All Clear: How a UPS operates to clear faults

Size: px
Start display at page:

Download "All Clear: How a UPS operates to clear faults"

Transcription

1 All Clear: How a UPS operates to clear faults 12 th /13 th March Alex Emms Operations Director Kohler Uninterruptible Power

2 Company Overview Uninterruptible Power Supplies Ltd (UPSL) founded First 3ph transformerless UPS in UK&I First 3ph transformerless modular UPS in UK&I UPSL acquired by Kohler Power Group UPSL Sales & Service operations in Singapore Kohler Co. acquires Pure Power Systems, Ireland 1997 Critical Power Protection Solutions UPSL renames to become Kohler Uninterruptible Power UPS & Emergency Lighting Single and Three Phase systems Transformerless UPS from 1kVA to 5 MVA BS EN Kitemarked emergency lighting Modular & Standalone 10kVA to 3.3MVA Choice of engine manufacturers Service Excellence Nationwide 24/7 Service Maintenance & Response Contracts Remote Monitoring Best in Class Customer NPS rating ISO9001, ISO14001, OHSAS Years of Experience c.100 Employees Installed UPS Base Service Contracts +90% First Time Fix Rate

3 Content 1. How does the UPS react to a downstream fault. 2. Fault clearance with static bypass. 3. Fault clearance without static bypass. 4. Q&A 3

4 How does a UPS react to a fault downstream Inverter has limited fault clearing capability. eg. 2.5 In for 100mS Bypass supply has high fault clearing capabilities. eg. 10 In for 10mS Short Circuit!! 4

5 How does a UPS react to a fault downstream? SHORT CIRCUIT Fault occurs downstream Is the fault >150%? Is the bypass available? Transfer load to the static bypass Has the fault cleared? Return load to Inverter OVERLOAD Overload timer activated Fault cleared within time? Return to rmal Operation Inverter gives max. short circuit current Short circuit timer activated Bypass or UPS protection operates Has the fault cleared? Inverter turns off. Return to rmal Operation 5

6 Fault clearance on Bypass BS th Edition Chapter 55 Other Equipment Additional requirements for installations incorporating static convertors Where fault protection for parts of the installation supplied by the static convertor relies upon the automatic closure of the bypass switch and the operation of protective devices on the supply side of the bypass switch is not within the time required by Section 411, supplementary equipotential bonding shall be provided between simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts on the load side of the static convertor in accordance with Regulation

7 Fault clearance on Bypass BS7671 section Allows for the use of the static bypass to operate downstream protective devices supplied by a UPS under certain circumstances. Short Circuit!! By using the static bypass supply the protective device must operate in the required time (0.4 sec or 5 sec) This is not permitted when supplying a safety service (see section ). 7

8 Fault clearance on Inverter Chapter 56 Safety Services Uninterruptible power supply sources (UPS) Where an uninterruptible power supply is used, it shall: (i) be able to operate distribution circuit protective devices, and (ii) be able to start the safety devices when it is operating in the emergency condition from the inverter supplied by the battery, and (iii) comply with the requirements of Regulation , and (iv) comply with BS EN and BS EN , as applicable. Examples of safety services include (this list is not exhaustive): - Emergency lighting - Fire evacuation systems - Fire pumps - Smoke ventilation systems - Fire rescue service lifts - Fire services communication systems - Fire detection and alarm systems - Essential medical systems - CO detection and alarm systems - Industrial safety systems 8

9 How does a UPS powering safety services react to a fault downstream? SHORT CIRCUIT Fault occurs downstream Is the fault >150%? Chapter 56 Safety Services Transfer load to the static bypass Has the fault cleared? Return load to Inverter OVERLOAD Overload timer activated Fault cleared within time? Return to rmal Operation Inverter gives max. short circuit current Short circuit timer activated Bypass or UPS protection operates Has the fault cleared? ncompliant Return to rmal Operation 9

10 Fault clearance on Inverter BS The inverter must be capable of operating both the protective devices and the dependent safety services. Short Circuit!! The Inverter must be able to operate the protective device in the required time (0.4 sec or 5 sec) in all circumstances. The inverter must also be capable of handling any start-up currents of the connected load without using the static bypass. 10

11 System design implications For systems covered by BS th Edition Chapter 56 (Safety Services) Need to increase the size of the UPS inverter to operate protection devices and clear faults as bypass cannot be used. This can increase operating costs unless the inverter is of a modular type that can switch down significantly. Alternatively, reduce the size / activation current of the protective devices being used in the system, so an inverter better matched to the load can activate them. 11

12 Additions to the 18 th Edition BS th Edn. Chapter 41 Protection against Electric Shock 419 PROVISIONS WHERE AUTOMATIC DISCONNECTION ACCORDING TO REGULATION IS NOT FEASIBLE Where automatic disconnection is not feasible in circumstances where: (i) electronic equipment with limited short-circuit current is installed, or (ii) the required disconnection times cannot be achieved by a protective device the provisions of Regulations and are applicable For installations with power electronic convertors with nominal voltage U0 greater than 50 V AC or 120 V DC and where automatic disconnection is not feasible, the output voltage of the source shall be reduced to 50 V AC or 120 V DC or less in the event of a fault between a live conductor and the protective conductor or Earth in a time as given in Regulation , or , as appropriate (see BS EN ). The power electronic convertor shall be one for which the manufacturer gives adequate methods for the initial verification and periodic inspection and testing of the installation. 12

13 Additions to the 18 th Edition SHORT CIRCUIT Fault occurs downstream Is the fault >150%? Is the bypass available? Transfer load to the static bypass Has the fault cleared? Return load to Inverter OVERLOAD Overload timer activated Fault cleared within time? Return to rmal Operation Inverter gives max. short circuit current Short circuit timer activated Bypass or UPS protection operates Has the fault cleared? Reduces Voltage in Reqd Time Return to rmal Operation 13

14 System design implications BS7671 Chapter UPS voltage reduction must take place in required time ask manufacturer. Chapter 41 voltage reduction approach can not be used for safety services. Chapter 41 does NOT allow for the shutdown of the inverter to be used as disconnection in all situations. This could be used for non safety services that would normally use the static bypass to operate the protective device ONLY when the bypass is not available (I.E. during a mains failure). te - This will also shutdown all connected loads. 14

15 Questions? Alex Emms DCW Stand D920 15

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2008 + Amendment 1:2011 (Corrigendum June 2013) Requirements for Electrical Installations IET Wiring Regulations Seventeenth Edition ISBN-13: 978-1-84919-730-4 BS 7671 Requirements

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A

(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A Electrical Installation & Test Engineers DETAILS OF THE CLIENT Client / Freshco Food Stores, Kiln Park Business Estate, Milton Keynes, MK3 5FS ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with

More information

» EN50171» Lighting» Reliable

» EN50171» Lighting» Reliable PowerPro EL Ranges Single & Three Phase Options EL100XA / ELMOD / EL100 / EL300DSP / CBU» EN50171» Lighting» Reliable The PowerPro EL ranges are Static Inverter Systems designed specifically for emergency

More information

Your specialist partner for total electrical compliance. Electrical Testing

Your specialist partner for total electrical compliance. Electrical Testing Your specialist partner for total electrical compliance Electrical Testing "To achieve compliance with the legal requirements of the Electricity at Work Regulations 1989 requires proof that an electrical

More information

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Introduction Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Who are Certsure? Where do we come from? 1923 - A National Register created 1956 - NICEIC established as a Charity

More information

An overview of the main proposals in BS th Edition. Electrical Contractors Association

An overview of the main proposals in BS th Edition. Electrical Contractors Association An overview of the main proposals in BS 7671 17 th Edition Electrical Contractors Association Why have Regulations Behold the electrician standing there. Soot, soil & verdigris defile his greasy hair.

More information

Guide to: 17 th Edition Consumer Units

Guide to: 17 th Edition Consumer Units Guide to: 17 th Edition Consumer Units Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

User Manual. Power Distribution Unit. Version: 1.0

User Manual. Power Distribution Unit. Version: 1.0 User Manual Power Distribution Unit Version: 1.0 Table Of Contents 1. Introduction... 1 1-1 Package Contents... 1 1-2 Safety... 1 1-3 Disposing of PDU... 1 1-4 Function... 1 1-5 Overview... 2 2. Installation...

More information

ER 52 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) EA 147M(c)(i) (1 mark) EA 147M(c)(ii)

ER 52 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) EA 147M(c)(i) (1 mark) EA 147M(c)(ii) ER 52 Electrician Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker can

More information

Replacing a consumer unit in domestic premises where lighting circuits have no protective conductor

Replacing a consumer unit in domestic premises where lighting circuits have no protective conductor Replacing a in domestic premises where lighting circuits have no protective conductor This is one of a series of Best Practice Guides produced by the Electrical Safety Council* in association with leading

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017 STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017 STANDARD INFORMATION Standard Number: UL 412 Standard Name: Refrigeration Unit Coolers Standard Edition and Issue Date: 5 th Edition Dated August 22,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 3323 - CENTRAL BATTERY EQUIPMENT [for Evanston campus only] PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Contact Details. Please note that some of the contact details on this PDF document may not be current.

Contact Details. Please note that some of the contact details on this PDF document may not be current. Contact Details Please note that some of the contact details on this PDF document may not be current. Please use the following details if you need to contact us: Telephone: 0844 879 3588 Email: customer.services@gdcgroup.co.uk

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

BS Outcomes 6

BS Outcomes 6 BS7671 2015 Outcomes 6 Inspection and testing 6.1 Identify the general requirements for inspection and testing of installations 6.2 State the need for diagrams, charts or tables to be available e prior

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

EMEX 110 and EMEL. EMEX 110 and EMEL. 110, 50 and 24 volt AC/DC Central Battery Systems. EMEX 110 and EMEL

EMEX 110 and EMEL. EMEX 110 and EMEL. 110, 50 and 24 volt AC/DC Central Battery Systems. EMEX 110 and EMEL and EMEL and EMEL 110, 50 and 24 volt AC/DC Central Battery Systems and EMEL System design units provide 110V AC/DC to provide power to 110V slave fittings or converted mains luminaires. Systems provide

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

Mains Power Filter 970MF10 970MF20. Installation Instructions

Mains Power Filter 970MF10 970MF20. Installation Instructions Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...

More information

Organizations need a secure, reliable, sustainable power protection system to safeguard mission critical applications and reduce energy consumption:

Organizations need a secure, reliable, sustainable power protection system to safeguard mission critical applications and reduce energy consumption: Company Profile Organizations need a secure, reliable, sustainable power protection system to safeguard mission critical applications and reduce energy consumption: whether you are an oil and gas, petrochemical,

More information

Guide to sollysta Wiring Accessories

Guide to sollysta Wiring Accessories Guide to sollysta Wiring Accessories Introduction This guide expands upon some of the requirements found in the 17 th Edition of the IEE Wiring Regulations and Building Regulations and how they affect

More information

3. RCCB (residual current operated circuit-breaker without integral overcurrent protection)

3. RCCB (residual current operated circuit-breaker without integral overcurrent protection) RESIDUAL CURRENT DEVICE (RCD) - Contents 1. Introduction 2. General 3. RCCB (residual current operated circuit-breaker without integral overcurrent 4. RCBO (residual current operated circuit-breaker with

More information

MAC-A R410A Series Air cooled Modular Chiller

MAC-A R410A Series Air cooled Modular Chiller Catalogue MAC R410A 2011(60Hz) MAC-A R410A Series Air cooled Modular Chiller Model: Refrigerant: Co ling Capacity: MAC210A5 R410A 72kW Overview Based on the successful McQuay air-cooled modular chiller,

More information

METZIN Bearing Induction Heater. Operating Instructions

METZIN Bearing Induction Heater. Operating Instructions METZIN Bearing Induction Heater Operating Instructions Model: MIH-8.0/ S Specifications and chassis color subject to change without notice. METZIN Technologies & Consulting Pte Ltd. Tel: +65 6898 2957

More information

Early Warning Fire Detection Engineering

Early Warning Fire Detection Engineering Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful

More information

Stored Water District Heating Interface Units. Heat Interface Units

Stored Water District Heating Interface Units. Heat Interface Units Stored Water District Heating Interface Units Heat Interface Units Why choose Elson Elson are a Heatrae Sadia company, the UK s leading manufacturer of hot water solutions utilising thermal store technology

More information

WELCOME BLUE - NEUTRAL BROWN LIVE GREEN AND YELLOW - EARTH

WELCOME BLUE - NEUTRAL BROWN LIVE GREEN AND YELLOW - EARTH Zephyr 16 DC FAN WELCOME Thank you and congratulation for choosing an EcoAir DC Fan to help you improve the air quality within your home. Inside you will find many helpful tips on how to use and maintain

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60

More information

Declaration of Conformity

Declaration of Conformity Declaration of Conformity DEMONSTRATION OF CONFORMITY WITH RECOGNIZED STANDARDS TO SATISFY THE SAFETY AND EFFECTIVENESS REQUIREMENTS OF THE CANADIAN MEDICAL DEVICES REGULATIONS Name of the medical device

More information

Silcon DP300E Series 480V kVA User Guide

Silcon DP300E Series 480V kVA User Guide Silcon DP300E Series 480V 120 160kVA User Guide Copyright 1999 APC Denmark A/S Due to continuous product development information given in this manual is subject to change without notice. User Guide Silcon

More information

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Maintenance Guide 2015 EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Safety Best Practices Manual

Safety Best Practices Manual CHAPTER 24 OSHA Compliance Checklist te: This is not a comprehensive checklist. It is designed for a typical corporate aviation maintenance department. You must consult the OSHA 1910 Regulations for specific

More information

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING THE ILLUMINATOR ILLUMINATOR SERIES IE The Illuminator Series IE is an interruptible lighting inverter. It transfers to inverter mode (battery

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60519-1 Third edition 2003-07 Safety in electroheat installations Part 1: General requirements Sécurité dans les installations électrothermiques Partie 1: Exigences générales

More information

Compact substation to be placed close to the load center.

Compact substation to be placed close to the load center. Addendum to ESAH Version 3 Connection Guideline Addendum 3.2.1 3.2.1 Substation Categories d. Distribution Substation (Pencawang Elektrik PE) Distribution substations are capacity injection points from

More information

X10 Mini, Midi & Maxi

X10 Mini, Midi & Maxi Industrial Sounder, Sounder Beacon X0 Mini, Midi & Maxi Installation Manual EAT X0 Mini, Midi & Maxi Installation Manual (90F) Contents Overview and purpose... Product assembly... Select wiring method......

More information

Amendment Number 3 of BS how it might affect you

Amendment Number 3 of BS how it might affect you Amendment Number 3 of BS7671 2008 - how it might affect you Geoff Cronshaw provides us with a look ahead at the proposals of Amendment 3 to BS 7671:2008 IET Wiring Regulations and the resulting changes

More information

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING ALSO AVAILABLE FROM MYERS POWER PRODUCTS: ILLUMINATOR SERIES CIII 4.8 kva TO 50 kva THREE PHASE ILLUMINATOR CM 500 VA TO 2000 VA SINGLE PHASE

More information

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671 Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Catalogue MAC-D-2013 (50Hz) MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Model: Refrigerant: Cooling Capacity: Heating Capacity: MAC210D5-MAC1680D5 MAC230D5-MAC1840D5 MAC210DR5-MAC1680DR5 MAC230DR5-MAC1840DR5

More information

3 o/c2 The symbol used to show that a BS 88 device has a motor circuit application is a gg b gm c l z d I 2.

3 o/c2 The symbol used to show that a BS 88 device has a motor circuit application is a gg b gm c l z d I 2. Sample Questions - C&G 2382 17th Edition PaperB 1 o/c1 Electrical installation design shall take into account a electromagnetic disturbances b direct lightning strikes c current world copper prices d local

More information

Recent Topics in IEC TC 62 (Electrical Equipment in Medical Practice) and its Subcommittees

Recent Topics in IEC TC 62 (Electrical Equipment in Medical Practice) and its Subcommittees INTERNATIONAL ELECTROTECHNICAL COMMISSION Recent Topics in IEC TC 62 (Electrical Equipment in Medical Practice) and its Subcommittees Don Heirman presenting for Robert Sitzmann (TC 62) APEMC symposium

More information

AP-EH500-L/RQA9837. Installation Guide

AP-EH500-L/RQA9837. Installation Guide AP-EH500-L/RQA9837 Duct Mounted Burst Fire Heater The EMC Directive 2004/108/EC The Low Voltage directive 2006/95/EC 1.0 Duct Mounted Burst Fire Heater This Burst Fire Heater should only be used as a supplementary

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Standards Update Notice (SUN) Issued: January 9, 2017

Standards Update Notice (SUN) Issued: January 9, 2017 Standard Information This SUN contains new/revised requirements from updates dated September 2, 2016 and October 7, 2016 Standard Number: UL 1795 Standard Name: Hydromassage Bathtubs Standard Edition and

More information

IT system floor-standing distribution

IT system floor-standing distribution IT system floor-standing distribution cabinet series -IPS-F/EDS for supplying power to medical locations in accordance with IEC 60364-7-710 and featuring a built-in insulation fault location system IT

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY π H-6621 INDUSTRIAL DEHUMIDIFIER 1-800-295-5510 uline.com WARNINGS Plug into a grounded 3 prong outlet. Do not remove ground prong. Do not use an adapter. Do not use an extension cord if possible. Failure

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

NFPA 70E Edition Update

NFPA 70E Edition Update NFPA 70E- 2018 Edition Update Paul Colangelo- STSC, CHST, CET, CRIS National Director of Compliance Programs ClickSafety 1 ASSE Construction Practice Specialty Quarterly Meeting 11/17/2017 Agenda Overview

More information

PROFILE. industrial services rental trading

PROFILE. industrial services rental trading PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field

More information

Arc Fault Detection Devices (AFDDs) Protecting People and Property

Arc Fault Detection Devices (AFDDs) Protecting People and Property Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS

More information

Test Unit GTL 100 for Fire Detectors

Test Unit GTL 100 for Fire Detectors Test Unit GTL 100 for Fire Detectors Description and Operation Manual Zertifiziertes QM System Nach DIN EN ISO 9001 Description and Operation Manual Table of Contents 1. Instructions 1.1 General 1.2 Standards

More information

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016 IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the

More information

GAS EXTINGUISHING SYSTEMS COMPACT EXTINGUISHING SYSTEMS. OneU. Fire Protection Systems for 19" Racks

GAS EXTINGUISHING SYSTEMS COMPACT EXTINGUISHING SYSTEMS. OneU. Fire Protection Systems for 19 Racks GAS EXTINGUISHING SYSTEMS COMPACT EXTINGUISHING SYSTEMS OneU Fire Protection Systems for 19" Racks SMALL BUT IT systems once occupied an entire area of a computer center but now are typically combined

More information

FDOOT241-9, FDOOT241-A, FDO241, FDT241

FDOOT241-9, FDOOT241-A, FDO241, FDT241 Sinteso S-LINE FDOOT241-9, FDOOT241-A, FDO241, FDT241 Automatic fire detectors For the automatically addressed detector bus FDnet The ideal fire detector for every application Line separators for uninterrupted

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60364-1 Fifth edition 2005-11 Low-voltage electrical installations Part 1: Fundamental principles, assessment of general characteristics, definitions This English-language version

More information

WR-E - Practical Electrical Wiring Standards - IEE BS Edition+A12011 Edition

WR-E - Practical Electrical Wiring Standards - IEE BS Edition+A12011 Edition IDC Technologies - Books - 1031 Wellington Street West Perth WA 6005 Phone: +61 8 9321 1702 - Email: books@idconline.com WR-E - Practical Electrical Wiring Standards - IEE BS7671-2008 Edition+A12011 Edition

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

OOH740-A9-Ex Multisensor fire detector

OOH740-A9-Ex Multisensor fire detector OOH740-A9-Ex Multisensor fire detector ASAtechnology TM For potentially explosive areas Cerberus PRO Collective Signal processing with ASAtechnology Multiple protocol detector (collective/c-net-ex) Event-controlled

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60364-4-41 Fifth edition 2005-12 GROUP SAFETY PUBLICATION Low-voltage electrical installations Part 4-41: Protection for safety This English-language version is derived from

More information

Project Briefing Document. Section 3 Electrical Services design guide and specifications

Project Briefing Document. Section 3 Electrical Services design guide and specifications ESTATES SUPPORT SERVICE Project Briefing Document Section 3 Electrical Services design guide and specifications Issue 1.1 June 2014 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor...

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60364-4-41 Fourth edition 2001-08 GROUP SAFETY PUBLICATION Electrical installations of buildings Part 4-41: Protection for safety Protection against electric shock This English-language

More information

AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1

AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1 PRODUCT DATA SHEET AUTOMATIC FIRE CURTAIN FM 1 AUTOMATIC FIRE CURTAIN FIRE CURTAIN FM 1 FM-1 fire curtains are used where, if there is a fire, it is necessary to create a temporary barrier within an opening

More information

LiteMinder. LM Series Inverter Pure Sine Wave Modular Inverter Technology. Fast Transfer System 1.0 to 18.75KVA LED Compatible

LiteMinder. LM Series Inverter Pure Sine Wave Modular Inverter Technology. Fast Transfer System 1.0 to 18.75KVA LED Compatible LiteMinder Fast Transfer System 1.0 to 18.75KVA LED Compatible Series Pure Sine Wave Modular Technology Modular AC System Evenlite s LiteMinder Central System provides an innovative Emergency Lighting

More information

RELAY BASES & COVERS

RELAY BASES & COVERS RELAY BASES & COVERS FOR SMOKE, HEAT & CARBON MONOXIDE ALARMS Instruction Manual Contains vital information on the product s operation and installation. Read and retain carefully. If you are just installing

More information

Electrical Hazards and NFPA-70E: Protecting Your Employees

Electrical Hazards and NFPA-70E: Protecting Your Employees Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Operating Instructions

Operating Instructions Bracken Hill South West Industrial Estate Peterlee Co Durham SR8 2SW ENGLAND Tel: +44(0)191 5863511 www.seaward.co.uk sales@seaward.co.uk service@seaward.co.uk Part Number 347A550 Revision 1 2006 Seaward

More information

Fire / CO Alarm Interface

Fire / CO Alarm Interface Fire / CO Alarm Interface Model: Ei414 Instruction Manual Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your Fire

More information

FDA241, FDA221 Siemens ASD

FDA241, FDA221 Siemens ASD FDA241, FDA221 Siemens ASD Patented Technology Sinteso TM Cerberus PRO Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red)

More information

Instruction Manual (Supplementary) Open Type Inverter

Instruction Manual (Supplementary) Open Type Inverter 1 Instruction Manual (Supplementary) Open Type Inverter TOSVERT VF-S11 Thank you for purchasing a Toshiba Open type TOSVERT VF-S11 series inverter. This Manual gives a supplementary explanation of some

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

Saletto. Operating Instructions. Low Profile Panel Heaters Models: LPP050 LPP075 LPP100 LPP150. A world of expertise

Saletto. Operating Instructions. Low Profile Panel Heaters Models: LPP050 LPP075 LPP100 LPP150. A world of expertise A world of expertise Operating Instructions These instructions should be read carefully and retained for future use. Note also the information presented on the appliance. Saletto Low Profile Panel Heaters

More information

Girona. Operating Instructions. Glass Panel Heaters. Models: GFP050 W/B GFP075 W/B GFP100 W/B GFP150 W/B GFP200 W/B. A world of expertise

Girona. Operating Instructions. Glass Panel Heaters. Models: GFP050 W/B GFP075 W/B GFP100 W/B GFP150 W/B GFP200 W/B. A world of expertise A world of expertise Operating Instructions These instructions should be read carefully and retained for future use. Note also the information presented on the appliance. Girona Glass Panel Heaters Models:

More information

CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT

CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT These Conditions of Service apply to all NBN Services. These Conditions of Service form part of our Standard Form of Agreement found at www.adam.com.au/legal.

More information

Line Isolation & Overload Monitor. E05 Series. Installation Instructions MU TE TE S T E. S.P. ALARM MUT E D OVE R LOAD WAR NING PHC WARNING

Line Isolation & Overload Monitor. E05 Series. Installation Instructions MU TE TE S T E. S.P. ALARM MUT E D OVE R LOAD WAR NING PHC WARNING MU TE ALARM MUT E D OVE R LOAD WAR NING E. S.P. E0 5 LI NE IS OLATION AND OVERLOAD MONITOR 9 6 5 ma 8 7 4 3 2 1 PO W E R PR OSPE CTIVE HAZ ARD CUR RENT LEVE L TE S T PHC WARNING Line Isolation & Overload

More information

The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition

The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition Issued in the interests of safety by The Legal Obligations of Employers to Maintain all Electrical Installations

More information

Electrical Safety Policy and Management System

Electrical Safety Policy and Management System TITLE: PAGE: 1 OF 14 Housing Solutions Limited Electrical Safety Policy and Management System Page 1 of 15 TITLE: PAGE: 2 OF 14 FOREWORD This document details the system for the management of electrical

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

GUARDIANTM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED MECHANICALLY PROTECTED CABLES

GUARDIANTM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED MECHANICALLY PROTECTED CABLES Cables Limited MADE IN IRELAND SINCE 1934 QUALITY APPROVED CABLES IDH CABLES LIMITED GUARDIANTM MECHANICALLY PROTECTED CABLES The original BS-8436, IS-273 multifunctional, easy to install, connect-and-protect

More information

National Electrical Code

National Electrical Code National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation

More information

Notice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world

Notice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world Notice No. 7 Rules and Regulations for the Classification of Ships, July 2014 The status of this Rule set is amended as shown and is now to be read in conjunction with this and prior Notices. Any corrigenda

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

Warning Signs & Labels Fitted to Electrical Equipment on Rail Mounted Vehicles

Warning Signs & Labels Fitted to Electrical Equipment on Rail Mounted Vehicles Railway Group Standard Date August 1996 Warning Signs & Labels Fitted to Electrical Equipment on Rail Mounted Vehicles Synopsis This Standard details the requirements for Danger: electricity triangular

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal FBC 419.3.15.6 All low-voltage system main or branch circuits entering or exiting the structure shall

More information

ELECTRICAL SAFETY IN HEALTHCARE FACITILIES

ELECTRICAL SAFETY IN HEALTHCARE FACITILIES ELECTRICAL SAFETY IN HEALTHCARE FACITILIES BY ENGR. S.M. NASEERUDDIN Dar Al-Majd Consulting Engineers Riyadh, Saudi Arabia ABSTRACT The increasing use of electrical diagnostic and treatment equipment in

More information

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Microgrid Fault Protection Based on Symmetrical and Differential Current Components Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information