characters for user 1 (engineer) How to set system date and time To activate the system date and time programming window use Set date and Set time in the Additional submenu of the programming menu. The display will look like the below: <Config> Set date and time 14 Jun :41:24 (Set) (Cancel) You can move between parameters using the keys [ ] [ ], and setting of values is made with [ ], [ ]. Activation of new system date and time is done with the help of the Set item of the window menu How to reset engineer password to factory defaults When necessary you can reset the engineer password to factory default following the below steps: - deenergize the panel (both mains and battery); - open the lid and fit the jumper Р7 of MCU; - apply power and in not less than 5 sec. remove the jumper. When the procedure is complete the engineer password will be reset to factory default How to reset values of ZONE and OUTPUT to factory defaults To reset all parameters of AL and Output to factory defaults use Reset FACP in the Additional submenu of the programming menu How to autoconfigure the panel After you have added a new board or replaced a failed one perform the Autoconfiguring function using the item AutConf from the programming menu. 34

35 10.9. How to exit programming mode To exit the programming mode press [Esc] a few times Factory defaults Users Password Rights to zones Rights to outputs 1 (engineer) All zones All outputs All zones All outputs Type Algorithm Cur Thr Up1 Zone Cur Thr Dn1 Cur Thr Up2 Cur Thr Dn2 Without 1 32 Combined 4 mа 1,5mА 3 mа 1 mа 5 sec 1 sec 180 sec verification NB. All zones are named by default by the following format: «Zone ХХ», where «ХХ» - number of zone from «01» to «16». Outputs Name (designation on PCB) Algorithm Active time, sec Delay time, sec Transient time, msec Disabled time, sec Allow ON at S/C Allow ON at O/C Allow ON at TEST Та1 (act/act), sec Та2 (pas/act), sec Reset time Тp1 (act/pas), sec Wait Time Тp2 (pas/pas), sec Verif time 1 «FAULT» With inversion Not limited (disabl.) no yes no «NORM» W/o inversion Not limited (disabl.) no yes no «FIRE» W/o inversion Not limited (disabl.) no yes no «ALARM» W/o inversion Not limited (disabl.) no yes no «LIGHT» W/o inversion (disabl.) no yes no «SOUND» W/o inversion (disabl.) no yes no «OutXX*» W/o inversion Not limited (disabl.) no yes no * - ХХ numbers for outputs 7 14 correspondently. 35

36 11. MAINTENANCE It is advisable at least annually to replace the lithium battery for the real time clock. (see Connecting the real-time clock power supply) 12. GUARANTEE The manufacturer guarantees the compliance of the panel with the technical specifications provided the user keeps the rules of usage, proper transportation, storage and installation specified by the technical specifications. The panel is warranted for 12 months from the commissioning date but no longer than 18 months from the shipment date to the customer s address. 13. COMPLIANCE/ PACKING CERTIFICATE The ARTON-16F fire alarm control panel complies with the requirements of DSTU EN 54-2 and DSTU EN The ARTON-16F has been packed in compliance with the factory rules complete with the items as shown in table Table 17.1 Name Quantity Serial number ARTON-16F fire alarm control panel 1 Operational manual 1 Spare parts and accessories (according to Section 14) 1 Manufacturing date..201 This product has been successfully tested by the quality control department and was released for sale according to the existent specifications. Quality control mark 14. SPARE PARTS AND ACCESSORIES Table 18.1 Name Qnty 1 3 А Fuse А Fuse 1 3 3,3 kohm 0,25W Resistor ,4 kohm 0,25W Resistor 16 36

37 1 ANNEX 1. ARTON-16F front panel

38 1 alphanumeric display (4 lines x 40 characters); 2 indications and controls; 3 dual-colour indicators of «AC» and «Back-up» power indicate the mains, battery power supply and charger (green light norm, yellow fault); 4 general indicators of Fire, Fault, Disablement, Test modes; 5 indicators of Disablement mode for Fire, Fault outputs, sounders and CMS communication devices; 6 reset button of Fire mode; 7 indicators of Fault mode for Fire, Fault outputs, sounders, CMS communication devices; System error; 8 test button for alphanumeric display, LED indicators and internal buzzer; 9 panel lid s key; 10 silence button for internal buzzer; 11 reset button for output delay; 12 functional buttons for menu items. Button functionalities are displayed in the bottom part of the display (in the navigation line); 13 menu key launches the main menu (each following pressing leads to going to the next point); 14 alphanumeric keypad with cursor control keys; 15 indicators of signal transmission status to CMS «Fire», «Fault», «Disablement», «Test», and indicator of warning system activation; 16 indicator of output delay status (presence, off/on); 17 indicator of disabled internal buzzer; 38

39 ANNEX 2. Dimensions Upper mounting bracket. Lower mounting bracket. 39

40 ANNEX 3. Location of PCBs, units, components inside the cabinet main control PCB (MCU); 2 input-output PCB (I/O); 3 holes for cable entry; 4 power supply PCB (PSU); 5 terminal block with 1A fuse holder for mains connection; 6 mains cable clamp; 7 rechargeable battery (BAT). 40

41 ANNEX 4. Layout of Main Control PCB and Input/Output PCB Ch1 Ch16 outputs for zone connection; Out1 Out8 outputs for control of automatic fire fighting equipment (AFFE), activating when the Fire status has been registered in two adjacent zones (zones united by AND function). The panel can perform the other functions depending on the panel s settings; LIGHT beacon output (light alarm); SOUND sounder output (sound alarm); NORM terminal block for remote indicator «NORM»; FIRE terminal block «FIRE» to CMS ; ALARM terminal block «ALARM» to CMS; FAULT terminal block «FAULT» to CMS; NB. To monitor line integrity of all outputs (AFFE output, CMS output, outputs to sounders/beacons «Alarm», «Light», «Sound») fit resistors from 2 kohm to 10 kohm parallel to loads (not on the drawing). Resistors should be installed from the load side. 41

42 ANNEX 5. Typical wiring diagrams Wiring diagram for active detectors (SPD type and others) Fig. 6.1 Quantity of detectors must be such so that total current consumption of all detectors in standby mode is not greater than 3 ma. At the same time, in compliance with EN54-2:2003, the maximum quantity of detectors per zone must not exceed 32. The value of limiting and EOL resistors should be chosen depending on zone voltage. For 15 V: CLR = (680 Ohm - 1,5 kohm), EOLR (1,2kOhm 2kOhm). For 24 V: CLR= (1,1kOhm 3kOhm), EOLR (2,4kOhm - 3,9kOhm). Wiring diagram for heat detectors (SPT-2A, SPT-3A, FT series) Fig. 6.2 Quantity of detectors must be such so that total current consumption of all detectors in standby mode is not greater than 3 ma. At the same time, in compliance with EN54-2:2003, the maximum number of detectors per zone is 32. The value of limiting and EOL resistors should be chosen depending on zone voltage. For 15 V: CLR = (680 Ohm - 1,5 kohm), EOLR (1,2kOhm 2kOhm). For 24 V: CLR= (1,1kOhm- 3kOhm), EOLR (2,4kOhm - 3,9kOhm). 42

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F ISO 9001:2008 CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F OPERATIONAL MANUAL Private enterprise "ARTON" 6 Prutska street Chernivtsi 58008 Ukraine EN 54-2 EN 54-4 For further information please

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 11/01.17 Contents 1. Introduction... 3 2. Terminology... 3 3. Function... 4 4. Technical features... 4 4.1 Fire alarm lines... 4 4.2. Current thresholds

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

S INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL

S INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL S2000-4 INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL Installer s and User s manual S2000-4 INTRUSION&FIRE AND ACCEESS CONTROL PANEL ATTENTION! To modify configuration parameters use the program uprog.exe

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 4/02.11 Contents 1. Introduction... 4 2. Terminology... 4 3. Function... 5 4. Technical features... 5 4.1 Fire alarm lines... 5 4.2. Current thresholds

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual S2000-ASPT Fire Alarm and Extinguishing Control Panel Engineer s and User s Manual FIRE ALARM AND EXTINGUISHING CONTROL PANEL ATTENTION! To modify the panel configuration parameters use the program UProg.exe

More information

CONTROL AND INDICATOR MODULE. Potok-BKI INSTRUCTION MANUAL

CONTROL AND INDICATOR MODULE. Potok-BKI INSTRUCTION MANUAL CONTROL AND INDICATOR MODULE Potok-BKI INSTRUCTION MANUAL 1. TECHNICAL DATA 1.1 General 1.1.1 The control and indicator module Potok-BKI of version 1.00 (hereinafter referred to as the module) is designed

More information

UniPOS Wireless Fire Alarm Control Panel VIT 01 WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL

UniPOS Wireless Fire Alarm Control Panel VIT 01 WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL Revision 8/10.13 Instruction manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.3. 4.4. 5. 5.1. 5.2. 5.3. 6. 6.1. 6.2. 6.3. 7. 7.1 7.2. 7.3. 8. 8.1. 8.2. 8.3.

More information

Ref.1067/032 Ref.1067/042

Ref.1067/032 Ref.1067/042 DS1067-033A Mod. 1067 LBT8631 BUS CONTROL PANEL 8/32 INPUTS Ref.1067/032 Ref.1067/042 USER MANUAL TABLE OF CONTENTS 1 PREFACE... 5 2 COMMAND DEVICES... 6 2.1 1067/021 DISPLAY KEYPAD... 6 2.2 ELECTRONIC

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Orion ISS. Intrusion and Fire Alarm Panel. Signal-10. User s Manual

Orion ISS. Intrusion and Fire Alarm Panel. Signal-10. User s Manual Orion ISS Intrusion and Fire Alarm Panel Signal-10 User s Manual This User s Manual is intended to help for studying operability principles and maintenance of Signal-10 Intrusion and Fire Alarm Panel of

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL

STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL IMPORTANT: Please note the Sterling 10 LCD keypad is not compatible for use with the Sterling 10 ICON keypad. RINS1413-1 Pyronix

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL USER MANUAL Read carefully before use GENERAL INFORMATION This device is a gas control unit with RS485 serial communication, based

More information

DYGIZONE GJD910 Lighting Controller & Enunciator

DYGIZONE GJD910 Lighting Controller & Enunciator DYGIZONE GJD910 Lighting Controller & Enunciator MASTER WIRING IDENTIFICATION Power up to the DygiZone and you will see: All the LED s (red,yellow,green and blue buttons) will flash All the LCD icons will

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

EC-P Zone Intruder Alarm System

EC-P Zone Intruder Alarm System EC-P10 10-20 Zone Intruder Alarm System Installation Manual Contents 1. System Overview... 4 System Configuration... 4 Control Panel... 5 Remote Keypads... 5 EC-LED Remote Keypad... 5 EC-LCD Remote Keypad...

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

BURGLAR ALARM PANEL BS-468

BURGLAR ALARM PANEL BS-468 BURGLAR ALARM PANEL BS-468 Contents 1. Description... 3 2. Instructions for the user... 4 2.1Basic operations... 4 Complete system.... 4 Split system.... 4 2.2 Armed system indication... 5 2.3 Advanced

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

QA16 Addressable System

QA16 Addressable System QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.

More information

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Operating instructions Vigilon panel and Network node Fire detection and alarm system Healthy 15:45 Fault Power Fault Vigilon Fire System GENT 2015 Designed to EN54 Pt 2 & 4 System Fault Operating instructions Vigilon panel and Network node Fire detection and alarm system Test Fire Fault/Dis

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A DS1067-062C Mod. 1067 LBT20063 REMOTE CONTROLLABLE ALARM CONTROL PANELS Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A USER MANUAL TABLE OF CONTENTS INTRODUCTION... 6 1 CONTROL DEVICES... 7 1.1 1067/022 keypad

More information

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize)

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize) FAAST LT FIRE ALARM ASPIRATION SENSING TECHNOLOGY ADVANCED SET-UP AND CONTROL GUIDE CONTENTS Introduction....1 The FAAST LT Functional State Diagram....1 Password Procedure (to enter Maintenance Mode)

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 OPERATORS MANUAL AFP-300/400 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02) 9899-4155

More information

REPEATER FS5200R OPERATION MANUAL

REPEATER FS5200R OPERATION MANUAL REPEATER FS5200R OPERATION MANUAL 1. Function Repeater FS5200R receives and transmits data for Fire condition and Fault condition from remote fire control panels (repeaters) and provides information about

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

Fire Alarm Control Panel EN54 2 & Operation & Programming MAN

Fire Alarm Control Panel EN54 2 & Operation & Programming MAN ZoneSense PLUS Fire Alarm Control Panel EN54 2 & 4 1997 Operation & Programming MAN 2374-10 Responding to an Alarm 1. Indicators FIRE FIRE ZONE 1 ZONE 2 FAULT/DISABLED/ Z2 ZONE SEVEN Common Fire Indicator

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

FIRERAY 5000 range USER GUIDE

FIRERAY 5000 range USER GUIDE FIRERAY 5000 range USER GUIDE 0044-003-04 IMPORTANT PLEASE NOTE: The beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal.

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

BENTEL SECURITY declines all responsibility in the event of unauthorized intervention on the FireClass200 control panel.

BENTEL SECURITY declines all responsibility in the event of unauthorized intervention on the FireClass200 control panel. V4.2 BUI 0.1 061099 The FireClass200 is available in the following models: FC200 - Master panel with 4 A Linear power supply; FC200/S - Master panel with 2.5 A Switching power supply; FC200/SL - Slave

More information

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V1.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-1028 Issue 2 Fike s policy is one of continual

More information

Fire Command Keypad. XR5 User s Guide

Fire Command Keypad. XR5 User s Guide Fire Command Keypad XR5 User s Guide Silencing an Alarm While the fire alarm horns, strobes, or sirens are sounding use one of the following methods to silence the alarm depending on which type of keypad

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL Fire Alarm Control Panel & MANUAL CONTENTS SECTION -. Description of the fire control panel fascia.... Alarm.... Reset the system.... Sound and silence the alarms.... Read the Fire, Fault, Test and Disabled

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

HS-5100, HS-5200, HS-5400 ANALOGUE ADDRESSABLE CONTROL PANELS. User Manual. Approved Document UI-ELAN-02 Revision 03

HS-5100, HS-5200, HS-5400 ANALOGUE ADDRESSABLE CONTROL PANELS. User Manual. Approved Document UI-ELAN-02 Revision 03 HS-5100, HS-5200, HS-5400 ANALOGUE ADDRESSABLE CONTROL PANELS User Manual Approved Document UI-ELAN-02 Revision 03 This page is intentionally blank Page 2 of 42 Table of Contents 1 INTRODUCTION 5 1.1 Standards

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

DIGITAL TEMPERATURE RELAY TR-100

DIGITAL TEMPERATURE RELAY TR-100 LTD Research-and-Manufacture Company DIGITAL TEMPERATURE RELAY USER S MANUAL www.novatek-electro.com - 2 - Service manual is intended for getting acquaints with hardware, operation principals, modes of

More information

FIRE BRIGADE RESPONSE GUIDE. LoopSense. Fire Alarm Control Panel (AS4428 & AS & 4) Operation & Onsite Programming MAN

FIRE BRIGADE RESPONSE GUIDE. LoopSense. Fire Alarm Control Panel (AS4428 & AS & 4) Operation & Onsite Programming MAN LOOPSENSE FIRE BRIGADE RESPONSE GUIDE LoopSense Fire Alarm Control Panel (AS4428 & AS7240. 2 & 4) Operation & Onsite Programming MAN 1567-2 LOOPSENSE FIRE BRIGADE RESPONSE GUIDE Responding to a Fire Access

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

Intruder alarm panel Terxon MX Operating instructions

Intruder alarm panel Terxon MX Operating instructions Intruder alarm panel Terxon MX Operating instructions Operating instructions Perfect Security for home and office These operating instructions are an important product accessory. They contain important

More information

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V2.00) Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0959

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Intruder - Fire - Water Combined Alarm

Intruder - Fire - Water Combined Alarm 65 Intruder - Fire - Water Combined Alarm Installation Manual and User Operating Instructions TALE OF CONTENTS Page First Power-Up 2 Power Supply Unit 3 Input & Detection Circuits 3 Output & Alarm Circuits

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Power Wave LCD Keypads. Users Operating and Programming Guide Version 2.00

Power Wave LCD Keypads. Users Operating and Programming Guide Version 2.00 Power Wave LCD Keypads CR-16S CR-16M Users Operating and Programming Guide Version 2.00 P/N 7102265 Rev. C N.A May 2003 Contents Introduction...4 Meet the PowerWave Alarm Control System... 4 Typical Alarm

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

C2 Compact Range Installation & Programming Manual

C2 Compact Range Installation & Programming Manual C2 Compact Range Installation & Programming Manual Page 1 Onsite training is available and telephone technical support with optional remote access for further assistance is all part of the support we can

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM 2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM OPERATING INSTRUCTIONS MODELS: 2300 2500 2700 This information is relevant to systems fitted with Issue 4.1 (or later) Master Keypad Software, also to Networked

More information

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0 Release 3 System Program Version 3.8.0 Operator's Handbook Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330 Protecting life, environment and property... ASAFE-FO/FE Rev. I, 2009-02-27 COPYRIGHT

More information

Ammonia Leak Detector Manual

Ammonia Leak Detector Manual Ammonia Leak Detector Manual Document No. 70-PHW-1023-R2.5 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,

More information

8 plus and16 plus. User s Guide * # ent. esc GALAXY 16+ V2.XX TUE 30 JUN. IU ZST 962 Issue 2. A u B u

8 plus and16 plus. User s Guide * # ent. esc GALAXY 16+ V2.XX TUE 30 JUN. IU ZST 962 Issue 2. A u B u 8 plus and16 plus User s Guide GALAXY 16+ V2.XX 06.22 TUE 30 JUN 1 2 3 4 5 6 7 8 9 0 * # A u B u ent esc IU1-0018 ZST 962 Issue 2 Contents INTRODUCTION... 1 Glossary of Terms... 3 KEYPAD INFORMATION...

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information