Metasys Integrator Vilter Application

Similar documents
Metasys Integrator Compu-Aire Application

Metasys Integrator TITUS Application

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Airflow Application

Metasys Integrator York Application

Metasys Integrator Liebert Application

Metasys Integrator McQuay Application

Reciprocating Chiller

Metasys Integrator Carrier Application

USER MANUAL FOR OPERATING SYSTEM

P2267 NETWORK INTERFACE

FCD-wire Contents. List of Figures

TC-9102 Applications

HRX Technical Manual. Version 1.2

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

Open Protocol Data Communications

ACT2-CS Convenience Store Controller

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

York 25-Ton VAV Rooftop Unit

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

MicroTech Series-200 Flooded Screw Chiller

DX-9100/9120 Local Sonalert Logic

ACCURATE ELECTRONICS INC

Multistate Alarm. Introduction

READ AND SAVE THESE INSTRUCTIONS

21-light Remote Annunciator. Owner s Manual

MicroTech Series 200 Centrifugal Chiller

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

DX-9100 Applications from Engineering Services

Fire Operator Workstation (Fire OWS) User s Guide

20 Light Remote Annunciator

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Instruction Manual Model Backup Switch, 1 for 8

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

Installation Guide Bacharach Communications Adapter HGM-MZ to Johnson Controls Metasys N2 Network (Electrically Isolated N2 Port Version)

MicroTech Unit Ventilator

Capacity controller for water chiller AK-CH 650

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

AKSolutions Data Sheet April 2007 AK882X RF POWER MONITOR. Description: Features:

User manual. KNXpar. version

Avigilon Control Center System Integration Guide

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

User manual. KNXgal. version

Model A1700 Series Annunciator

FieldServer Driver - Serial FS SBT-FSI (Siemens Building Technologies Foreign Systems Interface)

725B Configuration Software Manual

Model A2100 Series Annunciator

mti085 Temperature Interface

TEC210x-2 Series Networked Thermostats

Roo232 User Guide. Revision 1.0. Copyright 2006 RoboDynamics Corp

CBI-064. User Manual. Caddx to KNX-BUS Interface

TEC Networked Multi-Stage Economizer Thermostat

AK-CS On Board Guide

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Figure 1. Proper Method of Holding the ToolStick. Figure 2. Improper Method of Holding the ToolStick

AIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)

Avigilon Control Center System Integration Guide

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

FieldServer FS Secutron

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Brivis Touch Controller. Installer Manual

User Manual DPM 208. Alarm and Control Network Element. Um119889

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

TEC2100 Series Networked Thermostats

MicroTech Self-Contained Air Conditioning System

MicroTech Water-Cooled Screw Chiller Controller

Product Manual SZ1144

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Quick Alert Remote (QA216R)

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

TEC Networked Multi-Stage Thermostat

Engineering Guideline. pac- Carriers Type Universal

INSTALLATION AND OPERATION MANUAL FOR THE PILOTEYE 2000

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Ice Rink (Single and Dual Configurations) Custom Control Features

Introduction. What is the W2W Open controller?

Rev Flame Detection Sensor. TF100 User Manual

Model AD C AD RS-422 Distributor

M1000 Alarm Annunciator

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

HRX3000. Technical Manual

APP 721 MODBUS Mapping

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

INSTALLATION INSTRUCTIONS

Transcription:

Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3 Component Requirements 4 Vendor Contact Information 6 Design Considerations 6 Cable Connections 7 Cable Pinouts 7 Connecting the Cable 7 Metasys Integrator Setup 9 Point Mapping Tables 11 Reciprocating 11 Twin Screw 13 Single Screw 15 Evaporative Condenser 17 Metasys Network Setup 19 Mapping to a CS Object 19 * Indicates those sections where changes have occurred since the last printing. 1994 Johnson Controls, Inc. 1 Code No. LIT-6295520

2 Metasys Integrator Metasys Integrator Vilter Application

lntroduction This document explains Metasys Integrator Vilter Manufacturing Corporation applications. Use this document with the Metasys Integrator Technical Bulletin, which provides information on installing and commissioning Metasys Integrator. For information on Vilter equipment, see Vilter documentation (obtainable from Vilter representative). Application Details Metasys Integrator allows Vilter equipment to become an integral part of the Metasys and Metasys Companion Networks. Once Vilter refrigeration controllers are connected to a Metasys or Companion Network via the Metasys Integrator, their data is available to the full complement of Metasys Facility Management System (FMS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. Metasys Integrator transmits both status information and commands between the Vilter devices and the Metasys or Companion Network. Metasys Integrator supports four Vilter controllers: Reciprocating Twin Screw Single Screw Evaporative Condenser One controller (of any type) is designated as a master controller, and acts as the interface between Vilter equipment and non-vilter devices (such as Metasys Integrator). The master controller connects to Metasys Integrator through the RS-232 Bus, and to the other controllers through the RS-485 8044 BITBUS. Each Metasys Integrator vendor port can connect to one master controller. Each master controller can connect up to 250 Vilter controllers. Figure 1 shows Vilter and Metasys integration, and Figure 2 shows Vilter and Metasys Companion integration. N1LAN Standard NCU RS-232 BUS Reciprocating (Master Node) Metasys Integrator Twin Screw Single Screw Evaporative Condenser RS-485 8044 BITBUS UNT N2 Bus vilter1 Figure 1: Vilter and Metasys Integration Metasys Integrator Metasys Integrator Vilter Application 3

PC-Version Panel Version/LTD or Converter RS-232 Reciprocating (Master Node) Metasys Integrator RS-485 8044 BITBUS UNT Twin Screw Single Screw Evaporative Condenser N2 Bus voltcomp Figure 2: Vilter and Metasys Companion Integration Component Requirements To integrate Vilter equipment, you ll need the following components: properly installed Vilter devices RS-232 cable (for connecting the master controller to Metasys Integrator) Metasys Integrator N2 Bus (for connecting Metasys Integrator to the Metasys or Companion Network) portable PC for downloading vendor communication tables (.VCT files) and network setup information into Metasys Integrator, and for running diagnostics cable for connecting portable PC to Metasys Integrator the correct vendor communication table (.VCT file) to download into Metasys Integrator (supplied on Metasys Integrator diskette) This document describes the RS-232 cable and the vendor communication tables. Vilter documentation describes their equipment. The remaining components are described in the Metasys Integrator Technical Bulletin. Metasys Release Requirements To integrate Vilter equipment into the Metasys Network, you ll need: Metasys OWS software Release 4.0 or higher Metasys Integrator software/firmware Release 2.0 or higher Metasys Companion Release Requirements Vendor Component Requirements To integrate Vilter equipment into the Metasys Companion Network, you ll need: Metasys Companion Release 4.0 or higher Metasys Integrator software/firmware Release 2.0 or higher Integration between Metasys Integrator and Vilter has been tested with the equipment listed in Table 1. Changes to this equipment or integration of Vilter products not discussed in this document will require additional software development and testing by 4 Metasys Integrator Metasys Integrator Vilter Application

Systems Products. For information on integrating other products, call the Installation and Retrofit Systems Team in Milwaukee (extension 4662). Metasys Integrator Metasys Integrator Vilter Application 5

Table 1: Vilter Part and Software Version Numbers Vilter Product Style Number Software/Firmware Version Number* VMC Reciprocating VMC VMC3.XX VRS Twin Screw VRS VRS2.XX VSS Single Screw VSS VSS4.XX Evaporative ALL VCF2.XX * XX following the revision number indicates any revision of that level is valid. Vendor Contact Information Vilter Manufacturing Corporation 2217 South First Street Milwaukee, WI 53207 Technical Support Phone: (414) 744-0111 FAX: (414) 744-2084 Design Considerations When integrating Vilter equipment, keep the following considerations in mind: Make sure all Vilter equipment is set up, started, and running properly before attempting to integrate with the Metasys or Companion Network. (The Vilter representative is responsible for operation of refrigeration controllers.) Make sure one of the controllers is designated as the master controller. (The Vilter representative is responsible for defining the master controller.) Make sure the controller baud rate is set to 1200. (The Vilter representative is responsible for setting the controller s baud rate.) RS-232 cable distance between Metasys Integrator and the master controller can be a maximum of 50 feet. Cable distance between the master controller and the last controller can be a maximum of 4000 feet. Up to 28 controllers can be supported without the use of a repeater (each repeater counts as one device). 6 Metasys Integrator Metasys Integrator Vilter Application

Cable Connections Cable Pinouts Use the following cable pinouts for the RS-232 connection between Metasys Integrator and the Vilter master controller. Vendor Port A or B on Integrator RS-232C Terminal Block on the Master Controller DB-9 Female Signal RD TD GND Pin 2 3 5 RS-232 (50 ft. maximum) Pin 6 5 1 2 9 Figure 3: Cable Pinouts Signal TXD RXD GND +5V DSR VILTER2 Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on Metasys Integrator. Connect the other end of the cable to the RS-232 terminal block on the master controller. Metasys Integrator Vilter Master Controller Vendor Port A or B RS-232 Cable 6 5 1 2 9 RS-232 Terminal Block VILTER3 Figure 4: Port to Port Connection Metasys Integrator Metasys Integrator Vilter Application 7

8 Metasys Integrator Metasys Integrator Vilter Application

Metasys Integrator Setup To set up Metasys Integrator, you ll use a portable PC connected to Metasys Integrator s Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers The following table provides information specific to Vilter applications. For detailed procedures, see the Metasys Integrator Technical Bulletin. Table 2: Metasys Integrator Setup for Vilter Applications Vendor Communication Table (.VCT File) Reciprocating VM_RECIP.VCT Twin Screw Single Screw Evaporative Condenser Port Setup Baud Rate 1200 Word Length 8 Stop Bits 1 Parity Interface Network Setup VM_TSCRW.VCT VM_SSCRW.VCT VM_EVPCD.VCT None RS-232 Vendor Address Master Controller 0 only Reciprocating 5-49 Twin Screw 50-99 Single Screw 100-149 Evaporative Condenser 150-174 Timeout Value 5000 ms Poll Delay Performance Guide Approximate Scan Time (For a single N2 address) Reciprocating Twin Screw Single Screw Evaporative Condenser 55 ms 3 seconds 3 seconds 3 seconds 3 seconds Metasys Integrator Metasys Integrator Vilter Application 9

10 Metasys Integrator Metasys Integrator Vilter Application

Point Mapping Tables The following tables (one for each application) show the points available for mapping in the Vilter controllers. Reciprocating To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Discharge Temperature 2 is 3. Table 3: Reciprocating NPT 1 NPA 2 Unit Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Amps % Hour Suction Temperature Discharge Temperature 1 Discharge Temperature 2 Oil Temperature Suction Pressure Discharge Pressure 1 Discharge Pressure 2 Filter Outlet Pressure Filter Inlet Pressure Calculated Oil Pressure Calculated Filter Differential Pressure Motor Current Percent Capacity Runtime BI 1 On 0-no, 1-yes BI 2 Alarm Active 0-ok, 1-alarm BI 3 Trip Active 0-ok, 1-trip BI 4 Mode 0-local, 1-central BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait BI 6 Comp Wait - Max Time @ Min Cap 0-ok, 1-wait BI 7 Comp Wait - Hot Starts/Hour 0-ok, 1-wait BI 8 Comp Wait - Anti recycle Timer 0-ok, 1-wait BI 9 Comp Wait - Remote Command 0-ok, 1-wait BI 10 Hi Suction Pulldown Control 0-off, 1-active 1 Network Point Type 2 Network Point Address Continued on next page... Metasys Integrator Metasys Integrator Vilter Application 11

NPT 1 (Cont.) NPA 2 Unit Description BO BO 1 2 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 16 BD 17 BD 18 BD 19 BD 20 BD 21 BD 22 1 Network Point Type 2 Network Point Address Mode Off/Auto 0-off, 1-auto Alarm Acknowledge 0-n/a, 1-ack Suction Temp Alarm 0-ok, 1-alarm Discharge Temp 1 Alarm 0-ok, 1-alarm Discharge Temp 2 Alarm 0-ok, 1-alarm Oil Temp Alarm 0-ok, 1-alarm Suction Pressure Alarm 0-ok, 1-alarm Discharge Pressure 1 Alarm 0-ok, 1-alarm Discharge Pressure 2 Alarm 0-ok, 1-alarm Filter Outlet Pressure Alarm 0-ok, 1-alarm Filter Pressure Alarm 0-ok, 1-alarm Oil Pressure Alarm 0-ok, 1-alarm Suction Temp Trip 0-ok, 1-trip Discharge Temp 1 Trip 0-ok, 1-trip Discharge Temp 2 Trip 0-ok, 1-trip Oil Temp Trip 0-ok, 1-trip Suction Pressure Trip 0-ok, 1-trip Discharge Pressure 1 Trip 0-ok, 1-trip Discharge Pressure 2 Trip 0-ok, 1-trip Filter Outlet Pressure Trip 0-ok, 1-trip Filter Pressure Trip 0-ok, 1-trip Oil Pressure Trip 0-ok, 1-trip Motor Aux Safety Trip 0-ok, 1-trip Aux #1 Safety Relay Trip 0-ok, 1-trip 12 Metasys Integrator Metasys Integrator Vilter Application

Twin Screw Table 4: Twin Screw NPT 1 NPA 2 Unit Description 1 2 3 4 5 6 7 8 9 10 11 12 13 Amps % Hour Suction Temperature Discharge Temperature Spare Temperature Oil Injection Temperature Suction Pressure Discharge Pressure Manifold/Filter Outlet Pressure Filter Inlet Pressure Calculated Oil Pressure Calculated Filter Differential Pressure Motor Current Percent Capacity Runtime BI 1 On 0-no, 1-yes BI 2 Alarm Active 0-ok, 1-alarm BI 3 Trip Active 0-ok, 1-trip BI 4 Mode 0-local, 1-central BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait BI 6 Comp Wait - Remote Command 0-ok, 1-wait BI 7 Comp Wait - Hot Starts/Anti recycle 0-ok, 1-wait BI 8 Comp Wait - Prelube Timer 0-ok, 1-wait BI 9 Comp Wait - Percent Capacity 0-ok, 1-wait BI 10 Comp Wait - Oil Pressure 0-ok, 1-wait 1 Network Point Type 2 Network Point Address Continued on next page... Metasys Integrator Metasys Integrator Vilter Application 13

NPT 1 (Cont.) NPA 2 Unit Description BO BO 1 2 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 16 BD 17 BD 18 BD 19 BD 20 BD 21 BD 22 BD 23 BD 24 1 Network Point Type 2 Network Point Address Mode Off/Auto 0-off, 1-auto Alarm Acknowledge 0-n/a, 1-ack Suction Temp Alarm 0-ok, 1-alarm Discharge Temp Alarm 0-ok, 1-alarm Lo Oil Injection Temp Alarm 0-ok, 1-alarm Hi Oil Injection Temp Alarm 0-ok, 1-alarm Suction Pressure Alarm 0-ok, 1-alarm Discharge Pressure Alarm 0-ok, 1-alarm Manifold Pressure Alarm 0-ok, 1-alarm Percent Capacity Alarm 0-ok, 1-alarm Run Oil Pressure Alarm 0-ok, 1-alarm Filter Pressure Start Alarm 0-ok, 1-alarm Filter Pressure Run Alarm 0-ok, 1-Alarm Suction Temp Trip 0-ok, 1-trip Discharge Temp Trip 0-ok, 1-trip Lo Oil Injection Temp Trip 0-ok, 1-trip Hi Oil Injection Temp Trip 0-ok, 1-trip Suction Pressure Trip 0-ok, 1-trip Discharge Pressure Trip 0-ok, 1-trip Manifold Pressure Trip 0-ok, 1-trip Percent Capacity Trip 0-ok, 1-trip Run Oil Pressure Trip 0-ok, 1-trip Filter Pressure Start Trip 0-ok, 1-trip Filter Pressure Run Trip 0-ok, 1-trip Motor Aux Safety Trip 0-no, 1-trip Aux #1 Safety Relay Trip 0-no, 1-trip 14 Metasys Integrator Metasys Integrator Vilter Application

Single Screw Table 5: Single Screw NPT 1 NPA 2 Unit Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Amps % % Hour Suction Temperature Discharge Temperature Oil Separator Temperature Oil Injection Temperature Suction Pressure Discharge Pressure Manifold/Filter Outlet Pressure Filter Inlet Pressure Calculated Differential Pressure Calculated Run Cycle Monitor Pressure Calculated Allow Start Pressure Calculated Filter Differential Pressure Motor Current Percent Capacity Percent Volume Runtime BI 1 On 0-no, 1-yes BI 2 Alarm Active 0-ok, 1-alarm BI 3 Trip Active 0-ok, 1-trip BI 4 Mode 0-local, 1-central BI 5 Comp Wait - Suction Pressure 0-ok, 1-wait BI 6 Comp Wait - Remote Command 0-ok, 1-wait BI 7 Comp Wait - Hot Starts/Anti recycle 0-ok, 1-wait BI 8 Comp Wait - Percent Capacity 0-ok, 1-wait BI 9 Comp Wait - Percent Volume 0-ok, 1-wait BI 10 Comp Wait - Oil Pressure 0-ok, 1-Wait 1 Network Point Type 2 Network Point Address Continued on next page... Metasys Integrator Metasys Integrator Vilter Application 15

NPT 1 (Cont.) NPA 2 Unit Description BO BO 1 2 BD 1 BD 2 BD 3 BD 4 BD 5 BD 6 BD 7 BD 8 BD 9 BD 10 BD 11 BD 12 BD 13 BD 14 BD 15 BD 16 BD 17 BD 18 BD 19 BD 20 BD 21 BD 22 BD 23 BD 24 BD 25 BD 26 BD 27 BD 28 BD 29 BD 30 BD 31 1 Network Point Type 2 Network Point Address Mode Off/Auto 0-off, 1-auto Alarm Acknowledge 0-n/a, 1-ack Suction Temp Alarm 0-ok, 1-alarm Discharge Temp Alarm 0-ok, 1-alarm Lo Oil Separator Temp 1 Alarm 0-ok, 1-alarm Lo Oil Separator Temp 2 Alarm 0-ok, 1-alarm Lo Oil Injection Temp Alarm 0-ok, 1-alarm Hi Oil Injection Temp Alarm 0-ok, 1-alarm Suction Pressure Alarm 0-ok, 1-alarm Discharge Pressure Alarm 0-ok, 1-alarm Manifold Pressure Alarm 0-ok, 1-alarm Percent Capacity Alarm 0-ok, 1-alarm Percent Volume Alarm 0-ok, 1-alarm Run Cycle Oil Press Alarm 0-ok, 1-alarm Filter Pressure Start Alarm 0-ok, 1-alarm Filter Pressure Run Alarm 0-ok, 1-Alarm Suction Temp Trip 0-ok, 1-trip Discharge Temp Trip 0-ok, 1-trip Lo Oil Separator Temp 1 Trip 0-ok, 1-trip Lo Oil Separator Temp 2 Trip 0-ok, 1-trip Lo Oil Injection Temp Trip 0-ok, 1-trip Hi Oil Injection Temp Trip 0-ok, 1-trip Suction Pressure Trip 0-ok, 1-trip Discharge Pressure Trip 0-ok, 1-trip Manifold Pressure Trip 0-ok, 1-trip Percent Capacity Trip 0-ok, 1-trip Percent Volume Trip 0-ok, 1-trip Start Cycle Oil Pressure Temp 0-ok, 1-trip Run Cycle Oil Press Trip 0-ok, 1-trip Filter Pressure Start Trip 0-ok, 1-trip Filter Pressure Run Trip 0-ok, 1-trip Motor Aux Safety Trip 0-no, 1-trip Aux #1 Safety Relay Trip 0-no, 1-trip 16 Metasys Integrator Metasys Integrator Vilter Application

Evaporative Condenser Table 6: Evaporative Condenser NPT 1 NPA 2 Unit Description 1 2 3 4 5 6 7 8 9 10 Amps % # # Hour Ambient Temperature Spare Temperature #1 Spare Temperature #2 Spare Temperature #3 Condenser Pressure Motor Current Percent Capacity Total Fans On Total Pumps On Condenser Runtime BI 1 Condenser Control On 0-no 1-yes BI 2 Alarm Active 0-ok, 1-alarm BI 3 Trip Active 0-ok, 1-trip BI 4 Mode 0-local, 1-central BI 5 Comp Wait - Condenser Pressure 0-ok, 1-wait BI 6 Ambient Temperature Alarm 0-ok, 1-alarm BI 7 Condenser Pressure Alarm 0-ok, 1-alarm BI 8 Ambient Temperature Temp 0-ok, 1-trip BI 9 Condensing Pressure Trip 0-ok, 1-trip BO 1 Mode Off/Auto 0-off, 1-auto BO 2 Alarm Acknowledge 0-n/a, 1-ack 1 Network Point Type 2 Network Point Address Metasys Integrator Metasys Integrator Vilter Application 17

18 Metasys Integrator Metasys Integrator Vilter Application

Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator Technical Bulletin. This section contains details specific to Vilter applications. Mapping to a CS Object Table 7: Software Model and CS Object Definition Application Software Model (on Models diskette) Display Attribute (recommended) Reciprocating Twin Screw Single Screw Evaporative Condenser VM_RECIP.DDL VM_TSCRW.DDL VM_SSCRW.DDL VM_EVPCD.DDL 5 Suction Pressure 1 Ambient Temperature NT Command Attribute (recommended) BI1 On BI1 Condenser Control On Metasys Integrator Metasys Integrator Vilter Application 19

Notes Controls Group FAN 629.5 507 E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Metasys Integrator Release 5.0 Milwaukee, WI 53201 Printed in U.S.A. 20 Metasys Integrator Metasys Integrator Vilter Application