Comfort Zone Or Acceptable Comfort Zone? : Comparison of Resident Behavior of Operating Air Conditioner According to Charge for Energy

Size: px
Start display at page:

Download "Comfort Zone Or Acceptable Comfort Zone? : Comparison of Resident Behavior of Operating Air Conditioner According to Charge for Energy"

Transcription

1 Comfort Zone Or Acceptable Comfort Zone? : Comparison of Resident Behavior of Operating Air Conditioner According to Charge for Energy Suh-hyun Kwon, Nu-ri Bae, Chi-hye Bae and Chungyoon Chun Yonsei University, Korea Corresponding amy611@hanmail.net SUMMARY This research compared two groups operation behavior of cooler, one is the resident of studio apartment who pays their energy charge per month, and the other is the resident of university dormitory who doesn t pay energy charge beside their rental fee. The amount of time to use a cooler and room temperatures were measured when they turn on/off air conditioner. Residents were interviewed about their cooling needs and decision factor on their operation behavior. Main results are as follows. 1. Dormitory group used the air-conditioner twice as much as studio apartment group. 2. Dormitory group turned on/off air-conditioner at lower temperature compare to the studio apartment group. 3. Studio apartment group s acceptable comfort zone was in or higher than ASHRAE summer comfort zone, but dormitory group s that is in or lower than ASHARAE comfort zone. INTRODUCTION Building systems have been developed and complicated, and it follows the energy which is consumed for the building is extending too. In a life cycle of the building, most using much energy is a dwelling phase. Big effects to these energy consumptions in a dwelling phase are the behavior and attitude of residents, and energy charge affects to these residents behavior and attitude. Consequently, we can assume that there would be a big difference between the residents who pay for the energy or not; house and office. Meanwhile, the electric consumption in Korea was increased 4 times much as 20 years before. Big parts of these residential energy consumptions are consent, lighting and cooling. Especially, cooling demand is expected to increase fast. On this background, this research compared two groups operation behavior of cooler according to charge for energy. METHODS Thermal environment and using time of air conditioner are measured in seven studioapartments and eight rooms in university dormitory where air conditioners were located. Measurement was conducted during 9 days from August 13 th to 22 nd in Subjects were selected to twenties who can operate air conditioner well and were limited to independent resident for restricting effects from other generations. We do an experiment in two groups operation behavior of cooler; one is the residents who pay their energy charge per month, and the other is the residents of university dormitory who doesn t pay energy charge beside their rental fee. This is for finding out whether charging for energy has effect on using time of air conditioner. Air temperature and relative humidity were measured at 110cm high from the floor and air temperature blowing from air conditioner was also measured to detect the

2 condition of on/off of air conditioner. Air temperature, relative humidity, and air temperature blowing from the air conditioner are measured with RH-temperature data logger. Interviews were also conducted to investigate characteristics of residents behaviors of operating air conditioner in addition to physical environment; time of staying at home, a way they operate air conditioner, a purpose that they use air conditioner, their Clo value, sex, age, kinds of AC, and spending electric power. RESULTS Outdoor temperature and relative humidity Outdoor weather data was obtained form Korea Meteorological Administration. The mean outdoor temperature was and relative humidity was 67% during experiment period Outdoor Air Temperature 100 Relative Humidity 80 Ta( ) RH(%) /14 8/15 8/16 8/17 8/18 8/19 8/20 8/20 8/21 Date a) Outdoor air temperature Figure 1. Climate during experiment periods 20 8/14 8/15 8/16 8/17 8/18 8/19 8/20 8/20 8/21 Date b) Relative humidity Comparison on the amount of time to use an air conditioner between two groups Table1 shows that the results of the time used with air conditioner for two groups. The dormitory group used air conditioner twice as much as the studio-apartment group: Dormitory group spend 43hours 55minutes and studio-apartment group spend 23hours 21minutes in the experiment period. All of the residents in two groups were university students or graduate students. Although considering their life style was similar, we calculated index of amount of time to use an air conditioner to more accurate analysis. The method of calculating of index was that amount of time to use an air conditioner divided by mean time for which residents stayed at home. As the result, index of dormitory (0.4) was higher than that of studio apartment (0.17). Even though, we excluded A-6 and A-7 that never used air conditioner during experiment period from a calculating, index of studio apartment became 0.24 to be still lower than dormitory. It was one of the reasons that residents even maintained running air conditioner when they went out for thermal comfort to come back. While, when going out, residents of studio apartment always turned off their air conditioner. A-3 of studio apartment group was the highest both time of use and index of time, because this one stayed at home by far than others. Most of studio apartment except A-3 was lower than dormitory in index of time. Also, despite of high temperature of outdoor, A-6 and A-7 never turned on air conditioner because of charge for energy.

3 Table 1. Operating time of air conditioner. Studio-apartment Dormitory Resident Operating time Index Operating time Index Resident (hour, minute) of operating time (hour, minute) of operating time A-1 29h 8m 0.29 B-1 49h 24m 0.50 A-2 10h 36m 0.10 B-2 45h 58m 0.46 A-3 64h 4m 0.44 B-3 73h 0.50 A-4 40h 40m 0.28 B-4 54h 52m 0.38 A-5 18h 8m 0.08 B-5 37h 0.37 A-6 0m 0 B-6 31h 32m 0.31 A-7 0m 0 B-7 33h 20m 0.37 B-8 26h 16m 0.27 Avg. 23h 21m 0.17 Avg. 43h 55m 0.40 * Index of operating time = Operating time of air conditioner / inhabitant time Indoor Thermal Environment when residents operate air conditioner There was a gap between two groups about mean temperature at the point time that air conditioner turned on or off. Table 2 shows that indoor air temperature fight at the point time that residents turn on air conditioner and turn them off. It appeared that residents of the studio apartment start air conditioner at 29.9 of air temperature, and switch off at While, residents of the dormitory turn on air conditioner at 27.0, and turn off at It means that residents of studio apartment turn on and off at higher temperature than residents of dormitory. Like above these results, we know that the dormitory group not to charge for energy used air conditioner in lower temperature than the studio apartment group to charge for energy. Table 2. Mean indoor air temperature when AC was turned on or off. Studio-apartment Dormitory Resident On( ) Off( ) Resident On( ) Off( ) A B A B A B A B A B A-6 Never used B A-7 Never used B B Avg Avg Interview of resident cooling behavior Interview was conducted to help understanding about residents behavior of operating air conditioner. When asked whether residents still remain air conditioner turn on for going out, more than 50 percent of the dormitory residents blamed yes, but all of the studio apartment residents answered no. Setting temperature of air conditioner in both groups was similar, 20. They controlled indoor temperature by switch on and off, not the setting temperature. The main reason why they turn on air conditioner is high temperature, the other is to exsiccate. Also, it seems that their habituation of operating air conditioner is only to turn on or off cooler

4 than to regulate. When they ho to sleeping, all in both groups stopped cooler and opened windows, but only one in the dormitory remained cooler running beside opening windows. Indoor mean Clo value of the studio apartment group was higher rather than the dormitory group: the studio apartment group was 0.15 clo and the dormitory group was 0.24 clo. When asked How much could you pay for using air conditioner?, they answered each 34 dollars on the dormitory and 70 dollars on the studio apartment. It means that residents of the studio apartment who pay for energy have more recognition than them of the dormitory. Comparison with a previous research We compared this result with previous research, which was studied from Nu-Ri Bae for finding out resident operating behavior of air conditioner according family members as well as charge for energy.[1] The previous research was conducted during 60days from July 3 rd to August 31 st in 2004 in six family apartments living rooms there air conditioner were located. Indoor thermal environment was measured and air temperature blowing from air conditioner was also measured to find out the condition of on/off of air conditioner. Mean outdoor temperature was 25.2 and relative humidity was 76.5% in experiment period. 1. Thermal environment of three groups In Figure 2~ 4 thermal environments at the point time air conditioner was started and was stopped in three groups compared with thermal comfort range of ASHRAE Standard 55. [2] First of all, compared with thermal environment according charge for energy, three groups have a clear distinction. Figure 2 shows that the result of studio apartment group. When residents started air conditioner, most cases of thermal environment were on very high temperature that is not contained ASHRAE comfort zone and when air conditioner was stopped, some cases was covered or accessed ASHRAE comfort zone of summer. Also, Figure 4 indicated that family apartment was as same as studio apartment but was rather high range. An air conditioner was started and switched off at thermal range that was not included ASHRAE comfort zone. On the other hand, Figure 3 displayed that residents behavior of the dormitory was different from other two groups. They turned on air conditioner at air temperature whose one third already was included on summer comfort zone of ASHRAE and turned off it at air temperature whose most was contained on lower air temperature, winter comfort zone, as well as summer comfort zone of ASHRAE. It means that range of thermal environment which residents controlled was significantly different according charge for energy. Judging from air temperature, residents can use air conditioner on very low air temperature in case of no charging for energy. From interview, there are some responses that residents still keep cooler in running until feeling cold and wear more clothes instead of stopping cooler.

5 a) Thermal range when AC was turned on b) Thermal range when AC was turned off Figure 2. apartment Indoor thermal range on ASHRAE comfort zone when AC operated in studio a) Thermal range when AC was turned on b) Thermal range when AC was turned off Figure 3. Indoor thermal range on ASHRAE comfort zone when AC operated in dormitory a) Thermal range when AC was turned on b) Thermal range when AC was turned off Figure 4. Indoor thermal range on ASHRAE comfort zone when AC operated in family apartment

6 2. Prediction of time to use air conditioner What effect will outdoor weather factors including mean temperature, highest temperature, lowest temperature, mean relative humidity and highest wind velocity have on time to use air conditioner? The relationship between outdoor weather factor and using time was calculated by linear regression model. As a result, the relationship with both mean temperature and highest temperature is the strongest in the family apartment, the relationship with lowest temperature is the strongest in the dormitory and the relationship with both highest temperature and lowest temperature is the strongest in the studio apartment. It is appeared that residents of the family apartment start air conditioner when outdoor temperatures getting hotter but residents of the dormitory turn off it when weather become colder. In other words, residents in family apartment don t use air conditioner usually and then start it when air temperature reach the maximum, but the residents in dormitory use air conditioner always and then they switch off it when air temperature go down. Table 3. Correlation coefficient between outdoor weather and time of using AC Weather factor Studio apartment Dormitory Family apartment R R R Mean outdoor air temperature Highest outdoor air temperature Lowest outdoor air temperature Mean relative humidity Highest wind velocity 1E Using time of air conditioner of each group was predicted through regression model with mean outdoor temperature that is related in all groups comparatively high. 26 and 30 of outdoor air temperature were applied to regression model, and mean using time of each group was calculated. Showing fig. 6, the dormitory has each value of 319 minutes and 540minutes, the studio apartment has each value of 222minutes and 364minutes and the family apartment has value of 119mimutes and 202minutes. From this graph, we can see the order of using time of air conditioner in same outdoor temperature is Dormitory, Studio apartment, and Family apartment. And an angle of inclination by temperature increasing shows same order. The reason why residents of the family apartment use less time compared with studio apartment could be from generation gap about energy saving and charging for energy, different thermal sensation between ages, and housewife economical conception, etc Apartment Studio Apartment Dormitory Time(min) Room Temperature( ) Figure 5. Predicted AC using time by outdoor air temperature

7 DISCUSSION When people turn off air conditioner, which means room air temperature became cool enough to them. This enough cool temperature was different between three groups. Of course, it is because of economical factor. Thermal comfort zone like ASHRAE Std.55 is based on sensory comfort in climate chamber. It was calculated from experiment results in climate chamber. Subjects didn t get the influence from economical factor, and tried to find out just comfortable temperature. If we call this just comfortable temperature as sensory comfort zone, we can call acceptable comfort zone in this study as cognitive comfort zone. Sensory comfort zone is related on human sensory system physiological & physical characteristics. Cognitive comfort gets the influence from many factors economical situation, thermal history, adaptation state, etc. These differences made the difference between many chamber study results and field study results. In ordinary, field study results show wider acceptable range than chamber study results. This tendency respected to the revise of ASHRAE Std. 55 (2004). Both of them Sensory & Cognitive Comfort are necessary and worth. However, broad acceptable range may be desirable in point of human thermal adaptation and environment of the earth. REFERENCES 1. Nu-ri Bae A study on acceptable thermal comfort zone and resident behavior of operating cooling devices in apartment. Proceedings of Healthy buildings. 2. ASHRAE ANSI/ASHRAE Standard , Thermal Environmental Conditions for Human Occupancy, Atlanta: American Society of Heating, Refrigerating, and Air conditioning Engineers, Inc. 3. Busch, J.F A tale of two populations: thermal comfort in air-conditioned and naturally ventilated offices in Thailand. Energy and Buildings. 18: Cena, K.M. Thermal and non-thermal aspects of comfort surveys in homes and offices. in Thermal comfort: Past, Present and Future, ed. by N.A. Oseland and M.A. Humphreys Garston: Building Research Establishment de Dear, R. and A. Auliciems Air-conditioning in Australia Ⅱ - User Attitudes. Architectural Science Review, 31: de Dear, G.J. and M.E. Fountain Field experiments on occupant comfort and office thermal environments in a hot-humid climate, ASHRAE Transactions, 100(2): de Dear, R.J. and G.S. Brager Thermal comfort in naturally ventilated buildings: revisions to ASHRAE Standard 55, Energy and Buildings, 34: 549: ISO. ISO Ergonomics of the Thermal Environment-Analytical determination and interpretation of the PMV and PPD indices and local thermal comfort criteria. Geneva: International Organization for Standardization. 9. Meyer, W.B Why indoor climates change: a case study, Climatic Change, 55: Parsons, K.C The effects of gender, acclimation state, the opportunity to adjust clothing and physical disability on requirements for thermal comfort, Energy and Buildings, 34: Raja, I.A., J.F. Nicol, K.J. McCartney and M.A. Humphreys Thermal comfort: use of controls in naturally ventilated buildings, Energy and Buildings, 33:

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY M Kojima, T Saito Graduate School of Environmental Studies, NAGOYA University, Chikusa, Nagoya, 464-8603

More information

Thermal Environment Evaluation in Commercial Kitchens of United States

Thermal Environment Evaluation in Commercial Kitchens of United States Downloaded from orbit.dtu.dk on: Jul 25, 2018 Thermal Environment Evaluation in Commercial Kitchens of United States Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation

More information

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between

More information

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International

More information

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure Validation of an Energy Demand Model of Residential Buildings Yohei Yamaguchi 1*, Yoshiyuki Shimoda 1 1 Graduate School of Engineering Osaka University, S4 Building, 2-1 Yamadaoka, Suita, Osaka, 565-871,

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

* Currently, lecturer at the Department of Architecture, The University of Adelaide. Adelaide. South Australia.

* Currently, lecturer at the Department of Architecture, The University of Adelaide. Adelaide. South Australia. THERMAL COMFORT STUDY IN A NATURALLY VENTILATED RESIDENTIAL BUILDING IN A TROPICAL HOT-HUMID CLIMATE REGION Veronica I. Soebarto* and Siti Handjarinto Department of Architecture University of Indonesia

More information

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan

More information

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Thermal Comfort with Convective and Radiant Cooling Systems

Thermal Comfort with Convective and Radiant Cooling Systems Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with

More information

The risk of indoor air pollutants accumulation in the five housing types in Ho Chi Minh City (Vietnam)

The risk of indoor air pollutants accumulation in the five housing types in Ho Chi Minh City (Vietnam) The risk of indoor air pollutants accumulation in the five housing types in Ho Chi Minh City (Vietnam) Thuy T. T. Tran 1,5 *, Diem T. K. Nguyen 1,5, Thanh Ng. Tran 2, Phong D. H. Dinh 2, Tan V. Le 1, Olivier

More information

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Indoor Thermal Environment of Residential Buildings in Three Cities of China Indoor Thermal Environment of Residential Buildings in Three Cities of China Hiroshi Yoshino 1 and Haihong Lou 2 1 Prof, Laboratory of Building Environmental Engineering, Department of Architecture & Building

More information

Section 9. Comparing Energy Consumption: More for Your Money. What Do You See? What Do You Think? Investigate. Learning Outcomes

Section 9. Comparing Energy Consumption: More for Your Money. What Do You See? What Do You Think? Investigate. Learning Outcomes Section 9 Comparing Energy Consumption: More for Your Money Section 9 Comparing Energy Consumption: More for Your Money What Do You See? Learning Outcomes In this section, you will Measure and compare

More information

Applications of Thermodynamics: Heat Pumps and Refrigerators

Applications of Thermodynamics: Heat Pumps and Refrigerators Applications of Thermodynamics: Heat Pumps and Refrigerators Bởi: OpenStaxCollege Almost every home contains a refrigerator. Most people don t realize they are also sharing their homes with a heat pump.

More information

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS Proceedings of BS13: SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS Hiromi Habara 1, Rakuto Yasue 1 and Yoshiyuki Shimoda 1 1 Graduate School

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator 18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.

More information

Survey on Cooling Costs and Related Factors for Apartments in an Urban. Area of Osaka

Survey on Cooling Costs and Related Factors for Apartments in an Urban. Area of Osaka Survey on Cooling Costs and Related Factors for Apartments in an Urban Area of Osaka Noriko Umemiya Xiaoyong Lin Ginjirou Inoue Associate Professor Graduate student Graduate student Osaka City University

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017 Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM 13 th May 2017 0 1 Portion of Inverter Residential Air Conditioners Worldwide (2015) and in Vietnam (Mar 2017) What is "Inverter"?

More information

A novel test method for predicting crushing elasticity in medium fluting with higher relevance than for instance currently used methods like CMT

A novel test method for predicting crushing elasticity in medium fluting with higher relevance than for instance currently used methods like CMT White paper Thomas Fürst (ABB) Lorentzen & Wettre products, Sweden Peter Gerards (Smurfit Kappa) Product Development, Netherlands A novel test method for predicting crushing elasticity in medium fluting

More information

Attitudes Toward Recycling: A survey of residents of Sheridan, WY December 2012

Attitudes Toward Recycling: A survey of residents of Sheridan, WY December 2012 Attitudes Toward Recycling: A survey of residents of Sheridan, WY December 2012 #122250 Lori Weigel Partner Public Opinion Strategies conducted a survey of 250 residents of the city of Sheridan, Wyoming.

More information

Reducing Energy Use in Grain Dryers

Reducing Energy Use in Grain Dryers Reducing Energy Use in Grain Dryers J. Dyck, P. Eng. FACTSHEET 17-001 Agdex 111/736 january 2017 (replaces OMAFRA factsheet 88-003, Reclaiming Corn Drying Energy) INTRODUCTION Are you paying too much to

More information

Wayside horn noise investigation

Wayside horn noise investigation Wayside horn noise investigation Simon Moore AECOM, Level 28, 91 King William Road, Adelaide, Australia ABSTRACT Warning horns are used by trains and sounded when approaching a level to warn of its presence.

More information

TESTS OF ADSIL COATING

TESTS OF ADSIL COATING TESTS OF ADSIL COATING Test B - Long Term Test FSEC-CR-1259-01 July 11, 2001 Prepared for: Bob Suggs Florida Power & Light Company 9250 W. Flagler Street Miami, Florida 33174 Principal Investigator Dr.

More information

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner P. Suntivarakorn, S. Satmarong, C. Benjapiyaporn, and S. Theerakulpisut Abstract This paper was to study the clothes

More information

Collusion or Illusion: A Tri-State Analysis of Gas Prices. Presented to the city of Eau Claire Fiscal Advisory Committee 12/12/2012

Collusion or Illusion: A Tri-State Analysis of Gas Prices. Presented to the city of Eau Claire Fiscal Advisory Committee 12/12/2012 Collusion or Illusion: A Tri-State Analysis of Gas Prices Presented to the city of Eau Claire Fiscal Advisory Committee 12/12/2012 Presenters Dr. Ryan Weichelt assistant professor Geography and Anthropology

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration

More information

Experimental study of space cooling using ceiling panels equipped with capillary mats

Experimental study of space cooling using ceiling panels equipped with capillary mats Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding email: tiberiu.catalina@insa-lyon.fr SUMMARY

More information

SPEECH PRIVACY DISTANCE IN 3 OPEN-PLAN OFFICE LAYOUTS: COMPUTER MODELLING AND SIMULATION APPROACH

SPEECH PRIVACY DISTANCE IN 3 OPEN-PLAN OFFICE LAYOUTS: COMPUTER MODELLING AND SIMULATION APPROACH SPEECH PRIVACY DISTANCE IN 3 OPEN-PLAN OFFICE LAYOUTS: COMPUTER MODELLING AND SIMULATION APPROACH Joko Sarwono, Annisa E. Larasati, F.X. Nugroho Soelami, and Indra Sihar Department of Engineering Physics,

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing Vipac Engineers & Scientists DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption The physical testing Sydney 16 August 2016 Introduction to Vipac AGENDA

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

SIEMENS ULTRAMAT 6 IR CARBON MONOXIDE ANALYZER METHOD VALIDATION FOR TESTING CARBON MONOXIDE IN NITROGEN, NF

SIEMENS ULTRAMAT 6 IR CARBON MONOXIDE ANALYZER METHOD VALIDATION FOR TESTING CARBON MONOXIDE IN NITROGEN, NF 2015 SIEMENS ULTRAMAT 6 IR CARBON MONOXIDE ANALYZER METHOD VALIDATION FOR TESTING CARBON MONOXIDE IN NITROGEN, NF FINAL APPROVAL REVISION #: 0 ISSUE DATE: December 4, 2015 PAGE: 1 of 13 This Methods

More information

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii

Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii Jenny Yaillen, Evergreen Economics Chris Ann Dickerson, CAD Consulting Wendy Takanish and John Cole, Hawaii Public Utilities

More information

EFFECTS OF AIR VELOCITY AND CLOTHING COMBINATION ON HEATING EFFICIENCY OF AN ELECTRICALLY HEATED VEST (EHV): A PILOT STUDY

EFFECTS OF AIR VELOCITY AND CLOTHING COMBINATION ON HEATING EFFICIENCY OF AN ELECTRICALLY HEATED VEST (EHV): A PILOT STUDY EFFECTS OF AIR VELOCITY AND CLOTHING COMBINATION ON HEATING EFFICIENCY OF AN ELECTRICALLY HEATED VEST (EHV): A PILOT STUDY Faming Wang, Chuansi Gao, and Ingvar Holmér Thermal Environment Laboratory, Division

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

This presentation is posted for public use. ACEEE does not endorse any product or service.

This presentation is posted for public use. ACEEE does not endorse any product or service. This presentation is posted for public use. ACEEE does not endorse any product or service. ACEEE accepts no responsibility for any facts or claims this presentation may contain. Water Heater Performance

More information

Broomfield Garbage & Recycling Survey. Draft Report of Results

Broomfield Garbage & Recycling Survey. Draft Report of Results Broomfield Garbage & Recycling Survey Draft National Research Center, Inc. 3005 30 th Street Boulder, CO 80301 tel. 303-444-7863 fax. 303-441-1145 e-mail: nrc@n-r-c.com www.n-r-c.com Table of Contents

More information

INDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE

INDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE INDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE SKD Coward, GJ Raw, JW Llewellyn and DI Ross BRE, Watford WD25 9XX, UK ABSTRACT BRE has conducted a national survey of air pollutants in 876 homes

More information

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM - 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,

More information

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Jae-Han Lim 1, Myoung-Souk

More information

Scholars Research Library. The Role of Plant Clinic in Protecting Vertical Urban Green Spaces in Tehran

Scholars Research Library. The Role of Plant Clinic in Protecting Vertical Urban Green Spaces in Tehran Available online at www.scholarsresearchlibrary.com Annals of Biological Research, 2011, 2 (3) :255-261 (http://scholarsresearchlibrary.com/archive.html) ISSN 0976-1233 CODEN (USA): ABRNBW The Role of

More information

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2 01-014 The 2005 World Sustainable Building Conference, DEVELOPMENT OF A PASSIVE COOLING STRATEGY USING DOUBLE-ROOFING SYSYTEM WITH RAINWATER SPRAYING AND ITS FIELD TESTING IN TERMS OF THE INDOOR THERMAL

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

Smoke Alarm Response Time:

Smoke Alarm Response Time: Smoke Alarm Response Time: Examining the Relationship Between Working Smoke Alarms, Fire Service Response Times and Fire Outcomes Joseph Clare, Charles Jennings, Len Garis November 2018 Executive Summary

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

QUANTIFICATION OF TONAL PENALTIES IN ENVIRONMENTAL NOISE ASSESSMENTS

QUANTIFICATION OF TONAL PENALTIES IN ENVIRONMENTAL NOISE ASSESSMENTS QUANTIFICATION OF TONAL PENALTIES IN ENVIRONMENTAL NOISE ASSESSMENTS S.A. Nordby O.-H. Bjor Norsonic AS, Tranby, Norway Norsonic AS, Tranby, Norway 1 INTRODUCTION Most people listening to an unwanted noise

More information

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Bill Rittelmann, IBACOS Building Enclosure Technology and

More information

Public Works and Infrastructure Committee Front Yard Parking Regulations. Transportation Services. June 8, 2017

Public Works and Infrastructure Committee Front Yard Parking Regulations. Transportation Services. June 8, 2017 RE: PW22.5 Public Works and Infrastructure Committee Front Yard Parking Regulations Transportation Services June 8, 2017 1 BACKGROUND 2 HISTORY Providing parking on the boulevard and/or front yard within

More information

Appendix F PENNSYLVANIA LOCAL PARKS AND THE COMMUNITIES THEY SERVE

Appendix F PENNSYLVANIA LOCAL PARKS AND THE COMMUNITIES THEY SERVE Appendix F PENNSYLVANIA LOCAL PARKS AND THE COMMUNITIES THEY SERVE August 8, 2014 By The Center for Rural Pennsylvania Profile Data Profiles and Analysis Introduction To assist in the development of the

More information

EXTERNALLY HEATED DESICCANT AIR DRYERS. GEHD Series

EXTERNALLY HEATED DESICCANT AIR DRYERS. GEHD Series EXTERNALLY HEATED DESICCANT AIR DRYERS GEHD Series GARDNER DENVER GEHD DESICCANT AIR DRYERS Why Dry Compressed Air? Compressed air has long been described as the fourth utility after electricity, natural

More information

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load Philip Boudreaux, Roderick Jackson, Jeffrey Munk and Anthony Gehl, Oak Ridge National

More information

Investigation of Thermal Environments in Humid Tropical Classroom in Indonesia

Investigation of Thermal Environments in Humid Tropical Classroom in Indonesia Journal of Engineering and Architecture June 2017, Vol. 5, No. 1, pp. 1-14 ISSN: 2334-2986 (Print), 2334-2994 (Online) Copyright The Author(s). All Rights Reserved. Published by American Research Institute

More information

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography Amit Kumar Gautam¹, Dr. J. L. Bhagoria² ¹M.Tech. Scholar, Mechanical Engineering, ²Professor,

More information

A Comparative Study on the Utilization Configuration and Characters of Urban Comprehensive Park in China and Korea

A Comparative Study on the Utilization Configuration and Characters of Urban Comprehensive Park in China and Korea International Conference on Management Science and Innovative Education (MSIE 5) A Comparative Study on the Utilization Configuration and Characters of Urban Comprehensive Park in China and Korea Xiaoyan

More information

Indicators for enhanced fire safety

Indicators for enhanced fire safety Indicators for enhanced fire safety Assignment Identify and suggest 8-10 indicators that can be used long-term and followed up Suggest a number of measurable goals related to the indicators National strategy

More information

ARTI Charcoal Solar Briquette Dryer Improvement Project Report

ARTI Charcoal Solar Briquette Dryer Improvement Project Report ARTI Charcoal Solar Briquette Dryer Improvement Project Report Nicole Ozminkowski Dan Sweeney MIT D-Lab Introduction In sub-saharan Africa, 4 out of 5 households depend on charcoal and wood for cooking

More information

Fan Selection. and Energy Savings

Fan Selection. and Energy Savings Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC

More information

Energy Center of Wisconsin Residential Characterization Study Homeowner Survey

Energy Center of Wisconsin Residential Characterization Study Homeowner Survey Energy Center of Wisconsin Residential Characterization Study Homeowner Survey Name: Address: Building ID (To be filled in by field crew): HOME AND FAMILY 1 About when was your home built? 1 1995 or later

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

Heat loss via internal drainage vent pipes

Heat loss via internal drainage vent pipes Full version of poster submission Leipzig 2015 Heat loss via internal drainage vent pipes Alan Clarke, E-Mail alan@arclarke.co.uk Nick Grant, E-Mail nick@elementalsolutions.co.uk Elemental Solutions, www.elementalsolutions.co.uk

More information

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT DAVID CHARTERS DEAN MCGRAIL Arup Fire, 78 East Street, Leeds, LS9

More information

EXTERNALLY HEATED BLOWER PURGE DESICCANT AIR DRYERS. GBPD Series

EXTERNALLY HEATED BLOWER PURGE DESICCANT AIR DRYERS. GBPD Series EXTERNALLY HEATED BLOWER PURGE DESICCANT AIR DRYERS GBPD Series GARDNER DENVER GBPD DESICCANT AIR DRYERS Why Dry Compressed Air? Compressed air has long been described as the fourth utility after electricity,

More information

Cooling Systems for Georgia Dairy Cattle. Dr. John W. Worley, Extension Engineer

Cooling Systems for Georgia Dairy Cattle. Dr. John W. Worley, Extension Engineer Cooling Systems for Georgia Dairy Cattle Dr. John W. Worley, Extension Engineer Heat stress can reduce summer milk production in dairy cows by 15 to 22 percent according to University heat stress, costing

More information

Buying Products for Home Building & Remodeling: Who and Where. By Paul Emrath, Ph.D. Economics and Housing Policy

Buying Products for Home Building & Remodeling: Who and Where. By Paul Emrath, Ph.D. Economics and Housing Policy Buying Products for Home Building & Remodeling: Who and Where Special Studies,, 2012 By Paul Emrath, Ph.D. Economics and Housing Policy In the course of their business, home builders and remodelers buy

More information

VASHON-MAURY FIRE AND RESCUE Community Needs Survey Executive Summary March 2000

VASHON-MAURY FIRE AND RESCUE Community Needs Survey Executive Summary March 2000 VASHON-MAURY FIRE AND RESCUE Community Needs Survey Executive Summary March 2000 Table of Contents RESEARCH OBJECTIVES... 2 METHODOLOGY... 3 EXPLANATION OF MULTIVARIATE ANALYSIS... 4 SERVICES UTILIZED...

More information

S TAR-ORION S OUTH D IAMOND P ROJECT E NVIRONMENTAL I MPACT S TATEMENT APPENDIX A FUNDAMENTALS OF ACOUSTICS

S TAR-ORION S OUTH D IAMOND P ROJECT E NVIRONMENTAL I MPACT S TATEMENT APPENDIX A FUNDAMENTALS OF ACOUSTICS APPENDIX 5.2.5-A FUNDAMENTALS OF ACOUSTICS Definition of Acoustical Terms Acoustics is the study of sound and noise is defined as unwanted sound. Airborne sound is a rapid fluctuation or oscillation of

More information

Ohio Department of Health, Bureau of Environmental Health and Radiation Protection, Radon Licensing Program. School Radon Testing Checklist

Ohio Department of Health, Bureau of Environmental Health and Radiation Protection, Radon Licensing Program. School Radon Testing Checklist Ohio Department of Health, Bureau of Environmental Health and Radiation Protection, Radon Licensing Program School Radon Testing Checklist Purpose: This checklist has been prepared to provide school employees

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

THE RELIABILITY OF RADON REDUCTION TECHNIQUES. CB Howarth

THE RELIABILITY OF RADON REDUCTION TECHNIQUES. CB Howarth Radon in the Living Environment, 052 THE RELIABILITY OF RADON REDUCTION TECHNIQUES CB Howarth National Radiological Protection Board Chilton, Didcot, Oxon, OX11 0RQ, UK Tel: +44 1235 822796, Fax: +44 1235

More information

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617) Unwanted Fire Alarms Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 (617) 984-7463 mahrens@nfpa.org Unwanted fire alarms, however they are defined, are a problem

More information

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS Chainarong Chaktranond *, and Peachrakha Doungsong Department of Mechanical Engineering, Faculty of Engineering,

More information

Data-Driven Energy Efficiency in Buildings

Data-Driven Energy Efficiency in Buildings Data-Driven Energy Efficiency in Buildings Amir Kavousian, PhD Candidate Stanford University February 20, 2013 Photo: David Clanton What is my research about? to demonstrate the power of data mining. [

More information

Community Development and Recreation Committee

Community Development and Recreation Committee STAFF REPORT ACTION REQUIRED Results of the Fire Insurance Grades Study Date: November 20, 2013 To: From: Wards: Reference Number: Community Development and Recreation Committee Fire Chief and General

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 217 Europe July 2-5, 217, Lublin, Poland Paper ID 95 ISBN: 978-83-7947-232-1 Verification of gymnasium designed by high thermal insulation considering elderly people in disaster Koki

More information

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles Available online at www.sciencedirect.com ScienceDirect Agriculture and Agricultural Science Procedia 2 ( 2014 ) 207 211 ST26943, 2nd International Conference on Agricultural and Food Engineering, CAFEi2014

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

1. Select the group that best represents your connection with Eagle Hall.

1. Select the group that best represents your connection with Eagle Hall. University of Wisconsin La Crosse Eagle Hall Thermal Comfort Survey Synopsis and Corrective Action Plan - February 203 I. Background UW-La Crosse s (UW-L) Eagle Hall earned LEED Gold certification in May

More information

Overview: Objectives: Targeted Alaska Grade Level Expectations: Vocabulary: Whole Picture:

Overview: Objectives: Targeted Alaska Grade Level Expectations: Vocabulary: Whole Picture: CONVECTION CONNECTION (MODIFIED FOR ADEED) Overview: In this lesson, students observe convection current by performing two lab experiments. As a result of these activities, students develop an understanding

More information

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way 1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Numbers of Abstract/Session (given by NOC) - 1 - STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Seok Ho Yoon, Kong Hoon Lee, Chan Ho Song, and Ook Joong Kim Environment and Energy

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings

Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings Overview Thermal Comfort Heat Transfer Fans + Air Conditioning Theory Example Scenarios A/C Fans + A/C Application Examples Ancillary

More information

InterNACHI Home Energy Inspection for th Street

InterNACHI Home Energy Inspection for th Street InterNACHI Home Energy Inspection for 1750 30th Street Estimated Yearly Energy Costs: $1,491 per year Dear Client, This house has been scored on a scale of 1 to 100. A 100 would represent a home with perfect

More information

As mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort.

As mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort. Human Comfort Section Preview This section discusses the following topics: Factors of human comfort including air temperature, motion and cleanliness, and the relative humidity of the air HVAC engineering

More information

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE NH Wong, BRJ Huang, KW Tham, C Sekhar and DKW Cheong Dept. Of Building, School of Design and Environment, National University of Singapore, Singapore

More information

Air Movement for Energy-Efficient Comfort in Conditioned Spaces

Air Movement for Energy-Efficient Comfort in Conditioned Spaces Air Movement for Energy-Efficient Comfort in Conditioned Spaces ASHRAE Standard 55-2010: Thermal Comfort Specify the combination of indoor thermal environmental factors and personal factors that will produce

More information

Received: 26 th Feb-2014 Revised: 29 th March-2014 Accepted: 30 th March-2014 Research article

Received: 26 th Feb-2014 Revised: 29 th March-2014 Accepted: 30 th March-2014 Research article Received: 26 th Feb-2014 Revised: 29 th March-2014 Accepted: 30 th March-2014 Research article THE ROLE OF PLANT CLINICS IN INCREASING KNOWLEDGE, ATTITUDE AND SKILLS OF EXPERTS IN COMBATING PLANT PESTS

More information

Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten

Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten Aalborg Universitet Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten Published in: Proceedings of the World Renewable Energy Congress

More information

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL GROUP 1 HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL Daniel Abrahamson Department of Architecture University of Oregon Eugene, Oregon 97403 dva@uoregon.edu Dijon Jones Department of Architecture

More information