Experimental study of space cooling using ceiling panels equipped with capillary mats

Size: px
Start display at page:

Download "Experimental study of space cooling using ceiling panels equipped with capillary mats"

Transcription

1 Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding SUMMARY The purpose of this paper is to investigate the thermal performances and the effect on the thermal comfort of a cooling ceiling installed in an experimental test room called Minibat. With a 9.6m 2 surface and controlling the temperatures on all the exterior walls of the cell, Minibat was the perfect environment for this experimental study. The studied ceiling panels were equipped with capillary mats using polypropylene as material. During the experiment we have analyzed different cases where the ceiling surface temperature varied between 15 C and 19 C. Different parameters like air temperature, humidity or surface temperature were measured during the experiment. To evaluate the thermal comfort we have calculated the PMV value for different chilled ceiling surface temperatures. The results indicate that the cooling ceiling could assure the indoor thermal comfort and with good thermal performances in terms of specific cooling rate or vertical temperature asymmetry. INTRODUCTION The majority of air-conditioning devices function on the principle of pulsated air, where the hot air of the room is recycled, cooled and returned into the room. The increase of the thermal loads in the buildings, mainly due on arrival of data processing and of office computers, the installation of air-conditioning systems was necessary to neutralize these loads and to create a good indoor thermal comfort. Air conditioning systems, which consume large quantities of energy, have become a necessity for almost all the buildings [1] to provide a comfortable indoor environment. Currently the evacuation of these quantities of latent and sensible heats is done mainly with air treated introduced by air diffusers. To maintain comfort under these conditions, a greater volume of cooled air must be provided to the working area. Disadvantages such as noise, cold-drafts, air temperature differences between the human head and foot or energy wasting in certain cases, show that a new cooling system needs to be proposed. The use of water as a coolant to cool surfaces of buildings (ceilings or walls) is consequently a tempting alternative solution. It is even more appealing as water cooling requires much lower flow rates and thus much smaller areas of piping. The chilled ceiling radiant panels are room cooling systems for placement in the ceiling zone. Their cooling surfaces are connected with closed circuit heat conducting pipework containing flowing chilled water. With a cooled ceiling, the temperatures of a room s surfaces are lower than with air-conditioning solutions and the same is true when other partition surfaces are

2 cooled. The principles of cooling ceilings are not very different from those of a radiator with tubes or hotplates. The hot air arriving in contact with the cooled surface is cooled below the average temperature of the room and therefore descends at low speed into the occupation zone [2, 3]. The main difference between cooling ceilings and air-conditioning systems is the mechanism of heat transportation. Air-conditioning using air employs convection only, while cooled ceilings employ a combination of radiation and convection. With cold ceilings, the transfer of radiant heat occurs by a clear emission of electromagnetic waves from the hot occupants and their environments to the radiant ceiling. The sensation of comfort produced by a cold ceiling can be compared to that felt during a summer night where one feels the freshness of the sky even if the ambient air temperature can be higher than 26 C so when using a chilled ceiling it is possible to get the same conditions of comfort with more elevated air temperatures than a classical air-conditioning system [5]. With a cooling ceiling the temperature of water or its flow rate can be varied so that the surface temperature is adapted to the desired conditions. However the many advantages on thermal comfort [4] or energy reduction [5], the cooling ceiling has not reached its full potential because of the condensation risk on the chilled surface. To prevent the risk of condensation on the chilled water pipes or radiant surfaces, the water flow temperature should not be below 16 C. The dew point temperature of the indoor air must always be lower than the surface temperature of the cooling ceiling, this being a reliable way to avoid condensation. For a more precise protection dew point detectors can be installed at the coldest point on the flow pipe of the cooling ceiling installation. They indicate the beginning of condensation at an early stage and trigger an increase in supply water temperature or a chilled water supply shutoff. To reduce the dew point temperature and assure the hygienic quality of the indoor air it is necessary to have a ventilation system to bring fresh air in the occupancy area. This article purpose is to present an experimental study on a chilled ceiling installed in a test cell called Minibat. The main aims were to analyze the vertical temperature asymmetry and the thermal comfort. By taking measurements of air temperature, relative humidity or surface temperature we have been able to give relevant and realistic conclusions on this subject. THE EXPERIMENTAL SET-UP The experimental cell Minibat, presented in Figure 1, is composed of two identical parts which dimensions are 3.10m x 3.10m x 2.50m respectively to (x, y, z). In our study we have used the test cell number 2 where we have installed the radiant cooling ceiling panels. The glazed façade separates Minibat from a climatic chamber whose temperature is controlled and can vary between -10 C and 40 C. A thermal guard allows keeping the five others faces at a constant temperature, which can vary between 5 C and 30 C. During our tests, the thermal guard temperature was kept at 26 C. A battery of 12 spotlights, of 1000W each one, not used in this study, makes it possible to simulate an artificial sunning (gas-discharge lamps with metal halides which spectrum is similar to the sun one). All the faces temperatures are measured using thermocouples of resolution ±0.4 C, and each face with 9 thermocouples. The temperatures of the climatic chamber and the various parts of the thermal guard are measured using Pt100 probes which resolution is of ± 0.3 C.

3 z y Cell 1 Cell 2 Φ VERTICAL VIEW Figure 1. Experimental test cell Minibat HORIZONTAL VIEW 23 Table 1 presents the structure of the wall, ceiling and floor of the experimental test chamber. The cooling ceiling panels are metallic and are insulated with 8 cm foam to reduce the heat losses. These one have been added on the lower face of the existing ceiling. Table 1. Composition of the test cell Minibat (before adding the cooling ceiling) Wall Material λ ρ Thickness [W/m C] [kg/m³] [mm] Floor concrete Wall plaster plate insulated material plaster plate wood plate Ceiling plaster plate wood plate insulated material wood For the data acquisition we have used a computer and a multifunction board with more than 100 connections. To measure the indoor humidity we have used a humidity sensor placed at the centre of the room with a precision of ± 2.5% for measurement of relative humidity between 10 and 90%. A globe temperature is also measured at the center of the room. Concerning the cooling ceiling, we have used 9 panels equipped with capillary mats and being placed only in cell 2. The exterior diameter of the tubes is 3mm and they are spaced by 1.5cm. An indoor heat gain of 250W was installed in the test cell which has a surface of 9.61m 2. To measure the vertical asymmetry of temperature we have taken measurements for six points of height. Several tests were done by modifying the surface temperature of the cooling ceiling in order to see the effect on the thermal comfort or the vertical asymmetry.

4 RESULTS The temperature of the thermal guard was set to 26 C during the whole experimentation. It was observed that there were variations but with a maximum of 1 C due to the system controller but which we have considered totally acceptable. Figure 2 presents the temperature for different heights on the exterior and interior walls surfaces of the test cell. Exterior walls (thermal guard) Interior walls (cooling ceiling activated) Figure 2. Temperature variation against the walls during the experiment Being surrounded by surfaces that have large temperature differences (cooling ceiling and the walls in our case) may be a cause of discomfort, even when the air temperature is considered in the comfort zone. These conditions of discomfort are frequently caused by cold windows, un-insulated walls or direct sunlight. In general, people are more sensitive to asymmetric radiation caused by a warm ceiling than that caused by warm vertical surfaces [7]. Figure 3. Thermal screenshots of the cooling ceiling during the experiment The temperature on the surface of the chilled ceiling is relative constant on each panel, except the connection between them (see Figure 3). A reason that temperature on the surface is not perfectly uniform could be that a gap of air was formed between the tubes and the metallic panels and acting like an insulation on some areas.

5 Figure 4. Specific cooling power of the cooling ceiling in function of the difference between the mean water temperature and the air temperature The cooling power of a radiant ceiling (RC) system is a function of the heat transfer between the room and the cooled ceiling. This heat transfer has two components: radiation and convection which can be calculated. In Figure 4 is presented the specific cooling power of the chilled ceiling depending on the difference of the mean water temperature which was measured during the experiment and the air temperature. The specific cooling power of a cooled ceiling can be expressed by the following empirical equation: q = 8.92 (t air -t cold surface ) 1.1 where q is the sum of the convective and radiant heat transfer [W/m 2 ] t air is the air temperature of the room [ C] t coldsurface is the temperature of the cooling ceiling [ C] A large vertical air temperature difference between the head and ankles may be also a discomfort cause. Based on criteria of 5% dissatisfied, the allowable temperature difference is 3 C, which applies for situations where the temperature increases with height from the floor (i.e., the head is warmer than the feet). With a cooling ceiling the temperature decreases when we are approaching the chilled ceiling height and when the temperature of the ceiling is low enough we can even sense the refreshment on the body skin. The results indicate that in the centre of the test cell, the stratification is acceptable and is smaller than the 3 C limit imposed by standards. In Figure 5 it can be observed the vertical temperature asymmetry for three different cooling ceiling temperatures. In all the cases the difference between the ankle and the head is about 1 C. The data presented in Figure 4 was obtained by measuring the temperature in six points of height, from 0.4m to 2.3m. The time step of one measure was of 45 seconds which correspond to the minimum imposed by the acquisition system to pass throw all the measurements including air and surface temperatures, water temperature, relative humidity or globe temperature. We can conclude on this part that the cooling ceiling don t create discomfort in the working area but the need of taking

6 measurements also near the walls seems necessary to be done. All the temperatures were measured by thermocouples type K with a precision of ± 0.3 C. Figure 5. Vertical temperature asymmetry in the centre of the test room for different ceiling temperatures Thermal comfort is very difficult to define because we need to take into account a range of environmental and personal factors when deciding on the temperatures or the ventilation that will make a comfortable indoor space. The best that we can realistically hope to achieve is a thermal environment which satisfies the majority of people or the so called reasonable comfort. In order to analyze the thermal comfort in a room cooled by a chilled ceiling we have taken measurements of air temperature, globe temperature, relative humidity and surface temperatures (9 thermocouples per internal surface of the room). By simulating the test cell using the computational fluid dynamics (CFD) we have estimated the air velocity inside the room. The PMV (Predicted Mean Vote) [6] was calculated by using the data obtained after the tests. The PMV index establishes a thermal strain based on steady-state heat transfer between the body and the environment and assigns a comfort vote to that amount of strain. Figure 6. Relative humidity and globe temperature when using the cooling ceiling at 18.8 C In Figure 6 are presented the evolutions of relative humidity and the globe temperature during more than 12 hours of experimentation. We can observed that the relative humidity was stabilized at a value of 43.5% and the globe temperature at 25 C when using the chilled ceiling at 17.4 C. The PMV equation for thermal comfort is a steady-state model. It is an empirical equation for predicting the mean vote on an ordinal category rating scale of thermal

7 comfort of a population of people. The air velocity was considered after the CFD simulations of 0.15 m/s, the rest of parameters influencing the thermal comfort being measured. In Figure 7 it can be observed that the PMV index for different clothing insulations when using the cooling ceiling surface at different temperatures. We have only presented two cases of ceiling surface temperature which were the more relevant, knowing that in general the cooling ceiling temperature must be kept at higher values than the dew point temperature of the indoor air in order to avoid the condensation risk. Figure 7. PMV for different clothing insulation when using the cooling ceiling at different temperatures The values presented in Figure 7 show that the cooling is a very attractive solution for the thermal comfort. It can be observed that when the cooling ceiling temperature is at 17.4 C and when the metabolism is 1.2 met (70W/m 2 ) and the clothing insulation is 0.9 clo the obtained value of PMV is in the limit proposed by the norms. DISCUSSION The results obtained after the experiment showed that with a cooling ceiling the vertical temperature asymmetry is less than 1.1 C, acceptable value which not create a discomfort in the occupancy zone. Another important aspect of the test was the effect of the chilled ceiling on the thermal comfort. The temperature of the ceiling was changed in order to see the effect on the thermal comfort, the results being very satisfying. The PMV was calculated for different clothing insulation, its values fulfilling the limits imposed by the standards. These discussions prove that ceiling radiant cooling systems can be more comfortable than conventional air cooling systems, due to less air movement, minimal vertical air temperature difference and with good results on the thermal comfort even for higher values of the ceiling temperature. However the big amount of data obtained more extensive experimental test research are sorely needed especially on the condensation risk problems or the effect of hygroscopic materials on the thermal performances.

8 REFERENCES 1. L.Z. Zhang, J.L. Niu, Indoor humidity behaviors associated with decoupled cooling in hot and humid climates, Building and Environment 38 (2003) Plafonds froids et introduction d air laminaire (Cold Ceilings and Laminar Introduction of Air), P.Pepinster, Division St-Group Technical Facilities Management (ST/TFM) CERN, Geneva (Switzerland) 3. Systèmes de rafraîchissement par le plafond (Systems of cooling by the ceiling), Chaud, froid, plomberie (Heat, cold, plumbing) N 607 November 1998; 4. T. Catalina, J.Virgone, J.J. Martin, B. White, F. Kuznik, Simulation of the ambient comfort of a cooling ceiling integrated into a room, Aicaar, Milano, April T. Catalina, J.Virgone, Evaluation of performances, thermal comfort and energy consumption of a reversible radiant ceiling by capillary mat: application for the prefabricated buildings, EPIC Lyon, November ISO 7730 (1994) Moderate Thermal Environments - Determination of the indices PMV and PPD and specifications of the conditions of thermal comfort 7. C. Huizenga, H. Zhang, P. Mattelaer, T. Yu, E. Arens, P. Lyons, Window performance for human thermal comfort, University of California, Berkley, Arup Façade Engineering BIBLIOGRAPHY 1. ASHRAE (1992) Thermal environmental conditions for human occupancy ANSI-ASHRAE, Standard ASHRAE , Heat Transfer and Thermodynamics, F.Kreith 1967, University of Colorado 3. ASHRAE (1993) Thermal Physiological Principles and Comfort, ASHRAE Fundamentals Handbook Chapter 8, Atlanta (USA): American Society of Heating, Refrigerating and Air- Conditioning Engineers Inc, 1993

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

A study of radiant cooling for a room with daytime application in tropical climate

A study of radiant cooling for a room with daytime application in tropical climate International Journal of Smart Grid and Clean Energy A study of radiant cooling for a room with daytime application in tropical climate Satinee Wongkee, Surapong Chirarattananon, Pipat Chaiwiwatworakul

More information

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts Article Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts Building Serv. Eng. Res. Technol. 206, Vol.

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International

More information

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER 2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

More information

Thermal Comfort with Convective and Radiant Cooling Systems

Thermal Comfort with Convective and Radiant Cooling Systems Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING G. COURRET, P. W. EGOLF, O. SARI Haute école spécialisée de Suisse occidentale, Institut de Génie Thermique, Rte de Cheseaux 1, CH

More information

Comparison of radiant and convective cooling of office room: effect of workstation layout

Comparison of radiant and convective cooling of office room: effect of workstation layout Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;

More information

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Vladimír Zmrhal Czech Technical University in Prague, Faculty of Mechanical Engineering Corresponding email: Vladimir.Zmrhal@fs.cvut.cz

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue

More information

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

International Forum on Energy, Environment Science and Materials (IFEESM 2015) The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,

More information

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Bill Rittelmann, IBACOS Building Enclosure Technology and

More information

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

Air Movement for Energy-Efficient Comfort in Conditioned Spaces

Air Movement for Energy-Efficient Comfort in Conditioned Spaces Air Movement for Energy-Efficient Comfort in Conditioned Spaces ASHRAE Standard 55-2010: Thermal Comfort Specify the combination of indoor thermal environmental factors and personal factors that will produce

More information

Experimental study of fan coil assisting radiant floor heating system

Experimental study of fan coil assisting radiant floor heating system Journal of Scientific Research and Studies Vol. 4(12), pp. 394-401, December, 2017 ISSN 2375-8791 Copyright 2017 Author(s) retain the copyright of this article http://www.modernrespub.org/jsrs/index.htm

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

How to ensure Thermal Comfort in buildings with CFD

How to ensure Thermal Comfort in buildings with CFD How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD

More information

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,

More information

Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings

Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings Sustainable HVAC Design: Using Air Movement in Air Conditioned Buildings Overview Thermal Comfort Heat Transfer Fans + Air Conditioning Theory Example Scenarios A/C Fans + A/C Application Examples Ancillary

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

ENERGY EFFICIENCY BRIEF REPORT

ENERGY EFFICIENCY BRIEF REPORT ENERGY EFFICIENCY BRIEF REPORT 1 Odooproject s energy efficient building design was mainly formed by the tight interaction of students from the Faculty of Architecture and the Faculty of Mechanical Engineering

More information

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN

More information

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity COOLING AND HEATING OF BUILDINGS BY ACTIVATING THE THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS EMBEDDED PIPE SYSTEMS Bjarne W. Olesen, Ph.D., Head of R&D, Wirsbo-VELTA, Germany Professor, Technical

More information

,Chaojian He6, f. School of Guangxi University, Nanning , China.

,Chaojian He6, f. School of Guangxi University, Nanning , China. 5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) The Research on Running Characteristics of A New Type of Radiant Air Conditioning Combined with Fresh

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

The thermal performance of green roofs in a hot, humid microclimate

The thermal performance of green roofs in a hot, humid microclimate Sustainable Development and Planning VI 475 The thermal performance of green roofs in a hot, humid microclimate U. D Souza F-o-CUS: Focus on Construction Urbanism Sustainability, UAE Abstract Green roof

More information

DYNAMIC THERMAL MODELING OF A RADIANT PANELS SYSTEM AND ITS ENVIRONMENT FOR COMMISSIONING: APPLICATION TO CASE STUDY

DYNAMIC THERMAL MODELING OF A RADIANT PANELS SYSTEM AND ITS ENVIRONMENT FOR COMMISSIONING: APPLICATION TO CASE STUDY DYNAMIC THERMAL MODELING OF A RADIANT PANELS SYSTEM AND ITS ENVIRONMENT FOR COMMISSIONING: APPLICATION TO CASE STUDY Nestor Fonseca Diaz PhD Student Facultad de Ingenieriá Mecánica Universidad Tecnológica

More information

Halton Vario Design Guide

Halton Vario Design Guide Halton Vario Design Guide Enabling Wellbeing Table of contents 1. Halton Vario - ventilation and air conditioning system overview 3 1.1 Room level, Zonal level and central level 4 1.2 Flexible design and

More information

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation and Design Optimization of Refrigerated Display

More information

The Corbioli House is a single-family house situated

The Corbioli House is a single-family house situated All-in-one high-performing system for ZEB houses Maria Ferrara Grant researcher TEBE Research Group Energy Department Politecnico di Torino at Turin, Italy maria.ferrara@polito.it Frederic Kuznik Full

More information

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

Thermal Environment Evaluation in Commercial Kitchens of United States

Thermal Environment Evaluation in Commercial Kitchens of United States Downloaded from orbit.dtu.dk on: Jul 25, 2018 Thermal Environment Evaluation in Commercial Kitchens of United States Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation

More information

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT Ashak Nathwani AM Adjunct Senior Lecturer ashak.nathwani@sydney.edu.au PRESENTATION THREE SESSIONS This presentation will be in three parts addressing

More information

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca

More information

ω = (1) Kirby S. Chapman Ph.D.

ω = (1) Kirby S. Chapman Ph.D. White Paper: Relative Humidity Impacts of the AirFloor System in the Built Environment Kirby S. Chapman Ph.D. kirby.chapman@scavengetech.com Introduction Relative humidity is specified as one of the seven

More information

Section 9. Comparing Energy Consumption: More for Your Money. What Do You See? What Do You Think? Investigate. Learning Outcomes

Section 9. Comparing Energy Consumption: More for Your Money. What Do You See? What Do You Think? Investigate. Learning Outcomes Section 9 Comparing Energy Consumption: More for Your Money Section 9 Comparing Energy Consumption: More for Your Money What Do You See? Learning Outcomes In this section, you will Measure and compare

More information

Chapter 10. Passive Cooling Contents

Chapter 10. Passive Cooling Contents Chapter 10. Passive Cooling Contents 10.1 Introduction to Cooling 10.2 Historical and Indigenous Use of Passive Cooling 10.3 Passive Cooling Systems 10.4 Comfort Ventilation VS Night Flush Cooling 10.5

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: januar 28, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen * Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement

More information

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM STUDY ON A FLOOR SULY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED CM S. Takeda, K. Nagano, K. Nakayama, K. Shimakura Hokkaido University Sapporo, 060-8628 Japan Tel: +81-11-706-7597

More information

Space Air Diffusion II

Space Air Diffusion II MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong

More information

Air and operative temperature measurements in a plus-energy house under different heating strategies

Air and operative temperature measurements in a plus-energy house under different heating strategies Downloaded from orbit.dtu.dk on: Oct 03, 2018 Air and operative temperature measurements in a plus-energy house under different heating strategies Kazanci, Ongun Berk; Olesen, Bjarne W. Published in: Proceedings

More information

System technology. System technology. List of contents

System technology. System technology. List of contents System technology ---------------------------------------------------------------------- System technology System technology List of contents INDOOR CLIMATE HEAT TRANSFER CLIMATE CONCEPTS COMFORT COOLING

More information

C o o l i n g a n d h e a t i n g s y s t e m s

C o o l i n g a n d h e a t i n g s y s t e m s 2 C o o l i n g a n d h e a t i n g s y s t e m s Cooling ceiling system description Preliminary remarks Cooling ceilings Cooling ceilings are room cooling systems for placement in the ceiling zone. Their

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek

More information

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Haiye Lou TurboMoni Applied Dynamics Lab Abstract It is often happened, when a project

More information

Cooling load calculations of radiant and all-air systems for commercial buildings

Cooling load calculations of radiant and all-air systems for commercial buildings Downloaded from orbit.dtu.dk on: Aug 17, 2018 Cooling load calculations of radiant and all-air s for commercial buildings Bourdakis, Eleftherios; Bauman, Fred; Schiavon, Stefano; Raftery, Paul; Olesen,

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina Department of Mechanical Engineering, Faculty of Engineering, King Mongkut

More information

Heat transfer and heating rate of food stuffs in commercial shop ovens

Heat transfer and heating rate of food stuffs in commercial shop ovens Sādhanā Vol. 32, Part 5, October 2007, pp. 535 544. Printed in India Heat transfer and heating rate of food stuffs in commercial shop ovens P NAVANEETHAKRISHNAN,PSSSRINIVASAN and S DHANDAPANI Department

More information

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing Vipac Engineers & Scientists DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption The physical testing Sydney 16 August 2016 Introduction to Vipac AGENDA

More information

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS Stefano Schiavon, Ph.D., P.E. Center for the Built Environment, University of California at Berkeley, Member ASHRAE

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

ENSC 388: Engineering Thermodynamics and Heat Transfer

ENSC 388: Engineering Thermodynamics and Heat Transfer ENSC 388: Engineering Thermodynamics and Heat Transfer Experiment 3: Free and Forced Convection Objective Determination of heat transfer coefficient for free and forced convection for different geometries.

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009

More information

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY M Kojima, T Saito Graduate School of Environmental Studies, NAGOYA University, Chikusa, Nagoya, 464-8603

More information

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI International Journal of Scientific & Engineering Research Volume 9, Issue 4, April-2018 238 ANALYSIS OF RADIANT COOLING IN CONCRETE SLABS WITH EMBEDDED PIPES ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA

More information

API MANUAL OF PETROLEUM MEASUREMENT STANDARDS

API MANUAL OF PETROLEUM MEASUREMENT STANDARDS API MANUAL OF PETROLEUM MEASUREMENT STANDARDS Chapter 22 Testing Protocols Section 1 General Guidelines for Developing Testing Protocols for Devices Used in the Measurement of Hydrocarbon Fluids Type Testing

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

American Society of Heating, Refrigerating and Air-Conditioning Engineers

American Society of Heating, Refrigerating and Air-Conditioning Engineers Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:

More information

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER WULANDANI, D., K. ABDULLAH, E. HARTULISTIYOSO Department of Agricultural Engineering, Faculty of Agricultural

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

Unit 4: Science and Materials in Construction and the Built Environment. Thermal Comfort

Unit 4: Science and Materials in Construction and the Built Environment. Thermal Comfort 2.1 Introduction Thermal Comfort The thermal comfort of human beings is governed by many physiological mechanisms of the body and these vary from person to person. In any particular thermal environment

More information

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Koji Fujita, Graduate Student, Graduate School of Science and Technology, Kobe University; 039d892n@stu.kobe-u.ac.jp Atsushi

More information

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total. 1. State 2 75 o F Exhaust M amb T amb State 3 Room Q chiller State 1 60 o F M total A room at steady state has a supply air stream of cool air entering at 60 o F. The lights, office appliances and people

More information

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection DS 4094 E 05.2007/1 Technical Selection Main features 2 Preliminary remarks 3 Construction design 3 Main dimensions and materials 3 Design data 3 Layout example 5 Design specifications 8 Installation instructions

More information

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Journal of Electronics and Information Science (2018) 3: 22-33 Clausius Scientific Press, Canada Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Lian-Tuu Yeh, ASME Fellow

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Compression of Fins pipe and simple Heat pipe Using CFD

Compression of Fins pipe and simple Heat pipe Using CFD Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages

More information

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION Kuklane, Kalev Published in: [Host publication title missing] Published: 2014-01-01 Link to publication Citation for published

More information

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection Finned s for Cooling Outdoor Electronics under Natural Convection Lian-Tuu Yeh, Ph D & PE Thermal Consultant, Dallas, TX, 75252 USA Abstract For tower or poled mounted electronics, the heat sink weight

More information

The Use Of Attic Space For Cooling and Dehumidification

The Use Of Attic Space For Cooling and Dehumidification Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Use Of Attic Space For Cooling and Dehumidification H. F. Abaza Virginia

More information

* Currently, lecturer at the Department of Architecture, The University of Adelaide. Adelaide. South Australia.

* Currently, lecturer at the Department of Architecture, The University of Adelaide. Adelaide. South Australia. THERMAL COMFORT STUDY IN A NATURALLY VENTILATED RESIDENTIAL BUILDING IN A TROPICAL HOT-HUMID CLIMATE REGION Veronica I. Soebarto* and Siti Handjarinto Department of Architecture University of Indonesia

More information

As mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort.

As mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort. Human Comfort Section Preview This section discusses the following topics: Factors of human comfort including air temperature, motion and cleanliness, and the relative humidity of the air HVAC engineering

More information

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena Proceedings of the World Congress on Mechanical, Chemical, and Material Engineering (MCM 2015) Barcelona, Spain July 20-21, 2015 Paper No. 276 The Experimental Validation of Numerical Modeling of the Air

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

AR/IA 241 LN 231 Lecture 6: Passive Cooling

AR/IA 241 LN 231 Lecture 6: Passive Cooling Faculty of Architecture and Planning Thammasat University AR/IA 241 LN 231 Lecture 6: Passive Cooling Author: Asst. Prof. Chalermwat Tantasavasdi 1. Passive Cooling Methods and Application Passive cooling

More information

Effect of acoustical canopies and fans on acoustical and chilled ceiling performance

Effect of acoustical canopies and fans on acoustical and chilled ceiling performance Effect of acoustical canopies and fans on acoustical and chilled ceiling performance Fred Bauman and Caroline Karmann Center for the Built Environment, University of California, Berkeley Golden Gate and

More information

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way 1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2 01-014 The 2005 World Sustainable Building Conference, DEVELOPMENT OF A PASSIVE COOLING STRATEGY USING DOUBLE-ROOFING SYSYTEM WITH RAINWATER SPRAYING AND ITS FIELD TESTING IN TERMS OF THE INDOOR THERMAL

More information

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan

More information

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system Zhang, C., Heiselberg, P.K., Chen, Q., and Pomianowski, M. 2017. Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system, Building Simulation, 10(2): 203-218.

More information