PC4010 v3.0 Installation Manual DLS-2 v1.3

Size: px
Start display at page:

Download "PC4010 v3.0 Installation Manual DLS-2 v1.3"

Transcription

1 PC4010 v3.0 Installation Manual DLS-2 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.

2 WARNING Please Read Carefully Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system. System Failures This system has been carefully designed to be as effective as possible. There are circumstances, however, involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm system of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons. Some but not all of these reasons may be: Inadequate Installation A security system must be installed properly in order to provide adequate protection. Every installation should be evaluated by a security professional to ensure that all access points and areas are covered. Locks and latches on windows and doors must be secure and operate as intended. Windows, doors, walls, ceilings and other building materials must be of sufficient strength and construction to provide the level of protection expected. A reevaluation must be done during and after any construction activity. An evaluation by the fire and/or police department is highly recommended if this service is available. Criminal Knowledge This system contains security features which were known to be effective at the time of manufacture. It is possible for persons with criminal intent to develop techniques which reduce the effectiveness of these features. It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not provide the protection expected. Access by Intruders Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the proper operation of the system. Power Failure Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a device operates only by AC power, any interruption, however brief, will render that device inoperative while it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a security system. After a power interruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended. Failure of Replaceable Batteries This system s wireless transmitters have been designed to provide several years of battery life under normal conditions. The expected battery life is a function of the device environment, usage and type. Ambient conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery life. While each transmitting device has a low battery monitor which identifies when the batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance will keep the system in good operating condition. Compromise of Radio Frequency (Wireless) Devices Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio path or deliberate jamming or other inadvertent radio signal interference. System Users A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm. Smoke Detectors Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of reasons, some of which follow. The smoke detectors may have been improperly installed or positioned. Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the other side of closed doors. Smoke detectors may not detect smoke from fires on another level of the residence or building. Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches or arson. Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning to allow all occupants to escape in time to avoid injury or death. Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installation instructions. They cannot discriminate between intruders and intended occupants. Motion detectors do not provide volumetric area protection. They have multiple beams of detection and motion can only be detected in unobstructed areas covered by these beams. They cannot detect motion which occurs behind walls, ceilings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether intentional or unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or any other part of the detection system will impair its proper operation. Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness can be reduced when the ambient temperature rises near or above body temperature or if there are intentional or unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters, radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on. Warning Devices Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if there is an intervening wall or door. If warning devices are located on a different level of the residence or premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other appliances, or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired person. Telephone Lines If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect. Insufficient Time There may be circumstances when the system will operate as intended, yet the occupants will not be protected from the emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may not occur in time to protect the occupants or their belongings. Component Failure Although every effort has been made to make this system as reliable as possible, the system may fail to function as intended due to the failure of a component. Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance. The complete system should be tested weekly and immediately after a break-in, an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity inside or outside the premises. The testing should include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of the system. Security and Insurance Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation. AVIS: L étiquette de l Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de protection, d exploitation et de sécurité des réseaux de télécommunications. Industrie Canada n assure toutefois pas que le matériel fonctionnera à la satisfaction de l utilisateur. Avant d installer ce matériel, l utilisateur doit s assurer qu il est permis de le raccorder aux installations de l entreprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode acceptée de raccordement. L abonné ne doit pas oublier qu il est possible que la conformité aux conditions énoncées ci-dessus n empêchent pas la dégradation du service dans certaines situations. Les réparations de matériel homologué doivent être effectuées par un centre d entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut demander à l utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l utilisateur ou à cause de mauvais fonctionnement. Pour sa propre protection, l utilisateur doit s assurer que tous les fils de mise à la terre de la source d énergie électrique, les lignes téléphoniques et les canalisations d eau métalliques, s il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales. AVERTISSEMENT: L utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir recours à un service d inspection des installations électriques, ou à un électricien, selon le cas. L indice de charge (IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut être raccordée à un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut être constituée de n importe quelle combinaison de dispositifs, pourvu que la somme des indices de charge de l ensemble des dispositifs ne dépasse pas 100. L Indice de charge de ce produit est 0.1B. NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. Industry Canada does not guarantee the equipment will operate to the user s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. User should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate. The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100. The Load Number of this unit is 0.1B.

3 Table of Contents Section 1: Introduction Out Of The Box Specifications and Features...1 Section 2: Installation and Wiring Planning the System Terminal Descriptions Current Ratings Alarm Control Panel and Modules Combus Operation and Wiring Zone Wiring Specialized Zone Wiring Programmable Output Wiring AML Device Wiring Wiring Powered Devices (AUX, SAUX+) Telephone Line Wiring Bell Output Wiring (BELL+ and BELL-) Earth Ground Wiring Applying Power (AC and Battery) Lithium Batteries 8 Section 3: How to Program Introduction to Programming Programming by Reference Number Programming Decimal Data Programming Hexadecimal Data Programming Toggle Options...10 Section 4: Module Enrollment Enrolling Keypads and Modules Deleting Modules Confirming Modules Enrolling AML Devices...12 Section 5: Partitions and Zones Zone Supervision Creating Partitions Adding Zones to Partitions Zone Programming...14 Section 6: Keypad Operation Partition Keypads Global Keypads Keypad Time-out Keypad Blanking Fire, Auxiliary and Panic Keys Keypad Lockout Keypad Tampers Function Key Programming...19 Section 7: Installer and Access Codes Installer s Code Other Access Codes Guard Code Access Code Options Access Levels...23 Section 8: Arming and Disarming Arming and Disarming Options Automatic Arming Section 9: Entry and Exit Delay Entry and Exit Delay Times Entry and Exit Delay Options Section 10: System Programming AC/DC Power Options Bell Circuit Supervision Clock Options Event Messages Swinger Shutdown Tampers Telephone Line Supervision Test Transmissions Transmission Delay Cross Zone (Police Code) Alarm Section 11: Programmable Outputs Main Panel Outputs Programmable Output Options Output Pulse Times Section 12: Communications Programming Telephone Numbers Account Numbers Dialing Parameters Communicator Toggle Options Dialer Direction Communicator Formats Reporting Codes Section 13: Downloading Downloading Options Periodic Call-up PC-Link Section 14: Event Scheduling Date Schedules Holiday Groups Open/Close Suppression Arming/Disarming Schedules Scheduled AMS-220/220T Smoke Detector Test Section 15: LINKS Communications LINKS1000 (Cellular Communications) LINKS2XXX (Long-range Radio Communications) Section 16: Diagnostics and Troubleshooting General Diagnostics Restoring Factory Default Programming Hardware Reset Viewing Trouble Conditions System Fault Squawk Appendix A: Reporting Codes 42 Appendix B: Zone Reporting Codes 44 Appendix C: ASCII Characters 45 i

4 ii PC4010 Wiring Diagram

5 Section 1: Introduction 1.1 Out Of The Box Please verify that the following components are included in the PC4010 package. 1 PC4050C or PC4001C cabinet 1 PC4010A main control module 1 Hardware package which includes: 16 EOL resistors (5600Ω) 1 Black cabinet plug 1 Green ground strap PCB mounting standoffs 1 set of documents which includes: 1 PC4010 Installation Manual 1 PC4010 Programming Worksheets 1 PC4010 Instruction Manual 1.2 Specifications and Features Main Control Panel AC Input 16 VAC, 40VA minimum Battery Charger 350 ma to charge 12VDC lead-acid batteries Bell Circuit 12 VDC, 700 ma continuous maximum Auxiliary Power Output: 12 VDC, 500 ma maximum Switched Auxiliary Power Output 12 VDC, 300 ma maximum PGM 1 options: 12 VDC, 50 ma maximum each as standard outputs 12 VDC, 170 ma maximum each when used for Addressable Loop 4-wire Combus power 500 ma maximum 8 Zone inputs Supervised dialer output Earth ground connection All outputs rated to operate over the range of 11.6 to 12.6V for UL listed systems. Expansion Capabilities Up to 64zones total using PC4108A 8 zone input modules PC zone input modules PC4164-RS v2.0 Wireless receiver and wireless devices PGM output for addressable devices Up to 16 keypads total using LCD4500 keypads v2.02 for function key support (number keys 1-5) LCD4501 keypads (with function keys) v2.0 or later Up to 144 low power outputs total using PC4216 low power output modules (v2.1 required for Temporal Fire option) Up to 64 relay outputs total using PC4204 quad relay and power supply module; also for Combus repower (v2.1 required for Temporal Fire option) Up to 32 card access-controlled doors PC4820 dual card reader modules (up to 16) System Printer/DVACS output using PC4400 printer module Backup communication using LINKS1000 Cellular Communicator* LINKS2150 Long-Range transmitter LINKS2450 Long-Range transmitter* Telephone access & automation items using ESCORT4580 Audio Assistant (v1.2 or greater) Remote annunciation using PC zone point annunciator PC zone point/graphic annunciator PC zone point/graphic annunciator Downloading Capabilities Downloading Software: DLS-2 v1.3* PC-Link connector for local upload/download *Not UL listed. Do not use in conjunction with UL listed systems. 1

6 Section 2: Installation and Wiring 2.1 Planning the System The speed and efficiency of installing a MAXSYS system will be greatly enhanced by planning the installation. As a minimum, the following checklist should be used to ensure that all of the details have been considered: Draw a diagram of the installation showing the location of the main panel, all keypads, all zone inputs, all bell outputs, all relay outputs and all annunciators. Indicate all partitions on the diagram. Decide which zones, bell and relay outputs, keypads and remote annunciators belong to each partition. Determine where each system module is going to be located and how far each module will be from the main panel. Determine the current draw on the main panel and each system component used to ensure the system requirements can be met (see Section 2.3 Current Ratings Alarm Control Panel and Modules ). Calculate each wire run using the Combus wiring guidelines. Determine which wire gauge should be used and where to place PC4204 modules to repower the Combus. For Addressable devices, determine where each device is to be located and consult the Addressable Loop wiring guidelines to determine wire gauge and wiring lengths (see Section 2.8 AML Device Wiring ). 2.2 Terminal Descriptions The following terminals appear on the PC4010 Alarm Control Panel: Terminals Red and Black Leads AC AUX+ and AUX- SAUX+ BELL+ and BELL- PGM1 RED, BLK, YEL, GRN Z1 to Z8 TIP, RING, T1, R1 EGND Description Battery Connection. WARNING: Do not connect the battery or transformer until all other wiring is complete. Power Terminals. WARNING: Connect the battery before connecting the AC. Do not connect the battery or transformer until all other wiring is complete. Auxiliary Power, 500mA MAX Switched Auxiliary Power, 300mA MAX Bell/Siren Power. These terminals are used for powering bells, sirens or other devices requiring steady output voltage on alarm; 700mA MAX Programmable Output Terminal. 50mA MAX (standard output) or 170mA MAX (addressable loop) Combus Terminals. The Combus is used by the panel and the modules to communicate with each other. RED and BLK are used for power, and YEL and GRN for data. NOTE: The four Combus terminals of the main panel must be connected to the four Combus terminals or wires of all modules. For instructions regarding Combus wiring, refer to Section 2.4 Combus Operation and Wiring. Zone Input Terminals. Zone inputs Z1 to Z8 are provided for wiring 168 zones on the alarm control panel Telephone Line Terminals Earth Ground Connection. A ground connection assembly is included with the control panel. Please refer to the control panel wiring diagram for instructions on how to wire the ground connection. 2

7 S e c t i o n 2 : I n s t a l l a t i o n a n d W i r i n g 2.3 Current Ratings Alarm Control Panel and Modules In order for the system to operate properly, the power output of the alarm control panel and power supply modules cannot be exceeded. Use the data below to ensure that the available current is not exceeded. PC4010 Alarm Control Panel AUX - 500mA available for devices connected to the AUX, SAUX+ and PGM terminals and modules connected to Combus terminals. At least 100mA must be reserved for the Combus. To calculate the amount of current required, complete the following chart: Main Panel Current Calculation Maximum (Standby or Alarm) AUX (500mA max.) SAUX+ (300mA max.) PGM1 (50/170mA max.*) Combus (500mA max.)** Calculating Total Current Requirement Once you have determined which modules will draw power from the main panel, use the following chart to calculate the Combus current. Combus Current Selection Chart Item Current (ma) x Quantity Total (ma) Keypad 50 x PC4108A* 30 x Current required for connected devices = PC4116* 30 x Current required for connected devices = PC4164-RS 110 x PC x PC4702BP 75 x PC x PC4216* 15 x Current required for connected devices = ESCORT x PC x PC x SECTION Bell+ (700mA max. continuous) Total (must not exceed 900mA) Alarm (for 4 min. maximum) Bell (2A max.) * PGM1 (Standard Output) = 50mA max. PGM1 (Addressable Loop) = 170mA max. To calculate Addressable Loop current, see Section 2.8 AML Device Wiring. ** See Combus Current Calculation Chart at right. NOTE: For UL, ULC and Fire applications, the total standby AND alarm current cannot exceed 900mA. PC4010 Module Ratings The current draw of compatible PC4010 modules is listed below: Device...Current Draw (ma) Keypad (PRS400) PC4108A Zone Expander PC4116 Zone Expander PC4164-RS Wireless Receiver PC4701 Fire Module PC4702BP Dual Bell Output Module PC4204 Relay Output Module PC4216 Low Current Output Module ESCORT4580 Audio Assistant PC4400 Serial Printer Interface Module PC4820 Access Control Module Total Combus Current = * These units draw current from the Combus to power devices external to the module. This current must be added to the total Combus current. See manufacturer's specifications for the current draw of each device. Each LED assembly draws up to 20mA of current. 2.4 Combus Operation and Wiring The Combus is used by the control panel and the modules to communicate with each other. The four Combus terminals of the main panel must be connected to the four Combus terminals or wires of all modules. Modules can be home run, connected in a daisy chain or T-tapped anywhere on the Combus. The following rules MUST be followed when wiring the Combus: 1. The Combus must be run in minimum 22-gauge wire. 2. No module can be more than 1000' (305m) in cable length from the main control panel. 3. Shielded wire should only be used in areas that present excessive RF noise or electromagnetic interference. If shielded wire is used, the maximum distance a module can be located from the main panel is significantly reduced. Check the capacitance limit of 3

8 the wire to calculate the maximum distance (see Capacitance Limits below). 4. The total capacitance of the Combus wiring must not exceed 80nF (see Capacitance Limits below). Line Loss When current is drawn through a piece of wire, voltage will be lost due to the wire s resistance. This voltage loss must be considered for all installations. To ensure proper operation, at least 12.5VDC must be applied to all modules on the system (when AC is applied and the battery is fully charged). If less than 12.5VDC is applied, system operation will be adversely affected. To correct the problem, try any or all of the following: 1. Connect a PC4204 power supply near the module to provide power to the Combus. 2. Reduce the length of the Combus run to the module. 3. Increase the gauge of wire. Capacitance Limits An increase in capacitance on the Combus will affect data transmission and will cause the system to slow down. Capacitance will increase for every foot of wire added to the Combus. The capacitance rating of the wire used will determine the maximum length of the Combus. For example, 22-gauge, non-shielded, 4-conductor wire has a typical capacitance rating of 20 picofarads per foot (which is 20nF/1000 ). For every 1000' of wire added regardless of where it is run the capacitance of the Combus will increase by 20nF. The following chart indicates the total Combus wire allowed depending on the capacitance rating of the wire used: Wire Capacitance per 1000'(300m) 15nF 20nF 25nF 30nF 35nF 40nF TOTAL Combus Wire Length 5300'/1616m 4000'/1220m 3200'/976m 2666'/810m 2280'/693m 2000'/608m Wires run in parallel also increase Combus capacitance. For example, when using 20nF wire, the following would be some of the combinations allowed: Four wire runs at 1000'/305m each Six wire runs at 666'/203m each Eight wire runs at 500'/152m each 10 wire runs at 400'/122m each etc NOTE: Contact the wire manufacturer for the capacitance ratings of the wire being used. PC4204 Power Supply PC4204 power supply modules are required to power additional modules and devices when the total current from the main panel is insufficient. A PC4204 should also be used if excessive line loss is encountered. PC4204 Current Requirement AUX - 1.5A available for devices connected to the AUX terminal, including devices connected to relay outputs and modules connected for Combus repower (see Section 2.4 Combus Operation and Wiring ). Combus Repower Only Relay 1 on the PC4204 can be used for Combus repower. The Combus must be wired to the PC4204 according to the following diagram for Combus repower: PC4204 IMPORTANT NOTE: Do not use any power supply other than the PC4204 to repower the Combus. In the event of a power surge or transient, a module may lock up and cease to communicate with the control panel. If the panel loses communication with the module, it will initiate a module reset and will power down the Combus for five seconds in an attempt to reset the problem module. After five seconds, the panel will reapply power to the Combus and the problem module should begin to operate as intended. If a power supply other than the PC4204 is used, the Combus repower function will not operate as intended. NOTE: New versions of the PC4204 power supply module have a jumper marked J1. Ensure that this jumper is configured for Combus Relay. Otherwise, the power reset function will not operate. For more information regarding the PC4204, please refer to the PC4204 Installation Instructions. 2.5 Zone Wiring Zones on the system are wired according to the diagrams below. Once you have selected which type of zone supervision you require, you must program the Zone Supervision section. See Section 5.1 Zone Supervision for instructions. NOTE: Fire, LINKS Supervisory, LINKS Answer or Forced Answer zones always use single EOL supervision, regardless of the programmed zone supervision. No End of Line (No EOL) All No EOL zones are normally closed loops. The zone will be violated when it is open. 4

9 S e c t i o n 2 : I n s t a l l a t i o n a n d W i r i n g Single End of Line (EOL) All Single EOL zones have a 5600Ω resistor across them. If the zone is shorted or open, it will be violated. Resistors should always be placed at the device end of the wire run. If programmed as a fire or waterflow zone, the open zone will generate a trouble condition and the short will generate an alarm. Double End of Line (DEOL) All Double EOL zones have two 5600Ω resistors across them. DEOL loops will allow the panel to detect zone faults, zone tampers, violated zones and restored zones. Resistors should always be placed at the device end of the wire run. The power for the 4-wire detectors must be supervised with an end-of-line relay (RM-1). The contacts of that relay are wired in series with the zone end-of-line resistor. With the relay energized, the relay contacts are closed and the zone is normal. If the power is lost, the relay de-energizes, the contacts open and a zone trouble is initiated. Multiple fire initiating normally open contacts may be used in parallel on the loop. Do not include burglary or other types of devices on a fire zone. NOTE: Minimum 18 AWG wire is required for Listed Residential Fire Alarm Systems. Keyswitch Zone Zones programmed as keyswitch arming zones must be wired according to one the following diagrams: SECTION NOTE: Only normally closed detection devices can be used with this type of zone supervision. Only one normally closed contact can be connected to each zone; multiple detection devices or contacts on one loop are not allowed, as the tamper condition will not be monitored. 2.6 Specialized Zone Wiring Some zones require wiring configurations unique to the selected zone type. These zones are listed below. For information regarding the various zone types, please see Section 5.4 Zone Programming. Fire Zone This zone type uses normally open contacts. The zone will initiate a fire alarm when the loop is shorted (contacts close). A Fire Zone trouble will be generated when the loop is opened (wire break). Typically, fire alarm initiating contacts originate from 4-wire smoke detectors. These types of detectors must be wired as shown in the diagram below. LINKS Supervisory Zone This zone is for use with a LINKS1000/LINKS2150/ LINKS2450 only. If the LINKS experiences a trouble condition, a LINKS output can be used to violate this zone type and the event will be reported to the central station. See the corresponding LINKS Installation Manual for wiring information. LINKS Answer Zone This zone is for use with a LINKS1000 only. In case of a telephone line failure, the panel can be uploaded/downloaded via the cellular network. If the LINKS detects an incoming call, it will activate an output that can be used to violate this zone type. This will force the panel to answer the cellular call and will begin communications with the downloading computer. This zone must be programmed as LINKS Answer and is wired according to the following diagram: 5

10 2.7 Programmable Output Wiring The PGM output is a programmable terminal and will connect to +12V when activated. The terminal can sink a maximum current of 50mA. If the desired current is higher than 50mA, a relay will be required. To connect the relay, refer to the diagram below: processing time required by the panel to activate the output These response times are worst case and typical response will be faster. 1 to 32 devices on the loop... up to 2.5s 33 to 56 devices on the loop... up to 5.4s Addressable Loop Current Calculation The addressable multiplex loop can draw a maximum of 170mA of current from the main panel. In order to determine the amount of current required for the AML loop, complete the following chart: Addressable Loop Current Calculation Chart Item Current (ma) x Quantity Total (ma) AMS-220/T 1.5 x AMB x AMB x AMA x AMP x AMP x Total Current = Each output can be programmed as one of numerous available output options. See Section 11.4 Programmable Output Options for a complete list of PGM output options. 2.8 AML Device Wiring Addressable Multiplex Loop (AML) devices use a 2-wire connection for power and to communicate to and from the control panel. All detectors are designed for low power consumption to make for an efficient system. The system can accommodate up to 56 addressable devices. Connect the addressable loop to PGM1, when programmed for AML operation. For instructions on configuring PGM1 for AML operation, and for AML device enrollment, see Section 4.4 Enrolling AML Devices. Addressable Devices The following addressable devices are available: AMS-220/220T Smoke Detector with optional temperature sensor* AMB-300 PIR Detector AMB-600 Dual PIR Detector AMA-100 Glass Break Detector AMP-700 Magnetic Door/Window Contact AMP-701 Contact Input Module *Fire alarm devices cannot be placed on the same loop as burglary devices. Addressable Loop Response Time The overall system response time for devices on the AML loop depends on two criteria: how many loops are used and how many devices are on each loop. The response times below include three factors: input debounce time addressable reporting and confirmation time When more AML devices are added to a single loop, the current draw increases. The loop wire length must be limited to the following distances depending on the total loop current: Loop Distance (feet/meters) Loop Current 24 AWG 22 AWG 20 AWG 18 AWG 10mA 1330/ / / / mA 840/ / / /864 40mA 390/ / / /411 80mA 155/47 250/76 375/ / mA 100/30 105/32 115/35 120/37 170mA 70/21 75/23 85/26 95/29 Addressable Loop Wiring AML devices can be home-run, connected in a daisy chain, or T-tapped. Wire the AML loop according to the following diagram: This configuration is only used for AML devices. Please see the installation sheet provided with each device for more information regarding operation and wiring. NOTE: No end-of-line resistors are required when installing these devices. 6

11 S e c t i o n 2 : I n s t a l l a t i o n a n d W i r i n g Once the devices are connected, the PGM terminal must be configured for AML operation and each device must be enrolled. See Section 4.4 Enrolling AML Devices for instructions 2.9 Wiring Powered Devices (AUX, SAUX+) AUX Auxiliary Power These terminals can be used to power motion detectors, glass break detectors and other devices requiring power. The AUX (positive) and GND (negative) terminals can provide up to 500mA of current. SAUX+ Switched Auxiliary Power This terminal provides positive power (12VDC) and can be de-energized via the [*][7][2] keypad command (provided that the output is programmed as Command Output #2). Typically, this output is used for providing power to latching type devices that require a power interruption in order to reset Telephone Line Wiring The telephone terminals provide connections to the incoming telephone lines for central station reporting. The wires from the RJ31-X jack must be connected in the following manner: Consult the following chart to determine the maximum wire length for the bell loop with respect to current. The values reflect the use of a 30 watt siren. Bell Loop Load Current 22 AWG Wire Distance to last bell/siren (ft/m) 20 AWG Wire 18 AWG Wire 16 AWG Wire 14 AWG Wire 2000mA 18/6 29/9 46/14 73/22 116/ mA 20/6 32/10 51/16 81/25 129/ mA 36/11 58/17 92/28 147/44 233/70 700mA 52/16 82/25 132/40 210/64 332/ mA 73/22 115/35 184/56 293/89 465/ mA 364/ / / / /705 To increase the length, double up on wire. For example, when using 22-gauge quad, use two conductors for the Bell+ connection and two for the Bell-. This effectively doubles the maximum distance. For UL installations, when a bell or siren is used for fire signaling with a pulsed cadence, it must be connected between the AUX+ and BELL- terminals. To maintain bell circuit supervision, do not connect more than one device to the BELL- terminal. A fire bell or siren used for this application must be UL Listed and have a current consumption of 400mA or less (e.g. Wheelock MT-12/24- R). SECTION NOTE: For proper operation, there must be no other telephone equipment connected between the control panel and the incoming telephone line (e.g. answering machines, fax machines, telephones, etc.). Ensure that plugs and jacks meet the dimension, tolerance and metallic plating requirements of 47 CFR Part 68 Subpart F Bell Output Wiring (BELL + and BELL - ) These terminals are used for powering bells, sirens or other devices requiring steady output voltage on alarm. The panel can provide up to 2A short-term or 700mA long-term current. The output is supervised. A trouble condition will be generated when the bell connection is lost. If no bell or siren is being used, connect a 1000Ω resistor across the BELL+ and BELL- terminals to eliminate a trouble condition. 2.12Earth Ground Wiring The cabinet should be earth grounded using the grounding kit supplied. Ensure that the connection from the cabinet to the metallic cold water pipe or earth grounding rod is made with minimum 14-gauge solid copper wire. The EGND terminal must be connected to earth ground to enable ground fault detection. A Ground Fault trouble will be indicated if any conductor on the system has a resistance to earth ground of 40kΩ or less. Only earth ground the main panel and the first module connected to the telephone line. To ensure proper operation, the wire length of the bell loop must be considered. 7

12 For example: Standby current = 500 ma Alarm current = 2 A On the 24Hr chart, the battery capacity required is 14Ah. 2.13Applying Power (AC and Battery) WARNING: Do not connect the battery or transformer until all other wiring is complete. Battery Connection Red and Black Battery Leads Connect the red battery lead to the positive terminal of the battery and the black lead to the negative terminal. WARNING: Observe the correct polarity. If the battery is connected backwards, the panel will not operate. AC Power Terminals WARNING: Connect the battery before connecting the AC. A 16.5V, 40 VA transformer connected to an unswitched AC power source should be wired to these terminals. To achieve the rated outputs as previously described, the AC input must be connected to the secondary of a transformer rated at 16 VAC, 40VA minimum. The transformer is not supplied with the equipment and must be mounted outside the cabinet. Do not connect the transformer primary to an outlet that is controlled by a switch. The PC4010 monitors the presence of AC. Upon the loss of AC power a trouble condition will be generated. The keypad trouble light will turn on. If programmed, the keypad will also beep. For more information regarding AC options, see Section 10.1 AC/DC Power Options. Applying Power to the Main Panel Once all field wiring has been completed and checked for opens, shorts and grounds, power can be applied to the panel as follows: 1. Connect the battery leads. 2. Connect the AC transformer. The panel will not power up correctly if AC power is applied before the battery is connected. Battery Selection Charts The charts below are to determine the battery required to support the main panel for either 24 hours or 60 hours in the standby mode. The battery size is measured in amp hours (Ah). To determine the appropriate battery size, perform the following: 1. Calculate the total current required when the panel is not in alarm. This is the standby current. See Section 2.3 for further information on current calculation. 2. Determine the current that will be drawn when the panel is in alarm. 3. On the chart below, find the standby current on the horizontal axis and the alarm current on the vertical axis. 4. Find the region of the chart where the standby current and the alarm current values intersect. The region corresponds to the required battery Ah capacity Lithium Batteries The PC4010 circuit board includes a lithium battery. (Please see the wiring diagram on page ii.) This battery is not replaceable. There is a danger of explosion if the battery is incorrectly replaced. If the lithium battery stops working, return the circuit board to DSC Ltd. Batteries may cause a fire when in contact with metal. If you need to dispose of the circuit board and/or the lithium battery, wrap the battery in non-conductive tape. Check with your local government for battery disposal regulations. WARNING: Do not store the batteries in such a way that they come into contact with each other or with any piece of metal. Explosion or fire may occur. Should fire occur, use only dry chemical fire extinguishers. Do not use water to put out the fire. Do not heat the batteries. Do not dispose of the batteries or circuit boards in a fire. Do not disassemble the batteries. Do not apply pressure to or deform the batteries. Ensure that the above precautions are strictly observed by related departments, including, but not limited to, production, sales and outside contractors. 8

13 Section 3: How to Program 3.1 Introduction to Programming The PC4010 is programmed via a menu system. Use the arrow keys (<>) to scroll through different menu options and press the [*] key to select the menu option displayed. Continue this procedure until the required program section is displayed, then press the [*] key to select it. To arrive at a program section where data can be entered may require scrolling and selecting items from several menus. Press the [#] to return to the previous menu. To enter Installer s Programming, enter [*][8][Installer s Code] at any keypad that is enrolled on the system. In order to prevent unauthorized personnel from accessing Installer s Programming, the Installer s Code should be changed from the default setting. By default, the Installer s Code is [4010]. To change the Installer s Code, see Section 7.1 Installer s Code. Once you have entered Installer s Programming, the first menu consists of five items, listed below. Use the arrow keys (<>) to scroll to the desired menu item and press the [*] key to select it: System Area - These programming options affect the operation of the entire system. These options include communications, downloading, printer options, installer and master code programming, etc. Partition Area - These options are programmed for each partition. These options include zone assignments, partition times, partition options etc. Module Hardware - This menu is used when you enroll the system modules and keypads. Event Buffer - This menu allows access to the system s event buffer for printing. Diagnostics - These options pertain to trouble conditions reported by the modules. Use the arrow keys to scroll to the message indicating the area you wish to program and press [*]. For example, to program the Partition 2 customer ID code, scroll to each of the following messages and press [*]: Scroll to... PARTITION AREA < > Press [*] (01) ADD/EDIT PAR < > (01) WHICH PARTITION < > (01)-(04) Press [*] Scroll to... PARTITION 2 < > Press [*] (02) CUSTOMER ID CODE < > (00) Press [*]. Enter the 4-digit Partition 2 customer ID code. The display will return to the Customer ID Code display. Press [#] to return to the previous menus and to exit the installer programming mode. The arrow keys (<>) will appear in the top right-hand corner of the display to indicate that there are multiple menu items or program sections. 3.2 Programming by Reference Number A quicker method of programming the panel is to jump directly to a program section using the reference number system. These reference numbers appear beside each programming item in the Programming Worksheets, and under each heading in the Installation Manual. To program using reference numbers, enter Installer s programming([*][8][installer s Code]). Press and hold the [A]uxiliary key until the keypad displays the following message: Enter Ref # then *. Enter the reference number found in the programming Worksheets for the section you wish to program, then press the [*] key. The display will immediately go to the programming item you have selected. For example, the reference number for the Partition 2 Customer ID Code is [0100XX00]. The XX is the 2-digit partition number, in this case [02]. Once the Reference Number is entered and the [*] key is pressed, the keypad will jump directly to that programming item. If an error is made when entering the reference number, use the [<] key to move the cursor back to the first digit and re-enter the reference number. Once you have programmed the section, you must press [#] to save the change. Then, press and hold the [A] key to enter another reference number. Once you become familiar with each programming option s reference number, programming will become quick and simple. If you forget a particular reference number, you can always scroll through the menu items in order to refresh your memory. All programming reference numbers are listed in the Programming Worksheets. 3.3 Programming Decimal Data Some programming sections require decimal (0-9) entries, such as zone definitions and system times. Make sure to record all required decimal data in the Programming Worksheets before beginning to program each section. Many sections require a specific number of digits. Once all digits have been entered, the control panel will automatically exit that section and will return to the previous menu. If the [#] key is pressed, only the data entered will be changed. All programming data remaining will be left unchanged. For example, when programming telephone numbers, press the [#] key after the number is entered to exit the programming item and to save having to program all 32 digits. 9

14 3.4 Programming Hexadecimal Data Hexadecimal or Hex digits are often required for a programming item, such as telephone numbers and reporting codes. To insert a Hex digit into a given entry, press the [*] key to enter the Hex menu. Use the arrow keys to scroll through the each Hex digits (A through F). When the desired letter is displayed, press the [*] key. Hex digits can also be entered by pressing [*] key followed by the number from 1-6 corresponding to each Hex letter (A = 1, B = 2, C = 3, up to F = 6). Once the digit is entered, the control panel will automatically return to the decimal programming mode. For example, to enter data ABCD on a PC4010 you would enter: [*], [1], [*], [2], [*], [3], [*], [4] 3.5 Programming Toggle Options Many programming items are toggle options that are either enabled or disabled. Use the arrow keys (< >) to scroll through the toggle options. Press the [*] key to switch back and forth between [Y]es (enabled) and [N]o (disabled). Once all the toggle options have been programmed, press the [#] key to save your changes and return to the previous menu. 10

15 Section 4: Module Enrollment 4.1 Enrolling Keypads and Modules Once the wiring of all keypads and modules is complete, they must be enrolled on the system. Apply power to the system by first connecting the battery, followed by the AC transformer. All LCD keypads will display the message LCD45XX DSC Ltd. NOTE: Make sure all power to the system is OFF when connecting modules. NOTE: Record the location and number of each module for future reference. Enrolling the First Keypad to Partition 1 To enroll the first keypad, go to the keypad that is to be assigned to Partition 1. Press any key on that keypad. The keypad will beep and display the message 45XX Mod. #1. This keypad will automatically be assigned to Partition 1. Once the first keypad has been enrolled, the rest of the system keypads and modules can be enrolled through the Module Hardware section of installer s programming. Enrolling All Other Keypads and Modules Ref # [0200] then scroll to desired module Enter the following at the keypad you have just enrolled: 1. Enter installer s programming by pressing [*] [8] [Installer s Code]. NOTE: The default installer s code is [4010]. 2. Scroll to Module Hardware and press the [*] key. 3. The message Enroll Module will appear. Press [*]. 4. Scroll through the different modules until the module you wish to enroll is displayed. Press the [*] key. PRS400 Keypads The keypad will display the message Press Any Key On Desired Unit. Go to the keypad to be enrolled and press any key. Return to the original keypad. A message similar to the following will appear to confirm enrollment (e.g. LCD4500 Mod 02 Enrolled ). Next, you must select which partition the keypad is to control. Use the arrow keys to scroll to the desired partition and press the [*] key to select. If the enrolled keypad is slated for global operation, scroll to Option 09 Global and press [*]. If you press the [#] key, the keypad will be assigned to Partition 1 by default. For more information regarding partition and global keypads, see Section 6 Keypad Operation. Module Tampers When enrolling PC4108A, PC4116, PC4204, PC4216, PC4400, PC4702, PC4820 or PC4164-RS modules, the message Create Tamper On Desired Unit will be displayed. The tamper is required for enrollment. To create the required tamper, secure the tamper zone on the module and then open it. It is this transition from secure to violated which enrolls the module. After this is done, the keypad will display the module number and will confirm enrollment (e.g. PC4204 Mod 01 Enrolled ). Record the module number in the programming worksheets. Once the module is enrolled, re-secure the tamper. Zone Expanders NOTE: Enroll all zone expanders before assigning zones to PC4820 and AML devices. When enrolling zone expanders (PC4108A, PC4116 and PC4164-RS), the panel will display PC41XX Module. It does not ask what type of expander is being enrolled. Once the tamper is created, the control panel will automatically indicate the type of expander and will confirm enrollment (e.g. PC4116 Mod 01 Enrolled ). Zones 1 to 8 are located on the main control panel. Additional zones are added in sequence. For example, if two PC4108A zone expanders are enrolled, the first one enrolled will be assigned zones 9 to 15 and the second will be assigned zones 16 to 24. The system can have a maximum of 64 zones. To confirm which zones are assigned to which expander, press any key when the enrollment confirmation message is displayed. NOTE: Be sure to record the zones assigned to each zone expander module in the System Overview section of the Programming Worksheets. The PC4164-RS is a wireless receiver. It should be the last expander enrolled as it will reserve up to 56 zones for wireless use. For example, if the PC4164-RS were enrolled as the first expander, it would be assigned zones 9 to 64, limiting the available number of hardwire zones. If more than 8 hardwire zones are already enrolled, the PC4164-RS will be assigned the remaining zones. For example, if 24 zones are hardwire, the PC4164-RS will be assigned zones 25 to 64. ESCORT4580 and PC4701 Enrollment When enrolling the ESCORT4580 or the PC4701, the keypad will display the message Looking for PC4XXX Module. The panel will automatically scan the Combus for the module. Once it is found, the panel will confirm enrollment (e.g. ESCORT4580 Module Enrolled ). No tamper is required. 4.2 Deleting Modules Ref # [0201] then scroll to desired module Sometimes, a module must be deleted from the system. This could be when zone expanders are enrolled out of sequence, a keypad is assigned to the wrong Partition or if a module is defective. To delete a module, enter the following at any enrolled keypad: 1. Enter installer s programming by pressing [*] [8] [Installer s Code]. 2. Enter reference number [0201] then press [*]. 3. Scroll through the different modules until the module you wish to enroll is displayed. Press [*] to select. 4. Scroll to the correct module type, then to the correct module number. For example, to delete LCD4501 Module 04, scroll to LCD4501 (04). Press the [*] key to delete the module. NOTE: When deleting and/or replacing zone expanders, all remaining zone expanders should be reenrolled. This will ensure proper zone assignment and operation. 11

PC4020 v3.2 Installation Manual DLS-3 v1.3

PC4020 v3.2 Installation Manual DLS-3 v1.3 PC4020 v3.2 Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

PC4020 v3.2 Installation Manual DLS-3 v1.3

PC4020 v3.2 Installation Manual DLS-3 v1.3 PC4020 v3.2 Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

PC4020 v3.5 (International) Installation Manual DLS2002 or higher

PC4020 v3.5 (International) Installation Manual DLS2002 or higher PC4020 v3.5 (International) Installation Manual DLS2002 or higher This manual is in compliance with the requirements of CTR21 WARNING: This manual contains information on limitations regarding product

More information

Contents. Programming Worksheets 22. Appendix A: Guidelines for Locating Smoke Detectors 27. Index 28

Contents. Programming Worksheets 22. Appendix A: Guidelines for Locating Smoke Detectors 27. Index 28 Contents Section 1: Introduction 4 1.1 How to use this Manual...4 1.2 Specifications and Features...4 1.3 Compatible Wireless Devices... 5 1.4 Batteries...5 Section 2: PC5132-RS Set up & Wiring 6 2.1 Unpack

More information

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

Instruction Manual. ESCORT558O Version 1.1

Instruction Manual. ESCORT558O Version 1.1 Instruction Manual ESCORT558O Version 1.1 AVIS: L étiquette de l Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de protection,

More information

Instruction Manual PC55O. With PC5OORK Keypad

Instruction Manual PC55O. With PC5OORK Keypad Instruction Manual PC55O With PC5OORK Keypad Industry Canada Notice NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications

More information

Installation Manual Premier LCD/LCDL INS180-4

Installation Manual Premier LCD/LCDL INS180-4 Installation Manual Premier LCD/LCDL INS180-4 1. UL/C-UL Requirements Only the following keypads are to be used in a UL/C-UL Installation. Model No DBD-0135 DBD-0133 DBD-0144 DBD-0143 DBD-0148 DBD-0147

More information

Digital Security Controls

Digital Security Controls Digital Security Controls Publications Cover Sheet Part Number: 29005043 Revision: 004 Release Number: 4930 Notes:RF Jam note added Description: PC5132-433 Receiver v4.2 Installation Manual Type: 33-01

More information

Introduction. S e c t i o n 1

Introduction. S e c t i o n 1 Introduction S e c t i o n 1 The Escort4580 Voice Assisted Security Control provides easy to understand audible information about the status of your security system, and makes operation simple by prompting

More information

Installation Manual RF55O1-433

Installation Manual RF55O1-433 WARNING: Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. Installation

More information

Instruction Manual W A R N I N G

Instruction Manual W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Power864. Installation Manual IMPORTANT. PC5O2O Version 3.1 DLS-3 v1.3 and higher

Power864. Installation Manual IMPORTANT. PC5O2O Version 3.1 DLS-3 v1.3 and higher IMPORTANT This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

W A R N I N G

W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Escort4580 v1.3 Installation Manual

Escort4580 v1.3 Installation Manual 2001 Digital Security Controls Ltd. Toronto, Canada 1-800-387-3630 www.dsc.com Printed in Canada 29003579 R004 Escort4580 v1.3 Installation Manual FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications

More information

PC4020 v3.5 Instruction Manual

PC4020 v3.5 Instruction Manual PC4020 v3.5 Instruction Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

Introduction. S e c t i o n 1. Specifications. Features

Introduction. S e c t i o n 1. Specifications. Features Introduction S e c t i o n 1 Features Allows the Maxsys PC4010 and PC4020 security systems to be operated through local and remote touch-tone telephones NOTE: The Escort4580 v1.2 cannot be used with PC4010CF

More information

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging 1.1 Specifications System Introduction S E C T I O N 1 Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master,

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC security equipment has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer instruct

More information

RF v1.0 Installation Manual

RF v1.0 Installation Manual RF5108-433 v1.0 Installation Manual Thank you for purchasing the RF5108-433 Wireless Receiver. This product is the result of several years of development and will allow you to connect up to 8 wireless

More information

PC51O2-433NA v1.0 Installation Manual

PC51O2-433NA v1.0 Installation Manual PC51O2-433NA v1.0 Installation Manual If you are intending to use DLS-3 software with this product, a new DLS-3 driver must be downloaded from the DSC web site at http://www.dscsec.com/dls3drivers.htm.

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

PC56O. Instruction Manual

PC56O. Instruction Manual Instruction Manual PC56O Software Version 1.OA W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher IMPORTANT WARNING:This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be

More information

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1 1.1 PC5015 Specifications System Introduction S E C T I O N 1 Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master, 2 Duress and 1 maintenance

More information

System Introduction. 1.1 Specifications S E C T I O N 1

System Introduction. 1.1 Specifications S E C T I O N 1 System Introduction S E C T I O N 1 1.1 Specifications Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 37 Access Codes: 32 User, 1 System Master, 2 Partition Master

More information

HEXA PROGRAMMING: All digits from 0 to F are valid. Values are programmed into memory locations from address 000 to 043 and from address 300 to 547.

HEXA PROGRAMMING: All digits from 0 to F are valid. Values are programmed into memory locations from address 000 to 043 and from address 300 to 547. 708EPE-03 DIGITAL COMMUNICATOR RESET: Installer lock must be unlocked. (Address 049: enter any value other than 147) Power down reset (1) Remove the auxiliary power* (12 volts). (2) Connect a jumper between

More information

System Manual W A R N I N G. PC4O2OKT Version 1.0CAP. Book 1

System Manual W A R N I N G. PC4O2OKT Version 1.0CAP. Book 1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

WARNING Software Version 2.3 / DLS-1 v6.7 and up See Back Cover for New Features in Version 2.3

WARNING Software Version 2.3 / DLS-1 v6.7 and up See Back Cover for New Features in Version 2.3 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

P Zone Expandable Hybrid Security System

P Zone Expandable Hybrid Security System Page 1 of 11 up to 8 hardwired keypads and 4 wireless keypads 4 hardwired keypads available with zone input PWLS910 wireless handheld keypad added wireless control is provided by - PWLS908 wireless panic

More information

System Introduction. 1.1 Specifications

System Introduction. 1.1 Specifications System Introduction S E C T I O N 1 1.1 Specifications Downloading Software Support PC585 uses DLS-1 v6.5 and up. Flexible Zone Configuration Four fully programmable zones; system expandable to eight zones

More information

PROGRAMMING WORKSHEETS

PROGRAMMING WORKSHEETS 16 Hook-up Diagram Table of Contents INTRODUCTION 2 Features... 2 Specifications... 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Wiring... 3 Burglary Zone Wiring... 4 Fire Zone Wiring...

More information

Installation Instructions Instructions d Installation Instrucciones de Instalacion

Installation Instructions Instructions d Installation Instrucciones de Instalacion LCD5511 version 1.O Installation Instructions Instructions d Installation Instrucciones de Instalacion WARNING: Please refer to the System Installation Manual for information on limitations regarding product

More information

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction.

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction. INTRODUCTION The PC4020 is a highly flexible and versatile control which will enable the installer to meet the most demanding security requirements. The heart of the system is the main control panel, designated

More information

Installation Manual. This panel will not operate if installed outside of North America. See section 1.1 for details.

Installation Manual. This panel will not operate if installed outside of North America. See section 1.1 for details. WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Introduction S E C T I O N 1

Introduction S E C T I O N 1 Introduction S E C T I O N 1 The PC4164-RS is a wireless signal receiver for use with Maxsys PC4010 and PC4020 v3.0 panels. The PC4164-RS receives signals from WLS9XX wireless devices. The PC4164-RS has

More information

PC155O. Installation Manual W A R N I N G. Software Version 4.1 DLS-1 V6.5 and later

PC155O. Installation Manual W A R N I N G. Software Version 4.1 DLS-1 V6.5 and later Installation Manual PC155O Software Version 4.1 DLS-1 V6.5 and later W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations

More information

Installation Manual. PC1565 Software Version 2.4ZD DLS-3 v1.3 and higher

Installation Manual. PC1565 Software Version 2.4ZD DLS-3 v1.3 and higher WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC security equipment has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer instruct

More information

Instruction Manual W A R N I N G

Instruction Manual W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Simon Security System. User Guide. Technical Manuals Online! Rev J May Part No: ZZZ*(,QWHUORJL[FRP

Simon Security System. User Guide. Technical Manuals Online! Rev J May Part No: ZZZ*(,QWHUORJL[FRP ) 466-1871 Rev J May 2003 *(,QWHUORJL[ ZZZ*(,QWHUORJL[FRP Part No: 60-875 Doors & Motion Windows Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion Time Sensor On

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

PC4820 v1.3 Installation Manual

PC4820 v1.3 Installation Manual PC4820 v1.3 Installation Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

INSTALLATION MANUAL. PC255O Version 1.3

INSTALLATION MANUAL. PC255O Version 1.3 INSTALLATION MANUAL PC255O Version 1.3 NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

Table of Contents. Appendix A Special Characters 31

Table of Contents. Appendix A Special Characters 31 Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM

More information

Installation Instructions

Installation Instructions Installation Instructions S E C U R I T Y S Y S T E M Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

PARTNER Small Office Edition. Customer Support Document

PARTNER Small Office Edition. Customer Support Document PARTNER Small Office Edition Customer Support Document 15-300602 Issue 1 June 2005 0 Ordering Documents 0 To order additional documents, you may do the following: Call: Write: Avaya Publications Center

More information

INSTALLATION MANUAL. PC3OOO Version 7.51

INSTALLATION MANUAL. PC3OOO Version 7.51 INSTALLATION MANUAL PC3OOO Version 7.51 DOC NOTICE NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications

More information

WIRELESS CONTROLS & DETECTORS

WIRELESS CONTROLS & DETECTORS WIRELESS CONTROLS & DETECTORS WLS908 Panic Pendant Press 2 buttons for 2 seconds to initiate a panic alarm Water-resistant Pendant test function Supervised for low battery Each pendant is a wireless zone

More information

Instruction Manual W A R N I N G

Instruction Manual W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Simon Security System. User Guide Rev A June Part No: ZZZ*(6HFXULW\FRP. Motion. Doors & Windows

Simon Security System. User Guide Rev A June Part No: ZZZ*(6HFXULW\FRP. Motion. Doors & Windows ) *(6HFXULW\ 466-1871-01 Rev A June 2004 ZZZ*(6HFXULW\FRP Part No: 60-875 600-1012 Doors & Windows Motion Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion Time

More information

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE Advanced Life Safety Solutions RAM-208 Remote Multiplex Annunciator Panel A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE LAMP TEST SYSTEM RESET Wiring & Installation Installation

More information

INSTALLATION MANUAL PC15OO

INSTALLATION MANUAL PC15OO INSTALLATION MANUAL PC15OO This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2)

More information

RAM-216. Remote Multiplex Annunciator Panel. Wiring & Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE

RAM-216. Remote Multiplex Annunciator Panel. Wiring & Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE Advanced Life Safety Solutions RAM-216 Remote Multiplex Annunciator Panel A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE LAMP TEST SYSTEM RESET Wiring & Installation Manual LT-658

More information

Digiplex Control Panel (DGP-848) - V4.0

Digiplex Control Panel (DGP-848) - V4.0 Digiplex Control Panel (DGP-848) - V4.0 DGP-848 Reference and Installation Manual TABLE OF CONTENTS INTRODUCTION... 4 1.0 1.1 Features... 4 1.2 Specifications... 4 INSTALLATION... 5 2.0 2.1 Location &

More information

PC4820 v1.4 Installation Manual

PC4820 v1.4 Installation Manual PC4820 v1.4 Installation Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

Installation Manual CFP-500. Dual Line Dialer. Version 1.0

Installation Manual CFP-500. Dual Line Dialer. Version 1.0 CFP-500 Dual Line Dialer Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of

More information

AXI LED USER MANUAL (REV. 1.0)

AXI LED USER MANUAL (REV. 1.0) Security & Home Automation System AXI LED USER MANUAL (REV. 1.0) CONTENTS PREFACE FEATURES LED KEYPAD OUTLOOK 1.0 LIGHT INDICATION 1 2 4 6 CHAPTER 1: ALARM SYSTEM CONTROL 1.0 USING LED KEYPAD 1.0.1 ARMING

More information

INSTALLATION MANUAL PC56O. Version 1.OA

INSTALLATION MANUAL PC56O. Version 1.OA INSTALLATION MANUAL PC56O Version 1.OA TABLE OF CONTENTS INTRODUCTION 3 Features... 3 Specifications... 3 INSTALLATION 4 Mounting the Control Panel... 4 Mounting the Keypad... 4 Wiring... 5 Burglary Zone

More information

Digital Security Controls

Digital Security Controls Digital Security Controls Publications Cover Sheet Part Number: Revision: Release Number: Description: Notes: Material Type: Pieces: Printing Instructions: Master Size: # Sheets in Master: Cover Printing:

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

PARTNER Advanced Communications System. Customer Support Document

PARTNER Advanced Communications System. Customer Support Document PARTNER Advanced Communications System Customer Support Document 518-456-163ADD Issue 5 August 2003 0 Ordering Documents 0 To order additional documents, you may do the following: Call: Write: Avaya Publications

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

Feb 25, 1993 Software Version 1.3 SYSTEM MASTER. Instruction Manual PC4OOO SECURITY SYSTEM

Feb 25, 1993 Software Version 1.3 SYSTEM MASTER. Instruction Manual PC4OOO SECURITY SYSTEM Feb 25, 1993 Software Version 1.3 SYSTEM MASTER Instruction Manual PC4OOO SECURITY SYSTEM DOC NOTICE NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification

More information

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

1100D Wireless Receiver

1100D Wireless Receiver 00D Wireless Receiver INSTALLATION GUIDE Description The 00D Wireless Receiver provides up to 32 wireless zones for XT30/XT50 Series panels with Version 02 or higher. The 00D provides two-way, supervised

More information

PowerSeries. PC1616/PC1832/PC1864 version 4.1. Installation Guide

PowerSeries. PC1616/PC1832/PC1864 version 4.1. Installation Guide PowerSeries PC1616/PC1832/PC1864 version 4.1 Installation Guide Note to Installer:Center pages contain important end user information. Leave with End User. WARNING: This manual contains information on

More information

RAM-2644LCD. LCD Remote Annunciator. Installation Manual. Advanced Life Safety Solutions

RAM-2644LCD. LCD Remote Annunciator. Installation Manual. Advanced Life Safety Solutions Advanced Life Safety Solutions RAM-2644LCD LCD Remote Annunciator Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 U.S.A. 60 Industrial Parkway Cheektowaga, NY 14227 Tel:

More information

UltraGard and Custom Versions

UltraGard and Custom Versions UltraGard and Custom Versions Installation Instructions This document describes the basic procedures necessary for an experienced installer to install, set up, and program an UltraGard Security System.

More information

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3

More information

Advanced Communications System. Customer Support Document

Advanced Communications System. Customer Support Document PARTNER Advanced Communications System Customer Support Document 518-456-163ADD Issue 1 October 2000 0 Ordering Documents 0 To order additional documents, you may do the following: Call: Publications

More information

All-In-One Wireless Security System V1.0. Model #: MG-6060

All-In-One Wireless Security System V1.0. Model #: MG-6060 All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual DRAFT Table of Contents Introduction... 5 About Magellan and this Manual... 5 Conventions... 5 Specifications...

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3 This manual is for the LINKS2150 software version 1.3 TABLE OF CONTENTS FEATURES 1 Keypad Programmable... 1 EEPROM Memory... 1 Static/Lightning

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

System Overview. PC4020 v3.3

System Overview. PC4020 v3.3 System Overview PC4020 v3.3 The MAXSYS system meets today s challenges with the seamless integration of security, access control, fire alarm, automation, and intercom features that single function systems

More information

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99 9,67$6(D 6\VWHP6HFXULW\ 86(5*8,'( N7229AUV2 12/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 Burglary Protection...4 Zones...4 Alarms...5 Fire Protection...5 Chime Feature...5 Phone Access & Voice

More information

Instruction Manual PC585. Direct all comments and suggestions concerning DSC publications to

Instruction Manual PC585. Direct all comments and suggestions concerning DSC publications to W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

ÃÌ> >̈œ Ê ÃÌÀÕV̈œ Ã. Contents

ÃÌ> >̈œ Ê ÃÌÀÕV̈œ Ã. Contents ÃÌ> >̈œ Ê ÃÌÀÕV̈œ à Document Number: 466-178-ITI Rev. B April 2001 $GYHQWŒ &RPPHUFLDO%XUJODU\DQG +RPH1DYLJDWRU6\VWHP Commercial Burglary Panels 20 Zone 60-62-01 132 Zone 60-62-04 Contents About This

More information

6HFXULW\6\VWHP 8VHU*XLGH N /01

6HFXULW\6\VWHP 8VHU*XLGH N /01 6HFXULW\6\VWHP 201, 201,(8 8VHU*XLGH N9942-2 1/01 TABLE OF CONTENTS (cont d) QUICK REFERENCE...3 System Turn On...3 System Turn Off...3 System Turn On/Stay Inside...3 System Turn On/Stay Inside/Instant

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

L900 series USER MANUAL

L900 series USER MANUAL INTRODUCTION The BLUGUARD Control Panel is designed for simple operation yet provides the maximum protection for you. Please read this manual carefully and follow the instructions contained in this book.

More information

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4 Programming Guide We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information