DIESEL ENGINE AUTOMATICS
|
|
- Mariah Tate
- 5 years ago
- Views:
Transcription
1 DIESEL ENGINE AUTOMATICS MANUAL Address: UTE d.o.o. ULJANIK TESU ELEKTRONIKA Flaciusova PULA REPUBLIC of CROATIA Phone: +385 (52) Fax: +385 (52) ute@pu.hinet.hr Cat. N.: BR001102E.1 Page 1 (1)
2 1. FRONT PANEL VIEW POWER START STOP START. STOP RUNNING OVERSPEED OIL PRESS. WATER TEMP. WATER LEV. SHORT CIRC. ALARM FUEL LEAK. LAMP TEST Fig. 1. Alarms and commands in standard version 2. APPLICATION: Manual Diesel Engine Control Unit is intended for alarm monitoring and manual control of diesel engine. Very often this is the engine of a diesel generating set. The control is manual via the keyboard on front panel. It includes the indispensable protections of engine such as: - overspeed, - too high temperature, - lubricating oil low pressure and - fuel low level - short circuit - generator overloaded Cat. N.: BR001102E.1 File: e knjiga uputa Page 2 (2)
3 3. BRIEF DESCRIPTION: The Control Unit is housed in a box of DIN standard dimensions (72x144 mm) and is intended for being built in the panel or door of switch gear cabinet. It is supplied from the diesel-engine starting batteries or some other uninterruptable DC supply in range of V DC. It is made in CMOS technology with microprocessor control and special attention is paid to safe operation, low consumption, wide supply voltage range and resistance to disturbances on the input - output terminals. ADA 1011 has RS 485 communication port with MODBUS protocol. Parameterisation of automatics is terminal. via PC and appropriate software or via hand 3.1. Inputs - information to ADA-1010 unit are: Input from speed sensor which can be: - tacho-generator (AC voltage), - passive pick-up (magnetic) and - active pick-up (inductive or capacitive). Contacts from usual sensors such us: - temperature switch - oil pressure switch - fuel oil low level switch - other possible contacts of alarm conditions 3.2. Outputs - from control unit are relay contacts for: - diesel engine start and stop - alarm siren - genset operating indication. - critical alarm - noncritical alarm 3.3. ALARM CONDITIONS are grouped in: Critical non-critical - which stop the engine and - which produce alarm but do not stop the engine operation CRITICAL ALARMS in standard version are: - overspeed, - engine high temperature, - lubrication oil low pressure 3.5. NON-CRITICAL ALARMS in standard version are: - fuel low level Cat. N.: BR001102E.1 File: e knjiga uputa Page 3 (3)
4 Beside these alarms, four more input channels could be used for alarms. Every alarm can be choosen as critical or non critical via communication (except overspeed wh ich is allways critical). Cooling water high temperature can have stop delay. 4. METHOD OF OPERATION: Engine starting is manual via the START key on front panel. Stopping can also be effected manually via STOP key but it is also automatic in case the critical alarms appear. When non-critical alarms appear the alarm siren is on but the engine is NOT stopped. The standard version is maximally adjusted to different versions of engines it will be used with but it is also possible to agree with customer / user on details of operation of automatics. The customer can request some non standard details e.g. specific values of time delays or similar. T.G. A 1 RS485 + _ Tacho generator 3-20 V, 50 Hz Fuse 2 A slow B 1 B 2 B 3 B 4 B 5 B 6 B 7 B 8 B 9 B 10 B 11 B 12 A 2 A 3 A 4 A 5 A 6 A 7 A 8 A 9 GND -Rx/Tx +Rx/Tx Sensors: Overspeed Lub oil pressure Cool. wat. temp. Fuel oil level Short circuit Gener. overload Alarm 7 Alarm 8 0 V Plus pole of supply C 1 C 2 C 3 C 4 C 5 C 6 C 7 C 8 C 9 C 10 C 11 C 12 D 1 D 2 D 3 D 4 D 5 D 6 D 7 D 8 D 9 D 10 D 11 D 12 Start Stop - + Outputs Generator running Siren Critical alarm Noncritical alarm max. 100 V, 6 A Inputs Sensors external commands SUPPLY min. 10 V max. 29 V Fig. 2. Connection diagram of automatics Cat. N.: BR001102E.1 File: e knjiga uputa Page 4 (4)
5 PULA B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 A1 A2 A3 A4 A5 A6 A7 A8 A9 C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 Fig. 3. Rear panel view Cat. N.: BR001102E.1 File: e knjiga uputa Page 5 (5)
6 143,00 136,00 130,00 149,00 Fig. 4. Mechanical dimensions Required depth is: 149 mm, plus space for wires which are connected on the rear side terminals. Cat. N.: BR001102E.1 File: e knjiga uputa Page 6 (6)
7 Fig. 5. Cutout in panel Cat. N.: BR001102E.1 File: e knjiga uputa Page 7 (7)
M2000 Engine Controller
M2000 Engine Controller Integrated control and protection of diesel and gas engines for all purposes Especially suited for auxiliary generator sets 1 IN OPERATION 1 2 STARTFAIL 2 3 OVERSPEED RPM FAIL 3
More informationM2000 Engine Controller
M2000 Engine Controller Integrated control and protection of diesel and gas engines for all purposes Especially suited for auxiliary generator sets 1 IN OPERATION 1 2 STARTFAIL 2 OVERSPEED R.P.M. FAIL
More informationM2500 Engine Controller Installation Manual
M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...
More informationPowerWizard. Level 1.0 & Level 2.0 Control Systems Training
PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts
More informationDEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option
Description of options Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M 4189340401D SW 1.4X.X Description of option Functional description DEIF A/S Parameter list DEIF A/S,
More informationDGC-500 DIGITAL GENSET CONTROLLER
DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized
More informationProcess Alarm Solutions
Process Alarm Solutions Reliable Supervision and Control» Control. Monitor. Protect. SELCO Flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring
More informationM1000 Alarm Annunciator
Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions
More informationDGC-1000 DIGITAL GENSET CONTROLLER
DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.
More informationAPPLICATION DATA SHEET
APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors
More informationDIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)
DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationEXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability
EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration
More informationEXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability
EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration
More informationHGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics
HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...5 5. PROTECTION...6 6. PARAMETER
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More informationM3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO
User s Manual Copyright 2017 SELCO SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com www.selco.com Table of contents 1 INTRODUCTION...4 2 SOFTWARE
More informationRittal roof-mounted fans Efficiency on top
Rittal roof-mounted fans Efficiency on top 2 Climate control/roof-mounted fans The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have bundled our
More informationAPP 721 MODBUS Mapping
SUMMARY This document is intended to be a reference for communicating with the Flygt APP721 controller using MODBUS RTU communication. Communication settings to the unit are as follows: MODBUS RTU, 8 data
More informationDPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-
DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature
More informationTechnical Manual. Level Alarm Unit CARLA & WIDS
CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationGenerator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control
MULTI-LINE 2 APPLICATION NOTES Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control Application description Needed options Wiring diagrams Functional description
More informationUser s Manual DCU 305 R3 DCU 305 R3 LT. Diesel Engine Control Unit. Auto-Maskin
User s Manual DCU 305 R3 DCU 305 R3 LT Diesel Engine Control Unit Auto-Maskin Content Document information 2 Introduction 3 ABOUT THIS MANUAL 3 ABOUT THE DCU 305 R3 & R3 LT 3 CERTIFICATES 4 TECHNICAL SPECIFICATIONS
More informationUniversal fault annunciator for panel mounting
Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs
More informationelite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems
5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification
More informationMoulded case circuit brakers
Moulded case circuit brakers CONTENT Range 1 Protection Releases 2 Salient Features 5 Accessories 7 Widest Range 10 Time Current Characteristics 12 Overall Dimensions 14 SN4 SN3 SN2 SN1 3 RANGE SN1 Rated
More informationVariable Frequency Drive SERIES MP800 VFD
Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for
More informationConstant climate chambers
Constant climate chambers KBF 115 (E2) - Constant climate chamber The KBF series was particularly designed for absolutely reliable stability tests and precise maintenance of constant climatic conditions.
More informationAPPLICATION DATA SHEET
APPLICATION DATA SHEET Wed : www.saenchotesei.com WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 920 - Wall, 19 Rack or Panel Mounting Units - 110/230V 50/60Hz AC operation - 250 Addressable
More informationME 3011C / Alarm Indication / Quick Reference Guide
Tables of Contents Page Application 1 Features 1 Important Safety Information! 2 Note to this Guide 2 Further Information 2 Device Variants 2 General Functions 3 Annunciator Sequences - ISA 18.1 3 Plan
More information21-light Remote Annunciator. Owner s Manual
21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With
More informationHow to use the BTRM in Remote Enclosures
How to use the BTRM in Remote Enclosures Part Number: BTRM-200 Product Release Date: April 01, 2013 Software version: BTRM2_2013-05-06_2316_DNPV2V130D The Ventev Battery Test Remote Monitor (BTRM) has
More informationSafety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device
Safety Instructions Used symbols Important Comments Before starting with installation of the MS 10B Alarm Unit, we recommend you to read the important information beneath. Qualification The installation
More informationREMOTE CONTROL FOR CHILLER MYCHILLER
REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN
More informationDigital Control Systems & Remote Communications Options
Digital Control Systems & Remote Options PowerWizard Providing Safe Control of Your Generating Set PowerWizard 1.0 and 2.0 The Olympian PowerWizard range of digital control panels combine straight forward
More informationA36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS
SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers
More informationFrequently asked questions: Intelligent Transmitter Series
Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring
More informationSpectron LSN (Life Safety Network) Suggested Specifications
1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without
More informationEngine Control Unit, ECU 100 Functional description Additional functions Parameter list
DESIGNER'S REFERENCE HANDBOOK Engine Control Unit, ECU 100 Functional description Parameter list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com
More information20 Light Remote Annunciator
Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator
More informationINSTALLATION INSTRUCTIONS. Anti Knocking System, AKR 3. Document no.: A SW version:
INSTALLATION INSTRUCTIONS Anti Knocking System, AKR 3 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel: +45 9614 9614 Fax: +45 9614 9615 info@deifcom wwwdeifcom Document no: 4189340792A SW version: 1 General
More informationFire Pump Controllers Foam (Additive) Controllers
Fire Pump Controllers Foam (Additive) Controllers Diesel Additive (Foam) Pump Controllers 1.4 Foam (Additive) Fire Pump Controllers FDF20 Foam (Additive) - Limited Service... FDF30 Foam (Additive) - Across-the-Line...
More informationB. Section Transfer Switches: Automatic transfer switch.
SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof
More informationSTA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16
ST-97106N Revised 07-04 Section 25 (00-02-0283) STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16 Certain danger to human safety and to equipment may occur if some equipment
More informationTYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM
2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40
More informationSMS GSM Alarm Messenger
SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up
More informationParameterisable compact fault annunciator with permanent display
Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator 31.08.2010 Permanent display even on power failure Compact module for 10 alarms Supply and alarm signal
More informationSCIENTIFIC WARMING CABINET Installation, Operation and Maintenance Instructions
SCIENTIFIC WARMING CABINET Installation, Operation and Maintenance Instructions GENERAL 2 Inspection 2 Location 2 INSTALLATION 2 Door Alignment 2 Shelf Installation 2 Remote Contacts 3 2-10 Volt DC Output
More informationPowerWizard Range. Digital Control Systems & Remote Communication Options. PowerWizard Providing Safe Control of Your.
PowerWizard Providing Safe Control of Your Generating Set The Fg Wilson PowerWizard range of digital control panels combine straight forward menu navigation with advanced metering and protection technology.
More informationMetasys Integrator Liebert Application
Application Note Issue Date May, 00 Metasys Integrator Liebert Application lntroduction Application Details Component Requirements 0 Vendor Contact Information Design Considerations Cable Connections Cable
More informationPanel Mounted Fault Annunciator Series
Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case
More informationRACK MONITORING SYSTEM - RAMOS Ultra
CONTEG DATA SHEET version: 9-05-0 COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM marketing@dafnia.com www.dafnia.com ABU DHABI UAE +97 55575 DUBAI JAFZA +97 4 5995 +97 4 8840 MUSCAT DOHA OMAN +968 4 75005
More informationACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System
SHIFT TEST BACK ENTER C910 SERIES STATUS OUTPUT ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM ACS-30 System MONITOR CONFIG POWER CONTROL MODULE ACCS-PCM-5 PROGRAMMABLE SINGLE POINT HEAT-TRACING CONTROLLER
More informationRemote switching machines with a SMS text from your mobile phone! Remote Monitoring your assets in the worldwide by your mobile Phone!
Remote switching machines with a SMS text from your mobile phone! Remote Monitoring your assets in the worldwide by your mobile Phone! GSM SMS Controller DCS-130 User Manual Ver 1.20 Date Issued: 14-9-2010
More informationXLH210: controller for gas leak detectors
pag. 1 / 7 XLH210: controller for gas leak detectors Dixell introduces the new digital controllers designed to be combined with 4 20mA gas leak detectors. XLH210 is a microprocessor based controller, designed
More informationSALES SUPPORT DOCUMENT
SALES SUPPORT DOCUMENT ML-322 MAXLOGIC CONVENTIONAL FIRE EXTINGUISHING CONTROL PANEL ML-322 series operates on cross-zone principle, has 4 detection zones and one extinguishing release output which is
More informationInstaller Certification Expiration. Terms
Cellwatch Installer Training Primer Material in this document is designed to complement the Cellwatch Installer Certification training. Material in this document may appear on the Certification Examination
More informationMiLAB Oxygen Control MANUAL & INSTALLATION. MOC-100 Ver 3.0
MiLAB Oxygen Control MANUAL & INSTALLATION MOC-100 Ver 3.0 Contents 1 INTRODUCTION...3 2 FUNCTIONS...4 2.1 O 2 REGULATION...4 2.2 DISPLAY BOARD...4 2.3 COMMUNICATION THROUGH PANEL...5 2.3.1 Set parameters...5
More informationUniversal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01
Gamma instabus Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG1 528-1DB01 Technical Product Information Universal Dimmer for switching or dimming of dimmable lamps Supports dimmable lamps including
More informationReplaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge
Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays
More informationFerrous debris monitoring. Ferrous debris in oil
Ferrous debris monitoring Cause and Effect What causes metallic debris? Bearings Inadequate Lubrication 34.4% Contamination 19.6% Installation Errors 17.7% Overload 6.9% Storage & Handling Errors 2.8%
More informationCONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.
CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse
More informationBS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE
BS-100 DYFI Protecting environment, life and property... P-BS100/DCE P-BS100/DCE/Doc/961023 2 Autronica Fire and Security AS Contents Please observe! This handbook contains installation instructions for
More informationHA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE
D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system
More informationEKL3 short circuit and earth fault indicator
EKL3 short circuit and earth fault indicator Summary EKL3 short circuit grounding fault indicators are mainly used in various Ring Main Units(RMU), high-voltage switchgears and cable branch units to ascertain
More informationTRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE
TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS APPLICATION OVERVIEW Control and monitoring systems can play an essential role in heat tracing applications which
More informationME 3011 compact. Electronic Alarm Indication Systems. Power Station Control Systems. Automation Equipment. Power Distribution Control Systems
Electronic Alarm Indication Systems ME 3011 compact Power Station Control Systems Power Distribution Control Systems Control Room Technology Automation Equipment 2 Table of Contents Contents Page System
More informationProSens Dust Measurement
EN Operating Instructions ProSens Dust Measurement SWR engineering Messtechnik GmbH CONTENTS Page 1. Introduction.......................................................................... 3 1.1 Safety............................................................................
More informationSentry G3 Machinery Protection Monitor
TECHNICAL INFORMATION Sentry G3 Machinery Protection Monitor CONDITION MONITORING SOLUTIONS The Sentry G3 Machinery Protection Monitor is a high performance signal conditioning unit; providing a universal
More informationSentry G3 Machinery Protection Monitor
TECHNICAL INFORMATION Sentry G3 Machinery Protection Monitor CONDITION MONITORING SOLUTIONS The Sentry G3 Machinery Protection Monitor is a high performance signal conditioning unit; providing a universal
More informationQuick Alert Remote (QA216R)
Quick Alert Remote (QA216R) Description The QA 216 Remote is used by AT&T to monitor tower lights and turned down facilities. It is a 16-bit alarm unit used to transport discrete alarms from a remote location
More informationGMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly
Operation Manual GMA200-MT Gas detection controller for mounting rail assembly GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE 99 44143 DORTMUND, Germany TEL. +49 / (0)231 / 564 00 0 FAX +49 / (0)231
More informationUNICA - ALARM SYSTEM WITH VISUAL VERIFICATION. All in One - All in Touch Video - Alarm System
UNICA - ALARM SYSTEM WITH VISUAL VERIFICATION All in One - All in Touch Video - Alarm System UNICA is a revolutionary alarm system based on architecture all-in-one composed by a burglar alarm (wired and
More informationINSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO
INSTRUCTIONS FOR USE OF COMBINED BOILER INTENDED FOR COMBUSTION OF BOTH PELLETS AND SOLID FUEL ABC COMBO .Technical specifications Boiler power DESCRIPTION Water content in a boiler Required draft Supply
More informationDIESEL Engine Fire Pump Controllers Features
September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.
More information931D Style B Process Gas Chromatograph
Product Specifications PSS 6-4N1 D 931D Style B Process Gas Chromatograph The new 931D Style B Process Gas Chromatograph continuously analyzes, measures and reports the concentration of components in process
More informationDusty / Dusty Ex Low-Cost Broken Bag Detection
EN Operating Instructions Superior Dusty / Dusty Ex Low-Cost Broken Bag Detection SWR engineering Messtechnik GmbH PART OF THE ENVIRONNEMENT S.A GROUP CONTENTS Page 1. Introduction..............................................................
More informationPowerWizard Range. Digital Control Systems & Remote Communication Options.
www.fgwilson.com PowerWizard Range Digital Control Systems & Remote Communication Options PowerWizard Providing safe control of your generating set The FG Wilson PowerWizard range of digital control panels
More informationViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1
ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5
More informationConstant voltage charger. Type UP 610. »We store the world's energy« Network
Type UP 610»We store the world's energy« Switchmode rectifier that fulfil new standards > New technique - sine wave input (PFC) > New princip - fully equipped > New technlogy - easy to use > High rate
More informationDanfoss gas detection units
Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning
More informationTHE CHANGE IN GEAR ENGINEERING
THE CHANGE IN GEAR ENGINEERING THE GEARING OF THE FUTURE IS ELECTRIFIED, AUTOMATED AND NETWORKED. GEARCONTROL: i:gear 4.0 GEARCONTROL-SYSTEM GEARCONTROL-OIL EISENBEISS LEADING THE WAY IN SPECIAL GEAR ENGINEERING
More informationEP364 USER MANUAL ALARM AND MANAGEMENT SYSTEM
EP364 USER MANUAL ALARM AND MANAGEMENT SYSTEM User Manual v1.0 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: DO NOT use
More informationTECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB
Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7
More informationTRACENET TM TCM18 CONTROL AND MONITORING SYSTEM
TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to
More informationPRODUCTS AND SOLUTIONS FOR PUMPING, IRRIGATION AND PIPING
PRODUCTS AND SOLUTIONS FOR PUMPING, IRRIGATION AND PIPING TRA DITIONS AND INNOVATION Since 1922 The first LOVATO Electric headquartes founded in Bergamo in 1922: the starting point of the grand industrial
More informationP2267 NETWORK INTERFACE
P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61
More informationINSTALLATION INSTRUCTIONS
www.altronicinc.com INSTALLATION INSTRUCTIONS WARNING: WARNING: DEVIATION DEVIATION FROM THESE FROM INSTRUCTIONS THESE INSTRUCTIONS MAY LEAD MAY TO IMPROPER LEAD TO OP- ERATION OF IMPROPER THE MACHINE
More informationMHC Series Sensors
MHC - 4000 Series Sensors Smart Sensors for Permanent Installation Shaft Speeds above 30 RPM & 0.25-60 RPM Sigma Sensors for Intermittant Operation Kittiwake Holroyd Ltd A Kittiwake Group Company The MHC
More informationMULTIGUARD MULTIGUARD USERS MANUAL TYPE S3/240W 26/01/2010
195,00 mm N MAIN CONNECTION Description Type S3 240W Uninterruptable Power Supply is an industrial grade unit for stationary and indoor use only. ACCESS HOLE FOR OUTPUT VOLTAGE ADJUSTMENT PROTECTION UNIT
More informationINDEX. 1.1 Main Features Environmental Conditions and Power Requirement Optional Accessories Tyre-Killer Main Parts...
ISO 9001: 2008 EN ISO 14001: 2004 SECURITY SYSTEMS Tyre Killers INSTALLATION INSTRUCTIONS ELECTROMECHANICAL TYRE KILLERS INDEX Page 1. GENERAL INFORMATION... 3 1.1 Main Features... 3 1.2 Environmental
More informationMeasuring Recording Online Monitoring Regulation Alarming
Measuring Recording Online Monitoring Regulation Alarming Temperature Humidity CO 2 Dew point Atmospheric pressure Analog signals Two-state inputs Pulses Battery operated recorders and printers Economical
More informationLAYOUT The system requires no data network. Very simple installation. Only 220V ac power supply indispensable. LEGEND P ET C P COIN BAR PAN KIT CAP
13 LAYOUT The system requires no data network. Very simple installation. Only 220V ac power supply indispensable. LEGEND P ET C P COIN PAN KIT CAP PARKY NS ET C Entrance Station (detector included) PARKY
More informationBlueSpin Magnetic Hotplate Stirrer
BlueSpin Magnetic Hotplate Stirrer BlueSpin LCD Digital 7 Inch Square Magnetic Hotplate Stirrer MS7-H550-Pro 7 inch square hotplate magnetic stirrers are widely used in chemical synthesis, physical and
More informationPEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K
PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)
More informationREC-8R Environmental Control. Operation and Installation Manual
REC-8R Environmental Control Operation and Installation Manual This manual is published by Rotem Computerized Controllers Ltd. All rights to this publication are reserved. No part of this document may
More informationPanel Mounted Fault Annunciator Series
Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with 8, 16, 24, 32, 40 and 48 signal inputs Status retention of inputs and sequence in case
More informationINSTALLATION INSTRUCTIONS
www.altronicinc.com INSTALLATION INSTRUCTIONS WARNING: WARNING: DEVIATION DEVIATION FROM THESE FROM INSTRUCTIONS THESE INSTRUCTIONS MAY LEAD MAY TO IMPROPER LEAD TO OP- ERATION OF IMPROPER THE MACHINE
More informationMark 25 Ultrapure Water Conductivity Analyzer
Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects
More information