1 SECTION BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes basic electrical materials and methods including: 1. Conduit, fittings and accessories. 2. Wire, cable, connectors and markers. 3. Boxes. 4. Wiring devices. 5. Supporting devices. B. Related Work: 1. Section Trenching and Backfilling for Utilities 2. Section Service and Distribution C. References: 1. American National Standards Institute (ANSI): a. ANSl C Specification for Rigid Steel Conduit, Zinc-Coated. b. ANSl C Fittings for Rigid Metal Conduit and Electrical Metallic Tubing. 2. Federal Specifications (FS): a. FS W-C-586B - PVC Coated Electrical Cast Metal Conduit Outlet Boxes, and Bodies b. FS W-F Fittings for Cable, Power, Electrical and Conduit, Metal, Flexible. 3. National Electrical Manufacturers Association (NEMA): a. NEMA FB 1 - Fittings and Supports for Conduit and Cable Assemblies. b. NEMA RN 1 - Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit. c. NEMA WC 5 - Specific Purpose Wiring. 4. Underwriter's Laboratories, Inc.(UL): 1.02 SUBMITTALS a. UL 1 - Flexible Metal Electrical Conduit. b. UL 6 - Rigid Metal Electrical Conduit. c. UL 486A - Wire Connectors and Soldering Lugs for Use with Copper Wire. A. Submit manufacturer's product data sheets verifying compliance with specified requirements QUALITY ASSURANCE A. Where Underwriter's Laboratories, Inc. has established standards for specified products, provide only products bearing the UL label. B. Comply with NEC requirements as applicable for work of this Section.

2 PART 2 - PRODUCTS 2.01 CONDUIT, FITTINGS AND ACCESSORIES A. Design Requirements: 1. UL listed and labeled conduit, on each length, fittings and accessories. 2. Type and sizes of conduit, fittings and accessories as indicated, specified, or as required by Electrical Codes and Standards. B. Metal Conduit: 1. Rigid steel, threaded type, zinc-coated inside and outside, conforming to ANSl C80.1, FS WW- C-581 and UL Fittings and Conduit Bodies: a. Conform with ANSl C80.4, FS W-F-408 and NEMA FB 1. b. Cast malleable iron, threaded or gland compression type, galvanized or cadmium plated. Compression type may be used only in non-hazardous areas and where necessary to avoid a union. c. Insulating or insulated throat type bushings. d. Steel or malleable iron lock nuts. C. Liquid-Tight Flexible Metal Conduit: 1. Interlocked steel construction with PVC jacket conforming with FS WW-C-566 and UL 1. Rated for outdoor service. 2. Fittings and Conduit Bodies: a. Conform with FS W-F-406. e. Cadmium plated, malleable iron fittings with compression type steel ferrule, neoprene gasketed sealing rings and insulated throat. D. Rigid Nonmetallic Conduit: 1. Schedule 40 PVC conforming with NEMA TC2, Type 3 and FS W-C-1094, for direct burial and normal above-ground duty. 2. Fittings and Conduit Bodies: NEMA TC3, solvent weld type, match to conduit type and material WIRES, CABLES AND ACCESSORIES A. Control and Power Cable: 1. Sizes and types as indicated on the drawings. 2. Single conductor cables 120 volt and above: a. Thermoplastic insulated wire conforming to NEMA WC 5. b. Feeder and Branch Circuits: Type THHNITHWN, 600 volt, soft-drawn annealed stranded copper conductor, PVClnylon insulation with PVC overall jacket, #I2 AWG minimum. c. Control Circuits: Type TC, 600 volt, soft-drawn annealed copper conductor, PVClnylon insulation with PVC overall jacket, #I4 AWG stranded wire for 120 volt controls. 3. Direct burial cable: Type USE cable identified for underground use. Only use where indicated on the drawings.

3 B. Terminal Lugs: 1. Provide terminal lugs on the ends of feeder and branch circuit conductors unless lugs are provided on the connected device. a. Use solderless, compression type copper locking spade terminal lugs for wires #6 AWG and smaller. b. Two-hole type for connection of wires #4 AWG and larger to copper bus bars. 2. Sizes as recommended by manufacturer for the wire being terminated. C. Connectors: 1. Designed and sized for the specific wire or cable bring connected. 2. Rated current-carrying capacity equal to or greater than, the wire or cable being connected. 3. Equipment feeder or branch circuits: a. Use mechanical compression or bolted type connector for #6 AWG and larger. b. Use compression type ring tongue terminal connectors bolted together for #8 AWG and smaller. c. Cover connector with insulating tape or heat shrinkable insulation equivalent to 150% conductor insulation. 4. Lighting and receptacle circuits: a. Use insulating spring compression connectors for #I0 AWG and smaller. b. Cover splice with insulating tape equivalent to 150% conductor insulation. D. Terminal Blocks: 2.03 BOXES 1. Designed and sized for the wires being terminated. 2. Block rated for 600 volts. 3. Binding screw-type terminals for power and control wires #8 AWG and smaller. 4. Rated current carrying capacity equal to or greater than the wire being terminated. 5. Marking strip. A. Outlet and Device Boxes: 1. Outdoor Boxes or Exposed Indoor Boxes in Wet or Damp Location: PVC coated cast iron, deep type, stainless steel fasteners, watertight, gasketed, threaded hubs. B. Junction Boxes: 1. Galvanized steel with drip lip and galvanized steel covers fastened with stainless steel screws or bolts; or cast iron with galvanized finish and flanged bolt covers. 2. Threaded conduit entrances or rigid conduit hubs on all boxes. 3. Rubber or neoprene gasket for cover. 4. Conform to NEMA 3R unless otherwise indicated. 5. Include stainless steel piano-hinged, gasketed cover and interior back panel when enclosing terminal blocks and control relays. 6. Lockable. C. Pull Boxes:

4 1. Underground type as manufactured by Quazite, Synertec or equal. 2. Constructed of fiberglass reinforced polymer concrete. 3. Open bottom type with standard duty, gasketed, bolt-down cover rated for minimum 7500 pound vertical loading. 4. Cover stamped "Electric" and equipped with stainless steel hold-down bolts and washers. 5. Minimum dimensions of 12" x 18" x 20" depth. 6. Provide with mouse holes for conduit entry as required for specific location. 7. Provide conduit system bonding using ground lug type bushings WIRING DEVICES A. Receptacles: 1. Duplex: Specification grade, 20A,120 volt, straight blade, 3-wire grounding, side wired. 2. Ground Fault Circuit Interrupter: Specification grade, terminal type, UL Class A-Group 1, 20A, 125 volt, solid state,ground fault sensing and signaling, 5mA trip level. Each protected device shall have individual test and reset buttons. B. Device Plates: 1. Stainless steel for flush mounted devices in finished areas. 2. Galvanized steel for surface mounted devices in unfinished areas. 3. Weatherproof, cast metal, gasketed for outdoor mounted devices. Provide spring-loaded cover for receptacles, allowing cord and cap to be inserted with cover closed SUPPORTING DEVICES A. Fabricated from galvanized steel manufactured framing members equal to B-Line as indicated. B. Construct as required to rigidly support all conduit runs, boxes, switches, and panels. C. Support PVC coated metal conduit with conduit clamps, sized for specific conduit size. D. Provide galvanized steel support hardware including anchors, inserts, bolts, washers and nuts ELECTRICAL IDENTIFICATION A. Wires and Cables: 1. Service, Feeder and Branch Circuits and Cable Identification: PART 3 - EXECUTION a. Tag cable insulation for #2 AWG and smaller cables. b. Color-coded self-adhesive vinyl phase designation tape not less than 3 mils thick by inches wide for #6 AWG and larger individual conductors. c. Standard Colors: Conform to NEC INSTALLATION OF CONDUIT A. General: 1. Install conduit sizes and runs as indicated on the drawings. Shift locations as required to avoid interference with other equipment and piping being installed. 2. Where routing of conduit is not indicated, such as for small lighting home run circuits and other systems requiring small conduit runs, route conduit as specified subject to Engineer's approval. 3. Maintain 6-inches clearance between conduit and piping. 4. Unless otherwise indicated no conduit shall be smaller than 314, except 112" flexible conduit

5 may be used where indicated. 5. Cut conduit square, properly ream to remove burrs, and cut threads for RGS conduit, deep and clean. Coat all field cut threads with zinc rich paint. 6. Bring conduit to shoulder of fittings and fasten securely. 7. Field-bend conduit with benders designed for purpose so as not to distort nor vary internal diameter. 8. Provide nylon pull cord in conduits to be installed but left empty. 9. Indoors, fasten conduit terminations in sheet metal boxes by 2 locknuts, and terminate with insulated bushing. Outdoors, use threaded hub or sealing locknuts. 10. Use of running threads at conduit joints and terminations is prohibited. 11. Use suitable conduit caps to protect installed conduit against entrance of dirt and moisture during construction. 12. Complete installation of conduit before starting installation of conductors. 13. Comply with applicable requirements of NEC pertaining to installation of conduit systems. 14. Bond electrical boxes, fittings and enclosures to conduit to provide electrical continuity. B. Metal Conduit: 1. lnstall in locations as indicated. 2. Make all joints watertight by field-applied coat of vinyl plastic compound. C. Liquid-Tight Flexible Metal Conduit: 1. Use between RGS conduit and motor terminal boxes or other equipment subject to vibration. 2. Install at points of connection to equipment mounted on supports to allow for expansion and contraction. 3. lnstall at locations where rigid connections are impractical. 4. Use minimum length required for the application, not to exceed 3 feet unless otherwise approved by the Engineer. 5. lnstall an external bonding jumper to conform to NEC on conduit sized inches and larger. D. Rigid Nonmetallic Conduit: 1. lnstall at locations indicated. 2. Solvent weld PVC conduit joints with solvent recommended by conduit manufacturer. 3. Follow manufacturer's solvent welding instructions to provide watertight joints WIRES AND CABLES A. General Wiring Methods: 1. Install wires and cables of types, sizes and groups indicated and specified. 2. Use no wire smaller than #I2 AWG for feeder and branch circuits. Stranded wire unless otherwise allowed. 3. Use no wire smaller than #I4 AWG for 120 volt control circuits; stranded wire. 4. Unless otherwise indicated, use #I0 AWG for 20A, 120-volt branch circuits home runs longer than 60 feet and #8 AWG for runs longer than 130 feet. 5. Install separate neutral conductor for each branch circuit. Unless otherwise indicated, combining neutrals will not be permitted. 6. Neatly train and lace wiring inside boxes, equipment and panelboards. 7. Make wire lengths for parallel circuits equal. 8. Terminate spare conductors with electrical tape and roll up in box. B. Wiring Installation In Conduits:

6 Thoroughly clean and swab conduits before installing wire. Pull wires simultaneously where more than one is being installed in same conduit. Use UL listed wire pulling lubricant for pulling #4 AWG and larger. Use of soap, oil, or grease as pulling lubricant will not be permitted. Use pulling means including fish tape, cable, rope and basket weave wirelcable grips which will not damage wire or conduit. Do not subject cable to pulling tension in excess of manufacturer's recommendations. Attach pulling grips over the wire sheath to prevent slipping the cable insulation. Do not subject wire to bending radius of less than 8 times the wire outside diameter during or after installation. Sealing of Conduits: a. After wires are installed and connected, seal conduit ends by forcing non-hardening sealing compound into the conduits to a depth at least equal to the conduit diameter. Seal conduit ends at junction boxes, pull boxes and conduit connections to equipment. b. Provide NEMA 7 conduit seal with sealing compound in conduits entering corrosive or hazardous areas. C. Wiring Connections and Terminations 1. Keep conductor splices to a minimum. Splice only in accessible junction boxes. 2. Make splices with enough spare wire for a minimum of two splices to be remade with the wire. 3. Install splices which possess equivalent, or better, mechanical strength and insulation ratings than conductor being spliced. 4. Make splices, taps and connections to carry full ampacity of conductors without perceptible temperature rise. 5. Thoroughly clean wires before installing lugs and connectors. 6. Tighten electrical connectors and terminals, including screws and bolts, in accordance with manufacturer's published torque tightening values. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Standard 486A. 7. #I0 AWG and smaller, splice using permanently mounted terminal strips and ring tounge connectors. No more than 3 ring connectors will be permitted under 1 terminal. D. Electrical Identification: 3.03 BOXES 1. Feeder and Branch Circuits a. Provide color-coded markers for each conductor as specified in Part 2.06 A.1. this Section. b. Attach to each conductor in junction boxes, pull boxes, panelboards, switchgear enclosures and motor control centers. 2. Control Circuits: A. General: a. Tag each individual wire with marker as specified in Part 2.06 A.2. this Section. b. With terminal designation indicated on schematic diagrams or given on manufacturer's equipment drawings. I. Provide electrical boxes as indicated on the drawings, and as required for splices, taps, wire pulling, equipment connections and code compliance. 2. Coordinate with conduit installation work.

7 3. Locate and install boxes to allow access. 4. Fasten electrical boxes firmly and rigidly to substrates, or structural surfaces to which attached, or solidly embed in concrete or masonry. 5. Support boxes independent of conduit system. 6. Provide stainless steel boxes for outdoor locations. 7. Provide electrical connections for installed boxes. 8. Protect from construction debris and damage. B. Pull and Junction Boxes: 1. Provide pull and junction boxes of type and size indicated and specified WIRING DEVICES A. Provide wiring devices as indicated on the drawings and as specified. B. Install wiring devices only in electrical boxes which are clean and free from excess construction debris. C. Install wiring devices after wiring work is complete. D. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for wiring devices. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with the tightening torques specified in UL Standard 486A. E. Install device plates as indicated and specified. F. Unless otherwise indicated, install outdoor weatherproof receptacles: 2'-0" to 4'-0" above grade SUPPORT DEVICES A. Provide equipment supports as indicated on the drawings and as specified. B. Construct with sufficient rigidity to hold all mounted equipment and material in permanent and neat alignment FIELD QUALITY CONTROL A. Prior to energization of circuitry, check installed wiring with megohm meter to determine insulation resistance levels to ensure requirements are fulfilled. B. Prior to energization, test wiring for electrical continuity and for short-circuits. Ensure proper polarity of connections is maintained. C. Subsequent to completing wiring connections, energize circuitry and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units and then retest to demonstrate compliance. END OF SECTION

8 THIS PAGE INTENTIONALLY LEFT BLANK

9 SECTION SERVICE AND DISTRIBUTION PART 1 - GENERAL 1.01 SUMMARY A. Section includes electrical service and distribution systems including: 1. Service entrance. 2. Disconnect switches. 3. Secondary grounding. 4. Over-current protective devices. 5. Motor starters. B. Related Work: 1. Section Basic Electrical Materials and Methods C. References: 1. National Electrical Code (NEC). 2. National Electrical Manufacturers Association (NEMA). a. NEMA KS 1 - Enclosed Switches. b. NEMA AB 1 - Molded-Case Circuit Breakers. c. NEMA ICS 2 - Industrial Control Devices, Controllers and Assemblies. 3. Underwriter's Laboratories, Inc. (UL) SUBMITTALS A. Submit as specified in Section B. Furnish manufacturer's product data indicating electrical characteristics and verifying compliance with specified requirements. C. Furnish dimensional drawings of equipment including spatial relationship to proximate electrical equipment. D. Furnish power and control wiring diagrams. Clearly differentiate between portions of wiring that are manufacturer-installed and portions that are field-installed QUALITY ASSURANCE A. Where Underwriter's Laboratories, Inc. has established standards for specified products, provide only products bearing the UL label. B. Comply with NEC requirements as applicable to construction and installation of service and distribution systems. PART 2 - PRODUCTS 2.01 GENERAL: A. Provide service and distribution equipment and accessories of types, sizes, ratings and electrical characteristics indicated on the drawings.

10 2.02 DISCONNECT SWITCHES A. Acceptable Manufacturers: 1. Square D. 2. Cutler Hammer. 3. Allen Bradley. 4. Approved equal. B. Fusible and Nonfusible Disconnect Switches: 1. Heavy duty type conforming with NEMA KS Quick-make, quick-break, load interrupter, enclosed knife switch with externally operable handle interlocked to prevent opening front cover with switch in ON position. Handle lockable in OFF position. 3. Fused type where indicated. Designed to accommodate Class R Fuses. C. Enclosures: Provide NEMA Type 1 in interior locations and NEMA Type 3R in exterior locations, unless otherwise indicated on the drawings GROUNDING MATERIALS A. Conductors: 1. Solid copper in #6 AWG and smaller. 2. Stranded copper in #4 AWG and larger. B. Connections: 1. Above grade: Compression type bronze clamps or grounding lugs OVER-CURRENT PROTECTIVE DEVICES A. Acceptable Manufacturers: 1. Circuit Breakers: a. Square D. b. Cutler-Hammer. c. General Electric. d. Approved equal. 2. Fuses: a. Bussmann. b. Gould-Shawmut c. Approved equal. B. Circuit Breakers: 1. Factory assembled molded-case type conforming to NEMA AB Of electrical characteristics indicated on the drawings, with interrupting rating to meet available fault current. If available fault current is not indicated on the drawings, contact servicing utility. 3. Permanent thermal and instantaneous magnetic trips in each pole.

11 4. Provide fault current limiting protection to comply with series rated fault protection. 5. Constructwith over-center, trip-free, toggle-type operating mechanism with quick-make, quickbreak action and positive handle trip indication. 6. Provide push-to-trip button on cover for mechanical tripping circuit breakers. 7. Equip with mechanical screw type removable connector lugs for number, size and material of conductors indicated. C. Fuses: 1. Unless otherwise indicated on the drawings, provide UL Class RK5 current-limiting,time delay fuses with 100,000 RMS amperes interrupting rating for protecting service entrance, feeder or branch circuits of 600 amperes or less. Bussman FRN-R for 250 volt and FRS-R for 600 volt MAGNETIC MOTOR STARTERS A. Acceptable Manufacturers: 1. Square D 2. Cutler Hammer 3. General Electric 4. Approved equal B. Comply with applicable requirements of NEMA ICS 2. C. Open or enclosed, full voltage, non-reversing or reversing type as indicated. D. Electrical and mechanical interlocks on reversing starters to prevent both contactors from closing simultaneously. E. Provide with disconnect switch or thermal-magnetic circuit breaker in common enclosure where indicated or specified as combination starter. F. Enclosure: NEMA 1 indoors and NEMA 3R outdoors. G. Equip starters with block type manual reset overload relays. Provide with thermal units to match motor nameplate data. H. 120 volts, 60 hertz, coil operating voltage unless otherwise indicated or specified. I. Built-in volt control transformer on 480volt units of adequate capacity for all control devices as indicated on wiring diagrams. J. Provide auxiliary contacts as required by means of starter or relay. K. Provide operating handle for disconnect switch mechanism with indication and control of switch position, with enclosure door either opened or closed, and capable of being locked in OFF position. L. Accessories: 1. Push Buttons, Selector Switches and Pilot Lights: UL rated, heavy-duty, oil-tight type. 2. Auxiliary Relays a. 8 or 11 pin plug-in type relays and sockets. b. Coil voltage as indicated. c. Contacts rated 10 amperes up to 300 volts. d. Contacts as required for control of associated equipment 3. Timing Relays: a. Solid state plug-in type. b. Digitally adjustable timing range as indicated. c. On delay, off delay, or on-and-off delay as indicated. d. Contact arrangement as indicated. e. Contacts rated 5 amperes continuous at 75% power factor at 120 vac, except as otherwise

12 indicated. f. Operating voltage as indicated. g. Timing indication provided by LED which flashes during timing, glows steadily after timing, and is off when timer is de-energized ELECTRICAL IDENTIFICATION A. Engraved phenolic nameplates, black face with white core lettering, punched for mechanical fastening. B. Minimum size of 1" x 3" x 1/16" thickness with 318" letters. C. Stainless steel fasteners. D. Coordinate names and other designations with corresponding designations shown, specified or scheduled. Provide numbers, lettering or wording as indicated or approved by Engineer. PART 3 - EXECUTION 3.01 GENERAL A. Install service and distribution equipment, materials and devices as indicated, in accordance with the manufacturer's written instructions and with recognized industry practices to ensure that equipment, materials and devices fulfills requirements. B. Comply with applicable installation requirements of NEC and NEMA standards INSTALLATION OF DISTRIBUTION EQUIPMENT A. Install distribution equipment including disconnect switches, circuit breakers, starters and combination starters at locations indicated and as follows: 1. Surface mount on walls or support devices approximately 4 feet to center line above floor or grade when possible. Anchor enclosures firmly, ensuring that they are permanently and mechanically secure. 2. Arrange with proper clearances from other equipment and material to obtain accessibility for operation and maintenance. 3. Coordinate with installation of conduits and wires. B. Provide properly wired electrical connections within enclosures. C. Provide engraved phenolic nameplates on cover of each device identifying the loads connected. D. Provide type-written circuit directory card for existing panelboards upon completion of installation work INSTALLATION OF ELECTRICAL GROUNDING SYSTEM A. General: 1. Install grounding system as indicated on the drawings. 2. Ground metal conduits and electrical equipment. 3. Bond together system neutrals, service entrance enclosures, exposed non-current carrying metal parts of electrical equipment, metal conduit systems, grounding conductor in conduits and cables, and receptacle ground connectors. B. Connections: 1. Conform to manufacturer's instructions for grounding system connections. 2, Install clamp-on connectors only on thoroughly cleaned metal contact surfaces, to ensure

13 electrical conductivity and circuit integrity. 3. Make connections to equipment clean and tight to assure a low-resistance connection with resistance not exceeding 3 ohms. Install so as not to be susceptible to mechanical damage during operation or maintenance of equipment. C. Equipment Grounding Conductors: 1. Install a separate, continuous, insulated equipment grounding conductor in all feeder and branch circuits. 2. Route in same conduit as phase conductors. 3. Bond grounding conductor to all boxes and equipment enclosures through which they pass and at each end of conduit run by means of grounding bushings FIELD QUALITY CONTROL A. Upon completion of installation of distribution equipment, energize circuitry and demonstrate capability and compliance with requirements. B. Prior to energization of over-current protective devices, test devices for continuity of circuitry and for short-circuits. C. Upon completion of electrical connections and after circuitry has been energized with rated power source, test connections to demonstrate capability and compliance with requirements. Ensure that direction of rotation of each motor fulfills requirements. D. Where possible, correct malfunctioning units, then retest to demonstrate compliance. Otherwise, remove and replace with new units and retest. END OF SECTION

14 THIS PAGE INTENTIONALLY LEFT BLANK

15 SECTION PRE-WIRED MOTOR CONTROL PANEL PART 1 - GENERAL 1.01 SUMMARY A. Section includes devices, features, and installation requirements for pre-wired motor control panel to operate an existing duplex submersible sewage pump station as indicated on the drawings. Principal control panel components include the following: 1. Enclosure. 2. Starter units. 3. Disconnects. 4. Overload protection. 5. Over-current protection. 6. Accessory devices and features. B. Related Work: 1. Section Basic Electrical Materials and Methods 2. Section Service and Distribution C. References: 1. National Electrical Code (NEC). 2. National Electrical Manufacturers Association (NEMA): a. NEMA ICS 2 - Industrial Control Devices, Controllers and Assemblies. 3. Underwriter's Laboratories, Inc. (UL): 1.02 SUBMITTALS a. UL 486A - Wire Connections and Soldering Lugs for Use with Copper Conductors. A. Submit as specified in Section B. Submit manufacturer's technical product data indicating electrical characteristics and verifying compliance with specified requirements. C. Submit dimensional drawings of control panel showing basic layout of panel components. D. Submit power and control wiring diagrams. Clearly differentiate on wiring diagrams those conductors which are factory-installed and those which are field-installed QUALITY ASSURANCE A. Comply with requirements of NEC as applicable to motor control equipment and components. B. Coordinate with pump manufacturer to insure compatibility of pumps and control panel components. PART 2 - PRODUCTS 2.01 GENERAL: A. Provide pre-wired motor control panel to operate an existing duplex submersible sewage pump

16 station as indicated on the drawings. 1. Existing electrical service is volt, 3-phase, 4-wire. 2. Existing pumps are AuroralHydromatic Model S4NX200JB. B. Pump control panel shall be manufactured by a UL panel builder and the assembly shall bear a serialized UL label for "Enclosed Industrial Control Panels" CONTROL LOGIC A. Control system shall automatically start and stop pump motors in response to liquid level variations in the wet well through direct acting float switches (4-required). B. Rising Wet Well Level: The lead pump shall be started when the liquid level in the wet well rises to a predetermined elevation. The lag pump will be started and operate in conjunction with the lead pump when the liquid level in the wet well rises above the lead pump on elevation. The high level alarm system shall be activated when the liquid level in the wet well rises above the lag pump on elevation. C. Descending Wet Well Level: The high water alarm system will deactivate when the liquid level in the wet well descends below the lag pump on elevation. When the wet well level descends to a point below the lead pump on elevation, both pumps will be stopped. D. Active pump will alternate each pumping cycle. Normal alternation will occur when the lead pump stops. Include provisions to select automatic alternation or lock-in either pump in the lead position. E. Provide adjustable time delay relay (0-60 sec) to prevent simultaneous starting of pumps after power restoration. F. Provide intrinsically safe circuit extensions for float switches. G. The following conditions will cause an alarm which will be indicated at the control panel. 1. Seal Failure (Amber pilot light for each pump mounted on enclosure inner door). 2. High Wet Well Level (NEMA 4X red lexan alarm light mounted on top of enclosure) PANEL ENCLOSURE A. NEMA 3R, dead-front type suitable for rack mounting as indicated. Enclosure door shall be hinged with a continuous stainless steel hinge pin and secured with fast-operating clamp assembly. Equip with hasp and staple for padlocking. B. Provide removable inner swing panel fabricated of 14 gauge steel witkwhite enamel finish to accommodate specified operator controls and instruments. Panel shall have a minimum horizontal swing of 90 degrees and be held in the closed position with quarter-turn latches. Include bolted-on engraved name plates indicating functions of all operating controls and instruments. C. Provide removable back panel of 14 gauge steel with white enamel finish attached to enclosure with collar studs, to accommodate specified control components. Mount components securely to back panel utilizing screws and washers. Tap back panel to accept mounting screws. Do not use self-tapping screws to mount any components PANEL DEVICES AND FEATURES A. Equip panel with the following devices and features, logically arranged with separate power and control sections. Locate intrinsically area so that no other wiring comes within 2-inches of intrinsically safe wiring. Conform with applicable requirements of Sections and 16400, except as modified herein. 1. Main Disconnect:

17 a. Provide non-fused disconnect to interrupt incoming power supply to panel for maintenance or repairs. b. Operating handle operable without opening the inner swing panel. 2. Branch Circuit Breakers: a. Provide properly sized heavy duty thermal-magnetic trip circuit breakers for branch circuit disconnect service and short circuit protection of all motor, control and auxiliary circuits. b. Circuit breaker operating handles shall be operable without opening the inner swing panel. 3. Motor Starters: a. Provide properly sized NEMA rated magnetic motor starter for each pump motor. b. Furnish starter contacts which can be easily replaced without removing starter from its mounted position. c. Provide overload reset device operable without opening the inner swing panel. 4. Pump Selection Mode: a. Provide UL rated, heavy duty, oil-tight "H-0-A" switches for each pump motor. b. Momentary in hand position. c. Hand position not to override motor overload shutdown. 5. Alternator Relay: a. Provide relay of electronic design, plug-in type. b. Equip with 3-position selector switch to select automatic alternation or lock-in either pump in the lead position. 6. Elapsed Time Meter: a. Equip panel with elapsed time meter for each pump motor. b. Connect to motor starter to indicate total running time. c. Six digit, non-resettable type reading in hours and tenths of hours. d. Mount in inner panel swing door. 7. Pilot Lights: Equip panel with UL rated, heavy duty, oil-tight pilot light indicators for each pump as follows: a. Run, green light. b. Seal failure, amber light. 8. AudioNisual Alarm: Provide audio/visual alarm system to signal high water level. System to be activated by a "fault closing" contact initiated by a float switch installed in pump station wet-well. Alarm system to reset automatically when alarm condition has been cleared. a. Audible Alarm Device: Vibratone horn or bell suitable for outdoor mounting with an audio output of at least 85 db. b. Visual Alarm Device: Vapor-proof light fixture with at least 50 watt lamp suitable for outdoor mounting with red globe and guard. 9. Push Buttons: Equip panel with UL rated, heavy duty, oil-tight push buttons for the following

18 functions: a. Test seal failure detection system. b. Test high level alarm system. c. Silence audible alarm. 10. Lugs and Terminal Blocks: a. Provide tin or silver plated copper lugs for connection of incoming power supply and pump power leads. b. Provide terminal blocks suitable for use with locking fork or ring tongue connectors for control inputs/outputs. c. Mount lugs and terminal blocks to allow wire bending space in accordance with NEC. d. Locate such that no field wiring will cross factory wiring. 11. Wiring: a. Control panel shall be completely factory wired, except for field connections. All wiring, workmanship, and schematic wiring diagrams shall conform to applicable NEC standards. b. All user serviceable wiring shall be type THHNITHWN, 600 volts, stranded copper, color coded as follows: 1) Line and Load Circuits, AC powerblack 2) AC Control Circuits Less Than Line VoltageRed 3) Equipment Grounding ConductorGreen 4) Current Carrying GroundWhite 5) Hot with Circuit Breaker Openorange 6) Intrinsically Safe CircuitsBaby Blue c. Wire Identification and Sizing: 1) Control circuit wiring inside panel, except internal wiring of individual components, shall be 14 gauge minimum. Power wiring shall be 12 gauge minimum. 2) Wires shall be clearly numbered at each end in accordance with the schematic wiring diagram. d. Wire Bundles: 1) All internal wiring shall be neatly routed in bundles and tied in accordance with good commercial practice. 2) Bundles routed to components mounted on inner swing panel shall be made flexible at the hinged side. Provide adequate length and flex to allow swing panel to fully open without undue stress or abrasion on the wire or insulation. Secure bundles in place on each side of hinge with mechanical fastening devices. e. Schematic Wiring Diagrams: 1) Provide a laminated electrical schematic diagram of the pump controls including terminal block connections. 2) Permanently mount on the inside of the enclosure door.

19 2.05 SPARE PARTS A. Provide the following spare parts: 1. One Alternating Relay. 2. One Control Relay (Each Type Used). 3. Three Fuses (Each Size and Type Used). B. Packaged for long term storage and properly labeled for easy identification. PART 3 - EXECUTION 3.01 INSPECTION A. Examine area and conditions under which motor control panel is to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to installer INSTALLATION A. Install motor control panel as indicated, in accordance with manufacturer's written instructions and with recognized industry practices to ensure that equipment fulfills requirements. B. Coordinate with other electrical work including conduit and wiring work, as necessary to interface installation of motor control panel with other work. C. Provide all necessary materials, components and adjustments as required for a complete and operating pumping system. D. Make all electrical and control connections. E. Tighten connectors and terminals, including screws and bolts, in accordance with manufacturer's published torque tightening values for equipment connectors. Where manufacturer's torque requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL standard 486A GROUNDING A. Provide equipment grounding connections for motor control panel as indicated. B. Tighten connections to comply with tightening torques specified in UL Standard 486A to assure permanent and effective ground FIELD QUALITY CONTROL A. Prior to energizing motor control panel, check with insulation resistance tester for proper values of phase-to-phase and phase-to-ground insulation resistance. B. Subsequent to completing wiring connections, energize motor control panel, check each motor for proper phase rotation and demonstrate capability and compliance with requirements. C. Make all necessary equipment adjustments and corrective work indicated by tests. Repeat testing as necessary. END OF SECTION

20 THIS PAGE INTENTIONALLY LEFT BLANK

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION SANITARY SEWAGE PUMP STATIONS

SECTION SANITARY SEWAGE PUMP STATIONS SECTION 11303 SANITARY SEWAGE PUMP STATIONS PART 1 GENERAL 1.1 DESCRIPTION: This work shall include the construction of a sewage pumping station complete with all pumping and electrical equipment, all

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

MN/DOT SPECIFICATION FOR A ROADWAY LIGHTING SERVICE CABINET

MN/DOT SPECIFICATION FOR A ROADWAY LIGHTING SERVICE CABINET MN/DOT SPECIFICATION FOR A ROADWAY LIGHTING SERVICE CABINET LIGHTING SERVICE CABINET TYPE: L1 & L2 02/02 /2012 Page 1 of 21 SPECIFICATIONS FOR L1 & L2 LIGHTING SERVICE CABINETS Table of Contents 1. General

More information

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications:

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications: CONTROLLER CABINETS, POLE MOUNTED - Item No. Special Provision No. 682S27 June 2017 1. SCOPE This Special Provision covers the requirements for the installation of pole mounted controller cabinets and

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

CADDY CORPORATION. Utility Distribution Systems

CADDY CORPORATION. Utility Distribution Systems Food Service Equipment Air Systems Utility Distribution Systems page 1 of 2 Equipment Specifications General Specifications Caddy Corporation of America Energy Distribution and Management System, which

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

METRO SEWER DISTRCT (MSD), CINCINNATI, OHIO DETAILED PROVISIONS FOR ELECTRICAL PUMP CONTROL PANELS FOR PUMP OR LIFT STATIONS

METRO SEWER DISTRCT (MSD), CINCINNATI, OHIO DETAILED PROVISIONS FOR ELECTRICAL PUMP CONTROL PANELS FOR PUMP OR LIFT STATIONS METRO SEWER DISTRCT (MSD), CINCINNATI, OHIO DETAILED PROVISIONS FOR ELECTRICAL PUMP CONTROL PANELS FOR PUMP OR LIFT STATIONS PART 1 - GENERAL 1.01 Scope A. The contractor shall furnish all labor, materials,

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

SECTION 4000 LIFT STATIONS

SECTION 4000 LIFT STATIONS SECTION 4000 LIFT STATIONS LIFT STATIONS PART 1 GENERAL 1.01 Section Summary A. Lift station control panels. B. Related requirements include those established in the General Requirements Division 1, Division

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing piping heat tracing for freeze prevention, domestic hot-water-temperature maintenance, and

More information

MEDIUM, LOW AND CONTROL VOLTAGE CABLES

MEDIUM, LOW AND CONTROL VOLTAGE CABLES Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

GRUNDFOS SEWAGE & EFFLUENT PUMP ACCESSORIES

GRUNDFOS SEWAGE & EFFLUENT PUMP ACCESSORIES GRUNDFOS SEWAGE & EFFLUENT PUMP ACCESSORIES GRUNDFOS CONTROL PANELS Simplex Panel Duplex Panel Standard Features LISTING: Underwriters Laboratories, UL 508. RATINGS: Model S1 rated up to 120 VAC, 1 Hp,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

Custom Duct Heaters. Special Applications

Custom Duct Heaters. Special Applications Special Applications Air Conditioning & Air Handling Units For more than 55 years, INDEECO has been supplying special heaters for use in air handling and air conditioning equipment (Figure 49). A wide

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

Job No A. Submit the following equipment, materials and products, including all fittings and accessories:

Job No A. Submit the following equipment, materials and products, including all fittings and accessories: SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS SECTION 23 22 23 - STEAM CONDENSATE PUMPS PART I - GENERAL 1.1 SECTION INCLUDES A. Steam Condensate Return Units, Gravity Return Type 1. Receiver 2. Pumps 3. Control Panel 4. Accessories Note to PSC: Although

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Custom Duct Heaters. Special Applications

Custom Duct Heaters. Special Applications Special Applications Air Conditioning & Air Handling Units For more than 50 years, INDEECO has been supplying special heaters for use in air handling and air conditioning equipment (Figure 50). A wide

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

SECTION COOLING TOWERS

SECTION COOLING TOWERS SECTION 23 65 00 COOLING TOWERS PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged, induced draft open circuit cooling tower complete with fill, fan, inlet louvers and associated accessories and equipment. 1.2

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER TABLE OF CONTENTS 1. Warnings...................................................... 3 2. Component Match-Up...........................................

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5

More information

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP RV Products Division INSTALLATION INSTRUCTIONS FOR 46515 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings.................................................. 2 2. Component

More information

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE:

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation.

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation. Brochure# 228E 122011 TYPE VSA SEWAGE PUMP Capacities to 100 gpm, Heads to 120, Horsepower range 3/ thru 0, 3 thru discharge, 1750 and 1150 operation. HIGHLIGHTS Wet-Pit Installations Pumps Suspend From

More information

DIVISION 16. ElECTRICAl

DIVISION 16. ElECTRICAl DIVISION 16 ElECTRICAl SECTION 16030 ELECTRICAL POWER SYSTEM STUDIES PART 1 -GENERAL 1.01 SUMMARY A. Section Includes: 1. Short circuit study, protective device evaluation study, protective device coordination

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 260500 - BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................

More information

Electricity Unit Notes. Agriculture Mechanics I

Electricity Unit Notes. Agriculture Mechanics I Electricity Unit Notes Agriculture Mechanics I Principles of Electricity Electricity is a form of energy that can produce light, heat, magnetism, chemical changes Resistance: tendency of a material to

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information