D326A/D334A/D339A. Installation Instructions. Point Contact Modules

Similar documents
These instructions detail procedures to follow in order to avoid damage to equipment.

Addressable NAC Output Module D327A

D7052. Installation Instructions Multiplex Dual Input Module

D7044. Installation Instructions Multiplex Single Input Module

D7053. Installation Instructions Multiplex Input/Output Module

DS7465i. Installation Instructions. Input/Output Module

F220-B6PS/M. Installation Guide. Addressable Detector Bases

FMR Installation Instructions. Addressable Fire System Controller

Notification Appliance Circuit Module

D250A/D253/D261AW/D280A/D290 Series

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

Multiplex Eight Input Remote Modules

SIGA-CC1 Single Input Signal Module Installation Sheet

Remote NAC Power Supply D7038

Print Specification. Publication. Instructions. Specific requirements. General requirements

Duct smoke housing, 2-wire D340/D340P

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Control Relay Modules

Signature Series Auto-Sync Output Module (CC1S)

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

Multi-Application Peripherals and Accessories

Battery charger modules

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

Fire Control/Communicator

Booster Power Supply Manual

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

D720 and D1255 Command Centers

Operation and Installation Guide. Zone Expansion Module D8125

D8125MUX. Operation and Installation Guide. Multiplex Bus Interface

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

D2071A. Operation & Installation Guide Fire Alarm Control Panel

D343. Installation Instructions. Air Duct Smoke Housing

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

Commercial Series TriTech Motion Detector. Reference Guide

MMF Six Zone Interface Module

Installation Guide for models:

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

Installation Guide for models:

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

IDP-Zone-6 Six Zone Interface Module

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

ECC-50/100(E) Emergency Command Center

TrueAlarm Analog Sensing

GEMC-FW-SLC FIRE SIGNALING LINE CIRCUIT MODULE INSTALLATION INSTRUCTIONS

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

Public Safety DAS Annunciator Panel

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

MR-2602 Two Zone Fire Alarm Control Panel

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

RELEASE DEVICE CONTROLS

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

Installation Guide. Control/Communicator

AL600ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide

Independent Zone Control (I.Z.C.)

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

System Accessories, LCD Annunciators

/5121/5122 TrueAlert Power Supply Installation Instructions

June 10, 2002 DF C S2424

LifeAlarm Fire Alarm Control Panels

General Routing Interface

LifeAlarm Fire Alarm Controls

SECTION FIRE ALARM SYSTEMS

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

PSN-1000 & PSN 1000(E) Installation Manual

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

D7024 Fire Alarm Control Panel

Conventional Fire Alarm Systems

Releasing System Peripherals

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Duct and Rough Service Carbon Monoxide Sensor

MONROE PUBLIC LIBRARY WATERFLOW MONITORING SYSTEM

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

AU MX Digital Loop Card Installation Instructions

July 14, 1999 DF C-100.

4100U City and Relay Cards Installation Instructions

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Installation Instructions Model HZM

TrueAlert Addressable Notification Appliances

TrueAlert Addressable Notification Appliances

ECC-50/100C. Emergency Command Center

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

MANUAL RESET ALARM RELEASE

TrueAlert Addressable Notification Appliances

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

SC-6 Six Supervised Control Module

TECHNICAL DATA OBSOLETE

Transcription:

D326A/D334A/D339A EN Installation Instructions Point Contact Modules

D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point Contact Modules in an analog system that is controlled by a Bosch D8024, D9024, or D10024A Analog Fire Alarm Control Panel (FACP). These modules provide a Class B/Style B initiating device circuit, and allow the panel to supervise their circuits for contact closure, contact opening, or wiring fault. Installing detection devices in an analog system consists of the following: Addressing the devices Wiring the modules to the FACP Installing the module in a back box. Install, test, and maintain these devices according to these instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction (AHJ). Failure to follow these instructions could result in failure of the device to initiate a proper response. Bosch is not responsible for improperly installed, tested or maintained devices. 1.0 Description The D326A, D334A, and D339A are single ID addressable device input modules. They provide a point for connection of a two-wire dry contact closure device input loop with the FACP. All are UL Listed for fire alarm initiating device and supervisory device applications. The address is set by programming an EEPROM microchip. The D326A module mounts on a plate that attaches directly to a UL Listed four-inch square back box having a minimum depth of 2-1/8 inches. A cover plate leaves the status LED visible. The D326A has a response time of 2 seconds. The D334A module is mounted in a plastic enclosure that attaches to the inside of a back box and is normally out of view. The D334A has a response time of 2 seconds. The D339A is part of the D325A Manual Fire Alarm Box. The D339A allows a FACP to recognize activation within 2 seconds. This module can be mounted into any gang back box. The D326A and D334A have an LED that flashes green when the module is active, indicating that they are correctly programmed and learned into the system. When a device is polled, the LED flashes once every 18 seconds. The LED latches on red when an input circuit is in alarm (detection loop shorted). 2.0 Device Addressing The device address must be set before the cover plate is attached. When using the back box enclosure, the address must be set before the module is placed in the enclosure. Each module in an analog system has a specific address that is set by programming an EEPROM microchip. Each polling circuit can support up to 126 addresses. It is not necessary to wire the devices in any particular order in the circuit. 2.1 D5070 Analog Device Programmer The D5070 Analog Device Programmer must be used when programming addresses on the D326A, D334A and the D339A. Make sure the battery is connected prior to programming. Figure 1: D5070 Analog Device Programmer 1 Module programming jack receptacle 2 Twist on sensor head here 3 Display 4 Programming buttons 2 Bosch 12/04 37098G

D326A/D334A/D339A Installation Instructions 2.0 Device Addressing. Figure 2: Modular Programming Adapter 1 Non-polarized plug 2 To remote programming jack 2.1.1 Programming Buttons Refer to Table 1 for a description of the D5070 Analog Device Programmer s three programming buttons. Table 1: D5070 Programming Buttons 4. When the desired address is displayed, press the red button to store that address. The three red dots on the display disappear. 5. To program the address on the D339A, the black and red wires that extend from the Programming Adapter must be wired to the terminal strip on the D339A module (refer to Figure 3). Plug the remote programming jack on the Programming Adapter into the remote programming jack receptacle on the D5070 Analog Device Programmer, and then follow Steps 2 through 4 as described above. 2.1.3 Reading Analog Values Install the module and power the D5070 up as previously described. Press the red button. An A appears on the display followed by the analog value (refer to Table 2). This value is continuously updated for 3 minutes or until the unit is turned off. Table 2: Analog Values Programming Button Left, gray Right, gray Red Description Power On. Automatically reads the address of a sensor. Subsequent operations will advance the device by ten. Power Off. Advances the device address by one. Stores the displayed address to the device, and is used to read analog levels. 2.1.2 Address Setting The following steps explain how to set an address using the D5070 Analog Device Programmer. For more details, refer to Figure 1 and Figure 2 on page 2 and Figure 3 and Figure 4 on page 4. 1. To program the address on the D326A or D334A, insert the non-polarized plug on the Programming Adapter into the address programming pins on the D326A/D334A module. Plug the remote programming jack on the Programming Adapter into the remote programming jack receptacle on the D5070 Analog Device Programmer (refer to Figure 3, page 4). 2. Press the left gray button to turn the D5070 on. A battery check message appears followed by the device s address. 3. Set the required address by pressing the left and right gray buttons until the desired address is reached (the display shows three red flashing dots if the address being programmed is different than the device s current address). Description D5070 Reading FACP Reading Normal Reading 0 16 Alarm 1 64 Open Condition* E6 (refer to Table 2) 44 * For example, No EOL 2.1.4 Display Messages Table 3 lists the display messages that might appear on the D5070 Analog Device Programmer. Table 3: D5070 Display Messages Display Messages bat E0 E1 E2 E3 E4 E5 E6 Description Battery Check. Displayed upon power up, and when the battery is low. A low battery is good for up to 3,000 address setting operations. The panel does not recognize addresses past 127. Attempting to program an address with no device connected. Cannot find the device after power up or replace device. Replace the detector. Cannot find the device to program. Device read error. Replace the detector. Bosch 12/04 37098G 3

D326A/D334A/D339A Installation Instructions 2.0 Device Addressing Figure 3: D326A/D334A Programming Connections 1 Status LED 2 Address programming pins 3 Non-polarized plug 4 To module programming jack receptacle 5 D326A/D334A Point Contact Modules Figure 4: D339A Programming Connections 1 To programmer 2 Black 3 Red 4 Bosch 12/04 37098G

. 3.0 Wiring Connections Disconnect all power to the FACP before installing any of these modules. 3.1 Module to FACP Connections Analog polling circuits connect to the FACP over two-wire cable. The circuit resists interference from most types of EMI and RF generated noise, and no special wiring requirements are required other than attention to wire gauge. Under extremely noisy conditions, use twisted pair wire to reduce interference. Polling circuits connect the FACP in either a Class A or Class B circuit. T tapping is acceptable in Class B circuits only. Consult NFPA 72 for specific Class A and Class B circuit installation requirements. Refer to the FACP s installation instructions for details. FACP polling circuit wiring and initiating device circuit wiring for the D326A, D334A, and D339A is identical. 3.1.1 Circuit Length Data circuit length is the distance over the circuit wire from the connection at the FACP to the most distant device and back to the FACP. Data circuit length must include the distance to any device connected to the circuit in a T tap. The screw terminals can accept 14 AWG (1.5 mm), but this reduces the allowable length of the circuit (refer to Table 4). Table 4: Polling Circuit Length/Wire Gauge D326A/D334A/D339A Installation Instructions 3.0 3.1.2 Shielded Cable Wiring Connections Unless the shielded cable is properly grounded, it might aggravate rather than eliminate noise problems. The shield must be reconnected each time the cable is cut to install a device. If Electro-magnetic interference (EMI) is a problem, use shielded cable. Ground the drain wire to the E terminal on the FACP Control Module. Refer to the FACP s installation instructions for details. If shielded cable is used, and the cable is of good quality, then it should not have a significant effect on the polling circuit length. Good quality shielded cable will allow 1 µf of capacitance, 1 mh of inductance and 50 Ω resistance. Connect the drain wire for shielded cable to the E terminal on the FACP s data terminal block. Refer to Figure 5 for details. Figure 5: FACP Shielded Cable Connections Polling Circuit Length Up to 4,000 ft (1,219 m) Up to 7,200 ft (2,195 m) Up to 6,800 ft (2,073 m) Wire Gauge 18 (1.1 mm) 16 (1.3 mm) 14 (1.5 mm) 1 Data/power positive (+) in 2 Data/power common ( -) in 3 Earth ground for shield cable drain 4 Data/power positive (+) out 5 Data/power common ( -) out 6 Data terminal block Bosch 12/04 37098G 5

D326A/D334A/D339A Installation Instructions 3.0 Wiring Connections 3.1.3 FACP Polling Circuit Connections Wire the D326A, D334A, or the D339A in the polling circuit by connecting the Data/Power Positive (+) and Data/Power Common (-) terminals as shown in Figure 6. The D334A is shown as an example. Figure 6: FACP Polling Circuit Connections 1 To/from dry contact notification appliance activation circuit 2 Data/power common in/out 3 Data/power positive in/out 4 Data/power positive 5 Data/power common 6 Bosch 12/04 37098G

. 3.2 Initiating Device Circuit Connections D326A/D334A/D339A Installation Instructions 3.0 Wiring Connections The Initiating Device Circuit can use any number of UL-listed Normally Open (N/O) contact closure devices. Device circuit wiring should not exceed 50 Ω. Install contact closure devices according to the manufacturer s installation instructions. All wiring shown is supervised and inherently power-limited. Do not mix fire alarm initiating and supervisory devices on the same module. Figure 7: NFPA 72 Class B/Style B Initiating Device Circuit 1 10 kω EOL resistor 2 Typical initiating device circuit wiring for N/O contact 3 Data/power common in/out 4 Data/power positive in/out Bosch 12/04 37098G 7

D326A/D334A/D339A Installation Instructions 4.0 4.0 Device Mounting Refer to the following sections for specific mounting instructions for each point contact module. 4.1 D326A Mounting The D326A module mounts on a plate that attaches to a 4-inch square electrical box at least 2-1/8 in. deep. A cover plate conceals the address programming pins and leaves the LED visible. After wiring the module to the FACP and connecting the initiating device circuitry as shown in Figure 7 (page 7), attach the D326A plate to the back box as shown in Figure 8. Install the cover plate. 4.2 D334A Mounting Set the D334A address before wiring the module and installing it in the back box. Once the D334A is installed in the back box, setting or changing the address involves removing the device and removing and opening the module case. Device Mounting The D334A mounts in a single gang back box behind the device and is secured with a Velcro patch. A retrofit installation in a manual pull station is a typical application of the D334A. Connect the module to the FACP and to the initiating device as shown in Figure 6 (page 6) and Figure 7 (page 7). Set the module in the enclosure back and snap the enclosure top closed over it. Attach the enclosure to the Velcro patch in the back. Refer to Figure 8 for details. Install the initiating device. 4.3 D339A Mounting The D339A can mount in any single gang back box, and it is part of the D325A Manual Fire Alarm Pull Box. The D339A attaches to the back box with a Velcro patch. Refer to Figure 8 for back box installation details. Figure 8: Mounting the Point Contact Modules 1 Cover plate 2 Point contact module mounting plate 3 back box 4 Enclosure top 5 Point contact module 6 Enclosure back 7 Velcro patch 8 Bosch 12/04 37098G

D326A/D334A/D339A Installation Instructions 5.0 Specifications. 5.0 Specifications Table 5: Point Contact Module Specifications Description Voltage Range D326A D334A D339A 4 in. module on plate 17 VDC to 41 VDC, 24 VDC Nominal Remote module 17 VDC to 41 VDC, 24 VDC Nominal Remote module 17 VDC to 41 VDC, 24 VDC Nominal Idle Current 350 µa 350 µa 350 µa Polling Current Alarm Current 22 ma ±20% 22 ma ±20% 22 ma ±20% 28 ma 28 ma 28 ma Bosch 12/04 37098G 9

D326A/D334A/D339A Installation Instructions Notes Notes 10 Bosch 12/04 37098G

. D326A/D334A/D339A Installation Instructions Notes Notes Bosch 12/04 37098G 11

Bosch 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 2004 Bosch 37098G