Department for Communities and Local Government Research Report:

Size: px
Start display at page:

Download "Department for Communities and Local Government Research Report:"

Transcription

1 Department for Communities and Local Government Research Report: BD 2890 Investigation of real fires - Electrical consumer unit fire experiments (E3V2) CPD/04/102/027 Prepared for: Brian Martin Department for Communities and Local Government Building Regulations and Standards Division Zone 2/J6, Eland House Bressenden Place London, SW1E 5DU 10 th April 2014

2 1 Research Report BD 2890 (E3V2) FIRE BD 2890 Investigation of real fires Research Report on Electrical consumer units fire experiments Prepared for Brian Martin Prepared by Ciara Holland, Martin Shipp, and David Crowder BRE output ref (E3V2) Approved on behalf of BRE Name Dr Corinne Williams Position Deputy Lot Manager Date 10 April 2014 Signature BRE Bucknalls Lane Garston Watford WD25 9XX Tel : Fax : hollandcm@bre.co.uk Website :

3 2 Research Report BD 2890 (E3V2) Executive Summary BRE Global carries out fire investigation activities, under contract, on behalf of the Department for Communities and Local Government (DCLG) Building Regulations and Standards Division (BD 2890). In addition to the continued investigative work carried out by BRE Global, this contract includes an element of experimental work to allow further analysis of issues arising from investigations of incidents. The overall aim of the current experimental project was to assess the performance of typical, commerciallyavailable, domestic electrical consumer units from an ignition originating within the unit, and provide a report of findings from the experiments to inform DCLG. This work was intended as a scoping study and assumed that a fire had already been established; this study was not intended to replicate ignition scenarios from an electrical fault in a consumer unit or replicate ignition scenarios used in standard testing methods. Four experimental fires were carried out using two different types of consumer unit and two types of backing board. Two metal and two plastic consumer units were wired up as typical domestic systems with the openings in the top but without connection to power. The consumer units were fixed to an 18mm thick plywood backing board or an 8mm thick vinyl faced plasterboard sheet fixed to 18mm thick plywood. These backing boards were 600mm by 600mm in area. A hot wire loop energised by a variable power source was used to ignite the consumer units from within the units. This hot wire loop was capable of generating 0.5kW of heat with an estimated temperature of 1000 C. For the conditions studied, the conclusions of this scoping study are as follows. Both plastic consumer units caught fire and their casings became involved in the fire. It was necessary to use a water hose reel to extinguish both fires in the plastic consumer units. It should be noted that the plastic unit mounted on the plasterboard backing was more difficult to ignite than that mounted on the plywood backing, taking 19 minutes for established flaming. It is BRE Global s opinion that this delay in ignition was due to the non-combustible backing board. However, once the fire was established in that unit it burned more rapidly and more of the unit s casing became involved in the fire. With the plastic unit on the plywood backing, the fire, once established (after nine minutes), involved the plywood board above the unit and less of the plastic unit below in contrast with the plastic unit on the plasterboard backing. Both metal consumer units contained the fire within the unit; the casings did not become involved in fire except for the front plastic cover and this only melted away from the heat. The backing board did not make any difference to the performance of these units. Smoke was emitted from all four units as soon as the ignition source was energised. The smoke exited the units through openings where the wiring passed into the units. It is BRE Global s opinion that the suggested test method in the proposed amendment to BS 7671:2008, for the verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects, whilst relevant to consumer units, is not severe enough to verify the resistance of the casing material to abnormal heat and fire when considering a resistive heating fault from within such units which could be a prolonged event.

4 3 Research Report BD 2890 (E3V2) Table of Contents 1 Introduction Project objectives 4 2 Methodology Materials Instrumentation Experimental method 6 3 Observations and findings Experiment 1 Plastic consumer unit on plywood backing Experiment 2 Metal consumer unit on plywood backing Experiment 3 Plastic consumer unit on plasterboard backing Experiment 4 Metal consumer unit on plasterboard backing 19 4 Discussion 21 5 Conclusions 22 6 Summary of the potential impact/implications for regulation and/or policy 23 7 References 24 Appendix A Publishable summary 25

5 4 Research Report BD 2890 (E3V2) Electrical consumer unit fire experiments 1 Introduction This work is part of the project commissioned under the Department for Communities and Local Government Building Regulations Research and Development Programme Framework Agreement with the BRE led consortium under contract reference CPD/04/102/027, BD 2890 titled Investigation of Real Fires. An important element of this contract is to ensure that findings from fire investigations are made available to the fire community, and other stakeholders. In addition to the continued investigative work carried out by BRE Global, this contract includes an element of experimental work to allow further analysis of issues arising from investigations of incidents. The current experimental work is in response to a request from the Department for Communities and Local Government (DCLG) Building Regulations and Standards Division to submit a proposal against their specification for a project titled Electrical consumer unit fire experiments. 1.1 Project objectives The overall aim of this project was to assess the performance of typical commercially-available, domestic electrical consumer units from an ignition originating within the unit and provide a report of findings from the experiments to inform DCLG Building Regulations and Standards Division. This work was intended as a scoping study and assumed that a fire had already been established; this study was not intended to replicate ignition scenarios from an electrical fault in a consumer unit or replicate ignition scenarios used in standard testing methods (see Section 6). 2 Methodology 2.1 Materials Two types of wall mountable electrical consumer unit were used; two metal and two plastic. These consumer units were wired up as a typical domestic system without connection to power by a qualified electrician. The plastic consumer units used were both from the same manufacturer and the same model and were 12 way split load insulated with 24 Miniature Circuit Breakers (MCBs). The metal consumer units were both from the same manufacturer and the same model and were 8 way with 16 MCBs. Two types of backing board were used; a plywood backing and a plasterboard backing. Both were 600mm by 600mm in area, the plywood was 18mm thick, the plasterboard was vinyl faced and 8mm thick, fixed to a sheet of 18mm thick plywood. Each type of unit was tested on each type of backing board. The consumer units and backing boards were sourced from an electrical suppliers by the electrician and came pre-assembled to BRE Global. For the experiments, the consumer unit complete with backing board was held on a metal support so that it was a free standing unit (see Figure 1). Each of the units had four openings in their top portion; for the plastic units all the openings were along the top, for the metal units there were three openings along the top and one at the side near the top (see Figure 2). There was one further opening at the bottom of the unit, used to insert the ignition source and a thermocouple but this opening was sealed up with tape for the experiments.

6 5 Research Report BD 2890 (E3V2) Figure 1 Typical setup for the experiments; consumer unit with backing board clamped to a metal support 2.2 Instrumentation Each opening in the consumer units had a Type K 1.0mm diameter steel sheathed thermocouple which was suspended approximately 20mm into the opening to measure the temperature of any smoke or flame escaping from the openings. Figure 2 Layout of thermocouples within the consumer units; the openings were labelled anticlockwise, stars indicate approximate locations of thermocouples and the cross indicates the approximate location of the ignition source. Opening 5 was sealed with tape but a thermocouple was introduced close to the hot wire loop to record temperatures near the source of ignition. The ignition source for the experiments was a 20 standard wire gauge (normally referred to as SWG) ferritic iron-chromium-aluminium alloy hot wire loop (see Figure 3) which was energised using a variable power source. This power source was rated at 5 amperes (A) output current with a variable voltage up to 100 volts (V). The hot wire loop was capable of generating 0.5 kilowatts (kw) of heat energy. The temperature of the hot wire loop when energised to 100 V was estimated at 1000 C. The performance of the consumer units was monitored during the experiments with visual observations and using video equipment and a stills camera.

7 6 Research Report BD 2890 (E3V2) Figure 3 Hot wire loop, indicated by red arrow, used as the ignition source. The loop was connected to the power source using ceramic blocks and was positioned appropriately within the consumer unit 2.3 Experimental method The consumer units were ignited from within the closed unit using the hot wire loop. The fire was allowed to develop and, using a grid on the backing board, flame heights from the top of the units were measured and temperature measurements were taken at each opening in the units. The hot wire loop ignition source was fitted inside the consumer unit in contact with wiring and plastic components (see Figure 4). Figure 4 Location of hot wire loop in a plastic consumer unit indicated by a red arrow The hot wire loop was left powered on until flames continuously extended out of the top of the consumer unit at which time the power was removed. In cases where flames did not extend beyond the consumer unit the hot wire loop remained powered on until termination of the experiment. Where necessary the fire was extinguished using water from a hose reel. Table 1 outlines the four experiments which were carried out.

8 7 Research Report BD 2890 (E3V2) Table 1 Order of experiments listing type of consumer unit and backing board Experiment Consumer unit type Boarding type 1 Plastic, 12 way split-load insulated with 24 MCBs 2 Metal, 8 way with 16 MCBs 3 Plastic, 12 way split-load insulated with 24 MCBs 4 Metal, 8 way with 16 MCBs 18mm plywood 18mm plywood 8mm vinyl faced plasterboard fixed to 18mm plywood 8mm vinyl faced plasterboard fixed to 18mm plywood 3 Observations and findings 3.1 Experiment 1 Plastic consumer unit on plywood backing This experiment was carried out on a plastic consumer unit mounted on a plywood backing (see Figure 1). Trial and error was used to determine the optimum voltage required for ignition using the hot wire loop. The power source was initially at 70 volts (V); this generated very light wispy smoke within 15 seconds. The generation of smoke continued for seven minutes, after which time it was decided by BRE Global to increase the voltage to the ignition source. The voltage was increased to 100V, the maximum voltage possible, seven minutes after the start of the experiment. Almost instantly more smoke was visible from the top of the consumer unit and also a flash of flame. The hot wire loop remained energised for a further two minutes to allow flames to develop after which time (nine minutes after start of test) the power was switched off (see Figure 5). Figure 5 Early stages of flaming approximately nine minutes into the experiment after switching off power to the ignition source The fire, now established, continued to grow and three minutes after the first sign of flames, 10 minutes into the experiment, flames were extending ~0.3m from the top of the consumer unit (see Figure 6). Flames reached a maximum of 0.5m from the top of the consumer unit, extending beyond the height of the backing board.

9 8 Research Report BD 2890 (E3V2) Figure 6 Plastic consumer unit on plywood backing board approximately 16 minutes into the experiment The fire was extinguished approximately 18 minutes into the experiment because it was considered that no further data would be gained. It was clear that the fire size, immediately prior to extinguishing, would have been sufficient to ignite any combustible items that might be present nearby. An interesting observation was that the flames did not initially extend out of the openings at the top of the unit but instead burned through the plastic between Opening 3 and Opening 4. The maximum temperature recorded, as shown in Figure 7 and Figure 8, was 901 C at Opening 4. The area approximately 20mm below the ignition source recorded a maximum temperature of 790 C. See Section 4 for comparison with other experiments. Figure 7 Temperature-time curve for Experiment 1; plastic consumer unit with 18mm plywood backing board

10 9 Research Report BD 2890 (E3V2) Figure 8 Temperature-time curve (x-axis normalised for comparison with other experiments) for Experiment 1; plastic consumer unit with 18mm plywood backing board Figure 9 and Figure 10 shows the damage to the consumer unit after the fire was extinguished and also shows the damage to the backing board. The plywood backing board did not burn through during the fire but was charred. Figure 9 Damage caused to plastic consumer unit and plywood backing board by the fire started within the consumer unit Figure 10 Damage to plywood backing board after Experiment 1 after removal of burned plastic consumer unit

11 10 Research Report BD 2890 (E3V2) Experiment 2 Metal consumer unit on plywood backing This experiment was carried out on a metal consumer unit mounted on a plywood backing (see Figure 11 and Figure 12). Having established the ideal settings for the ignition source in Experiment 1, the decision was made by BRE Global to go straight to 100V on the power source for the remaining experiments. Given the layout and construction of the metal units, the ignition source was placed closest to items most likely to burn to assess a worst case scenario. The position of the ignition source is shown in Figure 11; the loop was in contact with an MCB and also close to the plastic gap filler (see Figure 12). Figure 11 Location of hot wire loop in metal consumer unit Figure 12 Location of hot wire loop with cover on metal consumer unit showing plastic gap filler, red arrow. Also of note are the locations of the openings in the metal units with this unit having one opening to the side and three at the top. White wispy smoke was visible 55 seconds after switching on the hot wire loop. After approximately four minutes, the plastic gap filler, shown in Figure 12, started to melt and at approximately five minutes, the hot wire loop was visible and glowing (see Figure 13). It was possible to view into the part of the consumer unit at this time and it was noted that the MCB in contact with the hot wire had started to melt.

12 11 Research Report BD 2890 (E3V2) Figure 13 Glowing of the hot wire loop after the plastic gap filler had melted away due to the heat After 7½ minutes, the outer screen of the unit was showing signs of heat damage and there was discolouration of the metal above this area (see Figure 14). A small hole formed in the outer screen after 14½ minutes and this ventilation allowed for a very small flaming fire centred around the MCB. Figure 14 Outer plastic cover has been damaged by the heat and some small flames can be seen within the metal consumer unit with some discolouration of the metal The flames did not reach more than 25mm in length throughout the experiments and were contained inside the metal unit. After 25 minutes, the flames became smaller. The power to the hot wire loop, which had remained switched on for the duration of the experiment, was switched off at 30 minutes. Some small flames (20mm in length) were still evident but the fire had self-extinguished by 2¼ minutes after switching off the hot wire loop power. The maximum temperature recorded, as shown in Figure 15, was 269 C approximately 20mm below the ignition source. The maximum recorded temperature at the openings was 66 C. See Section 4 for comparison with other experiments.

13 12 Research Report BD 2890 (E3V2) Figure 15 Temperature-time curve for Experiment 2; metal consumer unit with 18mm plywood backing board Figure 16 and Figure 17 show the damage to the metal consumer unit after the fire was extinguished. The fire was contained within the unit and hence the damage is also contained to within the unit with the exception of the plastic outer cover which became heat damaged. Figure 16 Damage to metal consumer unit after Experiment 2; the fire was contained by the unit and centred around the hot wire loop which remained energised throughout the experiment Figure 17 Damage to metal consumer unit after Experiment 2; the front casing has been removed to show the extent of the damage within the unit which was minimal after 30 minutes exposure

14 13 Research Report BD 2890 (E3V2) Experiment 3 Plastic consumer unit on plasterboard backing This experiment was carried out on a plastic consumer unit mounted on a vinyl faced 8mm plasterboard backing which was mounted onto an 18mm sheet of plywood (see Figure 18). This experiment was split into three parts (phases) as the consumer unit did not catch fire after the initial experiment and the purpose of the experiment was to assess the performance of these units to the most severe conditions. This required optimising the position of the hot wire loop to create such conditions. As with Experiment 2 the optimum setting for the power supply for the ignition source of 100V was used for all three parts. Figure 18 Plastic consumer unit on vinyl faced plasterboard backing board for Experiment 3 Parts 1 to 3 The location of the hot wire loop for Part 1 and 2 is shown in Figure 19. Figure 19 Location of hot wire loop in plastic consumer unit for Experiment 3 Part 1 and Part 2 Part 1 White, wispy smoke was visible from the unit approximately 10 seconds after energising the ignition source and it was possible to see a glow from the hot wire loop on the backing board after 35 seconds. There appeared to be a flicker of flames after one minute but this did not develop any further or extend beyond the unit. Approximately four minutes after starting the experiment the volume of smoke had reduced and there were no flames. No change was apparent up to 25 minutes from the start of the experiment at which time it was decided by BRE Global to terminate the experiment.

15 14 Research Report BD 2890 (E3V2) The hot wire loop was de-energised at 25 minutes. After allowing the hot wire loop to cool down, the front cover of the plastic consumer unit was removed to assess the damage. There was minor discolouration of the wiring close to the hot wire loop but no damage was apparent on the consumer unit itself. It appeared as though the loop may have moved after installation. It was decided to re-position the hot wire loop and run the experiment again under the same conditions. The maximum temperature recorded, as shown in Figure 20, was 170 C at Opening 3. The area approximately 50mm below the ignition source recorded a maximum temperature of 36 C. See Section 4 for comparison with other experiments. Figure 20 Temperature-time curve for Experiment 3 Part 1; plastic consumer unit on plasterboard backing. (There were no flames visible outside the unit for this experiment). Part 2 The hot wire loop was re-positioned after becoming dislodged from its original position as shown in Figure 19. The hot wire loop was in more contact with the wiring for Part 2 than Part 1. The same conditions as with Part 1 were then applied. Dark grey smoke was visible approximately 32 seconds after energising the hot wire loop. Looking into the unit from above, it was possible to see the glow of the hot wire loop and some of the insulation on the wiring burning with a glow but no flames were visible. As with Part 1, the smoke volume reduced after the initial few minutes and remained low until the experiment was terminated at 20½ minutes. The maximum temperature recorded, as shown in Figure 21, was 114 C at Opening 3. The area approximately 50mm below the ignition source recorded a maximum temperature of 32 C. See Section 4 for comparison with other experiments.

16 15 Research Report BD 2890 (E3V2) Figure 21 Temperature-time curve for Experiment 3 Part 2; plastic consumer unit on plasterboard backing. (As with Part 1, no flaming was observed for this experiment.) Figure 22 to Figure 24 show damage caused by the hot wire loop within the plastic consumer unit after carrying out the experiment twice (Part 1 and Part 2). There is some discolouration of wiring; parts of the plastic MCBs have charred and a small area of the plastic back of the unit has melted, exposing the plasterboard backing board behind. Figure 22 Damage to the top exterior of the plastic consumer unit after Part 1 and Part 2 of Experiment 3. There is some evidence of heat damage but the unit did not become involved in fire. Figure 23 Damage/discolouration to wiring after Parts 1 and 2 of Experiment 3; red arrow indicates location of hot wire loop which is behind the wiring.

17 16 Research Report BD 2890 (E3V2) Figure 24 Damage to back of plastic consumer unit after Parts 1 and 2 of Experiment 3; part of the plastic has melted away to expose the vinyl face of the plasterboard behind. Some damage to the MCBs is also evident. The unit was left to cool overnight before attempting Part 3 of this experiment. Part 3 After Parts 1 and 2, the unit was examined and it was clear that the hot wire loop had created heat damage inside the unit and also to the back of the unit. The decision was made to re-position the hot wire loop so that it was in direct contact with the plastic back of the unit rather than the wiring. The hot wire loop was turned around and moved slightly to an undamaged part of the back of the unit. The same conditions as with all other experiments were used again; 100V power to the hot wire loop. Approximately 18 seconds after energising the hot wire loop, dark grey smoke was visible rising out of the unit through the openings at the top. The volume of the dark grey smoke continued to increase and began to discolour the plasterboard backing (see Figure 25). Figure 25 Dark grey smoke issuing from top of plastic consumer unit for Experiment 3 Part 3 After approximately 12 minutes, the first flames were observed extending outside the unit, out of Opening 1, and were approximately 20mm in length and grew to approximately 50mm. This flame died back after approximately 20 seconds. At this time, the top of the unit was showing signs of heat damage and was distorting (see Figure 26).

18 17 Research Report BD 2890 (E3V2) Figure 26 Distortion of plastic consumer unit during Experiment 3 Part 3 After approximately 17 minutes, there were some small flames extending from Opening 4, again the flames were only approximately 20mm in length. Opening 4 at this point had been distorted and large section of the plastic top had melted away from the opening. Approximately 10 seconds after these flames emerged the length increased to approximately 150mm above the top of the unit but only briefly. The flames died back again, with only smoke visible above the top of the unit. At approximately 18 minutes, flames started to pulse out of Opening 4, reaching a height of 150mm. This pulsing flame turned into a continuous growing flame after a few seconds, reaching a height of 200mm. The fire then spread to the right hand side of the unit with flames extending out of Opening 1 (see Figure 27 and Figure 28). Figure 27 Flames extending from openings at the top of the plastic consumer prior to deenergising the hot wire loop Figure 28 Side view of the plastic consumer unit showing flames having melted the plastic backing travelling along the backing board

19 18 Research Report BD 2890 (E3V2) The power to the hot wire loop was switched off at 19 minutes and the fire was allowed to develop and involve the unit. The fire was extinguished after approximately 21 minutes since the unit had started to detach from the backing board. The maximum temperature recorded, as shown in Figure 29, was 819 C at Opening 2. The area approximately 50mm below the ignition source recorded a maximum temperature of 427 C. See Section 4 for comparison with other experiments. Figure 29 Temperature-time curve for Experiment 3 Part 3; plastic consumer unit on vinyl faced plasterboard backing board Figure 30 and Figure 31 show damage caused by the hot wire loop and resulting fire within the plastic consumer unit after carrying out the experiment three times (Part 1 to Part 3). As noted previously, during Part 3 of this experiment, the consumer unit caught fire. It can be seen that the vinyl facing of the plasterboard backing was damaged in a localised area and that the plastic casing of the consumer unit has been significantly damaged by the fire. Figure 30 Damage to plastic consumer unit and backing board after Experiment 3 Part 3

20 19 Research Report BD 2890 (E3V2) Figure 31 Close up of damage to plastic consumer unit and backing board after Experiment 3 Part Experiment 4 Metal consumer unit on plasterboard backing This experiment was carried out on a metal consumer unit mounted on a vinyl faced 8mm plasterboard backing which was mounted onto an 18mm sheet of plywood (see Figure 32). As with Experiment 2, the optimum setting for the power supply for the ignition source of 100V was used. The hot wire loop was installed in the same location as with Experiment 2 with the plastic gap filler placed over it. The openings in this unit were slightly different to Experiment 2 as the side opening was on the right hand side in this unit but there were still three openings in the top (see Figure 32). Figure 32 Metal consumer unit for Experiment 4 Approximately one minute after switching on the hot wire loop, the plastic gap filler had started to melt (see Figure 33). After 5.25 minutes very small flames (~20mm) were visible around the MCB in contact with the hot wire loop (see Figure 34). As with Experiment 2, the hot wire loop remained energised for 30 minutes after which time the power was switched off. Flames were still apparent but self-extinguished approximately one minute after the hot wire loop was de-energised.

21 20 Research Report BD 2890 (E3V2) Figure 33 Plastic gap filler melted away showing the glowing hot wire loop in the metal consumer unit Figure 34 Flames visible behind the melting plastic outer cover of the metal consumer unit The maximum temperature recorded, as shown in Figure 35, was 162 C at Opening 3. The area approximately 20mm below the ignition source recorded a maximum temperature of 88 C. See Section 4 for comparison with other experiments. Figure 35 Temperature-time curve for Experiment 4; metal consumer unit mounted onto a vinyl faced plasterboard backing board which was fixed to a sheet of plywood Figure 36 shows the damage to the metal consumer unit after the fire was extinguished. The fire was contained within the metal unit and did not spread to involve the plasterboard backing board. Some discolouration of the cables outside the unit was evident but this was due to the hot gases and not flame.

22 21 Research Report BD 2890 (E3V2) Figure 36 Damage caused by fire to the metal consumer unit on vinyl faced plasterboard backing after Experiment 4 4 Discussion Comparison of the four experiments helps demonstrate the differences between each of the units and their backing boards. Table 2 compares the maximum recorded temperatures for each of the units and notable observations from the experiments. Table 2 Comparison of maximum recorded temperatures and notable observations from the experiments Experiment Conditions Maximum temperature at openings ( C) Maximum temperature near ignition source ( C) Flame height above unit (m) Time to established flaming from power on (minutes) Time fire extinguished (minutes) 1 Plastic consumer unit with plywood backing 2 Metal consumer unit with plywood backing 3 (Part 3) Plastic consumer unit with vinyl faced plasterboard backing 4 Metal consumer unit with vinyl faced plasterboard backing 901 (Opening 2) 66 (Opening 1) 819 (Opening 2) 163 (Opening 3) (selfextinguished) (selfextinguished)

23 22 Research Report BD 2890 (E3V2) Same units, different backing board For the metal consumer units, the fire was contained within the unit so the backing boards were unaffected by the fire and did not contribute to the fuel load. For the plastic consumer units, there was a difference in the way the units burned. The plastic unit on the plywood backing burned for approximately six minutes before it was extinguished by BRE Global staff. The plastic unit on the plasterboard backing only burned for two minutes before it was necessary to extinguish the fire. The fire in the second plastic unit (Experiment 3 Part 3), while reaching flame heights of ~0.4m, had a lot of material dripping or dropping from the base of the unit. Most of the damage to the first plastic unit (Experiment 1) was to the upper portion of the unit with minimal dripping from the base. The hot wire loop in both experiments was located near the top. It also took three attempts to ignite the plastic unit mounted on the plasterboard backing (Experiment 3) and when it eventually did ignite, it took 10 minutes longer than it had with the plywood backing. It is BRE Global s opinion that the difference in the backing boards account for this difference in burning characteristics due to the plywood backing board being involved in the fire. Same backing board, different units It is clear from the experiments that the metal units, regardless of the backing board, contained the fire within the unit and the plastic units did not contain the fire and their casings became involved in the fire. While the fire was contained within the metal units, smoke did escape from the units through the openings as it did with the plastic units. Due to the typical location of these units in domestic premises, a fire in an electrical consumer unit could go undetected for some time leading to the smoke itself being enough of a hazard in a property prior to it being detected. 5 Conclusions This report has summarised the results of four experiments carried out to assess the performance of typical commercially-available, domestic electrical consumer units from an ignition originating within the unit This work was limited to assessing the performance of two different types of consumer units. Two plastic units and two metal units each mounted on either a plywood backing or a plasterboard backing. Furthermore this work assumed that a fire had already been established within in the unit. In conclusion, both plastic consumer units caught fire and their casings became involved in the fire. It was necessary to use a water hose reel to extinguish both fires in the plastic consumer units. It should be noted that, of the two plastic units, the unit mounted on the plasterboard backing was more difficult to ignite and it is BRE Global s opinion that this delay in ignition was due to the non-combustible backing board. However, once the fire was established in that unit it burned more rapidly and more of the unit s casing became involved in the fire. With the plastic unit on the plywood backing the fire, once established, involved the plywood board above the unit and less of the plastic unit below in contrast with the plastic unit on the plasterboard backing. Both metal consumer units contained the fire within the unit; the casings did not become involved in fire except for the front plastic cover and this only melted away from the heat. The backing board did not make a difference to these units. Smoke was emitted from all four units as soon as the ignition source was energised. The smoke exited the units through openings where the wiring passed into the units.

24 23 Research Report BD 2890 (E3V2) It should be noted that this was a simple scoping study. This study has only looked at two types of wall mounted consumer units; there are several other types of domestic consumer unit available, e.g. flushmounted consumer units, which have not been addressed in this work. Further work would be required to establish the performance of other types of consumer units not covered by this study. 6 Summary of the potential impact/implications for regulation and/or policy Amendment No 3 of BS 7671:2008 [1] has recently been available for public consultation and there are several proposed changes to the current standard [2]. The proposed wording, relevant to consumer units, for inclusion in BS 7671:2008 incorporating Amendment No 3 Chapter 42 Protection against thermal effects, and due to be published in 2015 is as follows: Switchgear assemblies including consumer units shall: (i) have their enclosure manufactured from non-combustible or not readily combustible material, or (ii) be enclosed in a cabinet or enclosure constructed of non-combustible or not readily combustible material. NOTE 1: Ferrous metal e.g. steel is deemed to be an example of a non-combustible material NOTE 2: For the purposes of this regulation insulating material e.g. plastic meeting a 960 ºC glow-wire flammability test as defined in BS EN is considered to be an example of a not readily combustible material. The findings of the consumer unit experiments here support the proposed amendment regarding noncombustible and not readily combustible material. However, BRE Global questions whether the glow-wire flammability test BS EN [3] will be sufficient for the conditions under which a consumer unit may become involved in fire. This glow-wire test (BS EN ) is based upon exposure of the test specimen to the wire at the relevant temperature for 30 seconds. As noted from the experiments carried out here, exposure of the plastic consumer units to the hot wire loop, at an estimated temperature of 1000 C, took between nine and 19 minutes for flaming to be established outside the consumer unit. It is BRE Global s opinion that this 30 second exposure is not severe enough to verify the resistance of the casing material to abnormal heat and fire when considering a resistive heating fault from within such units. It is BRE Global s experience that undetected resistive heating faults can continue over prolonged periods beyond that of 30 seconds as tested by the standard. Furthermore, BS EN :2009 [4] would appear to be a more relevant standard to use in this proposed regulation. This standard does make reference to BS EN but also includes specific criteria for enclosures of switchgear. Paragraph Resistance of insulation materials to abnormal heat and fire due to internal electric effects states: parts which might be exposed to thermal stresses due to internal electric effects, and the deterioration of which might impair the safety of the ASSEMBLY, shall not be adversely affected by abnormal heat and fire and shall be verified by the glow wire test in NOTE: The glow wire test in refers to BS EN :2001, IEC :2000 Fire hazard testing. Also of note is that while Approved Document B [5] refers to Approved Document P [6], it does not refer to BS 7671:2008 directly. Inclusion of reference to BS 7671:2008 in Approved Document B perhaps should be considered given the proposed amendments relevant to fire safety.

25 24 Research Report BD 2890 (E3V2) References [1] BS 7671:2008 incorporating Amendment No 1:2011 Requirements for electrical installations. IET Wiring Regulations Seventeenth Edition, and British Standards Institution, [2] Private communication between BRE Global and Mr Ken Bromley of the Department for Communities and Local Government, 7 th March [3] BS EN :2001, IEC :2001 Fire hazard testing Test methods. Glowing/hot wire based test methods Glowing-wire flammability test method for end-products. British Standards Institution, [4] BS EN :2009 Low voltage switchgear and control gear assemblies General rules. British Standards Institution, [5] Approved Document B: Fire Safety Volume 2: Buildings other than dwellinghouses edition incorporating 2007, 2010 and 2013 amendments. [6] Approved Document P: Electrical safety Dwellings. P1 Design and installation of electrical installations edition.

26 25 Research Report BD 2890 (E3V2) Appendix A Publishable summary BRE Global carries out fire investigation activities, under contract, on behalf of the Department for Communities and Local Government (DCLG) Building Regulations and Standards Division (BD 2890). In addition to the continued investigative work carried out by BRE Global, this contract includes an element of experimental work to allow further analysis of issues arising from investigations of incidents. The overall aim of the present experimental project was to assess the performance of typical commerciallyavailable, domestic electrical consumer units from an ignition originating within the unit and provide a report of findings from the experiments to inform DCLG. This work was intended as a scoping study and assumed that a fire had already been established; this study was not intended to replicate ignition scenarios from an electrical fault in a consumer unit or replicate ignition scenarios used in standard testing methods. Four experiments were carried out to assess the performance of typical, commercially-available, domestic electrical consumer units from an ignition originating within the unit Four experimental fires were carried out using two different types of consumer unit and two types of backing board. Two metal and two plastic consumer units were wired up as typical domestic systems with the openings in the top and without connection to power. The consumer units were fixed to an 18mm thick plywood backing board or an 8mm thick vinyl faced plasterboard sheet fixed to 18mm thick plywood. These backing boards were 600mm by 600mm in area. A hot wire loop energised using a variable power source was used to ignite the consumer units from within the units. This hot wire loop was capable of generating 0.5kW of heat at an estimated temperature of 1000 C. Both plastic consumer units caught fire and their casings became involved in the fire. It was necessary to use a water hose reel to extinguish both fires in the plastic consumer units. It should be noted that the plastic unit mounted on the plasterboard backing was more difficult to ignite than the one mounted on the plywood backing, taking 19 minutes for established flaming. It is BRE Global s opinion that this delay in ignition was due to the non-combustible backing board since it did not become involved in the fire. However, once the fire was established in that unit, it burned more rapidly and more of the units casing became involved in the fire. With the plastic unit on the plywood backing the fire, once established (after nine minutes), involved the plywood board above the unit and less of the plastic unit below in contrast with the plastic unit on the plasterboard backing. Both metal consumer units contained the fire within the unit; the casings did not become involved in fire except for the front plastic cover and this only melted away from the heat. The backing board did not make any difference to the performance of these units. Smoke was emitted from all four units as soon as the ignition source was energised. The smoke exited the units through openings where the wiring passed into the units. It is BRE Global s opinion that the suggested test method in the proposed amendment to BS 7671:2008, for the verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects, whilst relevant to consumer units, is not severe enough to verify the resistance of the casing material to abnormal heat and fire when considering a resistive heating fault from within such units which could be a prolonged event and may need another review.

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han

More information

Heat and Smoke Release of a Ceiling-Installed Speaker

Heat and Smoke Release of a Ceiling-Installed Speaker WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke

More information

Personal Protection Systems (PPS)

Personal Protection Systems (PPS) Personal Protection Systems (PPS) Guidance on the use, deployment and limitations of Personal Protection Watermist Systems in the homes of vulnerable people Prepared for: BRE Global Date: 12.11.2015 Report

More information

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Fire Performance of external thermal insulation for walls of multistorey buildings

Fire Performance of external thermal insulation for walls of multistorey buildings Fire Performance of external thermal insulation for walls of multistorey buildings third edition Sarah Colwell and Tony Baker fire performance of external thermal insulation for walls of multistorey buildings

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper BACKGROUND: Safety is paramount in the home appliance industry. Due to the possibility of human mis-application, over-current, or short circuit

More information

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS

More information

BS 5839: Part THE CHANGES

BS 5839: Part THE CHANGES BS 5839: Part 1 2013 THE CHANGES INTRODUCTION This document has been created to summarise the main changes that have been made to the BS 5839 Part 1 2013. This data is correct at the time of publication

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988

More information

Incident Summary (II )

Incident Summary (II ) Incident Summary (II-636492-2018) Incident Date December 15, 2017 Location Langley SUPPORTING INFORMATION Regulated industry sector Impact Injury Damage Qty injuries 0 Injury description Injury rating

More information

Effectiveness of sprinklers in residential premises:

Effectiveness of sprinklers in residential premises: Effectiveness of sprinklers in residential premises: Section 7: Other considerations and Recommendations for further work Project report number 204505 Dr Corinne Williams and Dr Jeremy Fraser-Mitchell

More information

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves. Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan

More information

MEDIUM-DENSITY HOUSING # 7. Fire safety

MEDIUM-DENSITY HOUSING # 7. Fire safety BRANZ FACTS MEDIUM-DENSITY HOUSING # 7 Fire safety Moving from low-density to medium-density housing (MDH) involves people living in closer proximity. This has a number of implications for fire safety

More information

ENHANCED FIRE PERFORMANCE CABLE

ENHANCED FIRE PERFORMANCE CABLE FIRE PERFORMANCE CABLE Manufactured to BS 7629-1 Table 1 Plain Annealed Copper Conductors / Silicone Rubber Insulated / Glass Fibre Tape / Tinned Copper Circuit Protective Conductor / Double Layer of Copper/Polyester

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper 23 May 2013 Rev A 503-32020 GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY Background Safety is paramount in the home appliance industry. Due to the possibility of human misapplication, over-current,

More information

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device

More information

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of

More information

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50. Classification of reaction to fire performance in accordance with BS EN 13501-1: 2007 +A1: 2009 on Sandwich Panel, WP 50 Prepared for: Sandwich Panel Factory Jeddah Saudi Arabia 13 July 2011 0578 Page

More information

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy BS 476: Part 7: 1997 on K-Flex IN Clad Foil Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, 36 20877 RONCELLO (MB) Italy 30 th October 2012 0578 Page 1 of 6 Prepared on behalf of BRE Global

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

Incident Summary (Reference # )

Incident Summary (Reference # ) Incident Summary (Reference # 5616714) Incident Date June 06, 2017 Location Regulated industry sector Abbotsford Gas Natural Gas System SUPPORTING INFORMATION Impact Injury Damage Incident rating Qty injuries

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1282: Issue 1.1 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

FIRE PERFORMANCE CABLE

FIRE PERFORMANCE CABLE FIRE PERFORMANCE CABLE Manufactured to BS 7629-1 Table 1 Plain Annealed Copper Conductors / Silicone Rubber Insulated / Double Layer of Aluminium/ Polyester Laminated Tapes / Circuit Protective Conductor

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1196: Issue 1.2 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC

Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Introduction Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Who are Certsure? Where do we come from? 1923 - A National Register created 1956 - NICEIC established as a Charity

More information

Guide to Amendment 3. Innovators - Developers - Manufacturers Passive Fire Prevention Products

Guide to Amendment 3. Innovators - Developers - Manufacturers Passive Fire Prevention Products Innovators - Developers - Manufacturers Passive Fire Prevention Products IS-AM3-10-15 Guide to Amendment 3 Guide How to comply with Amendment 3 (regarding Consumer Units) T +44 (0) 1304 842 555 F +44 (0)

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Amendment Number 3 of BS how it might affect you

Amendment Number 3 of BS how it might affect you Amendment Number 3 of BS7671 2008 - how it might affect you Geoff Cronshaw provides us with a look ahead at the proposals of Amendment 3 to BS 7671:2008 IET Wiring Regulations and the resulting changes

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

F.R.A.M.E. EVENT NETWORKS used in FRAME. EVENT NETWORKS used in "FRAME". In 2004, Dipl. Ing. Trond Maag wrote his doctorates' thesis "Risikobasierte Beurteilung der Personensicherheit von Wohnbauten im Brandfall unter Verwendung von Bayes'schen

More information

F I R E S A F E T Y R E G I S T E R

F I R E S A F E T Y R E G I S T E R F I R E S A F E T Y R E G I S T E R (Short Version) Cork County Fire Department www.corkcoco.ie April 2015 Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all

More information

Incident Summary (Reference # )

Incident Summary (Reference # ) Incident Summary (Reference #5605195) Incident Date September 13, 2016 Location White Rock Regulated industry sector Natural gas system and low voltage electrical system (30V to 750V) SUPPORTING INFORMATION

More information

Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC :1999

Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC :1999 Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC 60331-25:1999 Prepared for: Teldor Cables & Systems Ltd Ein-Dor Kibbutz Ein-Dor 19335 Israel 16 March 2011 0578 Page 1 of

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Middle School, St. Johns Hall, Machen Fire Safety Risk Assessment for Wyclif Christian School Introduction Regulatory Reform Order

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information

Grand Avenue Primary and Nursery School. Policy for Fire Safety. Contents. 6. Prevention of fire Events taking place outside school hours

Grand Avenue Primary and Nursery School. Policy for Fire Safety. Contents. 6. Prevention of fire Events taking place outside school hours Grand Avenue Primary and Nursery School Policy for Fire Safety Contents 1. Aims/Objectives 2. Prevention of fire Maintenance 3. Prevention of fire - Responsibilities 4. Prevention of fire Fire Safety Training

More information

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Determination 2016/058 Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Summary This determination considers whether signage is required between

More information

Guide to: 17 th Edition Consumer Units

Guide to: 17 th Edition Consumer Units Guide to: 17 th Edition Consumer Units Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are

More information

Fire Safety in a Laser Lab

Fire Safety in a Laser Lab Fire Safety in a Laser Lab DOE LSO Workshop Sep 10-12, 2013 R. DeWayne Holcomb, CLSO, CHP Laser Safety Manager University of Texas at Austin Info Began working in the Laser and Radiation Safety field in

More information

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article DOMESTIC SMOKE ALARMS AND SPRINKLERS Frank SWANN 1 Abstract: Key words: Making further inroads into the reduction of fire deaths and injuries in the home is a clear ambition of the UK Chief Fire Officers

More information

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern Hugh Hoagland Consulting, Inc. ArcWear.com 1566 Red Brush Road Newburgh, IN 47630 Phone: 502-314-7158 Fax: 603-457-5960 E-mail: hugh@arcwear.com Electric Arc Exposure Tests for Stern & Stern October 2002

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

VERIFICATION OF AN AEROSOL LEAK DETECTOR FOR THE ALTERNATIVE TO THE WATERBATH METHOD FOR RAUPACK LIMITED

VERIFICATION OF AN AEROSOL LEAK DETECTOR FOR THE ALTERNATIVE TO THE WATERBATH METHOD FOR RAUPACK LIMITED VERIFICATION OF AN AEROSOL LEAK DETECTOR FOR THE ALTERNATIVE TO THE WATERBATH METHOD FOR RAUPACK LIMITED 5/559464/PRD-A REV. 1 MARCH 2009 BY BURGOYNE CONSULTANTS LIMITED Burgoyne Consultants Ltd, Burgoyne

More information

UNDERSTANDING ELECTRICAL SAFETY RISKS

UNDERSTANDING ELECTRICAL SAFETY RISKS UNDERSTANDING ELECTRICAL SAFETY RISKS The Electrical Safety Program at BC Safety Authority (BCSA) is responsible for overseeing the safety of electrical systems across British Columbia in accordance with

More information

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report

More information

Global Requirements for the Fire Protection of Ships. Dr Janet Murrell Warrington Certification Ltd

Global Requirements for the Fire Protection of Ships. Dr Janet Murrell Warrington Certification Ltd Global Requirements for the Fire Protection of Ships Dr Janet Murrell Warrington Certification Ltd Arch Timber 3 rd Castleford June 2011 International Maritime Organisation (IMO) International Maritime

More information

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone Medicine Hat Fire Service Construction Site Fire Safety Plan ABC Part 9 Buildings 1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone 403-529-8282 Email fireprevention@medicinehat.ca Small Buildings

More information

EMERGENCY LIGHTING COMPLETION CERTIFICATE For small installations and verification of existing installations

EMERGENCY LIGHTING COMPLETION CERTIFICATE For small installations and verification of existing installations A DETAILS OF THE CLIENT Client/ B DETAILS OF THE EMERGENCY LIGHTING INSTALLATION Extent of the installation covered by this certificate The Owner 19 Walker Grove, Hatfield, Hertfordshire 19 Walker Grove,

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS

STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS STUDY ON THE REACTION TO FIRE OF MEDIUM VOLTAGE CABLES SYSTEMS Neus GENERÓ, Juan de Dios MARTÍNEZ, Jacint ROVIRA, Grupo General Cable Sistemas, (Spain), ngenero@generalcable.es, jdmartinez@generalcable.es,

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

Consumer unit replacement in domestic and similar premises

Consumer unit replacement in domestic and similar premises Consumer unit replacement in domestic and similar premises 6 Issue 2 The Electrical Safety Council is indebted to the following organisations for their contribution and/or support to the development of

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

All Prysmian FP400 cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

All Prysmian FP400 cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB. Certificate No 077b Certificate No 517b > Prysmian FP400 is the original fire resistant armoured cable providing an easy to install and terminate, robust fire resistant wiring system. In addition to maintaining

More information

Fire Risks of Loviisa NPP During Shutdown States

Fire Risks of Loviisa NPP During Shutdown States Fire Risks of Loviisa NPP During Shutdown States Sami Sirén a*, Ilkka Paavola a, Kalle Jänkälä a a Fortum Power And Heat Oy, Espoo, Finland Abstract: Fire PRA for all 15 shutdown states of Loviisa NPP

More information

THE EFFECTS OF SMOKE ON PEOPLE S WALKING SPEEDS USING OVERHEAD LIGHTING AND WAYGUIDANCE PROVISION

THE EFFECTS OF SMOKE ON PEOPLE S WALKING SPEEDS USING OVERHEAD LIGHTING AND WAYGUIDANCE PROVISION THE EFFECTS OF SMOKE ON PEOPLE S WALKING SPEEDS USING OVERHEAD LIGHTING AND WAYGUIDANCE PROVISION M S Wright, G K Cook and G M B Webber Research Group for Inclusive Environments, The Department of Construction

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

Materials Testing by Gregory Havel

Materials Testing by Gregory Havel Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics

More information

2 Examination of Cladding Panels (Laboratory)

2 Examination of Cladding Panels (Laboratory) 30th November 2016 Fire and Safety Department Report To: For the attention of: Our ref: Your ref: LFB/Fire Investigation Team - Dowgate Examination of Cladding Panels Flat 28 Shepherds Court, 21 Shepherd

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Abstract. Introduction

Abstract. Introduction Smoke Alarms in Dwellings: Occupant Safety Through Timely Activation and Effective Notification Ian Thomas and Dorothy Bruck Centre for Environmental Safety and Risk Engineering Victoria University, Melbourne

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

SELECTION, INSTALLATION & TESTING OF ELECTRICAL EQUIPMENTS IN HAZARDOUS AREA

SELECTION, INSTALLATION & TESTING OF ELECTRICAL EQUIPMENTS IN HAZARDOUS AREA Training Title SELECTION, INSTALLATION & TESTING OF ELECTRICAL EQUIPMENTS IN HAZARDOUS AREA Training Duration 5 days Training Venue and Dates REF EE019 Selection, Installation & Testing of Electrical Equipments

More information

Characterising the smoke produced from modern materials and evaluating smoke detectors

Characterising the smoke produced from modern materials and evaluating smoke detectors www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Wall-mounted pen recording thermometer Product verification protocol: E06/TR04VP Applies to specification ref(s):

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Brine Generation Study

Brine Generation Study DOE/WIPP 00-2000 Brine Generation Study April 2000 Waste Isolation Pilot Plant Carlsbad, New Mexico Processing and final preparation of this report was performed by the Waste Isolation Pilot Plant Management

More information

Management Practices: Fire Protection Impairments November 2015

Management Practices: Fire Protection Impairments November 2015 RiskTopics Management Practices: Fire Protection Impairments November 2015 When business capital is invested in fire protection, it is difficult to explain any fire protection outage that allows a fire

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures ON THE BUTTON A reference guide to environmental ratings used for push button enclosures A REFERENCE GUIDE TO KEY TOPICS IN PUSH BUTTON SELECTION AND SAFETY CONTENTS I. INTRODUCTION...............................

More information

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests For Innovative Textiles Fabric system Outer Layer: 5.5 oz/yd² IUS Twill, 88% Cotton 12% Nylon, Style 341, Khaki. 6.6 oz/yd² Inner Layer: 6.5 oz/yd²

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance This certificate is issued for the following: KS103SSF, KS103MSF, AND KS110CTF PANELS AS CLASS 1 INTERIOR WALL AND CEILING PANELS FOR INSTALLATION WITH NO HEIGHT RESTRICTION Prepared

More information

BS EN : 2001 & IEC :2000

BS EN : 2001 & IEC :2000 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000

More information

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref.: T4/4.01 MSC.1/Circ.1272 4 June 2008 GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415 ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and

More information

Final Report on Electric Clothes Dryers and Lint Ignition Characteristics May 2003

Final Report on Electric Clothes Dryers and Lint Ignition Characteristics May 2003 Final Report on Electric Clothes Dryers and Lint Ignition Characteristics Abstract In FY 22, U.S. Consumer Product Safety Commission staff completed a test program to evaluate residential electric clothes

More information

Saving lives with coatings

Saving lives with coatings Saving lives with coatings The essentials of passive fire protection. Paul Mather. Passive fire protection by means of intumescent, cementitious or ceramifying coatings or layers has gained importance

More information

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace Journal of Mechanics Engineering and Automation 7 (2017) 160-164 doi: 10.17265/2159-5275/2017.03.005 D DAVID PUBLISHING Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water

More information

Roof Ventilators and Terminals: Fire Performance. CI/SfB (37.9) Uniclass L529 May 2012

Roof Ventilators and Terminals: Fire Performance. CI/SfB (37.9) Uniclass L529 May 2012 Roof Ventilators and Terminals: Fire Performance CI/SfB (37.9) Uniclass L529 May 2012 Fire - one of nature s destructive forces There is a view held by some in the industry that roof ventilators are an

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

( )

( ) Course Title: Fire Dynamics (3087) Course Number: FST - 3087 Course Credit Hours: (3) Three Semester Hours Instructor Information: Bernard W. Becker, III, MS (937-751-7371) ccfdchiefbecker@yahoo.com Textbook:

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

Lloyd s Register Type Approval System Test Specification Number 3

Lloyd s Register Type Approval System Test Specification Number 3 Working together for a safer world Lloyd s Register Type Approval System Test Specification Number 3 July 2015 Performance Test Specification for Equipment to be used in Marine Applications: Electric Cables

More information

Heat pump supplemental heating system for motor vehicles

Heat pump supplemental heating system for motor vehicles 1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance

More information

USER GUIDE VOGUE MAX SYSTEM

USER GUIDE VOGUE MAX SYSTEM USER GUIDE VOGUE MAX SYSTEM 15 18 26 32 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293.

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293. AS 2293.1 2005 AS 2293.1 2005 Australian Standard Emergency escape lighting and exit signs for buildings Part 1: System design, installation and operation This Australian Standard was prepared by Committee

More information

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529

Australian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529 AS 60529 2004 IEC 60529 Ed 2.1:2001 AS 60529 Australian Standard Degrees of protection provided by enclosures (IP Code) This Australian Standard was prepared by Committee EL-026, Protective Enclosures

More information