INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 3-1/2 thru 5 Ton Wall Mount Air Conditioners and Heat Pumps

Similar documents
INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ERVR-A3D-X ERVR-C3D-X RETROFIT ENERGY RECOVERY VENTILATOR

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV. Bard Manufacturing Company, Inc.

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES EHWA02-AXD EHWA02-AXH EHWA03-AXH EHWA03-AXK EHWA05-AXH EHWA05-AXK

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES

INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH

INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

LOW VOLTAGE CONTROL CIRCUIT WIRING

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY) CONTROL BOX KIT (12 VDC HEAT/COOL)

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes

QW SERIES WALL SLEEVE (THROUGH WINDOW OPENING) INSTALLATION INSTRUCTIONS. Bard Manufacturing Company, Inc. Bryan, Ohio 43506

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

INSTALLATION & OPERATING INSTRUCTIONS. Roof Top Unit. Model. USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

SERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER

THE WALL-MOUNT TM SIX TON AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

THE WALL-MOUNT 6-TON AIR CONDITIONERS

INSTALLATION INSTRUCTIONS FOR 7330*5511 OR 7330*5512 MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY)

INSTALLATION AND MAINTENANCE INSTRUCTIONS. MCE4 Series. Electric Cooling Package Unit. Save these instructions for future reference

INSTALLATION INSTRUCTIONS

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN CAUSE FIRE, EXPLOSION, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

KR Series Air Defrost Unit Coolers Operating and Installation Manual

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

THE WALL-MOUNT TM QUIET CLIMATE HEAT PUMPS

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS

Installation & Operations Manual for. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers. 4/17 Rev.

GREEN REFRIGERANT R-410A

29" (73.7 CM) ELECTRIC DRYER INSTALLATION INSTRUCTIONS DRYER SAFETY

INSTALLATION INSTRUCTIONS Low Ambient Kit NASA201LA, NASA401LA

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

REPLACEMENT PARTS MANUAL

Installation & Operations Manual for R-290 SERIES. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/

KNHX32 SERIES NEMA 4/4X AIR-TO-AIR HEAT EXCHANGERS

Installation Instructions

INSTALLATION INSTRUCTION

DDNECNJ SEQUENCE OF OPERATION This sequence assumes employment of a single enthalpy economizer using a two stage thermostat.

REPLACEMENT PARTS MANUAL

BMG-HGP & BMG-SLP Model Bottom Mounted Full-Length Glass Door Refrigerator Merchandisers

SWIMMING POOL & SPA HEATER D-2

Your safety and the safety of others are very important.

Installation, Operation, and Maintenance Manual RTE14S & RTE14S-2. For the Taco Bell "Rethermalizer" Model Numbers

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

INSTALLATION INSTRUCTIONS COMMERCIAL DRYER Gas (120-Volt, 60-Hz) or Electric (120/240-Volt, 60-Hz)

Induction Unit. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air

SWIMMING POOL & SPA HEATER D-2

T-Series Air Conditioner T20 Model

REPLACEMENT PARTS MANUAL

DDNECNJ SEQUENCE OF OPERATION This sequence assumes employment of a single enthalpy economizer using a two stage thermostat.

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS

ACNF Series Ceiling-Mount Air Handlers 1½ to 2½ Tons

Installation Instructions

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

Air Conditioner

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS WH381 WH431 WH491

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5

Installation, Operation and Maintenance Manual

GREEN REFRIGERANT R-410A

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

REPLACEMENT PARTS MANUAL

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

Dishwasher. Installation Manual USA FOR MODELS

THE WALL-MOUNT Quiet Climate A/C 10.0 EER

APARTMENT MAINTENANCE SERIES

T-Series Air Conditioner T53 Model

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

CLe-series Dishwashers

Packaged Air Conditioning Units. Owner s Guide to Operating and Maintaining Your Air Conditioner. This manual should be left with the owner.

Transcription:

INSTLLTION INSTRUTIONS OMMRIL ROOM VNTILTORS WITH XHUST MOL RV-5 For Use with ard 3-1/2 thru 5 Ton Wall Mount ir onditioners and Heat Pumps ard Manufacturing ompany ryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-222 Supersedes: 2100-222 File: Volume III Tab 19 ate: 12-15-00 opyright 2000

ONTNTS General... 1 General Information... 1 Unpacking... 1 escription... 1 Installation... 1 asic Installation... 1 lade djustment for esired Ventilation ir... 7 ommercial Room Ventilator W, WH & WL Series... 13 Figures Figure 1 Remove ccess Panels... 2 Figure 2 Remove ir Filter and xhaust over Plate... 3 Figure 3 Reroute Wires Left Hand Units... 4 Figure 4 Install Ventilator... 5 Figure 5 Top View of ontrol Panel... 6 Figure 6 Lead onnections... 7 Figure 7 lower Operation... 12 Figure 8 Loss of lower Operation... 13 Tables Table 1... 8 & 9 Table 2... Table 3... & 11 Manufactured under U.S. patent nuber 5,301,744 Other patents pending OPYRIGHT MR 2000 R MNUFTURING OMPNY RYN, OHIO US 43506

GNRL GNRL INFORMTION The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step by step procedure with which the mechanically inclined owner can install the package. The ventilator housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions. UNPKING Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped. Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier s agent. oncealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt. SRIPTION The RV-5 ventilator is designed to be used with ard 3-1/2 thru 5 ton wall mount series air conditioners and heat pumps. They are electromechanical vent systems designed to provide fresh air to meet indoor air quality standards with built in exhaust provisions. INSTLLTION SI INSTLLTION 1. Unpack the ventilator assembly which includes the integral ventilator with attached electrical harness and miscellaneous hardware. WRNING Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to off. MOL RV-2 RV-3 RV-5 W1881 W241 W301 W361 W421 W482 W602 FOR US WITH FOLLOWING UNITS WH181 WH241 WH301 WH361 WH421 WH482 WH602 WL181 WL241 WL301 WL361 WL421 WL482 WL602 Page 1

2. Remove and save the existing exterior blower access and service access panels on the ard wall mount unit. (See Figure 1.) FIGUR 1 RMOV SS PNLS MIS-425 Page 2

3. Remove and save existing unit air filter and screws from front center grille. (See Figure 2.) 4. Remove and discard the exhaust cover plate. FIGUR 2 RMOV IR FILTR N XHUST OVR PLT MIS-427 Page 3

5. For Installation of Left Hand Units Only Remove strain relief in right side of RV. Un-clip the (2) wire ties holding the wire harness. Reroute wires to left side of RV. Reinstall wire ties in left side holes. Route wires through left side and reinstall strain relief. (See Figure 3.) FIGUR 3 RROUT WIRS FOR LFT HN UNITS ONLY MIS-1334 Page 4

6. Install ventilator by inserting the ventilator into the unit to the far left side clearing the right filter bracket. Once the ventilator is fully inserted, slide the ventilator to the right until it is tight against the back of the control panel. (See Figure 4.) IMPORTNT: front lip of ventilator on top of front grille and condenser partition. (See Figure 4 inset.) This is important to ensure proper drainage of any water entering damper assembly. 7. Open control panel to gain access to unit low voltage terminal block. 8. Route electrical harness leads through the 7/8 bushing in control panel (Figure 4) into low voltage box. FIGUR 4 INSTLL VNTILTOR MIS-426 Page 5

Page 6 FIGUR 5 TOP VIW OF ONTROL PNL MIS-354 NOT: Rotate thumbwheel up to open; down to close.

9. onnect leads with fork terminal to corresponding points on terminal strip to terminals and G. (See wiring diagram, Figure 6 below or on ventilator.) 10. lose control panel cover 11. Replace left filter support, filter and four (4) screws in condenser grille. 12. Reinstall the blower access panel at top of unit and secure with sheet metal screws. 13. Ventilator heckout. Remove mist eliminator to allow access to minimum position thumbwheel. (See Figures 4 & 5.). Resupply power to unit.. nergize the evaporator blower by switching thermostat to the manual fan position with heat/cool in OFF position.. Ventilator should open to the position set by position adjustment thumbwheel. ycle position adjustment thumbwheel to full open through full close. Observe damper blade operation throughout travel to assure free, unobstructed movement. (See Figure 5.). djust position adjustment thumbwheel until desired blade setting is reached with power applied to unit. See Tables 1 through 3 for required blade setting versus ventilator air. F. e-energize evaporator blower. amper blade should close. G. This completes ventilator checkout. 14. Replace mist eliminator. e sure it is installed with the drain holes to the bottom. 15. Remove blank off plate or barometric fresh air damper installed on service access door. Plug four (4) mounting holes with the plastic plugs provided with the ventilator. 16. Replace service access panel. 17. Ventilator is now ready for operation. L JUSTMNT FOR SIR VNTILTOR IR The amount of ventilation air supplied by the commercial room ventilator is dependant on four (4) factors. 1. Return air duct static pressure drop. 2. Supply air duct static pressure drop. 3. Indoor blower motor speed. 4. amper blade open position setting. To determine the amount of fresh air that will be supplied to the structure first determine the pressure drops of the supply and return air ducts. For free blow application with return air filter grille and supply grille assume.05 supply static,.10 return static. See application Table 3. etermine on what speed the evaporator motor is running. Refer to the tables on the following pages to determine the blade setting necessary to achieve the ventilation air requited at the supply and return static duct pressures drops that are applicable. FIGUR 6 L ONNTIONS 4096-121 Page 7

OMMRIL ROOM VNTILTOR RV-5 VNTILTION IR WITH UT SYSTM TL 1 HIGH SP amper Return Static 185 345 500 660 820 270 425 535 685 835 0.00 SUPPLY IR STTI Ventilation ir 350 460 570 415 855 390 500 615 740 870 (FM) 425 540 660 770 885 490 595 710 805 910 550 650 755 840 930. 25.30 HIGH SP amper Return Static 175 325 480 630 780 260 385 515 660 805 0.20 SUPPLY IR STTI Ventilation ir 350 450 550 690 830 390 495 600 720 840 (FM) 430 540 650 750 850 490 590 695 785 875 550 645 740 820 900. 25.30 HIGH SP amper Return Static 185 320 460 600 745 255 375 500 625 755 0.30 SUPPLY IR STTI Ventilation ir 330 435 540 655 770 380 485 590 690 795 (FM) 430 535 640 730 820. 25.30 HIGH SP amper Return Static 195 320 440 575 710 255 365 480 595 710 0.40 SUPPLY IR STTI Ventilation ir 315 420 525 650 715 (FM). 25.30 Page 8

TL 1 (continued) LOW SP amper Return Static 200 295 390 520 650 260 345 430 550 675 0.00 SUPPLY IR STTI Ventilation ir 320 395 470 585 700 380 460 540 630 725 (FM) 440 525 610 680 750. 25.30 LOW SP amper Return Static 185 280 380 505 635 250 335 425 540 660 0.10 SUPPLY IR STTI Ventilation ir 310 385 465 570 680 375 450 530 620 710 (FM) 435 515 595 665 740. 25.30 LOW SP amper Return Static 180 275 370 490 615 240 325 415 525 635 0.20 SUPPLY IR STTI Ventilation ir 300 380 465 560 660 365 445 530 610 690 (FM) 430 510 595 655 720. 25.30 Page 9

NON-UT LOW PPLITION VNTILTION IR WITH RTURN IR FILTR GRILL N SUPPLY IR GRILL TL 2 Ventilation ir (FM) High Speed Low Speed amper Posiiton 350 460 575 720 870 315 390 465 575 690 RV-5 TOTL LIVR IR WH602, W602 and WL602 TL 3 HIGH SP LOWR amper Total Static lose 2040 2030 1995 1960 1885 1810 TOTL LIVR IR 1955 1950 1910 1875 1750 1725 1870 1870 1830 1790 1615 1640 1775 1775 1740 1700 1575 1550 (FM) 1680 1680 1645 1610 1535 1460 1585 1585 1550 1520 1490 1370. 00. 30. 40.50 LOW SP LOWR amper Total Static lose 1510 1490 1465 1440 1405 1370 TOTL LIVR IR 1480 1460 1435 1415 1375 1340 1450 1430 1410 1390 1350 1310 1420 1400 1380 1360 1320 1280 (FM) 1385 1370 1350 1330 1290 1255 1350 1340 1320 1300 1260 1230.25 Page 10

RV-5 TOTL LIVR IR WH482, W482 and WL482 WH421, W421 and WL421 TL 3 (continued) HIGH SP LOWR amper Total Static lose 1865 1860 1850 1840 1770 1700 TOTL LIVR IR 1775 1770 1755 1740 1680 1610 1685 1685 1660 1655 1590 1525 1585 1585 1560 1555 1490 1425 (FM) 1485 1485 1460 1455 1390 1325 1485 1385 1360 1355 1290 1225. 00. 30. 40.50 LOW SP LOWR amper Total Static lose 1560 1545 1530 1510 1480 1445 TOTL LIVR IR 1530 1515 1495 1485 1450 1415 1500 1480 1460 1455 1420 1380 1460 1445 1430 1420 1385 1345 (FM) 1425 1415 1400 1385 1345 1305 1390 1380 1365 1350 1310 1270.25 Page 11

OMMRIL ROOM VNTILTOR W, WH N WL SRIS FTURS One piece construction easy to install with no mechanical linkage adjustment required. xhaust air damper built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings. ctuator motor 24 volt, power open, spring return with built in torque limiting switch. Provides up to 75 percent of outside air. OMMRIL ROOM VNTILTOR SQUN OF OPRTION On a call for blower operation, RV opens to a position as set by minimum position potentiometer. See Figure 7. FIGUR 7 LOWR OPRTION SUPPLY IR OOLING OIL MPR L RTURN IR OUTSI IR XHUST IR ON. IR ONNSR OIL MIS-347 Page 12

call for cooling cycles the compressor, and dampers remain in the ventilation mode. On loss of blower operation, RV closes fully. See Figure 8. FIGUR 8 LOSS OF LOWR OPRTION SUPPLY IR OOLING OIL RTURN IR MPR L ON. IR ONNSR OIL MIS-348 Page 13