1 Document: M70.1SGLENG Issue: 10/1998 Rev. : B.1 Intrinsic safety Photoelectric smoke detector SGLEx Installation and operating manual NOTIFIER ITALIA a Pittway Company
2 INDEX General 1 Construction 1 Operation 1 Technical Features 1 Instructions 2 Installation 2 Operating test 2 Operation in case of fire 2 Operation after fire detection 2 Maintenance 2 Sixmonthly maintenance 2 Cleaning 2 Troubles and remedies Zone trouble Alarm on the zone without fire Dimensions Intrinsic safety barrier wiring engndx.vp Installation and operating manual Doc. M70.1SGLExENG Rev. B.1 NOTIFIER ITALIA
3 INTRODUCTION General The aim of this device is detecting the danger condition (fire beginning), monitoring a series of environmental physical quantities depending on the internal danger condition. This device is used in potentially explosive areas together with an intrinsical safety barrier. Construction The detector consists of two parts: one fixed (base) and one removable (head). It is built externally in polycarbonate, while the internal parts are made of stainless steel. The head is attached to the base by a special bayonet type self locking system. The fixed base contains the wiring terminals, the indicating light (LED) and the contacts for the detector connection. The removable head contains the electronics circuits, the photoelectric cells and a labyrinth smoke chamber. The chamber itself is removable for maintenance and periodical cleaning. The detector is built with solid state components and the electronic circuits are protected against the humidity by the resin. Operation The photoelectric smoke detector is based on the principle of light scatter (tyndall effect). A light source generates a beam, while a receiver is situated opposite the transmitter, in an obscured position, therefore it does not receive any source of light in normal condition. When smoke or some particles go into the detector chamber, a part of the light reaches the receiver because it is reflected by the particles themselves. This will cause the detector alarm condition, therefore the LED placed on the detector base will turn on. TECHNICAL FEATURES Dimensions = diam. 100 mm, height 92 mm. Weight = 0,270 Kg. Body colour = white Terminal number = 2 Line voltage = 24 Vdc. Operating voltage = 15 0 Vdc. Current absorption = 5 micro A at 24 V Operating Temperature = 20 C 0 C ( 4 F 140 F) Humidity = less/equal 95% Air speed = max 5 mt/sec. CESI certificate = AD Class of risk = EEx ia IIC T SGLExManu.vp Installation and operating manual Pag. 1 Doc. M70.1SGLExENG Rev. B.1 NOTIFIER ITALIA
4 INSTRUCTIONS Installation The detectors are normally installed directly on the ceiling and/or on junction box. The wiring is carried out with bipolar cable according to the CEI normatives. The installation must be performed in compliance with CEI 4.2 normatives. Since it is an intrinsical safety device, the conductors must have a 1,5 mm 2 minimum section and cables have to run in separated cable conduits. The detector location must be performed according to the design drawings. The electric connection and the endofline resistances on the terminal detectors of each loop line, must comply with operating diagrams. Operating test Before starting the operating test be sure that the detector wiring and installation have been performed following the design indications and in compliance with the installation normatives.» Attention: if the detector is installed on a line mapped to a release system, put the release command board in RESET position. The operating test must be performed with a smoke generator located under the detector, by verifyng that the smoke goes into the detector itself. The turned on LED located on the detector base will confirm the detector set up which have to transmit the alarm condition to the control panel. If the sensor detects again an alarm condition, though a zone reset has been performed, it means that some smoke residual are in the detector. Before executing an operating test on a second detector, reset the zone and be sure that this one is not in alarm condition. Operation in case of fire When a fire occurs one or more sensors detect the smoke and transmit an analog signal to the control panel to indicate the alarm condition. The turned on LED located on the detector base indicates the alarm event. Operation after fire detection At the end of the cause which has generated the alarm condition, after having reset the zone on the control panel, if the alarm condition persists, it needs to remove the smoke from detectors and room. If it is not enough, check the detector and its line. In case of damages replace it. Sixmonthly maintenance MAINTENANCE Exclude release systems connected to the detection line. Performe a practical test on some detectors of each zone to verify the right operating. Tests must be programmed in order to periodically check the detectors. During the test verify that alarm transmission occure and the LED on the detector base be turned on. Cleaning This operation requires to remove the detector from the base and to open the labyrinth. Pag. 2 Installation and operating manual SGLEXManu.vp NOTIFIER ITALIA Rev. B.1 Doc. M70.1SGLExENG
5 TROUBLES AND REMEDIES Zone trouble Verify that all the detector are installed in field. Verify the line continuity and its integrity. Verify the presence of the endofline resistance and its value. Verify the intrinsic safety barrier Alarm on the zone without fire Verify which detector is in alarm condition and remove it. If after having reinstalled the detector the alarm condition persists, replace it. Verify the intrinsic safety barrier DIMENSIONS INTRINSIC SAFETY BARRIER WIRING RF 4 5 RF 4 5 MOD S RF = IT DEPENDS ON THE CONTROL PANEL OR THE CONNECTED MODULE SAFE ZONE DANGEROUS ZONE FOR DETECTORS SGLE EExi (tyndal effect smoke) SGLExManu.vp Installation and operating manual Pag. Doc. M70.1SGLExENG Rev. B.1 NOTIFIER ITALIA
6 Documento: M70.1SGLENG Edizione: 10/1998 Rev. : B.1 All rights reserved. All specifications are subject to change without notice. Delivery times depend on product availability. NOTIFIER ITALIA S.r.l. Via Grandi, San Donato Milanese (MI) Tel. : 02/ (ISDN) Fax : 02/
Barrier. ED /07/09 Release to production R.P. A ECO N DATE DESCRIPTION OF CHANGE CHG By ISSUE TITLE TC842B1007 AE PRODUCT SPECIFICATION
DESCRIPTION: TC842B1007 AE is a low-profile addressable analog intrinsically safe photoelectronic smoke sensor. TC842B1007 AE is approved by BASEEFA and has an EEx ia IIC T5/T4 Ga (-20 C Ta 40 C/60 C)
More information0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS
INSTALLATION AND MAINTENANCE INSTRUCTIONS 2251EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2,
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationRF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors
RF80THS EN Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS Installation Instructions Trademarks Trademarks Chamber Check is a registered trademark of Bosch Security Systems
More informationD2E Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationDUR 40Ex Intrinsically Safe SMOKE DETECTOR
DUR 40Ex Intrinsically Safe SMOKE DETECTOR Installation and Maintenance Manual IK E317 001GB IB Issue 2 IK E317 001GB The Universal Optical Smoke Detector DUR 40Ex covered by the present manual, complies
More informationALK-V PHOTOELECTRIC SMOKE SENSOR
ALK-V PHOTOELECTRIC SMOKE SENSOR APPLICATION The HOCHIKI America ALK-V Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as
More informationSIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL.
Page 1 / 15 Installation and user manual Page 2 / 15 Sira s.r.l. reserves the right to make modifications to this manual and the product described herein without prior notice. Sira s.r.l. shall not be
More informationED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR
ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk
More information16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5
Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series
More informationDetectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.
Détecteur de gaz OLCT80 Detectors-Transmitters for Flammable, Toxic Gases and Oxygen Non-intrusive operation via intrinsically safe infrared remote control Disponible en version déportée, ADF ou de SI
More informationTransmitters/Sensors. OLCT Series
Transmitters/Sensors Gas Monitoring Solutions OLCT 20-40-50-60 Series SIL2 based on EN 50402 (OLCT 60 based on EN 50271) FLP approved Intrinsically Safe (IS) Precalibrated block module local or remote
More informationMR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION
DOCUMENT CONTROL NUMBER / MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION 1. INTRODUCTION The MR300 range of optical smoke detectors forms part of the M300 series of plug-in
More informationD285DH. Installation Instructions Photoelectric Duct Smoke Detector
D85DH EN Installation Instructions Photoelectric Duct Smoke Detector D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal
More informationSET-2000 Hi Level/Oil
Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationSECTION FIRE ALARM
SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationBristol Babcock Oil Content Monitor "oil in water"
NORTHEAST CONTROLS INC. ONLINE www.nciweb.net 123 Pleasant Avenue - Upper Saddle River - New Jersey 07458 USA Tel: 201-327-7660 / Fax: 201-327-3242 Bristol Babcock Oil Content Monitor "oil in water" General
More informationOilSET-1000 (12 VDC)
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009
More informationTX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.
TX7130 Conventional Reflective Beam Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property, read
More informationInstallation Instructions
48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................
More informationThe CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)
The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater
More informationFireNET FN-LCD-S Serial Annunciator Installation and Operation Manual
FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692
More informationINSTRUCTION MANUAL. Software Revision Card 3.2 DOCUMENT SES-KS E REV. 3
2402 COMBUSTIBLE GAS CARD 2 CHANNELS 2404 TOXIC GAS CARD 2 CHANNELS 2407 OXYGEN GAS CARD 2 CHANNELS INSTRUCTION MANUAL Software Revision Card 3.2 DOCUMENT SES-KS-2402-04-07-E REV. 3 2402 2404 2407-2 CHANNELS
More informationSolarSET GSM SolarSET GSM with a Beacon
Labkotec Oy Myllyhaantie 6 FI-33960 Pirkkala FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 13.08.2009 Internet: www.labkotec.fi SolarSET GSM SolarSET GSM with a Beacon Solar Powered Oil Separator Alarm
More informationD7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector
D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex
More informationCONVENTIONAL >FIRE DETECTION C400 SYSTEM FIRE DETECTION
FIRE DETECTION >FIRE DETECTION CONVENTIONAL C400 SYSTEM FIRE DETECTION EFFICIENT AND MODULAR Elkron fire detection systems protect your business and grow with it Elkron's conventional fire detection range
More informationSET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions
SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...
More informationOPTIBAR DP 7060 Supplementary Instructions
OPTIBAR DP 7060 Supplementary Instructions Differential pressure transmitter Category ATEX II 1/2G, 2G Ex db ia IIC T6...T1 Ga/Gb, Gb IECEx Ex db ia IIC T6...T1 Ga/Gb, Gb Housing Aluminium: Single chamber,
More informationFX-PDD Duct Smoke Detector Installation Sheet
FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state.
More informationDICTATOR Hold-Open Systems for Hazardous Areas
DICTATOR for Hazardous Areas Products to be used in hazardous areas obviously have to meet special demands. The European ATEX directives (first the EN 94/9/EG and then the directive 2014/34/ EU) brought
More informationOptical Beam Smoke Detector RK90R - RK90RS
Optical Beam Smoke Detector RK90R - RK90RS TECHNICAL INFORMATION APPLICATIONS museums churches art galleries libraries hotels shops cinemas computer rooms control rooms storehouses, etc. The RK90R it's
More informationTechnical Information OUSTF10
TI00500C/07/EN/02.16 71316944 Products Solutions Services Technical Information OUSTF10 Optical sensor with the OUA260 flow assembly for the measurement of turbidity and undissolved solids Application
More informationE-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from
More informationmod. ERHSO712 mod. ERRHSO712 ENGLISH CONTROLLER mod. CSRLS MAINTENANCE ADDITIONAL CONTROLS
CONTENTS mod. ERHSO712 (Transmitter-Receiver version) Basic characteristics.......................................... 3 Product characteristics........................................ 3 Working Principle............................................
More informationDH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS Air Duct Smoke Detector with Extended Air Speed Range A Division of Pittway 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495 The Innovair
More informationInstructions. Explosion Proof Smoke Detector U Rev: 9/
Instructions Explosion Proof Smoke Detector U0. Rev: 9/ 9-7 Table of Contents OVERVIEW... FEATURES... BENEFITS... SPECIFICATIONS... OPERATION... Warm Up... Outputs... Integral Wiring Compartment... LED...
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationDH100LP Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed, CSFM Approved* Features Air aspiration duct smoke detection** system provides remote sensor location for ducts with difficult service access: Available as either
More informationIR FLAME DETECTOR RIV-601/F
IR FLAME DETECTOR EN 54-10 class 2 VdS approval G 205044 application manual CONTROL LOGIC rev. 4 DEC07 MAFE DEC07 IR FLAME DETECTORS SUMMARY Page general notions...3 description...4. Electrical and general
More informationFire & Security Products. Siemens Building Technologies Group
Fire & Security Products Siemens Building Technologies Group . 1 Brief overview.................................................... 1 1.1 Characteristics....................................................
More informationDETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS
TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance
More informationFIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF
DETECTOR TYPE ED816 ZE 1 ZE 2 ZE 3 ZE 4 ZE 5 ZE 6 ZE 7 S ZE 8 CIRCUIT 1 ZE 9 ZE 10 ZE 11 ZE 12 ZE 13 ZE 14 ZE 15 ZE 16 CIRCUIT 1 POWER POWER SUPPLY GENERAL MENT DC GENERAL SYSTEM ALARM DELAYED ALARM RESOUND
More informationFire Alarm System Accessories
UL, ULC Approved* Fire Alarm System Accessories Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer isolated barrier
More informationManual No: Revision: E. Groundwater Sensor. Installation Guide
Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationEVC-P CONVENTIONAL PHOTOELECTRIC SMOKE DETECTOR. instruction manual. evolution EVC-P Conventional Photoelectric Smoke Detector
EVC-P CONVENTIONAL PHOTOELECTRIC SMOKE DETECTOR instruction manual Ref No: NISM/EVC-P/03 Date: Jan 2010 Issue: 3 Quality System Certificate No. 041 Assessed to BS EN ISO 9001:2000 NITTAN (UK) LTD. Hipley
More informationIntrinsically Safe Solutions
Intrinsically Safe Solutions INSTALLATION MANUAL 04/12/14 Rev D DOC-01-029 Documentation Feedback Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions
More informationInstruction Manual EVA-PY
Instruction Manual EVA-PY Analog Photoelectric Smoke Detector NITTAN COMPANY, LIMITED 1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN http://www.nittan.com Before Installation Please read these instructions
More informationSK-Duct Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications
More informationD350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS
D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for
More informationModel OOHC941 ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors
Intelligent Detection Devices Multi-Criteria Fire / CO Detector [with ASAtechnology TM ] ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that has optical, thermal and CO sensors
More informationInstallation and Operation Manual
[Please read this installation & operation manual before install and use this Installation and Operation Manual Address: 8-701,Dongfangming Industry Zone, Dabao Road., Baoan, Shenzhen, China-518101 Page
More informationE N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI
E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor
Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000
More informationARCHITECT AND ENGINEER SPECIFICATIONS
s Data Sheet Fire Safety Products Intelligent Detection Devices Multi-Criteria Fire / CO Detector [with ASAtechnology TM ] ARCHITECT AND ENGINEER SPECIFICATIONS Advanced multi-criteria fire detector that
More informationAnnubar Flowmeter Series
Reference Manual Appendix B Approvals Annubar Flowmeter Series Hazardous Locations Installations.................. page B-1 Rosemount 3051SFA Product Certifications.......... page B-1 Rosemount 3095MFA
More informationInstructions. Det-Tronics SmokeWatch Explosion Proof Smoke Detector U Rev: 3/
Instructions Det-Tronics SmokeWatch Explosion Proof Smoke Detector U5015 Rev: 3/17 95-8723 Table of Contents OVERVIEW...1 FEATURES...1 BENEFITS...1 SPECIFICATIONS...2 OPERATION...3 Warm Up...3 Outputs...3
More information1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights
1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights These 1 Exam Prep Highlights are based on the Fire Alarm Signaling Systems, 4th Edition. Each Tabs sheet has five rows of tabs. Start with the
More informationThe system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.
FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001
More informationDependable Solutions for Gas Detection
Dependable Solutions for Gas Detection Combustibles/Flammables Standard & Exotic Toxics Oxygen Enrichment/Deficiency Introduction to Sensidyne Established in 1983 - acquired by Schauenburg GmbH in April
More informationDESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)
DESIGN MANUAL MODEL GIR910 INFRARED CARBON DIOXIDE (CO 2 ) GAS SENSOR 70091 The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0) The information and
More informationIntelligent Detection Devices
Intelligent Detection Devices Multi-Criteria Fire Detector [with ASAtechnology TM ] Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena
More information7251DH Intelligent Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS 7251DH Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:
More informationDräger Polytron Pulsar 2 Open Path Gas Detector
Dräger Polytron Pulsar 2 Open Path Gas Detector The Dräger Polytron Pulsar 2 represents the latest infrared technology in open path gas detection. Equipped with all the same functions as the standard Dräger
More informationAlarmLine Addressable Linear Heat Detector
Line Addressable Linear Heat Detector P/N 7-0001-00 Effective: March 2008 K-7-02 FEATURES UL Listed FM Approved CSFM MEA (pending) Low-cost interface between Line sensor cable and control panel accepting
More informationENGINEERING PRODUCT GUIDE
RDM ENGINEERING PRODUCT GUIDE Radio linked detectors and interfaces CONTENTS Radio Detector Monitoring 1 RDM Ionisation Smoke Detector RDM Radio-linked detectors with base and interfaces Operating Principles
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec
More informationOOH740-A9-Ex Multi-sensor fire detector
OOH740-A9-Ex Multi-sensor fire detector ASAtechnology TM For potentially explosive areas Cerberus PRO Collective Signal processing with ASAtechnology Multiple protocol detector (collective/c-net-ex) Event-controlled
More informationU L T R A S O N I C G A S L E A K D E T E C T O R
U L T R A S O N I C G A S L E A K D E T E C T O R GasSonic Surveyor ultrasonic gas leak detector APPLICATIONS (EXAMPLES) Offshore and Onshore Oil and Gas Installations Petrochemical Processing Plants Gas
More information1400 Direct Wire Ionization Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:
More informationSET-2000 Oil/Sludge 12 VDC
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with
More informationCARETAKER PLUS: MOST FREQUESNTLY ASKED QUESTIONS. Which sensor programming group should I use for a wireless freeze sensor?
CARETAKER PLUS: MOST FREQUESNTLY ASKED QUESTIONS Which sensor programming group should I use for a wireless freeze sensor? Group 29 (Auxiliary Environmental) is the sensor group for freeze or water sensors.
More informationOOH740-A9-Ex Multisensor fire detector
OOH740-A9-Ex Multisensor fire detector ASAtechnology TM For potentially explosive areas Cerberus PRO Collective Signal processing with ASAtechnology Multiple protocol detector (collective/c-net-ex) Event-controlled
More informationDH100ACDCI Ionization Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),
More informationIECEx Certificate of Conformity
IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate IECEx
More informationDH500ACDC Intelligent Air Duct Smoke Detector Housing
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5
More informationConventional Detectors
Conventional Detectors ECO1000 The world s finest manufacturing facility Sensor s European products are researched, designed and manufactured at our 10,000m2 state-of-the-art facility in Trieste, Italy.
More informationAUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION
AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very
More informationTRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495
More informationDONALD H. BERG, ARCHITECT
DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:
More informationDNR-AUS Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the
More informationAlarmLine Linear Heat Detector
7.01 7/11/2000 8:1 AM Page 1 CP Scan#1:Desktop Folder:hold:90 Catalog:7.01.job: 7.01 AlarmLine Linear Heat Detector FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm
More informationPEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K
PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)
More informationAir Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)
FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main
More informationEx Safety and Installation Instructions GS030 Slew sensor Transmitter & GS031 Slew Sensor Encoder
Ex Safety and Installation Instructions GS030 Slew sensor Transmitter & GS031 Slew Sensor Encoder Load Systems International 2666 Boul du Park-Technologique Québec QC G1P 4S6 Canada www.loadsystems.com
More informationRecommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.
SMOKE GUARD SYSTEM MODEL 200 SPECIFICATION Smoke Guard inc. 287 N. Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/
More informationInstrumentationTools.com
Author: Instrumentation Tools Categories: Fire & Gas System Overview of Fire/Smoke/Flame/Heat/Gas Detectors Fire Detectors Fire detectors are available for residential, commercial, and industrial use.
More informationDNR Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-004R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the
More informationMS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels
R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:
More informationClarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group
Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01
More informationAir Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)
FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main
More informationITALIANO BST-100 ACTIVE INDOOR AND OUTDOOR INFRARED BARRIER WITH 2 BEAMS OF PROTECTION INSTALLATION MANUAL. Manuale istruzioni BST-100. Pag.
BST-100 ACTIVE INDOOR AND OUTDOOR INFRARED BARRIER WITH 2 BEAMS OF PROTECTION INSTALLATION MANUAL Manuale istruzioni BST-100 Pag. 1 1 - Product Discription The BST-100 is an active indoor & outdoor infrared
More informationSECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER
SECTION 08 3493 AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Smoke detector-activated, vertical closing fire barrier conveyor system closure.
More informationInstruction Manual EVA-S6 Base
Instruction Manual EVA-S6 Base Sounder Base NITTAN COMPANY, LIMITED 1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN http://www.nittan.com Before Installation Please read these instructions carefully
More informationTITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.
TITLE SLIDE FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR Doc. No: 32-0009-01 OPTICAL BEAM SMOKE DETECTORS This training material provides information to assist the Fire System Designer and Installer in
More informationA. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.
SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationTrueAlarm Analog Sensing
UL, ULC Approved* TrueAlarm Analog Sensing TrueAlarm Analog Sensors Photoelectric and Heat; Standard Bases and Accessories Features TrueAlarm analog sensing provides: Digital transmission of analog sensor
More information