SPRINKLER TECHNOLOGY:

Size: px
Start display at page:

Download "SPRINKLER TECHNOLOGY:"

Transcription

1 SPRINKLER TECHNOLOGY: CURRENT STATE OF THE ART AND GLIMPSE INTO THE CRYSTAL BALL James Golinveaux Senior Fellow Tyco Fire Protection Products

2 First known patent for automatic suppression system to Mr. Ambrose Godfrey, an English chemist for: Cask of water containing a chamber filled with gunpowder Ignited by fire using fuses Intended to be strategically placed within buildings At least one success

3 First known patent for automatic suppression piping system to Mr. John Carey of England for: Perforated piping Supplied from elevated water tank Valve on tank is opened by dropping of weights when rope across ceiling is burned

4 Perforated pipe systems in the U.S.

5 Perforated pipe systems in the U.S.

6 Performance of perforated piping Advantages: First widely used fire suppression systems Distributed approximately.05 gpm/ft 2 (2 mm/min) over floor area NOTE: 2 mm/min = 2 L/min/m 2 Disadvantages: Water not concentrated where needed, resulting in excessive water damage over large floor areas not involved in the fire High potential for corrosion, since open piping accumulated rust and scale that clogged orifices

7 Automatic suppression system patents in the United States 1872 Phillip Pratt revolving perforated pipe arms, activated by cord burn-through 1872 John Souther steam dispensed through brass perforated pipes 1873 J.C. Meehan Fuse-activated steam system

8 Early automatic sprinklers Credit sometimes given to Major A. Stewart Harrison of the First London Volunteers who in 1864 developed a 75 mm diameter sphere with 1.6 mm holes spaced 3 to 19 mm apart, with fusible solder activation Never patented or marketed

9 Early automatic sprinklers Credit for the first practical automatic sprinkler to Henry Parmelee of New Haven, Connecticut, who patented his first sprinkler in 1874, and protected his own piano factory with a later model In 1875 he created a sprinkler that used a brass cap soldered over a water distributor

10 Parmelee Sprinkler

11 Early automatic sprinklers Grinnell patented a sprinkler in 1882 that used a plate orifice instead of perforations or slots Soldered levers held a valve against the orifice in the plate The diaphragm action of the orifice plate allowed an increase in water pressure to seal the orifice tighter against leakage

12 Early automatic sprinklers Over 450 patents on automatic sprinklers in the United States between 1872 and 1914, mainly using solder

13 First glass bulb sprinkler

14 Major Sprinkler Innovations 1935 Duraspeed sprinkler for faster response Cycling valve On-off sprinkler Bimetallic disc Wax motor On off Sprinklers

15 Major Sprinkler Innovations 1955 Spray sprinkler available to replace conventional sprinkler, allowing larger protection areas Upright Pendent Spray Sprinklers Upright Pendent Ceiling Floor Ceiling Old Style/Conventional Sprinklers Floor

16 Standard Spray vs. Conventional

17 Major Sprinkler Innovations Extended coverage sprinkler Quick response sprinkler Residential (domestic) sprinkler Large drop sprinkler ESFR sprinkler Residential ESFR

18 What is water mist? NFPA 750 (2010) Definition Water Mist. A water spray for which the Dv99 for the flow-weighted cumulative volumetric distribution of water droplets, is less than 1000 microns at the minimum design operating pressure of the water mist nozzle 18

19 19 Residential Sprinklers LFII

20 20 Residential Sprinklers LFII

21 How did we get here? For Control Mode Density Area (CMDA) sprinklers the Standard Spray K5.6 (K80) and K8.0 (K115) pendent and upright automatic sprinklers were the only CMDA K factors for storage until

22 CMDA (continued) In 1992 Tyco (Central Sprinkler) introduced the first CMDA K11.2 (K160) pendent and upright automatic sprinklers approved for Storage formerly known as the ELO

23 CMDA (continued) K14.0 (K200) K16.8 (K240) K25.2 EC Upright (K360) K25.2 EC Pendent (K360) The K14 (200), K16.8 (K240) and K25.2EC (K360EC) CMDA automatic sprinklers 23

24 Control Mode Specific Application (CMSA) K11.2 (K160) K16.8 (K240) K19.6 (K280) K25.2 (K360) K25.2EC (K360EC) CMSA automatic sprinklers 24

25 Suppression Mode (ESFR) K14.0 (K200) K14.0 (K200) K16.8 (K240) K16.8 (K240) K22.4 (K320) K25.2 (K360) Suppression Mode automatic sprinklers 25

26 K25 ESFR 26

27 Higher Faster - Further How high can we go? Ceiling Only? 27

28 2 8

29 Where In-Racks Become Mandatory Based on Type of Sprinkler and Storage or Ceiling Height NFPA 13 Chapter Commodity Storage Height Building Height CMDA CMSA ESFR Class IV >22 ft (6.7 m) NA x Class I - III >25 ft (7.6 m) NA x 16 Class I - IV >35 ft (10.6) >40 ft (12.1 m) x Class I - IV >40 ft (12.1 m) >45 ft (13.7 m) x 17 Group A plastic commodities in cartons, encapsulated or nonencapsulated Group A plastic Cartoned Unexpanded Group A plastic Cartoned Unexpanded Group A plastic Exposed Unexpanded 20 ft (6.1 m) >25 ft (7.6 m) x >20 ft (6.1 m) NA x >35 ft (10.6) >40 ft (12.1 m) x >40 ft (12.1 m) >45 ft (13.7 m) x >35 ft (10.6) >40 ft (12.1 m) x 29

30 The Challenge Currently NFPA 13 and FM 8-9 limit Ceiling Only protection for some commodities to 45 ft (13.7m). UL Specific Application Sprinklers (Reliable K22 and Tyco K25 ESFR) extend Ceiling Only protection for some commodities to 48 ft (14.6m). K14 (200) ESFR have been limited to 35 ft (10.6m) ceilings from it s original 40 ft (12m) application. When installing in-rack sprinklers, most vertical spacing's are limited to 10 ft (3m) to 12 ft (3.7m) requiring many levels of in-rack sprinklers. At what height is Control Mode not enough for local fire department capability? There are 17 different sprinklers in CMDA, CMSA and ESFR categories to select from for storage applications. 30

31 Skipping - Description of Full Scale Fire Test 3 Fuel Arrangement: FMRC Group A Plastics Fuel Height: 1.73 m Clearance to ceiling: 15.9 m Arrangement: 2 by 8, solid pile, 1 tier Density: 12 mm/min Sprinklers: K115, RTI 140 (m-s) 1/2 Standard Response element, Upright Spacing: 3.0 m x 3.0 m 31

32 Skipping Plan View of Sprinkler Operation Test 3 32

33 What is the Big Deal? FM Global and NFPA have made Significant Changes for Storage in 2011 and 2012 FM has eliminated all names of storage sprinklers such as ESFR, CMSA and CMDA, NFPA still uses the names to differentiate the rules FM has banned K5.6 (K80) and K8.0 (K115) from ceiling protection of storage, NFPA restricts the use but not a ban FM has banned 286 degree (high temperature) sprinklers from wet systems FM has eliminated density and area from design considerations, NFPA still highly dependent on density curves FM has eliminated storage height from design consideration of ceiling only protection, storage height and clearance a significant design consideration in NFPA FM and NFPA now recognize ceiling only designs with as few as 6 sprinklers in the hydraulic demand. 33

34 K5.6 Spray 7 psi (0.5 bar) to 100 psi (7 bar) 34

35 K25EC Droplet Size 7 psi (0.5 bar) to 100 psi (7 bar) 35

36 Droplets Ability to Penetrate the Fire Plume 22 MPH (45 KPH) 36

37 Small Drops are Carried Back to Ceiling - May Skip or Prevent Adjacent Sprinklers from Opening Skipping 22 MPH (45 KPH) 37

38 K8.0 (115).33 gpm/ft 2 / 3000 sq ft (13.44 / 279)

39 EC-25

40 CMDA - Pressure is not the Issue PRESSURE (PSI) K5.6 K8.0 K11.0 K K25 EC DENSITY (100 SQ FT) 40

41 4 1 Expanded Exposed Plastic

42 Activated Sprinklers RSP 7 vs. K11.2 (160) RSP 7 Operated Sprinklers 29 sprinklers K8.0 (115) Sprinkler Demand Operated Sprinklers Only 4 K11.2 (160) Sprinkler Demand K8.0 (115) K11.2 (160) 1740 GPM (6587 L/min) 240 GPM 908 L/min)

43 EC-25 Pendent In-Rack (Reliable) Performance Based Protection FSC7JY

44 EC-25 Pendent (Reliable) Performance Based Protection

45 EC-25 Pendent (Reliable) Performance Based Protection N252 EC Sprinklers Centered in Longitudinal Flue and Centered Between Rack Uprights = 8-3 on center.

46 Testing with a Continuous Barrier Across the Uprights Tests 1, 2, & 3 Tests 4 & 5

47 EC-25 Pendent (Reliable) Performance Based Protection

48 ESFR- Dry-Type K14 (200) & K17 (240) Ambient Temperature of Discharge End of Sprinkler Exposure Length of Sprinkler inches (mm) in Heated Area Temperature of Heated Area 40 F (4 C) 40 F (4 C) 0 30 F ( 1 C) 0 20 F ( 7 C) 4 (100) 10 F ( 12 C) 8 (200) 0 F ( 18 C) 12 (305) 10 F ( 23 C) 14 (355) 20 F ( 29 C) 14 (255) 30 F ( 34 C) 16 (405) 40 F ( 40 C) 18 (455) 50 F ( 46 C) 20 (510) 60 F ( 51 C) 20 (510) Do not attempt to add additional insulation around the barrel in the heated area as a method to minimize condensation. This will reduce the calculated Exposure Length. 48

49 Quell 49

50 UL Specific Application Listing K22 & K25 ESFR Provide ceiling-only protection up to and including: 48 ft (14.6 m) Ceiling 43 ft (13.1 m) Storage Eliminates need for in-rack sprinklers for storage arrangements beyond NFPA 13 Lower pressure provides flexibility when sizing system piping when compared to other listed sprinklers 10-Year Limited Warranty 5 0

51 5 1 ESFR Obstructed

52 Specific Application Sprinklers Attic Sprinklers Window Sprinklers Combustible Concealed Sprinklers Institutional Sprinklers Hallway Sprinklers 52

53 New Challenges

54 Outside the scope of NFPA 13 Table A.5.6 Examples of Commodities Not Addressed by Classifications in Section 5.6 Ammunition Components Bulk primers and powder Batteries Lithium and other similar exotic metals Lithium ion and other rechargeable batteries that contain combustible electrolyte Boat Storage Stored on racks Boxes, Crates Empty, wood slatted* Carpet Rolls Combustible Metals unless specifically identified otherwise Compressed or Liquefied Flammable Gases (i.e., filled propane cylinders) unless specifically identified otherwise Explosives Blasting primers and similar items Fertilizers (nitrates) Fireworks Consumer and display Flammable and CombustibleLiquids unless specifically identified otherwise Liquids that contain greater than 20% alcohol Hanging Garments, Bulk Storage Lighters (butane) Loose in large containers (Level 3 aerosol) Storage Container Large container storage of household goods

55 Lightweight Construction New Construction will not burn Fire Safe Home

56 Lithium Battery Storage FPRF Report A total of thirteen tests were conducted. Ignition was achieved using an external fire. The key findings reported by FM Global included: The fire growth characteristics for the Li-ion batteries and the FM Global standard commodities that were evaluated exhibited similar fire development leading to the estimated time of first sprinkler operation. Commodity containing densely packed Li-ion batteries and minimal plastics (i.e., cylindrical and polymer cells) exhibited a delay in the battery involvement. For the Li-ion batteries used in this project, significant involvement was observed within five minutes after ignition. Commodity containing a significant quantity of loosely packed plastics (i.e., CUP and power tool packs) exhibited a rapid increase in the released energy due to plastics involvement early in the fire development. Battery involvement was not observable due to the contribution from the plastics.

57 Lithium Battery Storage FPRF Report The CUP commodity exhibited a fire hazard leading to initial sprinkler operation that was similar or greater than the Li-ion battery products tested. Therefore, the CUP commodity was chosen as a suitable surrogate for Li-ion batteries in a bulk packed rack storage test scenario, provided the fire protection system suppresses the fire prior to the time of significant Li-ion battery involvement. Without full-scale sprinklered testing experience with Li-ion batteries, protection system performance must preclude Li-ion battery involvement..

58 Lithium Battery Storage FPRF Report The second test series evaluated the level of protection provided by ceiling level only sprinklers. Two large-scale fire sprinkler tests were conducted with CUP commodity and were based on the reduced commodity testing approach data. Full-scale tests were conducted with CUP commodity due to the costs associated with purchasing Li-ion cells and/or battery packs. In both large-scale fire tests, the CUP commodity cartons were breached by the fire before initial sprinkler operation, resulting in persistent, deep seated flames beyond the predicted time of battery involvement. At this time, the adequacy of ceiling level sprinkler protection cannot be established without repeating the large-scale fire sprinkler tests using bulk packed Li-ion cells and/or battery packs

59

60 Car Stackers 2016 Edition of NFPA 13 A Extra hazard (Group 2) occupancies include occupancies having uses and conditions similar to the following: (9) Car stackers and car lift systems with 2 cars stacked vertically

61 Boat Storage

62 Boat Storage Facilities First facilities 1960s. Southeast U.S. 25 ft. boats loaded by standard fork lifts 3 to 4 tiers of storage 1990s 40 ft. boats Specialty forklifts, stacker cranes Today 8-10 tiers of storage Boats of ft. in length Even more exotic designs 62

63 Retail Fireworks Sprinkler Tests Prior testing has been relatively limited with only two known programs conducted Battelle Tests, January 2000 Report Impetus- Ohio River Fireworks store in Scottown, Ohio on July 3, 1996 Client - Ohio Department of Commerce/Fireworks Fire Suppression Task Force Southwest Research Institute (SwRI), 2009 Report Impetus document performance in typical retail sales display scenarios with and without fire mitigation techniques, support for NFPA 1124 Client American Fireworks Standards Laboratory 63

64 Approximate Configuration 7700 cfm exhaust ( attained) 12 ft 22 ft 36x80 Door 45 ft 155 F, K=5.5 Standard 165 F, K=25 ESFR 64

65 Battelle Tests, Observations Showroom of 1,000 ft², single door opening, 11-8 ceiling Sprinklers short time frames first sprinkler operated at 5 seconds all 10 sprinklers operated within 35 seconds Projectile behavior of fireworks common to all tests Smoke/temperature untenable conditions (6 ft smoke layer height, 200 F) developed rapidly in some tests ESFR sprinklers, best control on temperatures (majority of test below 200 F) 7,700 cfm smoke evacuation system was ineffective Very limited fuel package arrangements three 12 feet long gondolas shelve volume utilization only percent majority of the room was empty floor space 65

66 SwRI, Test Configuration 66

67 SwRI, Observations Slow to develop fires Test 6, first sprinkler, 2 minutes 45 seconds after ignition In four of five tests first sprinkler operation at min. Either two or four sprinklers operated in each test Burning Product on the two lowest gondola shells generally continued to burn for the duration of the test due to shielding of the water spray by the shelving units Test 9, without mesh caging around aerials lots of fireworks were injected into the aisle aerial devices were launched outside of the immediate fire area Very limited fuel package arrangements 16 feet long gondolas shelve volume utilization only percent majority of the room was empty floor space 67

68 Summary and Key Points Battelle tests Relatively small space Potential fast hazard development indicated No flame breaks, no fuse covers Fuel density compared to retail environment ESFR sprinklers??? SwRI Tests Fuse covers showed effectiveness Containment bins effective for aerials Flame breaks useful to limit spread Tall ceiling, hazard of room environment unknown Fuel density compared to retail environment Standard response CMDA sprinklers??? 68

69 Field Survey Findings Retail Areas Similar to Grocery Stores Layout Product distribution Organization Displayed in Original Packaging Removal of Damaged Products 6 969

70 Field Survey Findings Retail Areas Fuse Covers / Protective Packaging Shelving Sizes & Types Varied Gondolas (up to 5 shelves) Pallets Single level bins Storage Heights & Lengths Varied Most shelving 72 inches tall All shelving 32 feet long 7 070

71 Field Survey Findings Storage Areas Storage Protection Sprinkler System Building Separation DOT Approved Packaging Shelving Sizes & Types Varied Predominant Method: Solid Pile Rack Storage in Five Stores Storage Heights Varied 120 Inches for Solid Pile 166 Inches for Racks 7 171

72 Proposed Testing Concept Full Scale Testing Retail Configurations Shelf storage arrays Palletized arrays Influence of projectiles Influence of spark spray Storage Configurations Rack storage array Palletized array 7 272

73 Household Storage Pods

74 Thank You

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General Description TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast

More information

Box-in-Box Cold Storage Fire Protection Options

Box-in-Box Cold Storage Fire Protection Options Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges

More information

High Ceiling Protection

High Ceiling Protection High Ceiling Protection High Ceiling Protection An Investigation of Automatic Sprinkler Protection of Buildings with Non-Storage Occupancies and High Clearances Company Confidential 2 Background New architectural

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK500 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed. March 7, 2008 Sprinkler 120a Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed. Sprinkler 121a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

The Effect of Large Orifice Sprinklers on High-Challenge Fires

The Effect of Large Orifice Sprinklers on High-Challenge Fires SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

TECHNICAL DATA NOTICE

TECHNICAL DATA NOTICE Page 1 of 5 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

STORAGE FIRE PROTECTION SPRINKLERS

STORAGE FIRE PROTECTION SPRINKLERS STORAGE FIRE PROTECTION SPRINKLERS HOW CAN YOU REDUCE YOUR FIRE SPRINKLER INSTALLATION COSTS? Tyco Storage Sprinklers are intended for use in storage applications such as big box retail, extra hazard,

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) February 27, 2009 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-50 Model Early Suppression Fast Response Pendent Sprinklers 16.8 K-factor General Description The Model Pendent Sprinklers (Ref. Figure 1) are Early

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending FireLock LP-46 Low Pressure Storage Sprinkler This storage sprinkler was designed for controlling fires in single, double and multiple row rack storage of up to Cartoned, Unexpanded, Group A plastic commodities

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description The Tyco Model

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Sprinkler Solutions for Storage Applications

Sprinkler Solutions for Storage Applications Sprinkler Solutions for Storage Applications Logistics and Distribution As storage facilities and their distribution methods have evolved, so have the challenges of protecting them. When installing a fire

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised Engine Module Page 1 of 5 SPRINKLER HEADS Types of Sprinkler Heads There are many different types of sprinkler heads utilized in fire protection systems. Most are equipped with a thermal detector that

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description The Tyco Model

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series ELO-231 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Response, Standard Coverage Upright and Pendent

More information

STORAGE PRODUCT BROCHURE

STORAGE PRODUCT BROCHURE STORAGE PRODUCT BROCHURE J168 HL-22 Spec App ESFR N252 EC JL-17 ESFR Control-mode, density area standard coverage Coverage for 48 ft high buildings 14 x 14 coverage Protection of encapsulated or non-encapsulated

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

standard response elo upright and pendent sprinklers (storage-density/area)

standard response elo upright and pendent sprinklers (storage-density/area) December 5, 2008 Sprinkler 13e 1. DESCRIPTION The Viking Standard Response ELO Upright and Pendent Sprinklers are thermosensitive glass bulb spray sprinklers available in several different finishes and

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229)

More information

New Facilities. Minimum Requirements

New Facilities. Minimum Requirements 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and

More information

A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating.

A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating. Control / Residential / Suppression Mode Sprinklers Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible occupancies. There are

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2284) are decorative, fast response, fusible solder sprinklers

More information

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description The TYCO RAPID RESPONSE

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing Extended Coverage Sprinklers Extended Coverage Sprinklers are intended for the protection of areas larger than those specified in standard installation rules and for specific light, ordinary, or extra

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2234) are

More information

standard/quick response extended coverage light and ordinary hazard elo sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0) Sprinkler 83h 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Upright Sprinkler VK570 and Pendent Sprinkler VK572 are thermosensitive glass bulb spray sprinklers

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2524)

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

ESCUTCHEON PLATE SEATING 3/4 NPT SURFACE. 1-1/2 (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 6.9 K-factor, Pendent/Recessed Pendent/Concealed, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Correlating Committee on

More information

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 6.9 K-factor, Pendent/Recessed Pendent/Concealed, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SUMMARY NFPA FIRE INVESTIGATION REPORT BULK RETAIL STORE FIRE TEMPE, ARIZONA MARCH 19, 1998 SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 600 fpeschulte@aol.com 504/0-7475

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

High-Piled Combustible Storage

High-Piled Combustible Storage High-Piled Combustible Storage Presenters: Rob Neale & Scott Adams Tuesday, September 12, 2017 1:30 PM - 4:30 PM High-piled Combustible Storage Based on the 2015 International Fire Code ICC Annual Conference

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE March 2, 2007 Sprinkler 147k 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK425 is small a highsensitivity solder link and lever residential sprinkler designed for installation

More information

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA Page 1 of 7 1. DESCRIPTION The Viking Attic Upright VK696 is a specific application concealed space sprinkler that provides superior fire protection in combustible and non-combustible sloped attic spaces

More information

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems where the appearance

More information

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA September 5, 2008 Sprinkler 147u 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK457 is a small highsensitivity solder link and lever residential sprinkler designed for installation

More information

sprinkler vk538 (K11.2)

sprinkler vk538 (K11.2) December 6, 2012 Sprinkler 89h 1. DESCRIPTION Viking Mirage EC/QREC ELO Concealed Pendent Sprinkler VK538 is a thermosensitive solder link spray sprinkler designed for installation on concealed pipe systems

More information

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA Sprinkler 53a 1. DESCRIPTION Viking Horizon Quick Response Flush Pendent Sprinklers are small, flush, solder link and lever spray sprinklers. Designed for use with concealed piping, the units are mounted

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Pendent Sprinkler VK537 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information

freedom residential flush pendent sprinkler vk476 (K4.9)

freedom residential flush pendent sprinkler vk476 (K4.9) January 6, 2010 Sprinkler 145h 1. DESCRIPTION Viking Freedom Residential Flush Pendent Sprinkler VK476 is a small high-sensitivity fusible element residential sprinkler designed for installation on concealed

More information

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 3 of 398 11/14/2016 10:55 AM First Revision No. 632-NFPA 13-2016 [ Global Input ] See attached

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System

More information

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA Page of 5. DESCRIPTION Viking Horizon Standard Response Flush Pendent Sprinkler VK400 is a small, flush, solder link and lever spray sprinkler. Designed for use with concealed piping, the unit is mounted

More information

Non-Storage / Special Protection / Storage Sprinklers

Non-Storage / Special Protection / Storage Sprinklers Non-Storage / Special Protection / Storage Sprinklers General Information Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible

More information

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Pendent Sprinkler Wet Pipe and Dry Pipe Systems General Description TYCO RAPID RESPONSE Series Recessed Pendent

More information

Refer to the specific sprinkler or spray nozzle technical data pages for sprinkler listings and approvals.

Refer to the specific sprinkler or spray nozzle technical data pages for sprinkler listings and approvals. Page 1 of 5 1. DESCRIPTION A. Sprinkler Cabinets Viking sprinkler cabinets are metal enclosures constructed to store an emergency supply of spare sprinklers and a sprinkler installation wrench. NFPA 13

More information

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH) Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a 14.0 (202 metric*) nominal

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems General Description LFII Residential Flush Horizontal Sidewall

More information

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications: Page 1 of 8 1. DESCRIPTION The Viking Attic Upright VK697 is a specific application attic sprinkler that provides superior fire protection in combustible and non-combustible sloped attic spaces when used

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

The Series LFII (TY3596) Residential

The Series LFII (TY3596) Residential Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series LFII Residential Concealed Pendent Sprinklers, Flat Plate 4.9 K-factor General Description The Tyco Rapid Response Series LFII (TY3596)

More information

NFPA 30 FLC-SWC Public Comment Report

NFPA 30 FLC-SWC Public Comment Report of 224 9/6/2016 1:13 PM Public Comment No. 56-NFPA 30-2016 [ Global Input ] These definitions of Protected and Unprotected are intended for inclusion in Sections 9.2, 10.2, 11.2, 13.2 and 16.2. The current

More information

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS Last Updated: April 28, 2008 FIRE REGULATIONS The purpose of fire regulations is to maintain an acceptable level of fire safety within CGS facilities.

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved,

More information

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Pendent Sprinkler Wet Pipe and Dry Pipe Systems General Description TYCO RAPID RESPONSE Series Recessed Pendent

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2) Page 1 of 6 1. DESCRIPTION Viking EC/QREC Pendent Sprinkler VK534 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements.

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series ELO-231 Upright and Pendent Sprinklers Standard Response,

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634) January 1, 2011 Sprinkler 92a 1. DESCRIPTION Viking Mirage Quick Response Extended Coverage Concealed Pendent Sprinkler VK632 and VK634 are thermosensitive glass-bulb spray sprinkler designed for installation

More information

Stillwater Area Community Services Center Inc.

Stillwater Area Community Services Center Inc. Fire Prevention Plan 1. Purpose The purpose of this Fire Prevention Plan is to eliminate the causes of fire, prevent loss of life and property by fire, and to comply with the Occupational Safety and Health

More information

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series

More information

standard response/ quick response extended coverage

standard response/ quick response extended coverage 1. DESCRIPTION Viking Extended Coverage Adjustable Recessed Dry Pendent Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers are designed for dry

More information

Early Suppression Fast Response Sprinklers and Obstructions

Early Suppression Fast Response Sprinklers and Obstructions Early Suppression Fast Response Sprinklers and Obstructions Presented at SUPDET 2016 March 1, 2016 San Antonio, Texas Presented by: Garner Palenske, P.E. Senior Vice President Aon Fire Protection Engineering

More information

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5609 is amended, to read as follows, with the entire section being an addition to the Fire Code: SECTION 5609. FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

More information