SECTION INTERIOR LIGHTING

Similar documents
SECTION INTERIOR LIGHTING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL

E. Luminaire: Complete lighting fixture, including ballast housing if provided.

SECTION INTERIOR LIGHTING

2. Lighting fixtures mounted on exterior building surfaces.

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices:

SECTION INTERIOR LIGHTING

SECTION LIGHTING CONTROL DEVICES

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

LIGHTING CONTROL DEVICES

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

SECTION LIGHTING

SECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES

Catalog Number. Notes. Type. FST Snap on frosted, diffuse L/LENS No diffuser

Catalog Number. Notes

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

B. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.

WINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016

SETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition

CDL8 LED Architectural

S R 8 Circular LED Engine Product Specification

LHB LED High Bay. Technical Specifications. Description. Performance Data. Dimensions & Weights. Delivered Lumens Efficacy.

THE HIGH STRIP FIXTURE SERIES PERFORMANCE KEY FEATURES INCLUDE: LED Fixture Series for General, Direct and Indirect Illumination

CLM 422 Series LED Ceiling Luminaire Module - 45Watt

SDL4 LED Strip Diffused Lens

BAS SDL8' LED Strip Diffused Lens

Dimensions (111mm) 3 (76mm) (111mm) (48mm)

Emery County Senior Center Green River 06/07

LHBXD LED Linear High Bay

THE HIGH STAIRWELL AND PASSAGEWAY FIXTURE PERFORMANCE KEY FEATURES INCLUDE:

SECTION (16510) - INTERIOR LIGHTING

Dimensions (111mm) (111mm) 3 (76mm)

Product Specifications MaxLumen MRI LED Diffused Lighting

THE HIGH STAIRWELL AND PASSAGEWAY FIXTURE PERFORMANCE KEY FEATURES INCLUDE:

Explosion Proof LED Light - Equivalent to Watt HID C1D2, UL Listed

CLARA AC Crystal CLARA AC 50. LED-modules for downlight. A qualified solution to replace and exceed Halogen solutions in Downlights.

DRD5S & SurfaceFrame Alt/EM Surface Mount LED Downlight

Energy Star Directional Luminaire Test Report ELEC-TECH INTERNATIONAL CO LTD. LED Downlight

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

BAS SFP22 Edge-lit LED Panel

SECTION AUTOMATIC TRANSFER SWITCHES

UNIFIED FACILITIES GUIDE SPECIFICATIONS

LED Linear Design Highlights

Product Specifications MaxLumen MRI LED Diffused Lighting

FPLHB - Fidelux Premier Linear Highbay

SECTION EXTERIOR LIGHTING

MN/DOT Specification Sign Lighting Luminaire With 150 or 250 Watt Metal Halide Lamps 11/05/09

Product Specifications MaxLumen MRI LED Diffused Lighting

IN2 Lighting Control Devices

Solid State Lighting Sub-Assembly Interfaces for Luminaires. Andrew D. Jackson Philips Lighting Corporate Regulatory and Certification Laboratory

LUMINAIRE ID SIZE CENTER OPTICS SIDE OPTICS LIGHT SOURCE CRI LUMEN PACKAGES COLOR TEMP. VOLTAGE. LED - high performance LED 80-80CRI 90-90CRI

MAR2 LED SERIES M A R 2 L E D. Linear LED Lighting for Hazardous Locations

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

LED RETROFIT CONVERSION KITS

PRODUCT DATA SHEET LIGHTING PRODUCTS

Rating. Class I Div II

LED retrofits! 4 T8 Specification Guide. Retrofit your existing Fluorescent Lights in Seconds No Electrician Needed! Pure Bright

Bdl60u Fluorescent Emergency Ballast

Millenium Os. Luminaire LED. For Stairwells and Public Spaces. Designed and manufactured in the USA. High Abuse Motion-Activated Lighting Product

208W Explosion Proof Low Profile LED - Emergency Backup - 27,040 Lumens - C1&2 D1&2 - ATEX /IEC

CPPG ENERGY EFFICIENT CANOPY LIGHTS FOR PARKING AREAS

OLUX LED Flood Light OSRAM. Datasheet APPLICATIONS.

DuroSite LED RTO Area Light - UL / CSA. for Indoor and Outdoor Industrial Applications #

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Safety Certification of Solid-State Lighting Products. September 23, 2009 Todd Straka Director - Lighting Services

Low Profile Clean Room 150W LED Light - 2x2 Lay-In Troffer C1D1 - C2D2 - ISO 14644/FS-209E

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

Alliance 4 - ALI4 LED 4 Linear High Bay

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

Class 1 Div 2 LED Pivoting Light - 2 foot 2 lamp - LED T series Style V Dimmable

300W Low Profile Clean Room LED Light - LED Signal Light - C1D1 - C2D2 - ISO 14644/FS-209E Rated

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

T8 Self Ballasted UL & CSA LED TUBE RETROFITS

80W C1D2 Hazardous Location Integrated LED - Corrosion Resistant for Marine - Emergency Backup

INSTALLATION INSTRUCTIONS

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

26 Watt Explosion Proof Low Profile LED Fixture - 3,380 Lumens - Class 1 & 2 Div 1 & 2 - ATEX / IECE

Fast. Precise. Versatile. UL Lighting Sciences

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

Explosion Proof C1D2 0-10V Dimmable LED Fixture - 4ft 2 Lamp - Emergency Ballast - Terminal Strips

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

150W Explosion Proof High Bay LED Light Fixture - C1D1&2 - C2D1&2-17,500 Lumens - 60 Beam

DuroSite LED High Bay - UL for Indoor and Outdoor Industrial Applications. Patent Pending

Evolution EXWW RECESSED LINEAR WALL WASH LUMINAIRE

LED RETROFIT CONVERSION KITS

Albeo LED Luminaire. Heavy Industrial Low Bay Lighting. (ALR1 - Series)

FIRE SUPPRESSION SPRINKLER SYSTEM

Applications. Standard Materials

CONTENTS AUTOMATIC TRANSFER SWITCHES

LED Reliability and Current Standards for Measurement

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK 13045

IBLED SERIES 4' PROJECT: FEATURES AND SPECIFICATIONS LINE DRAWING

SYSTEM. field cuttable. lipleds 8200 Series

DRD5S & SurfaceFrame Alt/EM 18" Linear Surface Mount LED Area Light

Transcription:

SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Exterior and Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4. Lighting fixture supports. 1.3 DEFINITIONS A. BF: Ballast factor. B. CCT: Correlated color temperature. C. CRI: Color-rendering index. D. LER: Luminaire efficacy rating. E. LED: Light Emitting Diode F. Lumen: Measured output of lamp and luminaire, or both. G. Luminaire: Complete lighting fixture, including ballast housing if provided. 1.4 SUBMITTALS A. Product Data: For each type of lighting fixture, arranged in order of fixture designation. Include data on features, accessories, finishes, and the following: 1. Physical description of lighting fixture including dimensions, emergency battery and charger. B. Installation instructions. 1.5 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Comply with NFPA 70. 13-032 26 51 00-1

1.6 COORDINATION A. Coordinate layout and installation of lighting fixtures and suspension system with other construction that penetrates ceilings or is supported by them, including HVAC equipment, firesuppression system, and partition assemblies. 1.7 WARRANTY A. Warranty for lighting fixtures: Manufacturer's standard form in which manufacturer of fixture agrees to repair or replace components that fail in materials or workmanship within specified warranty period. 1. Warranty Period for fixtures: One year from date of Substantial Completion. 2. Warranty Period for Emergency Fluorescent Ballast and Batteries: Five years from date of Substantial Completion. Full warranty shall apply for first year, and prorated warranty for the remaining four years. 3. Warranty Period for LED Fixtures: Five years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Products: Subject to compliance with requirements, provide products by one of the following: 1. As shown on drawing. B. Lighting fixtures are scheduled on the drawings 2.2 GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS A. LED Fixtures: Comply IESNA LM-79 and IESNA LM-80. B. Metal Parts: Free of burrs and sharp corners and edges. C. Sheet Metal Components: Steel unless otherwise indicated. Form and support to prevent warping and sagging. D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under operating conditions, and designed to permit relamping without use of tools. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position. E. Diffusers and Globes: 1. Acrylic Lighting Diffusers: 100 percent virgin acrylic plastic. High resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation. a. Lens Thickness: At least 0.125 inch minimum unless otherwise indicated. b. UV stabilized. 26 51 00-2 13-032

F. Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and ballasts. Labels shall be located where they will be readily visible to service personnel, but not seen from normal viewing angles when lamps are in place. 2.3 EXIT SIGNS A. General Requirements for Exit Signs: Comply with UL 924; for sign colors, visibility, luminance, and lettering size, comply with authorities having jurisdiction. B. Internally Lighted Signs: 1. Lamps for AC Operation: LEDs, 50,000 hours minimum rated lamp life. 2. Self-Powered Exit Signs (Battery Type): Integral automatic charger in a self-contained power pack. a. Battery: Sealed, maintenance-free, nickel-cadmium type. b. Charger: Fully automatic, solid-state type with sealed transfer relay. c. Operation: Relay automatically energizes lamp from battery when circuit voltage drops to 80 percent of nominal voltage or below. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. d. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. e. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. 2.4 EMERGENCY LIGHTING UNITS A. General Requirements for Emergency Lighting Units: Self-contained units complying with UL 924. 1. Battery: Sealed, maintenance-free, lead-acid type. 2. Charger: Fully automatic, solid-state type with sealed transfer relay. 3. Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. 4. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. 5. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. 2.5 LED LUMINAIRES A. General: Except as otherwise indicated, provide LED luminaries, of types and sizes indicated on fixture schedules. B. Material and specifications for each luminaire are as follows: 1. Each luminaire shall consist of an assembly that utilizes LEDs as the light source. In addition, a complete luminaire shall consist of a housing, LED array, and electronic driver (power supply). 13-032 26 51 00-3

2. Each luminaire shall be rated for a minimum operational life of 50,000 hours at an average operating time of 12.0 hours per day. This life rating must be conducted 40C ambient temperature. 3. The rated operating temperature range shall be -30 C to +40 C. 4. Each luminaire is capable of operating above 100 F [37 C], but not expected to comply with photometric requirements at elevated temperatures. 5. Photometry must be compliant with IESNA LM-79 and shall be conducted at 25 C ambient temperature. 6. The individual LEDs shall be constructed such that a catastrophic loss or the failure of one LED will not result in the loss of the entire luminaire. 7. Luminare shall be constructed such that LED modules may be replaced or repaired without replacement of whole luminaire. 8. Each luminaire shall be listed with Underwriters Laboratory, Inc. under UL1598 for luminaires, or an equivalent standard from a nationally recognized testing laboratory. C. Technical Requirements 1. Electrical a. Power Consumption: Maximum power consumption allowed for the luminaire shall be determined by application. The luminaire shall not consume power in the off state. b. Operation Voltage: The luminaire shall operate from a 60 HZ ±3 HZ AC line over a voltage ranging from 108 VAC to 305 VAC. The fluctuations of line voltage shall have no visible effect on the luminous output. c. Power Factor: The luminaire shall have a power factor of 0.90 or greater. d. THD: Total harmonic distortion (current and voltage) induced into an AC power line by a luminaire shall not exceed 20 percent. e. Surge Suppression: The luminaire on-board circuitry shall include fused surge protection devices (SPD) to withstand high repetition noise transients as a result of utility line switching, nearby lightning strikes, and other interference. The SPD shall protect the luminaire from damage and failure for common mode transient peak voltages up to 10 kv (minimum) and transient peak currents up to 5 ka (minimum). SPD shall conform to UL 1449 depending of the components used in the design. SPD performance shall be tested per the procedures in ANSI/IEEE C62.41-1992 (or current edition) for category C (standard). The SPD shall fail in such a way as the Luminaire will no longer operate. The SPD shall be field replaceable. f. Each Luminaire shall have integral UL Listed Class II power supplies. Class I power supplies will not be acceptable. g. Operational Performance: The LED circuitry shall prevent visible flicker to the unaided eye over the voltage range specified above. h. RF Interference: LED Drivers must meet Class A emission limits referred in Federal Communications Commission (FCC) Title 47, Subpart B, Section 15 regulations concerning the emission of electronic noise. i. Drivers shall have a Class A sound rating. 2. Photometric Requirements a. Optical Assemblies: LEDs shall be provided with discreet over optical elements to provide proper distributions. All LEDs shall provide the same optical pattern such that catastrophic failures of individual LEDs will not constitute a loss in the distribution pattern. b. Illuminance: The illuminance shall not decrease by more than 30% over the expected operating life. The measurements shall be calibrated to standard photopic calibrations. 26 51 00-4 13-032

c. Light Color/Quality: The luminaire shall have a correlated color temperature (CCT) range of 4,000K to 4,500K. The color rendition index (CRI) shall be 80 or greater. Binning of LEDs shall conform to ANSI/ G. NEMA SSL 3-2010. 3. Thermal Management a. The thermal management (of the heat generated by the LEDs) shall be of sufficient capacity to assure proper operation of the luminaire over the expected useful life. b. The LED manufacturer s maximum thermal pad temperature for the expected life shall not be exceeded. c. Thermal management shall be passive by design. The use of fans or other mechanical devices shall not be allowed. d. The luminaire shall have a minimum heat sink surface such that LED manufacturer s maximum junction temperature is not exceeded at maximum rated ambient temperature. e. The heat sink material shall be aluminum. 4. Physical and Mechanical Requirements a. The luminaire shall be a single, self-contained device, not requiring on-site assembly for installation. The power supply for the luminaire shall be integral to the unit. b. The assembly and manufacturing process for the LED luminaire shall be designed to assure all internal components are adequately supported to withstand mechanical shock and vibration from high winds and other sources. c. The electronics/power supply enclosure shall meet the requirements for NEMA/UL wet location. d. Door shall be hinged and secured to the housing in a manner to prevent its accidental opening. e. The circuit board and power supply shall be contained inside the luminaire. Electrolytic capacitors used in the power supplies shall be rated for -40 F to 220 F (-40 C to +105 C), long life ( > 5000 hours ), and operated at no more than 70% of their rated voltage, and 70% of rated current. 2.6 LIGHTING FIXTURE SUPPORT COMPONENTS A. Comply with Division 26 Section "Hangers and Supports for Electrical Systems" for channeland angle-iron supports and nonmetallic channel and angle supports. B. Single-Stem Hangers: 1/2-inch steel tubing with swivel ball fittings and ceiling canopy. Finish same as fixture. C. Twin-Stem Hangers: Two, 1/2-inch steel tubes with single canopy designed to mount a single fixture. Finish same as fixture. D. Wires: ASTM A 641/A 641M, Class 3, soft temper, zinc-coated steel, 12 gage. PART 3 - EXECUTION 3.1 INSTALLATION A. Lighting fixtures: 1. Set level, plumb, and square with ceilings and walls unless otherwise indicated. 13-032 26 51 00-5

2. Install lamps in each luminaire. B. Lay-in Ceiling Lighting Fixtures Supports: Use grid as a support element. 1. Install ceiling support system rods or wires, independent of the ceiling suspension devices, for each fixture. Locate not more than 6 inches from lighting fixture corners. 2. Support Clips: Fasten to lighting fixtures and to ceiling grid members at or near each fixture corner with clips that are UL listed for the application. 3. Fixtures of Sizes Less Than Ceiling Grid: Install as indicated on reflected ceiling plans or center in acoustical panel, and support fixtures independently with at least two 3/4-inch metal channels spanning and secured to ceiling tees. C. Suspended Lighting Fixture Support: 1. Pendants and Rods: Where longer than 48 inches, brace to limit swinging. 2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers. 3. Continuous Rows: Use tubing or stem for wiring at one point and tubing or rod for suspension for each unit length of fixture chassis, including one at each end. 4. Do not use grid as support for pendant luminaires. Connect support wires or rods to building structure. D. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and Cables." 3.2 IDENTIFICATION A. Install labels with panel and circuit numbers on concealed junction and outlet boxes. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." 3.3 FIELD QUALITY CONTROL A. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify transfer from normal power to battery and retransfer to normal. END OF SECTION 26 51 00 26 51 00-6 13-032