SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

Size: px
Start display at page:

Download "SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE"

Transcription

1 SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE Urs Welte Amstein + Walthert AG, Switzerland ABSTRACT The paper aims at a detailed analysis of the current know-how in the construction of tunnel cabling systems and shows the impact of fire and heat and the respective measures to be taken. Therefore the results of the test projects EUREKA Firetun and MEMORIAL are scrutinized and evaluated in view of the today's boundary conditions in typical cross sections. It will clearly be shown how the heat distribution is dependant on the cross section and the ventilation system. Further it will be shown how concrete will protect cables from heat and damage even if the coverage is low and how far open mounted installation channels are endangered. For typical cabling systems it shall be outlined which requirements and specifications regarding fire and heat resistance are reasonable and required. A short discussion of the applicable norms and standards shall provide further information and decision guidance. It shall be clarified that high safety standards re isolation and fire resistance are not generally required. 1. CABLES IN THE TUNNEL Cables are accommodated in road tunnels at different places: in lower floor panel troughing systems, containing tubing blocks and pits, on routes at the tunnel cover (lighting, communication, fire protection), on routes behind the wall lining, as well as in pits, ascents, air ducts, traversing and in accessible cable tunnels. cable channel lamp fire sensor cable radio cable ceiling tube fresh air exhaust air ventilator wall ascent signal wall ascent fire emergency lighting tubing block tubing block cable duct transfer tubing block LED-lighting cable duct Fig. 1: Cabling systems in typical cross section The different fire hazard of the cable systems can be judged due to the heat distribution in the case of fire.

2 FIRE IN THE TUNNEL A fire event in a tunnel is often combined with a rapid temperature rise, connected with a fast propagation of smoke gases. The fire scenario depends on most diverse factors, which are substantial: fire load: Passenger vehicles, bus, truck with/without charge ventilation system of the tunnel air flow conditions at the beginning of the fire The fire load can reach very high values, in particular if several vehicles are involved. It starts for individual vehicles at 5 MW (passenger vehicle) over 20 MW (bus) up to 100MW (truck). Additionally the air flow (partially affected by the mechanical ventilation) has an impact on the propagation of the hot combustible gases in the tunnel. 3. STANDARD FIRE CURVES In order to have a uniform basis for technical calculations as well as for practical tests, the temperature gradient is defined by so-called standard fire curves. Temperature [ C] Fire duration [min] Fig. 2: Standard fire curves The most common standard fire curve is the ISO standard 834. It forms the basis for the examination of buildings and construction units. The examination of cable systems (cables inclusive fittings and laying systems) is described in the DIN and led to the wellknown inspection certificates like e.g. "E30" (function during 30 minutes). However, the ISO standard was developed for above ground structures - not for tunnels -, and has therefore only limited relevance for this special field. Therefore, also the curve of the Netherlands authorities (Rijkswaterstaat) is used, the so-called RWS-curve. The temperatures reach in accordance with this fire curve over 1300 degrees after approximately 50 minutes. However, this curve is internationally not recognized.

3 FIRE TESTS Some time ago two series of fire tests in tunnels were executed. The results thereof are often consulted for the evaluation of fire risks. Truck Bus Car Temperature [ C] Distance to fire [m] Fig. 3: Maximum temperatures at the ceiling (EUREKA-Project 499 Firetun) The tests showed very high roof temperatures over the fire source, which were reached after a short time of only 20 minutes. However, the tunnels had a cross-section area of 30 m2 only. This corresponds with about the half of a modern road tunnel with two driving lanes. 5. MEMORIAL TEST USA 1993 The American Memorial tunnel has a 60 m2 cross section and is similar to the Swiss standard; thanks to ventilation systems also the simulation of air flows were possible.

4 Fig. 4: Memorial Tunnel Fire Ventilation Test Program: 10 minutes after fire start, 20 MW-fire Fig. 5: Memorial Tunnel Fire Ventilation Test Program: 10 minutes after fire start, 50 MW-fire The comparison with EUREKA shows that with attention of the flow effect and the cross section many lower temperatures are measured. Further, the higher temperatures were measured with relatively high fire loads only. 6. WHICH TEMPERATURES HAVE TO BE EXPECTED? A critical comparison of the fire curves and the test series leads to the clear result that the temperatures reach generally neither the values of the standardized fire curves, nor those of the EUREKA tests. Very close to the Swiss conditions are the MEMORIAL tests. The Memorial tunnel tests showed clearly that with an efficient smoke exhaust close to the fire source the temperature and smoke propagation can be reduced considerably (in accordance with the new Swiss guidelines for the project engineering of road tunnels the ventilation system must offer the possibility of a local smoke exhaust). The following illustration shows the temperatures which can be expected.

5 no temperature change 50 C small temperature change C high temperature change 150 C Fig. 6: Temperature zones during fire 7. CABLE UNDER FIRE: STANDARDS For cable systems the behaviour in case of fire (passive characteristics) as well as the fire resistance (active characteristics) are important to consider. In order to define the appropriate safety level, the standardization situation has to be regarded more closely. Properties International Europe flame retardant IEC EN halogen free IEC EN no corrosive gases IEC EN low smoke emission IEC EN low flame propagation IEC EN Fig. 7: Applicable standards for behaviour in case of fire For the active characteristics of cables the following standards are relevant. They define the requirements during fire. Properties International Switzerland Circuit integrity - Fire only - Voltage (<1kV) - Data cable - Fibre optic cable IEC Fig. 8: Applicable standards for circuit integrity The system circuit integrity of cable systems is mostly the most important issue. Thus the system function can be guaranteed during fires for a certain period. In the extensive standardization work DIN 4102 the system circuit integrity is treated for electrical cable systems in the part 12. The standard comprises the entire cabling system, i.e. cable inclusive carrying system. However, it is applicable only to low-voltage cables (< 1 kv), thus not to high-voltage cables and also not to fibre optic cables. System circuit integrity classes are defined (in minutes): E30, E60, E90. Furthermore, the requirements can be divided in three groups:

6 Requirements Group Requirements IEC-Standard Halogen free and flame retardant cables (FE 0) Circuit integrity ( FE 5) Circuit integrity (E30 - E90) Function Circuit integrity DIN X Isolation Circuit integrity IEC X Material flame retardant IEC X X X halogen free IEC X X X no corrosive gases IEC X X X low smoke emission IEC X X X low flame propagation IEC X X Fig. 9: Requirements groups 8. RECOMMENDED CABLE SAFETY CLASS Safety cable systems cause extra costs; it is therefore worthwhile to regard conditions: Basic Requirements Higher Requirements Additional cost cables: 1.5 mm 2 16 mm 2 FE 0 FE 180 (E 30) % 30-50% FE 5 FE 180 (E 30) 20-40% 10-20% FE 180 E 30 0% 0% Installation material no fire protection E % Cable trough Material: without fire protection E % Installation: without fire protection E % Fig. 10: Additional cost for circuit integrity cables In which cases are these extra costs justified? Generally, halogen-free and flame-retardant cables are mandatory for a tunnel. Also safety cables, which offer a protection against the consequences and the propagation of a fire. Safety cables with system circuit integrity are recommended if temperature and availability risk are relevant, e.g. installation cables in the tunnel cross section: Lighting, ventilation, signing. Cable systems in tubing blocks or in pipes with sufficient concrete cover (> 10 cm) usually require no system circuit integrity, since they are sufficiently protected by their specific situation. Safety relevant cables have to be considered especially, e.g. cables for uninterrupted power supplies (UPS): They should at least have the same system circuit integrity as the overall system they belong to. 9. CONCLUDING REMARK Fire accidents in road tunnels result often in high temperatures due to the limited cross section. The temperatures indicated in the standards always describe the values maximally arising during a fire event; however, these values have to be expected only within the upper tunnel area. At the lower level the temperatures are significantly lower. Due to safety considerations, the general demand for system circuit integrity cannot be justified for cable systems in accordance with DIN , since the risk reduction is only marginal in many cases. However, each project must separately be regarded due to the object-specific conditions.

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS - 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria

More information

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS 25 TH INTERNATIONAL CONGRESS OF THE AERONAUTICAL SCIENCES DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS Dipl.-Ing. Kai Behle Keywords: Fire, Smoke

More information

The Quality Connection. BETAflam Fire Resistant Safety Cables

The Quality Connection. BETAflam Fire Resistant Safety Cables The Quality Connection BETAflam Fire Resistant Safety Cables BETAflam Contact Your personal customer number To offer you a more efficient service, we kindly ask you to mention your personal customer number

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61892-4 First edition 2007-06 Mobile and fixed offshore units Electrical installations Part 4: Cables Commission Electrotechnique Internationale International Electrotechnical

More information

Procedure for the Approval of New Fire Detection and Alarm Technologies

Procedure for the Approval of New Fire Detection and Alarm Technologies VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing

More information

Üntel is ready for CPR

Üntel is ready for CPR 2016 Üntel is ready for CPR Hakan Kubas Marketing Manager 01.11.2016 Construction Products Regulation What is the CPR? The Construction Products Regulation (CPR) lays down conditions for the placing or

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook Useful Contact Numbers Promat Technical Services Department Telephone: 01344 381 400 Fax: 01344 381 401 E-mail: technicaluk@promat.co.uk Promat Marketing Services Department Telephone: 01344 381 350 Fax:

More information

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL - 119 - ABSTRACT: PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL Darko Šaric Civil Engineering Institute of Croatia Croatia, 10.000 Zagreb, J. Rakuše 1 e-mail: dsaric@zg.igh.hr Goran Legac Croatian

More information

The safe choice. Now real safety is possible and easy. The evolution of safety. Fire resistant LSOH cables. Ecology Line. Traditional standard cables

The safe choice. Now real safety is possible and easy. The evolution of safety. Fire resistant LSOH cables. Ecology Line. Traditional standard cables The safe choice Pirelli has been producing Low Smoke Zero Halogen (LSOH) cables for more than 20 years. LSOH cables have generally been a niche product, for special uses. The new Afumex range, building

More information

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik

More information

Hot Issues in Fire Engineering 12 March 2013

Hot Issues in Fire Engineering 12 March 2013 Hot Issues in Fire Engineering 12 March 2013 An Update on Design Fires of Vehicular Tunnels W.K. Chow Fellow, Hong Kong Academy of Engineering Sciences Research Centre for Fire Engineering, Department

More information

HRS Hand Rail System 1

HRS Hand Rail System 1 HRS Hand Rail System 1 Safety in tunnels Hand rail system for rail tunnels In accordance with the requirements of the TSI (technical specification for interoperability), all tunnels in the trans-european

More information

White paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations?

White paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations? White paper by Multimedia Connect Construction Product Regulations* We are all concerned by the safety of persons and property. In 2010, 8 million fires were recorded: they are estimated to have caused

More information

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report D M T G m b H & C o. K G B u i l d i n g S a f e t y Expert Body for Fire Protection Tremoniastraße 13 44137 Dortmund GERMANY Phone +49 231-5333-0 Fax +49 231-5333-299 Emaill: gs@dmt.de http://www.dmt.de

More information

Havells Fire Survival Cables

Havells Fire Survival Cables Fire Survival Cables Designed for Critical Installation of National Importance Airports / Thermal Power Plants Metro Rail Projects / Rail Terminals / Nuclear Interstate Bus Terminals / Installation Prone

More information

Fire Safety Fire Resistant Building Components

Fire Safety Fire Resistant Building Components Fire Safety Fire Resistant Building Components NBN 713-020 1968 Fire fighting - Fire performance of building materials and products - Fire resistance of building materials NBN 713-020/A1 1982 Protection

More information

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation CPR Construction Products Regulation Index Construction Products Regulation... 3 What is the Construction Products Regulation (CPR)... 4 What is the objective of the CPR... 4 Who does the application of

More information

CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag

CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag STANDARD COLOR CMZH Low Smoke 0-Halogen Flame- Retardant Mass Transit Tag TECHNICAL DATA SHEET Revision Number. 1 Last Edited 9. januar 2019 OTHER COLORS MATERIAL Flat band cross linked polyolefin. OPERATING

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Fire Protection and Safety in Tunnels Conference Opening Remarks Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Agenda Background to the conference Key themes Recent tunnel fires Major infrastructure

More information

STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS

STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS Neus GENERÓ, Juan de Dios MARTÍNEZ, Jacint ROVIRA, Grupo General Cable Sistemas, (Spain), ngenero@generalcable.es, jdmartinez@generalcable.es,

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60287-3-1 Edition 1.1 1999-05 Edition 1:1995 consolidated with amendment 1:1999 Electric cables Calculation of the current rating Part 3-1: Sections on operating conditions IEC

More information

Road tunnel safety rules in Italy: the tunnel country

Road tunnel safety rules in Italy: the tunnel country Safety and Security Engineering II 317 Road tunnel safety rules in Italy: the tunnel country M. Guarascio, M. Lombardi, G. Rossi & G. Sciarra Safety Engineering Sapienza, Rome University, Italy Abstract

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter 1 Introduction AUGUST 2017 The Passive Fire Protection Handbook Contents Chapter 1: Introduction2 Applications

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

Significance of the Construction Products Regulation, including for data centers WHITEPAPER

Significance of the Construction Products Regulation, including for data centers WHITEPAPER Significance of the Construction Products Regulation, WHITEPAPER The aim of the Construction Products Regulation is to protect people in buildings against the consequences of a fire. The priorities in

More information

TUNPROTEC. Active Tunnel Fire Protection

TUNPROTEC. Active Tunnel Fire Protection VID FIre KIll TUNPROTEC Active Tunnel Fire Protection 9 An Active Tunnel Fire General The tunnel structures are very valuable. Infrastructure tunnels, such as train tunnels and road tunnels represent very

More information

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility and connectivity assessment of system components Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility

More information

DNVGL-CP-0401 Edition February 2016

DNVGL-CP-0401 Edition February 2016 CLASS PROGRAMME Type approval DNVGL-CP-0401 Edition February 2016 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Cable tray solutions. For tunnels GUIDE. The global specialist in electrical and digital building infrastructures

Cable tray solutions. For tunnels GUIDE. The global specialist in electrical and digital building infrastructures Cable tray solutions For tunnels GUIDE The global specialist in electrical and digital building infrastructures II Cable routing solutions for tunnels The Legrand Group, the global specialist in electrical

More information

Interferry Ro Ro Deck Fire Safety Operational Best Practice Guidance

Interferry Ro Ro Deck Fire Safety Operational Best Practice Guidance Interferry Ro Ro Deck Fire Safety Operational Best Practice Guidance Author: Editor: Contributors: Abstract: Status: D. Johnston, BC Ferry Services J. Roos, Interferry Interferry Fire Safety Ad-hoc Working

More information

ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves

ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves STANDARD TUBE COLOR ZH Low Smoke 0-Halogen Flameretardant Identification Sleeves TECHNICAL DATA SHEET Revision Number. 1 Last Edited 24. juli 2018 The ZH-2X Heat Shrinkable Wire Markers are made of halogen

More information

CLEARING MISCONCEPTIONS ABOUT LOW-SMOKE, HALOGEN-FREE CABLES

CLEARING MISCONCEPTIONS ABOUT LOW-SMOKE, HALOGEN-FREE CABLES CLEARING MISCONCEPTIONS ABOUT LOW-SMOKE, HALOGEN-FREE CABLES EXECUTIVE SUMMARY The use of low-smoke, halogen-free (LSHF) cables in commercial and residential building projects can help reduce equipment

More information

Cablosam Tapes for Fire-Resistant Cables

Cablosam Tapes for Fire-Resistant Cables Cablosam Tapes for Fire-Resistant Cables 2 Cablosam Tapes for Fire-Resistant Cables We Enable Energy As one of the oldest industrial companies in Switzerland, founded in 1803, we focus on products and

More information

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS - 259 - COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS Kratzmeir S. 1, Rothe R. 1 Peters B. 2, 1 IFAB Institute for applied fire safety research, Rostock 2 Fogtec Fire Protection, Cologne

More information

EN l CartWash Plus. CartWash Plus. Hygienically perfect cleaning of laundry carts

EN l CartWash Plus. CartWash Plus. Hygienically perfect cleaning of laundry carts EN l CartWash Plus CartWash Plus Hygienically perfect cleaning of laundry carts Two belts with a different width (option) for a more flexible adaptation to different cart types. Active Drying (option)

More information

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica

More information

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Julio Toko, Martin Fromme, Bernd Horbach and Wieland Hill LIOS Technology GmbH, Cologne, Germany

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61300-2-33 Edition 3.0 2012-07 Fibre optic interconnecting devices and passive components Basic test and measurement procedures Part 2-33: Tests Assembly and disassembly of fibre

More information

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS Dr. Arnd Rogner Metaphysics SA 1 Contents Actual detection technologies (in Europe) Field experience in tunnel fire detection System integration 2 Road

More information

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE Carol Harris, EMEA Product Manager WHITE PAPER Molex Connected Enterprise Solutions EXECUTIVE SUMMARY Combustible construction materials

More information

OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY

OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY , Volume 5, Number 1, p.1-5, 2003 OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

Heat pump supplemental heating system for motor vehicles

Heat pump supplemental heating system for motor vehicles 1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Presley House Presley Way Crownhill Milton Keynes MK8 0ES United Kingdom Contact: Jeremy Hodge Tel: +44 (0) 1908 267300 Fax: +44 (0) 1908

More information

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,

More information

Fire protection on chemical manufacturing sites

Fire protection on chemical manufacturing sites CFPA-E No 18:2008 Fire protection on chemical manufacturing sites FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60092-350 Second edition 2001-06 Electrical installations in ships Part 350: Shipboard power cables General construction and test requirements Installations électriques à bord

More information

ITU-T L.63. Safety practice for outdoor installations

ITU-T L.63. Safety practice for outdoor installations International Telecommunication Union ITU-T L.63 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (10/2004) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT

More information

Page 1. Brussels, 11 October europacable Rue Marie de Bourgogne 58 B-1000 Brussels EU Transparency Register ID

Page 1. Brussels, 11 October europacable Rue Marie de Bourgogne 58 B-1000 Brussels   EU Transparency Register ID Prevent the reduction of fire safety in railway tunnels across Europe: Europacable urges to safeguard B2ca,s1a,a1 classification as the minimum requirement for exposed cables Europacable comments on ERA

More information

New European Cable Testing and Classification

New European Cable Testing and Classification New European Cable Testing and Classification THE BENCHMARK IN FIRE TESTING New European Cable Testing and Classification Cables will be tested using 5 test methods, and classified by extending the provisions

More information

Cable technology for highest safety requirements

Cable technology for highest safety requirements Cable technology for highest safety requirements Daetwyler We are a provider of high-grade quality system solutions and services in the areas of structured data cabling, telecom carriers, safety cabling,

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Conformity Approvals Rated insulation voltage Ui

Conformity Approvals Rated insulation voltage Ui GIOVENZANA INTERNATIONAL B.V. GENERAL CHARACTERISTICS ELECTRICAL CHARACTERISTICS CONTACT BLOCKS CAM SWITCHES Giovenzana International B.V., widely recognized as a leader in elevator technology and the

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

UL268 7 th challenge with single infrared smoke detector

UL268 7 th challenge with single infrared smoke detector UL268 7 th challenge with single infrared smoke detector Hans Aebersold Siemens Schweiz AG, Building Technologies Division, Switzerland Abstract Coming up UL217 8th and UL268 7th edition with added new

More information

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported

More information

DNVGL-CP-0399 Edition March 2016

DNVGL-CP-0399 Edition March 2016 CLASS PROGRAMME Type approval DNVGL-CP-0399 Edition March 2016 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES Javier CORMENZANA Ormazabal Spain jco@orrmazabal.com Sergio SEBASTIAN Ormazabal -

More information

BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST

BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST FIRE FIGHTING IS RESPONSIBILITY Fire monitoring Fire detection Fire suppression We are a leading international supplier

More information

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET I. S. Hwang and Y. L. Lee Department of Mechanical Engineering, Kongju National University, Korea E-Mail: ylee@kongju.ac.kr ABSTRACT

More information

Loss Prevention Standards

Loss Prevention Standards Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building

More information

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING Page 1 of 10 CONTENTS 1 SCOPE 2 DEFINITIONS 2.1 SURGE ARRESTER 2.2 GAPLESS METAL-OXIDE SURGE ARRESTERS 2.3

More information

Product Specification CAT 6 UNSHIELDED PATCH CORDS

Product Specification CAT 6 UNSHIELDED PATCH CORDS Product 108-93017 Specification 23/Nov/06 Rev. A CAT 6 UNSHIELDED PATCH CORDS 1. SCOPE 1.1 Content This specification describes performance and material requirements and tests procedures for NETCONNECT

More information

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores)

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores) 600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores) FFX400 1SZ1-R(PH60)(CU/SR/LSZH 600/1000V Class 2) FFX400 1SZ1-F(PH60)(CU/SR/LSZH 600/1000V Class 5) Silicone Rubber Insulation Plain

More information

Characterising the smoke produced from modern materials and evaluating smoke detectors

Characterising the smoke produced from modern materials and evaluating smoke detectors www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62496-3-1 Edition 1.0 2009-08 Optical circuit boards Part 3-1: Performance standards Flexible optical circuit boards using INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE

More information

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle

More information

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION Stefan Kratzmeir*, IFAB Institute for applied fire safety research, Rostock, Germany Max Lakkonen, FOGTEC Fire Protection, Cologne, Germany

More information

Selecting the AFUMEX range guarantees quality and offers the widest choice and the greatest safety.

Selecting the AFUMEX range guarantees quality and offers the widest choice and the greatest safety. When it matters most, you can be sure of a company that has an unrivalled reputation for high quality, British Standard compliant and cost effective Low Smoke, Zero Halogen (LSOH) cables. Our customers

More information

Data sheet OpDAT universal cable 1x24 OM4 - bend insensitive

Data sheet OpDAT universal cable 1x24 OM4 - bend insensitive Illustrations Principle diagram Page 1/7 Product specification installation cable U-DQ(ZN)BH universal fiber optic cable for indoors/outdoors with central or stranded loose tube bend insensitive fiber

More information

Seismic Countermeasures for Environmental Radiation Monitoring System

Seismic Countermeasures for Environmental Radiation Monitoring System Seismic Countermeasures for Environmental Radiation Monitoring System Osamu Maekawa Takeshi Miyairi Teruo Ebato ABSTRACT Environmental radiation monitoring system continually measures and monitors the

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS - 87 - EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN 1 500 FIREGUARD SENSORS W.W. Schuldt SIGRIST-PHOTOMETER AG, Switzerland ABSTRACT Major fire incidents in road tunnels with a larger number

More information

speed pipe indoor system. Secure indoor networks.

speed pipe indoor system. Secure indoor networks. speed pipe indoor system. Secure indoor networks. www.gabocom.com gabo Systemtechnik 2 3 Networks of the future. Safety obliges. Fiber-optic more and more approaches the end-user also inside buildings

More information

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION Fire alarm cables for highest safety requirements TRADITION INNOVATION PASSION Datwyler Datwyler Cabling Solutions is an internationally operating company with its headquarters in Switzerland and affiliates

More information

and Sprinkler System in Resalat Tunnel of Tehran

and Sprinkler System in Resalat Tunnel of Tehran CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home

More information

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS - 195 - IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS Rajko Rothe; IFAB, Berlin, Germany Max Lakkonen and Dirk Sprakel, FOGTEC Fire Protection, Cologne, Germany ABSTRACT This paper discusses the

More information

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION CEN/TC 305 Business Plan Page: 1 Business environment, benefits and priorities EXECUTIVE SUMMARY CEN/TC 305

More information

WHAT MAKES PRYSMIAN CABLES DIFFERENT?

WHAT MAKES PRYSMIAN CABLES DIFFERENT? WHAT MAKES PRYSMIAN CABLES DIFFERENT? UALITY PRYSMIAN PERFORMANCE TEST TALLATION SAFETY INSTALL N IN ECONOMIC ADVANTAG PRYSMIAN PERFORMANCE TEST Prysmian Group presents Prysmian Performance Test (PPT):

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62054-11 First edition 2004-05 Electricity metering (a.c.) Tariff and load control Part 11: Particular requirements for electronic ripple control receivers IEC 2004 Copyright

More information

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very

More information

THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK

THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK 1. Introduction A) General information According to the European Community standard 2037/2000, it is prohibited in Europe, to employ extinguishing equipment

More information

Saving lives with coatings

Saving lives with coatings Saving lives with coatings The essentials of passive fire protection. Paul Mather. Passive fire protection by means of intumescent, cementitious or ceramifying coatings or layers has gained importance

More information

ecodry Figure 1 - Process Diagram ecodry B General Process Description

ecodry Figure 1 - Process Diagram ecodry B General Process Description ecodry The process principal of the ecodry system is centered around the concept of drying in a closed steam loop, with a process-integrated thermal oxidation. The separation of flue gas from the drying

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

Unit 2 Fire Safety (Zone 1)

Unit 2 Fire Safety (Zone 1) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured

More information

Lloyd s Register Type Approval System Test Specification Number 3

Lloyd s Register Type Approval System Test Specification Number 3 Working together for a safer world Lloyd s Register Type Approval System Test Specification Number 3 July 2015 Performance Test Specification for Equipment to be used in Marine Applications: Electric Cables

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

Annex to the Accreditation Certificate D PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D PL 17819 01 00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 29.06.2017 to 10.08.2019 Holder of certificate: MPA

More information

FAÇADE FIRE TESTS Towards a new European standard method

FAÇADE FIRE TESTS Towards a new European standard method FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on

More information

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 240 244 A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China LIU Xiao-lu *, WANG Wen-qing Shenyang

More information

AO Annunciator Module

AO Annunciator Module General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,

More information

Soot Mitigation Strategies

Soot Mitigation Strategies Soot Mitigation Strategies Walter P. Drosjack, P.E. David L. Oar, P.E., F.S.F.P.E. 32 nd Nuclear Air Cleaning Conference June 18-19, 2012 Who is URS? URS is one of the world s largest engineering, construction

More information