APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

Size: px
Start display at page:

Download "APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)"

Transcription

1 OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP) OFFICE USE ONLY APPLICATION #: OSP OSHPD Special Seismic Certification Preapproval (OSP) Type: New Renewal Manufacturer Information Manufacturer: Hochiki America Corporation Manufacturer s Technical Representative: Bill Denney Mailing Address: 7051 Village Drive, Suite 100, Buena Park, CA Telephone: bdenney@hochiki.com Product Information Product Name: Product Type: FireNET Alarm Control Panels Fire Alarm Control Panel Product Model Number: See Attachment 1 (List all unique product identification numbers and/or part numbers) General Description: Analog addressable fire alarm control panels and battery cabinets. Mounting Description: Rigid wall mounted. Applicant Information Applicant Company Name: Manwill Engineering LLC Contact Person: Derek Manwill, SE Mailing Address: PO Box 1194, Bend, OR Telephone: derek@manwillse.com I hereby agree to reimburse the Office of Statewide Health Planning and Development review fees in accordance with the California Administrative Code, Signature of Applicant: Date: 3/15/2017 Title: President Company Name: Manwill Engineering LLC Access to Safe, Quality Healthcare Environments that Meet California s Diverse and Dynamic Needs STATE OF CALIFORNIA HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 1 of 3 03/15/2017 OSP Page 1 of 7

2 OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION California Licensed Structural Engineer Responsible for the Engineering and Test Report(s) Company Name: Manwill Engineering LLC Name: Derek Manwill, SE California License Number: S6266 Mailing Address: PO Box 1194, Bend, OR Telephone: Supports and Attachments Preapproval Supports and attachments are preapproved under OPM- (Separate application for OSHPD Preapproval of Manufacturer s Certification (OPM) of Supports and attachments is required) Supports and attachments are not preapproved Certification Method Testing in accordance with: Other (Please Specify): ICC-ES AC156 Testing Laboratory Company Name: Contact Name: National Technical Systems (NTS) Ratish Rao Mailing Address: 1536 East Valencia Drive, Fullerton, CA Telephone: ratish.rao@nts.com Access to Safe, Quality Healthcare Environments that Meet California s Diverse and Dynamic Needs STATE OF CALIFORNIA HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 2 of 3 03/15/2017 OSP Page 2 of 7

3 Seismic Parameters OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION Design in accordance with ASCE 7-10 Chapter 13: Yes No Design Basis of Equipment or Components (Fp/Wp) = 1.88 SDS (Design spectral response acceleration at short period, g) = 2.5 ap (In-structure equipment or component amplification factor) = 2.5 Rp (Equipment or component response modification factor) = 6.0 Ω0 (System overstrength factor) = 2.0 Ip (Importance factor) = 1.5 z/h (Height factor ratio) = 1 Equipment or Component Natural Frequencies (Hz) = (wall mounted) Overall dimensions and weight (or range thereof) = See Attachments 1 & 2 Equipment or grade designed in accordance with ASCE 7-10 Chapter 15: Yes No Design Basis of Equipment or Components (V/W) = SDS (Design spectral response acceleration at short period, g) = SD1 (Design spectral response acceleration at 1 second period, g) = R (Response modification coefficient ) = Ω0 (System overstrength factor) = Cd (Deflection amplification factor) = Ip (Importance factor) = 1.5 Height to Center of Gravity above base = Equipment or Component Natural Frequencies (Hz) = Overall dimensions and weight (or range thereof) = Tank(s) designed in accordance with ASME BPVC, 2015: Yes No List of Attachments Supporting Special Seismic Certification Test Report(s) Drawings Calculations Manufacturer s Catalog Other(s) (Please Specify): Attachments 1 & 2 OSHPD Approval (For Office Use Only) Approval Expires on December 31, 2022 Signature: Date: 3/15/2017 Print Name: M. R. Karim Title: SHFR Special Seismic Certification Valid Up to : SDS (g) = 2.5 z/h = 1.0 Condition of Approval (if applicable): Access to Safe, Quality Healthcare Environments that Meet California s Diverse and Dynamic Needs STATE OF CALIFORNIA HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 3 of 3 03/15/2017 OSP Page 3 of 7

4 ATTACHMENT 1: CERTIFIED COMPONENTS TABLE 1 MANUFACTURER: PRODUCT FAMILY: MODEL NUMBER DIMENSIONS (in) MAX. WT. DEPTH WIDTH HEIGHT (lb) DESCRIPTION / NOTES BASIS FireNET Analog Addressable Fire Alarm Control Panels FN-4127N UUT 1 FN-4127-DDWN UUT 2 Plus UUT 3 FN-ACC UUT 4 weighed 27-lb UUT 4,5 NOTES: FireNET ALARM CONTROL PANELS & BATTERY ENCLOSURE SEISMIC Rigid wall mounted. S DS = 2.5g for z/h = 1 LEVEL Product Construction:. Options/Subcomponents: Model number uniquely identifies subcomponents except for FN-ACC. FN-ACC can have a range of battery sizes as shown in Table 2. TABLE 2 - SUBCOMPONENTS I P = 1.5 MANUFACTURER: PRODUCT FAMILY: FireNET ALARM CONTROL PANELS & BATTERY ENCLOSURE MODEL NUMBER DIMENSIONS (in) MAX. WT. DEPTH WIDTH HEIGHT (lb) DESCRIPTION / NOTES BASIS MK Battery - 12V Batteries ES UUT 4 ES INTERP ES INTERP ES INTERP ES INTERP ES INTERP ES INTERP ES INTERP ES UUT 5 NOTES: Mounted within unit. SEISMIC LEVEL(S) S DS = 2.5g for z/h = 1 I P = 1.5 Product Construction/Options: Model number uniquely identifies manufacturer, materials and configuration of subcomponents. 03/15/2017 OSP Page 4 of 7

5 ATTACHMENT 2: UNIT UNDER TEST SUMMARIES UUT 1 MODEL NUMBER: FireNET FN-4127N UNIT FUNCTION: Alarm Control Panel SERIAL NUMBER: CBC ICC-ES AC156 NTS UUT 2 MODEL NUMBER: FireNET FN-4127-DDWN UNIT FUNCTION: Alarm Control Panel SERIAL NUMBER: Model number uniquely identifies subcomponents. Model number uniquely identifies subcomponents. 03/15/2017 OSP Page 5 of 7

6 ATTACHMENT 2: UNIT UNDER TEST SUMMARIES UUT 3 MODEL NUMBER: FireNET Plus-1127 UNIT FUNCTION: Alarm Control Panel SERIAL NUMBER: UUT 4 MODEL NUMBER: FN-ACC UNIT FUNCTION: Alarm Battery Panel SERIAL NUMBER: Model number uniquely identifies subcomponents. MK Battery - battery (two ES7-12) 03/15/2017 OSP Page 6 of 7

7 ATTACHMENT 2: UNIT UNDER TEST SUMMARIES UUT 5 MODEL NUMBER: FN-ACC UNIT FUNCTION: Alarm Battery Panel SERIAL NUMBER: MK Battery - battery (two ES33-12) 03/15/2017 OSP Page 7 of 7

APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP) OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP) OFFICE USE ONLY APPLICATION #: OSP 0169 10 OSHPD

More information

2016 California Building Code Adoption OC amendments Summary Title/Subject Justification/Comments Action

2016 California Building Code Adoption OC amendments Summary Title/Subject Justification/Comments Action OC Ordinance 7-1-12 2016 Code 2013 Code 2016 Adoption OC amendments Summary Title/Subject Justification/Comments Action Adoption of the, International Building Code, California Residential Code, California

More information

Michael J. Caron, Test Engineer. Lee R. Senne, Test Technician. Kent L. Erickson, Dynamics Division Manager

Michael J. Caron, Test Engineer. Lee R. Senne, Test Technician. Kent L. Erickson, Dynamics Division Manager Engineering Report 49820-1 Vibration Test for Crystal Group Inc. Prepared by Michael J. Caron, Test Engineer Lee R. Senne, Test Technician Approved by Kent L. Erickson, Dynamics Division Manager This document

More information

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM PART 1 - GENERAL 1.01 SUMMARY SECTION 08 34 84 ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM A. Section Includes: Fire protective elevator smoke containment curtain system designed to provide a tight-fitting,

More information

C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT

C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT BUSINESS TAX CERTIFICATE NEW AND RENEWALS Frequently Asked Questions The following are answers to some commonly asked questions regarding

More information

DATE: CHECK AMOUNT: CHECK NUMBER: RENEWAL APPLICATION. COMPANY CERTIFICATE OF REGISTRATION And INDIVIDUAL LICENSE RENEWAL

DATE: CHECK AMOUNT: CHECK NUMBER: RENEWAL APPLICATION. COMPANY CERTIFICATE OF REGISTRATION And INDIVIDUAL LICENSE RENEWAL ARKANSAS FIRE PROTECTION LICENSING BOARD 7509 Cantrell Road, Suite 103-A Little Rock, Arkansas 72207 Telephone (501) 661-7903 Fax (501) 603-3540 Email: afplb@att.net DATE: CHECK AMOUNT: CHECK NUMBER: RENEWAL

More information

Engineering Report Vibration Test for Intertek Testing Services Prepared by Approved by 9725 Girard Avenue South Minneapolis, MN 55431

Engineering Report Vibration Test for Intertek Testing Services Prepared by Approved by 9725 Girard Avenue South Minneapolis, MN 55431 Engineering Report 47566-1 Vibration Test for Intertek Testing Services Prepared by Michael J. Caron, Test Engineer Lee R. Senne, Test Technician Approved by Kent L. Erickson, Dynamics Division Manager

More information

CITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax

CITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax REV 11/09 CITY OF DANIA BEACH Phone: 954-924-6805 ext 3644 / Fax 954 924-6812 BUSINESS LICENSE APPLICATION INFORMATION & REQUIREMENTS PLEASE SUBMIT THE FOLLOWING DOCUMENTS (AS APPLICABLE): 1. BEFORE submitting

More information

Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial

Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial ` Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial and home development before construction has begun (or

More information

Application for Certification for an Alarm System Contractor

Application for Certification for an Alarm System Contractor Application for Certification for an Alarm System Contractor IOWA STATE FIRE MARSHAL S OFFICE 215 E 7 th STREET DES MOINES, IA 50319 PH: 515-725-6145 FAX: 515-725-6172 NEW AMEND RENEWAL This form is to

More information

Commercial Business Licensing Requirements

Commercial Business Licensing Requirements SPRINGVILLE CITY BUSINESS LICENSING 110 SOUTH MAIN STREET SPRINGVILLE, UT 84663 OFFICE 801.491.7811 Commercial Business Licensing Requirements In our effort to make this application a One-Stop process

More information

PIKES PEAK REGIONAL BUILDING DEPARTMENT Fire Alarm Contractor License Application

PIKES PEAK REGIONAL BUILDING DEPARTMENT Fire Alarm Contractor License Application PIKES PEAK REGIONAL BUILDING DEPARTMENT Fire Alarm Contractor License Application Review the type of work to be performed with the contractor descriptions listed below. If necessary, discuss your licensing

More information

CHRISTMAS TREE LOT INFORMATION & REQUIREMENTS

CHRISTMAS TREE LOT INFORMATION & REQUIREMENTS CHRISTMAS TREE LOT INFORMATION & REQUIREMENTS Applications must be submitted to the Business License Division prior to November 30 th. All required departments must sign off prior to the business start

More information

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents SECTION 01410 PART I - GENERAL 1.01 SECTION INCLUDES A. Relationship between Code, Ordinances, Standards and Contract Documents B. Applicable Codes, Laws and Ordinances C. Project Inspections D. Office

More information

CURRICULUM VITAE L. EARLE GRAHAM

CURRICULUM VITAE L. EARLE GRAHAM CURRICULUM VITAE L. EARLE GRAHAM CSC Principal Consultant 25851 Avatar Lane Laguna Niguel, CA 92677 Telephone: (949) 364-0870 EDUCATION Bachelor of Arts, Public Service Management, University of Redlands

More information

Technical Data Submittal Documents

Technical Data Submittal Documents Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections

More information

WH-1404, Rev. Feb 97

WH-1404, Rev. Feb 97 WH-1404, Rev. Feb 97 Page No. i REVISIONS REPORT NO. T56737 DATE December 20, 2011 REV DATE PAGE OR PARAGRAPH AFFECTED BY APP'L DESCRIPTION OF CHANGES A 12/16/11 Cover Page Changed total of pages and title.

More information

Flexible Air-sampling Smoke Detection

Flexible Air-sampling Smoke Detection Flexible Air-sampling Smoke Detection BY Technology Pioneers in Highsensitivity Air-sampling Smoke Detection Systems Providing Solutions Beyond Traditional Smoke and Fire Detection Hochiki, a world-leader

More information

Carbon Dioxide Enrichment Systems

Carbon Dioxide Enrichment Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6100 Carbon Dioxide Enrichment Systems Guideline G-17 Serving the Cities

More information

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL The FireNET 427 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with each loop supporting 27 devices of

More information

ARES-G2 Rheometer. Site Preparation Guide. Revision A Issued June 2016 Page 1

ARES-G2 Rheometer. Site Preparation Guide. Revision A Issued June 2016 Page 1 ARES-G2 Rheometer Site Preparation Guide A Issued June 2016 1 1 A Issued February 2017 Table of Contents Table of Contents... 1 Ideal Setup... 2 System Components... 3 Instrument Measurements... 4 Utility

More information

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: Mech Code 601 Effective: 2-07-79 DOCUMENT NO. P/BC 2002-018 Revised: 9-25-03 Previously Issued As: RGA 2-79, MGD101 INSTALLATION OF ACCESS FLOOR

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-07 FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS TABLE OF CONTENTS 0780-02-07-.01 Definitions 0780-02-07-.08 Installation,

More information

RESIDENTIAL ALARM USER PERMIT APPLICATION

RESIDENTIAL ALARM USER PERMIT APPLICATION RESIDENTIAL ALARM USER PERMIT APPLICATION Portland Police Alarm Administration PO Box 1867 Portland, OR 97207 Phone: (503) 823-0031 Fax: (503) 823-0507 Email: Alarms@PortlandOregon.Gov Date Received: Amount

More information

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator 215 E Seventh Street; Des Moines, IA 50319 Email: sfmlicense@dps.state.ia.us APPLICATION CHECKLISTS (EFFECTIVE IMMEDIATELY) 1. DO NOT mail

More information

At least 10 calendar days prior to project start date Within the last 30 days of a project that will extend beyond 12 months

At least 10 calendar days prior to project start date Within the last 30 days of a project that will extend beyond 12 months New York State Department of Labor Division of Safety and Health (518) 485-9263 Filing an asbestos project notification Who must provide asbestos project notification If the asbestos removal project is:

More information

PASCO COUNTY, FLORIDA

PASCO COUNTY, FLORIDA PASCO COUNTY, FLORIDA Bringing Opportunities Home May 18, 2015 West Pasco Government Center Planning & Development Department 8731 Citizens Drive, Suite 230 New Port Richey, FL 34654 Telephone: (727) 847-8132

More information

EXHIBIT A BE IT ORDAINED BY THE MAYOR AND THE CITY COUNCIL OF THE CITY OF BELLEVUE, NEBRASKA.

EXHIBIT A BE IT ORDAINED BY THE MAYOR AND THE CITY COUNCIL OF THE CITY OF BELLEVUE, NEBRASKA. EXHIBIT A 1 1 1 1 1 1 0 ORDINANCE NO. AN ORDINANCE TO AMEND ARTICLE VI OF CHAPTER OF THE BELLEVUE CITY CODE PERTAINING TO ALARM SYSTEM REGISTRATION REQUIREMENTS INCLUDING WITHOUT LIMITATION INCREASING

More information

FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS

FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS www.madison-heights.org COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 300 W. THIRTEEN MILE RD. MADISON HEIGHTS, MICHIGAN 48071 (248) 583-0831 FAX (248)

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

Additional deviations may possibly be found if a complete type test is carried out on the product.

Additional deviations may possibly be found if a complete type test is carried out on the product. Diary No. 13EV4171 Reference No 1315333 MARKET SURVEILLANCE TEST REPORT - LVD The tests cover parts of the requirements for AC adapter stated in the standard SS-EN 60950: 2006 + A11 + A1 + A12 and EN 50075.

More information

Redlands Fire Department Fire Protection Standard

Redlands Fire Department Fire Protection Standard Title: High piled Storage Standard Number: FS-100 Revision: A Date: 10-07-2015 Scope: To provide a standard for High Piled Storage plan review submittals. Description: A standard for High Piled Storage

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

Bruce E. Johnson Underwriters Laboratories 395 Kingston Drive Ridge, New York Phone: (631)

Bruce E. Johnson Underwriters Laboratories 395 Kingston Drive Ridge, New York Phone: (631) Bruce E. Johnson Underwriters Laboratories 395 Kingston Drive Ridge, New York 11961 Phone: (631) 680-5174 Bruce.Johnson@ul.com EXPERIENCE April 2015 to Present Senior Regulatory Engineer Codes and Advisory

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

Fire and Life Safety Requirements San Mateo City Special Events

Fire and Life Safety Requirements San Mateo City Special Events San Mateo City Special Events Fire and Life Safety Requirements cket VERSION 1.0 12/2015 Fire and Life Safety Requirements San Mateo City Special Events The San Mateo Fire Department has a vested interest

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD Revised 1/1/17 The Fire Department has a vested interest to ensure the fire and life safety of all events and activities within the city. The

More information

Food Service Incentive Application for Business Customers

Food Service Incentive Application for Business Customers 2019 Food Service Incentive Application for Business Customers A Cash Incentive Energy Efficiency Program brought to you by: IMPORTANT INSTRUCTIONS: Step 1: Determine Eligibility: Pre-approval is required

More information

CIVIL ENGINEERING PERMIT APPLICATION

CIVIL ENGINEERING PERMIT APPLICATION CIVIL ENGINEERING PERMIT APPLICATION OFFICIAL USE ONLY Engineering Permit # Date: Received By: Staff Contact: FOR STAFF USE ONLY: OFD RSH LOTT Stormwater Planning Water Shop PLEASE SUBMIT TWO (2) SETS

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.34 Control Number: A.1 Revision Date: TITLE: SCOPE: PURPOSE:

More information

AREA LIGHTING TABLE OF CONTENTS PUD SERVICE TERRITORY & CONTACTS FOR YOUR PROPERTY OVERHEAD FEED UNDERGROUND FEED. Electrical Service Requirements

AREA LIGHTING TABLE OF CONTENTS PUD SERVICE TERRITORY & CONTACTS FOR YOUR PROPERTY OVERHEAD FEED UNDERGROUND FEED. Electrical Service Requirements Electrical Service Requirements AREA LIGHTING PUD SERVICE TERRITORY & CONTACTS FOR YOUR PROPERTY Yard light Flood light OVERHEAD FEED PUD responsibilities Customer responsibilities UNDERGROUND FEED PUD

More information

FIRE PREVENTION STANDARDS

FIRE PREVENTION STANDARDS DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable

More information

Enraf Servo Gauge 854 XTG

Enraf Servo Gauge 854 XTG Enraf Servo Gauge 854 XTG Cut costs, not repeatability. Honeywell s 854 XTG servo gauge is a high performance alternative to other tank level measurement technologies such as radar tank level gauges. It

More information

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS Mass Flow Computers Series 155 The Kurz 155 Mass Flow Computer is a versatile system transmitter that integrates the functions of flow and temperature measurement, flow totalization,

More information

WYLE LABORATORIES, INC. Huntsville Facility

WYLE LABORATORIES, INC. Huntsville Facility Page No. TOC 1 of 1 TABLE OF CONTENTS Page No. 1.0 INTRODUCTION... 1 1.1 Scope... 1 1.2 Product Description... 1 1.3 References... 1 1.4 Compliance Summary... 2 2.0 SYSTEM TEST CONFIGURATION... 2 2.1 Details

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE Insulation monitoring device with integrated load and temperature monitoring and locating current injector for insulation fault location systems for medical IT systems _D00043_02_D_XXEN/09.2016 Insulation

More information

MODEL 4000A & 4001A ACCELEROMETER

MODEL 4000A & 4001A ACCELEROMETER MODEL 4000A & 4001A ACCELEROMETER dimensions 4001A Connector Attachment SPECIFICATIONS Silicone MEMS Accelerometer Signal Conditioned Output Temperature Calibrated Low Cost, Lightweight The Model 4000A

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

Eseta. Architectural LED Wall Sconce. Area lighting for outdoor wall-mounted applications.

Eseta. Architectural LED Wall Sconce. Area lighting for outdoor wall-mounted applications. Eseta Architectural LED Wall Sconce Area lighting for outdoor wall-mounted applications www.leotek.com Eseta s subtly distinctive form has a versatile architectural aesthetic that makes it an appealing

More information

'+8 ===========================================================

'+8 =========================================================== PALM BEACH COUNTY BOARD OF COUNTY COMMISSIONERS AGENDA ITEM SUMMARY Agenda Item#: '+8 ===========================================================--------------- Meeting Date: August 17, 2010 Department:

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION

CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION CLASSROOM AMPLIFICATION SYSTEMS FORM A - BIDDER INFORMATION Instructions to ders: Please complete this bid form in its entirety. Provide the following information about your company's bid: Name of Company

More information

Project phasing plan (if applicable) 12 copies of site plan

Project phasing plan (if applicable) 12 copies of site plan SITE PLAN REVIEW PERMIT APPLICATION City of Grand Haven, 11 N. Sixth Street, Grand Haven, MI 49417 Phone: (616) 847-3490 Fax: (616) 844-2051 Website: www.grandhaven.org 1. Project Information Address/location

More information

UNIFORM POLICIES AND PROCEDURES MANUAL TABLE OF CONTENTS CHAPTER 7- CROSS CONNECTIONIBACKFLOW PREVENTION

UNIFORM POLICIES AND PROCEDURES MANUAL TABLE OF CONTENTS CHAPTER 7- CROSS CONNECTIONIBACKFLOW PREVENTION UNIFORM POLICIES AND PROCEDURES MANUAL TABLE OF CONTENTS r CHAPTER 7- CROSS CONNECTIONIBACKFLOW PREVENTION Page 7.1 General 7.2 Prohibition of Cross Connections 7.3 Requirements for Backflow Prevention

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

START UP FORM PACKET

START UP FORM PACKET START UP FORM PACKET Condensing Unit DIVISIONS OF RAE CORPORATION 4492 Hunt St. - Pryor, OK 74361 - (918) 825-7222 - Fax (918) 825-6366 www.rae-corp.com RAE Corporation Condensing Unit Start-Up Form Century

More information

QATAR STANDARD QS SASO 2692/201 QS SASO 2692 ENERGY LABELLING REQUIREMENTS OF HOUSEHOLD ELECTRICAL CLOTHES WASHING MACHINES

QATAR STANDARD QS SASO 2692/201 QS SASO 2692 ENERGY LABELLING REQUIREMENTS OF HOUSEHOLD ELECTRICAL CLOTHES WASHING MACHINES QS SASO 2692 ENERGY LABELLING REQUIREMENTS OF HOUSEHOLD ELECTRICAL CLOTHES WASHING MACHINES 1 ENERGY LABELLING REQUIREMENTS OF HOUSEHOLD ELECTRICAL CLOTHES WASHING MACHINES. Date of QS Approval : Date

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

Vibration tests on a TNAML Luminaire

Vibration tests on a TNAML Luminaire Sebert Trillingstechniek B.V. Report M13.001-P13.001 rev.01 Date 26 august 2013 Vibration tests on a TNAML Luminaire Client Technor Benelux B.V. Veersteeg 15 4212 LR Spijk The Netherlands Contact Person

More information

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to amend Section 4601-01 of Title 3 of the Rules

More information

ENGROSSED SUBSTITUTE HOUSE BILL State of Washington 60th Legislature 2007 Regular Session

ENGROSSED SUBSTITUTE HOUSE BILL State of Washington 60th Legislature 2007 Regular Session ENGROSSED SUBSTITUTE HOUSE BILL 1968 State of Washington 60th Legislature 2007 Regular Session By House Committee on Commerce & Labor (originally sponsored by Representatives Simpson, Conway and Ormsby)

More information

Westerville, OH Code of Ordinances. CHAPTER 969 Alarm Systems

Westerville, OH Code of Ordinances. CHAPTER 969 Alarm Systems Westerville, OH Code of Ordinances CHAPTER 969 Alarm Systems 969.01 Definitions. 969.02 Alarm user permit required. 969.03 Application for alarm user permits. 969.04 Renewal. 969.05 System standards. 969.06

More information

2018 Rebate Catalog and Application

2018 Rebate Catalog and Application 2018 Rebate Catalog and Application Save money on qualified Home Cooling Systems, Appliances and more. Read about rebates for your home and business at mid.org/rebates REV 01.2018 Modesto Irrigation District

More information

FOR THE PERIOD JANUARY 1, TO DECEMBER 31, GENERAL INFORMATION

FOR THE PERIOD JANUARY 1, TO DECEMBER 31, GENERAL INFORMATION 3850-PM-BCW0083h Rev. 11/2016 COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER PAG-03 NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) GENERAL PERMIT FOR

More information

Plant Processing and Extraction Facilities

Plant Processing and Extraction Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Plant Processing and Extraction Facilities Guideline G-16 Serving the

More information

PL400 Patient Lift Scale Indicator Owner s Manual

PL400 Patient Lift Scale Indicator Owner s Manual PL400 Patient Lift Scale Indicator Owner s Manual CARDINAL SCALE MFG. CO. 8551-M912-01 Rev C PO BOX 151 WEBB CITY, MO 64870 Printed in USA 07/04 PH (417) 673-4631 - FAX (417) 673-5001 www.cardinalscale.com

More information

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS B 2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS COMMUNITY DEVELOPMENT DEPARTMENT 345 N. EL DORADO STREET STOCKTON, CA 95202 (209) 937-8561 www.stocktongov.com/cdd/building BUSINESS

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

MEMORANDUM. TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR

MEMORANDUM. TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR MEMORANDUM TO: FROM: BY: CITY COUNCIL TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR KELLY HEFFERNON, ASSOCIATE PLANNER SUBJECT: CONSIDERATION OF ADOPTION OF AN ORDINANCE AMENDING CHAPTER 16.84 OF THE

More information

ZoomLock TM Flame-Free Refrigerant Fittings

ZoomLock TM Flame-Free Refrigerant Fittings ZoomLock TM Flame-Free Refrigerant Fittings Form P-528, Engineering Specification, February 2018 FLAME-FREE REFRIGERANT FITTINGS Page 2 / ZoomLock Engineering Specification PART 1: GENERAL 1.0 SUMMARY

More information

FIRE DEPARTMENT PERMIT GUIDELINES

FIRE DEPARTMENT PERMIT GUIDELINES FIRE DEPARTMENT PERMIT GUIDELINES SPECIAL EVENT PUBLIC ASSEMBLY (EACH EVENT) The Special Event Assembly Permit is applicable to any public event, exhibit space, booth, festival or any other similar event

More information

Adopted September 18, 2017

Adopted September 18, 2017 SOLID WASTE - OPERATING PROCEDURES MANUAL 1.01 General 1.02 Landfill procedure and policy 1.03 Scale house procedure and policy 1.04 Office procedure and policy 1.05 Recycling and Convenience Site procedure

More information

IAEA CERTIFICATE OF COMPETENT AUTHORITY SPECIAL FORM RADIOACTIVE MATERIALS CERTIFICATE USA/0297/S-96, REVISION 8

IAEA CERTIFICATE OF COMPETENT AUTHORITY SPECIAL FORM RADIOACTIVE MATERIALS CERTIFICATE USA/0297/S-96, REVISION 8 U.S. Department of Transportation Pipeline and Hazardous Materials Safety Administration IAEA CERTIFICATE OF COMPETENT AUTHORITY SPECIAL FORM RADIOACTIVE MATERIALS CERTIFICATE /0297/S-96, REVISION 8 East

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

CITY OF MORRO BAY PUBLIC SERVICES DEPARTMENT 955 SHASTA AVENUE. MORRO BAY, CA

CITY OF MORRO BAY PUBLIC SERVICES DEPARTMENT 955 SHASTA AVENUE. MORRO BAY, CA CITY OF MORRO BAY PUBLIC SERVICES DEPARTMENT 955 SHASTA AVENUE. MORRO BAY, CA 93442 805-772-6261 When is a Permit Required? Implementation Measures For Major Vegetation Removal, Replacement and Protection

More information

It is my pleasure to welcome you to the world of Kravet Inc. fabrics and furnishings.

It is my pleasure to welcome you to the world of Kravet Inc. fabrics and furnishings. WELCOME Dear New Kravet Inc. Customer, It is my pleasure to welcome you to the world of Kravet Inc. fabrics and furnishings. We have enclosed some important information about Kravet Inc. to help you become

More information

EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE

EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE ICC-ES Report PMG-1083 Reissued 05/2017 This report is subject to renewal 05/2018 EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE DIVISION: 22 00 00 PLUMBING SECTION: 22 13

More information

Design Review Commission Report

Design Review Commission Report City of Beverly Hills Planning Division 455 N. Rexford Drive Beverly Hills, CA 90210 TEL. (310) 285-1141 FAX. (310) 858-5966 Design Review Commission Report Meeting Date: Thursday, March 2, 2017 Subject:

More information

Commercial/Industrial Combustion Control Level Three Announcement

Commercial/Industrial Combustion Control Level Three Announcement Commercial/Industrial Combustion Control Level Three Announcement SUBJECT: C6097 requiring venting Model Numbers Affected: C6097A and B Ref. Number L3-08-006 Issue Date 12/9/08 Author P.Yuen/L.Ziller Date

More information

PRESENTERS OVERVIEW COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS

PRESENTERS OVERVIEW COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS Prepared By PRESENTERS Truong Huynh, Building and Safety Bureau David Zinnen, Fire Prevention

More information

Melrose Fire Department

Melrose Fire Department Melrose Fire Department Office of Fire Prevention Re: 9/20/18 Guidelines for the Type and Placement of Smoke and Carbon Monoxide Alarms Purpose of this guide is to help homeowners protect their homes and

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 1028031 AN ORDINANCE OF THE BOARD OF SUPERVISORS OF THE COUNTY OF MARIN ADDING CHAPTER 19.08 TO THE MARIN COUNTY CODE PERTAINING TO THE REDUCTION OF AIR POLLUTION BY REGULATING THE INSTALLATION

More information

STATIONARY FOOD CART REQUIREMENTS

STATIONARY FOOD CART REQUIREMENTS COUNTY OF MARIN ENVIRONMENTAL HEALTH SERVICES 3501 CIVIC CENTER DRIVE, RM 236 SAN RAFAEL, CA 94903 415.499.6907/ (Fax) 415.507.4120 www.co.marin.ca.us/ehs STATIONARY FOOD CART REQUIREMENTS Hot Dog Carts

More information

Valuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work:

Valuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work: PERMIT FEE: $ 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the following information. Please PRINT).

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

URGENT - Field Safety Notice Medical Device Correction

URGENT - Field Safety Notice Medical Device Correction Dear Customer, According to our records, you currently have one of the V60 ventilators noted above. This Field Safety Notice (FSN) is to advise you that Respironics California, LLC ( Respironics ) is voluntarily

More information

Enraf Servo Gauge 854 ATG

Enraf Servo Gauge 854 ATG Enraf Servo Gauge 854 ATG Setting the standard in gauging. From the company that pioneered development of modern tank gauges, Honeywell s 854 Automatic Tank Gauge has become an industry standard all over

More information

START UP FORM PACKET

START UP FORM PACKET START UP FORM PACKET Condenser/Fluid Cooler DIVISIONS OF RAE CORPORATION 4492 Hunt St. - Pryor, OK 74361 - (918) 825-7222 - Fax (918) 825-6366 www.rae-corp.com Bulletin# CONFLUIDCOOLER-START UP-1213 RAE

More information

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805) Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including

More information

62 MAX/62 MAX + Infrared Thermometer

62 MAX/62 MAX + Infrared Thermometer 62 MAX/62 MAX + Infrared Thermometer Users Manual PN 4060712 April 2012 Rev. 1, 11/12 2012 Fluke Corporation. All rights reserved. Printed in China. Specifications are subject to change without notice.

More information

Miniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version)

Miniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version) PSC-SSS-PM Series Miniature Infrared Temperature Sensors with Optional Touch Screen Display PSC-SSS-PM with touch screen display (- version) FEATURES Miniature sensing head and configurable electronics

More information

Ceiling Mount Pre-Installation Guidelines

Ceiling Mount Pre-Installation Guidelines Ceiling Mount Pre-Installation Guidelines This guide is a general overview of the mounting requirements, not full installation instructions. It is recommended that the full installation manual be completely

More information

Fan Speed Controllers Type RGE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Fan Speed Controllers Type RGE REFRIGERATION AND AIR CONDITIONING. Technical leaflet Fan Speed Controllers Type RGE REFRIGERATION AND AIR CONDITIONING Technical leaflet Contents Page Introduction...3 Features...3 Specifications...4 Adjusting Method...5 Operation...5 Dimensions...6 Wiring...7

More information

qube mini Overview

qube mini Overview D a t a S h e e t qube mini Overview The 91389 qube mini is a compact, robust, and light-weight patient monitor with extensive clinical usability. Key features of the qube mini monitor include: Eye-level

More information

ANSI/ANS- An American National Standard

ANSI/ANS- An American National Standard ANSI/ANS- An American National Standard Published by the 555 N. Kensington Ave La Grange Park, IL 60526 ANSI/ANS-2.2-2016 American National Standard Earthquake Instrumentation Criteria for Nuclear Power

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.54 Control Number: A.0 Effective Date: TITLE: PROPRIETARY

More information