Public Comment No. 2-NFPA [ Section No ]

Similar documents
Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Correlating Committee on Automatic Sprinkler Systems

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item


Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

MODULE 2. Water-Based Suppression System Basics

Public Comment No. 16-NFPA 13D-2014 [ Section No ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Public Comment No. 20-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

12/21/2015 National Fire Protection Association Report

"Spray area" is the term that is used throughout the document. This change is for consistency.

Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]


Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Comment No. 7-NFPA [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

26 of 128 9/23/2014 9:25 AM

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input


Throughout standard remove references to the following and replace with the following:

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 140-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Comment No. 2-NFPA [ Section No ]

Public Input No. 79-NFPA [ Section No. 1.1 ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Remove the "Exception" text to be consistent with direction provided in the MOS.

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Public Comment No. 3-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

First Draft Meeting (F2017) Agenda Friday, March 11 th, :30 AM 4:00 PM ET

UNIFIED FACILITIES GUIDE SPECIFICATIONS

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Public Input No. 11-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Technical Committee on Fluidized Bed Boilers

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

NFPA 30 FLC-SWC Public Comment Report

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*


First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Second Revision No. 2-NFPA [ Section No ]

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Sprinkler System Installer Level 2

Floor Action on Certified Amending Motions Documents for the June 2014 Association Technical Meeting


Public Comment No. 13-NFPA [ Section No ]

NFPA 37 Public Comment Responses Page 1 of 32

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

NFPA Technical Meeting (Tech Session) June 16, 2016 Agenda*

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 6-NFPA [ Section No. 2.2 ]

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

NFPA Edition Update

Deluge & Preac tion Systems

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

NFPA 101 SAF-RES PUBLIC COMMENTS

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

Public Comment No. 3-NFPA [ Chapter 7 ]

Committee Input No. 60-NFPA [ Sections , ]

FINAL* REPORT OF THE MOTIONS COMMITTEE

Foam Products ENGLISH

SECTION SPRINKLER SYSTEMS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Design & Construction Standards, Revised January

Transcription:

Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped with discharge devices, consisting of sprinklers or nozzles, for discharging the extinguishing agent over the area to be protected. The piping is connected to the water supply through a control valve that is commonly actuated by operation of automatic detection equipment installed in the same areas as open discharge devices. When this valve opens, water flows into the piping system, foam concentrate is injected into the water, and the resulting foam solution discharging through the discharge devices generates and distributes foam. Upon exhaustion of the foam concentrate supply, water discharge follows and continues until manually shut off. Existing deluge sprinkler systems that have been converted to the use of aqueous film-forming foam or film-forming fluoroprotein foam are considered foam-water sprinkler systems. 3.3.6.1* Foam-Water Deluge System. A foam-water sprinkler system employing open discharge devices, which are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system, which is installed in the same areas as the discharge devices. When this valve opens, water flows into the piping system and discharges from all discharge devices attached thereto. 3.3.6.2* Foam-Water Dry Pipe System. A foam-water sprinkler system employing automatic sprinklers or nozzles that are attached to a piping system that contains air or nitrogen under pressure, the release of which (as from the opening of a sprinkler) permits the water pressure to open a valve known as a dry pipe valve. The water then flows into the piping system and out the opened sprinklers. 3.3.6.3* Foam-Water Preaction System. A foam-water sprinkler system employing automatic sprinklers or nozzles attached to a piping system containing air that might or might not be under pressure, with a supplemental detection system installed in the same area as the sprinklers. Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that have activated. 3.3.6.4* Foam-Water Spray System. A foam-water sprinkler system designed to use nozzles rather than sprinklers. 3.3.6.5* Preprimed System. A wet pipe system containing foam solution. The sentences proposed to be deleted in the definitions are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comments # 3 through 6) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area. Submitter Full Name: Marcelo Hirschler Organization: GBH International Affilliation: NFPA GOT Submittal Date: Mon Nov 04 21:17:24 EST 2013

Committee Accepted Resolution: SR-1-NFPA 16-2014 Statement: The sentences proposed to be deleted in the definitions are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comments # 3 through 6) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.a list of discharge devices was added to the revised single sentence definition.

Public Comment No. 8-NFPA 16-2013 [ Section No. 5.11.2 ] 5.11.2 Unless required by other standards or product listings, strainers shall be required only where there are discharge orifices that are 3 8 in. (10 mm) or smaller. CC NOTE: The following CC Note No. 1 appeared in the First Draft Report as First Revision No. 14. Please clarify what system components are being referred to in section 5.11 (concentrate line or strainers protecting nozzles/orifices). If the dimensions in this section refer to nozzles, the committee should look at using k-factor instead of a dimension in inches. If this strainer is being installed as a means for protecting the pump, this should be clarified by the technical committee. Related Item First Revision No. 14-NFPA 16-2013 [Section No. 5.11.2] Submitter Full Name: CC on AUT-AAC Organization: CC on Automatic Sprinkler Systems Submittal Date: Thu Nov 14 13:15:53 EST 2013 Committee Accepted Resolution: SR-4-NFPA 16-2014 Statement: This section was addressing the protection of the concentrate pump. In reviewing this section, the TC realized the pump is not within the scope of this TC, therefore this section is being deleted.

Public Comment No. 1-NFPA 16-2013 [ Section No. 7.3.3.2 ] 7.3.3.2 Where actual system discharge density exceeds the minimum as specified in 7.3.2.1, a proportionate reduction in the duration of the foam discharge time shall be permitted, but in no case shall the duration be less than 7 minutes. Discharge could be interpreted to be in terms of flow (i.e., gallons per minute) or in this case, density. Submitter Full Name: Bill Galloway Organization: Southern Regional Fire Code De Submittal Date: Tue Oct 29 14:49:01 EDT 2013 Committee Resolution: Rejected The proposed verbiage may lead users to believe that a field measurement is required for each device, which is not the intent of the section.

Public Comment No. 9-NFPA 16-2013 [ Section No. 7.4.1.5 ] 7.4.1.5 For purposes of computing friction loss in piping, the C values shall be used for the Hazen-Williams formula in accordance with Table 7.4.1.5. Table 7.4.1.5 Hazen-Williams C Values Pipe or Tube C Value * Unlined cast or ductile iron 100 Black steel (dry systems including preaction) 100 Black steel (wet systems including deluge) 120 Galvanized steel (dry systems including preaction) 100 Galvanized steel (wet systems including deluge) 120 Plastic (listed) all 150 Cement-lined cast or ductile iron 140 Copper tube or stainless steel 150 Asbestos cement 140 Concrete 140 *The authority having jurisdiction is permitted to allow other C values. [13:Table 23.4.4.7.1] CC NOTE: The following CC Note No. 3 appeared in the First Draft Report as First Revision No. 5 and also related to Public Input No. 7. Review the issue of c-value for galvanized piping. This item was revised in the 2013 edition of NFPA 13 and will be reviewed again as part of the A2015 revision cycle for NFPA 13. The committee is urged to review the work done at the NFPA 13 First Draft meeting to ascertain the point of last consensus of the NFPA 13 TC on this issue. Related Item First Revision No. 5-NFPA 16-2013 [Section No. 7.4.1.5] Public Input No. 7-NFPA 16-2013 [Section No. 7.4.1.5] Submitter Full Name: CC on AUT-AAC Organization: CC on Automatic Sprinkler Systems Submittal Date: Thu Nov 14 13:18:01 EST 2013 Committee Resolution: Rejected The referenced table is being extracted from NFPA 13 2013 edition and therefore will correlate with the requirements from NFPA 13.

Public Comment No. 3-NFPA 16-2013 [ Section No. A.3.3.6 ] A.3.3.6 Foam-Water Sprinkler System. The piping network is equipped with discharge devices, consisting of sprinklers or nozzles, for discharging the extinguishing agent over the area to be protected. The piping is connected to the water supply through a control valve that is commonly actuated by operation of automatic detection equipment installed in the same areas as open discharge devices. When this valve opens, water flows into the piping system, foam concentrate is injected into the water, and the resulting foam solution discharging through the discharge devices generates and distributes foam. Upon exhaustion of the foam concentrate supply, water discharge follows and continues until manually shut off. Existing deluge sprinkler systems that have been converted to the use of aqueous film-forming foam or film-forming fluoroprotein foam are considered foam-water sprinkler systems. These systems can be preprimed with foam solution. This solution would remain in the piping until the system is called upon to operate. Preprimed systems could require draining, flushing, and repriming on a periodic basis (see Section 9.3). This procedure will require an investment in both time and material and should be programmed into the total system operating cost. The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 3) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area. Related Public Comments for This Document Related Comment Public Comment No. 2-NFPA 16-2013 [Section No. 3.3.6] Relationship Submitter Full Name: Marcelo Hirschler Organization: GBH International Affilliation: NFPA GOT Submittal Date: Mon Nov 04 21:22:28 EST 2013 Committee Accepted Resolution: SR-2-NFPA 16-2014 Statement: The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 3) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.

Public Comment No. 4-NFPA 16-2013 [ Section No. A.3.3.6.1 ] A.3.3.6.1 Foam-Water Deluge System. Foam-water sprinklers are open-type sprinklers designed to do the following: (1) Receive foam solution (water plus liquid concentrate) (2) Direct the solution through an integral foam maker, the nozzle action of which breaks the solution into spray and discharges it into a mixing tube, where it combines with air drawn in through openings in the housing (3) Provide mixing chamber capacity for development of the air foam (4) Direct the formed foam discharging from the open end of the mixing tube against a deflector, shaped to distribute the foam in a pattern essentially comparable to the water distribution pattern of present-day standard sprinklers (nomenclature from NFPA 13, Standard for the Installation of Sprinkler Systems) and to do so with essentially no impingement of the foam on the ceiling (5) Develop a water distribution pattern directly comparable to that of standard sprinklers, in the case of discharge of water only (i.e., in the absence of foam) The normal direction of discharge from foam-water sprinklers is downward. To provide a choice in installation design, foam-water sprinklers are produced for installation in the upright position and in the pendent position with the pattern of discharge in either case in the downward direction. Sprinkler deflectors are formed to produce the required discharge pattern, which could mean differing shapes of deflectors for each of the two positions of installation. The variation in the shape of deflectors is illustrated in Figure A.3.3.6.1. When the valve in a foam-water deluge system opens, water flows into the piping system and discharges from all discharge devices attached thereto. Figure A.3.3.6.1 Variations in Deflector Shape. The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 4) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.

Related Public Comments for This Document Related Comment Public Comment No. 2-NFPA 16-2013 [Section No. 3.3.6] Public Comment No. 3-NFPA 16-2013 [Section No. A.3.3.6] Relationship Submitter Full Name: Marcelo Hirschler Organization: GBH International Affilliation: NFPA GOT Submittal Date: Mon Nov 04 21:24:50 EST 2013 Committee Accepted Resolution: SR-5-NFPA 16-2014 Statement: The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 4) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.

0 Public Comment No. 5-NFPA 16-2013 [ Section No. A.3.3.6.2 ] A.3.3.6.2 Foam-Water Dry Pipe System. After the valve is opened, the water then flows into the piping system and out the opened sprinklers. Dry pipe systems are inherently slower in operation and have a tendency to develop internal scale. Since the foam solution would be proportioned into the system upon operation, the first discharge would be an effective foam. However, due to the slower operation, this should be considered the least desirable type of sprinkler system for closed-head foam-water sprinkler application. The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 5) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area. Related Public Comments for This Document Related Comment Public Comment No. 2-NFPA 16-2013 [Section No. 3.3.6] Public Comment No. 3-NFPA 16-2013 [Section No. A.3.3.6] Public Comment No. 4-NFPA 16-2013 [Section No. A.3.3.6.1] Relationship Submitter Full Name: Marcelo Hirschler Organization: GBH International Affilliation: NFPA GOT Submittal Date: Mon Nov 04 21:27:48 EST 2013 Committee Accepted Resolution: SR-6-NFPA 16-2014 Statement: The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 5) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.

1 Public Comment No. 6-NFPA 16-2013 [ Section No. A.3.3.6.3 ] A.3.3.6.3 Foam-Water Preaction System. Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that have activated. These systems combine the features of both wet pipe and dry pipe systems. The piping is empty and might or might not contain air under low pressure for supervision of the piping. There is a separate detection system that operates the water control valve to release foam solution into the piping. (The actuating means of the valve is described in NFPA 13, Standard for the Installation of Sprinkler Systems.) This detection system should be more sensitive than the sprinkler elements. With this arrangement, foam solution is usually released into the piping before the sprinklers operate so that, when they do, there is an immediate discharge, as with a wet pipe system. To ensure this discharge, supervision of the actuation system is recommended. Foam solution would be proportioned into the system upon operation, so there is no need for prepriming. Overall response time generally approaches that of a wet pipe system. Actual time of foam discharge would depend on the type of separate detection system used and the type of fire. With a rapidly developing fire, the sprinklers might begin to operate very close to the initial operation of the separate detection system, and the piping might not have time to fill with foam solution to achieve immediate discharge. With a slowly developing fire, there would be sufficient time to fill the piping, and there would be a discharge of fresh foam upon sprinkler operation. These systems are more complex than dry pipe and wet pipe systems, and this factor should be considered. The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 6) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area. Related Public Comments for This Document Related Comment Public Comment No. 2-NFPA 16-2013 [Section No. 3.3.6] Public Comment No. 3-NFPA 16-2013 [Section No. A.3.3.6] Public Comment No. 4-NFPA 16-2013 [Section No. A.3.3.6.1] Public Comment No. 5-NFPA 16-2013 [Section No. A.3.3.6.2] Relationship Submitter Full Name: Marcelo Hirschler Organization: GBH International Affilliation: NFPA GOT Submittal Date: Mon Nov 04 21:30:52 EST 2013

2 Committee Accepted Resolution: SR-7-NFPA 16-2014 Statement: The sentences proposed to be deleted from the definitions in public comment # 2 are not part of the definition but are an explanation which should be placed either in the annex (as recommended in public comment # 6) or in a separate part of the standard. Definitions are not enforceable and requirements or additional information should be placed out side the definitions area.