Air-to-water Heat Pump Monobloc Versati

Similar documents
Air-to-water Heat Pump Split Versati

VERSATI SERIES AIR TO WATER HEAT PUMP WATER HEATER

AIR TO WATER HEAT PUMP SERVICE MANUAL Versati II

S-Therm Air to Water Heat Pumps

Product Line Introduction. Karl Zhang Technical support engineer

HERO SERIES-DC INVERTER HEAT PUMPS

ULTRA SERIES CIRCULATING AIR SOURSE HEAT PUMP WATER HEATER

DC Inverter Smart VRF Products(R410A)

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

MINI CHILLER INVERTER H4 Service manual MUENR-H4 (5, 7, 10, 12, 14, 16 kw)

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

13 SEER CONDENSING UNITS & AIR HANDLERS

INSTALLATION AND USER MANUAL

MODELS LIST. Nominal Capacity RT

Do you want a versatile solution

INSTALLATION AND USER MANUAL

Amendment Sheet. Nomenclature M 5 AC V 100 C R - F X AA. Code : M5ACV Date : Superceded : M5ACV

EVI Scroll Air To Water Heat Pumps

DAIKIN Modular Inverter Air Cooled Chiller

Modular Air-cooled Scroll Chiller

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

PAC BT LOW TEMPERATURE HEAT PUMP

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump

Air Cooled Scroll Chiller

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

R22 air-cooled modular chiller 50Hz unit. Content

Multi Inverter Air Conditioning Condensing Units - Summary

Air to Water SPLIT TYPE & MONOBLOCK TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING. High Power model Comfort model Compact model

COMMERCIAL AIR CONDITIONERS. R410A All DC Inverter VRF V5 X Series 50/60Hz

NABILATON PRO. The Nabilaton Pro heat pumps consist of MDV brand outdoor units and suitable hydraulic modules from Nabilaton.

MRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design

Condensing Unit Service Manual (T1/R410a/60Hz)

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

Aqua Mini Full DC Inverter Unitary Chiller 50Hz. Content

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

MAC-A R410A Series Air cooled Modular Chiller

C&H NORDIC Commercial 4 SERVICE MANUAL

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

NATURAL HEATING MACHINE


SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01G (Replace: 5BPM0-01F)

mini-cassette W MULTI SPLIT R410A & VRF SERIES AUTO MODEL MDH13HLS MDH13HLS

AHU Plus. DX Air Handling Units

DES IGN I T ALI A N O

Hot water supply. Indoor unit. Domestic hot water tank. Take thermal energy from atmosphere. Outdoor unit

SOLUTIONS DE TRAITEMENT HEATING SOLUTIONS. Comfort Module 5-20 kw. Choose the easy heating solution!

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

High temperature air-to-water heat pumps

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

LZT High efficiency air to water heat pumps with E.V.I. compressors

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C

CASE STUDY AIR-CONDITIONERS

Digital Inverter 4 series 8 & 10HP

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01J (Replace: 5BPM0-01H)

HT V2 HT Split

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics Distributed by

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

Inverter Hot Water Heat Pumps

Air-water heat pump. Hydronic terminals. HYDROLution NEW 172 SINGLE HT 176 DUAL HT 178 MINI CHILLER 180 MODULAR CHILLER 182 WARM COIL 184 FAN COIL 186

Technical data LA 60TUR+

Commercial Air Conditioners. VRF 60Hz V4+S/V4+R/V4+W/Mini VRF

2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER. AIR-TO-WATER HEAT PUMP cooling - heating

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

VENTILATION. Effective heat exchange and fresh air ventilation

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

TABLE OF CONTENTS ERSQ-AAY1

All DC Inverter Multi VRF

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

Compact design & easy maintenance

Inverter Swimming Pool Heat Pump

Models: ACC 75D/DR ACC 100D/DR. ACC - D (Draft) Ceiling Concealed Split Systems

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Technical Manual Binair Monobloc Heat Pump

Technical Manual. R410A 50Hz Universal Outdoor Series Inverter type. R410A50Hz Universal Outdoor Series Technical Manual LCAC/2016.

DESIGN ITALIANO

The Energy Solutions of Withair Heat Pumps Catalogue 2017 Take Control of Your Energy Future!

Part 1 General Information... 1 Part 2 Indoor Units... 7 Part 3 Outdoor Units Part 4 Installation Part 5 Control...

The natural. hoice installer leaflet. DAikin Altherma low temperature heat pump

Increase your flexibility.

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Transcription:

Change for life Air-to-water Heat Pump Monobloc Versati Engineering Data GREE ELECTRIC APPLIANCES, INC.OF ZHUHAI

CONTENTS 1 Product Data... 1 1.1 Lineup... 1 1.2 Nomenclature... 1 1.3 Product Features... 2 1.4 Operating Principle... 4 1.5 Technical Data... 5 2 Outline Dimensions... 7 3 Explosive Views and Part Lists... 8 4 Supply Scope...11

Engineering Data 1 Product Data 1.1 Lineup 1.1.1 Main Unit Model Product Code Cooling Capacity (kw) Heating Capacity (kw) GRSCQ14Pd/ NaC-M ER01000110 14.5 14.2 GRSCQ12Pd/ NaC-M ER01000120 GRSCQ10Pd/ NaC-K ER01000140 GRSCQ8.0Pd/ NaC-K ER01000130 Series VERSATI Ⅱ+ Power Supply Refrigerant Appearance 380-415V 3Ph 50HZ 13.6 13.0 R410A 9.8 9.5 210-230V ~ 50HZ 8.6 8.2 1.1.2 Water Tank Model Product Code Nominal Cubage(L) SXVD200LCJ/A-K ER20000160 200 SXVD200LCJ/A-M ER20000240 200 SXVD300LCJ/A-K ER20000180 300 SXVD300LCJ/A-M ER20000250 300 SXVD200LCJ2/A-K ER20000170 200 SXVD200LCJ2/A-M ER20000260 200 SXVD300LCJ2/A-K ER20000190 300 SXVD300LCJ2/A-M ER20000270 300 Appearance 1.2 Nomenclature 1.2.1Main Unit G RS 1 2 - C Q 14 Pd 3 4 5 6 NO. Description 1 GREE 2 Heat Pump Water Heater 3 Heating Mode 4 Function 5 Nominal Heating Capacity 6 Compressor Style 7 Refrigerant 8 Design Serial Number 9 Power Supply / Na C 7 8 Options G-GREE Air to water heat pump RS S= Static; C=Circulating Q=Multi-function; Omit=Single-function 6.0=6.0kW; 8.0=8.0kW;10=10kW; 12=12kW; 14=14kW; 16=16kW Pd=DC Inverter; Omit=On/Off Na=R410A B,C,D... K=220-240V,~,50Hz; M=380-415V,3N~,50Hz 1 - M 9

1.2.2 Water Tank SX V D 200 L C J2 / A - K 1 2 3 4 5 6 7 8 9 NO. Description Options 1 Symbol of Heat Pump Water Tank SX 2 Tank Type Default-Common heat pump water tank; V-Heat pump water tank for multi VRF system 3 Function Code Default-No electric heating function; D-Electric heating function available 4 Nominal Water Tank Volume 200=200L,300=300L 5 Structure Type B-Wall mounted type; L-Floor standing type 6 Bearing Default-Non-bearing water tank; C-Bearing water tank 7 Type of Heat Exchange Tube Default-No heat exchanger; J-Inner coil static heating(j-single coil; J2-Double coils); JW-Outer coil static heating 8 Serial Number A,B,C 9 Power Supply K=220V-240V,~,50Hz; M=380V-410V,3ph,50Hz; H=380,3ph 60Hz 1.3 Product Features 1.3.1 General The Versati Ⅱ + monobloc unit is designed specially for the european market where there is a demand for high-tempeature water. Thanks to the dual-stage compression and enthalpy gain through gas injection, the heating energy effficney at low temperateure will rise up greatly with the leaving water temperature up to 61 C. The whole series of products strictly comply with EN14511-2100 and EUROVENT energy efficiency Class A. Their COP can reach up to 4.5. This monobloc unit can realize sapce heating and sanitary hot water supply through terminal units, like the fan coil unit, floor coil and radiator. Environment-friendly refrigerant R410A is adopted for the monobloc unit, with ODP of 0 and quite low GWP. Besides, the adopted heat pump technologies will reduce consumption of coal and other energy source and lower greatly CO 2 emission. Ranged from 4kW~14kW, it is widely applicable to small and medium-sized aparment, large-sized villa etc. 1.3.2 Features Wide Operation Range Heating: -20~35 C; Cooling: 10~48 C; Water Heating: -20~45 C Unique Low-Temp Hi-heat Dual-stage Compressor 1. Under low-temperature conditions, compared with the conventional compressor, the dual-stage low-temp hi-heat compressor will generate less loss of heat capacity and get higher energy efficiency. 2. Floodback, high discharge temperature and other problems can be completely avoided under low-temp conditions and the compressor s reliability will be enhanced greatly. 3. Dual-stage compression, dual-stage throttling and intermediate enthalpy adding though gas injection will raise the leaving water temperature and improve the control accuracy. Upper flange Upper rolle Upper cylinder Partition Lower cylinder Lower flange Crank Cover plate 2

High-efficiency Component(Inverter pump, Inverter fan, Plate heat exchanger) 1. The A-class high-efficiency inverter water pump which complies with the European Erp directive, can control the running frequency based on the actual load. Therefore, it can enhance the operation effcieicy and control the water temperature more accurately. 2. The DC inverter fan can control the air volume accuratately and make the system run more stably and save more energy. 3. The high-efficiency plate heat exchaner will improve the unit s performance largely. All-in-one Design 1. The unit can integrate with terminal units, like the radiator, floor heating device, FCU, water heating device, solar kit, gas furnace and swimming pool etc. Versatile functions can meet various kinds of demands from different users and enhance applicability of this product. 2. The all-in-one structure design can save more installation cost, reduce risks of refrigerant leak, and improve safety and reliability of the system. Brand-new Controller 1. White appearance, exquisite design, and the wall-mounted design will facilitate installation; 2. The dot-matrix display can show in both English and Chinese to show information in a more direct and convenient way. 3. The six-lattice display pattern will accommodate more information. 4. The 12V JACK interface can supply power to the control separately and lengthen the communication distance. 5. The remote monitoring interface can monitor the unit through the Mobus interface and be integrated into the BMS system Smart Control, Powerful Function 1. The running mode can be switched freely. Furemore, based on different demands, the holiday mode, environment-dependent mode, quite timer,tempertuere timer and floor commingming can activated. 2. Multiple protections can make this product much safer. The added electric heater will prevent the plate heat exchanger from being frostbitten owing to too low water temperature and resultantly extend the service life of the product and enhance its safety and reliability. 3. The newly developed smart defrosting control program, do defrost when necessary; do not defrost when unnecessary; defrost more when it frosts heavily; defrost less when it frosts lightly, can bring more comfortability, avoid inadequacy of heat supply and ensure sustainbale heat supply for the users. 3

1.4 Operating Principle 1.4.1 Schematic Diagram No. Name No. Name No. Name No. Name 1 Inverter compressor 13 Solenoid valve 25 Water filter 37 2 Discharge temperature sensor 14 EXV 2 26 Inlet temperature sensor (plate heat exchanger) Solar system inlet temperature sensor 38 Water separator 3 High-pressure switch 15 Low pressure sensor 27 Safety valve 39 2-way Valve 1 4 High pressure sensor 16 5 4-way Valve 17 Suction temperature sensor Outlet water temperature sensor (plate heat exchanger) 6 Finned heat exchanger 18 Auxiliary electric heater 30 28 Exhaust valve 40 Floor radiator 29 3-way valve 2 41 Water collector Water tank temperature sensor 1 42 FCU 7 Environment temperature sensor 19 Expansion tank 31 Water tank 43 By-pass valve 8 Defrosting temperature sensor 20 Main outlet temperature sensor 32 Solar system outlet temperature sensor 44 Vapor liquid separator 9 Filter 21 Main water pump 33 Solar system flow switch 45 Main plate heat exchanger 10 EXV 1 22 Main flow switch 34 Solar system water pump 46 Water tank temperature sensor 2 11 Flasher 23 Outlet pipe connector 35 Solar panel 12 Pressure sensor 24 Inlet pipe connector 36 Solar panel temperature sensor 4

1.5 Technical Data 1.5.1 Parameter List 5 Engineering Data GRS-CQ8.0Pd/ GRS-CQ10Pd/ GRS-CQ12Pd/ GRS-CQ14Pd/ Model NaC-K NaC-K NaC-M NaC-M Product Code ER01000130 ER01000140 ER01000120 ER01000110 Capacity* 1 Cooling(floor cooling) kw 8.6 9.8 13.6 14.5 Heating(floor heating) kw 8.2 9.5 13.0 14.2 Power Cooling(floor cooling) kw 2 2.5 3.45 3.70 Input* 1 Heating(floor heating) kw 1.82 2.2 2.85 3.35 EER* 1 (floor heating) W/W 4.3 3.92 3.94 3.92 COP* 1 (floor heating) W/W 4.51 4.3 4.56 4.24 Capacity* 2 Cooling(for Fan coil) kw 6.2 7.4 9.55 10.30 Heating(Fan coil or Radiator) kw 7.8 9.5 12.5 13.0 Power Cooling(for Fan coil) kw 1.9 2.38 3 3.3 Input* 2 Heating(Fan coil or Radiator) kw 2.3 2.69 3.35 3.60 EER* 2 (for Fan coil) W/W 3.26 3.11 3.18 3.12 COP* 2 (Fan coil or Radiator) W/W 3.39 3.53 3.73 3.61 Refrigerant charge volume kg 3.5 3.5 4 4 Sanitary water Temperature 40~80 40~80 40~80 40~80 Sound cooling db(a) 53 53 54 54 Pressure Level heating db(a) 56 56 57 57 Dimensions Outline mm 1390 412 890 1350 384 1438 (W D H) Packaged mm 1463 428 1020 1440 430 1500 Net weight/gross weight kg 148/161 205/220 Notes *1 indicates the capacity and power input are tested based on the conditions below. 1Cooling Indoor Water Temperature: 23 C/18 C; Outdoor Temperature: 35 CDB/24 CWB 2Heating Indoor Water Temperature: 30 C/35 C; Outdoor Temperature: 7 CDB/6 CWB *2 indicates the capacity and power input are tested based on the conditions below. 1Cooling Indoor Water Temperature: 12 C/7 C; Outdoor Temperature: 35 CDB/24 CWB 2Heating Indoor Water Temperature: 40 C/45 C; Outdoor Temperature: 7 CDB/6 CWB 1.5.2 Nominal Working Conditions Water Side Heat Source/User Side Item Entering Water Temp ( C) Leaving Water Temperature ( C) Dry Bulb Temperature ( C) Wet Bulb Temperature ( C) FCU Cooling 12 7 35 FCU Heating 40 45 7 6 Floor Cooling 23 18 35 Floor Heating 30 35 7 6 Water Heating 53-7 6 1.5.3 Operation Range Item Water Side Leaving Water Temperature ( C) Heat Source/User Side Environment Dry Bulb Temperature ( C) Cooling 7 ~ 25 10~48 Heating 25 ~ 60-20~35 Water Heating 40~80 (Water Tank Temperature) -20~45 Note: when operating conditions are out of the range listed above, please contact GREE.

1.5.4 Electric Data Model Power Supply Leakage Switch Minimum Sectional Area of Earth Wire Minimum Sectional Area of Power Supply Wire V,Ph,Hz (A) (mm 2 ) (mm 2 ) GRS-CQ8.0Pd/NaC-K 63 16 3 16 220-240V,~,50Hz GRS-CQ10Pd/NaC-K 63 16 3 16 GRS-CQ12Pd/NaC-M 40 10 5 10 380-415V,3Ph,50Hz GRS-CQ14Pd/NaC-M 40 10 5 10 Notes 1Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in use, action response time must be less than 0.1 second, leakage circuit must be 30mA. 2The above selected power cable diameters are determined based on assumption of distance from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of power cable must be increased to a further grade. 3The power supply must be of rated voltage of the unit and special electrical line for air-conditioning. 4All electrical installation shall be carried out by professional technicians in accordance with the local laws and regulations. 5Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment of the building and must be installed by professional technicians. 6The specifications of the breaker and power cable listed in the table above are determined based on the maximum power (maximum amps) of the unit. 7The specifications of the power cable listed in the table above are applied to the conduit-guarded multiwire copper cable (like, YJV XLPE insulated power cable) used at 40 C and resistible to 90 C(see IEC 60364-5- 52). If the working condition changes, they should be modified according to the related national standard. 8The specifications of the breaker listed in the table above are applied to the breaker with the working temperature at 40 C. If the working condition changes, they should be modified according to the related national standard. 1.5.5 Capacity Correction Cooling Capacity Correction GRS-CQ8.0Pd/NaC-K, GRS-CQ10Pd/NaC-K, GRS-CQ12Pd/NaC-M, GRS-CQ14Pd/NaC-M Performance correction Leaving Chilled Water ( ) Ambient Temperature ( ) 25(77) 30(86) 35(95) 40(104) 45(113) 5(41.0) 0.995 0.955 0.905 0.855 0.805 6(42.8) 1.045 1.005 0.955 0.905 0.855 7(44.6) 1.090 1.050 1.000 0.950 0.900 8(46.4) 1.145 1.102 1.052 1.000 0.950 9(48.2) 1.190 1.150 1.100 1.050 1.002 10(50.0) 1.245 1.200 1.150 1.100 1.050 11(51.8) 1.290 1.250 1.202 1.152 1.102 12(53.6) 1.340 1.300 1.252 1.200 1.152 13(55.4) 1.390 1.350 1.302 1.252 1.202 14(57.2) 1.442 1.402 1.350 1.302 1.252 15(59.0) 1.490 1.450 1.400 1.350 1.302 18(64.4) 1.539 1.502 1.451 1.402 1.350 Computer of actual cooling capacity: actual cooling capacity = nominal cooling capacity x cooling capacity 6

correction coefficient. Heating Capacity Correction GRS-CQ8.0Pd/NaC-K, GRS-CQ10Pd/NaC-K,,GRS-CQ12Pd/NaC-M, GRS-CQ14Pd/NaC-M Performance Correction Outflow Heated Water ( ) Ambient Temperature ( ) -15(5) -10(14) -5(23) 0(32) 5(41.0) 10(50) 15(59.0) 20(68.0) 25(77.4) 30(86) 0.81 0.91 1.00 1.10 1.18 1.26 1.35 1.41 1.45 35(95) 0.74 0.84 0.93 1.03 1.11 1.19 1.28 1.36 1.41 40(104) 0.67 0.77 0.87 0.96 1.04 1.12 1.20 1.25 1.31 45(113) 0.60 0.70 0.80 0.89 0.97 1.05 1.13 1.19 1.25 50(122) 0.53 0.63 0.73 0.82 0.90 0.98 1.06 1.11 1.18 55(131) 0.46 0.56 0.66 0.74 0.83 0.90 0.98 1.05 1.10 Computer of actual heating capacity: actual heating capacity = nominal heating capacity x heating capacity correction coefficient. 2 Outline Dimensions GRS-CQ8.0Pd/NaC-K, GRS-CQ10Pd/NaC-K 1390 412 361 388 890 GRS-CQ12Pd/NaC-M, GRS-CQ14Pd/NaC-M 367 340 1430 1390 7

Engineering Data 3 Explosive Views and Part Lists GRS-CQ8.0Pd/NaC-K, GRS-CQ10Pd/NaC-K No Name Code 1 Handle 26235253 2 Front Side Plate 3 01312800031P 3 Water Pump 43138223 4 Steam Current Switch Sub-assy 45028062 5 Filter 07412808 6 Magnet Coil 4300040029 7 Expansion Drum 07422800004 8 Sensing Device 322101002 9 4-way Valve 43040000002 10 Pressure Protect Switch 460200062 11 Accumulator 07424100031 12 Electrical Heater(Compressor) 7651521216 13 Compressor and Fittings 00202800017 14 Gas-liquid Separator Sub-Assy 0722501801 15 Electromagnetic Valve 43044107 16 Pressure Sensor(High Pressure) 322101037 17 Magnet Coil 4300040062 18 Plate-type Heat Exchanger 00902800030 19 Electrical Heater 765100047 20 Drainage Connecter 06123401 21 Drainage Hole Cap 06813401 22 Front Side Plate 2 01312800030P 23 Front Side Plate Sub-Assy 01312800037P 24 Diversion Circle 10474100001 25 Cabinet 01514100002P 26 Front Grill 01574100009 27 Heater 32112800008 28 Axial Flow Fan 10338731 29 Strainer 07212121 8

30 Electric Expand Valve Fitting 4304413228 31 Left Side Plate 01314100013P 32 Fan Motor 1570411501 33 Electric Expand Valve Fitting 4304413227 34 Electronic Expansion Valve 07334468 35 Fan Motor 15704115 36 Motor Support Sub-Assy 01802800138 37 Sensor (High Pressure) 322101032 38 Electric Box Assy 01392800137 39 Terminal Board 42010249 40 Terminal Board 42011254 41 Terminal Board 42011135 42 Terminal Board 42011103 43 Terminal Board 42011051 44 Transformer 4311027001 45 Reactor 43130192 46 AC Contactor 44010232 47 Radiator 49018000074 48 Thermostat 4504800201 49 Display Board 30292000031 50 Receiver Board 30261014 51 Coping 01262800143P 52 Main Board 30223000013 53 Inductance 43128000014 54 Main Board 30224000070 55 Filter Board 30223000044 56 Main Board 30223000060 57 Electrical Heater 32112800002 58 Relief Valve 07382814 59 Auto Air Outlet Valve 07108208 60 Condenser Assy 01122800076 61 Rear Grill 01574100004 62 Sensor Support 26905202 63 Silencer 07245012 64 Rear Side Plate 01312800032P 65 Temperature Sensor 3900028316G 9

GRS-CQ12Pd/NaC-M, GRS-CQ14Pd/NaC-M No Name Code 1 Handle 26235253 2 Front Side Plate 3 01312800031P 3 Water Pump 43138223 4 Steam Current Switch Sub-assy 45028062 5 Filter 07412808 6 Magnet Coil 4300040029 7 Expansion Drum 07422800004 8 Sensing Device 322101002 9 4-way Valve 43040000002 10 Pressure Protect Switch 460200062 11 Accumulator 07424100031 12 Electrical Heater(Compressor) 7651521216 13 Compressor and Fittings 00202800017 14 Gas-liquid Separator Sub-Assy 0722501801 15 Electromagnetic Valve 43044107 16 Pressure Sensor(High Pressure) 322101037 17 Magnet Coil 4300040062 18 Plate-type Heat Exchanger 00902800030 19 Electrical Heater 765100047 20 Drainage Connecter 06123401 21 Drainage Hole Cap 06813401 22 Front Side Plate 2 01312800030P 23 Front Side Plate Sub-Assy 01312800037P 24 Diversion Circle 10474100001 25 Cabinet 01514100002P 26 Front Grill 01574100009 27 Heater 32112800008 28 Axial Flow Fan 10338731 29 Strainer 07212121 10

30 Electric Expand Valve Fitting 4304413228 31 Left Side Plate 01314100013P 32 Fan Motor 1570411501 33 Electric Expand Valve Fitting 4304413227 34 Electronic Expansion Valve 07334468 35 Fan Motor 15704115 36 Motor Support Sub-Assy 01802800138 37 Sensor (High Pressure) 322101032 38 Electric Box Assy 01392800137 39 Terminal Board 42010249 40 Terminal Board 42011254 41 Terminal Board 42011135 42 Terminal Board 42011103 43 Terminal Board 42011051 44 Transformer 4311027001 45 Reactor 43130192 46 AC Contactor 44010232 47 Radiator 49018000074 48 Thermostat 4504800201 49 Display Board 30292000031 50 Receiver Board 30261014 51 Coping 01262800143P 52 Main Board 30223000013 53 Inductance 43128000014 54 Main Board 30224000070 55 Filter Board 30223000044 56 Main Board 30223000060 57 Electrical Heater 32112800002 58 Relief Valve 07382814 59 Auto Air Outlet Valve 07108208 60 Condenser Assy 01122800076 61 Rear Grill 01574100004 62 Sensor Support 26905202 63 Silencer 07245012 64 Rear Side Plate 01312800032P 65 Temperature Sensor 3900028316G 4 Supply Scope S= Standard O= Optional F= Field Supplied Name Standard Optional Field Supplied Owner's Manual for the Main Unit / / Owner s Manual for the Control / / 2-way Valve / / 3-way Valve / / Remote Temperature Sensor / / Wired Controller / / Communication Cable / / Water Tank Temperature Sensor / / Expansion Bolt / / Solar System Water Pump / / Solar System Flow Switch / / 11