SPECIFICATIONS Model HWP 59RKS Item No. (Standard/Opposite Hand) 509-059-001 / 509-059-011 Cooling capacity (net) to AS/NZS 3823 T1 5.7 kw Heating capacity H1 5.4 kw Electrical input - cooling 1.6 kw Electrical input - heating 1.5 kw EER / AEER (cooling) 3.61 / 3.60 Unit Controller UC8 Refrigerant R410A Refrigerant charge 1.05 kg Compressor type rotary connections 1/2" male SP Nominal EWT on cooling 30 C Nominal EWT on heating 21 C Nominal Flow @ EWT LWT = 5k 0.34 l/s Entering system pressure drop @ nominal flow 41 kpa (6 psi) Min. water temp. Heat cycle at nominal flow 10 C Min. water temp. Cool cycle at nominal flow 15 C Min. water temp. Cool cycle with water flow control valve 5 C Max. EWT Heat cycle at nominal flow 30 C Max. EWT Cool cycle at nominal flow 50 C Min. water flow @ nominal EWT 0.09 l/s Max. water pressure excluding hoses 3200 kpa (464 psi) Power supply 1 ph. 23 ac 50Hz Compressor run amps at rating cond. 6.6 A Compressor run capacitor 40 µfd Indoor fan motor size 230 W Indoor fan motor (1ph.) - full load 1.9 A Control circuit breaker (internal) 10 A Running amps (total system) 7.6 A Max. running amps (total system) 11.2 A Net weight 85 kg Accessories: Spring mounts supplied hoses 600mm long, rated 250psi 1/2" female SP, supplied Replacement filter 119-000-086 840x265x13 Condensate lift-pump 507-003-009 Optional: SAT-3 Room temperature controller 201-000-146 TZT-100 Room temperature controller 201-000-350 Refer to temperzone for other options, eg remote sensors Tested in accordance with AS/NZS 3823 15053
DIMENSIONS (mm) PROJECTION HWP 59RKS Standard W Air Flow ELECTRICAL OX X Not to Scale POINT LOADS (kg) W X Y Z 21 26 23 15 Note: Fan motor can be accessed from panel above, below or sides; no more than two panels at once. Z Air Flow Y HWP 59RKS Opposite Hand POINT LOADS (kg) W X Y Z 26 15 21 23 Note: Fan motor can be accessed from panel above, below or sides; no more than two panels at once. NOTE Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.
ELECTRICAL TL2W1 External Protection & Isolation N N1 N2 T1 T2 T3 T4 ETH3 CC Pump Verification Dry Contacts If Pump Verification Option fitted remove this link T6 Flow 1 Flow 2 E1 T7 Pump 1 Pump 2 Active A 6-A 6- C 6-D D 7-D UC8 DIP switch settings UC8 JUMPER settings DIP switch On/Off 1,13,14 On All Others Off Off Position Jumper J1 J2 REV DESCRIPTION ECN temperzone Ltd 2014 DATE DO NOT SCALE - ASK APPROVED Contactor now single pole. Earth points N3805 21-01-16 D.A.. changed. C Main Earth Symbol updated N3837 19-03-16 D.A.. D FR & SR now fitted as standard N3941 23-05-17 D.A.. Client Wiring CAP1 S R C CM M 1~ SR 1-C A 1-C Condensate Pump FR UC8 Temp Sensors (Refer to table) 1 A1 FLT EXV1 EXV2 AUX HI ME LO C1 IN#1 IN#1 C2 HT CP IN#2 IN#2 DL SL 12 2 A2 Modbus master port for optional T/stat (TZT100/SAT-3) Flow Control Valve E HIGH MED LOW C3 HPT LPT AM Pressure sensors DEI OC IC V1 V2 D1 D2 D3 SC ON CP4W1 CP2W1 0-1 to Regulating Valve If Condensate Float Switch Option fitted remove this link Condensate Float Switch (Normally closed) N L R/V R/V SSR1 SSR1 SSR2 SSR2 5 VF 12 VC TL2W2 L1 T5 ETH2 D 24VAC/12VDC controls Optional 0-1 controls E2R Relay 2 D DP1 Refer to DIP S/W settings Display SW1 SW2 J1 J2 Modbus slave port for MS (monitoring or control option) Relay 1 SW3 C4 Remote On/Off Dry Contact RV C 1-D D 1-D If Remote On/Off Option fitted remove this link CAP2 ORG ORG RN (HIGH) RED (MED-HI) LU M 1 GRY (MED-LOW) IFM1 WHT (LOW) Sensors (S) / Transducers (T) Name Type Colour DL Discharge Temp S RED SL Suction Temp S WHITE IC Indoor Coil S YELLOW HPT High Pressure T CAP CAPACITOR CC CONTROL CIRCUIT REAKER CM PRESSOR MOTOR PRESSOR CONTACTOR CP2W CONNECTOR PLUG 2 WAY CP4W CONNECTOR PLUG 4 WAY E2R EXV2 RELAY OARD FR FAULT RELAY OARD ETH EARTH IFM INDOOR FAN MOTOR RV REVERSING VALVE SR STATUS RELAY OARD T TERMINAL LOCK TL2W TERMINAL LOCK LINK 2 WAY UC8 UNIT CONTROLLER 8 Drawn: Apprvd: C.M.W. Date: 26-08-14 Title: Drawing No: Rev: 291-000-754 D HWP 59/79 & 98RKS UC8 Wiring Schematic SHEET 1 OF 1
003-000-021 06/17 www.temperzone.biz temperzone limited 2017
SPECIFICATIONS Model HWP 59CEKSY Item No. (Standard/Opposite Hand) 510-059-102 / 510-059-112 Cooling capacity (net) to AS/NZS 3823 T1 5.7 kw Heating capacity - Electric heat 3.0 kw Electrical input - cooling 1.5 kw Electrical input - heating 3.1 kw EER / AEER (cooling) 3.75 / 3.73 Unit Controller UC8 Refrigerant R410A Refrigerant charge 0.73 kg Compressor type rotary connections 1/2" male SP Nominal EWT on cooling 30 C Nominal Flow @ EWT LWT = 5k 0.34 l/s Entering system pressure drop @ nominal flow 41 kpa (6 psi) Min. water temp. Cool cycle at nominal flow 15 C Min. water temp. Cool cycle with water regulating valve 5 C Max. EWT Cool cycle at nominal flow 50 C Min. water flow @ nominal EWT 0.09 l/s Max. water pressure excluding hoses 3200 kpa (464 psi) Power supply 1 ph. 23 ac 50Hz Compressor run amps at rating cond. 6.0 A Compressor run capacitor 40 µfd Indoor fan motor size 230 W (EC) Indoor fan motor (1ph.) - full load 1.3 A Control circuit breaker (internal) 10 A Running amps (total system) 14.1 A Max. running amps (total system) 14.3 A Net weight 90 kg Accessories: Spring mounts supplied hoses 600mm long, rated 1720 kpa (250psi) 1/2" female SP, supplied Replacement filter - rated EU2/G2 119-000-086 840x265x13 Condensate lift-pump 507-003-009 Optional: SAT-3 Room temperature controller 201-000-146 TZT-100 Room temperature controller 201-000-350 Refer to temperzone for other options, eg remote sensors Tested in accordance with AS/NZS 3823 16051
DIMENSIONS (mm) PROJECTION HWP 59CEKSY Standard Not to Scale W Electrical ox X POINT LOADS (kg) W X Y Z 19 29 27 15 Note: Fan motor can be accessed from panel above, below or sides; no more than two panels at once. Z EC Motor Driver Y 46 HWP 59CEKSY Opposite Hand POINT LOADS (kg) W X Y Z W Electrical ox X 27 19 15 29 46 Note: Fan motor can be accessed from panel above, below or sides; no more than two panels at once. Z EC Motor Driver Y 139 NOTE Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.
ELECTRICAL ETH2 ETH3 ETH4 T1 T2 N T3 TL2W1 N1 CM R CAP1 T4 TL2W2 ECC driver located opposite main ebox M N2 S K 1~ T5 C L1 E ECC-240 ECH1 ECH2 EH External Protection & Isolation ETH4 PE PE ACN ACL CC ETH5 1-D A SR +12V 0-1 Optional 0-1 controls 1-D 24VAC/12VDC controls E2R Relay 2 Condensate Pump FR+ FR- MO- MO+ Use supplied resistor when wires are not fitted Relay 1 Purple Purple VC 12 VF HI ME LO C1 Flow Control Valve 5 IN#2 IN#2 IN#1 IN#1 C2 HT CP FR Pump Verification Dry Contacts 1 A1 AUX EXV2 EXV1 R Modbus slave port for MS (monitoring or control option) J1 UC8 Refer to DIP S/W settings A 5-C FLT W Red lack White 5-C T6 Flow1 Flow2 Modbus master port for optional T/stat (TZT100/SAT-3) 12 2 A2 J2 SW1 SW2 Temp Sensors (Refer to table) DP1 U V E1 DL SL Display ETH3 If Pump Verification Option fitted remove this link E 0-1 to Regulating Valve V1 V2 DEI AM SW3 E C 5-E OC IC Ferrite- coil 3 turns through ferrite core. Separarte these 3 wires from others. If Condensate Float Switch Option fitted remove this link CP4W1 D 5-E T7 Pump1 Pump2 IFM D1 D2 Pressure sensors HPT LPT Active Condensate Float Switch (Normally closed) Remote On/Off Dry Contact D3 SC C3 LOW MED HIGH CP2W1 SSR2 SSR2 SSR1 SSR1 R/V R/V ON N L C4 Ferrite- coil 4 turns through ferrite core Resistor Size (R) If Remote On/Off Option fitted remove this link HST C 1-E E2R EXV2 RELAY OARD ECC EC MOTOR CONTROLLER EH ELECTRIC HEAT EHC ELECTRIC HEAT CONTACTOR ETH EARTH FR FAULT RELAY OARD HST HIGH TEMPERATURE SAFETY THERMOSTAT IFM INDOOR FAN MOTOR K KLIXON MST MANUAL SAFETY THERMOSTAT R RESISTOR SR STATUS RELAY OARD T TERMINAL LOCK TL2W TERMINAL LOCK LINK 2 WAY UC8 UNIT CONTROLLER 8 t D 1-E MST EHC2 t TZ Motor p/n Ohms 046-000-070 62KΩ 046-000-071 62KΩ 046-000-360 3.9KΩ 046-000-361 3.9KΩ EHC1 UC8 JUMPER settings UC8 DIP switch settings Sensors (S) / Transducers (T) Name Type Colour AM Fast Temp Sensor S LACK DL Discharge Temp S RED SL Suction Temp S LUE IC Indoor Coil S YELLOW HPT High Pressure T Position Jumper J1 J2 DIP switch On/Off 1,3,4,6,13,14 On All Others Off Off CAP CAPACITOR CC CONTROL CIRCUIT REAKER CM PRESSOR MOTOR PRESSOR CONTACTOR CP2W CONNECTOR PLUG 2 WAY CP4W CONNECTOR PLUG 4 WAY REV DESCRIPTION ECN DATE APPROVED A Initial Release FR & SR now fitted as standard N3941 23-05-17 D.A.. Title: Drawing No: Rev: 291-000-798 C.M.W. Date: 29-02-16 Drawn: temperzone Ltd 2016 Client Wiring SHEET 1 OF 1 HWP 36/48 & 59CEKSY UC8 Wiring Schematic Apprvd: DO NOT SCALE - ASK
003-000-069 06/17 www.temperzone.biz temperzone limited 2017