M2500 Engine Controller Installation Manual

Similar documents
M2000 Engine Controller

M2000 Engine Controller

M1000 Alarm Annunciator

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

21-light Remote Annunciator. Owner s Manual

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device

CTT8 TEMPERATURE MONITOR DEVICE

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

MO n : 12JMC rév A

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

User s Manual DCU 305 R3 DCU 305 R3 LT. Diesel Engine Control Unit. Auto-Maskin

Installation, Operating and Maintenance Manual

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ME 3011C / Alarm Indication / Quick Reference Guide

Technical Manual. Level Alarm Unit CARLA & WIDS

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

AL800ULADA. NAC Power Extender. Installation Guide

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

Application, Installation, Operation & Maintenance Manual

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Product Manual SZ1145

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

APP 721 MODBUS Mapping

RS485 MODBUS Module 8AI

Zone Terminal, 2-fold, FM MT/U , GH Q R0111

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Across-the-Line SERIES MP300 Combined Manual and Automatic

Product Manual SZ1144

B-40/B-41 Modulating Temperature Controller

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics

Carbon Monoxide Transmitter

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

4 & 8-POINT ANNUNCIATORS Instruction Manual

Fire Control Panel FS4000

USER MANUAL FOR OPERATING SYSTEM

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Troubleshooting Manual

Soft Start Series MP700 Solid State, Reduced Voltage

Halton SAFE / 7.14 user guide and installation instructions

EXTINGUISHING AGENT RELEASE MODULE

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Lift Station Level Controller

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

ESSEX ENGINEERING CORPORATION

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Tri-Stack Smart System

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

Panel Mounted Fault Annunciator Series

20 Light Remote Annunciator

Instruction Manual SCD24. Read this document prior to installation. Contents

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Interface and EOL Modules 8

Flopurge TS. Operation Manual

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Installation and user manual for the BiWire / Conventional Repeater Panel

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

AIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Process Alarm Solutions

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Two-Channel Gas Controller

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Conventional Fire Alarm System 2014 V1.2

CONTROL DEVICE SLIDETRONIC HD

SCAN200E USER S MANUAL

Instructions OJ EC-Controller (Translation of the original) BA-ESR_OJ-EC /2013

Intelligent Security & Fire Ltd

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Built-on speed controller for GMPM plug fan with permanent magnet motor

Flostop TS D7E and A8E. Operation Manual

DCU 305 R2/R3. Troubleshooting Manual

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Combi B Alarm box. Mounting instructions

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

General Routing Interface

AL600ULADA. NAC Power Extender. Installation Guide

Window facia fault annunciators

PTE0705 Electric Fence Monitor

Transcription:

M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1

Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs... 7 4.2.1 Connection of Mode Selector Switch... 8 4.2.2 Remote Start (terminal 8)... 9 4.2.3 Remote Stop (terminal 9)... 9 4.2.4 Override (terminal 10)... 10 4.2.5 Crank Disconnect (terminal 11)... 10 4.2.6 Reset (terminal 12)... 10 4.2.7 COM (terminal 13)... 11 4.3 Speed detection... 11 4.3.1 Connection of magnetic pick-up... 11 4.3.2 Connection of PNP pick-up... 12 4.3.3 Connection of NPN pick-up... 12 4.4 Digital sensor inputs... 13 4.4.1 Connection of a normally open sensor without cable monitoring... 13 4.4.2 Connection of a normally closed sensor without cable monitoring... 14 4.4.3 Connection of a normally open sensor with cable monitoring... 14 4.4.4 Connection of a normally closed sensor with cable monitoring... 15 4.4.5 COM (terminal 13)... 15 4.5 Analogue sensor inputs... 15 4.5.1 Analogue inputs (terminals 27 to 34)... 16 4.5.2 COM (terminal 13)... 16 5 Outputs... 17 5.1 Engine Status Outputs... 17 5.1.1 Connection of Engine Status Outputs... 17 5.1.2 Ready (terminal 36)... 18 5.1.3 Start warning (terminal 37)... 18 5.1.4 Engine running (terminal 38)... 18 5.1.5 Cool Down (terminal 39)... 18 5.1.6 REF 1 (terminal 40)... 18 5.2 Engine Control Outputs... 19 5.2.1 Connection of Engine Control Outputs... 19 5.2.2 Auxiliary Lubrication Pump (terminal 41)... 19 5.2.3 Crank (terminal 42)... 20 5.2.4 C/B trip (terminal 43)... 20 5.2.5 Air Intake Valve (terminal 44)... 20 5.2.6 REF 2 (terminal 45)... 20 Revision: 23-04-2012 Page 2

5.3 Alarm Outputs... 20 5.3.1 Connection of alarm outputs... 21 5.3.2 Common Alarm (terminal 46)... 21 5.3.3 Shutdown (terminal 47)... 21 5.3.4 Cable break (terminal 48)... 21 5.3.5 CAN (terminal 49)... 21 5.3.6 REF3 (terminal 50)... 21 5.4 Digital Outputs... 22 5.4.1 Connection of digital outputs... 22 5.4.2 Digital Outputs Out 1 to Out 12 (terminals 51 to 62)... 23 5.4.3 REF 4 (terminal 50)... 23 5.5 Control Relays... 23 5.5.1 Engine Stop Output (terminal 64 and 65)... 23 5.5.2 Run/ Stop Solenoid (terminal 66 and 67)... 24 5.6 Siren Relay... 26 5.6.1 Connection of the Siren Relay... 26 6 Communication... 27 6.1 CAN J1939 Bus... 27 6.1.1 CAN J1939 Connector:... 27 6.1.2 CAN cable... 27 6.1.3 RS485 MODBUS... 28 6.1.4 RS485 cable... 28 7 Functional Description... 29 7.1 Remote Mode... 29 7.2 Alarm Monitoring... 31 7.2.1 Alarm flowchart:... 32 7.3 Shutdown Monitoring... 33 7.3.1 Shutdown flowchart:... 34 7.4 Specification... 35 Revision: 23-04-2012 Page 3

1 Preface The M2500 - Engine Controller is designed for control and monitoring of marine engines. Together with the optional M2600 - Shutdown Unit the M2500 - Engine Controller forms a complete alarm, control and protective safety system for marine engines. Typical applications are marine generator engines such as auxiliary generators, emergency generators, harbour generators and propulsion engines. The M2500 is designed for assembly in the main switchboard or at the engine. This manual describes the installation of the M2500 - Engine Controller. Revision: 23-04-2012 Page 4

2 Installation The M2500 is designed for flush mounting to the front panel of the switchboard. It is secured by 6 mounting brackets which are supplied with the M2500. The panel cut out dimension is 138mm x 210mm Revision: 23-04-2012 Page 5

3 Terminal Connections RS485 Modbus USB interface for configuration and read out of alarm log Primary and back-up power supply Inputs for activation of operation modes, Inputs for remote start and stop Input for magnetic, NPN or PNP pickup for speed detection Digital sensor inputs for alarms and shutdowns Analogue sensor inputs for alarms and shutdowns Outputs for indication of engine state (e.g. to PMS) Control outputs Common alarm outputs Programmable outputs for indication of alarms and shutdowns Engine stop relay Programmable output for stop or run solenoid with cable monitoring Siren relay Future use Adjustment of display contrast Interface for CANJ1939 Slot for SD card for read out of log and configuration Revision: 23-04-2012 Page 6

4 Inputs 4.1 Power Supply Redundant Power Supply (2x 24V DC, -30 % / +30 %) Alarm in case any power supply fails (common alarm + display text). Primary supply will not be monitored during cranking, as the battery voltage will drop during this process. Nr. Description 01 Primary Supply + 02 Primary Supply - 03 Primary Supply + 04 Primary Supply - 4.2 Mode/ Control Inputs Nr. Description Logic (NO/NC) 05 Remote Mode NO 06 Local Mode NO 07 Off Mode NO 08 Remote Start NO 09 Remote Stop NO 10 Override NO 11 Crank disconnect NO 12 Reset NO 13 COM Common reference for control inputs Revision: 23-04-2012 Page 7

4.2.1 Connection of Mode Selector Switch The external mode selector switch is used for switching the M2500 into OFF, REMOTE or LOCAL mode. 4.2.1.1 Local Mode (terminal 5) The local mode input is considered active when connected to COM, inactive when open. When active the M2500 will be in local mode. This means start and stop are only available from the push buttons on the front panel. The remote start and stop terminals are disabled. The LOCAL LED on the front panel will be lit. Not ready LED on the front panel will be lit and READY output terminal 36 will be deactivated indication that the engine is not available for remote start. 4.2.1.2 Remote Mode (terminal 6) The remote mode input is considered active when connected to COM, inactive when open. When active the M2500 will be in remote mode. This means start and stop are only available from the REMOTE START and REMOTE STOP terminals. The Local start and stop push buttons are disabled. Provided no alarm, shutdown or Off command is active, the green REMOTE LED on the front panel will be lit and the engine is ready for remote start. 4.2.1.3 Off (terminal 7) The off input is considered active when connected to COM, inactive when open. When activated, the M2500 will initiate a stop procedure. Engine start will be blocked as long as this input is active. Not ready LED on the front panel will be lit indicating that the engine is not available for remote start. Revision: 23-04-2012 Page 8

4.2.2 Remote Start (terminal 8) The Remote Start input is considered active when connected to COM, inactive when open. It can be a pulse or continuous signal. The input is only enabled in remote mode. When activated, the M2500 will generate a start signal to the engine. The pre-configured number of start attempts is available. During the start attempt the green Engine Running LED on the front panel will be fast flashing. During the rest periods between start attempts this LED will be slow flashing. When the engine is running, the LED will be lit continuously. If the engine does not start the M2500 will initiate a stop procedure and a Start Fail Alarm. The red ALARM LED on the front panel will be lit. The alarm text START FAILURE will be shown on the display. 4.2.3 Remote Stop (terminal 9) The Remote Stop input is considered active when connected to COM, inactive when open. It can be a pulse or a continuous signal. The input is only enabled in remote mode. When activated, the M2500 will initiate a stop procedure. During the stop procedure the green Running LED will be slow flashing. The Stopping LED will be lit. If the engine does not stop the M2500 will generate a Stop Fail Alarm. The red ALARM LED on the front panel will be lit. The alarm text STOP FAILURE will be shown on the display. The engine will be blocked for start as long as the stop input is active. When activated simultaneously, Stop overrides Start. Revision: 23-04-2012 Page 9

4.2.4 Override (terminal 10) The Override input is considered active when connected to COM, inactive when open. When activated all shutdowns that are marked override will be disabled, meaning the engine will continue running despite of a shutdown. If the override is deactivated while a shutdown is present, shutdown will be executed immediately. 4.2.5 Crank Disconnect (terminal 11) The Cranck Disconnect input is considered active when connected to COM, inactive when open. This input is only used in case there is no pick-up for speed detection. The input is a contact from a tacho-relay that signals that the speed of the engine is above ignition speed. When receiving the Crank Disconnect signal the M2500 will deactivate the crank output after a start attempt. If the M2500 looses this signal without a stop procedure, the ALARM LED will be lit and a Tacho Fail Alarm will be displayed. 4.2.6 Reset (terminal 12) This Reset is considered active when connected to COM, inactive when open. When activated, this input will reset the siren and the alarm/ shutdown. Revision: 23-04-2012 Page 10

4.2.7 COM (terminal 13) The COM is the common reference for all digital inputs.com and power supply minus are internally connected. 4.3 Speed detection Speed detection Remark 14 Supply voltage for PNP or NPN pick-up 15 Pick-up Pick-Up signal input 16 Reference for pick-up signal 4.3.1 Connection of magnetic pick-up The magnetic pick-up is connected as follows: For use of magnetic pick-up the DIP switches 3 and 4 on the rear side of M2500 must be in OFF position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500. DIP Switch Position 1 OFF 2 OFF Revision: 23-04-2012 Page 11

4.3.2 Connection of PNP pick-up The NPN pick-up is connected as follows: For use of PNP pick-up the DIP switch 3 on the rear side of M2500 must be in ON position, DIP switch 4 must be in OFF position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500. DIP Switch Position 1 ON 2 OFF 4.3.3 Connection of NPN pick-up The NPN pick-up is connected as follows: For use of NPN pick-up the DIP switch 3 on the rear side of M2500 must be in OFF position, DIP switch 4 must be in ON position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500. DIP Switch Position 1 OFF 2 ON Revision: 23-04-2012 Page 12

4.4 Digital sensor inputs Nr. Description Remark 17 Digital input 1 Sensor input for digital sensor 1 18 Digital input 2 Sensor input for digital sensor 2 19 Digital input 3 Sensor input for digital sensor 3 20 Digital input 4 Sensor input for digital sensor 4 21 Digital input 5 Sensor input for digital sensor 5 22 Digital input 6 Sensor input for digital sensor 6 23 Digital input 7 Sensor input for digital sensor 7 24 Digital input 8 Sensor input for digital sensor 8 25 Digital input 9 Sensor input for digital sensor 9 26 COM Common reference for digital sensor inputs The Digital sensor inputs are used for the connection of the digital sensors. Digital sensors can be Normally Open (NO) or Normally Closed (NC) logic. Cable break and short circuit monitoring is available. 4.4.1 Connection of a normally open sensor without cable monitoring The following example shows the Connection of a normally open sensor without cable monitoring. The sensor is considered active when connected to COM, inactive when open. When activated, the input generates an alarm or shutdowns or a control signal, depending on the configuration. Revision: 23-04-2012 Page 13

4.4.2 Connection of a normally closed sensor without cable monitoring The following example shows the Connection of a normally closed sensor without cable monitoring. The sensor is considered active when open, inactive when connected to COM. When activated, the input generates an alarm or shutdowns or a control signal, depending on the configuration. 4.4.3 Connection of a normally open sensor with cable monitoring The following example shows the Connection of a normally open sensor with cable monitoring. The sensor is considered active when connected to COM, inactive when open. Resistor R1 is used for cable break monitoring. Resistor R2 is used for short circuit monitoring. It is very important that both resistors are mounted close to the sensor. Revision: 23-04-2012 Page 14

4.4.4 Connection of a normally closed sensor with cable monitoring The following example shows the connection of a normally closed sensor with cable monitoring. The sensor is considered active when open, inactive when connected to COM. Resistor R1 is used for short circuit monitoring. Resistor R2 is used for cable break monitoring. It is very important that both resistors are mounted close to the sensor. 4.4.5 COM (terminal 13) The COM is the common reference for all digital inputs.com and power supply minus are internally connected. 4.5 Analogue sensor inputs Analogue sensor inputs are used for temperature and pressure measurements. All analogue sensors use 4-20mA signals. Analogue Sensor Inputs Remark 27 4mA -20mA Analogue input 1 28 4mA -20mA Analogue input 2 29 4mA -20mA Analogue input 3 30 4mA -20mA Analogue input 4 31 4mA -20mA Analogue input 5 32 4mA -20mA Analogue input 6 33 4mA -20mA Analogue input 7 34 4mA -20mA Analogue input 8 35 COM Common reference for analogue sensor inputs Revision: 23-04-2012 Page 15

4.5.1 Analogue inputs (terminals 27 to 34) The analogue sensor inputs are for generating alarms and shutdowns. In case the input signal is below 3mA or above 25mA the M2500 will generate a sensor fail alarm. Cable Error LED will be lit. Delay times can be programmed for alarms and shutdowns. 4.5.2 COM (terminal 13) The COM is the common reference for all digital inputs.com and power supply minus are internally connected. Revision: 23-04-2012 Page 16

5 Outputs All outputs are relay contacts. 5.1 Engine Status Outputs Nr. Description Type Rating 36 Ready/ Not Ready NO Relay 1A 37 Start warning NO Relay 1A 38 Engine Running NO Relay 1A 39 Cool down NO Relay 1A 40 REF1 Common reference for engine status outputs 5.1.1 Connection of Engine Status Outputs Following example shows the connection of an external relay for the engine running signal: Revision: 23-04-2012 Page 17

5.1.2 Ready (terminal 36) Normally Open Relay output. The Ready output indicates the availability of the engine for remote start e.g. for a power management system. The output can be configured as Engine Ready or Engine Not Ready. The output is activated when closed to COM (terminal) 40. Note: Configuration as Ready Output: The output is activated when the engine is available for remote start. The output is de-activated in all other conditions (e.g. M2500 in Local mode shutdown error or start blocking) (normally de-energized output). Note: Configuration as Not Ready output: The output is activated when the engine is not available for remote start (e.g. M2500 in Local mode shutdown error or start blocking). The output is de-activated when the output is ready for remote start (normally energized output). 5.1.3 Start warning (terminal 37) Normally Open Relay output. This output is activated for a preconfigured time before each start attempt. The output is activated when closed to COM (terminal) 40. The relay is normally deenergized. 5.1.4 Engine running (terminal 38) Normally Open Relay output. This output indicates that the engine is running. The output is activated when closed to COM (terminal) 40. The relay is normally de-energized. 5.1.5 Cool Down (terminal 39) Normally Open Relay output. This output indicates that the engine is in cool down mode. After receiving the engine stop command, the M2500 will trip the C/B. The engine will continue running for the duration of the cool down time. After expiration of the cool down time the M2500 will stop the engine. The cool down time can be configured. Cool Down only applies to remote mode and only for normal stops. Shutdowns will be executed immediately. Note: Purpose of this output is to give a signal to a synchronizer in order to avoid re-synchronization. The output is activated when closed to COM (terminal) 40. The relay is normally de-energized. 5.1.6 REF 1 (terminal 40) Common reference for all output relays terminals 36 to 39. Revision: 23-04-2012 Page 18

5.2 Engine Control Outputs Nr. Description Type Rating 41 Auxiliary lubrication pump NO Relay 1A 42 Crank NO Relay 1A 43 Circuit breaker trip NO Relay 1A 44 Air intake valve NO Relay 1A 45 REF 2 Common reference for the control outputs 5.2.1 Connection of Engine Control Outputs Following example shows the connection of an external relay for the C/B trip signal: 5.2.2 Auxiliary Lubrication Pump (terminal 41) Normally Open Relay output. When the engine is stopped the output becomes active every 30 min for 2 min. Immediately after stop the first lubrication period is after 20 min. The interval and duration times can be configured. The relay is normally de-energized. Revision: 23-04-2012 Page 19

5.2.3 Crank (terminal 42) Normally Open Relay output. This is the start output of the M2500. It activates for each start attempt and remains active until either the engine has fired or the crank time has expired or a stop command has been activated at the M2500. The relay is normally de-energized. 5.2.4 C/B trip (terminal 43) Normally Open Relay output. This output trips the circuit breaker before the engine stops. It is always activated after a stop command has been received or a shutdown has been activated. The relay is normally de-energized. 5.2.5 Air Intake Valve (terminal 44) Normally Open Relay output. This is an alternative stop output. The output is activated immediately when a stop procedure is activated, regardless if this is a normal stop or a shutdown. The relay is normally de-energized. 5.2.6 REF 2 (terminal 45) Common reference for all output relays terminals 41 to 44. 5.3 Alarm Outputs Nr. Description Type Rating 46 Common Alarm NO Relay 1A 47 Shutdown NO Relay 1A 48 Cable Break NO Relay 1A 49 Communication Error NO Relay 1A 50 REF 3 Common reference for the alarm outputs Revision: 23-04-2012 Page 20

5.3.1 Connection of alarm outputs Following example shows the connection of an external relay for signaling a shutdown to an external alarm system: 5.3.2 Common Alarm (terminal 46) Normally Open Relay output. This output becomes energized for each alarm and shutdown. The relay is normally de-energized. In case a new alarm/ shutdown appear while the relay is already energized, the alarm will de-energize for two seconds and then energize again. 5.3.3 Shutdown (terminal 47) Normally Open Relay output. This output becomes active for each shutdown. The relay is normally de-energized. 5.3.4 Cable break (terminal 48) Normally Open Relay output. This output becomes active for each cable break at the digital inputs or sensor fails at the analogue inputs. The relay is normally de-energized. 5.3.5 CAN (terminal 49) Normally Open Relay output. This output becomes active in case a communication error on the CAN J1939 is detected. The relay is normally de-energized. 5.3.6 REF3 (terminal 50) Common reference for all output relays terminals 46 to 49. Revision: 23-04-2012 Page 21

5.4 Digital Outputs Nr. Description Type Rating 51 52 Digital Output 1 (start fail in default config) Digital Output 2 (stop fail in default config) NO Relay NO Relay 1A 1A 53 Digital Output 3 NO Relay 1A 54 Digital Output 4 NO Relay 1A 55 Digital Output 5 NO Relay 1A 56 Digital Output 6 NO Relay 1A 57 Digital Output 7 NO Relay 1A 58 Digital Output 8 NO Relay 1A 59 Digital Output 9 NO Relay 1A 60 Digital Output 10 NO Relay 1A 61 Digital Output 11 NO Relay 1A 62 Digital Output 12 NO Relay 1A 63 REF 4 Common reference for the digital outputs 5.4.1 Connection of digital outputs Following example shows the connection of an external relay to digital output 2: Revision: 23-04-2012 Page 22

5.4.2 Digital Outputs Out 1 to Out 12 (terminals 51 to 62) Normally Open Relay output. These are programmable alarm and shutdown outputs. It is also possible to program these outputs to activate with any of the alarms generated from the analogue measurements. Note: In factory default configuration Digital Output 1 (terminal 51) is the START FAILURE OUTPUT. In factory default configuration Digital Output 2 (terminal 52) is the STOP FAILURE OUTPUT. 5.4.3 REF 4 (terminal 50) Common reference for all output relays terminals 51 to 62. 5.5 Control Relays Nr. Description Type Rating Remark 1 Engine Stop 2 Engine Stop Energized to stop 3 Run/ Stop Solenoid Energized to run or 4 Run/ Stop Solenoid energized to stop 1A 24V DC / 6A Cable monitoring Note: Cable break monitoring: Cable break monitoring is required for the stop solenoid output. The nominal voltage for this output is 24V DC, 6A current when activated. 5.5.1 Engine Stop Output (terminal 64 and 65) Terminals 64 and 65 are a normally open contact. This output will be activated for the stop procedure until the stop time has expired (energized to stop). The output is activated both for normal stops and shutdowns. It is active in parallel with the stop solenoid relay. Purpose of this output is to give a potential free signal to the shut. The relay is normally de-energized Revision: 23-04-2012 Page 23

5.5.2 Run/ Stop Solenoid (terminal 66 and 67) This output can be configured for control of the fuel valve (run solenoid) or stop solenoid. Output configured for control of stop solenoid In this case terminals 66 and 67 are the output for control of the stop solenoid. This output will be activated for the stop procedure until the stop time has expired (energized to stop) or (in case magnetic pick up is used for speed detection) until the engine speed is down to 10rpm (value depending on what is practical), both for normal stops and shutdowns. The relay is normally de-energized. This output includes cable monitoring for the stop solenoid. Note: The RUN/STOP solenoid can only be used with 24V DC. This can be either the same supply as for the controller or a separate power supply. Please observe correct polarity when connecting the fuel valve. When deactivated there will be a current of 5mA on this output due to the cable monitoring circuit inside the M2500. Note: The coil connected to this output must require a current > 5mA for activating. Otherwise the stop solenoid could be activated by the cable monitoring circuit. This is especially important in case the stop solenoid is not activated directly by the M2500 output but by an intermediate relay, that typically requires a much lower current to activate than the stop solenoid. The cable monitoring on this output can be disabled in the configuration, however the 5mA limit still applies. In case the connection to the stop solenoid is lost and cable monitoring is enabled an alarm will be activated. Revision: 23-04-2012 Page 24

Output configured for control of run solenoid (fuel valve) In this case terminals 66 and 67 are a normally open contact for control of the fuel valve. This output will be activated during start and operation of the engine (energized to run). For engine stop the output will be de-activated. The relay is normally de-energized. This output includes cable monitoring for the run solenoid. Note: Please note that this output can only be used with 24V DC. This can be either the same supply as for the controller or a separate power supply. Please observe correct polarity when connecting the fuel valve. When deactivated there will be a current of 5mA on this output due to the cable monitoring circuit inside the M2500. Note: The coil connected to this output must require a current > 5mA for activating. Otherwise the fuel valve could be activated by the cable monitoring circuit. This is especially important in case the fuel valve is not activated directly by the M2500 output but by an intermediate relay, that typically requires a much lower current to activate than the fuel valve. The cable monitoring on this output can be disabled in the configuration, however even then the 5mA limit still applies. In case the connection to the fuel valve is lost and cable monitoring is enabled an alarm will be activated. Revision: 23-04-2012 Page 25

5.6 Siren Relay Nr. Description Type Rating 68 ND Relay contact in de-energized position 1A 69 REF 5 Reference contact of alarm relay 1A 70 NE Relay contact in energized position 1A The siren relay is typically used for connection of a siren. It is normally energized. It will de-energize with any new alarm or shut-down. After pressing RESET the alarm relay will energize again. 5.6.1 Connection of the Siren Relay In below example the siren will activate with any new incoming alarm or shutdown. Revision: 23-04-2012 Page 26

6 Communication 6.1 CAN J1939 Bus The M2500 can communicate directly with the engine ECU by CAN bus, SAE J1939 for a maximum distance 250m. 6.1.1 CAN J1939 Connector: Pin 1: Pin 2: Pin 3: CAN H CAN L CAN COM The CAN J1939 is to be terminated on both ends with a 120Ω resistor. 6.1.2 CAN cable Unshielded twisted pair 2 x 2 x 0,22... 2 x 2 x 0,5 (e.g. Lapp Kabel UNITRONIC, BUS CAN UL/CSA (CMX), part number 2170267). One pair is to be used for CAN H and CAN L, one wire of the remaining pair is to be used for CAN com. Revision: 23-04-2012 Page 27

6.1.3 RS485 MODBUS M2500 includes an RS485 interface MODBUS RTU communication. RS485 Connector: Pin 1: Pin 2: Pin 3: RS485 A RS485 B RS485 COM The RS485 Modbus is to be terminated on both ends with a 120Ω resistor. 6.1.4 RS485 cable Unshielded twisted pair 2 x 2 x 0,22... 2 x 2 x 0,5 (e.g. Lapp Kabel UNITRONIC, BUS CAN UL/CSA (CMX), part number 2170267). One pair is to be used for RS485 A and RS485 B, one wire of the remaining pair is to be used for RS485 com. Revision: 23-04-2012 Page 28

7 Functional Description 7.1 Remote Mode In remote mode (terminal 5 connected to com) Start and stop is only available from the REMOTE START (terminal 08) and REMOTE STOP (terminal 09) terminals. Provided the engine is ready for remote start (Not Ready LED on the front panel of M2500 is off) the start procedure works as follows: Remote Start flowchart: Lube pump according config Ready for remote start Engine ready for REMOTE START Remote Start Command NO YES Start Warning Fuel Valve on Start Delay NO Cranking Fuel Valve on Cranking Rest Time Engine running? YES NO NO All start attempts completed? YES Start Fail Not ready Lube Pump C/B Trip Air Intake Common Alarm Engine Stop Stop Solenoid Alarm Relay Run Fuel Vanve Survey Delay YES Run Fuel Vanve Engine Running Revision: 23-04-2012 Page 29

Remote Stop flowchart: Run Fuel Vanve Engine Running Remote Stop Command NO YES Run Fuel Vanve C/B Trip Cool Down Cool Down Run Cool Down Time expired? NO Engine Stop Stop Solenoid Stop Procedure Stop Time expired? NO YES Engine stopped? YES NO Stop Fail Not ready Run Fuel Valve Ready Lube Pump according config Engine stopped and ready for start Revision: 23-04-2012 Page 30

7.2 Alarm Monitoring The alarm monitoring is always active regardless of Local or remote mode. Note: Alarms are abnormal conditions that will be indicated and logged by the M2500, but they will not stop the engine. Alarms can be set to continuous monitoring (regardless if the engine is running or not) or conditional monitoring (only monitored if the engine is running). An individual programmable time delay is available for each alarm. A new incoming alarm will always shift the M2500 display to the Current Alarm display. At the same time the Alarm LED on the front panel will be fast flashing, the common alarm output (terminal 46) will activate and the Siren Relay (terminals 68, 69 and 70) will de-energize. Depending on the configuration it is possible to activate one or more of the digital outputs. The common alarm output will de-activate for 2s and re-activate when a new alarm appear. The siren relay (terminals 68, 69 and 70) will de-activate for 2s and re-activate when a new alarm appear. After accepting an alarm (by pressing the Reset button or external reset terminal 12) the common alarm LED will change to steady light, the common alarm output and the optional digital output will remain active, provided the alarm is still present on the input. The siren relay will energize again after pressing Siren Reset or Reset button or external reset terminal 12. When the all alarms disappear from the inputs and alarms have been acknowledged, the common alarm LED will switch off, the common alarm output and the optional digital outputs will deactivate. Revision: 23-04-2012 Page 31

7.2.1 Alarm flowchart: Run Fuel Vanve Engine Running Alarm input activated? NO Override activated AND Alarm marked for override? NO YES NO Alarm marked for blocking? YES Monitoring delay expired? Running Fuel Valve Not Ready Common Alarm Alarm Relay deenergized until Reset Alarm Procedure YES Revision: 23-04-2012 Page 32

7.3 Shutdown Monitoring The shutdown monitoring is always active regardless of Local or remote mode. Note: Shutdowns are abnormal conditions that will be indicated and logged by the M2500 and they will stop the engine. Shutdowns can be set to continuous monitoring (regardless if the engine is running or not) or conditional monitoring (only monitored if the engine is running). An individual programmable time delay is available for each shutdown. A new incoming shutdown will always shift the M2500 display to the Current Alarm display. At the same time the shutdown LED on the front panel will be fast flashing, the common shutdown output (terminal 46) will activate and the Siren Relay (terminals 68, 69 and 70) will de-energize. Depending on the configuration it is possible to activate one or more of the digital outputs. Note: A shutdown will block the engine for start until it has been reset and the shutdown signal has disappeared. After accepting a shutdown (by pressing the ACK button or external reset terminal 12) the Common shutdown LED will change to steady light. The shutdown output and the optional digital output will remain active provided the shutdown is still active on the input. The siren relay will energize again. Revision: 23-04-2012 Page 33

7.3.1 Shutdown flowchart: Run Fuel Vanve Engine Running Shut Down input activated? NO Override activated AND Shutdown marked for override? NO YES NO Shutdown marked for blocking? YES Monitoring delay expired? Not Ready C/B trip Air Intake Common Alarm Shut Down Engine Stop Stop Solenoid Alarm Relay deenergized until Reset Shut Down Procedure YES Stop Time expired? NO YES Engine stopped? NO Stop Fail Not ready YES Not Ready Lube Pump according config Common Alarm Shut Down Engine stopped and blocked for start NO Reset? YES Shutdown still active and marked for continuous monitoring? Engine ready for AUTO START Revision: 23-04-2012 Page 34

7.4 Specification Environmental conditions: Operating temperature: -15 C to +70 C Humidity: 95% Vibration: DNV vibrations class B EMC: IEC 60945 Enclosure: IP44 (panel front only) Supply: Primary Supply: Backup Supply: Pick Up Input: Connection: Type: switch. Rated frequency Sensor inputs: +24 V DC (-30 % / +30 %) Isolated, 500mA +24 V DC (-30 % / +30 %) Isolated, 500mA Screw terminals Magnetic (2-wire), NPN and PNP (3-wire), configurable via DIP 40.0 to 10000 Hz 9 Digital inputs: Normally open contacts to COM (default) or normally closed contacts to COM. Optional cable monitoring (short circuit and cable break). 8 Analogue inputs: 4-20mA -, with optional cable monitoring. Mode / Control inputs: Connection: Screw terminals (2,5mm 2 ) Activation: Connect to COM All relays (except where otherwise specified): Relay response time: Contact set(s) Contact rating: Function: Run/ Stop Solenoid relay: Relay response time: Contact set(s) Contact rating: Function: System fault output relay (Siren): Relay response time: Contact set(s) Contact rating: Function: 20 ms (worst case) 1 normally open AC: 1 A, 250 V AC, DC: 1 A, 35 V DC Normally de-energized. 20 ms (worst case) 1 normally open AC: 8 A, 250 V AC, DC: 8 A, 35 V DC Normally de-energized (Default) or normally energized Cable monitoring (cable break and short circuit). 20 ms (worst case) 1 change over AC: 1 A, 250 V AC, DC: 1 A, 35 V DC Normally energized. Revision: 23-04-2012 Page 35

SAE J1939, CAN Bus: Connection: Distance: Protocol: Speed: Termination: Screw terminal connector, 3-wire with COM (Isolated) Max. 40m SAE J1939 250Kbit/s 120 ohm termination RS485, Modbus: Connection: Distance: Protocol: Speed: Termination: USB: Connection: Screw terminal connector, 3-wire with COM (Isolated) Max. 500m Modbus RTU 19200 bit/s 120 ohm termination USB type B socket (Female connector), USB 2.0 Full speed Device, Mass storage device for configuration, inspection of log files and other diagnostics information. Revision: 23-04-2012 Page 36