Fire Risk Assessment 2017

Size: px
Start display at page:

Download "Fire Risk Assessment 2017"

Transcription

1 Document Ti tle Fire Risk Assessment 2017 Wolverhampton Homes Campion House Hi-Rise Hobgate Road Wolverhampton WV10 0PU WHF FRA th February 2017

2 Fire Risk Assessment 2017 Project no: BU 89800T Task 022R Document title: Fire Risk Assessment Document o.: WHF FRA Revision: A Date: 13 th February 2017 Client name: Wolverhampton Homes Client no: ADO Project manager: Lisa Long Author: Sam Bunch G.I. Fire E, Dip FMS File name: Campion House Hi-rise Jacobs UK Ltd 95 Bothwell Street Glasgow G2 7HX Copyright The concepts and information contained in this document are the property of Jacobs. Use or copying of this document in whole or in part without the written permission of Jacobs constitutes an infringement of copyright. Limitation: This report has been prepared on behalf of, and for the exclusive use of Jacobs Client, and is subject to, and issued in accordance with, the provisions of the contract between Jacobs and the Client. Jacobs accepts no liability or responsibility whatsoever for, or in respect of, any use of, or reliance upon, this report by any third party. Document history and status Revision Date Description By Review Approved A FRA report S Bunch C. Pritchard S Bunch 2 WHF FRA Campion House

3 Contents 1 Introduction 5 2 Record of Assessments 8 3 Property Overview 9 4 Occupancy Summary 11 5 Assessor Summary of Findings 12 6 Risk Assessment Grading 14 7 Findings and Action Plans High Priority 15 8 Findings and Action Plans Medium Priority 16 9 Findings and Action Plans Low Priority and Recommendations Audit Information Life Safety Issues Disability Issues Ignition Sources Electrical Safety Security and Arson Control Fuel Sources COSHH and Hazardous Materials Hi Flams and DSEAR Compartmentation Fire Doors Means of Escape - Internal Means of Escape - External Firefighting Equipment Fixed Firefighting Installations Smoke and Ventilation Systems Fire Evacuation Lift and Firefighting Shafts Fire Warning System Management of Fire Safety 38 3 WHF FRA Campion House

4 29 Statutory Training Evacuation Procedures Emergency Plan, Threat Procedure and Firefighting Plan Photographic References 42 4 WHF FRA Campion House

5 1 Introduction 1.1 Scope and Purpose Jacobs U.K. Ltd has been appointed by Wolverhampton Homes to conduct a non-intrusive fire risk assessment and where appropriate, identify the significant findings and make recommendations and / or action plans in order to assist the Responsible Person in meeting their obligations under the Regulatory Reform (Fire Safety) Order 2005 (RRFSO) to the extent of responsibility for premises or parts of premises falling under its control This Fire Risk Assessment has been prepared and presented by Sam Bunch, Dip FMS, G.I. Fire E, Fire Safety Consultant, Jacobs U.K. Ltd. Contact or at The sole purpose of this report is to provide an assessment of the risk to life from fire, and to assist Wolverhampton Homes in reducing the risk of fire to which the property may be exposed It is not an acceptance of responsibility for any acts, defects or omissions which could lead to a fire situation and subsequent loss. 1.2 Legislation The applicable legislation is the Regulatory Reform (Fire Safety) Order The RRFSO essentially replaces repeals or amends all previous fire regulations and laws, for all buildings, other than those where the HSE or the local authority is the enforcing authority or where the Control of Major Accident Hazard Regulations (COMAH) applies The aim of the RRFSO is to consolidate the general fire safety precautions of various parts of legislation. The legislation places the responsibility for enforcing fire precautions within buildings on the local Fire Authorities. The responsibility for enforcement is retained by the HSE for nuclear, shipbuilding and construction A risk-based approach is required under the RRFSO, in contrast to the prescriptive process previously imposed. The RRFSO requires that the Responsible Person should undertake a fire safety risk assessment, such that it can be demonstrated that the fire safety precautions are adequate and maintained to reduce the exposure of relevant persons, see article 8 below: the responsible person must (a) take such general fire precautions as will ensure so far as is reasonably practical the safety of its employees and (b) in relation to relevant persons who are not in their employ as may reasonably be required to ensure the premises are safe The Responsible Person can be defined as the owner, occupier, employer or person(s) in control of the building, whilst the relevant persons are described in the RRFSO as:- Any person who is or may be lawfully on the premises, and also any person in the immediate vicinity of the premises who is at risk from a fire in the premises, other than fire-fighters at the time of a fire. 5 WHF FRA Campion House

6 1.2.5 Under the RRFSO, it is required that the following information is stored and available for inspection onsite or be available: The Fire Risk Assessment; Where actions are required, proof of completion; Record books detailing the preventative and proactive measures and any arrangements associated with fire safety; planning, organisation, control, monitoring, review etc.; Staff training; Previous Fire Events; Dates of Fire Risk Assessment and reviews. Copies of equipment test certificates Under the RRFSO a risk assessment is also required to be undertaken to areas in block of flats and maisonettes; refuges; student halls of residence; the common areas of HMOs and sheltered accommodation where care is not provided. 1.3 Management Structure The responsibility for the development and implementation of the fire safety policy rests with the Responsible Person. However, responsibilities are frequently delegated to other persons and the management structure is detailed below All employees must be familiar with their duties, and the procedures to be followed in the event of a fire. Typically, these will be explained in detail during the staff / HSE induction. For this purpose, members of staff should be provided with adequate training A detailed list of fire safety responsibilities, along with the person responsible and details of any delegated persons should be provided alongside this document. 6 WHF FRA Campion House

7 1.4 Limitations and Exclusions The information and advice detailed within this report has been compiled following the principles of Publicly Available Specification; PAS79, and is considered to present a suitable level of fire safety taking in account the complexity of the building, proposed occupancy levels and local conditions. This report should be fully understood by the Responsible Person and the findings actions highlighted to be addressed within the timescales identified Unless explicitly stated this report does not include detailed evaluation of any fire protection equipment in terms of its adequacy or reliability, nor has the integrity of fire compartmentation been verified It is not considered practical for many older buildings to achieve full compliance with the current Building Standards due to their age and structural form. Consequently, the actions identified and recommended within this report should not be interpreted as a means of achieving compliance, but as a method of reducing risk and enhancing Life Safety and property protection This report does not address the risk to business continuity from fire The assessment relies on information gained from the site visit and provided to the assessor by Wolverhampton Homes Property Services from their associated maintenance records and during the course of the site visit on This fire risk assessment covers the conditions of the property on the day of the evaluation and from additional sources provided to the assessor by Wolverhampton Homes and does not necessarily apply to changes in conditions made after that date It is the Wolverhampton Homes responsibility to keep the fire risk assessment up to date if suspected to be no longer considered valid or if significant changes have taken place Where relied upon by any other party or used for any other purpose, such parties rely upon this document do so at their own risk It is considered reasonable to assume that the works to be completed will be in line with the recommendations of this report and be carried out with appropriate materials and in a competent manner. 7 WHF FRA Campion House

8 2 Record of Assessments Date of Assessment 15/2/2007 Reason for Assessment Initial assessment. Comments Issues identified for action and improvement. ame of Assessor Sam Bunch Signed Review of previous FRA. Minor issues identified for improvement. Sam Bunch FRA review. Minor issues identified for improvement. Sam Bunch 8/03/2013 Review and re-write of FRA. Issues identified for action and improvement. Sam Bunch FRA review Issues identified for action and improvement. Sam Bunch Review of FRA. Issues identified for action and improvement. Sam Bunch Review of FRA. Issues identified for action and improvement. Sam Bunch Review of FRA. Issues identified for action and improvement. Sam Bunch 8 WHF FRA Campion House

9 3 Property Overview Brief Description of Property & Construction Detached, steel framed hi-rise block, flat roofed with concrete floor separation and external cladding. Each upper floor common landing gives access to five residential flats, riser cupboard, meter cupboard, bin chute hopper within separate room, lift and single circulation stairwell. The topmost floor has no access to the lifts. The ground floor contains the residential flats, the electrical distribution riser cupboard, bin store, laundry room, former Concierge offices, communal storage area and main electrical intake room (accessed externally from the rear).. Twenty one o of Stairs One Approximate Floor 400 o of Floors inc. basement o of Basement levels one Location(s) and Use(s) of stairs Area covered by this Assessment Internal circulation stair accessing all floors from ground level, discharging to open air via main entrance at front and directly out at rear of property. Footprint Area (sq. m) Purpose Group/ Occupancy/Use(s) Residential All fire safety systems and their management, all accessible common areas including floor landings, stairwell, sprinkler cupboard, bin store, riser cupboards and main electrical intake room where access is available. Procedures and statutory notices are also considered. The residential areas are excluded, except for the main flat entrance doors which open onto the common landing, as domestic premises are not subject to the Fire Safety Order. Evacuation Strategy (including Provisions for Disability) The property is a hi-rise residential block. o common fire warning systems are provided which is consistent with the residential use. Localised automatic detection may be provided within each residence but this is not interconnected between individual flats. In the event of fire occurring, a stay put policy has been promoted by Wolverhampton Homes where residents will not evacuate unless directly affected by fire or smoke. 9 WHF FRA Campion House

10 Property Safety Strategy Physical separation between individual flats and common areas reduces the potential for fire spread and imperforate structural protection to the stairwell maintains the availability of the circulation stair for evacuation and firefighting access. Significant firestopping works have taken place to further prevent the passage of fire and smoke. This has included the installation of intumescent seals to the stairwell and landing doors, the sealing up of vertical shafts and the infill of gaps within cupboards. Fire Scenario The likelihood of accidental fire occurring within the communal areas is very low due to the lack of potential ignition sources and fuels. The electrical distribution cupboard contains a viable ignition source but this is considered to be a low risk. The potential for fire is greater within the residential properties where uncontrolled activities are permitted, i.e. cooking and smoking. If a fire occurs within a residence, the alarm will have to be raised locally and the Fire and Rescue Service contacted via 999. Fire spread into the communal areas will be restricted provided the flat entrance door is kept closed. Unless extinguished, fire will continue to develop within the area of origin until positive intervention by the attending Fire and Rescue Service. Any fire occurring in the parts of the ground floor protected by the sprinklers (where present) would be identified and actively controlled and / or extinguished. 10 WHF FRA Campion House

11 4 Occupancy Summary Person responsible for Fire Safety Myk Kaszuba Person responsible for Fire Safety Maintenance Programme Designation Stock Investment Manager, Wolverhampton Homes Designation Wolverhampton Homes Property Services Person providing Designation assessment information Wolverhampton Homes Property Services Contact Details Office Mobile Other Contact Details Office Mobile Other Contact Details Office Mobile Other ame of Owner(s) Occupier(s) Location Activity Wolverhampton Homes Whole of premises. Residential block of 103 flats Persons Present - Max os. (approx.) Daytime / Silent Hours Employees oung Persons Members of Public Tenants <2 0 Variable <250 (Occasional) Persons at Risk Location Activity Reason and umbers Sleeping Disability Remote Location Other Contractor Lift motor room Maintenance / Repair 0 <2 Lift motor room 0 11 WHF FRA Campion House

12 5 Assessor Summary of Findings Risk Category Summary of Provision Qualifying Comments Risk to Life Risk to Life is assessed as LOW. o significant issues identified. Risk to Firefighters Risk to Life is assessed as LOW. o significant issues identified. Risk to Property Risk to Property is assessed as LOW to Compartment breaches present within the ground floor. MEDIUM. Risk of Fire Risk of accidental fire is assessed as LOW. o significant issues identified. Risk of Fire Spread Risk of fire spread is assessed as LOW. Residual Risks The residual risks found are Compartmentation breaches at first floor. The residual risk control measures are one. Overall Summary The overall grading for this property has been assessed as LOW to MEDIUM. Findings which impact on the fire safety strategy have been listed for action at Sections 7-9 of this report. Implementation of these actions will maintain or further reduce the overall grading. For tenants with disability, particularly those with limited mobility, the stairwell area; not the lobby approach could be used as a temporary refuge provided they move across the landing towards the flight leading to the next level to await arrival of the Fire and Rescue Service. This will allow firefighters free access onto the affected floor with their equipment. It may then be necessary for tenants to move out of the stairwell onto the floor(s) below or above but this may involve assistance and direction from the Fire and Rescue Service personnel. This advice should be discussed with the Fire and Rescue Service before being published among tenants. The individual flat entrance doors are in the process of having self-closing devices installed as part of the new Decent Homes, Halo doorsets. The advice contained within the Fire safety in purpose built blocks of flats as published by the Local Government Group advises that these be installed. These doors will normally be in the closed position for security and privacy thereby providing protection to and from the communal areas. While there is an identifiable benefit in automatically ensuring that the door closes following evacuation in the event of fire, there is also a potential for accidental lock out and high opening pressures which may make access and egress difficult for elderly or disabled residents however as there is a stay put policy in place, the provision of self-closers further reduces the risks to occupiers by ensuring that the potential for smoke and fire spread is minimised. 12 WHF FRA Campion House

13 Additional Recommendations The recommendations from the findings of the Coroners Inquests into the hi-rise fires at Lakanal House, London and Shirley Towers have been reviewed and the following additional recommendations are made which are to be considered as common guidance to all hi-rise properties within the Wolverhampton Homes portfolio:- 1. All cabling in communal areas and within residential properties should be secured using fire rated clips and/or metal fastenings unless stored within metal cable trays mechanically fixed to the ceiling above. This work is ongoing within Campion House and involves the communal areas including the landing, the riser cupboards and one of the protected corridors to the stairwell. 2. All physical alterations which impact on the fire safety measures should be reviewed at design stage. This would allow a review of the materials used as well as any changes to structural layout. 3. Provision of low level floor identification signage to be made at all points of floor entry with additional low level directional exit signage. Preferably this signage would also be photo-luminescent. 4. Provision of site specific information systems for each block. This could be externally placarded information or an internal information box. The method of information provision and the range of information to be made available will be decided following discussions with the Fire and Rescue Service. While there is a recommendation that the existing sprinkler system be extended to cover all of the communal areas on the ground floor, the recommendation for retrospective sprinkler installation in all areas of hi-rise buildings over 30m is still being reviewed internally as this has extensive logistical and budget implications. Assessment Review Period Anticipating that the significant findings will be actioned and this FRA updated, it is recommended that the frequency of review for this property is Annually or earlier if required. Any changes e.g. Use, Staff profile, structural alterations or other change which may affect the outcomes of this assessment may require it to be reviewed immediately. All new findings identified must be actioned and the FRA updated accordingly. 13 WHF FRA Campion House

14 6 Risk Assessment Grading Gradings HIGH PRIORIT MEDIUM PRIORIT LOW PRIORIT OT APPLICABLE The grading reflects the most significant finding within the category. Other, less urgent issues may also have been identified and should be addressed. Major Improvement required within a short timescale. Signifies risk to life or property or failure to observe statutory requirements. Minor Improvement required within short to medium term timescale. Signifies minor infringement or poor process. Minor improvement recommended. Actions are not necessarily statutorily required but would improve the culture and effect of the fire safety strategy. o fixed timescale but should be considered medium to long term. The information required in this section does not apply to this particular property. 14 WHF FRA Campion House

15 7 Findings and Action Plans High Priority Report and Photo Reference Photo ref 01 and 02. Significant findings Gaps in the compartment walls above the suspended ceiling tile level within the ground floor have not been firestopped. Urgent Action Required The Contractor must ensure that effective firestopping is made and maintained at all times, particularly to the openings created above the suspended ceiling height. A review of the whole of the area should be carried out and all openings infilled. Date Corrective Action Completed ed Myk issues Send issues to Mac/Wilson Signed SCP Outstandin g The gaps should be infilled using appropriate materials and methods. Gaps <40mm may be infilled with intumescent mastic (not expanding foam). Gaps <40mm will require infill using a solid material in order to restore the fire separation. A methodical inspection of the firestopping throughout should also be undertaken when the current works have been completed and all deficiencies made good and certified. 15 WHF FRA Campion House

16 8 Findings and Action Plans Medium Priority Report and Photo Reference Significant findings The following doorsets are original installations whose fire rating is unknown. Floor 6 flats Floor 11 flat Floor 13 flat Floor 17 flat. Prompt Action Required While considered reasonably robust and compliant with the standards at the date of initial installation, the fire rating of these doors, doorframes and associated hardware is unknown. Verification of the fire rating of the doorset is required. Where necessary, upgrading of the door, doorframe and hardware is required to achieve a minimum resistance to fire of 30 minutes in accordance with BS476, so as to provide a consistency of protection to the communal areas in line with the other flats throughout the City. Date Corrective Action Completed Signed Programm e If any of the flats is owner occupied, the leaseholder should provide evidence that their doorset meets this minimum requirement otherwise replacement will be required The following doorsets are original installations whose fire rating is unknown and had the surrounding facings removed. Floor 6 flat Floor 13 flat Floor 17 flat The door facings should be re-instated to restore the fire separation between the residence and the communal areas. Before re-instatement, the gaps within the door framework should be infilled with approved fire resistant materials and methods. Gaps <40mm may be infilled with intumescent mastic (not expanding foam). Gaps <40mm will require infill using a solid material in order to restore the fire separation. Programm e 16 WHF FRA Campion House

17 The following fire doors do not close onto the doorframe and require repair: Floor 14 Stairwell door Floor 16 Lobby fire door at flat Floor 18 - stairwell door at flat Floor 19 Stairwell door at flat The fire doors should be repaired by a competent person in order that each door is made tight fitting in its frame and maintained effectively self-closing from all angles of swing. R&M Outstandin g The self-closing device had been disconnected from the fire door leading from the lift foyer to the Sprinkler / Tank room Floor mats present at flats These did not conform to the Wolverhampton Homes accepted standard Faults identified during the latest Emergency lighting discharge testing. o information on remedial works Latest test date recorded on the CO₂ extinguisher within the main electrical room as done September The self-closing device should be re-fitted to ensure that the door closes fully onto the doorframe from all angles of swing. The mats should be removed and guidance on the latest approved standard acceptable to Wolverhampton Homes should be given to the occupiers to assist them in identifying a suitable replacement. The lighting units identified as defective should be repaired by competent persons to assist evacuation and movement of occupants in the event of mains failure. Record of actions taken should be recorded to provide an audit trail and to demonstrate positive reaction to Fire Safety issues. All portable extinguishers which have not been tested in the last 12 months should be subjected to examination by a competent Contractor as soon as practicable and included in an ongoing testing regime thereafter. The date and result of such tests should be clearly indicated on each extinguisher or on attached tabs or labels and in the Fire Safety Log Book. R&M Outstandin g Housing manageme nt Outstandin g C&C Outstandin g C&C Outstandin g 17 WHF FRA Campion House

18 9 Findings and Action Plans Low Priority and Recommendations Report and Photo Reference Significant findings The existing sprinkler installation covers parts of the ground floor areas only and excludes the main entrance and lift lobby. Identified in previous FRA. Long Term Action Required In light of the deliberate fire at Longfield House which severely affected the lift lobby, consideration should be given to extending the existing sprinkler system to provide additional discharge heads throughout the ground floor area. This work should be carried out by competent and experienced contractors following a survey of the floor space. Date Corrective Action Completed Signed Previous assessment findings have not been actioned and completed. Records of actions taken in order to achieve compliance or to reduce hazards and risks or to correct identified shortcomings should be available for inspection. See Low Priority issue re. sprinkler installation. Reasons for not addressing issues should also be recorded. This will provide an audit trail of decisions; demonstrate compliance with requirements and a positive commitment to Fire Safety within the workplace A Firefighting Plan containing property specific information is not provided or immediately accessible. Refer to Section 5 Assessors Summary and specifically Additional Recommendations. Identified in previous FRA. 18 WHF FRA Campion House

19 10 Audit Information The following information was gathered during the assessment process and is subject to change due to changes in occupancy, use, structural alteration etc. All subject areas should be re-visited during any re-assessment process to identify a new overall assessment outcome. 11 Life Safety Issues 11.1 Areas to Assess Assessor Comments There are persons at significant risk within the property Staff work out of hours or are lone working Where necessary, compensatory measures are provided oung persons are employed oung persons Risk Assessments have been carried out Parents/guardians have been informed of the Risk Assessments and outcomes Compensatory measures are provided and/or implemented There are existing risks to Firefighters Visitors and Contractors are controlled Residential use only. 19 WHF FRA Campion House

20 12 Disability Issues 12.1 Areas to Assess Assessor Comments An Equality Act Access Assessment has been carried out There are persons who require additional assistance in emergency situations within the property Compensatory measures have been provided e.g. PEEPs, Refuge Areas, Contrasted Markings etc. A defend in place policy has been produced and practised Fire evacuation procedures consider disabled personnel Staff have been trained in disability escape etiquette Disability specific signs are in place e.g. to indicate wheelchair routes to refuge areas etc. The need to support the evacuation of visually impaired persons has been considered and procedures established Hearing impaired occupants can readily identify the fire warning system actuation. People with Cognitive disorders have been considered, procedures established and people informed There are management procedures for reviewing temporary disability of staff e.g. through pregnancy, injury Undertaken by Jacobs in October Stay put policy in place unless directly affected by fire or combustion products. o fire warning system provided in the communal areas or considered necessary for this residential block. 20 WHF FRA Campion House

21 13 Ignition Sources 13.1 Areas to Assess Assessor Comments Significant potential Ignition sources are present There are significant potential ignition processes in use Process control measures are in place one within communal areas assessed. Significant ignition sources are present within the residences e.g. cooking and smoking Gas-powered appliances are in use o gas present within the block Gas appliances are tested by Gas Safe Registered Engineers and current Gas Safety Records are available Where internal flues are present, access hatches are available to permit inspection CO detection is present where internal flues are located Where fitted, cooking filters and ductwork are maintained regularly Space heating method is appropriate o Smoking signs are visible Suitable provisions are made for smokers Smoking is unrestricted within the residences There are signs of breaches of policy There is an identified smoking room provided (England only) There is lightning or earthing control It is tested and records maintained in accordance with BS 6651 BS7430 Ongoing test regime managed by Wolverhampton Homes Property Services. Latest test recorded as due WHF FRA Campion House

22 Contractors are regularly monitored during work Contractors work methods are pre-approved (hot work permits, SSOW) Checked by Wolverhampton Homes as part of their approval process. 14 Electrical Safety 14.1 Areas to Assess Assessor Comments Electrical equipment is appropriate to the use of the property and is not misused Electrical equipment is operated by time switches Portable electrical equipment has been inspected on a regular basis and results recorded Portable electrical equipment within hi flam areas has been inspected every six months or more frequently where their age, condition or use warrants it and results recorded There is a register of miscellaneous electrical equipment available, There is evidence of overloading of electrical sockets or extensive use of cable drums, multi way extensions or transformer plugs There is a policy on the use of personal electrical appliances The fixed electrical installation is checked regularly in accordance with current IEE Regulations Electrical Circuits and fixed electrical Equipment in use within Hi Flam areas is tested annually one present in communal areas. one present within the communal areas. Ongoing PPM in place organised by Property Services, Hickman Avenue. Upgrading work to the electrical supply system was still in progress under the Strategic Construction Partners programme at the date of this reassessment. 22 WHF FRA Campion House

23 Records of testing are maintained and available Defects noted during testing have been rectified Cupboards containing Main Electrical Distribution boards are free from combustible storage or the storage is so positioned as to pose a low risk of fire A luminous discharge tube is present Where a luminous discharge tube is present, a Firemans cut off switch is provided and clearly indicated Where static electricity is a risk, there are adequate control measures Latest test date recorded on equipment as All records held centrally by Wolverhampton Homes Property Services. 23 WHF FRA Campion House

24 15 Security and Arson Control Areas to Assess Assessor Comments The property has experienced fires or other incidents in the previous 12 months o visible signs of recent fire activity noted. All incidents have been investigated and recorded Combustible materials are stored in close proximity to the building There is a regular, routine check of Fire Undertaken daily by Concierge staff. Safety measures undertaken Safety Check findings are recorded and Records maintained by Concierge staff. identified problems corrected Access to the site and / or property is Electronic entry system with fob control in place. effectively controlled There is CCTV or physical monitoring External CCTV provided and monitored remotely by Concierge staff. Tapes/discs are kept for a minimum of 30 days The property is enclosed by a fence or wall Fences and gates are in good repair Gates / perimeter access points are suitably protected to prevent unauthorised access but permit egress 24 WHF FRA Campion House

25 16 Fuel Sources 16.1 Areas to Assess Assessor Comments The standard of general housekeeping is adequate Fuel sources and ignition sources are kept apart There are significant potential sources of Fuel one found present within communal areas There are accumulations of unnecessary combustible materials or waste Soft furnishings have compliant upholstery finishes There are sources of Oxygen or supporters of combustion, apart from ambient air There are potential sources of dust ignition o furnishings permitted within the assessed communal areas. 25 WHF FRA Campion House

26 17 COSHH and Hazardous Materials 17.1 Areas to Assess Hazardous chemicals are present Assessor Comments Suitable arrangements are in place to manage the elimination or reduction of risks from hazardous substances Hazardous chemicals are effectively controlled during use and in storage Waste materials are adequately controlled Suitable and appropriate signage is present Material safety data sheets are available Emergency procedures inc. details of A and E services are available Appropriate PPE and/or specialised equipment are available as necessary Staff members are aware of the materials, the data sheet contents and safety procedures 26 WHF FRA Campion House

27 18 Hi Flams and DSEAR 18.1 Areas to Assess Hi flam substances are present Assessor Comments They are effectively controlled during use and storage The Dangerous Substances and Explosive Atmospheres Regulations 2002 apply Where DSEAR applies, a risk assessment been carried out and records maintained available (Written - if 5 or more employed) Drain and dispensing taps on external flammable liquid stores are kept locked Electrical Circuits and fixed electrical Equipment in use within Hi Flam areas are appropriate Electrical Circuits and fixed electrical Equipment in use within Hi Flam areas are tested annually and records maintained 27 WHF FRA Campion House

28 19 Compartmentation Areas to Assess Assessor Comments There is a risk of hidden Fire Spread within the structure There is a risk of vertical or lateral spread Bin chute has vertical access from bin store room to all floors. within the property e.g. between occupancies Lift accesses all levels with doors opening directly onto communal or via common areas landings. The basement (where present) is separated from the ground storey by 30 minutes FR construction (minimum) The risk of Fire Spread is effectively controlled Bin chute access hoppers are located within a protected cupboard off the communal landing and considered to be Low Risk. There is an automatic sliding shutter provided within the bin storage room which actuates via a heat sensor to close off access into the chute above. The bin storage room has sprinkler protection and access is controlled thereby reducing the potential for arson. The lift operates within a protected area. The property is sub divided into fire Each residential flat, the communal area and the stairwell are deemed to compartments be separate compartments. There are unprotected openings, gaps or holes in compartment walls Wall and ceiling linings routes add to the risk of flame spread Gaps in the compartment walls above the suspended ceiling tile level within the ground floor have not been firestopped. Photo refs 01 and WHF FRA Campion House

29 20 Fire Doors 20.1 Areas to Assess Assessor Comments Fire Doors are provided where necessary, are identified and freely available for use Corridor smoke-control doors are provided where necessary Fire and smoke control doors are in good condition, tight fitting to and free from distortion Smoke stop and intumescent seals are present, and in good condition Self-closing devices are present and functional and engage with the latch Where double doors are present, they close in line and have a selector where necessary The door threshold gap is consistent and doesn t foul the floor covering Doorframes are secure to the wall with no visible gaps present. Fire and smoke-control doors are indicated by signs Glazing panels are fire rated, undamaged with fire rated framework The following doorsets are original installations whose fire rating is unknown:- Floor 6 flats Floor 11 flat Floor 13 flat and Floor 17 flat. The following doorsets also had the surrounding facings removed. Floor 6 flat, Floor 13 flat and Floor 17 flat. All other flats have Decent Homes standard doorsets installed which is considered satisfactory. Doors into risk rooms and cupboards, those opening onto the stairwell and to the common landings areas are older pattern and considered to be fire rated. The following fire doors do not close onto the doorframe and require repair: Floor 14 Stairwell door, Floor 16 Lobby fire door at flat Floor 18 - stairwell door at flat, Floor 19 Stairwell door at flat. Installed in the Decent Homes doorsets. The self-closing device had been disconnected from the fire door leading from the lift foyer to the Sprinkler / Tank room. Self-closing devices are being installed to individual flats entrance doors see comments in Overall Summary - Section 5 re. Residential doors. The stairwell doors and cupboard doors are indicated as Fire Doors. The residential entrance doors do not require to be indicated. 29 WHF FRA Campion House

30 Automatic self-closing devices/hold open devices are present Automatic self-closing devices/hold open devices are closed at critical times Automatic self-closers are interlinked to the fire alarm system via smoke detection and/or alarm sounder circuit Correct signage is present for automatically self-closing doors one installed within the property 30 WHF FRA Campion House

31 21 Means of Escape - Internal Areas to Assess Sufficient internal escape routes are provided, available, appropriate for the likely users and lead to a place of safety Travel distances are acceptable Internal Escape Routes are adequately indicated by appropriate pictogram signs along their entire route to final exit point Signs are in good condition, unobstructed, legible and firmly fixed Sliding or revolving doors are present on escape routes Pass doors are provided for sliding or revolving doors Doors open in the direction of escape where appropriate Final exit doors are visible, accessible and easily opened Means of escape doors not in normal use are routinely checked Final exit doors are indicated internally by appropriate pictogram signs All Final Exit Points are indicated externally Fire Exit Keep Clear Final exit points lead into areas from where further dispersal can take place and are not in danger from fire and smoke Where required and appropriate, panic fastenings are fitted to the final exit doors Assessor Comments Single direction exit route from all floors into protected stairwell which discharges to open air at the rear of the property. Two directions of travel available through the ground floor area to exit at the main entrance point or via the rear exit. Low risk as only low numbers of users are anticipated at any one time. Push Button override provided for magnetic locking system on the main entry. Concierge staff members conduct a daily audit of the property. ot considered necessary for this property. Both means of access / egress are in everyday use. Located at rear exit door. 31 WHF FRA Campion House

32 All panic fastening methods of use are indicated e.g. Push Bar/Pad to Open on-standard securing devices are present on final exit doors with their method of operation clearly displayed Where non-standard securing devices are fitted, they are appropriate for the likely users Where fitted, magnetic locks release automatically on fire alarm actuation and/or have manual override Where present, exit doors or corridor doors with powered, automatic opening revert to normal operation during fire alarm actuation Internal corridor escape routes are protected where necessary Inner rooms are protected by auto detection or vision panels Protected stairwell escape routes are provided Floors, walkways, floor coverings, stairs and stair coverings are in good condition, free from obstruction or trip hazard Handrails are provided on stairs and are in good condition Internal escape routes are adequately lit by artificial or natural lighting Emergency Escape Lighting is provided along internal escape routes The internal Emergency Escape Lighting is in good repair Emergency Escape Lighting is regularly tested in accordance with BS5266, findings and corrective works recorded Located at rear exit door. Push button override provided to main entrance door. o alarm present within this property. Two door approach to stairwell on all levels except ground which has single door separation. Floor mats present at flats These did not conform to the Wolverhampton Homes accepted standard. Good level of borrowed light from exterior to stairwell and artificial lighting from common landings. Ongoing PPM organised by Property Services. Annual test scheduled to be carried out Deficiencies identified but no remedial works. 32 WHF FRA Campion House

33 22 Means of Escape - External 22.1 Areas to Assess External escape routes are provided, available, free from obstruction or hazard and lead to a place of safety External escape routes are regularly monitored and maintained to ensure continuing availability for use External escape routes are clearly indicated by pictogram signs along their entire route to final exit point Glazing within 2 metres horizontally and 9m vertically below an external escape stair, is fire resisting External metal escape stairs and platforms have been examined by a structural engineer within the last three years Records of examination of stairs are maintained and available Stairtreads and handrails are in good condition External escape routes are adequately lit by mains powered lighting The external mains lighting control is automatic Where not, the control switch is clearly identifiable Emergency Escape Lighting is provided along external escape routes External Emergency Escape Lighting is in good repair External Emergency Escape Lighting is regularly tested and findings recorded Assessor Comments Paths leading from exit points continue away from property. Part of the Concierge check. All exit routes are in open air and have background street lighting available. 33 WHF FRA Campion House

34 23 Firefighting Equipment 23.1 Areas to Assess Assessor Comments Portable Firefighting Equipment is provided, sufficient in number and appropriate to the risks present It is wall mounted or on dedicated floor stands with the operating handle at approximately 1m from the ground Extinguisher security tags are present Portable Firefighting Equipment positions are clearly indicated by signs where necessary and accessible on exit routes Portable Firefighting Equipment is annually tested to BS and results recorded Access for Fire and Rescue is satisfactory A fire hydrant is in close proximity to the building It is clearly marked and freely available An open water supply is provided Where provided, the Fire and Rescue Service access is maintained CO 2 extinguisher located within main electrical intake cupboard. Located within ground floor main electrical intake cupboard. Ongoing testing programme managed by Property Services. Latest test date recorded as done September Hydrant located on the street. 34 WHF FRA Campion House

35 24 Fixed Firefighting Installations Areas to Assess Assessor Comments Sprinklers or drenchers are present The isolation valve is located within a cupboard on the ground floor They cover the whole property Ground floor areas only excluding the main entrance and lift lobby. Extension of sprinkler system recommended. Spare heads are available In the event of actuation, the maintenance company are contracted to restore the system to full functionality The system is maintained with servicing Recorded on Wolverhampton Homes non domestic asset register as due records available which are appropriate and All reports held by Property Services at Hickman Avenue. current Fixed flooding Installations are present o identified requirement for this low risk property. The system is maintained with servicing records available which are appropriate and current A Wet Riser installation is present The inlet and outlets are clearly indicated and available for use One outlet per floor located on each common landing within a dedicated cupboard. The system is maintained in accordance with Ongoing test regime in place managed by Wolverhampton Homes BS , servicing records are Property services. Latest test date recorded on equipment as December available, appropriate and current All reports held by Property Services at Hickman Avenue. A Foam Inlet is provided o identified requirement for this property. It is clearly indicated and accessible The system is maintained with servicing records available which are appropriate and current 35 WHF FRA Campion House

36 25 Smoke and Ventilation Systems Areas to Assess Assessor Comments There is smoke/ventilation control present A manually openable window vent is provided within the stairwell at all levels. The system is maintained, servicing records are available, appropriate and current Ventilation ducts which breach compartments A Fire Damper is identified as being maintained by Property Services. have automatic fire dampers This is a sliding closer across the bottom of the rubbish chute and located The dampers are identifiable, maintained with servicing records available which are appropriate and current within the Bin Store area. Ongoing test programme organised by Property Services. Latest test date recorded as January Fire Evacuation Lift and Firefighting Shafts Areas to Assess Assessor Comments A firefighting/evacuation lift is provided Lifts are not considered to be part of the evacuation strategy. It is clearly indicated as a firefighting/evacuation lift DO OT USE I THE EVET OF FIRE signage is displayed The lift is maintained with servicing records Ongoing test programme organised by Property Services. available which are appropriate and current A firefighting shaft is provided o identified requirement for this property. The firefighting shaft is protected and maintained in good order 36 WHF FRA Campion House

37 27 Fire Warning System 27.1 Areas to Assess Assessor Comments A manually operated, electrical Fire Warning System is provided throughout the property The alarm sound is uniform, clearly identifiable and audible throughout the property Call points are sited appropriately, available and readily identifiable The warning system contains sensory warning devices including visual and aural stimuli Automatic Detection is provided throughout the property The automatic detection type is appropriate for the identified risks The Fire Warning system is connected to an Alarm Receiving Centre (ARC) The Testing regime is in accordance with BS5839 and results recorded Automatic detection is tested in accordance with BS5839 and results recorded A zone plan is available at the Control Panel When the Fire Alarm system is temporarily decommissioned, adequate alternative procedures have been implemented Manual Voice Warning systems are present o identified requirement Manually operated sounders e.g. bells, horn, whistle, are used Manually operated sounders can be operated safely o identified requirement for this residential property with a stay put policy in place. Single point detection may be present within each residence but these are for local alert only and are not interlinked to adjacent properties. 37 WHF FRA Campion House

38 28 Management of Fire Safety 28.1 Areas to Assess Assessor Comments There is a Fire Safety Management Policy The Responsible Person is identified Myk Kaszuba In multi occupied properties, there is adequate co-operation, communication and co-ordination between Responsible Persons and Landlord They meet regularly and communication is effective There has been a recent Fire and Rescue Service inspection Improvement notices have been served Improvement otices/ inspection results have been actioned and completed There are previous Fire Risk Assessments Previous assessment findings have been Several issues repeated. See Low Priority re Sprinkler installation actioned and completed Risks to Occupants identified in the FRA have been notified to them Occupiers have carried out individual Fire Risk Assessments Their assessment findings have been actioned and completed A Fire Log Book detailing all fire safety Records are held by Property Services at Hickman Avenue systems and training is available The range, detail and currency of information is satisfactory 38 WHF FRA Campion House

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Document Ti tle Client Name Fire Risk Assessment 2017 Wolverhampton Homes Lathe Court Lakefield Road Wolverhampton WV11 3RB WHF FRA 020 2017 9th February 2017 Fire Risk Assessment 2016 Project no: BU89800T

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Document Ti tle Fire Risk Assessment 2017 Wolverhampton Homes Connaught House Upper Vauxhall Wolverhampton WV1 4ST WHF FRA 078 2017 14 th September 2017 Fire Risk Assessment 2017 Project no: BU9980iL Task

More information

Fire Risk Assessment 2018

Fire Risk Assessment 2018 Document Ti tle Client ame Fire Risk Assessment 2018 Wolverhampton Homes Grosvenor Court Pickering Road Wolverhampton WV11 3RD WHF FRA 050 2018 11 th April 2018 Fire Risk Assessment 2018 Project no: BU000904

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

FIRE RISK ASSESSMENT Self Assessment

FIRE RISK ASSESSMENT Self Assessment FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

Fire risk management plan. MH/05/Revised/06/17

Fire risk management plan. MH/05/Revised/06/17 Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com

More information

A basic guide to... Fire Safety for Scout Premises

A basic guide to... Fire Safety for Scout Premises A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Fire Risk Assessment Case Study

Fire Risk Assessment Case Study Appendix B Fire Risk Assessment Case Study The purpose of this case study is to illustrate one practical approach to conducting a fire risk assessment. The checklist and proformas used in this case study

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group. FIRE SAFETY POLICY Approver Executive Management Team Policy Fire Safety Policy Monitored By Health, Safety and Fire Steering Group. Date last revised April 2017 Revised by James Warne Next Revision Date

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

Fire Risk Management Policy. UK September 2017

Fire Risk Management Policy. UK September 2017 UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Fire Precautions (Workplace) Regulations Before beginning the risk assessment, check to see if your workplace has a Fire Certificate. If the workplace does have a Fire Certificate,

More information

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT Fire Risk Assessment Company ame Address of premises (premises being assessed) Sandwell Valley School and Sandwell Community Care Trust Training 150 Birmingham Road, West Bromwich, B70 6QT ame of Responsible

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited June 2017 (Updated 18 January 2018) Fire Safety Policy Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited Trusted provider of quality homes, excellent landlord and support services,

More information

Fire Safety Management Audit Specification August 2017

Fire Safety Management Audit Specification August 2017 Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit

More information

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

NOT PROTECTIVELY MARKED. Fire Legislation

NOT PROTECTIVELY MARKED. Fire Legislation Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Premises Description Address Area Post Code Tel no. Num of Employees Normal Occupancy Max Allowed Use of Premises Building Length Building Breadth Area 0.00 M² Floors Storeys Below

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Department The Cockpit Risk Assessment number PM/06/2015 Date. 17 th June 2015 Review due date 17 th June 2016 Activity: Fire safety risk assessment Location: The Cockpit Name of Assessors:

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report 42 Haslucks Croft, Shirley, Solihull, B90 2EQ (t) 0121 249 1281 (m) 07814 203 977 www.veritas-consulting.co.uk The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Report Client The Company

More information

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN REVISED Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN July 2017 Responsible Person (e.g. employer) or person having control of the

More information

Areas of the building to which access was not available. Details of any onsite management (if known)

Areas of the building to which access was not available. Details of any onsite management (if known) SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

FIRE SAFETY POLICY Revised March 2013

FIRE SAFETY POLICY Revised March 2013 FIRE SAFETY POLICY Revised March 2013 CONTENTS Page No 1.0 Statement of Intent 1 2.0 Fire Safety Accountability Structure 2 3.0 Roles and Responsibilities 3 4.0 Fire Safety Management 7 5.0 Fire Risk Assessment

More information

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;

More information

Following a near miss (after a fire or where evidence suggests that a fire could have occurred).

Following a near miss (after a fire or where evidence suggests that a fire could have occurred). Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons

More information

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN FINAL VERSION Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN August 2017 Responsible Person (e.g. employer) or person having control of

More information

FIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018.

FIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018. FIRE SAFETY POLICY This policy document replaces any previously published documents and comes into effect September 2018. 1.0 Fire Safety: The priority of Shrewsbury School is to minimise the risk to life

More information

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

General needs sleeping accommodation

General needs sleeping accommodation Colwick Woods Court Colwick Road Colwick, ttingham NG2 4BA At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory

More information

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019 Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Manor House HS.F.119 (rev03) delivering promises improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

Independent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library

Independent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library Independent Living Scheme Fire Risk Assessment Strelley Court Strelley Road Strelley ttingham NG8 3BJ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE

Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Prepared by: Peter Golding Tech IOSH and Mark Alderson BSc Hons IEng MIFireE (IFE 0002248) Safety Management (UK) Ltd Holme Suite Clawthorpe

More information

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014 Fire Safety Policy Originator name: Section / Dept: Implementation date: Clive Parkinson Health & Safety March 2014 Date of next review: March 2017 Related policies: Health and Safety Policy Policy history:

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B

More information

Fire Safety in Communal Areas Policy

Fire Safety in Communal Areas Policy Fire Safety in Communal Areas Policy Date approved by senior management team 27 th July 2017 Board of Management / Committee name Board of Management Approval date 2 nd October 2017 Implementation date

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General

More information

Chesterfield Borough Council

Chesterfield Borough Council Reviews December 2013 Prepared For: Town Hall Rose Hill Chesterfield S40 1LP Prepared By: Savills UK Limited 33 Margaret Street London W1G 0JD CHESTERFIELD BOROUGH COUNCIL FIRE RISK ASSESSMENT Report by:

More information

Fire Safety Strategy

Fire Safety Strategy SH HS 02 Summary: Keywords (minimum of 5): (To assist policy search engine) Target Audience: The aim of this strategy is the provision and maintenance of a safe environment for all staff, visitors and

More information

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Name & Address of the Society IDENTIFY PEOPLE AT RISK 01 Have you identified who is at risk? 02 Have you identified

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma Reference Number: This risk assessment and ALL associated documents must be retained. Date : Sept 17 The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma This Fire Risk Assessment

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Ebenezer Chapel,Wyndham Street, Machen Fire Safety Risk Assessment for Small Premises Introduction Regulatory Reform Order The Regulatory

More information

The Gas Safety (Installations and Use) Regulations 1998.

The Gas Safety (Installations and Use) Regulations 1998. GAS SAFETY PROCEDURE December 2016 Purpose and Scope: This procedure sets out the arrangements and responsibilities for managing gas safety within buildings owned or managed by Tai Calon Community Housing

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation Keverne Close Wendover Drive Aspley ttingham NG8 5EF At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire

More information