TQ4400 TANKSCAN GAS SAMPLING SYSTEM OPERATING MANUAL

Similar documents
MULTIFUNCTION ALARM SYSTEM TYPE ED510 FIRE LEVEL GAS ZONE 1 ZONE 2 ZONE 1 ZONE 2 SENSOR 1 SENSOR 2 ALARM FAULT TEST ON TEST OFF

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

BX444-Mc Gas Detector

Technical Manual. Level Alarm Unit CARLA & WIDS

Application, Installation, Operation & Maintenance Manual

SCAN200E USER S MANUAL

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

ADOS Biogas 905. Multi-channel Gas Analyser. A D O S GmbH Instrumentation and Control Trierer Str FRG

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

Two-Channel Gas Controller

INSTALLATION AND OPERATING INSTRUCTIONS

Model D12-IR. Digital Gas Transmitter...

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

GS100M Gas Detector. Technical Specification

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

GS100M Gas Detection Controller

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Fill Point, Level Gauges, and Control Range

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Installation, Operating and Maintenance Manual

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

GAS DETECTION International Gas Detectors CH4 NO

USER MANUAL FOR OPERATING SYSTEM

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Carbon Monoxide Transmitter

SIL 2. Ultima X Series Gas Monitors CERTIFIED

Door Release Power Supply

Warranty Registration

Ax60+ Multi-Gas. Service Manual

Superdew 3. Hygrometer. Operating Instructions

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Danfoss gas detection units

Warranty Registration

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

TXgard-Plus. Flameproof Toxic and Oxygen Gas Detector with Non-intrusive One-man Calibration. Installation, Operation and Maintenance Instructions

Flostop TS D7E and A8E. Operation Manual

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Flopurge TS. Operation Manual

10yr O2NE & Safe-Ox. User Manual

Commercial and Light Industrial Fire Alarm Control Panel

Air Check Ex O 2 Deficiency Monitor

Intelligent Security & Fire Ltd

APPLICATION DATA SHEET

SIMRAD GD10 IR GAS DETECTOR

Instruction Manual. B Issue B. next Pump Accessories

RTD TEMPERATURE SENSING SYSTEM

Analog Room Pressure Monitor RPC Series

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

IJ3000 IJ3000 Flushing System N Revision B Installation Instructions Page 1 of 10

IMR 5000 Operating Manual S/N: SAMPLE For information only! IMR Environmental Equipment Inc.

APPLICATION DATA SHEET

Contents. Outline of Product. Features of Product. Specifications of Product. Name and central function of section. Illustration of Terminal

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Duct and Rough Service Carbon Monoxide Sensor

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

P2267 NETWORK INTERFACE

Operating Instructions

Danfoss gas detection units

On the job around the clock 24/7: Fire detection systems

Sieger Apex. Flexibility that meets your requirements

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Zareba Metro Gas Detector

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

14300 MAINS SEPARATOR ALARM MANUAL

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

Operation and Maintenance Manual

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

Environmental Monitoring & Control Units Types MCU 3 & 4 Installation and Hardware

ACCURATE ELECTRONICS INC

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

The EN54 Part 2 & 4 Fire System

SMART Gas Detector/Transmitter(4~20mA) with built-in LCD & explosion proof DA-500

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

IGD. O p e r a t i o n a n d M a i n t e n a n c e V International Gas Detectors. Triton House Crosby Street Stockport SK2 6SH England

ZXSe Range Data Sheet

IMR IX176 Portable Gas Detector User Manual

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

DC200 Digital Dispenser Operating Manual

Heatless Desiccant Compressed Air Dryers

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

Recalibrate the way you look at gas detection

Operation & Maintenance Manual

Transcription:

TQ4400 TANKSCAN GAS SAMPLING SYSTEM OPERATING MANUAL TQ Environmental Plc July 2009 This manual must not be copied or reproduced in part without the express written permission of TQ Environmental PLC. All information contained herein is subject to modification. TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP 44 (0) 1924 380700; FAX 44 (0) 1924 361700. E-mail : Sales@TQPLC.com Web Site : www.tqplc.com TQ ENVIRONMENTAL PLC BS EN ISO 9001 Date of Issue: 1 st September 2002 Author: S Burgess Filename: 4826/4826T5 Page 1 of 25

CONTENTS 1.0 INTRODUCTION 3 2.0 SYSTEM DESCRIPTION 5 2.1 Pneumatics: 5 2.2 Sensors 10 2.3 Control and Display Electronics. 10 2.4 Power Supply Change Over Unit 14 2.5 Watchdog 14 2.6 Outputs. 15 2.7 Technical Specification 15 3.0 OPERATION 16 3.1 System Start-up 16 3.2 Normal Operation 16 3.3 Panel Controls 17 3.4 Alarm Conditions 19 3.5 Time and Date 21 4.0 INSTALLATION 22 ( instalation notes are not included in this version) 5.0 COMMISSIONING 22 ( commissioning notes are not included in this version) 6.0 SCHEDULED MAINTENANCE 23 6.1 System Confidence Test Sequential Sampling Part 23 6.2 Filter Check 23 6.3 System Calibration (All Sensors) 24 6.4 Pump Service 24 6.5 Inspecting and Cleaning Snorkel Valves 24 6.6 Testing and Calibrating the TQ126F 25 Set up and Technician sub menus are not included in this version of the TQ 4400 operating manual. For all instructional on changing system parameters, further calibration instructions etc. Please request the following document from TQ Environmental sales office. TQ 4400 Gas Detection System Set Up Manual Document Ref: 4826CR2 Filename: 4826/4826T5 Page 2 of 25

1.0 INTRODUCTION The TQ4400 Tankscan is a multipoint, sequential, aspirated, gas sampling system. The System is designed to meet with IMO / Solas requirements, and comply with classification rules for monitoring Void Spaces on board Gas Carriers and Oil & Gas Tankers, in areas adjacent to the cargo areas. E.g. ballast tanks, pump rooms, cofferdams, pipe tunnels and duct keels. Refer to Fig 1 on page 4 for a typical system schematic. The TQ4400 Tankscan extracts a gas sample from a desired location, via transport lines to an analysing unit where the sample is monitored for Flammable, Toxic or Oxygen gases. This is a cost effective method of gas detection, as only one sensor is required per gas detected. The number of locations for a TQ4400 is dependant on the number of gases being detected. From 1 to 4 sensors and up to 48 locations. Typical explosive and toxic gas sensors, which can be installed within the TQ4400, can be seen in table 2, (other gases are available on request.) Explosive Methane 0-100% LEL Butane 0-100% LEL Methane 0-100% VOL Butane 0-100% VOL Toxic H 2 S Various ranges CO Various ranges CO 2 Various ranges Oxygen 0-25% VOL Table 2 The TQ4400 is capable of providing individual low and high alarm outputs for each sample location and corresponding individual alarm relays. These relays can be utilised when an application requires locations to be grouped into zones. This can provide an interface with alarm management systems, remote mimic panels, and audible / visual warning devices. With the ability to monitor for the gases indicated above, the system can be configured to allow a Pump Room Gas Monitoring System to be integrated into the TQ4400, thus eliminating the need for two separate systems. The TQ4400 Display Unit can be mounted within the cabinet or in a remote location, if for instance the analysing unit is installed in an un-manned area. The operator interface is via four push buttons and a backlit LCD. During normal operation the LCD display will provide the location, gas type and sample concentration for each individual location. N.B. A separate SET UP Manual for changing sample line No s., gas range and alarm levels is included. These are factory set to the customer s requirements, but can be altered on commissioning. Filename: 4826/4826T5 Page 3 of 25

WBT 1 PORT Cleaning F.W.T PORT Cleaning F.W.T STB WBT 1 STB SAMPLE LINE #16 SAMPLE LINE #17 SAMPLE LINE #18 SAMPLE LINE #19 SAMPLE LINE #20 SYSTEM FAULT N/C CONTACTS LOW ALARM N/O CONTACTS HIGH ALARM N/O CONTACT VENT DRAIN SAFE AREA System Schematic DISPLAY UNIT TQ4400 CONTROL UNIT CCR DIAGRAM SYSMBOLS KEY FLAME ARRESTOR AIR SUPPLY 10 Bar MAX MANUAL SHUT OFF VALVE END OF LINE FILTER/SNORKEL VALVE PENETRATION CLASSIFICATION ST'D WBT 5 PORT WBT 4 PORT WBT 3 PORT WBT 2 PORT HYDRAULIC ROOM SHIPS AIR SUPPLY ANALYSING UNIT POWER SUPPLY CHANG-OVER UNIT GAS DETECTOR 220V AC 60HZ 10A MAIN 220V AC 60HZ 10A STANDBY DETAIL 'A' BULKHEAD BULKHEAD Pipe Trunk Drain Drain Tank WBT 4 CENTRE WBT 3 CENTRE WBT 5 STB WBT 4 STB WBT 3 STB WBT 2 STB B.E Trunk Port B.E Trunk STB SAMPLE LINE #1 SAMPLE LINE #2 SAMPLE LINE #3 SAMPLE LINE #4 SAMPLE LINE #5 SAMPLE LINE #6 SAMPLE LINE #7 SAMPLE LINE #8 SAMPLE LINE #9 SAMPLE LINE #10 SAMPLE LINE #11 SAMPLE LINE #12 SAMPLE LINE #13 SAMPLE LINE #14 SAMPLE LINE #15 Lower Stool Aft Lower Stool Fwd Bulkhead Bulkhead Ships Air Supply Sample Lines Penetrate into Main Control Unit in Cargo Control Room (See Detail 'A') Vent Safe Area Fig 1 Typical 20 Point TQ4400 Tankscan System Filename: 4826/4826T5 Page 4 of 25

2.0 SYSTEM DESCRIPTION TQ Environmental Plc The TQ4400 Tankscan standard Analysing Unit is housed in a wall-mounted enclosure complete with front panel Display Unit. The enclosure contains all electrical, electronic and pneumatic equipment required to monitor, display, control and provide alarm outputs for the relevant locations. Refer to Fig 2, page 9 for a typical system schematic. The TQ4400 system is divided into following main components: Pneumatics Sensors Control & Display Unit Power Supply Change Over Unit Sample Line Accessories Outputs Technical Specification 2.1 Pneumatics: Please refer to Fig 2, 3, 4 and 5, pages 8, 9, 11 and 12 respectively. Every Sample Line from the relevant Location is firstly connected to its respective external Shut-off Valve to provide sample line isolation. The sample then passes through a flame arrestor mounted externally on either side of the cabinet, and into the Analyser Unit. The typical Analysing Unit contains the following Pneumatic devices: Solenoid Valves Catch pot - water trap Particulate Filter Double Ended Pump Coalescing Filter Flow Meter Reverse Purge Leak Detection 2.1.1 The Solenoid Valves are mounted in blocks of eight onto a common manifold. The manifolds are fitted in pairs to a gland plate, which allows direct external connection to the input port of each valve. Fitted onto each pair of manifolds is a Solenoid Driver Board. This board receives data from the BTC board to operate the solenoid valves. Each valve is complete with a 24V dc coil, and connection to each coil is via 3 pole connector containing an LED and snubbing diode. Filename: 4826/4826T5 Page 5 of 25

2.1.2 The Catch pot is fitted with a poly-carbonate bowl allowing visual inspection of the water levels. In the event of the bowl becoming full a float assembly will block the outlet, firstly to prevent water entering the system and secondly to create a Flow Fail Alarm. To empty the bowl, firstly stop the pump and open the drain valve at the bottom of the bowl. When empty Ensure that the drain valve is fully closed prior to re-energising the pump. 2.1.3 The Particulate Filter is fitted with a micro-fibre filter element, which cannot be cleaned and therefore must be replaced when discoloured or is suspected of reducing air flow. This unit is also fitted with a polycarbonate bowl to allow visual inspection of the filter element. Spare filter elements can be supplied, refer to Section 7 for Part numbers. 2.1.4 The Pump is an Industrial Double Ended type with the two pumps connected in series to ensure adequate flow rates for the larger installations. As an example on transport tube dimensions of 4.0mm I/D, flow rates in excess of 4 litres/min. are achievable for sample line lengths up to 300 metres. Based on these figures, sample times for a 300 metre sample line will be in the order of 1 minute, providing sharp bends and fittings are kept to a minimum. A Pump Service Kit can be supplied, refer to Section 7 for Part numbers. 2.1.5 The Coalescing Filter is of nylon construction and, as with the Particulate filter, incorporates a clear bowl for visual inspection of the filter and moisture level. Here again the element must be replaced when discoloured. The drain outlet is fitted with a needle valve, which is opened sufficiently to allow a small airflow through the Coalescing Filter all the time the pump is running. This should drain any moisture that has collected in the Filter bowl. Spare filter elements can be supplied, refer to Section 7 for Part numbers. 2.1.6 The Flow Meter is fitted in the sample flow line to indicate airflow to the sensors and works in conjunction with the Sample by-pass needle valve. The steel float, sensing ring and control relay, are all part of the flow fail device. If the float passes down through the sensor a Low Flow signal is sent to its control relay. When flow returns the float will raise back through the sensor and the signal to its control relay will revert to normal. 2.1.7 Reverse Purge: The system allows compressed air to be periodically blown down each sample line in order to keep the lines free of debris/moisture etc. This "Reverse Purge" can be initiated individually on each sample line as required, globally on each sample line when required, or globally on each sample line automatically. Filename: 4826/4826T5 Page 6 of 25

The compressed air, between 6 to 10 bar, is brought into the system through its own input port, and through a manual drain coalescing filter and pressure regulator. 2.1.8 A Leak Detection System is incorporated within the TQ4400 Analyser enclosure and monitors for any accumulation of flammable gases within the enclosure. This system utilises a catalytic flammable gas detector fitted in the top of the enclosure, which is connected to a TQ126F controller fitted in the Power Supply Change-over Unit, refer to section 2.4. If the gas concentration within the enclosure exceeds 30% LEL the Power Supply Change-over Unit will disconnect the supply to the TQ4400 Analysing Unit. The power supply cannot be re-connected until the gas concentration has fallen below the alarm level and a manual reset at the Power Supply Change-over Unit has been carried out. 2.1.9 Sample Line Equipment is available in several forms to suit the sample location. End of Line filters for Dry areas, Snorkel Valves for wet areas, In-line filter (where an End of line filter is not practical) There are two types of End of Line Filters. A fibre element type where the filter element has to be replaced periodically. A stainless steel type where the filter element can be cleaned. Both of the above filters are supplied with dual compression fittings to suit pipe sizes 6 or 8mm O/D, in either brass or stainless steel. It is advisable to protect the Filter when installed in a location where damage may occur. The Snorkel Valve is of a nylon cylindrical construction with an internal float that will block the sample line when immersed in water. This device is supplied with a stainless steel dual ferrule compression fitting to suit pipe sizes 6 or 8mm O/D. The In-Line Filter is a stainless steel unit that is suitable for attaching to a stop-valve when fitted in a stop valve box. It is advisable to remove the In- Line Filter complete for cleaning, as splitting the filter in situ may damage the threads. Refer to the Installation section 4.5 for Filter Drawings. Filename: 4826/4826T5 Page 7 of 25

HAZARDOUS AREA SAFE AREA Brass Compression Fittings For Connection Penetrations x N Sample Lines Connect Directly on to Flame Arrestors Via Brass Compression Fittings 1/4"BSPP St-St Shut off valves x N (Supplied as Loose Items) See Note 4 Sample Lines x N Flame Arrestors x N 8mm Vent Line (See Note 2) Vent Flame Arrestors (Connection Via 8mm Brass Compression Fitting) 8mm Brass Compression Fittings For Connection of Ships Air Supply Drain Fitting (8mm Compression) 8mm Drain Line (See Note 7) Test Point Analysing Unit TQ4400 Ballast Tank & Water Ballast Pump Trunk/Upper Stool Gas Sampling System TQ4400 CONTROL UNIT ALARM ALARM SYSTEM HEALTHY WATCHDOG UP DOWN SELECT MENU Cabinet Gas Internal Leak Detector Cables Enter Through Bottom Right of Cabinet NOTES 1) N= Number of sample points 2) Vent line is to be let to atmosphere with the outlet arranged in a safe location away from ignition sources. The end of the vent line must be bent downwards to prevent water ingress. 3) All Sample Line connections are Via left hand side of cabinet or right on request 4) Shut off valves and penetrations can be supplied as an optional extras. 5) Free Standing Cabinet Availible Upon Request. 6) Display Unit Can Be Installed In A Remote Location. 7) Drain Line to be led to atmosphere with the outlet arranged in a safe location away from ignition sources. The drain line should have a steady fall from the exit point of the cabinet to the outlet to allow self draining of condensate. FIXING DETAIL REAR VIEW OF FIXING BRACKET 15 20 29 20 SIDE VIEW OF FIXING BRACKET 10 54 1 2 Fig 2 Typical System Schematic for a TQ4400 Tankscan Filename: 4826/4826T5 Page 8 of 25

AIR IN (Min 6 Bar Max 10 Bar) (See Note 2) 17 Vent 2A Stream 1 17 1,1 2,1 Stream n 17 1,n 2,n NOTES 1) All process connections Brass 2) Air supply to be from dry filtered instrument air supply. Flame Arrestor Mounted On Outside Of Cabinet 3,1 C NO NC 3,n C NO NC 12 PNEUMATIC/INSTRUMENT SCHEMATIC DIAGRAM Pump Pump 5A 5B 4 16 9 13 NO 10 NC C Gas Detector Hydrocarbon Monitor 11B 6 7 Test Gas All system components are housed in a single enclosure. 15 NO 14 NC Drain C 1A 3) n = No. of sample lines Gas Detector 11A 8A BTC BOARD 8B Flow Fail Signal Link To Display Unit Fig 3 Typical Pneumatic Schematic for TQ4400 Tankscan -Please see separate Spare Parts List in Drawings section for Component identification an relevant part numbers. Filename: 4826/4826T5 Page 9 of 25

2.2 Sensors There are two type of sensors, the infrared type, for flammable gases, or the electro-chemical type for Toxic and Oxygen gases. When a system comprises of more than one sensor, they are connected in series in the sample line which then is vented out from the enclosure through a flame arrestor. 2.2.1 Infrared (GD 129NI) Flammable Gas Sensor. The operation of the infrared sensor within the TQ4400 Tankscan system has been developed from the infrared heat source detector utilised in the thermal imaging cameras measuring infrared radiation. These detectors have now developed into non-dispersive infrared analysers, for accurate Flammable gas detection. Please see the separate GD 129 Manual for more information and maintenance requirements. 2.2.2 Electro-chemical Type. These sensors typically monitor for Oxygen and Toxic Gases and because of their properties have a life span of approximately 2 years. These Electrochemical type, as with the Infrared sensor, provide a 4-20mA signal for their respective gas concentrations. 2.3 Control and Display Electronics. The TQ4400 Tankscan Analysing Unit is controlled by the micro-processor based Ballast Tank Controller (BTC) board. The BTC board accepts hard wired inputs from the gas detectors, flow fail relay and communicates the system status to the Display Unit via a RS 485 serial link. System status consists of gas concentrations, system fault and alarm status, and current sample locations. The Display Unit analyses the information and transmits back to the controller BTC board any system operations required, to operate gas concentration alarm relays, sample-line or reverse purge solenoid valves. Filename: 4826/4826T5 Page 10 of 25

System Electronics Hard wired signals Controller BTC Board RS485 Display BTC Board RS485 Display Unit Solenoid Driver Board Hard Wired Signals RS485 Watchdog Relay Board Fig. 6 Block diagram of Communications within TQ4400 Both the Control PCB and the Display PCB are constantly monitored by an individual watchdog unit. This alarms if the any or both of the processors on the relevant Board fail. 2.3.1 The Display Unit Refer to Fig 7, Page 15 The Display Unit houses the display BTC board and the display/operator interface controls. The display BTC board accepts details of the system status from the controller BTC board, analyses the information, displays the current system status and sends control commands back to the main BTC unit. During normal operation the Display Unit will show the current sample location, gas type, gas concentration and fault alarm status, and generate alarm outputs by communicating with the BTC board. Refer to section 3.3 for display operation. The Front Panel Display includes: Liquid Crystal Display. 4 * Push buttons (Ack, Reset, Hold and Skip function). 4 * LED s (Low Alarm, High Alarm, System Healthy and Watchdog Alarm) Filename: 4826/4826T5 Page 11 of 25

This Display Unit can be installed in either the front door of the TQ4400 Analysing Unit, or, remotely as a wall mounted or console mounted unit. The unit is supplied with plug and socket connections for ease of installation and maintenance. TQ ENVIRONMENTAL PLC TQ4400 GAS DETECTION SYSTEM 218 ALARM 1 ALARM 2 SYSTEM HEALTHY WATCHDOG ACK RESET HOLD SKIP 189 Fig 7 Front Display of TQ4400 Tankscan Filename: 4826/4826T5 Page 12 of 25

4 Holes x 10.0mm TQ Environmental Plc 570 580 Right Hand Opening Door NOTES: 1) Protection Rating of cabinent is IP65 380 322 410 380 POWER SUPPLY CHANGE-OVER UNIT FOR TANKSCAN GAS SAMPLING SYSTEM MAIN SUPPLY STANDBY SUPPLY GAS ALARM RESET TQ ENVIRONMENTAL PLC Flanshaw Way, Wakefield, W Yorks England, WF2 9LP Tel: + 44 1924 380700 Fax: + 44 1924 361700 Email: sales@tqplc.com website :http:// www.tqplc.com 10 8.3 Fig 8 Power Supply Change-over Unit Filename: 4826/4826T5 Page 13 of 25

2.4 Power Supply Change Over Unit Refer to Fig 8 Page 13. This Unit is connected to the Ship s Main and Emergency Power Supplies, to provide an automatic changeover for the supply to the Analyser Unit in the event of a Mains Supply failure. The unit will accept 110-240V a.c, 50-60 Hz inputs, and will automatically change back to Main when the main supply is restored. Incorporated within the Power Supply Change-Over Unit is a TQ126F controller, which monitors the TQ4400 Analysing Unit s Leak Detection gas detector. The TQ126F will disconnect the power supply to the Analyser Unit if the sensor detects a gas concentration of 30% LEL. The power supply to the Analyser Unit will not be restored until the gas concentration has fallen below 30% LEL and the reset button on the front of the Power Supply Change-Over Unit has been pressed. Front Panel indications are provided for: Mains Supply On Emergency Supply On Internal Gas Alarm 2.5 Watchdog This unit is mounted on the rear of the enclosure front door to monitor the main processors in the control board and the display board. In the event of either of these processors failing the LED and an audible buzzer will activate. WATCHDOG ALARM UNIT ALARM MUTE The audible buzzer can be extinguished using the mute button on the unit, but to reset the fault the system has to be restarted by powering down from either the fused isolator in the bottom right hand side of the cabinet or from the power supply changeover unit. Filename: 4826/4826T5 Page 14 of 25

2.6 Outputs. The TQ4400 standard outputs are in the form of: Two sets of Volt Free relay change-over contacts one for High and one for Low Alarms for each sensor One set of Volt Free Change-over relay contacts for System Fault Alarm. One set of Volt Free Change-over relay contacts for Mains Supply Fail One set of Volt Free Change-over relay contacts for Common Concentration Alarm The Common Alarm relays can be configured to provide a 24V dc output for each alarm level to drive audible/visual warning devices or remote indicators. Relays can also be configured to provide outputs for individual location gas alarms. These additional relay outputs must be specified prior to order placement. Other serial communication techniques such as RS 485 Modbus Protocol will be available shortly. For further information please contact TQ Environmental Plc. 2.7 Technical Specification Power 110/240V 50/60Hz @ 4 Amps non inductive Internal d.c power supplies 1 x 5V DC (System Electronics) 1 x 24V DC (Sensors / Solenoids) (factory fitted dependent on sensor ratings and overall system requirement) Max no. of locations for sequential 48 Locations for 1-3 Sensors monitoring per Max no. of Sensor 36 Locations for 4 Sensors Sensor types 4-20mA current sources (2 or 3 wire) Pump Capacity 36 Litres / Minute (open ended) Gas Concentration Alarm Outputs Standard: - 2 x Common Low / Common High Volt Free Contacts, @ 5Amps. Resistive. Custom: - Up to 1 Individual Volt Free Contact per Sample Location Gas Alarm, 5A Sample Lines Seamless Stainless Steel 316. (Preferred) OD 6mm - 8mm, ID 4mm - 6mm. Max length 300Metre @ 4.0mm I/D Fault Alarm Outputs 1 x Mains Fail Volt Free Contact 1 x System Fault Volt Free Contact 1 x Common Alarm Volt Free Contact Data communications RS 485 MODBUS on request Operational temperature and humidity 0 o C-40 o C 0-90%RH non-condensing. Filename: 4826/4826T5 Page 15 of 25

3.0 OPERATION This section explains in detail the TQ4400 system operation and typical alarm conditions. Four front panel push buttons are used for operator interface namely: SKIP, HOLD, ACK, and RESET. 3.1 System Start-up When power is applied to the system, the display will indicate System Set-up mode, as below SYSTEM SETUP PLEASE WAIT The system will stay in this mode for approximately 150 seconds. 3.2 Normal Operation After the start-up delay the system will enter the normal operating mode. CHAN 1 METHANE 00015%LEL WARNING: On Power Up the Infrared Sensor takes up to two minutes to reach operating temperature, and will initiate a Sensor Fault. This can be cleared after the warm up period by pressing the RESET button. Ensure the System Healthy LED is illuminated after pressing the RESET button. The top line of the display shows the channel location and the bottom line of the display will show the gas sensor name, concentration of the gas, and the units of the gas being analysed. The system will sequentially sample all of the channel locations, displaying the appropriate data on the LCD. Filename: 4826/4826T5 Page 16 of 25

3.3 Panel Controls At any time during the normal operating mode, the user has the option to GOTO, Hold or Skip a channel. These functions are invoked by pressing down the relevant push button, and are discussed further below: 3.3.1 GOTO Channel The user may press down and hold the RESET and HOLD button until the display reads GOTO, the user must then release the RESET and HOLD button. You can then select which sample location to GOTO by using ACK to go up and RESET to go down through the sample locations. Pressing Hold selects the desired channel. Once the unit is sampling from the desired location you can then either HOLD, SKIP or Reverse Purge the location. 3.3.2 Hold Channel The user may press down and hold the HOLD button until the display reads HOLD CHANNEL, the user must then release the HOLD button. CHAN 1 HOLD CHANNEL This will invoke the Hold Channel function. The current Channel location will be continuously sampled for a maximum period of 20 minutes after which time the system will revert to sequential sampling. At any time the user may release the channel and enable the system to revert back to sequential sampling. This is achieved by pressing down and holding the HOLD button until the display reads RELEASE CHANNEL, the user must then release the HOLD button. CHAN 1 RELEASE CHANNEL Filename: 4826/4826T5 Page 17 of 25

3.3.3 Skip Channel The user may press down and hold the SKIP button until the display reads SKIP MODE, the user must then release the SKIP button. CHAN 1 SKIP MODE This will invoke the Skip Channel function. The current channel location will be skipped when the system is sequentially sampling the channel locations. When the system returns to the skipped channel, the LCD will display SKIP MODE for 5 seconds and then proceed to the next sequential channel. When the LCD displays SKIP MODE the user may revoke the skip command by pressing down and holding the SKIP button until the display reads NORMAL MODE, the user must then release the SKIP button. CHAN 1 NORMAL MODE 3.3.4 Manual Global Reverse Purge. The user may press down and hold the ACK and RESET buttons until the display reads GLOBAL REVERSE PURGE followed by REVERSE PURGE. This initiates a global reverse purge where air is blown down every sample line for a set period of time. The purge duration is factory set and a Button box is required to be interfaced to the controller BTC board to change the value. After the system has finished purging it will revert back to sampling. 3.3.5 Manual Individual Reverse Purge. In order to reverse purge an individual sample location you initially have to GOTO the desired location, refer to section 3.3.1. Once the system is sampling from the required location you can then purge the sample line by pressing and holding the ACK and HOLD button until Filename: 4826/4826T5 Page 18 of 25

the display reads REVERSE PURGE. This will purge the line for the set duration, once completed revert back to sampling. 3.3.6 Automatic Global Reverse Purge. This is a reverse purge, for all sample points, which automatically initiates after a set number of complete cycles of sample points. We recommend this function to be enabled for an analyser unit which draws samples from points where water can be found, such as ballast tanks. The purge frequency is factory set and can only be altered using a button box being interfaced with the controller BTC board. The box can be obtained by contacting TQ. 3.4 Alarm Conditions 3.4.1 Fault Conditions There are three possible fault conditions: Sensor Fault, Flow Fail and Comms Failure. The sensor will be in fault if the output of the sensor falls below a set value. When this occurs the LCD will display SENSOR FAULT, the System Healthy LED will extinguish and the Fault relay will be activated. SENSOR FAULT The Flow Fail will occur if the pressure through the system drops to a set value. When this occurs the LCD will display FLOW FAIL, the System Healthy led will extinguish and the Fault relay will be activated. FLOW FAIL To clear the Fault condition press and hold the RESET button until the display reads RESET ALARM. At the same time, the System Healthy led will illuminate and the Fault relay will be de-activated. Filename: 4826/4826T5 Page 19 of 25

RESET ALARMS A Comms Failure will initiate when communications are interrupted for more than 2 minutes between the Display BTC PCB and the Control BTC PCB. COMMS FAILURE This cannot be reset by the RESET button; the panel has to be opened and powered down and back up again. However it is preferred to do this from the power supply changeover unit. 3.4.2 Concentration Alarms There are two alarms on the system, a low level alarm, ALARM 1, and a high level alarm, ALARM 2. When the gas concentration exceeds the set levels, the appropriate alarms will be activated, and operate the appropriate LED s and alarm relays. The LCD will display the first channel to be in alarm, together with the sensor gas type and relevant alarm condition. The system will continue to sample the channels sequentially. CHAN 1 METHANE LOW ALARM CHAN 1 SYSTEM HEALTHY METHANE HI ALARM Filename: 4826/4826T5 Page 20 of 25

The user may reset the alarmed channel by pressing the RESET button. At which point the alarms for that channel will be cleared. If there are any pending alarms then the LCD will display the next alarmed channel information. The user must again press the RESET button to clear that particular alarm. When no more alarms are present, the system will display the concentration as normal. The user may press the Ack button to clear the audible buzzer. This will acknowledge the alarmed channel and display ALARM ACKNOWLEDGED on the LCD. CHAN 1 ACKNOWLEDGED ALARM If there is a pending alarm the LCD will display the pending alarm information. When all alarmed channels have been acknowledged, the system will display the gas concentration sequentially, but will also display ALARM ACKNOWLEDGED on the LCD for 5 seconds. To de-activate the alarm relays the user must use the RESET function as described above. RESET ALARMS Each alarm is then reset on a channel per channel basis, i.e. if a particular channel is in alarm then another channel comes into alarm, then the first channel requires one reset and a second reset clears the next set of alarms in the second channel. 3.5 Time and Date. If a printer is included at time of supply, to record concentration values. The time and date can be set using the 4 x push button function keys on the front panel. The instructions are included on an additional functions plaque, mounted adjacent to the display. If no printer is included with the equipment, the time and date functions are disabled as there is no means of displaying the information. Filename: 4826/4826T5 Page 21 of 25

4.0 INSTALLATION Installation guidance is not included in this web version of the operation manual. Please contact TQ environmental for the complete Operating manual if installation notes are required. 5.0 COMMISSIONING Commissioning guidance is not included in this web version of the operation manual. Please contact TQ environmental for the complete Operating manual if Commissioning notes are required. Filename: 4826/4826T5 Page 22 of 25

6.0 SCHEDULED MAINTENANCE 6.1 System Confidence Test Sequential Sampling Part Frequency: 6 Months Equipment Needed: Calibration Gas suitable for the sequential sensors i.e. it is recommended that gas of 50% LEL (or similar) is used when a 0-100% LEL sensor is installed. Ensure that the concentration of gas used is greater than that of the highest alarm set point. Description: When sample locations are grouped into zones, and different zones activate different alarms, ensure that all zone alarm configurations are known so that alarms can be checked. Activate a flow fail alarm, this can be achieved by blocking the current sample line through the ball stop valve. Once the alarm is activated, acknowledge the alarm, refer to section 3.4. Connect the test gas to the calibration point within the analysing unit but do not turn the gas on. Ensure that the 3-Way valve is set on the calibration position and turn the gas on at a rate of 1 litre / minute. The system will now generate a gas alarm on the current sample location. Ensure all relevant alarms are activated, for example any external beacons and alarms on the Vessels alarm management system. Ensure also that the display reads the same concentration as that of the calibration gas used, i.e. 50% LEL if 50% LEL calibration gas is used. It must be noted however that all calibration gases have a tolerance that must be taken in to account. Repeat for all locations that activate different alarms. 6.2 Filter Check Frequency: Equipment Needed: 6 Months / when required Replacement Filter Elements Description: Check that all Coalescing; Particulate; End of Line; In- Line and Snorkel Valves are in good condition and clean/ replace if necessary. Filename: 4826/4826T5 Page 23 of 25

6.3 System Calibration (All Sensors) Frequency: Equipment Needed: 12 months Calibration Gas suitable for the sensors being calibrated i.e.: use 50% LEL gas (or similar) for a 0-100% LEL sensor. Description: Refer to section 6.1 for applying test gas. Repeat for all Sensors. Note, if the calibration for any of the sensors requires altering, a button box and instructions is required from TQ. 6.4 Pump Service Frequency: Equipment Needed: Description: 24 months Pump Service Kit Replace the pump diaphragms and valve springs. 6.5 Inspecting and Cleaning Snorkel Valves Frequency: Equipment Needed: Whenever Ballast Tanks are inspected High Pressure Water Supply Description: a) Power down the TQ4400 gas detection equipment. Visually inspect end of line snorkel valves for dirt and silt build up. Hose down and clean the valve as necessary. b) Inspect Snorkel Valve for any physical damage, repair or replace as necessary. Isolate the line as follows. Inhibit a sample line as per Section 3.3.3 and replace as soon as possible with Part No. 302-001. After Replacement re-instate that line as per Section 3.3.3. c) Allow to dry and power up the TQ4400 unit. Filename: 4826/4826T5 Page 24 of 25

6.6 Testing and Calibrating the TQ126F Frequency: Equipment Needed: 12 months Zero and Span Calibration Gas suitable for the sensor used. Span: 50% LEL or similar Zero: Synthetic Air 0% LEL Description: Please refer to section 2.1.3 for an introduction to the TQ126F, and the drawing showing the TQ 126F PCB Layout, Fig 14. Ensure the correct voltage is across the gas sensor by measuring the voltage across terminals 1 and 3 of the PEL terminal connector, next to VR2, within the sensor s junction box. Adjust VR1 so the voltage is 2.00V d.c, +/- 0.1v. Apply Zero gas to the sensor using a suitable gassing cap at a rate of 1 litre/minute, adjust VR2 so that the TQ126F display reads 0.00 %. Apply Span gas to the sensor using the suitable gassing cap at a rate of 1 litre/minute; adjust VRoVM so that the TQ 126F display reads the same value as the span gas, i.e. 50.00 %. While applying gas to the sensor and ensure that the power to the Analysing Unit is cut at 30 % LEL. VR 2 VR 1 RL 1 VRDVM VR 3 VR20MA S/W 1 VR4MA Fig.14 RBP 126F PCB Layout Drawing Filename: 4826/4826T5 Page 25 of 25