RPM1600 Series Room Pressure Monitors

Size: px
Start display at page:

Download "RPM1600 Series Room Pressure Monitors"

Transcription

1 RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How to Use This Technical Bulletin Safety Information Passcode Part One: User Basics The Instrument Operator Panel LCD Touch Screen Alarms Visual Alarm Audible Alarms Alarm Relays Part Two: Technical Section Configuration Local Configuration Changing the Room Mode Accessing the Menu System Entering Data Drop-Down Selection Numeric Setpoints Programming Example Menus and Menu Items Alarm Constraints Calibration Room Pressure Calibration Calibrating to the TA Sensor Calibrating to the Differential Pressure Transducer

2 Flow Calibration Airflow Measuring Station with Differential Pressure Transducer Calibration Linear Electronic Airflow Measuring Station Calibration Venturi Valve with Feedback Calibration Supply/Exhaust Switch Calibration Door Switch Configuration Temperature Sensor Configuration Relative Humidity Sensor Configuration Occupancy Sensor Configuration Maintenance and Repair Parts System Component Inspection TA Sensor Cleaning Display Screen Cleaning Replacement Parts Troubleshooting Hardware Troubleshooting Confirm Correct Wiring Confirm Correct Physical Installation Verify Mechanical Components Hardware and Software Troubleshooting Calling Johnson Controls for Assistance Appendix A: Technical Specifications RPM1600 Series Room Pressure Monitor Thermal Anemometer (TA) Sensor Appendix B: Network Communications RPM1600 Series Monitors BACnet MS/TP Protocol Implementation Conformance BACnet MS/TP Object Set Appendix C: Wiring Information Wiring Reference Wiring Various Input Devices Wiring Communications

3 RPM1600 Series Room Pressure Monitors Technical Bulletin How to Use This Technical Bulletin This technical bulletin describes how to operate, configure, calibrate, maintain, and troubleshoot the RPM1600 Series Room Pressure Monitors. This manual is divided into two parts. Part One: User Basics on page 4 describes the monitor and the user interface. This section applies to users, facilities staff, and anyone who requires a basic understanding of how the monitor operates. Part Two: Technical Section on page 9 describes the technical aspects of the monitor, which include operation, configuration, calibration, maintenance, and troubleshooting. This section applies to personnel who program or maintain the monitor. Read this manual thoroughly before changing any firmware settings or software items. Note: This technical bulletin assumes that the monitor has been properly installed. Refer to the RPM1600 Series Room Pressure Monitors Installation Instructions (Part No ) for information on properly installing the monitor. Safety Information This section gives instructions to promote safe and proper handling of RPM1600 Series Room Pressure Monitors. There are no user-serviceable parts inside the monitor. Opening the case voids the warranty. Refer all service of the unit to a qualified technician. Passcode RPM1600 Series Room Pressure Monitors have Passcodes to limit unauthorized access to the room mode or complete menu system. The access codes can be turned on or off through the Passcode menu item. When the monitor ships from the factory, it is configured with the access code off. See Configuration on page 9 for instructions on entering the access code. 3

4 Part One: User Basics This section is designed to provide a brief but thorough overview of the RPM1600 Series Room Pressure Monitors. These few pages explain the purpose and the operation of the monitor. Technical product information is available in Part Two: Technical Section on page 9. The Instrument The RPM1600 Series Room Pressure Monitors are designed to measure and report room pressure differentials in health-care facilities and other critical environments. Some models also can measure other parameters, such as supply flow, exhaust flow, relative humidity, and room temperature. Figure 1: Room Pressure Monitor Operator Panel The RPM1600 Series Room Pressure Monitors are easy to use. Room conditions (normal, alarm, no isolation) and room modes (Positive, Negative) appear on the LCD touch screen. You can configure the LCD touch screen to show the room pressure differential or all measurements. This section provides specific details about the LCD touch screen and controls. 4

5 Figure 2 and Figure 3 identify the important features on the LCD touch screen: Figure 2: Single Room Screen Figure 3: One Room with Anteroom Screen 5

6 LCD Touch Screen The LCD touch screen is highly configurable. It can display critical information, including pressure differential, flow rate, alarm status, menu options, and error messages. Use the LCD touch screen to program the device to display menus, menu items, and current value of the menu item. Table 1: Room Indicator Colors Color Definition Green Red Gray 1 The screen icon is colored green (NORMAL) when the room pressure and/or other configured measurements are adequate. This light indicates that the room is operating safely. If a setpoint cannot be maintained or an alarm limit has been reached, the green light turns off, and the red alarm light turns on. The room icon is colored red (ALARM) when the room pressure or other configured measurements exceed alarm limits. This light indicates the room is not operating safely. The display screen also indicates the type of alarm or an emergency message. The room icon is colored gray to indicate No Isolation mode. In No Isolation mode, the RPM1600 Series Monitors do not alarm. 1. Due to the blue screen, gray icons appear blue in digital images. These operator keys appear on the LCD touch screen: Table 2: Operator Keys Key Graphic Key Name Key Function MUTE The MUTE key silences an audible alarm. The alarm remains silent until the MUTE TIME value has been reached or the measurement returns to the control setpoint. ACKNOWLEDGE The ACKNOWLEDGE key stops visual and audible alarms. If you want to enable this feature, set the ALARM RESET item to LATCHED. (See Table 6 on page 22.) Alarms The RPM1600 Series Room Pressure Monitors use visual and audible alarms when room conditions exceed the alarm setpoints. When the room conditions are safely within the field-configured parameters, no alarms sound and the room icons on the LCD touch screen remain green. The alarms activate if the room pressure differential (or airflow) becomes too low or too high. The safe range for room pressure differential is in. W.C. (50 cfm) above the low alarm setpoint and in. W.C. (50 cfm) below the high alarm setpoint. You can program the audible and visual alarms to do one of the following: automatically turn off when the room pressure differential (or airflow) returns to the safe range stay in alarm until the key is pressed (see menu item ALARM RESET) 6

7 Example: Figure 4: Alarm Example for Negative Room Mode Low Alarm (higher pressure, less negative) Normal (safe range) Negative Low Alarm Setpoint High Alarm (lower pressure, more negative) Negative High Alarm Setpoint When a room is set to Negative mode, the low and high alarms are Neg Low Alm and Neg Hi Alm. The normal differential pressure range (safe zone) is between the Neg Low Alm and Neg Hi Alm setpoints. Table 3: Alarms and Differential Pressure Alarm Action Low Alarm High Alarm Alarm Setpoint in. W.C in. W.C. Alarm Activates < in. W.C. > in. W.C. Alarm Deactivates in. W.C in. W.C. Notes: Optional flow monitors are required for airflow alarms. Depending on the organization of your safety staff, the people who determine the parameters and the alarm setpoints may be in an Engineering, Industrial Hygiene, or Facilities group. Visual Alarm If an alarm condition occurs in a room, that room s icon on the LCD touch screen changes to red. The room icon remains red as long as that alarm condition remains. See Table 1 for an explanation of room icon colors. Audible Alarms The audible alarm is continuously on in all low and high alarm conditions, as long as that alarm condition remains. Press the key to silence the audible alarm. If the audible alarm has been muted, the alarm is silenced for a configurable period of time (see menu item MUTE TIME) or when the measurement returns to the safe range. The safe range is in. W.C. (50 cfm) above the low alarm setpoint and in. W.C. (50 cfm) below the high alarm setpoint. The audible and visual alarms can be programmed to either automatically turn off when the unit returns to the safe range or to stay in alarm until the key is pressed (see menu item ALARM RESET). Alarm Relays The monitor uses two alarm relays. The alarm relays open or close to indicate an alarm condition, according to programmed settings. The alarm relays close on loss of power. 7

8 Relay 1 (low alarm relay) activates after the alarm delay for the following alarms: low pressure low flow low temperature low RH Relay 1 activates immediately if either of the following occurs: a linear output module (LOM) alarm low pressure drop across a Venturi valve (if a flow input is configured for Venturi valves) Relay 2 is field-configurable to function as a high alarm relay or to indicate the room status. See the Relay 2 Out item in the Alarm Config menu (see Table 6 on page 22) for details on this operation. 8

9 Part Two: Technical Section The RPM1600 Series Monitors are ready to use after they are properly installed and configured. The thermal anemometer (TA) sensor is factory-calibrated, as are most differential pressure transducers (DPTs). Figure 1 on page 4 shows the Room Pressure Monitor (RPM), which is programmed with a default configuration that can be easily modified to fit your application. The technical section is separated into five parts that cover all aspects of the RPM. Each section is written as independently as possible. 1. Configuration on page 9 explains the programming keys, the programming sequence, and how to program the RPM. 2. Menus and Menu Items on page 17 lists all of the firmware items, some of which are available to program and change. The items are grouped by menu, which means that all setpoints are in one menu, all control signal items in another menu, and so on. The menu items include programming name, description of menu item, range of programmable values, and the default value (factory-set value). 3. Calibration on page 48 describes the required procedure to calibrate the RPM. This section explains how to compare the RPM s reading to a portable thermal anemometer and then adjust the span to establish an accurate calibration. This section also describes how to zero a flow station transducer (if installed). 4. Maintenance and Repair Parts on page 52 covers all routine maintenance of equipment, along with a list of repair parts. 5. Troubleshooting on page 54 describes how to diagnose and resolve mechanical or performance problems. Configuration Configuring the RPM1600 Series Room Pressure Monitor is quick and easy if you follow the proper keystroke procedure. This section covers how to configure the monitor through the LCD touch screen. IMPORTANT: The RPM1600 Series monitor continues operating during configuration. When you change the value of a menu item, the new value takes effect immediately after saving the change. You can configure the RPM1600 Series monitors by using either of the two methods: Local Configuration Method (uses only the LCD touch screen) Combined Configuration Method (uses the LCD touch screen and BACnet MS/TP network communications) Note: If you use the Combined Configuration Method, use the host computer s procedure (see Appendix B: Network Communications on page 63). 9

10 Local Configuration Changing the Room Mode 1. Tap the Room Mode button for the room on the touch screen. Figure 5: Main Running Screen Room Mode Button Note: To change the room mode, enter passcode 0317 and press Save. Figure 6: Passcode Screen 2. Tap the preferred room mode at the bottom of the screen. Figure 7: Room Mode Selection Screen Note: If you do not select a room mode, the monitor returns to the main running screen after a short delay. 10

11 Accessing the Menu System 1. Swipe across the display, from the top-right corner to the bottom-left corner. Figure 8: Swipe to Access Menu System Note: To access the menu system, enter Passcode 2887 and press Enter. Figure 9: Passcode Screen 2. The Main Menu screen appears. Tap any menu name to access that menu s items. Figure 10: Main Menu Screen After you tap a menu name, the screen changes to show the items associated with that menu. See Menus and Menu Items on page 17 for a list of the menus and their associated items. 11

12 Entering Data After you enter a menu item, the LCD touch screen changes, allowing you to select items. Some items have predefined settings selected through a drop-down menu; others allow numeric setpoints. Note: Not all menus or menu items are available on all models. Drop-Down Selection You can easily view available choices and make a selection from drop-down items: 1. Tap the item displayed in the drop-down box to view all available options. 2. Tap an item. 3. Tap Save to save your selection and exit the item or tap Cancel to exit the item without saving. Figure 11: Using a Drop-Down Selection Numeric Setpoints On a numeric setpoint screen, the current setpoint appears in a box at the top left of the screen. You can use the numeric keypad to enter a new setpoint between the Min and Max values listed on the screen. (The measurement units are displayed as Units.) <- deletes the last digit. Clr clears the entire setpoint. Save saves your selection and exits the item. Cancel exits the item without saving changes. Figure 12: Entering Numeric Setpoints 12

13 Programming Example The following example demonstrates the keystroke sequence. In this example, the negative low alarm setpoint for Room 1 changes from to in. W.C. Table 4: Programming Example (Part 1 of 4) Step Screen Description 1 Figure 13: Main Running Screen: Normal The Main Running Screen shows that the monitor is in normal operation. 2 Swipe from the top-right corner to the bottomleft corner to access the menu Figure 14: Accessing the Menu System system. 3 To access the menu system, enter Passcode Figure 15: Passcode Screen 2887 and press Enter. 13

14 Table 4: Programming Example (Part 2 of 4) Step Screen Description 4 The main menu screen appears. Figure 16: Main Menu Screen 5 Tap Rm1 Alarm. Figure 17: Select Room 1 Alarm Submenu 6 The Rm1 Alarm menu screen appears. Tap Figure 18: Room 1 Alarm Submenu Neg Low Alm. 14

15 Table 4: Programming Example (Part 3 of 4) Step Screen Description 7 The Neg Low Alm menu screen appears, Figure 19: Negative Low Alarm showing the default setting of in. W.C. Enter the new setpoint of in. W.C. Tap Save to save the new setting. 8 The Rm1 Alarm menu screen appears. Figure 20: RM1 Alarm Menu Screen Tap Exit to return to the main menu screen. 9 The main menu screen appears. Tap Exit to Figure 21: Main Menu Screen return to the main running screen. 15

16 Table 4: Programming Example (Part 4 of 4) Step Screen Description 10 Figure 22: Main Running Screen: Normal The Main Running Screen shows that the unit is in normal operation. 16

17 Menus and Menu Items The RPM1600 Series monitors are versatile devices configured to meet specific application requirements. This section lists all of the menu items, most of which are available to program and change. Change items by using the touch screen or through communications with the Building Automation System. See Configuration on page 9 for a detailed explanation of the keystroke procedure. This section provides the following information: a complete list of menus and all menu items the menu item or software name each menu item s function the range of available values the default (factory-set) item value The menus covered in this section are divided into groups of related items to ease programming. As an example, all setpoints are in one menu, all alarm information in another menu, and so on. The manual follows the menus as they appear in the monitor. Note: The menu items are always grouped by menu and then listed in menu item order, not alphabetical order. Figure 23 shows the RPM1611 monitor menu items. Figure 23: Menu Items RPM1611 Monitors Configure # of Rooms Press Modes Rm1 Label Display Meas Display Avg Units Passcode Num Format Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Rm1 Alarm Room Mode Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm Exh Low Alm Sup Low Alm Alarm Enable ACH Duct Room 1 Vol Diagnostics View Inputs View Outputs Relay Outputs Analog Output Touch Cal Reset Alarm Config Alarm Reset Audible Alm Alarm Delay Mute Time Door Delay Relay 2 Out Relay 1 Dir Relay 2 Dir Interface Comm Type Address MAC ID Baud Rate Nurse Address AO1 Sig Type AO2 Sig Type AO2 Sig Rnge AO2 Out Type AO3 Sig Type Input 1 Configure Input 2 Configure Input 3 Configure Input 4 Configure Input 5 Configure Input 6 Configure Input 7 Configure See menu for items. FIG:RPM1611_mnu Figure 24 shows the monitor menu items. Figure 24: Menu Items Monitors Configure # of Rooms Press Modes Rm1 Label Display Meas Display Avg Units Passcode Num Format Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Rm1 Alarm Room Mode Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm Exh Low Alm Sup Low Alm Alarm Enable ACH Duct Room 1 Vol AnteRm Alarm Room Mode Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm Rm2 Alarm Room Mode Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm Alarm Config Alarm Reset Audible Alm Alarm Delay Mute Time Door Delay Relay 2 Out Relay 1 Dir Relay 2 Dir Diagnostics View Inputs View Outputs Relay Outputs Analog Output Touch Cal Reset Interface Comm Type LON Address MAC ID Baud Rate Nurse Address AO1 Sig Type AO2 Sig Type AO2 Sig Rnge AO2 Out Type AO3 Sig Type AO3 Sig Rnge AO3 Out Type Input 1 Configure Input 2 Configure Input 3 Configure Input 4 Configure Input 5 Configure Input 6 Configure Input 7 Configure See menu for items. FIG:_mnu 17

18 Table 5: Configure Menu (Part 1 of 4) Menu Item Software Name Number of Rooms Monitored Language Number of Pressure Mode Selections Item Description Item Range Default Value # of Rooms The # of Rooms item selects the number of rooms the RPM1600 monitors and controls. RPM1611: 1 Room : 1 Room, 1 Room with Anteroom, 2 Rooms with Anteroom 1 Room Language The Language item selects the language of the user interface. English Dutch English Press Modes The Press Modes item determines the room modes available 2 Buttons, 3 Buttons 2 Buttons for selection when you press the Room Mode button on the main running screen. Press Mode: 2 Buttons Positive/No Isolation or Negative/No Isolation (based on the Room Mode item in the respective Alarm menu) Press Mode: 3 Buttons Negative/No Isolation/Positive IMPORTANT: Codes and Standards in the US and many other areas of the world do not allow a room to be switched from Positive to Negative Isolation. Consult local authorities before setting Press Modes to 3 Buttons. Label for Room 1 Rm1 Label The Rm1 Label item allows you to set the room number or other designator for Room characters of text ROOM 1 Label for Anteroom AnteRm Label The AnteRm Label item allows you to set the room number or other designator for the anteroom. Note: AnteRm Label is only active if the # of Rooms item is set to 1 Room with Anteroom or 2 Rooms with Anteroom. 13 characters of text ANTEROOM Label for Room 2 Rm2 Label The Rm2 Label item allows you to set the room number or other designator for Room 2. Note: Rm2 Label is only active if the # of Rooms item is set to 2 Rooms with Anteroom. 13 characters of text ROOM 2 18

19 Table 5: Configure Menu (Part 2 of 4) Menu Item Software Name Measurements Display Meas Displayed RPM1611 Display Average Display Units Enable Pass Codes Number Format Configure INPUT1 Display Avg Units Passcode Num Format Input 1 Item Description Item Range Default Value The Display Meas item selects which measurements are presented on the LCD touch screen during normal operating mode. Use the Units item to choose the units of measure: ROOM STATUS displays the room mode as negative, positive, or no isolation. ROOM PRESSURE displays the room mode and the current measurement of room pressure differential. ALL displays the room mode and all currently connected measurements. Only functions when the # of Rooms item is set to 1 Room. Note: Measurements that result in alarm conditions activate alarms, even if those measurements do not appear on the display. The Display Avg item selects the length of time the monitor averages the flow velocity before displaying the averaged velocity. Note: The higher the averaging value, the more stable the displayed averaged velocity. The Units item selects the unit of measure that the monitor displays. The Passcode item prevents unauthorized access to a menu. If the Passcode item is: OFF - no Passcode is required to enter the room mode or menu screens. ROOM MODE - a Passcode is required to enter the room mode screens but not the menu screens. MENUS - a Passcode is required to enter the menu screens but not the room mode screens. ALL - a Passcode is required to enter the room mode and menu screens. The Num Format menu item selects the way that numbers are displayed. The Input 1 item selects the pressure-sensing input type for Room 1. 1 Room Status, Room Pressure, All Room Status 1, 2, 3, 5, 10, 20, or 40 seconds 20 seconds in. W.C., CFM, F Pa, LPS, C Pa, CMH, C Off Room Mode Menus All Period Comma TA Sensor, Pressure Transducer in. W.C., CFM, F Menus Period TA Sensor 19

20 Table 5: Configure Menu (Part 3 of 4) Menu Item Software Name Configure INPUT2 Input 2 Configure INPUT3 Configure INPUT4 Configure INPUT5 Item Description Item Range Default Value The Input 2 item selects the pressure-sensing input type for the AnteRm. 1 Note: The Input 2 item is only active if the # of Rooms item is set to 1 ROOM WITH ANTEROOM or 2 ROOMS WITH ANTEROOM. Input 3 The Input 3 item selects the input type for Input3. 1 Note: The RPM1611 Monitor cannot be set to Sensor or Pressure Transducer. Note: Input 3 can only be set to Sensor or Pressure Transducer if the # of Rooms item is set to 2 Rooms with Anteroom. TA Sensor Pressure Transducer None RPM1611: Supply Pressure Flow Supply Linear Flow, Supply Venturi Flow Supply Switch None : Supply Pressure Flow Supply Linear Flow, Supply Venturi Flow Supply Switch TA Sensor 2 Pressure Transducer 2 None Input 4 The Input 4 item selects the input type for Input4. 1 Room1 Door Switch Room1 Occupancy Sensor None Input 5 The Input 5 item selects the input type for Input5. 1 Note: The RPM1611 Monitor cannot be set to Relative Humidity Sensor. Room1 Key Switch Relative Humidity Sensor ( Only) None None None None None 20

21 Table 5: Configure Menu (Part 4 of 4) Menu Item Software Item Description Item Range Default Value Name Configure INPUT6 Input 6 The Input 6 item selects the input type for Input6. 1 : None Note: The Input 6 item is not functional on the Room1 Temp Sensor RPM1611 Monitor. It is only active on the Room 2 Occupancy Sensor Monitor. Room 2 Door Switch None Configure INPUT7 Input 7 The Input 7 item selects the input type for Input7. 1 Note: Input 7 can only be set to Room 2 Key Switch if the # of Rooms item is set to 2 Rooms With Anteroom. Note: The RPM1611 Monitor cannot be set to Room 2 Key Switch. 1. Go to the submenu related to each numbered input item to adjust parameters associated with that input. 2. These items do not appear in the menu if you use the default setting 1 ROOM. RPM1611: Exhaust Pressure Flow Exhaust Linear Flow Exhaust Venturi Flow Exhaust Switch None : Exhaust Pressure Flow Exhaust Linear Flow Exhaust Venturi Flow Exhaust Switch Room 2 Key Switch None None 21

22 Table 6: Alarm Config Menu (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Alarm Reset Alarm Rest The Alarm Reset item selects how the alarms terminate after the measured condition returns to the setpoint [or within the range for normal operation]. The Alarm Reset affects the audible alarm, visual alarm, and relay output, which means all are latched or unlatched. LATCHED requires someone to press the key to clear alarms. Latched, Unlatched Unlatched Enable Sound Alarm Delay Mute Timeout Door Delay Relay 1 Output Direction Relay2 Output Signal UNLATCHED (alarm follow) automatically resets the alarm when the room pressure is: in. W.C. greater than the low alarm setpoint, or in. W.C. below the high alarm setpoint 50 cfm greater than the low alarm setpoint for flow alarms 0.3 F for temperature Audible Alm The Audible Alm item enables the audible alarm on the monitor. On, Off Off Alarm Delay The Alarm Delay item sets the period of time the room pressure differential, flow, or temperature must be above the high alarm setpoint or below the low alarm setpoint before the controller enters alarm mode. Use the Alarm Delay function to avoid momentary, nuisance alarms. Mute Time The Mute Time item sets the length of time the audible alarm is silenced if the mute button is pressed. The Mute Time can be set from 1 to 60 minutes. Door delay The Door Delay item sets the period of time the room pressure differential, flow, or temperature must be above the high alarm setpoint or below the low alarm setpoint before the monitor enters alarm mode when the door is open. Use the Door Delay function to avoid momentary, nuisance alarms. Note: Input4 Config or Input6 Config must be set to DOOR SWITCH for the Door Delay to take effect. Door Delay can be configured even if Input 4 or Input 6 is not set to DOOR SWITCH. Relay 1 Dir The Relay 1 Dir item sets the signal output to be used with Relay 1. (Relay 1 Output Signal is permanently set to HIGH ALARM.) Relay 2 Out The Relay 2 Out item sets the alarm output for Relay 2. If set to: HIGH ALARM - the monitor activates the relay if a high alarm condition exists. NEGATIVE ROOM - the monitor activates the relay when the mode for Room 1 is Negative. POSITIVE ROOM - the monitor activates the relay when the mode for Room 1 is Positive. 1 to 600 seconds 20 seconds 1 to 60 minutes 5 minutes 1 to 600 seconds 60 seconds OK = OPEN OK = CLOSED High Alarm Negative Room Positive Room OK = OPEN High Alarm 22

23 Table 6: Alarm Config Menu (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Relay 2 Output Direction Relay 2 Dir The Relay 2 Dir item sets the signal output to be used with Relay 2. Relay 2 Out is set to HIGH ALARM: OK = OPEN OK = CLOSED OK = OPEN Relay 2 Out is set to NEGATIVE ROOM or POSITIVE ROOM. Note: No Isolation (NO ISO) room mode is either relay open or relay closed. NO ISO = OPEN NO ISO = CLOSED NO ISO = OPEN Table 7: Rm1 Alarm Menu (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Mode of Room 1 Room 1 Negative Low Alarm Room 1 Negative High Alarm Room 1 Positive Low Alarm Room 1 Positive High Alarm Room Mode Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm The Room Mode item selects the room pressure direction. This item enables all related alarms, for pressure direction selected. Note: No Isolation Room Mode can be selected from the main running screen. The Neg Low Alm item sets the negative low pressure alarm setpoint. A low alarm condition occurs when the room pressure falls below the Neg Low Alm setpoint. This item is active when the ROOM MODE item is NEGATIVE. You can always access this item through the menu system. The Neg Hi Alm item sets the negative high pressure alarm setpoint. A high alarm condition occurs when the room is more negative than the Neg Hi Alm setpoint. This item is active when the ROOM MODE item is NEGATIVE. You can always access this item through the menu system. The Pos Low Alm item sets the positive low pressure alarm setpoint. A low alarm condition occurs when the room is less positive than the Pos Low Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. You can always access this item through the menu system. The Pos Hi Alm item sets the positive high pressure alarm setpoint. A high alarm condition occurs when the room pressure rises above the Pos Hi Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. You can always access this item through the menu system. Positive Negative to in. W.C. Note: Neg Low Alm cannot be set more negative than the Neg Hi Alm to in. W.C. Note: Neg Hi Alm cannot be set less negative than the Neg Lo Alm to in. W.C. Note: Pos Low Alm cannot be set more positive than the Pos Hi Alm to in. W.C. Note: Pos Hi Alm cannot be set less positive than the Pos Lo Alm. Negative in. W.C in. W.C in. W.C in. W.C. 23

24 Table 7: Rm1 Alarm Menu (Part 2 of 2) Menu Item Software Name Alarm Enable Room 1 Alarm Enable Room 1 Low Exhaust Flow Alarm Room 1 Low Supply Flow Alarm High Room Temperature Alarm Room 1 Low Room Temperature Alarm Room Volume Duct for Air Changes per Hour Calculation Low Relative Humidity Alarm High Relative Humidity Alarm Exh Low Alm Sup Low Alm Temp Hi Alm Temp Low Alm Room1 Vol ACH Duct RH Low Alm RH Hi Alm Item Description Item Range Default Value The Alarm Enable item enables the low and high alarm functions. When you enter this item, the monitor shows buttons for Low Alarms and High Alarms. Tap the button to toggle between enabling and disabling the alarms. Note: The Alarm Enable item enables or disables pressure, flow, temperature, and humidity alarms. The Exh Low Alm item sets the minimum exhaust flow alarm setpoint. A minimum flow alarm occurs when the exhaust flow is less than the Exh Low Alm setpoint. The Sup Low Alm item sets the minimum supply flow alarm setpoint. A minimum flow alarm occurs when the supply flow is less than the Sup Low Alm setpoint. The Temp Hi Alm item sets the maximum room temperature alarm setpoint. The Temp Low Alm item sets the minimum room temperature alarm setpoint. The Room1 Vol item sets the room volume for the Air Changes per Hour (ACH) calculation. The ACH Duct item sets the duct to be used for ACH calculations: SUPPLY is normally used for positive rooms EXHAUST is normally used for negative rooms OFF is used if you are not interested in the ACH calculation The RH Low Alm item sets the minimum relative humidity alarm setpoint. The RH Hi Alm item sets the maximum relative humidity alarm setpoint. Enabled Disabled Low Alarms Enabled High Alarms Disabled 0 to CFM 0 CFM 0 to CFM 0 CFM 50 to 100 F Note: Temp Hi Alm cannot be set less than the Temp Low Alm. 50 to 100 F Note: Temp Low Alm cannot be set greater than the Temp Hi Alm. 100 F 50 F 0 to ft 3 0 ft 3 OFF SUPPLY EXHAUST 0 to 100% Note: RH Low Alm cannot be set greater than the RH Hi Alm. 0 to 100% Note: RH Hi Alm cannot be set less than the RH Low Alm. OFF 0% 100% 24

25 Table 8: AnteRm Alarm Menu Menu Item Software Name Item Description Item Range Default Value Mode of Anteroom Anteroom Negative Low Alarm Anteroom Positive Low Alarm Anteroom Positive High Alarm Anteroom Alarm Enable Room Mode Neg Low Alm Pos Low Alm Pos Hi Alm Alarm Enable The Room Mode item selects the room pressure direction. This item enables all related alarms, for pressure direction selected. Selecting ROOM1 means that the Room Mode follows the Room Mode of Room 1. Note: You can select No Isolation Room Mode from the main running screen. The Neg Low Alm item sets the negative low pressure alarm setpoint. A low alarm condition occurs when the magnitude of the room pressure falls below the Neg Low Alm setpoint. This item is active when the ROOM MODE item is NEGATIVE. You can always access this item through the menu system. The Pos Low Alm item sets the positive low pressure alarm setpoint. A low alarm condition occurs when the room is less positive than the Pos Low Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. You can always access this item through the menu system. The Pos Hi Alm item sets the positive high pressure alarm setpoint. A high alarm condition occurs when the room pressure rises above the Pos Hi Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. You can always access this item through the menu system. The Alarm Enable item enables the low and high alarm functions. When this item is entered, the monitor shows buttons for Low Alarms and High Alarms. Tap the button to toggle between enabling and disabling the alarms. Positive Negative Room to in. W.C. Note: Neg Low Alm cannot be set more negative than the Neg Hi Alm to in. W.C. Note: Pos Low Alm cannot be set more positive than the Pos Hi Alm to in. W.C. Note: Pos Hi Alm cannot be set less positive than the Pos Lo Alm. Enabled Disabled Negative in. W.C in. W.C in. W.C. Low Alarms Enabled High Alarms Disabled 25

26 Table 9: Rm2 Alarm Menu Menu Item Software Name Item Description Item Range Default Value Mode of Room 2 Room 2 Alarm Enable Room 2 Negative Low Alarm Room 2 Negative High Alarm Room 2 Positive Low Alarm Room 2 Positive High Alarm Room Mode Alarm Enable Neg Low Alm Neg Hi Alm Pos Low Alm Pos Hi Alm The Room Mode item selects the room pressure direction. This item enables all related alarms, for pressure direction selected. Selecting ROOM1 means that the Room Mode follows the Room Mode of Room 1. Note: No Isolation Room Mode can be selected from the main running screen. The Alarm Enable item enables the low and high alarm functions. When this item is entered, the monitor shows buttons for Low Alarms and High Alarms. Press the button to toggle between enabling and disabling the alarms. The Neg Low Alm item sets the negative low pressure alarm setpoint. A low alarm condition occurs when the magnitude of the room pressure falls below the Neg Low Alm setpoint. This item is active when the ROOM MODE item is NEGATIVE. The Neg Hi Alm item sets the negative high pressure alarm setpoint. A high alarm condition occurs when the room is more negative than the Neg Hi Alm setpoint. This item is active when the ROOM MODE item is NEGATIVE. The Pos Low Alm item sets the positive low pressure alarm setpoint. A low alarm condition occurs when the room is less positive than the Pos Low Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. The Pos Hi Alm item sets the positive high pressure alarm setpoint. A high alarm condition occurs when the magnitude of the room pressure rises above the Pos Hi Alm setpoint. This item is active when the ROOM MODE item is POSITIVE. Positive Negative Room1 Enabled Disabled to in. W.C. Note: Neg Low Alm cannot be set more negative than the Neg Hi Alm to in. W.C. Note: Neg Hi Alm cannot be set less negative than the Neg Lo Alm to in. W.C. Note: Pos Low Alm cannot be set more positive than the Pos Hi Alm to in. W.C. Note: Pos Hi Alm cannot be set less than positive the Pos Lo Alm. Negative Low Alarms Enabled High Alarms Disabled in. W.C in. W.C in. W.C in. W.C. 26

27 Alarm Constraints The following constraints may prohibit you from incorrectly adjusting the setpoints: 1. Room mode. The positive pressure alarms are only active when positive control is selected. Negative pressure alarms are only active when negative control is selected. In No Isolation mode, all alarms are turned off. 2. The monitor is programmed with deadbands between alarm setpoints to prevent the controller from cycling between high and low alarms due to normal fluctuations. Setpoint deadbands are: Pressure = in. W.C. Flow = 50 cfm Temperature = 1 F Relative Humidity = 1% Position = 1% Open Example: The control NEG LOW ALM is set at in. W.C. The NEG HI ALM cannot be set less negative than in. W.C. 3. Alarms do not terminate until the room pressure slightly exceeds the alarm setpoint. 4. The ALARM RESET item selects how the alarms terminate when the controller returns to the safe range. The pressure and flow alarms all terminate the same; either latched or unlatched. If unlatched is selected, the alarms automatically turn off when the value slightly exceeds the alarm setpoint. If latched is selected, the alarms do not terminate until the pressure or flow exceeds the alarm setpoint and the key is pressed. 5. A programmable ALARM DELAY determines how long to delay before activating the alarms. This delay affects all alarms, pressure, and flow. 6. The MUTE TIME item temporarily turns the audible alarm off for all pressure and flow alarms. 7. The display can only show one alarm message. Therefore, the monitor has an alarm priority system, with the highest priority alarm being displayed. If multiple alarms exist, the lower priority alarms do not display until after the highest priority alarm has been eliminated. The alarm priority is as follows: a. Room 1 pressure sensor low alarm b. Room 1 pressure sensor high alarm c. Room 1 minimum exhaust flow d. Room 1 minimum supply flow e. Room 1 temperature alarms f. Room 1 relative humidity alarms g. Room 1 supply Venturi (low static pressure) alarm h. Room 1 exhaust Venturi (low static pressure) alarm i. Anteroom pressure sensor low alarm j. Anteroom pressure sensor high alarm k. Room 2 pressure sensor low alarm l. Room 2 pressure sensor high alarm m. Room 1 supply airflow-proving switch n. Room 1 exhaust airflow-proving switch 27

28 8. The low and high alarms are absolute values. Figure 25 shows how the values must be programmed in order to operate correctly. The value of each setpoint or alarm is not important (except for small dead band) in the following graph. It is important to understand that the high alarm is a greater negative (positive) value than the low alarm. Figure 25: Low and High Alarm Values -0.2 in. W.C. Minimum Transducer Reading (Maximum Negative) High Negative Alarm Low Negative Alarm Low Positive Alarm +0.2 in. W.C. Maximum Transducer Reading (Maximum Positive) High Positive Alarm FIG:Alrm_ HiLo_ Neg_Pos Table 10: Diagnostics Menu Menu Item Software Name Item Description Control Relay Outputs Relay Outputs The Relay Outputs item allows you to view and manually control the two relay outputs. Manually Adjust Analog Outputs Analog Outpt The Analog Outpt item allows you to manually control the Analog Outputs. View Measurement Inputs View Inputs The View Inputs item allows you to view the measurements for all seven inputs on one screen. View Output Signals View Outputs The View Outputs item allows you to view the current output signals, in units of V or ma. Recalibrate Touch Screen Reset to Default Touch Cal Reset The Touch Cal item starts the touch screen recalibration process. While recalibrating the touch screen, the RPM directs you to tap the screen in various places. Note: For best results, use a stylus, pen, or similar object when recalibrating the touch screen. The Reset item resets all parameters to factory default. Table 11: Interface Menu (Part 1 of 2) Menu Item Software Item Description Item Range Default Value Name Network Communications Protocol Comm Type The Comm Type item selects the communications protocol used to interface with the building management system. Modbus BACnet BACnet Not Used LON Not Used Not Used Not Used 28

29 Table 11: Interface Menu (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Network Address Address The Address item sets the main network address of the room pressure monitor. BACnet: 4 to Each unit on the network must have its own unique address. Note: Addresses Note: Address is only functional when Comm Type is set to MODBUS or 1 to 3 are BACNET. reserved. Note: Changes to the Address may take up to 1 minute to take effect. MAC ID Network Address for Nurses Station Baud Rate Analog Output Signal Type Analog Output Signal Type Analog Output Signal Type Analog Output Signal Type Analog Output Signal MAC ID Nurse Address Baud Rate AO1 Sig Type AO2 Sig Type MAC ID is the Device Instance. Note: MAC ID is only functional when Comm Type is set to BACNET. Note: Changes to the MAC ID may take up to 1 minute to take effect when using BACnet communications. The Nurse Address item sets the main network address of the room pressure monitor when communicating with the Nurses Station Display (NSD). Each device on the network must have its own unique address. Note: RPM1600 monitors have rooms displayed on the NSD in order of the Nurse Address. The monitor with the lowest Nurse Address is displayed at the top-left of the NSD screen. If a monitor is configured for more than one room, then the rooms display on the NSD in order of Room 1, Room 2, and Anteroom. The Baud Rate item sets the communication speed of the monitor. Note: Changes to the Baud Rate may take up to 1 minute to take effect. Baud Rate is not configurable when Comm Type is set to Modbus. The AO1 Sig Type item selects the measurement that the analog output signal represents. The AO2 Sig Type item selects the measurement that the analog output signal represents. 1 to to 8 1 BACnet : 9600, 19200, 38400, 76800, AutoBaud None Room 1 Pressure Exhaust Flow None AO2 Out Type The AO2 Out Type item selects the analog output (not control output signal). 0 to 10 VDC 4 to 20 ma AO3 Sig Type The AO3 Sig Type item selects the measurement that the analog output signal represents. Room 2 Pressure Supply Flow Exhaust Flow None AO3 Out Type The AO3 Out Type item selects the analog output (not control output signal). 0 to 10 VDC or 4to20mA 1. The default address is set to an invalid value. You must change the value of the Network Address to an address within the specified range. BACnet : None None 0 to 10 VDC None 0to10VDC 29

30 Table 12: Input 1 Config Menu - TA Sensor Menu Menu Item Software Item Description Item Range Default Value Name Set Sensor Zero Calibration Sensor Zero The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). None Unit is factory calibrated and should not need adjustment. Set Sensor Span Calibration Set Sensor Elevation Reset Calibration Check Sensor Status Sensor Span Elevation Reset Cal Check Status The Sensor Span item matches or calibrates the TA sensor to the average room pressure velocity as measured by a portable air velocity meter. The Elevation item enters the elevation of the TA sensor above sea level. The pressure value requires correction due to changes in air density when you use the RPM at different elevations. Note: The density adjustments are in 1,000 foot increments, even though this number can be entered in increments of 1 foot. For example, the monitor interprets Elevation settings between 0 and 999 feet as 0 feet, settings between 1000 and 1999 feet as 1000 feet, and so on. The Reset Cal item returns the RPM to the factory-default calibration, undoing field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Are You Sure. Enter YES to reset the Sensor Zero, Sensor Span and Elevation items to defaults. Enter NO to cancel the reset. The Check Status item checks the communication status of the sensor. After you tap the button, the RPM responds with: COMM ERROR - RPM cannot communicate with TA sensor. Check all wiring and the pressure sensor address. SENS ERROR - Physical damage to TA sensor circuitry. Unit is not fieldrepairable. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. CAL ERROR - Calibration data lost. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. DATA ERROR - Problem with TA sensor EEPROM, field calibration or analog output. Check all data configured and confirm unit is functioning correctly. None 0 to 10,000 feet above sea level None None Unit is factory calibrated and should not need adjustment. 0 N/A N/A 30

31 Table 13: Input 1 Config Menu - Press Trans Menu Menu Item Software Item Description Item Range Default Value Name Set Minimum Sensor Pressure Output Sensor Min The Sensor Min item sets the minimum reading of a DPT that measures room pressure differential. For example, if the DPT has a range of to in. W.C. (-62.5 to Pa), set the Sensor Min to in. W.C. (-62.5 Pa) to in. W.C. 0 Set Maximum Sensor Pressure Output Set Minimum Sensor Voltage Output Set Maximum Sensor Voltage Output Set Sensor Zero Calibration Reset Calibration Sensor Max Signal Min Signal Max Sensor Zero Reset Cal The Sensor Max item sets the maximum reading of the DPT that measures room pressure differential. For example, if the DPT has a range of to in. W.C. (-62.5 to Pa), set the Sensor Max to in. W.C. (+62.5 Pa). The Signal Min item sets the minimum output signal when you use a DPT to measure room pressure differential. The Signal Max item sets the maximum output signal when you use a DPT to measure room pressure differential. The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the monitor prompts you to verify that you want to do this by displaying the message Are You Sure? Enter YES to reset the Sensor Zero factor for this DPT to defaults. Enter NO to cancel the reset to in. W.C. 0to5V 1to10V Table 14: Input2 Config Menu - TA Sensor (Part 1 of 2) Menu Item Software Item Description Item Range Default Value Name Set Sensor Zero Calibration Sensor Zero The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). None Unit is factory calibrated and should not need adjustment. Set Sensor Span Calibration Sensor Span The Sensor Span item matches or calibrates the TA sensor to the average room pressure velocity as measured by a portable air velocity meter. None None None 0 0V 10V N/A N/A Unit is factory calibrated and should not need adjustment. 31

32 Table 14: Input2 Config Menu - TA Sensor (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Set Sensor Elevation Elevation The Elevation item enters the elevation of the TA sensor above sea level. The pressure value requires correction due to changes in air density when you use the RPM at different elevations. Note: The density adjustments are in 1,000 foot increments, even though this number can be entered in increments of 1 foot. For example, the monitor interprets Elevation settings between 0 and 999 feet as 0 feet, settings between 1000 and 1999 feet as 1000 feet, and so on. 0 to 10,000 feet above sea level 0 Reset Calibration Check Sensor Status Reset Cal Check Status The Reset Cal item returns the RPM to the factory default calibration, undoing field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Sensor Zero, Sensor Span, and Elevation items to factory defaults. Enter NO to cancel the reset. The Check Status item checks the communication status of the TA sensor. After you press the button, the RPM responds with: COMM ERROR - RPM cannot communicate with sensor. Check all wiring and the pressure sensor address. SENS ERROR - Physical damage to pressure sensor circuitry. Unit is not fieldrepairable. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. CAL ERROR - Calibration data lost. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. DATA ERROR - Problem with TA sensor EEPROM, field calibration or analog output. Check all data configured and confirm that the unit is functioning correctly. Table 15: Input2 Config Menu - Pressure Transducer (Part 1 of 2) Menu Item Software Item Description Item Range Default Value Name Set Minimum Sensor Pressure Output Sensor Min The Sensor Min item sets the minimum reading of a pressure transducer that measures room pressure differential. For example, if the pressure transducer has a range of to in. W.C. (-62.5 to Pa), set the Sensor Min to in. W.C. (-62.5 Pa) to+1.00 in. W.C. 0 Set Maximum Sensor Pressure Output Sensor Max The Sensor Max item sets the maximum reading of a pressure transducer that measures room pressure differential. For example, if the pressure transducer has a range of to in. W.C. (-62.5 to Pa), set the Sensor Max to in. W.C. (+62.5 Pa). None None -1.00to+1.00 in. W.C. N/A N/A 0 32

33 Table 15: Input2 Config Menu - Pressure Transducer (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Set Minimum Sensor Voltage Output Signal Min The Signal Min item sets the minimum output signal of a pressure transducer that measures room pressure differential. 0to5V 0 V Set Maximum Sensor Voltage Output Set Sensor Zero Calibration Reset Calibration Signal Max Sensor Zero Reset Cal The Signal Max item sets the maximum output signal of a pressure transducer that measures room pressure differential. The Sensor Zero item sets the signal from the pressure transducer that corresponds to a room pressure differential of 0 (neutral). The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Sensor Zero item to defaults. Enter NO to cancel the reset. 1to10V Table 16: Input3 Config Menu - Sup Pres Flow (Part 1 of 3) Menu Item Software Item Description Item Range Default Value Name Set Flow Station Zero Calibration RPM1611 Sensor Zero The Sensor Zero item sets the signal from the Supply Pressure Flow Sensor that corresponds to a room pressure differential of 0 (neutral). None N/A Set Maximum Sensor Pressure Output RPM1611 Set Minimum Sensor Voltage Output RPM1611 Set Maximum Sensor Voltage Output RPM1611 Flow Station Low Calibration RPM1611 Sensor Max Signal Min Signal Max The Sensor Max item sets the maximum reading when you measure supply airflow with a flow station and pressure transducer. For example, if the pressure transducer has a range of 0 to in. W.C. (0 to Pa), set the Sensor Max to in. W.C. (+62.5 Pa). The Signal Min item sets the minimum output signal when you measure supply airflow with a flow station and pressure transducer. The Signal Max item sets the maximum output signal when you measure supply airflow with a flow station and pressure transducer. None None 10 V N/A N/A 0 to 1.00 in. W.C in. W.C. 0to10V 1to10V Low Cal The Low Cal menu item enters the Low Cal Submenu. See Flow Calibration on page 49 0 V 10 V 33

34 Table 16: Input3 Config Menu - Sup Pres Flow (Part 2 of 3) Menu Item Flow Station High Calibration RPM1611 Reset Calibration RPM1611 Set Flow Station Duct Area RPM1611 Software Item Description Item Range Default Value Name High Cal The High Cal menu item enters the High Cal Submenu. See Flow Calibration on page 49 Reset Cal Duct Area The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Low Cal, High Cal and K-Factor factors for this sensor to defaults. Enter NO to cancel the reset. The Duct Area item programs the cross-sectional area of the duct where the flow station is mounted. The Duct Area is necessary to calculate the duct airflow because the flow station is used to measure duct velocity. Note: The RPM does not compute duct area. You must first calculate the area and enter that value into the RPM. Use the following equations to calculate the duct area in ft 2 or m 2. Round Duct Area (ft 2 ) = Rectangular [ 2 Duct Area (ft ) = duct diameter (in.) 3.14 *[ ] width (in.) * height (in.)] Round Duct 2 Area (m ) = Rectangular 2 Duct Area (m ) = duct diameter (mm) 3.14 *[ ] 2 1,000 width (mm) * height (mm) [ ] 1,000 IMPORTANT: Entering an incorrect value for Duct Area results in an inaccurate flow measurement. It also results in inaccurate measurements for all information based on the flow measurement, such as the flow alarms. 2 None 0 to ft 2 (0 to m 2 ) N/A 0.00 ft 2 ( m 2 ) 34

35 Table 16: Input3 Config Menu - Sup Pres Flow (Part 3 of 3) Menu Item Software Item Description Item Range Default Value Name Set Flow K-Factor Adjustment RPM1611 K-Factor The K-Factor menu item sets the K-factor for the flow signal. The K-factor is a multiplier that you set to ensure that the airflow measured by the RPM matches the airflow measured by a known-good reference measurement, such as a pitot tube traverse to Measure the Actual flow value using a known-good reference measurement. 2. The Flow signal value is the measured flow value from an airflow sensor connected to the RPM. 3. Use the equation to calculate the K-factor. Balance Flow RPM1611 Balance Flow K-factor = Actual flow value Flow signal value Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable. Flow Setpoint: 0 to 30,000 CFM Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K-factor here to match the monitor's measurement with the reference measurement. K-Factor: 0.01 to K-Factor: 1.00 Table 17: Input 3 Config Menu - TA Sensor Menu (Part 1 of 2) Menu Item Software Item Description Item Range Default Value Name Set Sensor Zero Calibration Sensor Zero The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). None Unit is factory calibrated and should not need adjustment. Set Sensor Span Calibration Sensor Span The Sensor Span item matches or calibrates the TA sensor to the average room pressure velocity as measured by a portable air velocity meter. None Unit is factory calibrated and should not need adjustment. 35

36 Table 17: Input 3 Config Menu - TA Sensor Menu (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Set Sensor Elevation Elevation The Elevation item enters the elevation of the TA sensor above sea level. The pressure value requires correction due to changes in air density when you use the RPM at different elevations. Note: The density adjustments are in 1,000 foot increments, even though this number can be entered in increments of 1 foot. For example, the monitor interprets Elevation settings between 0 and 999 feet as 0 feet, settings between 1000 and 1999 feet as 1000 feet, and so on. 0 to 10,000 feet above sea level 0 Reset Calibration Check Sensor Status Reset Cal Check Status The Reset Cal item returns the RPM to the factory-default calibration, undoing field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Are You Sure. Enter YES to reset the Sensor Zero, Sensor Span and Elevation items to defaults. Enter NO to cancel the reset. The Check Status item checks the communication status of the sensor. After you tap the button, the RPM responds with: COMM ERROR - RPM cannot communicate with TA sensor. Check all wiring and the pressure sensor address. SENS ERROR - Physical damage to TA sensor circuitry. Unit is not fieldrepairable. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. CAL ERROR - Calibration data lost. Contact the Johnson Controls Product Sales group for assistance in initiating the RMA and return of product. DATA ERROR - Problem with TA sensor EEPROM, field calibration or analog output. Check all data configured and confirm unit is functioning correctly. Table 18: Input 3 Config Menu - Press Trans Menu (Part 1 of 2) Menu Item Software Item Description Item Range Default Value Name Set Minimum Sensor Pressure Output Sensor Min The Sensor Min item sets the minimum reading of a DPT that measures room pressure differential. For example, if the DPT has a range of to in. W.C. (-62.5 to Pa), set the Sensor Min to in. W.C. (-62.5 Pa) to in. W.C. 0 Set Maximum Sensor Pressure Output Sensor Max The Sensor Max item sets the maximum reading of the DPT that measures room pressure differential. For example, if the DPT has a range of to in. W.C. (-62.5 to Pa), set the Sensor Max to in. W.C. (+62.5 Pa). None None to in. W.C. N/A N/A 0 36

37 Table 18: Input 3 Config Menu - Press Trans Menu (Part 2 of 2) Menu Item Software Item Description Item Range Default Value Name Set Minimum Sensor Voltage Output Signal Min The Signal Min item sets the minimum output signal when you use a DPT to measure room pressure differential. 0to5V 0V Set Maximum Sensor Voltage Output Set Sensor Zero Calibration Reset Calibration Signal Max Sensor Zero Reset Cal The Signal Max item sets the maximum output signal when you use a DPT to measure room pressure differential. The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the monitor prompts you to verify that you want to do this by displaying the message Are You Sure? Enter YES to reset the Sensor Zero factor for this DPT to defaults. Enter NO to cancel the reset. 1to10V Table 19: Input3 Config Menu - Sup Lin Flow (Part 1 of 3) Menu Item Software Name Item Description Item Range Default Value Set Minimum Sensor Voltage Output RPM1611 Set Maximum Sensor Voltage Output RPM1611 Set Maximum Sensor Output RPM1611 Signal Min Signal Max Sensor Max The Signal Min item sets the minimum output signal when a flow station and pressure transducer are used to measure supply airflow. The Signal Max item sets the maximum output signal when a flow station and pressure transducer are used to supply airflow. The Sensor Max item sets the maximum reading of a flow station used to measure supply airflow. The Sensor Max item has increments of 1,000 fpm. None None 0to10V 10V N/A N/A 0 V 1 to 10 V 10 V 0 to 10,000 fpm 0 37

38 Table 19: Input3 Config Menu - Sup Lin Flow (Part 2 of 3) Menu Item Software Name Item Description Item Range Default Value Set Flow Station Duct Area RPM1611 Set Flow K-Factor Adjustment RPM1611 Duct Area K-Factor The Duct Area item programs the cross-sectional area of the duct where the flow station is mounted. The Duct Area is necessary to calculate the duct airflow because the flow station is used to measure duct velocity. Note: The RPM does not compute duct area. You must first calculate the area and enter that value into the RPM. Use the following equations to calculate the duct area in ft 2 or m 2. Round Duct Area (ft 2 ) = Rectangular [ 2 Duct Area (ft ) = duct diameter (in.) 3.14 *[ ] width (in.) * height (in.)] Round Duct 2 Area (m ) = IMPORTANT: Entering an incorrect value for Duct Area results in an inaccurate flow measurement. It also results in inaccurate measurements for all information based on the flow measurement, such as the flow alarms. The K-Factor menu item sets the K-factor for the flow signal. The K-factor is a multiplier that you set to ensure that the airflow measured by the RPM matches the airflow measured by a known-good reference measurement, such as a pitot tube traverse. 1. Measure the Actual flow value using a known-good reference measurement. 2. The Flow signal value is the measured flow value from an airflow sensor connected to the RPM. 3. Use the equation to calculate the K-factor. K-factor = Rectangular 2 Duct Area (m ) = Actual flow value Flow signal value duct diameter (mm) 3.14 *[ ] 2 1,000 width (mm) * height (mm) [ ] 1,000 Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. 2 0 to ft 2 (0 to m 2 ) 0.00 ft to ( m 2 ) 38

39 Table 19: Input3 Config Menu - Sup Lin Flow (Part 3 of 3) Menu Item Software Name Item Description Item Range Default Value Balance Flow RPM1611 Balance Flow The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable. Flow Setpoint: 0 to 30,000 CFM Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K-factor here to match the monitor's measurement with the reference measurement. The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the K-Factor factor for this sensor to defaults. Enter NO to cancel the reset. K-Factor: 0.01 to K-Factor: 1.00 Reset Calibration RPM1611 Reset Cal None N/A Table 20: Input3 Config Menu-Sup Venturi (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Minimum Flow RPM1611 Maximum Flow RPM1611 Min Flow Max Flow The Min Flow item sets the flow rate through the Venturi valve when it is fully closed. The display indicates a volumetric flow rate. Adjust the displayed value to match the flow through the Venturi valve. Note: Obtain the flow information from the label on the Venturi valve or by closing the Venturi valve using the Flow Control item in the DIAGNOSTICS menu and performing a pitot tube traverse of the duct. Note: You must complete the Min Flow menu item before moving on to the Max Flow menu item. The Max Flow item sets the flow rate through the Venturi valve when it is fully open. The display indicates a volumetric flow rate. Adjust the displayed value to match the flow through the Venturi valve. Note: Obtain the flow information from the label on the Venturi valve or by closing the Venturi valve using the Flow Control item in the DIAGNOSTICS menu and performing a pitot tube traverse of the duct. Note: You must complete the Min Flow menu item before moving on to the Max Flow menu item. 0 to 10,000 cfm 0 cfm 0 to 10,000 cfm 0 cfm 39

40 Table 20: Input3 Config Menu-Sup Venturi (Part 2 of 2) Menu Item Software Name Item Description Item Range Default Value Set Flow K-Factor Adjustment RPM1611 Reset Calibration RPM1611 Balance Flow RPM1611 K-Factor Reset Cal Balance Flow The K-Factor menu item sets the K-factor for the flow signal. The K-factor is a multiplier that you set to ensure that the airflow measured by the RPM matches the airflow measured by a known-good reference measurement, such as a pitot tube traverse. 1. Measure the Actual flow value using a known-good reference measurement. 2. The Flow signal value is the measured flow value from an airflow sensor connected to the RPM. 3. Use the equation to calculate the K-factor. K-factor = Actual flow value Flow signal value Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the K-Factor factor for this sensor to defaults. Enter NO to cancel the reset. The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable to None Flow Setpoint: 0 to 30,000 CFM N/A Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K- factor here to match the monitor's measurement with the reference measurement. K-Factor: 0.01 to K-Factor: 1.00 Table 21: Input3 Config Menu-Supply Switch Menu Item Software Name Item Description Item Range Default Value Low Flow Alarm Signal RPM1611 Low Flow Sig The Low Flow Sig item sets the signal the RPM1600 Series Monitor receives from a flow-proving switch to indicate a low supply flow condition. Open, Closed Table 22: Input4 Config Menu-Rm1 Dr Sw Menu Item Software Name Item Description Item Range Default Value Signal to Indicate Open Door Dr Open Sig The Dr Open Sig item sets the signal that the RPM1600 Series Monitor receives to indicate a door is open. Open, Closed Closed Closed 40

41 Table 23: Input4 Config Menu-Rm1 Occ Sen Menu Item Software Name Item Description Item Range Default Value Room Unoccupied Signal Unocc Sig The Unocc Sig item sets the signal that indicates the room is unoccupied. Open, Closed Table 24: Input5 Config Menu-Rm1 Key Switch Item Description The RPM1600 Series Monitor displays a message Nothing to Configure when Input 5 is set to Rm1 Key Switch and you enter the Input5 Config menu. Table 25: Input5 Config Menu-Relative Humidity Sensor (RH) Menu Item Software Name Item Description Item Range Default Value Set Minimum Sensor Output Sensor Min The Sensor Min item sets the minimum reading of the relative humidity sensor. 0 to 100 % RH 0 % RH Set Maximum Sensor Output Set Minimum Sensor Voltage Output Set Maximum Sensor Voltage Output Adjust Sensor Calibration Reset Calibration Closed Sensor Max The Sensor Max item sets the maximum reading of the relative humidity sensor. 0 to 100 % RH 100 % RH Signal Min Signal Max Sensor Span Reset Cal The Signal Min item sets the minimum output signal of the relative humidity sensor. The Signal Max item sets the maximum output signal of the relative humidity sensor. The Sensor Span item adjusts the calibration of the relative humidity sensor. The Sensor Span is an offset adjustment and can only be adjusted by ±10% RH. The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Sensor Span factor for this sensor to defaults. Enter NO to cancel the reset. 0 to 10 V 0 V 1 to 10 V 10 V -10 to +10 % RH 0 % RH Table 26: Input6 Config Menu-Rm1 Temp (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Adjust Sensor Calibration Sensor Span The Sensor Span item adjusts the calibration of the temperature sensor. -10 to +10 F 0 F None N/A 41

42 Table 26: Input6 Config Menu-Rm1 Temp (Part 2 of 2) Menu Item Software Name Item Description Item Range Default Value Reset Calibration Reset Cal The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Sensor Span factor for this sensor to defaults. Enter NO to cancel the reset. Table 27: Input6 Config Menu-Rm2 Occ Sen Menu Item Software Name Item Description Item Range Default Value Signal to Indicate Room Unoccupied Unocc Sig The Unocc Sig item sets the signal that indicates the room is unoccupied. Open, Closed Closed Table 28: Input6 Config Menu-Rm2 Dr Sw Menu Item Software Name Item Description Item Range Default Value Signal to Indicate Open Door Dr Open Sig The Dr Open Sig item sets the signal the RPM receives to indicate a door is open. Open, Closed Closed None N/A 42

43 Table 29: Input7 Config Menu-Exh Pres Flow (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Set Flow Station Zero Calibration Set Maximum Sensor Pressure Output Set Minimum Sensor Voltage Output Set Maximum Sensor Voltage Output Flow Station Low Calibration Flow Station High Calibration Reset Calibration Sensor Zero Sensor Max Signal Min Signal Max The Sensor Zero item sets the signal from the TA sensor that corresponds to a room pressure differential of 0 (neutral). The Sensor Max item sets the maximum reading of a flow station and pressure transducer used to measure exhaust airflow. For example, if the pressure transducer has a range of 0 to in. W.C. (0 to Pa), set the Sensor Max to in. W.C. (+62.5 Pa). The Signal Min item sets the minimum output signal when you measure exhaust flow with a flow station and pressure transducer. The Signal Max item sets the maximum output signal when you measure exhaust flow with a flow station and pressure transducer. None N/A 0 to in. W.C in. W.C. 0 to 10 V 0 V 1 to 10 V 10 V Low Cal The Low Cal menu item enters the Low Cal Submenu. See Flow Calibration on page 49 High Cal The High Cal menu item enters the High Cal Submenu. See Flow Calibration on page 49 Reset Cal The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the Low Cal, High Cal and K-Factor factors for this sensor to defaults. Enter NO to cancel the reset. None N/A N/A N/A 43

44 Table 29: Input7 Config Menu-Exh Pres Flow (Part 2 of 2) Menu Item Software Name Item Description Item Range Default Value Set Flow Station Duct Area Set Flow K-Factor Adjustment Balance Flow Duct Area K-Factor Balance Flow The Duct Area item programs the cross-sectional area of the duct where the flow station is mounted. The Duct Area is necessary to calculate the duct airflow because the flow station is used to measure duct velocity. Note: The RPM does not compute duct area. You must first calculate the area and enter that value into the RPM. Use the following equations to calculate the duct area in ft 2 or m 2. Round Duct Area (ft 2 ) = Rectangular [ 2 Duct Area (ft ) = duct diameter (in.) 3.14 *[ ] width (in.) * height (in.)] IMPORTANT: Entering an incorrect value for Duct Area results in an inaccurate flow measurement. It also results in inaccurate measurements for all information based on the flow measurement, such as the flow alarms. The K-Factor menu item sets the K-factor for the flow signal. The K-factor is a multiplier that you set to ensure that the airflow measured by the RPM matches the airflow measured by a known-good reference measurement, such as a pitot tube traverse. 1. Measure the Actual flow value using a known-good reference measurement. 2. The Flow signal value is the measured flow value from an airflow sensor connected to the RPM. 3. Use the equation to calculate the K-factor. K-factor = Round Duct 2 Area (m ) = Rectangular 2 Duct Area (m ) = Actual flow value Flow signal value duct diameter (mm) 3.14 *[ ] 2 1,000 width (mm) * height (mm) [ ] 1,000 Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable. 2 0 to ft 2 (0 to m 2 ) 0.01 to Flow Setpoint: 0 to 30,000 CFM 0.00 ft 2 ( m 2 ) Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K-factor here to match the monitor's measurement with the reference measurement. K-Factor: 0.01 to K-Factor:

45 Table 30: Input7 Config Menu-Exh Lin Flow (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Set Minimum Sensor Voltage Output Set Maximum Sensor Voltage Output Set Maximum Sensor Output Set Flow Station Duct Area Signal Min Signal Max Sensor Max Duct Area The Signal Min item sets the minimum output signal when you use a flow station and pressure transducer to measure exhaust airflow. The Signal Max item sets the maximum output signal when you use a flow station and pressure transducer to measure exhaust airflow. The Sensor Max item sets the maximum reading of a flow station that is used to measure exhaust airflow. Note: The Sensor Max item has increments of 1,000 fpm. The Duct Area item is used to program the cross sectional area of the duct where the flow station is mounted. Since the flow station is used to measure duct velocity, the Duct Area is necessary to calculate the duct airflow. Note: The RPM does not compute duct area. The area must be first calculated and then entered into the unit. Use the following equations to calculate the duct area. Use the following equations to calculate the duct area in ft 2 or m 2. Round Duct Area (ft 2 ) = Rectangular [ 2 Duct Area (ft ) = duct diameter (in.) 3.14 *[ ] width (in.) * height (in.)] Round Duct 2 Area (m ) = Rectangular 2 Duct Area (m ) = duct diameter (mm) 3.14 *[ ] 2 1,000 width (mm) * height (mm) [ ] 1,000 IMPORTANT: Entering an incorrect value for Duct Area results in an inaccurate flow measurement. It also results in inaccurate measurements for all information based on the flow measurement, such as the flow alarms. 2 0 to 10 V 0 V 1 to 10 V 10 V 0 to 10,000 fpm 0 0 to ft 2 (0 to m 2 ) 0.00 ft 2 ( m 2 ) 45

46 Table 30: Input7 Config Menu-Exh Lin Flow (Part 2 of 2) Menu Item Software Name Item Description Item Range Default Value Set Flow K-Factor Adjustment Balance Flow K-Factor Balance Flow The K-Factor menu item sets the K-factor for the flow signal. The K-factor is a multiplier that you set to ensure that the airflow measured by the RPM matches the airflow measured by a known-good reference measurement, such as a pitot tube traverse. 1. Measure the Actual flow value using a known-good reference measurement. 2. The Flow signal value is the measured flow value from an airflow sensor connected to the RPM. 3. Use the equation to calculate the K-factor. K-factor = Actual flow value Flow signal value Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable to Flow Setpoint: 0 to 30,000 CFM Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K-factor here to match the monitor's measurement with the reference measurement. The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the K-Factor factor for this sensor to defaults. Enter NO to cancel the reset. K-Factor: 0.01 to K-Factor: 1.00 Reset Calibration Reset Cal None N/A Table 31: Input7 Config Menu-Exh Venturi (Part 1 of 2) Menu Item Software Name Item Description Item Range Default Value Minimum Flow Min Flow The Min Flow item sets the flow rate through the Venturi valve when it is fully closed. The display indicates a volumetric flow rate. Adjust the displayed value to match the flow through the Venturi valve. Note: Obtain the flow information from the label on the Venturi valve or by closing the Venturi valve using the Flow Control item in the DIAGNOSTICS menu and performing a pitot tube traverse of the duct. Note: You must complete the Min Flow menu item before moving on to the Max Flow menu item. 0 to 10,000 cfm 0 cfm 46

47 Table 31: Input7 Config Menu-Exh Venturi (Part 2 of 2) Menu Item Software Name Item Description Item Range Default Value Maximum Flow Set Flow K-Factor Adjustment Reset Calibration Balance Flow Max Flow K-Factor Reset Cal Balance Flow The Max Flow item sets the flow rate through the Venturi valve when it is fully open. The display indicates a volumetric flow rate. Adjust the displayed value to match the flow through the Venturi valve. Note: Obtain the flow information from the label on the Venturi valve or by closing the Venturi valve using the Flow Control item in the DIAGNOSTICS menu and performing a pitot tube traverse of the duct. Note: You must complete the Min Flow menu item before moving on to the Max Flow menu item. The K-Factor menu item sets the K factor for the flow signal. The RPM multiplies the flow signal by the K-Factor so that the flow measurement matches the actual flow, as determined with a pitot tube traverse or other reference measurement. Note: K-Factor modifies the entire range of the calibrated flow, not just a single point. The Reset Cal item returns the RPM to the factory-default calibration, undoing any field calibration adjustments. When you enter this menu item, the RPM prompts you to verify that you want to do this by displaying the message Reset Settings to Factory Default? Enter YES to reset the K-Factor factor for this sensor to defaults. Enter NO to cancel the reset. The Balance Flow submenu shows information for setting up the RPM and calibrating the flow. Only the Flow Setpoint and the K-factor are configurable. 0 to 10,000 cfm 0 cfm 0.01 to None Flow Setpoint: 0 to 30,000 CFM N/A Flow Setpoint: 0 CFM Note: Make a reference measurement of the flow and then adjust the K-factor here to match the monitor's measurement with the reference measurement. K-Factor: 0.01 to K-Factor: 1.00 Table 32: Input7 Config Menu - Exhaust Switch Menu Item Software Name Item Description Item Range Default Value Low Flow Alarm Signal Low Flow Sig The Low Flow Sig item sets the signal that the RPM1600 Room Pressure Monitor receives to indicate a low exhaust flow condition. Open, Closed Table 33: Input7 Config Menu - Room 2 Key Switch Item Description The Monitor displays the message Nothing to Configure when Input 7 is set to Room 2 Key Switch and the user enters the Input7 Config menu. Closed 47

48 Calibration The calibration section explains how to calibrate the RPM1600 Series Monitor and how to zero a flow station pressure transducer (optional). A warning message appears if the RPM1600 Series Monitor has not been calibrated. Note: This section assumes that the appropriate sensor has been correctly installed. Inaccurate readings may be detected if a sensor is not installed correctly. Review the Installation Instructions and verify that the sensor is installed correctly (this is usually only a problem on initial setup). Reference measurements from a capture hood are required to calibrate the monitors. IMPORTANT: The RPM1600 monitor is disabled during calibration. Alarms do not function to warn of unsafe conditions. To begin the calibration process, enter the appropriate INPUT# CONFIGURE menu (see Configuration on page 9 if not familiar with keystroke procedure). Room Pressure Calibration You can measure room pressure by using either a thermal anemometer (TA) sensor or a differential pressure transducer (DPT). Calibrating to the TA Sensor Note: The TA sensor is calibrated at the factory and does not normally need adjustment when installed. 1. Select SENSOR SPAN item. (See Table 12 on page 30, Table 14 on page 31, Table 25 on page 41, or Table 26 on page 41.) 2. Position a thermal anemometer (or other instrument configured to measure air velocity) in the door opening to obtain a velocity reading. Take a measurement of the air velocity entering or exiting the door. 3. Input the reference measurement from Step 2 into the monitor. 4. Save the reading and exit the menu system. Calibrating to the Differential Pressure Transducer Note: This calibration process configures the monitor to match the reading from the DPT. If the DPT itself needs to be calibrated, refer to the instructions that come with the DPT. 1. Write down the output signal range and pressure range of the DPT. As an example for these instructions, assume the DPT has an output signal range of 0 to 10V and a pressure range of to in. W.C. 2. Select the SENSOR MIN item and enter the minimum pressure range of the DPT. In this example, enter in. W.C. 3. Select the SENSOR MAX item and enter the maximum pressure range of the DPT. In this example, enter in. W.C. 4. Select the SIGNAL MIN item and enter the minimum output signal of the DPT. In this example, enter 0 V. 5. Select the SIGNAL MAX item and enter the maximum output signal of the DPT. In this example, enter 10 V. 6. To zero the DPT: a. Mark the high pressure tubing going to the high port of the DPT. b. Remove the tubing from the high and low ports of the DPT. c. Enter the SENSOR ZERO item on the controller. 48

49 d. Reconnect tubing to the high and low ports of the DPT, using the mark to connect the high pressure tubing to the high port. Flow Calibration Flow can be measured using a one of the following options: airflow measuring station with differential pressure transducer linear electronic airflow measuring station Venturi valve with feedback. Airflow Measuring Station with Differential Pressure Transducer Calibration Note: Flow stations are optional and may not be installed in your system. 1. Set DUCT AREA item to the duct area where the flow is measured. 2. Zero the flow station: a. Mark the high pressure tubing going to the high port of the DPT. b. Remove the tubing from the high and low ports of the DPT. c. Enter the Sensor Zero item on the monitor. d. Reconnect the tubing to the high and low ports of the DPT, using the mark to connect the high pressure tubing to the high port. 3. Enter the LOW CAL menu to perform the low flow calibration related to the following items: VOLTAGE INPUT: Current voltage from DPT UNCALIBRATED FLOW: Current flow rate ZERO VOLTAGE: Voltage from DPT output from Step 2 CALIBRATED FLOW: Input actual flow as measured with reference instrument here a. Adjust the flow to its minimum volume. Observe the VOLTAGE INPUT displayed on the screen, or use a voltmeter to read the voltage at the pressure input terminals on the back of the monitor. b. Slowly increase the flow until the VOLTAGE INPUT (DPT output) shows the first noticeable increase in voltage from the minimum flow. A general rule-of-thumb is that the voltage change should occur with the damper between 10% to 30% open. c. For reference only, the UNCALIBRATED FLOW item displays the default measured flow based on the current settings of the flow station (for example, duct area). d. Determine the actual flow with a duct traverse or other reference measurement. e. Enter the actual flow measurement under the CALIBRATED FLOW menu item. f. Press the Save key to save the flow data. The low flow calibration is complete. 4. Enter the HIGH CAL menu to perform the high flow calibration related to the following items: VOLTAGE INPUT: Current voltage from pressure transducer UNCALIBRATED FLOW: Current flow rate ZERO VOLTAGE: Voltage from DPT output from Step 2 CALIBRATED FLOW: Input actual flow as measured with reference instrument here a. Adjust the flow to its maximum volume. Observe the VOLTAGE INPUT displayed on the screen, or use a voltmeter to read the voltage at the pressure input terminals on the back of the controller. 49

50 b. Slowly decrease the flow until the VOLTAGE INPUT (DPT output) shows the first noticeable decrease in voltage from the minimum flow. c. For reference only, the UNCALIBRATED FLOW item displays the default measured flow based on the current settings of the flow station (for example, duct area). d. Determine the actual flow with a duct traverse or other reference measurement. e. Enter the actual flow measurement under the CALIBRATED FLOW menu item. f. Press the Save key to save the flow data. The high flow calibration is complete. Note: Use Balance Flow to verify flow station calibration and adjust the K-FACTOR. Linear Electronic Airflow Measuring Station Calibration Note: Flow stations are optional and may not be installed in your system. 1. Set DUCT AREA to the duct area at the linear flow station location. 2. Set SENSOR MAX to match the upper limit of the velocity that the sensor on the linear flow station can measure. 3. Set SIGNAL MIN to match the minimum voltage output (0 to 10 V) of the linear flow station (typically 0 V). 4. Set SIGNAL MAX to match the maximum voltage output (0 to 10 V) of the linear flow station (typically 10 V). 5. Exit the menu. Note: Use Balance Flow to verify flow station calibration and adjust the K-FACTOR. Venturi Valve with Feedback Calibration Note: Linear Output Module (LOM) Venturi Valves are optional and may not be installed in your system. 1. Obtain the Venturi valve minimum and maximum flow, either by reading the label on the Venturi valve or by performing duct traverses when the Venturi valve is fully closed and fully opened. 2. Set MIN FLOW to the minimum Venturi valve flow. 3. Set MAX FLOW to the maximum Venturi valve flow. 4. Exit the menu. Note: Use Balance Flow to verify Venturi with Feedback calibration and adjust the K-FACTOR. Supply/Exhaust Switch Calibration Note: Flow switches are optional and may not be installed in your system. Flow switches do not actually measure the flow, but are designed to provide an open or closed signal to indicate the presence or absence of flow. Set the LOW FLOW SIG to match the low flow indication from the switch. OPEN means the switch opens to indicate low flow. CLOSED means the switch closes to indicate low flow. 50

51 Door Switch Configuration Note: Door switches are optional and may not be installed in your system. Set the DR OPEN SIGN to match the door open indication from the switch. OPEN means the switch opens to indicate the door is open. CLOSED means the switch closes to indicate the door is open. Temperature Sensor Configuration Note: Temperature sensors are optional. Only 1000 ohm Platinum RTD elements are supported by this device. After you connect the 1000 ohm Platinum RTD element to the RPM1600 Series Monitor, you must use an accurate temperature device as a temperature reference when you calibrate the 1000 ohm Platinum RTD. Use the RPM menu system to access the specific input to which the 1000 ohm Platinum RTD is connected. Adjust the SENSOR SPAN so the displayed temperature matches the reference temperature measurement. This applies a slight offset to the unit s temperature reading, which compensates for any error in the temperature reading of the platinum element. If you need to reset the SENSOR SPAN back to the factory default, use the RESET CAL function. Relative Humidity Sensor Configuration Note: Relative Humidity sensors are optional and may not be installed in your system. 1. Set the SENSOR MIN to the minimum reading of the relative humidity sensor. This is usually 0%. 2. Set the SENSOR MAX to the maximum reading of the relative humidity sensor. This is usually 100%. 3. Set the SIGNAL MAX to the minimum output voltage of the relative humidity sensor. This is usually 0 V. 4. Set the SIGNAL MAX to the maximum output voltage of the relative humidity sensor. This is usually 10 V. 5. Adjust the SENSOR SPAN so the displayed relative humidity matches a reference measurement. Use the RESET CAL item to reset the SENSOR SPAN back to the factory default. Occupancy Sensor Configuration Note: Occupancy switches are optional and may not be installed in your system. Set the UNOCC SIG to match the occupancy indication from the switch. OPEN means the switch opens to indicate the room is unoccupied. CLOSED means the switch closes to indicate the room is unoccupied. 51

52 Maintenance and Repair Parts The RPM1600 Series Room Pressure Monitors require minimal maintenance. Periodically inspect the system components and clean the pressure sensors to ensure that the monitor is operating properly. System Component Inspection Periodically inspect the differential pressure transducer (DPT) or the Thermal Anemometer (TA) sensor for accumulation of contaminants. The frequency of these inspections depends upon the quality of the air being drawn across the sensor. If the air is dirty, the sensors require more frequent inspection and cleaning. Slide open the cover (Figure 26) and visually inspect the TA sensor. The airflow orifice should be free of obstructions. The small ceramic-coated sensors (not shown) protruding from the orifice wall should be white and free of accumulated debris. Figure 26: TA Sensor Orientation (Left) and Dimensions (Right) Proper Orientation On Wall Pressure Sensor Base Dimensions 4-1/4 in. (108 mm) 3-1/4 in. (83 mm) 3-3/16 in. (82 mm) FIG:TAsen_ornttn 1 in. (25 mm) 2 in. (51 mm) Airflow Orifice Screw Sliding Cover Thermal Anemometer Sensor 7/8 in. (22 mm) Wire Hole 2-1/4 in. (57 mm) Tube Hole Periodically inspect the other system components for proper performance and physical signs of excessive wear. TA Sensor Cleaning Remove accumulations of dust or dirt with a dry soft-bristled brush (such as an artist's brush). If necessary, you can use water, alcohol, acetone, or trichlorethane as a solvent to remove other contaminants. Use extreme care when cleaning the velocity sensors. The ceramic sensor may break if you: apply excessive pressure scrape the sensor to remove contaminants allow the cleaning apparatus to abruptly impact the sensor IMPORTANT: Pressure Monitor. If you are using a liquid to clean the sensor, turn off power to the RPM1600 Series Room Do not use compressed air to clean the velocity sensors. Do not attempt to scrape contaminants from the velocity sensors. The velocity sensors are quite durable; however, scraping may cause mechanical damage and possibly break the sensor. Mechanical damage due to scraping voids the pressure sensor warranty. Display Screen Cleaning Remove accumulations of dust or dirt with a dry soft cloth. If necessary, use isopropyl or ethyl alcohol to remove other contaminants. 52

53 Replacement Parts All components of the Room Pressure Monitor system are field-replaceable. Contact Johnson Controls or your nearest Johnson Controls Manufacturer's Representative for replacement part pricing and delivery. Table 34: Remote Pressure Monitors 1 Product Code Number LB-RPM LB--0 Description 1. You must also order an input device. See Table 35. Table 35: Input Devices RPM1611 Room Pressure Monitor (monitors one room) Room Pressure Monitor (monitors one or two rooms with anteroom) Product Code Number Description You can use with RPM1611 DPT2651-0R1B-MA Differential Pressure Transducer (DPT) 1 Y Y LB-ACC101-0 Differential Pressure Transducer Pickups Y Y LB-ACC100-0 Thermal Anemometer (TA) Sensor 1 Y Y TE-67PT-0N00 Platinum Temperature Sensor N Y HE-68P2-0N00WS Combination Humidity and Temperature Sensor N Y TE-68PT-0N00S, NS-WALLPLATE-0 Wall Temperature Sensor with Wallplate N Y TE-635GM-1 Duct Temperature Sensor, Platinum 1K ohm, 4 in. probe N Y TE-6351M-1 Duct Temperature Sensor, Platinum 1K ohm, 8 in. probe N Y HT N00W Humidity Sensor N Y MS-BACEOL-0 End of Line Terminator OLS Occupancy Switch N Y 1. You can use either a DPT or a TA sensor as the pressure input. 53

54 Troubleshooting The RPM1600 Series Room Pressure Monitors are designed to be trouble-free; however, installation errors or interaction with other HVAC components may cause system problems. The system is easy to troubleshoot if you use an organized approach to evaluate the system. Troubleshooting is broken down into hardware (mechanical) and software problems. Hardware problems include wiring problems, incorrectly installed equipment, and add-ons or non-johnson Controls equipment. Software problems include control problems, configuration problems, or interaction problems with the HVAC system. The hardware test determines if all Johnson Controls mechanical components are functioning correctly. The hardware test accesses the diagnostics menu items. If you are unfamiliar with the controller menus, see Configuration on page 9 for the keystroke procedure. You can quickly resolve the majority of problems if you troubleshoot the hardware first. Consider disconnecting any non-johnson Controls components before you begin troubleshooting the hardware. Complete the procedures in Hardware Troubleshooting to confirm that all Johnson Controls hardware is operating correctly. If these procedures do not resolve the problem, see Hardware and Software Troubleshooting on page 57. Select the problem that most closely resembles your problem, review the possible symptoms, and perform any required corrective action. Note: Separating Johnson Controls system problems from the laboratory HVAC system can be difficult. Software or system performance problems can be affected by (and can affect) the supply air system, exhaust air system, or physical configuration of the room. Hardware Troubleshooting Perform these three steps to determine that all hardware is functioning correctly: 1. Confirm correct wiring. 2. Confirm correct physical installation. 3. Verify mechanical components. Confirm Correct Wiring Closely check the wiring to verify that it exactly matches the wiring diagram. Wiring diagrams are located in Appendix C: Wiring Information on page 75 of this manual. Closely check the wiring associated with non-johnson Controls components for correct installation. Consider disconnecting any non-johnson Controls components before you begin troubleshooting the hardware. The most common problem with installed hardware is incorrect wiring. This problem may exist on initial installation, or it may occur when modifications to the system take place. Confirm Correct Physical Installation Verify the physical installation of the hardware components when you check the wiring. Review the installation instructions and verify that all of the components are correctly located and installed correctly. Verify Mechanical Components Use the tests in this section to verify that mechanical components connected to the RPM are operating correctly. Test the RPM s analog outputs and relay outputs first. Then use the Diagnostic menu to test each component (inputs and outputs). Note: These tests require power to the RPM and any connected devices, so if an RPM has no power, see Table 36 on page 57 to eliminate the power problem. 54

55 Test Analog Outputs Enter the Analog Outpt item in the Diagnostics menu to manually manipulate the analog outputs. Figure 27: Analog Outputs Screen in Diagnostics Menu Tap Output 1, Output 2, or Output 3 to manually set the output signal. Test Relay Outputs Enter the Relay Outputs item in the Diagnostics menu to manually manipulate the relay outputs. Figure 28: Relay Outputs Screen in Diagnostics Menu Tap Relay 1 Toggle or Relay 2 Toggle to manually open or close the relay. Test - View Inputs Enter the View Inputs item in the Diagnostics menu to view all inputs with real-time updates. Figure 29: View Inputs Screen in Diagnostics Menu 55

56 The LCD screen displays None for any inputs that have not been configured. Go to the Configure menu to configure these inputs appropriately. Test - View Outputs Enter the View Outputs item in the Diagnostics menu to view all output signals with real-time updates. Figure 30: View Outputs Screen in Diagnostics Menu The LCD screen displays None for any outputs that have not been configured. Go to the Alarm Configure menu and the Interface menu to configure these outputs appropriately. If the RPM1600 Series Room Pressure Monitor passes each of the tests, the mechanical parts of the system are functioning correctly. See Table 36 on page 57 for further troubleshooting information. 56

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20 PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644, REVISION J JULY 018 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644,

More information

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20 PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644, REVISION A JULY 01 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644,

More information

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20 PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644, REVISION F MAY 017 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644,

More information

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION C AUGUST 2015 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION

More information

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION G JULY 2018 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION

More information

PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC

PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC OPERATION AND SERVICE MANUAL P/N 1980243, REVISION J DECEMBER 2013 PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC OPERATION AND SERVICE

More information

PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM

PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM OPERATION AND SERVICE MANUAL P/N 1980242, REVISION G JUNE 2013 PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM OPERATION AND SERVICE MANUAL

More information

Critical Environments. Model FHC50/FHM10. Fume Hood Controller/Monitor. Operation and Service Manual. P/N , Revision B October 2010

Critical Environments. Model FHC50/FHM10. Fume Hood Controller/Monitor. Operation and Service Manual. P/N , Revision B October 2010 Critical Environments Model FHC50/FHM10 Fume Hood Controller/Monitor Operation and Service Manual P/N 6003830, Revision B October 2010 Model FHC50/FHM10 Fume Hood Controller/Monitor Operation and Service

More information

SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS BAC

SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS BAC SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS 8681 8681-BAC OPERATION AND SERVICE MANUAL P/N 1980476, REVISION E FEBRUARY 2013 SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS 8681 8681-BAC OPERATION AND SERVICE

More information

Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include:

Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include: Model Number: Product/System Title: 8630-PM-CRM Premium Clean Room Monitor Contents of this manual supplement include: 1) Sequence of operation 2) Menu structure drawing 3) Description of new software

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

SUREFLOW ROOM PRESSURE CONTROLLER MODELS BAC

SUREFLOW ROOM PRESSURE CONTROLLER MODELS BAC SUREFLOW ROOM PRESSURE CONTROLLER MODELS 8636 8636-BAC OPERATION AND SERVICE MANUAL P/N 1980441, REVISION H FEBRUARY 2013 SUREFLOW ROOM PRESSURE CONTROLLER MODELS 8636 8636-BAC OPERATION AND SERVICE MANUAL

More information

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include: Model Number: Product/System Title: 8635-ST Static Pressure Controller Contents of this manual supplement include: 1) Sequence of operation 2) Description of new software items 3) Deleted software menu

More information

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Critical Environments Model 8682KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Manual Supplement Contents of this manual supplement

More information

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin AD-1272 Code No. LIT-12012477 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of

More information

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106 Critical Environments TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106 Modbus communications are installed in all Model 8630 hospital room pressure controllers

More information

HVAC Controls Laboratory. Model EVERWATCH Face Velocity Monitor. Operation and Service Manual. P/N , Revision E October 2002

HVAC Controls Laboratory. Model EVERWATCH Face Velocity Monitor. Operation and Service Manual. P/N , Revision E October 2002 HVAC Controls Laboratory Model 8610 EVERWATCH Face Velocity Monitor Operation and Service Manual P/N 1980154, Revision E October 2002 Model 8610 EVERWATCH Face Velocity Monitor Operation and Service Manual

More information

Model SRCM Operation

Model SRCM Operation Model SRCM Operation 1 Contents OPERATION... 4 Condition Banner... 6 Condition Banner Touch Screen... 7 Operation... 7 Alarms Cause Condition Banner to Turn Red... 7 Condition Banner Functions... 7 Operating

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Ax60+ Multi-Gas. Service Manual

Ax60+ Multi-Gas. Service Manual Analox Limited 15 Ellerbeck Court, Stokesley Business Park, North Yorkshire, TS9 5PT, UK UK/RoW T: +44 (0)1642 711400 F: +44 (0)1642 713900 US T: (714) 891-4478 W: www.analox.net E: info@analox.net Copyright

More information

Siemens RDY2000BN. Start Up Guide

Siemens RDY2000BN. Start Up Guide Siemens RDY2000BN Start Up Guide Answers for infrastructure and cities. What this slide set is about This is a start up guide for the RDY2000BN BACnet Commercial Thermostat. This procedure show how to

More information

200i/KN2, KN4 Firmware Revision Sheet

200i/KN2, KN4 Firmware Revision Sheet 200i/KN2, KN4 Firmware Revision Sheet Revision 2.9 Special Release 1- November 2013 1. Added an external boiler Failsafe feature. The J6 Analog Output can be used to enable a SSR which can be used to enable

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528] Installation- & Operation manual [Dok. id: mi-303gb_180528] Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction and control output MF-PFA ver 3.x NOTE! Read through the entire manual

More information

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Manual# 1100334 User s Manual 200 Series DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Rev. March 2012 User's Manual for the Marine Pro 200 Series ~~~ DCU 210 Diesel Engine Control Unit DCU

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

Series RSM Room Status Monitor. Specifications - Installation and Operating Instructions 5-13/32 [137.16] 8 [203.20] 4-5/8 [117.

Series RSM Room Status Monitor. Specifications - Installation and Operating Instructions 5-13/32 [137.16] 8 [203.20] 4-5/8 [117. Series RSM Room Status Monitor Specifications - Installation and Operating Instructions Bulletin p-3-rsm 5-13/32 [137.16] 1-5/8 [41.66] 2-5/32 [55.12] 8 [203.20] 4-5/8 [117.09] TUBING HEADER PORT ROOM

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Description The TFHB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications.

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

Accuracy by Design Products for the HVAC Professional

Accuracy by Design Products for the HVAC Professional Accuracy by Design Products for the HVAC Professional Greystone Energy Systems Inc., is one of North America s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

EVERWATCH FACE VELOCITY MONITOR MODEL 8610

EVERWATCH FACE VELOCITY MONITOR MODEL 8610 EVERWATCH FACE VELOCITY MONITOR MODEL 8610 OPERATION AND SERVICE MANUAL P/N 1980154, REVISION H FEBRUARY 2013 EVERWATCH FACE VELOCITY MONITOR MODEL 8610 OPERATION AND SERVICE MANUAL P/N 1980154, REVISION

More information

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS TYPE C STANDARD & NIGHT SETBACK S Specifications and Owner s Manual PLASTEC VENTILATION, INC. TYPE C STANDARD & NIGHT SETBACK General Description BENEFITS Safety: air flow is maintained at required speed

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

SPM-4000-DC GUARDIAN INFINITY SPACE PRESSURIZATION MONITOR AND DUAL CONTROLLER

SPM-4000-DC GUARDIAN INFINITY SPACE PRESSURIZATION MONITOR AND DUAL CONTROLLER Technical Data Sheet SP-4000-DC GUARDIAN INFINITY PRESSURIZATION ONITOR AND DUAL CONTROLLER Description The Guardian Infinity is a true differential space pressure measurement system engineered to combine

More information

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670 Bulletin AV-670 Series 670 Hood Monitor Specifications - Installation and Operating Instructions DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Phone: 219/879-8000 Fax: 219/872-9057

More information

Multiview Monitor / Controller

Multiview Monitor / Controller FEATURES: Bright/sunlight readable 7.0 LCD touch screen. Displays large, easy to read values, set points, room status, modes and alarms Up to six fully configurable Icons including: Environmental points

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

BACnet SRCM User Manual

BACnet SRCM User Manual BACnet SRCM User Manual Building Technologies Division Copyright Notice Copyright Notice Notice Document information is subject to change without notice by Companies, names, and various data used in examples

More information

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3 Manual# 1100268 User s Manual DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3 Table of Content GENERAL INFORMATION... 3 ABOUT THIS MANUAL... 3 400 SERIES OVERVIEW... 3 Available Modules...

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

Installation & Calibration Guide

Installation & Calibration Guide Airflow Monitor AFA1000/2 MK3 Startup The AFA1000 must be field-calibrated once the room air supply and exhaust is balanced. When the unit is powered up, the following sequence of events occurs: 1. The

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A i.c³ User Guide For Helmer i.series Ultra-Low Freezers 360175-A/A Document History Revision Date CO Supersession Revision Description A 18 APR 2014* 9275 n/a Initial release. * Date submitted or change

More information

GLD-30 Gas Leak Detector

GLD-30 Gas Leak Detector GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

Software Version 2.01 LEVEL MONITOR MODEL 220

Software Version 2.01 LEVEL MONITOR MODEL 220 Software Version 2.01 LEVEL MONITOR MODEL 220 19 April 2000 CONTENTS 1. Introduction 1 1.1 Model Number Designation 2 1.2 Intrinsic Safety Considerations 3 2. Specification 4 3. Operation 6 3.1 Display

More information

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors Overview 2 This procedure shows how to replace VT8000 Room Controllers already installed, as

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

CRITICAL ENVIRONMENT MONITOR ALNOR AIRGARD 350 CEM

CRITICAL ENVIRONMENT MONITOR ALNOR AIRGARD 350 CEM CRITICAL ENVIRONMENT MONITOR ALNOR AIRGARD 350 CEM OWNER S MANUAL P/N 116159359, REV 06 SEPTEMBER 2014 LIMITATION OF WARRANTY AND LIABILITY (effective April 2014) (For country-specific terms and conditions

More information

Section 9 System Operation

Section 9 System Operation Section 9 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family NexSysLink CAN Instruments Product Family 2 CAN Display Operation Manual Contact Beede Beede Electrical Instrument Company, Inc. 88 Village Street Penacook, NH 03303 (603) 753-6362 Toll-free 800-451-8255

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Tri-Tech Medical Inc.

Tri-Tech Medical Inc. Submittal Data Sheet Project Information Project Number Approval Features The Tri-Tech Area and Master Alarm Panel digitally displays gas pressure (1 psi increments) monitors and displays normal and alarm

More information

CT224 Setup Tutorial

CT224 Setup Tutorial CT224 Setup Tutorial Table of Contents 1. Introduction 2. Configuring Controller for Operation A. Example 1 Over Temp Operation with Hysteresis @ 5º F. B. Example 2 Under Temp Operation with Hysteresis

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

End To End Optical Beam Smoke Detector. Additional Information

End To End Optical Beam Smoke Detector. Additional Information End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power. Technical Information Electric Slide-In Range JES9750BA* JES9860BA* Due to possibility of personal injury or property damage, always contact an authorized technician for servicing or repair of this unit.

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors)

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) Refrigerant Monitor User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

Med Touch Master Alarm

Med Touch Master Alarm Submittal Data Sheet Features The Powerex Med Touch Master Alarm Panel monitors and displays normal and alarm conditions from up to 128 remote medical gas source signals and provides alarm conditions as

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL

AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL M 890-00279 rev. 14 K 895-00004 rev. 00 Manufacturer: Viatron Electronics 5200, Armand-Frappier St-Hubert (Quebec) Canada J3Z 1G5 WARNINGS The warranty can be void

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Follett Performance Plus

Follett Performance Plus Follett Performance Plus touchscreen user guide The next level of control in undercounter refrigeration Controller Operation - Performance Plus touchscreen Use and care of the LCD Performance Plus touchscreen

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, mechanical, by photocopying, recording or in any other manner

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

TCA-9102 Series Surface Mount Temperature Controllers with High and Low Alarm

TCA-9102 Series Surface Mount Temperature Controllers with High and Low Alarm TCA-9102 Series Surface Mount Temperature Controllers with High and Low Alarm General Description & Applications The TCA-9102 Series Temperature Controller with Alarm offers a versatile solution for a

More information

EL-TSTAT-8820 Safety & Installation Instructions

EL-TSTAT-8820 Safety & Installation Instructions EL-TSTAT-8820 Safety & Installation Instructions TABLE OF CONTENTS WI-FI SETUP Wi-Fi Setup 2 INSTALLATION Installation location recommendations 3 Outdoor temperature sensor (included) 3 Remote temperature

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma Functional Safety Manual Deltapilot S FMB70 Level and Pressure Measurement with Output Signal 4...20 ma Application Use for process pressure measurement in aggressive and non-aggressive gases, vapours

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Pump-Down Controller MODEL 4052

Pump-Down Controller MODEL 4052 Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

CONTROL UNIT: REFERENCE MANUAL

CONTROL UNIT: REFERENCE MANUAL CONTROL UNIT: REFERENCE MANUAL 1 THE DISPLAY AND REVIEW SCREENS...3 1.1 The Single Bar-graph Display...4 1.2 The View Multiple Devices Display...5 1.2.1 Multiple Bar-graph Display...5 1.2.2 Multiple Device

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

EBC20. Instructions for fitting, installation and operation. Read and save these instructions! EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................

More information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B 2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS

More information

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL SAFETY WARNING Please Refer to the Safety Warning in Section 7.1 regarding the chemicals in the oxygen sensor Analox Sensor Technology

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information