VTC / VTH PRODUCT SPECIFICATIONS. ¾ Ton through 2 Tons VERTICAL TERMINAL AIR CONDITIONER AND HEAT PUMP

Similar documents
SPXA / SPXA-HP Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

SPXB / SPXB-HP Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

SPXR-A / SPXR-HP-A Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

SPXB-HW Series Single Package Vertical Unit Cooling with Hot Water Heat 1 through 2 tons, up to 47,800 BTUH Heating

PTAC Air Conditioners 11.7 EER / 3.4 COP. and Heat Pumps

PTAC Air Conditioners 11.7 EER / 3.4 COP. and Heat Pumps

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

Applied Packaged Terminal Air Conditioner with Catalog Top-Mounted Hydronic Heat

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

RTG Ultron. Up to 16 SEER. Specification Sheet. Split System Heat Pump

Series PIN. New Construction or Renovation. Application Flexible Quiet Comfort Damage Protection

Compak Unit Coolers. LCA - Air Defrost LCE - Electric Defrost LCH - Hot Gas Defrost. Bulletin LC-03A August 2004 (Replaces LC-03 3/03)

PRODUCT SPECIFICATIONS

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

Incremental Comfort Conditioners

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTION

PAR5. Product Specifications

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

TECHNICAL SPECIFICATIONS

High Heat COP. High/Low Stage

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

AP- Series AeroPak Thru-The-Wall (Modular) Package Units Electric Cooling / Electric Heat Electric Cooling / Gas Heat Heat Pump / Electric Heat

Series PIC. New Construction and Renovation; Replaces RetroAire VPAC and First Company DPU Application Flexible Quiet Comfort Damage Protection

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

PC SERIES 50 Hertz PRODUCT SPECIFICATIONS. Self-Contained Packaged Air Conditioners. 4 and 5 Ton [14.1 kw to 17.6 kw]

PAJ3. Product Specifications

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

WLCG/WLHG. Specifications and Performance WLCG/WLHG. (with EMI AmericaSeries condensers)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 60 HZ MODELS: EF-10 & FF-10

Vert-I-Pak Series. Single Package Vertical Air Conditioners. Installs easily in a closet for quiet operation THE EXPERTS IN ROOM AIR CONDITIONING

Concealed Ducted Split Series R-407C MBH

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

SKYPAK II Heating & Cooling Self Contained Packages

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

ACNF Series. Ceiling-Mount Air Handlers 1½ to 2½ Tons

Commercial High-Efficiency Condensing Units

Installation and Start-Up Instructions

McQuay Suite Type N Top Mounted Hydronic Heat Incremental Packaged Terminal Air Conditioners C:

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

PACKAGE AIR CONDITIONER

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

TECHNICAL SPECIFICATIONS

Enviromaster International LLC 5780 Success Dr. Rome, NY Nominal Capacities: 30,000-36,000 Btuh

MACH N-407 Heat Pump Air-Cooled Chiller

1 to 5 Ton Vertical Wall Mount Air Conditioners Models AVPA

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Zoneline vertical packaged terminal air conditioners

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

Single Package Vertical Air Conditioners. Vert-I-Pak

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

GE Zoneline. vertical packaged terminal air conditioners Home Products and Services

R21C Packaged Terminal Air Conditioner (PTAC) Specifications and Performance. The Right Fit for Comfort R21C. Straight Cooling Nominal Capacities

TECHNICAL SPECIFICATIONS

Product Specifications. Vertical Floor Consoles By First Co.

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

Commercial High-Efficiency Condensing Units

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

E Z S E R I E S " W X 16" H

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

Specifications and Performance

Q-Tec TM QC-Series Chilled Water Air Conditioner

9 EER 1-5 Ton Vertical Packaged Wall Mount Air Conditioners

AE/AH R410A Window Air Conditioners & Heat Pumps

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

TECHNICAL SPECIFICATIONS

GUIDE SPECIFICATIONS AQUARIUS ii

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Specifications and Performance

WJH4 Product Specifications

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

AEPF. 1½ to 5 Tons. Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Wiring Diagram... 6 Accessories... 7

SKYPAK II, 3 Ton Series, gives you a

General Description. Operation

R22C/H Packaged Terminal Air Conditioner (PTAC) Specifications and Performance. The Right Fit for Comfort

LIFTAIRE II ELEVATOR AIR CONDITIONER

Q-TEC QC-Series Chilled Water Air Conditioner

ARPT Series. Multi-Position. 2 to 5 Tons. Internal TXV, Multi-Speed PSC Motor

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

50TM COMBINATION HEATING/COOLING UNITS

Advance Release September 2009

ACNF Series. Ceiling-Mounted Air Handlers 1½ to 2½ Tons

PACKAGED TERMINAL AIR CONDITIONER SOLUTIONS. New Construction Model. Model EGN Superior Sound Performance. High Efficiency

Model 655A Sizes

AC, HP and Air Handler Units Up to 20 Tons. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

Transcription:

VTC / VTH VERTICAL TERMINAL AIR CONDITIONER AND HEAT PUMP PRODUCT SPECIFICATIONS No other unit in the industry offers so many extras already built in as standard on every unit. Don t settle for anything less than the Amana brand Standard Ad van tage! Evaporator Coil Freeze Pro tec tion Compressor Restart Delay Low Ambient Lock-out Manual Outside Air Damper Wall-mount Thermostat Electrical Disconnect Random Unit Restart Front Desk Control Fan On/Off Delay High-efficiency Operation Quiet Operation Reliability and Durability COOLING: 8,350-23,800 BTU/H HEAT PUMP: 8,120-22,800 BTU/H ¾ Ton through 2 Tons ELECTRIC HEAT: 5,100-34,100 BTU/H UP TO 3.5 COP SS-VTAC www.goodmanmfg.com 5/08 Supersedes 12/07

FEATURES Front Desk Control Enable or disable each unit from the front desk to save energy used to con di tion unoccupied rooms. Fan Delay Allows the evaporator blower to con tin ue running for up to 45 sec. after the ther mo stat is satisfied, maximizing cooling performance. Random Restart Protects against damage to electrical circuits by preventing all units from starting at one time after power disruption. Random restart occurs in 3 to 4 min. Evaporator Coil Freeze Protection Prevents ice build-up on coils and compressor damage during the cooling mode. Attached to the coil, a temperature sensor will de-energize the compressor when freezing conditions are detected and re-energize the compressor when the coil warms up again. Ductable Return Air Permits the con nec tion of return air ductwork using the provided tabs (usually not required) on the inlet of the evap o ra tor coil. (Figure 5, pg. 9) Note: Duct systems and registered sizes must be properly designed for the CFM and external static pressure rating of the unit. Adjustable Outside Air (manual) Meets code re quire ments for outside air introduction. The air vent (Figure 6, pg. 9) allows up to 50 CFM of outside air to be introduced into the equipment closet. The air mixes with return air entering the closet through the return air grille. Note: Negative pressure can be introduced through an external source to raise the 50 CFM level. Consult with the factory. Compressor Restart Delay (3 min.) Ensures that system pressure equalizes before the system restarts, so compressor life is extended. Low Ambient Lockout Locks out compressor at 40ºF and below, thus extending compressor life. Electrical Dis con nect (Factory-installed) Makes service and maintenance easier. Filter Brackets (Field-installed) Installed over evaporator coil and shipped with throw-away filter (20 x 24 x 1 ; see Figure 5, pg. 9). Unique Sleeve Drain Condensate System (Factory-installed) Connects evaporator drain pan to a vertical pipe connection in the unit s base pan via a drain line. Evaporator condensate is delivered from the unit to a catch tray in the wall sleeve and exits the sleeve through the ¾ male NPT fitting to allow complete piping of the drain to a condensate riser during the rough-in stage. This eliminates condensate connection problems when connecting the HVAC drain to the riser after the HVAC unit is installed in the closet. Unit can be removed for service without disconnecting the condensate piping. Additional closet space is not needed to connect the drain. Secondary Overflow Should the primary condensate riser become clogged, water will fill the catch tray and be diverted through the sleeve to the exterior of the building, ensuring no leakage into the interior area. Rain water entering the sleeve is automatically diverted to the building exterior. NOMENCLATURE VT C 09 1,2 3 4,5 3 B 03 6 7 8,9 A 10 A 11 Product Category Engineering V Vertical Package Revisions Terminal Unit Option Code Model Type A Standard Model C Air Conditioner H Hot Water Model H Heat Pump Electric Heat 230v-208v Models System Cooling Capacity 00 0.0 KW 05 5.0 kw 09 9,000 BTU/h 02 2.0 KW 06 6.0 kw 12 12,000 BTU/h 03 3.0 kw 08 8.0 kw 18 18,000 BTU/h 04 4.0 kw 10 10 kw 24 24,000 BTU/h Hot Water Models (H) 0A 2-row coil 0B 3-row coil Voltage Design Series 3 230/208v-60 Hz-1 Ph A Unit manufactured prior to 01/2006 B Unit meets 2006 DOE requirement 2 www.goodmanmfg.com SS-VTAC

VTC MODEL SPECIFICATIONS COOLING/ELECTRIC HEAT ELECTRICAL DATA (208/240V-1 PH-60HZ) Model kw Electric Heat Data Blower Data Condenser Data Minimum Total Heating Evaporator Condenser Circuit BTU/h Compressor Amps Motor Motor Ampacity Maximum Circuit Protection 240V 208V 240V 208V 240V 208V AMPS HP RLA LRA FLA HP 208V 230V 208V 230V VTC093B-0 0 0.0 0.0 0.0 0.0 0.0 7 7 15 15 VTC093B-2 2 1.5 6,800 5,100 9.0 7.9 10 12 15 15 0.72 1/8 3.7 21 0.5 1/15 VTC09EB-3 3 2.25 10,200 7,700 13.2 11.5 15 18 20 20 VTC093B-4 4 3.0 13,600 10,200 17.4 15.1 19 23 20 25 VTC123B-0 0 0.0 0.0 0.0 0.0 0.0 10 10 15 15 VTC123B-2 2 1.5 6,800 5,100 9.0 7.9 10 12 15 15 VTC123B-3 3 2.25 10,200 7,700 13.2 11.5 0.72 1/8 5.0 24 0.5 1/15 15 18 20 20 VTC123B-4 4 3.0 13,600 10,200 17.4 15.1 19 23 20 25 VTC123B-5 5 3.75 17,000 12,800 22.0 19.0 24 28 25 30 VTC183B-0 0 0.0 0.0 0.0 0.0 0.0 13 13 15 15 VTC183B-2 2 1.5 6,800 5,100 9.2 8.1 13 13 15 15 VTC183B-3 3 2.25 10,200 7,700 13.4 11.7 15 18 20 20 VTC183B-4 4 3.0 13,600 10,200 17.5 15.3 19 23 25 25 0.87 1/8 9.0 48 0.72 1/10 VTC183B-5 5 3.75 17,000 12,800 22.0 19.0 24 28 25 30 VTC183B-6 6 4.5 20,500 15,350 26.0 23.0 28 34 30 35 VTC183B-8 8 6.0 27,300 20,500 34.0 30.0 37 44 40 45 VTC183B-10 10 7.5 34,100 25,600 43.0 37.0 47 54 50 60 VTC243B-0 0 0.0 0.0 0.0 0.0 0.0 18 18 20 20 VTC243B-3 3 2.25 10,200 7,700 14.0 12.3 18 18 20 20 VTC243B-4 4 3.0 13,600 10,200 18.2 15.9 21 24 25 25 VTC243B-5 5 3.75 17,000 12,800 22.0 20.0 1.4 1/4 10.5 61 2.3 1/4 26 28 30 30 VTC243B-6 6 4.5 20,500 15,350 27.0 23.0 30 34 35 35 VTC243B-8 8 6.0 27,300 20,500 35.0 30.0 39 45 45 50 VTC243B-10 10 7.5 34,100 25,600 43.0 38.0 48 55 50 60 Ship Weight 245 245 255 255 COOLING PERFORMANCE DATA Model Standard Ratings 1 BTU/h EER VTC093B 8,350 9.3 VTC123B 11,500 9.6 VTC183B 18,900 9.7 VTC243B 23,100 9.1 ¹ Tested in accordance with ARI Standard 310/380-93 at 95 F DB/75 F WB outdoors and 80 F DB/67 F WB indoors. SS-VTAC www.goodmanmfg.com 3

VTC MODEL SPECIFICATIONS COOLING/ELECTRIC HEAT (CONT.) BLOWER DATA Model Motor Speed1 Connection CFM vs. External Static Pressure 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 VTC093B VTC123B VTC183B VTC243B High 490 475 460 450 435 420 400 --- Med 375 360 350 340 330 315 300 --- Low 290 280 270 260 240 230 215 --- High 490 475 460 450 435 420 400 --- Med 375 360 350 340 330 315 300 --- Low 290 280 270 260 240 230 215 --- High 660 655 650 645 640 635 625 610 Med 580 578 575 570 565 560 550 540 Low 485 480 475 470 465 460 455 450 High 1,030 1,000 980 950 920 890 860 820 Med 880 860 840 820 790 760 730 710 Low 770 760 750 740 720 700 680 660 Notes: (1) VTC12, 18- and 24-blower motors are factory-wired for medium (cooling) and low (heating) fan operation. VTC09 is low speed for both. (2) VTH12, 18- and 24-blower motors are factory-wired for medium (cooling/heat pump) and low (electric heat) speed operation. VTH09 is low speed in all modes. DIMENSIONAL DATA VTC/VTH Unit *See Wall Sleeve Installation In struc tions for complete details. "P" Trap Is shown for illustration purposes only. It may not be required by local codes. 4 www.goodmanmfg.com SS-VTAC

VTH MODEL SPECIFICATIONS COOLING/ELECTRIC HEAT ELECTRICAL DATA (208/240V-1 PH-60HZ) VTH243B VTH183B VTH123B VTH093B Model kw Electric Heat Data Blower Data Condenser Data Total Evaporator Compressor BTU/h Heating Motor Motor Amps Minimum Circuit Ampacity Maximum Circuit Protection 240V 208V 240V 208V 240V 208V AMPS HP RLA LRA FLA HP 208V 230V 208V 230V 2 1.5 6800 5,100 9.0 7.9 10 12 15 15 3 2.25 10,200 7,700 13.2 11.5 0.72 1/8 3.7 21 0.5 1/15 15 18 20 20 4 3.0 13,600 10,200 17.4 15.1 19 23 20 25 2 1.5 6800 5,100 9.0 7.9 10 12 15 15 3 2.25 10,200 7,700 13.2 11.5 15 18 20 20 0.72 1/8 5.0 24 0.5 1/15 4 3.0 13,600 10,200 17.4 15.1 19 23 20 25 5 3.75 17,000 12,800 22.0 19.0 24 28 25 30 2 1.5 6,800 5,100 9.2 8.1 13 13 15 15 3 2.25 10,200 7,700 13.4 11.7 15 18 20 20 4 3.0 13,600 10,200 17.5 15.3 19 23 25 25 5 3.75 17,000 12,800 22.0 19.0 0.87 1/8 9.0 48 0.72 1/10 24 28 25 30 6 4.5 20,500 15,350 26.0 23.0 28 34 30 35 8 6.0 27,300 20,500 34.0 30.0 37 44 40 45 10 7.5 34,100 25,600 43.0 37.0 47 54 50 60 3 2.25 10,200 7,700 14.0 12.3 18 18 20 20 4 3.0 13,600 10,200 18.2 15.9 21 24 25 25 5 3.75 17,000 12,800 22.0 20.0 26 28 30 30 1.4 1/4 10.5 61 2.3 1/4 6 4.5 20,500 15,350 27.0 23.0 30 34 35 35 8 6.0 27,300 20,500 35.0 30.0 39 45 45 50 10 7.5 34,100 25,600 43.0 38.0 48 55 50 60 Ship Wgt (lbs) 245 245 255 255 IMPORTANT: Heat pump does not operate simultaneously with electric heat. Electrical data in the above table only applies to units manufactured after 8/1/2000 (data code G08). Contact factory for electrical data for units manufactured prior to 8/1/2000. Compressors in these models (after 8/1/2000) do not operate simultaneously with heater elements. Models manufactured before 8/1/2000 (excluding the VTH24-HP) did feature simultaneous operation and therefore had higher circuit ampacities. COOLING PERFORMANCE DATA Model Standard Ratings 1 BTU/h EER VTH093B 8,350 9.3 VTH123B 11,500 9.6 VTH183B 18,900 9.7 VTH243B 23,100 9.1 ¹ Tested in accordance with ARI Standard 310/380-93 at 95 F DB/75 F WB outdoors and 80 F DB/67 F WB indoors. HEATING PERFORMANCE DATA Model BTU/h WATTS COP VTH093B 7,600 795 2.8 VTH123B 10,600 1,001 3.1 VTH183B 16,800 1,582 3.11 VTH243B 23,500 1,967 3.5 1. 47 F DB, 43 F WB Outdoor/70 F DB, 60 F WB Indoor SS-VTAC www.goodmanmfg.com 5

DIMENSIONAL DATA DUCT OPENING (C) 1 A B 10 6-1/8 ELEMENT FILTER BLOWER MOTOR RETURN AIR DISCONNECT 66 CONDENSER OUTLET ELECTRICAL KNOCKOUT 41-1/4 LOW VOLTAGE CONDENSER INLET 20 20 20 A B C VTC/VTH 09, 12, 18 6½ 6½ 6½ x 10 VTC/VTH 24 10 3 10 x 10 6 www.goodmanmfg.com SS-VTAC

ACCESSORIES Wall-mounted Low-voltage Thermostat Easily con trols the unit. Low-voltage wires exit the left side of the cabinet. (pg. 8) UNIT WITH INSTALLED REAR SLEEVE AND FLUSH-STYLE LOUVER Flush Style Architectural Louver Attaches to the outside of the wall sleeve for a flush appearance. Louvers recess into the wall sleeve; stock and custom colors available. (pg. 8) Wall Sleeves Standard 22 width x 44 height. Six sleeves (three rear installation, three side installation) avail able for vary ing wall widths, from 5 to 15. (See chart at right and Figure 7, page 9.) Shipped sep a rate ly to al low in stal la tion dur ing construction, each sleeve in cludes a factory in stalled weather guard to cover the sleeve opening during construction phase. Note: Due to better access to unit, wall sleeves in stalled in the rear application are recommended over side- installed wall sleeves whenever possible. Note: Sleeve, louver, filter, and thermostat required for each general installation. Side Wall Sleeves Model Wall Depth Sleeve Depth SVWS958A 5-8 Walls 26 SVWS9812A 8-12 Walls 30 SVWS91215A 12-15 Walls 33 Note: Side-installed wall sleeves require different closet sizes and configurations (See Page 10). Rear Wall Sleeves Model Wall Depth Sleeve Depth VWS958A 5-8 Walls 26 VWS9812A 8-12 Walls 30 VWS91215A 12-15 Walls 33 Separate wall mounting bracket is shipped with side install wall sleeves Architectural Grilles Available in various colors. Side Install Sleeve AGKV01CB Anodized Aluminum (Clear) AGKV01DB Dark Bronze AGKV01TB Stone Wood AGKV01WB White AGKV01SB Custom Color SS-VTAC www.goodmanmfg.com 7

ACCESSORIES (CONT.) Wall-mounted Low-voltage Thermostat* Easily con trols the unit. Low-voltage wires exit the left side of the cabinet. * Available for straight cool/hy dron ic chassis and heat pump chassis. Unit Mounted Freeze Sensor (UMF01A) De-energizes the unit when reduced air flow or ice build -up are detected. Re-energizes the unit when normal op er at ing conditions resume. Hydronic Flow Control Module (HFC01A)* Regulates the amount of hot water heat to the unit. *Applies to hydronic models only. Optional Access/Return Air Panel Panels are avail able in lou vered or non-louvered and are In su lat ed for sound reduction with tamper-proof screws. Louvered pan el in cludes a 18 x 24 x 1 filter. Non-louvered panels require external return air grilles and unit mount filters. 1246001 1246003 Straight Cool/ Hydronic Chassis Heat Pump Chassis Digital cool - off - heat, auto - on Digital cool - off - heat, auto - on Float Switch (FSE306A)* Opens the condensate pan automatically when water rises in the pan and shuts off the system by breaking low or line volt age cur rent to the compressor. Switch is normally closed. By clipping the float switch to the side of the auxiliary drain pan, ceiling water damage is prevented. In some areas, this switch can replace an auxiliary drain pan. Local building codes should be checked for application. Note: The float switch must be installed before unit is set in the sleeve. *Applies to hydronic models only. Access / Return Air Panel ³ 4 Access/Return Air Panel Dimensions (H x W) Ship Description Part # Frame Opening Wt. Louvered 1 87 X 31 84 X 28 LWP0187 40 Non-Louvered 2 87 X 31 84 X 28 N/LWP0187 Louvered 1 82 X 31 79 X 28 LWP0182 40 Non-Louvered 2 82 X 31 79 X 28 N/LWP0182 Notes: 1 Includes 18 x 24 x 1 filter 2 Requires external return air grille and unit mount filter 3 Both panels are insulated for sound reduction and have tamper-proof screws 4 Panels are shipped ten per carton Note: A solid door or panel with a side wall return air grille will result in lower sound levels Part # A B N/LWP0187 87.00 84.00 8 www.goodmanmfg.com SS-VTAC

ACCESSORIES (CONT.) Filter Clip Ducted Return Air Flanges Electrical Disconnect Filter Bracket Thermostat Connection Fresh Air Vent Figure 5 Filter Bracket Detail OUTDOOR AIR VENTILATION One end of a 4 alu mi num vent pipe is con nect ed to the con dens er ven turi and the other end is con nect ed to the side of the VTC/VTH cab i net. A mesh screen is in stalled in side the vent pipe, and a met al plate on the side of the cab i net cov ers the open ing of the vent pipe. Up to 50 CFM of outside air is introduced into the equip ment clos et by re mov ing the met al cov er plate. The outside air then mixes with the re turn air and is pulled through the evap o ra tor coil and into the sup ply duct. The cov er plate can be re-in stalled to par tial ly close the out side air open ing if less than 50 CFM is de sired. An ex ter nal source of neg a tive pres sure (i.e., a bathroom fan) could be used to in tro duce more than 50 CFM of out side air. Con sult with fac to ry for fur ther de tails. Note: It is suggested that a minimum 24 door be used for access. Closet interior may be small er than listed here as long as the door open ing allows for removing the unit. Door opening must line up with unit to allow removal. Closet Wall Footprint Figure 6 Note: Sleeve protrudes ¼" (min.) through Outside outside Wall wall surface Footprint Outside Wall Surface Closet Inside Width (min.) (VWS958A) (VWS9812A) Note: Bottom surface of sleeve pan to be located 6" (min.) above floor to facilitate drain installation. Please see Wall Sleeve Installation instruction book for complete instructions. (VWS91215A) Figure 7 SS-VTAC www.goodmanmfg.com 9

GENERAL ASSEMBLY Rough-In Di men sions 44 H x 21 5/8 W Ap prox i mate Fastener Locations Electrical Dis con nect Ar chi tec tur al Grille Filter Rear Access Panel Wall Sleeve Sleeve Seal Electrical Service Knock-out Drain 3/4 MPT Outside 10 www.goodmanmfg.com SS-VTAC

INSTALLATION REAR INSTALLATION Grille width: 22" Min. 2" Req'd Unit must line up with door opening to facilitate removal when necessary. Notes: 1. Sleeve rough-in opening is 44 (H) x 21-5/8 (W) 2. Bottom of opening should be approximately 6 above floor level. 3. Minimum 3 clearance is required on all sides of the unit. REAR INSTALLATION CLOSET DIMENSIONS A C 27" (minimum) Instructions: To find the minimum closet depth (dimension C ), use the following method: Determine dimension A which is the total finished wall thickness. * For 5-8 outside wall thickness, subtract A: from 29 (C = 29 - A ) * For 8-12 outside wall thickness, subtract A: from 33 (C = 33 - A ) * For 12-15 outside wall thickness, subtract A from 36 (C = 36 - A ) SIDE INSTALLATION CLOSET DIMENSIONS Wall Sleeve Outside Wall A Instructions: To find the minimum closet depth (dimension C ), use the following method: 27" min. min. 12" min. VT UNIT C 30" min. 30" min. Determine dimension A, which is the total finished wall thickness. * For 5-8 outside wall thickness, subtract A: from 39 (C = 39 - A ) * For 8-12 outside wall thickness, subtract A: from 43 (C = 43 - A ) * For 12-15 outside wall thickness, subtract A from 46 (C = 46 - A ) SS-VTAC www.goodmanmfg.com 11

GUIDE SPECIFICATIONS Ratings Each unit must meet the following specifications: ARI rating of BTU/h cool ing (and BTU/ h reverse cycle heating with a COP of at 47 F O.D.) Electric resistance heat of BTU/h. Total Amp draw must be of and Watts at volts. The EER must be a minimum of EER. Unit Chassis Each unit must be slide-out design, ready for installation into closet space. Unit must fit into closet space not to exceed 24 x 24 with over head duct con nec - tions designed to.25 ESP. Unit must be tested for con form ance to ASTME water infiltration spec i fication ASTME 331-86, which ensures no water infiltration when tested at 8" rain per hour at 63 mph wind for 15 min. Filter Filter provided with the unit. Installer must provide for easy accessibility. Heat Pumps Each unit must include a changeover thermostat that sens es an outside coil switch-over temperature of 25 F, lock-open refrigerant-reversing valve dur ing heat pump operation, temperature-activated de frost drain and au to mat ic emer gen cy heat operation to over ride the heat pump s change-over ther mo stat and bring on electric resistance heaters in the event of a sealed-system failure. Compressor The compressor must be hermetically sealed, internally isolated, rotary-type and permanently mount ed on rub ber iso la tors. No removal or adjustment of compressor hold-down bolts is to be required during installation. Unit Controls The unit must be controlled by a thermostat. Other unit con trols must include a con cealed ventilation control to allow the in tro duc tion of fil tered air into the room, a concealed fan mode switch to allow the owner to preset for either continuous fan or ther mo stat i cal ly cycled fan operation. Ad di tion al ly, the following con trols are to be in clud ed as stan dard on all units: Compressor restart delay Random restart circuit Front desk control Evaporator coil freeze pro tec tion Fan delay Low ambient lock-out Evaporator/Condenser Fans Direct drive with a permanent split capacitor, two-speed motor. Must have a condenser fan and separate indoor evaporator motor. Condenser fan must be pro pel ler type and evaporator fan must be blower type. Coils Unit s coils must have copper tubing expanded into rippled-edge louvered aluminum fins. Discharge and Return Air A unit must be able to discharge air through an overhead duct system with an external static pressure capability of 0.35" for 9,000 and 12,000 unit sizes and 0.40" for 18,000 and 24,000 unit sizes. The return air must be capable of a free return at the unit or a ducted return. Warranty Limited One-Year Warranty; Secondthrough Fifth-Year Limited Replacement Compressor Warranty The Wall Sleeve The wall sleeve must be of industry-accepted dimensions: from 21 [d] to 28 [d] (dependent upon wall width, from 5 to 15 ) x 22 [w] x 44 [h] and constructed of insulated gal va nized steel for corrosion re sis tance. Sleeve must be shipped with weath er-re sis tant rear closure panel installed. Condensate Drain The unit must have a condensate draining system. A vertical pipe con nec tion in the base pan is connected to the evaporator drain pan via a drain line. Condensate passes from the unit to a catch tray, located in the wall sleeve, and exits the sleeve through a ¾ male NPT fitting. (This allows piping to be done during construction stage). The unit must also have a secondary condensate draining system for overflow. If the primary condensate draining system becomes clogged, water will be directed from the catch tray, through the sleeve, to the outside of the building. Any external water source (rain, sleet, etc.) entering the sleeve will also be diverted to the building s exterior. Outdoor Grilles Must be architecturally extruded and made of anodized aluminum (AGKV***A). All other grilles must be submitted to our company for feasibility, airflow characteristics and compliance with U.L. regulations, where necessary. Hydronic Heat Units Required for heating functions in- Amana is a trademark of Maytag Corporation and used under license to Goodman Company, L.P. All rights reserved. Our continuing commitment to quality products may mean a change in specifications without notice. Copyright 2008 Goodman Company, L.P. Houston, Texas Printed in the USA. 12 www.goodmanmfg.com SS-VTAC