Multiplex Eight Input Remote Modules

Similar documents
DS7465i. Installation Instructions. Input/Output Module

D7052. Installation Instructions Multiplex Dual Input Module

D7044. Installation Instructions Multiplex Single Input Module

FMR Installation Instructions. Addressable Fire System Controller

D7053. Installation Instructions Multiplex Input/Output Module

F220-B6PS/M. Installation Guide. Addressable Detector Bases

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

Addressable NAC Output Module D327A

Remote NAC Power Supply D7038

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Notification Appliance Circuit Module

Duct smoke housing, 2-wire D340/D340P

D8125MUX. Operation and Installation Guide. Multiplex Bus Interface

D250A/D253/D261AW/D280A/D290 Series

Fire Alarm Control/Communicator

D7024 Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

D343. Installation Instructions. Air Duct Smoke Housing

DS7400Xi Addressable Control/ Communicator

Battery charger modules

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

Control Panels D9412GV4/D7412GV4/D7212GV4. Approved Applications Compliance Guide

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

Fire Alarm Control Panels FPD-7024

IDP-Zone-6 Six Zone Interface Module

These instructions detail procedures to follow in order to avoid damage to equipment.

FireNET Plus Wiring Instructions

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Control Panel. D9412GV4/D7412GV4 v2.00. en UL Installation Instructions

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

DS160/161 Request To Exit PIR sensors Installation Instructions

Microwave/PIR Intrusion Detector with POPIT Interface ZX970

MMF Six Zone Interface Module

ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector

Installation, Operating and Maintenance Manual

Model 17A00 Expansion Enclosure

Easy Series ICP-EZM2. System Reference Guide

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Operation and Installation Guide. Zone Expansion Module D8125

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

AL600ULADA. NAC Power Extender. Installation Guide

Operation and Installation Guide. Fire Alarm Control Panel

D1255RB/D1256RB/D1257RB

TECHNICAL DATA OBSOLETE

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

MANUAL RESET ALARM RELEASE

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

FW-RA-LED Remote Multiplex Annunciator Panels

DS160/DS161 Request To Exit PIR sensors Installation Instructions

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

30.45 Electric Release PDRP-2001

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Installation Instructions Model HZM

MO144. Operators Guide. Universal Timer Module

Reference Guide for the DS7400Xi (Version 3+) Control/Communicator

AL800ULADA. NAC Power Extender. Installation Guide

Addressable Fire Alarm Control Panel

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

General Routing Interface

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Conventional Releasing Control Panel

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

June 10, 2002 DF C S2424

Installation Instructions Model DLC

MANUAL RESET ALARM RELEASE BOX

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

Bosch EVAX System - High-rise Applications

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

ANNUNCIATOR FIXED MODULE

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

Installation Guide for models:

INTELLIGENT FIRE ALARM CONTROL PANEL

Conventional Fire Alarm System 2014 V1.2

Photo Beam 5000/3000 Series Heater. en Installation Guide

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

D720 and D1255 Command Centers

RA-1000 Series. Remote Multiplex Annunciator Panels. Installation and Wiring Manual

Multiple Input and Output Modules

MGD-32 and AGD-048. Remote Multiplex Graphic Driver Annunciators and Adder Boards. Wiring and Installation Manual

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

CZ-6A Six Zone Interface Module

Transcription:

Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control Panel (FACP). Install, test and maintain the D7042/D7042B Eight Input Remote Modules according to their instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction. Failure to follow these instructions may result in failure of the device to operate properly. Bosch is not responsible for improperly installed, tested or maintained devices. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. 2.0 Device Description The D7042/D7042B is an Eight Input Remote Module that provides a means of addressing up to eight input loops of conventional contacts to the multiplex bus of the control panel. It is suitable for use with the FPD-7024 Fire Alarm Control Panel (FACP) with ROM version 2.0 or greater using a D7039 Multiplex Expansion Module. Up to 30 D7042/ D7042B modules can be supported per FACP. e D7039 Multiplex Expansion Module is required in the system to use the D7042/D7042B Eight Input Remote Modules. 3.0 Installing the D7042/D7042B 3.1 Mounting the D7042 Use the mounting holes (upper left and lower right corners) to mount the D7042. The D7042 normally is mounted outside of the FACP enclosure. Mounting Hole Mounting Hole Rear Wire Entrance Surface Wire Entrance Figure 1: Mounting the D7042

3.2 Mounting the D7042B The D7042B will come partially preassembled with the circuit board attached to the mounting skirt. Select a mounting location for the D7042B. Using the enclosure as a template, mark the mounting holes on the mounting surface and make an opening for the unit s wiring. Mounting Holes Attach Mounting Skirt Here Figure 2: Mounting the D7042B Next, attach the mounting skirt if applicable (with the circuit board attached) to the enclosure (hardware provided). Then complete all wiring (see Section 4.0). ce installation and wiring is completed, attach the enclosure cover and secure with the screws (provided). Be sure all wiring is unpowered before routing. Do not use shielded or twisted pair cable. Refer to the D7039 Installation Guide (P/N: 38685) for multiplex wiring requirements. The length of the wire connected to the loop inputs on the D7042/D7042B must be less than 250 ft. (76 m) per loop. Route wiring as necessary from the D7039 in the FACP enclosure and from remote devices to the D7042/D7042B. If the wiring is to run along the surface of the enclosure, open the D7042/D7042B surface wire entrance. See Figure 2. D7042/D7042B F01U262014-01 Page 2 2011 Bosch Security Systems, Inc.

4.0 Wiring Locking tab P3 Tamper Switch DIP switch P2 + + 1 2 3 4 5 6 7 8 POWER BUS Rear Wire Entrance Surface Wire Entrance Figure 3: D7042/D7042B Front View without Cover Since NFPA 72 does not allow redundant/duplicate ground paths, do not connect wiring to the BUS (-) terminal on this module for fire applications. ly the BUS (+) needs to be connected. P2 When used with a D7039, power is connected to the option bus power terminals (RA or RB (+), BA or BB (-)). Connection to 24 VDC sources will damage the D7042/D7042B. + POWER + BUS 1 2 3 4 5 6 7 8 To D7024 Option Bus RA (or RB) terminal To D7024 Option Bus BA (or BB) terminal To D7039 MUX bus terminal 47 k ohm resistors 47 k ohm resistors EOL P/N: 28010 47 k ohm resistors 47 k ohm resistors Figure 4: Wiring the D7042/D7042B D7042/D7042B 2011 Bosch Security Systems, Inc. Page 3 F01U262014-01

DS9400 FACP DS9431Multiplex Expansion Module 1 2 3 4 5 6 7 8 9 Clear * Power Alarm 0Prog # Cmnd Trouble Silenced Drill Disable Test History Silence Reset SMK+ SMK- AUX+ AUX- 4- L+ 3-2- L+ 1- Power + may be connected to RA or RB on the FACP Option Bus terminal strip. Power - may be connected to BA or BB on the FACP Option Bus. DS7432 Eight Input Remote Module 24V Smoke Power (+) 24V Smoke Power (-) 12V Power (-) 12V Power (+) + + 1 23 45 67 8 POWER BUS I/O Module for the DS9431 Multiplex Expansion Module Smoke Detector Example: DS250 in a MB4W base Bus + and Bus - are connected to MUX A terminals for addresses 9-128. MUX B terminals are for addresses 129-255. Bus (+) EOL Resistor P/N: 28010 NFPA 72 does not allow redundant/duplicate ground paths, do not connect wiring to the BUS (-) terminal on this module for fire applications. ly the BUS (+) needs to be connected. Smoke Detector EOL Relay Example: EOL200 Figure 5: Wiring Four-wire Smoke Detectors D7042/D7042B F01U262014-01 Page 4 2011 Bosch Security Systems, Inc.

5.0 Programming the D7042/D7042B Refer to the programming section of the D7024 Reference Guide (P/N: 31499) for point programming information. The D7042/D7042B occupies eight multiplex point addresses when connected to the control panel. 6.0 Setting the Jumpers and DIP Switches 6.1 D7042 Jumper Settings P2 of the D7042/D7042B allows the tamper switch to be bypassed with a jumper when testing or servicing. Remove the jumper on P2 when testing or servicing has been completed. 6.2 D7042/D7042B DIP Switch Settings The DIP switches select which points will be activated by the loop inputs. Set the DIP switches as shown in Table 1. No two D7042/D7042B DIP Switch settings should be the same. The D7042/D7042B occupies eight points when connected to the FACP. The input loops of the D7042/D7042B correspond to the points of the FACP as shown in Table 2. Figure 6 shows the DIP switch positions for on and off settings. Figure 6: D7042/D7042B DIP Switch D7042/D7042B 2011 Bosch Security Systems, Inc. Page 5 F01U262014-01

DIP Switches 1 2 3 4 5 9-16 17-24 25-32 33-40 41-48 49-56 57-64 65-72 73-80 81-88 89-96 97-104 105-112 113-120 121-128 129-136 137-144 145-152 153-160 161-168 169-176 177-184 185-192 193-200 201-208 209-216 217-224 225-232 233-240 241-248 Table 1: D7042/D7042B DIP Switch Settings D7042/D7042B F01U262014-01 Page 6 2011 Bosch Security Systems, Inc.

Point Number D7042/D7042B Input Loop 1 2 3 4 5 6 7 8 9-16 9 10 11 12 13 14 15 16 17-24 17 18 19 20 21 22 23 24 25-32 25 26 27 28 29 30 31 32 33-40 33 34 35 36 37 38 39 40 41-48 41 42 43 44 45 46 47 48 49-56 49 50 51 52 53 54 55 56 57-64 57 58 59 60 61 62 63 64 65-72 65 66 67 68 68 70 71 72 73-80 73 74 75 76 77 78 79 80 81-88 81 82 83 84 85 86 87 88 89-96 89 90 91 92 93 94 95 96 97-104 97 98 99 100 101 102 103 104 105-112 105 106 107 108 109 110 111 112 113-120 113 114 115 116 117 118 119 120 121-128 121 122 123 124 125 126 127 128 129-136 129 130 131 132 133 134 135 136 137-144 137 138 139 140 141 142 143 144 145-152 145 146 147 148 149 150 151 152 153-160 153 154 155 156 157 1158 159 160 161-168 161 162 163 164 165 166 167 168 169-176 169 170 171 172 173 174 175 176 177-184 177 178 179 180 181 182 183 184 185-192 185 186 187 188 189 190 191 192 193-200 193 194 195 196 197 198 199 200 201-208 201 202 203 204 205 206 207 208 209-216 209 210 211 212 213 214 215 216 217-224 217 218 219 220 221 222 223 224 225-232 225 226 227 228 229 230 231 232 233-240 233 234 235 236 237 238 239 240 241-248 241 242 243 244 245 246 247 248 Table 2: Loop/Point Number Relationship D7042/D7042B 2011 Bosch Security Systems, Inc. Page 7 F01U262014-01

7.0 Specifications D7042/D7042B Current Draw (from option bus power) Current Draw (from multiplex bus loop) Total Current Draw for Battery Standby Calculation and Alarm Min. Bus Operating Voltage 8 ma Standby and Alarm 10 ma Standby and Alarm 18 ma Standby and Alarm 8 VDC peak Multiplex Bus Wiring Refer to the D 7039 Installation Guide (P/N: 38685) Local Alarm Loop Wiring 250 ft. (76.2 m) max.; #18 AWG (1.2 mm) minimum O perating Temperature Range +32 F to +120 F (+0 C to +49 C) 2011 Bosch Security Systems, Inc. 130 Perinton Parkway, Fairport, New York, USA 14450-9199 D7042/D7042B F01U262014-01 12/11 Page 8 of 8