The Effect of Large Orifice Sprinklers on High-Challenge Fires

Size: px
Start display at page:

Download "The Effect of Large Orifice Sprinklers on High-Challenge Fires"

Transcription

1 SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application of large orifice sprinklers to high-challenge fires. The information is intended as an overview of the performance and effect large orifice sprinklers have in comparison to traditional orifice sizes. This supplement is not intended to provide any specific design guidance. For specific application and design requirements, see NFPA 13 and the sprinkler manufacturer s listing materials. INTRODUCTION ft 2 ) wet adjacent sprinklers, even at lower pressures. Over With the completion of the FM test center in the late 1960s, the next years, the NFPA storage standards tried to combat the sprinkler industry had the opportunity to conduct more the skipping by limiting the spacing to no less than 80 ft 2. realistic tests. The test center was large enough to investigate With the advent of the large drop sprinkler in the 1970s and many fire test variables not previously understood in the ELO sprinkler (0.64 in. orifice) in the 1980s, a better smaller-scale testing. For warehouse-type storage, high densities method of achieving high densities was born. This generaprimarily (those greater than 0.35) were found to be necessary, tion of sprinklers largely eliminated the skipping problem. because of the storage of plastics. As the density Larger orifice sprinklers were then combined with other in- requirements increased up to 0.6 for certain high-challenge novations, such as more sensitive sprinklers (quickresponse) commodities, the use of 1 2 in. orifice and then in. orifice and deflector designs that helped optimize the use sprinklers required either higher pressures or closer spacing of existing water supplies. In most cases, the larger the sprinkler of the sprinklers. Both situations caused cold soldering or orifice was, the better the protection. Exhibit S2.1 shows skipping to occur during critical stages of the test fires. (For the pressure requirements for various-sized orifice sprinklers information on skipping, see A.12.6 of NFPA 13.) at various densities (all at 100 ft 2 sprinkler spacing). The high pressures created smaller droplets that were Each of the sprinkler K-factors identified in Exhibit more easily carried to adjacent sprinklers. Close spacing (50 S2.1 creates different combinations of droplet sizes ranging Bill Thomas, P.E., is executive vice president with TVA Fire and Life Safety Corporation in Chicago, IL. Bill Tomes is chairman of TVA Fire and Life Safety Corporation in Chicago, IL. 947

2 948 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Pressure (psi) Operating pressures Density (100 ft 2 ) EXHIBIT S2.1 Pressure Requirements for Various-Sized Orifice Sprinklers at Various Densities. K5.6 (¹ ₂ in.) K8.0 (¹⁷ ₃₂ in.) K11.0 (⁵ ₈ in.) K14.0 (0.7 in.) K17.0 (0.77 in.) K22.0 (0.87 in.) K25.0 (1.00 in.) from very small to large. The larger K-factors result in an increase in the subsequent downward water force created by the velocity and size of the droplet that more effectively penetrates through fire updrafts. This result is true even if the sprinklers are operating at the same pressures. Each of the manufacturers of a specific-size sprinkler has a different deflector, and each produces different combinations of small and large drop sprinklers throughout the pressure range of 7 psi (the minimum required by NFPA 13) to the upper limit of about 175 psi (normally only produced with fire pump installations). Large drops with acceleration downward create bigger forces to penetrate fire updrafts than small droplets but do little cooling above the storage commodity. Small drops do not normally penetrate the storage fire plume and can do some harm by being blown onto adjacent sprinklers, delaying or preventing their operation. Conversely, small drops are good for cooling the ceiling area, depositing drops on exposed structural steel and helping to keep it cool. TESTING PROCESS Listing/Approval Agencies At higher pressures (greater than 50 psi), more small droplets are created and less of the water reaches the top of storage and the burning commodity. The manufacturers, therefore, are presented with a dilemma how much acceleration and downward force to impart versus how many small droplets to produce. Two of the major approval and listing agencies (Factory Mutual and Underwriters Laboratories) have tried to answer that question by requiring each sprinkler to undergo rigorous testing, including full-scale tests of the standard plastic commodity at various storage heights and clearances. The clearance effect will vary depending on the pressure on the sprinklers. Research has consistently shown that for the older, smaller orifice sprinklers, high pressure (greater than about 50 psi) is good if the clearance is small (less than 5 ft), as more water is able to reach the top of the storage and the burning material below. However, high pressure is not as effective if the clearance is greater than about 5 ft, and becomes increasingly ineffective as the clearance increases. Testing has also shown that the large clearance concern has been lessened with the use of larger orifice sprinklers (0.64 and larger). Listing/approval agencies testing at various clearances has clearly demonstrated this. Ignition location in relation to ceiling sprinklers has also been shown by the listing agencies as necessary to show the sprinklers capability to control fires effectively when ignition occurs under one sprinkler, between two sprinklers, and between four sprinklers. As new commodities are stored and new storage arrangements are created, more large size testing will undoubtedly be needed to verify 2007 Automatic Sprinkler Systems Handbook

3 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires 949 the proper combinations of large drops, small drops, downward TABLE S2.2 Constant Density Test Comparisons force, and distribution. Sprinkler in. (K-8) 5 8 in. (K-11) Commodity Plastic Plastic Test Result Comparisons Arrangement Palletized Palletized Table S2.1 illustrates the effect changing K-factors has on Ceiling height 25 ft 25 ft a constant density fire test and the results of the fire test, Storage height 15 ft 15 ft including design pressure, steel peak temperature, sprin- Ignition location 4 4 klers operated, and pallet loads of commodity consumed. Pressure Steel peak temp Not measured 203 F The larger orifice sprinkler with lower pressures was able Density to penetrate the updraft and affect the fire faster than the Sprinklers operated smaller orifice sprinkler in this open rack arrangement. Pallet loads consumed 20 2 The larger orifice sprinkler in this palletized arrangement, as shown in Table S2.2, again reached the burning surfaces quicker via better penetration of the fire plume and produced a better result (both tests illustrated in Table the number of sprinklers operated and the pallet loads of S2.2 were successful). commodity consumed with the larger orifice sprinkler. The tests shown in Table S2.3 show a significant difference between the K-8 sprinkler and the other two. Obviously it was not possible in this comparison to show a REAL WORLD FIRE TESTING better result than the K-11 sprinkler when using the larger orifice K-17. Other tests have shown a better result with Warehouse Example the K-17 compared directly to the K-11. Following is an actual approximation of a water supply The test results shown in Table S2.4 come from UL curve with a pump that had a no control situation in a Report EX683-98NK7829, Fire Tests on Wood Pallets, real world hostile fire. With the pump running, the initial which was sponsored by CHEP International and Central pressure was about 175 psi. The first few K-8 ( in. Sprinkler. orifice) sprinklers in the warehouse that operated appar- The difference between the two tests shown in Table ently misted (almost all the drops were small), and the S2.4 was the spread of fire. It was more easily diminished drops did not penetrate the fire plume and were carried by the K-17, which operated less than half the number of upward and outward, thereby cooling adjacent sprinklers sprinklers operated by the K-11 sprinkler. and preventing them from operating. The result was fire Although it is feasible to find other direct comparisons travel through much of the warehouse, destroying the prodshowing the better results with a larger orifice sprinkler at uct and causing a very large loss. Fire testing was initiated the same density, Table S2.5 shows the last direct constant to determine if using a K-17 sprinkler would have helped density comparison for this study. the situation. Two of the tests showed these results as This comparison in Table S2.5 shows the low-pressure indicated in Table S2.6, including the peak steel temperarequirement and much better results as demonstrated by ture, number of sprinklers operated, and whether the fire spread was controlled. TABLE S2.1 Constant Density Test Comparisons Test Findings Three benefits of the larger orifice sprinkler were obvious Sprinkler 1 2 in. (K-5.6) 5 8 in. (K-11) during the tests shown in Table S2.6, as follows: Commodity Class II Class II Arrangement Rack Rack 1. The volume of water was greater. The K-8 sprinkler at Ceiling height 30 ft 30 ft 165 psi provides 103 gpm, while the K-17 sprinkler at Storage height 20 ft 20 ft 130 psi provides 216 gpm. Ignition location With such high initial discharge rates, the friction loss Pressure 43 psi 11 psi Steel peak temp 829 F 331 F on the supply pipes and sprinkler piping would be much Density greater with the K-17 sprinkler. This resulted in lower Sprinklers operated 18 9 first-operating sprinkler pressures with a greater rate of Pallet loads consumed 41 5 pressure reduction as more sprinklers operated, thus creating a self-regulated pressure reduction without a Automatic Sprinkler Systems Handbook 2007

4 950 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires TABLE S2.3 Constant Density Test Comparisons Sprinkler in. (K-8) 5 8 in. (K-11) 0.77 in. (K-17) Commodity Plastic Plastic Plastic Arrangement Rack Rack Rack Ceiling height 25 ft 25 ft 25 ft Storage height 15 ft 15 ft 15 ft Ignition location Pressure 55 psi 29 psi 12.5 psi Steel peak temp Not measured 163 F 135 F Sprinklers operate Pallet loads consumed TABLE S2.4 Constant Density Test Comparisons for Idle Pallet Storage Sprinkler 5 8 in. (K-11) 0.77 in. (K-17) Sprinkler temperature rating 165 F 155 F Commodity Idle 4-way wood pallets Idle 4-way wood pallets Arrangement 2 stacks 3 stacks 2 stacks 3 stacks Storage height 12 ft 12 ft Density Steel peak temperature 201 F 129 F Sprinklers operated 13 6 Approx. percentage of pallet damage 90% 23% TABLE S2.5 Constant Density Test Comparisons Sprinkler 1 2 in. (K-5.6) 0.77 in. (K-17) Commodity Plastic Plastic Arrangement Rack Rack Ceiling height 30 ft 30 ft Storage height 9 ft 9 ft Density Pressure 67 psi 7 psi Sprinklers operated 29 5 Pallet loads consumed 14 2 negative impact from high impact from high initial pressures. 3. The use of the lower temperature rated sprinklers with the larger orifice sprinklers showed effective control of the spread of the fire and no need to use hightemperature sprinklers to reduce the number of sprinklers on the periphery of the fire. Exhibit S2.2 highlights the differences of the K-8 and K-17 initial operating pressures. It can be seen from Exhibit S2.2 that as more sprinklers operate, the K-17 sprinkler would move down the curve further with the same number of sprinkler operations, thus reducing the pressure and restricting the misting effect. TABLE S2.6 Comparative Test Results INITIAL DENSITY ADVANTAGES Sprinkler in. (K-8) 0.77 in. (K-17) In the real world, with sloping water supplies and pipe Sprinkler temperature rating 286 F 155 F friction loss, higher initial pressures are inevitable. Since Commodity Class III Class III city water supplies vary considerably from being fairly flat Ceiling height 31 ft 31 ft to extremely steep, it is impossible to come up with a Storage height 22 ft 22 ft Pressure 165 psi 130 psi typical water supply. However, for storage occupancies, Steel peak temperature 421 F 113 F most NFPA requirements are for densities and pressures Sprinklers operated 2 2 well above those required for most buildings. If the city Fire spread controlled? No Yes water supply is flat, it usually requires a fire pump, boosting initial pressures. If the city water supply is steep, the higher 2007 Automatic Sprinkler Systems Handbook

5 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires 951 Pressure Available pressure with one K-8 sprinkler activated Available pressure with one K-17 sprinkler activated Flow (gpm) Water supply curve 1000 EXHIBIT S2.2 Differences Between K-8 and K-17 Initial Operating Pressures. USE OF THE QR LINK 1. A cheaper sprinkler piping system by eliminating some sprinkler lines (this usually offsets any possible increase in the cost of the sprinkler itself). 2. A wider distribution, so there is wetting ahead of the fire much quicker than with standard-spaced sprinklers. 3. More initial water delivered to the fire area with the first few sprinklers at pressures that produce the optimum combination of large and small drops. This can be done because of the wide range of sprinkler spacing combina- tions. Over the last few years, the use of the quick-response (QR) link in tests, even with the standard 1 2 in. and in. orifice sprinklers, has been shown to work as well as or better than the standard response sprinklers. However, when the QR link was combined with a certain distribution pattern designed to suppress the fire, the early suppression fastresponse (ESFR) sprinkler was born. It now made sense to put a lot of water on the fire quickly when the fire was small, allowing even less fire, smoke, and water damage to occur than with large orifice sprinklers. The K-11 and K-14 upright ESFR sprinklers have been listed and/or approved by the testing agencies, as has the K-22 pendent ESFR, but have not been included in the following compar- isons. At the time of this writing, two upright ESFRs and four pendent ESFRs are on the market. Table S2.8 shows the partial pressure requirements for each and again shows the advantages of the larger orifice sprinklers. As the pressure requirements are reduced with the use of larger orifice sprinklers, there will be fewer and fewer requirements for fire pumps. Since city water supplies are normally more reliable than having to use a fire pump, a more reliable sprinkler system is normally used if larger orifice sprinklers are installed. SPECIAL DISTRIBUTION CAPABILITIES initial pressures are already there. These high initial pres- sures can be anything over 50 psi up to close to 200 psi. For this example, 81 psi was chosen as a conservative point, the results of which are shown in Table S2.7. Table S2.7 shows the distinct advantage of having larger sprinklers and high initial pressures. There is more water on the fire and a much greater chance of operating fewer sprinklers away from the fire start area. Usually, that translates into a much smaller normal loss expectancy. This smaller normal loss expectancy is good for the owner as well as the insurance companies. Larger orifice sprinklers designed for high-challenge fires with unique distribution methods have been created that produce special protection methods. One is the large drop sprinkler, and the other is the K-25 EC (extended coverage) sprinkler. The large drop sprinkler has certain pressure requirements for certain storage and ceiling heights that are able to produce water penetration capabilities above the norm for upright sprinklers. The K-25 EC can be spaced up to 14 ft by 14 ft and can be used as a density/area sprinkler creating the following three positive features: LIMITATIONS There is not one sprinkler that can be designed that is good for all field situations. Just designing for larger orifice sprinklers is not good enough. Sometimes the cheaper, better protection occurs with smaller orifice sprinklers. Larger orifice sprinklers are not normally suggested in the following situations: TABLE S PSI Initial Operating Pressure (10 ft 10 ft Sprinkler Spacing) K-5.6 K-8 K-11 K-14 K-17 K-22 K-25 Q K P Q K P Q K P Q K P Q K P Q K P Q K P Q Q 8 81 Q Q Q Q Q Q 50 gpm Q 72 gpm Q 99 gpm Q 126 gpm Q 153 gpm Q 198 gpm Q 225 gpm Automatic Sprinkler Systems Handbook 2007

6 952 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires TABLE S2.8 Effect on Design Pressure Where Large Orifice Sprinklers Are Utilized Maximum Maximum Nominal Minimum In-Racks Commodity Staging Height Ceiling Height K-Factor Pressure Required? Cartoned No unexpanded plastics No No No No No Yes Yes No K in. orifice K in. orifice K in. orifice 1. When density requirements are less than 0.35 gpm/ft 2, higher with the need for greater densities, these safety as the minimum pressure requirement of 7 psi will cause factors were found not to be conservative at all. overkill for these hazards. Today s testing with the larger orifice sprinklers has 2. For some specialty hazards that cause flash fires or mostly been done by comparing the larger orifice sprinkler hidden fast-spreading fires that normally require in-rack tests directly with the previously conducted 1 2 in. and sprinkler protection, full-scale costly fire testing may in. orifice sprinkler tests meaning constant densities be necessary for acceptance by the fire community. throughout the test. This testing is correct, because it compares apples with apples, but it does not allow for the Also, in the larger orifice sprinkler categories there biggest advantages of the larger orifice sprinklers to be are many choices ( 5 8 in. to 1 in.). This variety of choices displayed. Future testing with large orifice sprinklers may means that careful study should be initiated to determine determine the smallest anticipated initial densities for flat the proper sprinkler for each specific hazard and arrangewater supplies, and may use that density for the first four ment. Not everyone in the fire protection design industry sprinklers operating during the test. If the water supply is is able to determine this. Therefore, some poor designs are known for the specific testing being conducted, of course more likely to occur. that water supply may be followed throughout the test. If the above procedure is followed, the true advantages of the larger orifice sprinklers will more easily be shown FUTURE TESTING PROCESS through the testing process. As the larger orifice sprinklers In the early testing of high-piled storage using 1 2 in. and are used in the field, they will undoubtedly show the same in. sprinklers, almost all the comparison testing was advantages. done with constant densities. This meant that the first sprinkler operated at the same pressure as the last sprinkler. At the time, this was thought to be the conservative approach SUMMARY to testing, as a normal water supply would start at higher Larger orifice sprinklers are normally better for the higher pressures and diminish as more sprinklers operated. This hazard warehouse/storage protection schemes because of meant that in the real world, there would always be more the following: water coming out of the sprinklers initially, and this would be a safety factor built into designs. Also, because public 1. Lower pressures are feasible for the design, allowing water supplies vary from very high initial pressures and fewer small drops to be produced, helping to eliminate step declines to very flat, testing engineers preferred con- skipping and causing better penetration through the stant densities so other variables could more easily be commodity to the fire. analyzed. These reasons for using constant density testing 2. Higher initial densities with a given water supply put were good when testing at lower pressures and a minimum more water on the fire, causing an overkill that often of 70 ft 2 to 80 ft 2 spacing. However, as pressures became produces fewer sprinkler operations outside the fire 2007 Automatic Sprinkler Systems Handbook

7 Supplement 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires 953 area. Also, the higher initial designs cause a quicker For high-hazard applications with density demands higher reduction in pressure for water supplies that normally than 0.35 gpm/ft 2, larger orifice sprinklers usually provided produce very high pressures and misting with smaller a more effective design. orifice sprinklers. This again causes a self-regulating method of producing a better combination of large and small drops. REFERENCE CITED 3. The combination of points (1) and (2) above will nor- UL Report EX683-98NK7829, Fire Tests on Wood Pallets, mally cause a hostile fire in the real world to be smaller Underwriters Laboratories Inc., Northbrook, IL, in size, cause less smoke to be created, and cause less June water damage than smaller orifice sprinklers. It can also, by eliminating the need for a fire pump, create a more reliable system that is less likely to fail. Automatic Sprinkler Systems Handbook 2007

8

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

High Ceiling Protection

High Ceiling Protection High Ceiling Protection High Ceiling Protection An Investigation of Automatic Sprinkler Protection of Buildings with Non-Storage Occupancies and High Clearances Company Confidential 2 Background New architectural

More information

Box-in-Box Cold Storage Fire Protection Options

Box-in-Box Cold Storage Fire Protection Options Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems Abstract In the industry of Fire Protection a large number of Automatic Fire Sprinklers has been developed trying to cover all

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection

More information

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General Description TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast

More information

Sprinkler Solutions for Storage Applications

Sprinkler Solutions for Storage Applications Sprinkler Solutions for Storage Applications Logistics and Distribution As storage facilities and their distribution methods have evolved, so have the challenges of protecting them. When installing a fire

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK500 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed. March 7, 2008 Sprinkler 120a Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Residential Sprinkler For Sloped Ceilings

Residential Sprinkler For Sloped Ceilings Bulletin 035 Rev. H Residential For Sloped Ceilings Bulletin 035 Rev. H Guidelines for Listed Residential installations below Sloped Ceilings The installation guidelines cover Residential Models: F1 Res

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Early Suppression Fast Response Sprinklers and Obstructions

Early Suppression Fast Response Sprinklers and Obstructions Early Suppression Fast Response Sprinklers and Obstructions Presented at SUPDET 2016 March 1, 2016 San Antonio, Texas Presented by: Garner Palenske, P.E. Senior Vice President Aon Fire Protection Engineering

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

STORAGE FIRE PROTECTION SPRINKLERS

STORAGE FIRE PROTECTION SPRINKLERS STORAGE FIRE PROTECTION SPRINKLERS HOW CAN YOU REDUCE YOUR FIRE SPRINKLER INSTALLATION COSTS? Tyco Storage Sprinklers are intended for use in storage applications such as big box retail, extra hazard,

More information

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed. Sprinkler 121a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

standard response elo upright and pendent sprinklers (storage-density/area)

standard response elo upright and pendent sprinklers (storage-density/area) December 5, 2008 Sprinkler 13e 1. DESCRIPTION The Viking Standard Response ELO Upright and Pendent Sprinklers are thermosensitive glass bulb spray sprinklers available in several different finishes and

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

TECHNICAL DATA NOTICE

TECHNICAL DATA NOTICE Page 1 of 5 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised Engine Module Page 1 of 5 SPRINKLER HEADS Types of Sprinkler Heads There are many different types of sprinkler heads utilized in fire protection systems. Most are equipped with a thermal detector that

More information

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing Extended Coverage Sprinklers Extended Coverage Sprinklers are intended for the protection of areas larger than those specified in standard installation rules and for specific light, ordinary, or extra

More information

SPRINKLER TECHNOLOGY:

SPRINKLER TECHNOLOGY: SPRINKLER TECHNOLOGY: CURRENT STATE OF THE ART AND GLIMPSE INTO THE CRYSTAL BALL James Golinveaux Senior Fellow Tyco Fire Protection Products First known patent for automatic suppression system - 1723

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) February 27, 2009 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description The Tyco Model

More information

STORAGE PRODUCT BROCHURE

STORAGE PRODUCT BROCHURE STORAGE PRODUCT BROCHURE J168 HL-22 Spec App ESFR N252 EC JL-17 ESFR Control-mode, density area standard coverage Coverage for 48 ft high buildings 14 x 14 coverage Protection of encapsulated or non-encapsulated

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series ELO-231 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Response, Standard Coverage Upright and Pendent

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-50 Model Early Suppression Fast Response Pendent Sprinklers 16.8 K-factor General Description The Model Pendent Sprinklers (Ref. Figure 1) are Early

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying

More information

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series ELO-231 Upright and Pendent Sprinklers Standard Response,

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

Obstructions and ESFR Sprinklers Phase 1

Obstructions and ESFR Sprinklers Phase 1 Obstructions and ESFR Sprinklers Phase 1 Final Report Prepared by: Garner A. Palenske, P.E. William N. Fletcher Aon Fire Protection Engineering Corporation San Diego, CA October 2014 Fire Protection Research

More information

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description The Tyco Model

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Worldwide Contacts www.tyco-fire.com Series EC-8 8.0 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Pendent Sprinklers are decorative glass bulb sprinklers

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description Extended Coverage and Pendent Sprinklers

More information

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16 (42,7 mm) CROSS SECTION Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description Extended Coverage and Pendent Sprinklers

More information

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Model/Sprinkler Identification Number JULY, 2011 WARNINGS Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series EC-11 & EC-14 11.2 and 14.0 K-factor Extended Coverage (Light and Ordinary Hazard) Upright, Pendent, and Recessed Pendent Sprinklers

More information

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Worldwide Contacts www.tyco-fire.com Series EC-8 8.0 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Pendent Sprinklers are decorative glass bulb sprinklers

More information

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix FINAL REPORT BY: Justin A. Geiman, P.E. Noah L. Ryder, P.E. Fire & Risk Alliance Rockville, MD, USA October 2017 2017 Fire Protection

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

More information

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2) Page 1 of 6 1. DESCRIPTION Viking EC/QREC Pendent Sprinkler VK534 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements.

More information

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers

More information

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA January 4, 2008 Sprinkler 57g 1. DESCRIPTION Viking Horizon Mirage Quick Response Large Orifice Concealed Pendent Sprinkler VK406 is a small solder link and lever spray sprinkler designed for installation

More information

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0) Sprinkler 83h 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 and Pendent Sprinkler VK572 are thermosensitive glass bulb spray sprinklers

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com AUGUST 2014 A-15 GLOBE RESIDENTIAL SPRINKLER

More information

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based

More information

Spray sprinkler system

Spray sprinkler system Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report Spray sprinkler system Recommendations on fire protection in tyre storage facilities using spray

More information

standard/quick response extended coverage light and ordinary hazard elo sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229)

More information

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems where the appearance

More information

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description Worldwide Contacts www.tyco-fire.com Series TY-FRL 5.6 and 8.0 K-factor Extended Horizontal Sidewall s Quick & Standard (Light Hazard) General Description The Series TY-FRL, 5.6, and 8.0 K-factor, Extended

More information

standard response elo upright sprinkler

standard response elo upright sprinkler Page of 5. DESCRIPTION The Viking Standard Response ELO Upright Sprinkler is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

MINUTES OF CONFERENCE CALL National Sunroom Association FOAM PANEL STORAGE SUBCOMMITTEE. Tuesday, February 27, :00 p.m.

MINUTES OF CONFERENCE CALL National Sunroom Association FOAM PANEL STORAGE SUBCOMMITTEE. Tuesday, February 27, :00 p.m. MINUTES OF CONFERENCE CALL National Sunroom Association FOAM PANEL STORAGE SUBCOMMITTEE Tuesday, February 27, 2007 2:00 p.m. Eastern Time ROLL CALL Those Present Dan Ochstein, Chairman Lyndon Johnson Tony

More information

Fire Prevention Coffee Break Training. May 2017

Fire Prevention Coffee Break Training. May 2017 Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small

More information

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending FireLock LP-46 Low Pressure Storage Sprinkler This storage sprinkler was designed for controlling fires in single, double and multiple row rack storage of up to Cartoned, Unexpanded, Group A plastic commodities

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Final Report Prepared by: UL LLC The Fire Protection Research Foundation One Batterymarch Park Quincy,

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

TECHNICAL DATA.   Cover Plate Assembly must be ordered separately: Page of 5. DESCRIPTION Viking Standard/Quick Response Concealed Pendent Sprinkler VK0 is a thermosensitive glass bulb spray sprinkler pre-assembled with a threaded adapter for installation with a domed

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2234) are

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2524)

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE March 2, 2007 Sprinkler 147k 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK425 is small a highsensitivity solder link and lever residential sprinkler designed for installation

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2284) are decorative, fast response, fusible solder sprinklers

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Pendent Sprinkler VK537 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings

More information

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

More information

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531 WWW.UL.COM 1.877.ULHELPS / (1.877.854.3577) File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531 Issued: August 4, 2004 Revised: April

More information

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal

More information

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS Table of Contents The History behind Halon...3 Addressing the

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634) January 1, 2011 Sprinkler 92a 1. DESCRIPTION Viking Mirage Quick Response Extended Coverage Concealed Pendent Sprinkler VK632 and VK634 are thermosensitive glass-bulb spray sprinkler designed for installation

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA September 5, 2008 Sprinkler 147u 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK457 is a small highsensitivity solder link and lever residential sprinkler designed for installation

More information

standard response Fusible Link Upright sprinkler VK204 (K8.0)

standard response Fusible Link Upright sprinkler VK204 (K8.0) Page 1 of 6 1. DESCRIPTION Viking Standard Response Sprinkler VK204 is a small thermosensitive solder link spray sprinkler available with various finishes and temperature ratings to meet design requirements.

More information

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

WRENCH FLATS NPT 1/2 7/16 (11,1 mm) NOMINAL MAKE-IN. 1-1/2 (38,1 mm) 2-3/16 (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN. Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information