Effectiveness of sprinklers in residential premises: Section 2: Description of the Project. Project report number

Similar documents
Effectiveness of sprinklers in residential premises:

New Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

Householders Guide to Fire Sprinklers

To obtain a greater understanding of the factors which contribute towards fire injuries and fatalities

Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

WELSH GOVERNMENT SPRINKLER PILOT STUDY

Structure Fires in Hotels and Motels

PREVENTION, PROTECTION, ROAD SAFETY

Lakanal House inquest: Statement from the Fire Sector Federation

FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT

Fire precautions in dwellings

Recent BRANZFIRE enhancements and validation

Bristol City Council Private Rented Sector Fire Safety Standards

Guideline No 11:2005. European guideline. Recommended Numbers of Fire Protection Trained Staff

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

Fire Safety in HMOs - Automatic Fire Sprinklers Ian Gough, BAFSA

The Loss prevention Council. Phase 1 report

Loss Prevention Standards

Evacuating vulnerable and dependent people from buildings in an emergency. David Crowder and David Charters

Retrofitting AFSS in Social Housing Highrises

Rosepark Care Home Fire An Overview

Fire safety and high rise student accommodation

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

carbon monoxide alarms

National Social Housing Fire Strategy Group

Implementing the Domestic Fire Safety Regulations 2013

Characterising the smoke produced from modern materials and evaluating smoke detectors

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

Timber escape stairs: Using timber stairs as means of escape. Summary. 1. Introduction

PREVENTION, PROTECTION, ROAD SAFETY

Fire Risk Assessment 2017

Fire prevention and protection

Design of Fire safety in Multi Occupancy Residential Accommodation

Domestic and Residential Fire Sprinklers Design Policy

The Association for Specialist Fire Protection. Understanding Best Practice in passive fire protection

Energy Efficiency Standards

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

IFE Level 4 Certificate in Fire Science and Fire Safety

Red Book News November 2010

Local area fire protection using automatic suppression

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Register of Significant Twentieth Century Architecture

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

UK Timber Frame Association

THE EFFECTS OF SMOKE ON PEOPLE S WALKING SPEEDS USING OVERHEAD LIGHTING AND WAYGUIDANCE PROVISION

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

RdSAP Conventions for SAP 2009

Library of Birmingham integrated with The REP

Fire prevention and protection

Department for Communities and Local Government Research Report:

PRODUCT GUIDE & INFORMATION. Professional Fire & Carbon Monoxide Solutions

Legislation Committee No.1

6.6.3 Minimum Provision for New Systems in New Dwellings Minimum Provision for New/Replacement Systems in Existing Dwellings

LIVERPOOL MIPIM

Considerations in the Design of Smoke Management Systems for Atriums

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA

Potential Impact of New UL Fire Test Criteria

Date: Place: Technical University of Denmark. Knowledge FOr Resilient society

Guidance Note EC Regulation No 842/2006 on Certain Fluorinated Greenhouse Gases. BFPSA Guidance for the Fire Protection Industry

1.4 Provide and fix the following ironmongery.

Local area fire protection using automatic suppression

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

Gothenburg dance hall, Sweden, 1998

Specialist Fire Safety Courses Xact Consultancy and Training Limited

HEAT RECOVERY VENTILATION For healthy, energy efficient ventilation

Energy Efficiency Rating

An experimental study of the impact of tunnel suppression on tunnel ventilation

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

The first tunnel fire. Benefits of fire

Date of assessment: 08 February 2014 Date of certificate: 10 February 2014 Reference number:

Related party disclosure: Technical Information Benchmark. 99 m² 336 kwh/m² per year 73 kg/m² per year

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Northern Ireland HMO Fire Safety Guide

Interim Advice Note 76 / 06 ASSESSMENT PART 1 AIMS AND OBJECTIVES OF ENVIRONMENTAL ASSESSMENT. Contents

Energy Performance Certificate

Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon

fire risk assessment For use by landlords of small premises Premises Address

ABOUT CALA HOMES CALA HOMES

WELSH GOVERNMENT DOMESTIC FIRE SPRINKLER PILOT STUDY. Colin Blick Building Standards Technical Manager Welsh Government

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

COMMUNITY GROWN FOOD IN WALES

1. Revise and A to read as follows:

NOTTINGHAM CITY HOMES

Scottish Building Standards and Fire Safety: A Brief Overview

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

Section 14 COST Action C17: Built Heritage: Associated Publications

The Macro Quallty Assurance System for Fire Safety Engineering

CHC's One Big Housing Conference Health and Safety Update: Gas Safety

Home Fires Involving Heating Equipment

This document is a preview generated by EVS

Why should getting a Fire Risk Assessment right be a vital management policy?

QUALIFICATIONS AND CREDIT FRAMEWORK (QCF) LOGIC CERTIFICATION LIMITED (LCL) QUALIFICATION SPECIFICATION

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

Transcription:

Effectiveness of sprinklers in residential premises: Section 2: Description of the Project Project report number 204505 Dr Corinne Williams Dr Jeremy Fraser-Mitchell Dr Stuart Campbell and R Harrison February 2004

Contents 2 Description of the Project 1 2.1 Steering Group 2 2.2 Pilot Study 2 2.3 Benchmark tests 3 2.4 Experimental programme 3 2.4.1 House fires 4 2.4.2 Compartment fires 4 2.5 Cost benefit analysis 5 2.6 Dissemination 6 2.7 Acknowledgements 6 2.8 References 7 Appendix 2A - Steering Group members 8

1 Section 2: Description of the Project 2 Description of the Project Residential sprinklers are the subject of much debate (in the UK) because they offer a potential means of saving lives in domestic/residential properties. The key question is: can a sprinkler system provide adequate fire control to allow escape/rescue at a reasonable cost? The publication of British Standard Drafts for Development DD251 1 and DD252 2 provides a basis on which an examination of both effectiveness and cost can be examined. There was a lack of information at the start of this Project regarding the overall effectiveness of residential sprinklers. Also, firm and transparent guidance is needed regarding the design parameters for these systems. FRS was commissioned by ODPM to carry out a two and a half-year study on the effectiveness of sprinklers in residential premises. The overall aim of the Project was to determine the benefits and effectiveness of sprinklers in residential accommodation. The specific objectives of this Project were: a) To analyse statistical information to determine how effective they have been in reducing life loss and property damage b) To make a risk-based assessment to determine potential benefits for the UK housing sector, including Houses in Multiple Occupation (HMOs), flats and maisonettes of varying heights c) To collect data on the benefits and costs of residential sprinklers d) To establish benchmark tests for UK conditions to support the further development of DD251 and DD252, and e) To carry out an experimental programme to examine and quantify the effectiveness in fire suppression of residential sprinklers, in particular with regards to life safety in the room of origin. To achieve these objectives, six main Tasks were carried out: Task 1 Steering Group, Task 2 Pilot study, Task 3 Cost benefit analysis, Task 4 Benchmark tests, Task 5 Experimental programme and Task 6 Dissemination of findings. Initial dissemination of the emerging results of this study was via a seminar which was held in December 2003. 1 British Standards Institution, DD 251 Sprinkler systems for residential and domestic occupancies Code of Practice, April 2000 2 British Standards Institution, DD 252 Components for residential sprinkler systems - Specification and test methods for residential sprinklers, July 2002

2 Section 2: Description of the Project The results from this project will provide input into the development of full UK design standards and will also provide the Regulators with sound engineering-based results that they can use for Regulatory decisions. In the short term, this will undoubtedly assist those working within the fire arena, offering them the potential to consider informed alternative approaches to the current guidance contained in Approved Document B (Fire safety). 2.1 Steering Group Industry contribution has been an integral part of the Project and has been co-ordinated/ focussed via a Steering Group. The Steering Group was established at the outset of the Project and comprised, representatives of Regulators, Fire Service, House Builders, residential sprinkler industry and the water industry. The Group has been active and enthusiastic and has met six times. A smaller experimental Working Group particularly focussed on reviewing the details of the experimental work. Table 2.1 details the individual Steering Group members and the organisations they represented during the course of the Project. The purpose of the Steering Group was to inform the Project, to review and comment on the FRS work programme, to provide relevant data/information and to discuss relevant issues and initiatives. Issues discussed by the Steering Group include: FRS work programme Residential sprinkler systems costs data Progress of British Standards activities Water supplies initiatives Residential sprinkler installation survey [Hardy 2003] Proposed Scottish Residential fire sprinklers bill [Matheson 2001] Alternative systems e.g. water mist Welsh initiatives. All these topics are covered elsewhere in this Report. Wider industry contribution has also been provided through a seminar (held on 11 December 2003). 100+ delegates attended, and provided a number of number of comments which have fed into this final report. 2.2 Pilot Study The Pilot study consisted of the following items: Statistical and other information were obtained, reviewed and analysed to determine the effectiveness of sprinklers in reducing life loss and property damage A simple assessment was made to look at the risks in residential premises and to determine the potential benefits for the UK housing sector including Scotland.

3 Section 2: Description of the Project A consideration of the suitability of DD 251 and DD 252 as the basis for future UK residential sprinkler standards was made by carrying out a critical review of the DDs to identify the technical knowledge gaps and other areas of uncertainty. The findings of this pilot study were summarised in a progress and project report with recommendations for the onward direction of the Project. 2.3 Benchmark tests A series of experimental Benchmark tests were carried out to establish a benchmark fire test for UK conditions to support the further development of BS DD251 and 252 and to assess the performance of residential sprinklers in fire test conditions. The DD 252 fire test essentially involves burning a stylised, representative fuel package of simulated furniture and wall and ceiling linings arranged inside a simulated residential 'room' with door openings and with two installed sprinkler heads. There are two open doorways and near the opening of one doorway is a third dummy sprinkler head. The sprinkler system performance is determined by its performance in controlling the fire for a period of time measured after sprinkler operation, the gas temperatures being limited to specified values and the dummy sprinkler head not operating. Five pre-selected commercially-available residential sprinkler heads were obtained and these were characterised using vertical and horizontal water distribution measurements. Four were chosen for further study in the fire tests. Suitable UK materials were obtained for the fuel package given in DD 252. Elements and the whole fuel package arrangement were characterised using seven fires, in free burns without sprinklers, under a calorimeter. A series of eighteen fire tests was conducted, including repeat tests, based on the procedures given in DD 252 to examine the effect of varying parameters on the performance of residential sprinklers. The parameters investigated were: sprinkler model (four 15 mm pendent types), location of fuel package within sprinkler spray (wall, corner and directly beneath sprinkler configurations), the effect of the presence of 0.3 m lintels (with and without), sprinkler water flow rate (3 and 4 mm/min). 2.4 Experimental programme The purpose of the Experimental programme was to examine and quantify the effectiveness of residential sprinklers, in particular to life safety in the room of fire origin. This programme was divided into two main parts: house, and compartment and fires. Calorimetry fires were also performed to characterise the fire scenarios in terms of heat release rate, etc.

4 Section 2: Description of the Project Sprinklers installed to in DD251 are not necessarily designed to extinguish the fires, but to control them to allow escape or rescue. The effectiveness of the residential sprinklers in the house and compartment fires was primarily assessed, particularly in the room of origin, by measuring their ability to control toxicity, temperature effects and visibility effects. In addition, the amount of fuel burnt by area, with and without sprinklers, was also measured. Fractional Effective Dose calculations were performed using the results of each test in order to assess the tenability, both of the fire room and connected spaces. These calculations were based on carbon monoxide, carbon dioxide and oxygen concentrations at head height, head height gas temperatures, and optical density per metre. 2.4.1 House fires Eight sprinklered and unsprinklered lounge fires using realistic fuel arrays were conducted inside the FRS house which was a two-storey detached house of traditional design, with a loft conversion The ground floor comprised a lounge (4 m by 3.5 m by 2.4 m), a kitchen, a dining room and a hallway. The ground floor could be converted into open plan by removing the lounge/hall wall. The first floor comprised two bedrooms and a bathroom area. There was a straight flight of conventional tread stairs up to the loft room which had a fire-resisting cut off door. The lounge, main bedroom and loft windows were double glazed and were closed for the tests. Inside the lounge, there was a chimney, two low level air bricks. The door of the main bedroom was partially open, the door of the loft room and bathroom were closed, the dining room/kitchen, back bedroom/landing and kitchen/hallway doors were closed and sealed. Five fire tests were performed in a standard lounge arrangement, and three in an open plan lounge arrangement. The effect of lounge/hallway door (open/closed), water flow rate, sprinkler orientation and sprinkler model (two 15 mm pendent types) were studied. The sprinkler water flow rates were 60 l/min for a single sprinkler for standard lounge arrangement, and 60 l/min for a single sprinkler or 84 l/min for two sprinklers operating, for the open plan lounge arrangement. 2.4.2 Compartment fires Twenty-nine fires using realistic fuel arrays representative of residential premises were conducted inside a compartment experimental facility.

5 Section 2: Description of the Project The compartment facility essentially comprised residential rooms with a timber structure supporting plasterboard walls and a ceramic fibre board ceiling. The facility was configured to provide alternative fire rooms at either end, each measuring 4 m by 4 m by 2.5 m high, connected to a middle room measuring 3.8 m by 4 m by 2.5 m high. With the fire room door open the effective enclosure volume was approximately 118 m 3, reduced to 40 m 3 with the fire room door closed. Some of the fire tests involved a larger room size of 8 m by 4 m by 2.5 m high. Smoke alarms were located inside the room of fire origin and its adjacent room and were replaced after every fire. Initially, sixteen fires comprising four main fire scenarios were conducted, each with and without sprinklers and with the door of the room of fire origin open and closed. The scenarios were, as follows: Lounge, nightlight and television fire, shielded fire Lounge, fire under table directly beneath sprinkler, shielded fire Bedroom scenario, fire on duvet, unshielded fire. Lounge, fire on sofa (compliant with 1988 Furniture Regulations), unshielded fire. The fuel was conditioned prior to each test and the house was allowed to dry out between tests. Following these initial fires, the television and table fires were chosen for further study of the effect of compartment size (either 4m by 4 m or 8 m by 4m by 2.5 m high 2.5m), sprinkler model (one of two 15mm pendent models), sprinkler orientation (parallel or perpendicular to axis of facility) and water flow rate. The sprinkler water flow rates were 60 l/min or 42l/min for a single sprinkler for standard compartment, and 60 l/min for a single sprinkler or 84 l/min for two sprinklers operating, for the large compartment. A kitchen scenario was examined, an unshielded oil pan fire, with or without sprinklers (two 15 mm pendent models). 2.5 Cost benefit analysis Cost benefit analyses have been performed for a range of domestic and residential building types, including houses, flats, various types of houses of multiple occupation (HMOs), and residential care homes. Further analyses were performed for different building heights, within certain of the broad categories listed above, in order to focus on properties that would be expected to have higher than average risks from fire.

6 Section 2: Description of the Project The benefits of sprinklers include the prevention of deaths and injuries, and the reduction of property damage. The estimated effectiveness of sprinklers, in terms of the percentage reduction of deaths and injuries, was based on a correlation between fire size and risk of death and/or injury. Full details of this method are described in the section covering the Pilot study. The other benefit considered was the reduction in property damage. Rather than assume the cost of the fire was directly proportional to the area damaged by the fire (which would neglect the larger area damaged by smoke), the estimated effectiveness from the USA statistics was used. Residential sprinkler systems costs include installation; provision of water supplies; annual maintenance. Estimates of these costs have been provided by members of the UK sprinkler and water industries. Government guidance was followed in assigning monetary values to the numbers of deaths and injuries prevented, the average cost of property damage per fire, and the interest rate to use when calculating the capital recovery factor to convert initial costs into annual terms. The costs and benefits all have uncertain values. An uncertainty analysis has been performed to estimate the degree of confidence that the monetary benefits from providing sprinklers are significantly greater than the costs 3, for all the cases of building type examined. 2.6 Dissemination Dissemination of the emerging results of this study was initially via a seminar which was held on 11 th December 2003. This was attended by about 100 delegates. A number of useful comments were received in feedback from this event, and have helped us to clarify aspects of the report. the Final Report which was provided to ODPM by December 2003, circulated to the Project Steering Group for comments and feedback and published in February 2004. Further dissemination is ongoing. 2.7 Acknowledgements The authors would like to thank the Steering Group and the Experimental Working Group for their enthusiasm, helpful comments and feedback during the course of this project. They would also like to acknowledge the contributions of the teams, as follows: Cost benefit analysis: Jeremy Fraser-Mitchell Additional advice and feedback on cost benefit analysis: Scott Dennison and Sophie Cruickshank (ODPM) and Richard Hartless (BRE) 3 a rough guideline is that if the calculated benefit-to-cost ratio exceeds 1.00 by more than the estimated uncertainty (2 standard deviations) in the benefit-to-cost ratio, then we can say with 95% confidence that sprinklers will be cost-effective.

7 Section 2: Description of the Project Benchmark tests: Roger Harrison, Dave Smit, Peter Walker, Corinne Williams Additional advice for Benchmark tests: John Stephens House fires: Stuart Campbell, Corinne Williams, Peter Walker, Frans Hofsteede, Compartment fires: Stuart Campbell, Rajesh Parbat, Corinne Williams Also, Peter Walker, John Stephens, Christian Nielson for assistance in some of the fires, Phil Clark for preparation of some of the graphs and photographs and Kelvin Annable for help with preparation of two project reports Advice on toxicity aspects and fractional effective dose modelling for house and compartment fires: Professor David Purser Advice on smoke alarms aspects: Nigel Smithies Tom Cray and assistants for building and altering experimental facilities. The Final Report is part of a contract placed by the Office of the Deputy Prime Minister (ODPM). Any views expressed in it are not necessarily those of the ODPM. 2.8 References Clarke C, Survey of residential sprinkler installations, September 2003. Hardy, P, Results of residential sprinkler installation survey, September 2003. Matheson M, Consultation document for proposed residential fire sprinklers bill, The Scottish Parliament web site, http://www.scottish.parliament.uk, September 2001.

8 Section 2: Description of the Project Appendix 2A - Steering Group members Member Williams, Corinne Campbell, Stuart Fraser-Mitchell, Jeremy Harrison, Roger Stephens, John Baker, David Bond, Allan Burd, Anthony Carvell, Tony Cornthwaite, Lea Eady, Mick Evans, Glyn Hartless, Richard Heaviside, Leslie Hird, Colin Hobbs, Darren Kidd, Stewart Reed, Mike Seaber, CFO Steve Stollard, Paul Tucker, Mike Whittaker, Ian Wilson, Tony Young, Roy Organisation represented Chairman and Co-ordinator, FRS, BRE FRS, BRE FRS, BRE FRS, BRE FRS, BRE House Builders Federation Welsh Assembly Government Buildings Division, ODPM Fire Brigades Union Fire Policy Unit, ODPM HM Fire Service Inspectorate, ODPM Fire Brigades Union Energy Technology Centre, BRE Wormald (Ansul) UK Ltd Buildings Standards Division, Scottish Executive Buildings Division, ODPM British Automatic Sprinkler Association Fire Policy Unit, ODPM CACFOA Buildings Standards Division, Scottish Executive NHBC Ltd Water UK AEA Technology Environment Fire Sprinkler Association (formerly Residential Sprinkler Association)