STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

Size: px
Start display at page:

Download "STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM"

Transcription

1 STUDY ON A FLOOR SULY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED CM S. Takeda, K. Nagano, K. Nakayama, K. Shimakura Hokkaido University Sapporo, Japan Tel: sayakat@eng.hokudai.ac.jp T. Nakamura Shimizu Corporation Tokyo, Japan 1. INTRODUCTION The peak demand for electricity during hot summer is increasing year by year and the daytime load has become double that of nighttime in the Metropolitan area of Japan, [TECO, 2004]. The main reason for this is air conditioning of commercial buildings. Therefore one policy to reduce the peak demand would be to produce and use electricity at night and store cold thermal energy in order to reduce the daytime air conditioner load. This would not only reduce the cost to consumers by allowing them to use cheaper nighttime electricity but would also avoid the need for capital investment in new electricity power plants. Moreover this would bring reduction of CO 2 emission due to decrease of peak power generation supplied by oil-fired thermal power plants. Building mass thermal storage is a means of thermal energy storage, which makes use of concrete building slabs as a medium [ASHRAE, 2003]. This can avoid large storage tanks and space required by ice or water storage. Generally it uses the space above ceilings or below free access floors so is mainly used in conjunction with ceiling or floor air conditioning systems. The authors have focused on the floor supply air conditioning system in which air is supplied to a room through porous OA floor boards and a permeable carpet rather than via vents in the floor [Akimoto et al., 1995]. Demonstrated advantages of such systems are that they push air upward without blowing dust or other debris around and do not cause uncomfortable drafts. However, when a floor supply air conditioning system incorporates building mass thermal storage, owing to cooling of the floor boards during night, the region near the floor may be perceived as too cold when the system is first turned on in the morning. This is a disadvantage that needs to be improved. Furthermore, with current building mass thermal storage systems, the limited thermal capacity makes it difficult to maintain cooling during afternoons. To overcome this, we have proposed a novel building mass thermal storage based on a floor supply air conditioning system which incorporates latent heat storage to increase the total cold storage capacity [Nagano et al., 2006]. A concept diagram of the proposed system is shown in Figure 1. In this system, latent heat is stored in phase change material (abbreviated below as CM) that is embedded directly under OA floor boards in the form of granules several millimeters in diameter. This CM packed bed is permeable to air so is suitable for use in the floor supply air conditioning system. During night, circulation of cool air through the under floor space allows cold energy to be charged to the concrete slab, OA floor board and CM packed bed. On the other hand, they in turn can be used to remove the cooling load in the room during the daytime. In this paper, the authors describe a demonstration system that simulates an air conditioning system in office buildings. An appropriate experimental condition is determined by a numerical analysis with varying temperature conditions during night and comparing the thermal characteristics of each storage mass and thermal environment in the room space. Then possibility whether the whole cooling load can be covered only by the stored heat during night in the suitable condition is confirmed through the demonstration. Moreover, voting about thermal sensation and comfort sensation is carried out with some subjects, in which improvement of excessive cooling near the floor in previous systems is clarified by use of the granulated CM.

2 Ceiling space Ceiling space Room space Under floor construction Breathable carpet OA floor board Granulated CM Cooling load (Sensible heat) Room space Metal stand Under floor space FAN FAN Concrete slab Floor supply air conditioning [N-Mode: Cold storage during night] AHU Air filter [D-Mode: Discharge during the daytime] AHU Air filter Figure 1 Concept diagram of the proposed system 2. OUTLINE OF THE COOLING SYSTEM 2.1. Experimental testing room Figure 2 shows a plan of the environmental testing room. The room consists of a test room and a utility space. The floor, the walls and the ceiling are made of hard urethane foams, which the thicknesses are 89 mm and the heat conductivity is 28 W/m 2 /K. The floor space is 9.2 m 2. Cold water which is supplied by a hot and cold water generator is used for cooling of the testing room. Hot water is used for warming of the utility space. Extra heat is exhausted to the outdoor. Six sets of spiral line heaters, which generate heat to simulate the cooling load such as sensible heat from human bodies, OA equipments and solar radiation hourly, are hung from the ceiling in the testing room. Figure 3 is a perspective diagram of the room as seen from the A direction in Figure 2. The structure is a ceiling space, concrete slabs, a CM packed bed, OA floor boards, breathable carpets and a room space from the bottom up. Each thickness is 200 mm, 120 mm, 100 mm, 30 mm at the maximum, 23 mm, 5 mm and 2120 mm respectively. Six openings are provided on the wall. Ventilation routes which simulate ones during day and night can be changed by switching four dampers. Cold air is entered to O1 and flowed out from O2 during the period of cold energy Cold water G Outdoor Indoor CB S O3 7 Hot water Utility space 3520 Window 2120 Exhaust A F M Door Window Testing room 9.15 m 2 Door 2600 O2 O4 O6 O1 O Notes: CB: Control board, F: Fan, G: Hot and cold water generator, : Heat exchanger, M: Flow rate meter, : ump, S: ower supply Figure 2 Schematic diagram and plan of the room Notes: O: Opening, 1: Ceiling space, 2: Concrete slab, 3: Under floor space, 4: CM packed bed, 5: OA floor board, 6: Breathable carpet, 7: Room space Figure 3 erspective diagram of the room as seen from the direction A

3 storage, called N-Mode. O6 is another exhaust opening and is used under conditions in which air is let also into the room space in order to augment the stored heat for CM. On the other hand, during the daytime called D- Mode, air entered from O1 is completely flowed upward into the room space and exhausted from O3 at the top of the room. The air is returned to the ceiling space and exchanges heat between the back side of the concrete slab. 2.2 Characteristics of FMC-CM FMC (Flocculated Micro-Capsule)-CM has been applied to the system as a granulated CM in this system. FMC-CM which was introduced to the previous study showed lower phase change temperature than the appropriate one and couldn t provide improvement of thermal environment in the morning [Takeda et al., 2004]. Thus, FMC-CM which has suitable phase change characteristics is applied in this experiment. Figure 4 shows results of DSC measurements at different temperature changing rates. hase changes of the melting and solidification processes were started around 17.9 ºC to 18.3 ºC and 21.1 ºC to 21.4 ºC, respectively. The difference of specific enthalpy between 15 ºC and 21 ºC was 110 kj/kg on the average. The FMC-CM has a diameter of around 2 mm and an average length of 2 mm. A packed bed of the FMC-CM was supported by a wire netting basket and placed beneath OA floor boards as shown in Figure 5. The packed amount was 12.5 kg/m 2 and the OA floor board (23mm) Breathable carpet (5mm) Temperature changing rate: [K/min] 1500 DSC signal output [µw/mg] Melting process Temperature [ºC] Figure 4 DSC curves of the FMC-CM thickness was around 25 mm. Solidification process Granulated CM (25mm) Concrete slab (120mm) Under floor space (100mm) Figure 5 Construction under the floor in the experimental 3. DEMONSTRATION EXERIMENT USING FMC-CM 3.1 Discussion about storage condition by computer simulation Outline of the computer simulation program The computer simulation program reported in the previous paper solves heat balance equations for each storage mass: granulated CM, concrete and OA floor board, and for each space: room, under floor and ceiling [Takeda et al., 2003]. The program can be used for a two dimensional area as shown in Figure 1. The program also calculates radiative heat transfer between each wall, floor and ceiling surfaces. The angle factor is derived by the net energy exchange, which is the rate of emission of the surface minus the total rate of absorption at the surface from all radiant effects in its surroundings, including the return of some of its own emission by reflection off its surroundings. In addition, a rectangular parallelepiped human model is positioned to simulate a seated person in the center of the room space and radiant heat exchanges are calculated among the surfaces [Horikoshi et al., 1978].

4 Thermal comfort in the room is evaluated by the MV index with a thermal insulation of clothing of 0.7 clo and a relative humidity of 50 % as standard values in summer.

5 3.1.2 arameters used in the simulation program Here, suitable experimental conditions are verified by the computer simulation. Supply air temperature in the under floor space during the N-Mode (T 1in-N ) is varied from 10 ºC to 15 ºC as a parameter. The calculated subject is the experimental testing room as shown in Figure 2. N-Mode is for 9 hours from 22:00 to 7:00 with a ventilation time of 12 times/hour. 70% of the air is circulated in the under floor space and the rest is supplied to the upper direction in order to permeate air space between CM granules and to enhance the stored heat in CM, which is embedded upward to the under floor space. On the other hand, the D-Mode is set for 12 hours from 8:00 to 20:00. The internal heat generation is given as the same as that from the experiment. Air flow rate is changed according to the heat load so that average room temperature at 1.1m high from the floor surface is kept below a set temperature 27.5 ºC. An air conditioner starts to operate when the temperature increases over the set temperature. The characteristics of CM granules are determined from the DSC measurements, such as the phase change range from 18.0 to 21.3 ºC and latent heat amount of 120 kj/kg Results and discussion In each figure of Figure 6, variations of stored heat during night, air conditioner load, load shifting rate and MV at 9:00 are plotted according to T 1in. The top figure shows that stored heat runs short to cover the cooling load during the daytime and decreases with increasing T 1in. Air conditioner load appears in the daytime at T 1in values higher than 13 ºC. Load shifting effect also decreases to less than 0.8 at 15 ºC of T 1in. On the other hand, complete load shifting effect can be observed at lower T 1in such as 10 ºC or 11ºC, while MV drops gradually and results in a slightly cool thermal sensation because of excessive cooling of the sensible thermal storage masses during night. MV remains relatively steady around 0.7 to 0.6 at T 1in values higher than 12 ºC in these calculations. From a condensation point of view, T 1in should be kept at least above 11ºC. Therefore, T 1in conditions between 12 ºC and 13 ºC could provide sufficient storage performance as well as comfortable thermal environment in the following experiment. Stored heat, Air conditioner load [MJ/m 2 ] Load shifting rate [-] MV (9:00) [-] Daytime Nighttime T 1in [ C] Heat loss OA floor board CM Concrete Neutral Slightly cool Cool Cold Figure 6 Variations of stored heat during night, air conditioner load, load shifting rate and MV at 9:00 vs supply air temperature T 1in

6 3.2 Experimental results and discussion Storage performance Demonstration experiments are conducted under the same conditions as ones used in the calculation above. The following results are ones in the 3 rd day and almost in periodical steady states. One result indicates internal heat generation in the room of 2.42 MJ/m 2 and heat gain through surrounding walls of 5 MJ/m 2 and then the total amount of them, that is, daily cooling load, of 2.47 MJ/m 2. Air conditioner load doesn t cause at all during the daytime and the whole cooling load can be covered by the stored cold energy during night. Shown in Figure 7 and Figure 8 are hourly variations of stored heat in each storage mass and stored heat at the end of N-Mode, 7:00. The sum of the stored heat shows nearly equal storage and discharge amounts in one day. Stored heat in the nighttime is 1.11, 1.08 and 0.18 MJ/m 2 in concrete, granulated CM and OA floor board, respectively and is 2.38 MJ/m 2 in total, which nearly reaches the daily cooling load. Stored heat [MJ/m 2 ] OA floor board -0.5 CM Concrete Sum [N-Mode] [D-Mode] 0:00 4:00 8:00 12:00 16:00 20:00 24:00 Figure 7 Hourly variations of stored heat in each storage mass Stored heat during night [MJ/m 2 ] OA floor board CM Concrete 1.16 Experiment Calculation Figure 8 Stored heat during N-Mode Thermal environment in the room Shown in Figure 9 are hourly variations of supply air temperature (T 1in ), surface temperature of the carpet in the center of the room space and air temperature at 1,050 mm high from the floor, which are measured by T type thermocouples. Supply air temperature keeps 12.5 ºC on average during the N-Mode. It can be seen that the temperature falls in the suitable condition described above. The variation of the surface temperature always remains 1 to 3ºC lower than that of the room temperature due to influence of cooled air supplied from the under floor. Vertical distributions of air temperature in the room space are indicated in Figure 10. ISO7730 recommends a temperature difference between 0.1 m high around an ankle and 1.1 m high around a head for a seated person to be within 3 ºC [ISO, 1994]. In this experiment, temperature differences between 0.1 m high and 1.1 m high are 0.7 ºC, 2.4 ºC and 3.0 ºC at 8:00, 10:00 and 12:00 respectively. These values can meet the requirement. Figure 11 also indicates distributions of floor surface temperature taken by an infrared camera. It is seen that the floor surface temperature measured by a thermocouple is 22.1 ºC at 8:00, which is almost the same as the average one taken by the camera. However, the temperatures measured by thermocouples are 22.7ºC and 23.1 ºC at 10:00 and 12:00. These are 0.7 to 1.0 ºC lower than the average temperatures by the camera. It is possible that spiral line heaters, which simulate the cooling load, influence radiative environment on the floor surface Comparison with calculation Comparison between the calculation and the experiment is shown with respect to stored heat during night and the average floor temperature in Figure 8 and Figure 10, respectively. The stored heat from calculation almost agree with the measured one. The floor temperatures also show close values each other in the morning, in which the differences are within 0.2ºC.

7 Temperature [ºC] [N-Mode] Supply air (T 1in ) Room air [D-Mode] Floor surface 10 0:00 4:00 8:00 12:00 16:00 20:00 24:00 Figure 9 Hourly variations of temperatures 2.0 8:00 10:00 12:00 [8:00] Av.21.9ºC Height from the floor surface [m] :Measured temperatures by thermocouples :Calculated temperatures (8:00) (10:00)(12:00) 0.2ºC 0.1ºC 0.2ºC Temperature [ºC] [Enlarged illustration at the floor surface] Floor surface Temperature [ºC] Figure 10 Vertical distributions of measured temperature and comparison at the floor surface between experiment and calculation [10:00] Av.23.4ºC [12:00] Ave.24.1ºC Figure 11 Floor surface temperature taken by an infrared camera Thermal sensation vote in the room Finally, thermal comfort in this system is examined through thermal sensation vote in the room. The experiment was conducted in July 15th and 16th in Four Japanese young people, three women and a man, were adopted as subjects. Each subject experienced two kinds of condition as shown in Table 1. Case1 is conducted in the morning and Case2 is done in the afternoon. Room temperature in Case1 is 26.3ºC, while that in Case2 is 28.4ºC and relatively high. Table 1 Experimental conditions for thermal sensation vote Case1 Case2 Morning 9:00~10:00 Afternoon 15:30~16:30 Room temp. [ C] Relative humidity [%] Air flow rate [times/h]([cm/s]) 6.3 (0.4) 12.3 (0.8)

8 Two subjects enter the room at the same time for one experiment. Fresh air is supplied to the room at a rate of 40 m 3 /h, which is the amount that two subjects require at least. Women wear an underwear, nylon stockings, a blouse with short sleeves and a light skirt. A man also wears an underwear, socks, a short sleeves shirt, a necktie and a normal trouser. They wear canvas shoes in the room. Total thermal insulation of the clothes is around 0.7 clo per person, which is an ordinary value in summer. The subjects stand by for one hour at a next room air-conditioned at 27 ºC before the experiment and then are exposed for one hour in the testing room in both cases. Thermal sensation vote is given by the subjects every 15 min for one hour. The subjects evaluate thermal sensation and comfort sensation according to the 9-grade and 5-grade respectively. Shown in Figure 12 are distributions of thermal sensation and comfort sensation on average for the whole body in the both case. Figure 13 also indicates average thermal sensations of each part. In Case1, thermal sensations for the whole body range from slightly cool to neutral. The subjects also report that the room is neutral to comfortable at that time. Some of women tell slightly cool at calves but others do neutral sensation. It is likely that uncomfortable sensation near the feet in the morning just after thermal energy storage in the floor supply air conditioning system can be generally improved by the use of CM in this system. In Case2, room temperature at 1.1 m high exceeds 28ºC. This results in the votes of neutral to warm sensation for the whole body and those in the warmer side for all parts of the body. In particular, thermal sensation at the hands or the faces, which are exposed to the environment, seems to lead to slightly uncomfortable sensation from some subjects. Contrary, another subjects show slightly comfortable sensation for the same condition. Therefore, the system can provide acceptable thermal environment on the average also in the afternoon by only discharged coolness from the concrete, OA floor board and granulated CM. Warm 2 Comfortable 2 Slightly warm 1 Slightly comfortable 1 Neutral 0 Neutral 0 Slightly cool -1 Slightly uncomfortable -1 Cool -2 Case 1 Case 2 Morning Afternoon Uncomfortable -2 Case 1 Case 2 Morning Afternoon Figure 12 Distributions of thermal sensation (left) and comfort sensation (right) on the average of the whole body (24.4ºC) (26.3ºC) (23.4ºC) Face Shoulders Upper arms Forearms Hands Back Waist Abdomen Thighs Calves Soles of feet (25.9ºC) (24.9ºC) (28.4ºC) Cool Neutral Warm Cool Neutral Warm [Case1:Morning] [Case2:Afternoon] Figure 13 Thermal sensations of each part on the average of the subjects and air temperature near the position

9 4. CONCLUSIONS The following summarizes the results reported in this paper. 1) A demonstration system is constructed with a floor supply cooling system utilized thermal energy storage for granulated CM as well as for building structure during night in order to evaluate the effect of load shifting to the nighttime and thermal environment quantitatively in the proposed system. 2) Calculations intended for the environmental testing room of 9.2m 2 predict that the whole cooling load can be covered by discharged cold energy storing during night without operation of air conditioners during the daytime in conditions of supply air temperatures in the under floor space around 12 to 13ºC. 3) An experiment in the testing room with a supply air temperature of 12.5ºC on average can result in completion of load shifting. The authors confirmed that the calculation give good agreement with the experiment under the similar operating conditions with respect to stored heat in the nighttime and the floor and room air temperatures in the room space. 4) The results of thermal sensation votes from 4 subjects don t show neither cold nor uncomfortable sensations for both the whole body and each part of the body even in the morning. It is found that the proposed system using the granulated CM can improve the uncomfortable coldness especially near the floor in the previous systems. ACKNOWLEDGEMENT This work was supported in part by the Grant for Environmental Research rojects in the Sumitomo Foundation (Research representative: rof. M. Enai of Hokkaido University). Technical cooperation of Mr. Ishiguro at the Mitsubishi aper Mills Limited is greatly appreciated. REFERENCES Akimoto, T., Nobe, T. and Takebayashi, Y. (1995) Experimental Study on the Floor-supply Displacement Ventilation system. ASHRAE Transactions: Symposia SD , ASHRAE. (2003). ASHRAE Handbook HVAC Applications Horikoshi, T. and Kobayashi, Y. (1978). Configuration Factors between a Rectangular Solid as a Model of the Human Body and Rectangular lanes, for Evaluation of the Influence of Thermal Radiation on the Human Body II Characteristics of Configuration factors for the Rectangular Solids. Trans. of A.I.J. 267(5). ISO7730. (1994). Moderate Thermal Environments- Determination of the MV and D Indices and Specification of the Conditions for Thermal Comfort. International Organization for Standardization. Nagano, K., Takeda, S., Mochida, T., Shimakura, K. and Nakamura, T. (2006). Study of a Floor Supply Air Conditioning System using Granular hase Change Material to Augment Buildings Mass Thermal Storage Heat Response in Small Scale Experiments. Energy and Buildings, 38, Takeda, S., Nagano, K., Mochida, T. and Nakamura, T. (2003). Development of Floor Supply Air Conditioning System with Granulated hase Change Materials. roceedings of FUTURESTOCK th International Conference on Thermal Energy Storage, Warsaw, Takeda, S., Nagano, K., Mochida, T. and Shimakura, K. (2003). Thermal Characteristics in Direct Heat Exchange between Granulated hase Change Materials and Air. roceedings of FUTURESTOCK th International Conference on Thermal Energy Storage, Warsaw, Takeda, S., Nagano, K., Shimakura, K. and Nakamura, T. (2004) Application of Granules Including CM for the Floor Supply Air Conditioning System. IEA, 6 th Workshop of ECES IA Annex 17, Advanced thermal energy storage through phase change materials and chemical reactions feasibility studies and demonstration projects. Tokyo Electric ower Company. (2004). TECO ILLUSTRATED FY2004,

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2 01-014 The 2005 World Sustainable Building Conference, DEVELOPMENT OF A PASSIVE COOLING STRATEGY USING DOUBLE-ROOFING SYSYTEM WITH RAINWATER SPRAYING AND ITS FIELD TESTING IN TERMS OF THE INDOOR THERMAL

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, 450-0003, JAPAN ABSTRACT In large

More information

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM Jae-Han Lim 1, Myoung-Souk

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

More information

EVALUATION OF THE THERMAL PERFORMANCE OF METAL ROOFING UNDER TROPICAL CLIMATIC CONDITIONS

EVALUATION OF THE THERMAL PERFORMANCE OF METAL ROOFING UNDER TROPICAL CLIMATIC CONDITIONS EVALUATION OF THE THERMAL PERFORMANCE OF METAL ROOFING UNDER TROPICAL CLIMATIC CONDITIONS Mohamed HARIMI Djamila HARIMI V. John KURIAN Bolong NURMIN 1 Center of Mineral and Materials, Universiti Malaysia

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

Experimental study of space cooling using ceiling panels equipped with capillary mats

Experimental study of space cooling using ceiling panels equipped with capillary mats Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding email: tiberiu.catalina@insa-lyon.fr SUMMARY

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

PCM-module to improve hot water heat stores with stratification: first tests in a complete solar system

PCM-module to improve hot water heat stores with stratification: first tests in a complete solar system Futurestock 2003 9 th International Conference on Thermal Energy Storage, Warsaw, POLAND PCM-module to improve hot water heat stores with stratification: first tests in a complete solar system *Luisa F.

More information

A study of radiant cooling for a room with daytime application in tropical climate

A study of radiant cooling for a room with daytime application in tropical climate International Journal of Smart Grid and Clean Energy A study of radiant cooling for a room with daytime application in tropical climate Satinee Wongkee, Surapong Chirarattananon, Pipat Chaiwiwatworakul

More information

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Koji Fujita, Graduate Student, Graduate School of Science and Technology, Kobe University; 039d892n@stu.kobe-u.ac.jp Atsushi

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY M Kojima, T Saito Graduate School of Environmental Studies, NAGOYA University, Chikusa, Nagoya, 464-8603

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between

More information

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET I. S. Hwang and Y. L. Lee Department of Mechanical Engineering, Kongju National University, Korea E-Mail: ylee@kongju.ac.kr ABSTRACT

More information

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings - 1 - Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings Mamoru Hamada, Living Environment Systems Laboratory, Mitsubishi Electric Co., Kamakura, Kanagawa, Japan Naomichi

More information

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca

More information

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 215, 9, 7-14 7 Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

Cooling load calculations of radiant and all-air systems for commercial buildings

Cooling load calculations of radiant and all-air systems for commercial buildings Downloaded from orbit.dtu.dk on: Aug 17, 2018 Cooling load calculations of radiant and all-air s for commercial buildings Bourdakis, Eleftherios; Bauman, Fred; Schiavon, Stefano; Raftery, Paul; Olesen,

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,

More information

DESIGN WITH HEAT LOAD SIMULATION OF COMBINED PASSIVE-ACTIVE SYSTEMS

DESIGN WITH HEAT LOAD SIMULATION OF COMBINED PASSIVE-ACTIVE SYSTEMS Ninth International IBPSA Conference Montréal, Canada August 18, DESIGN WIH HEA LOAD SIMULAION OF COMBINED PASSIVEACIVE SYSEMS Mitsuhiro Udagawa 1, Hyunwoo Roh 2 Department of Architecture, Kogakuin University,

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent

More information

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Passive building in Hot and Humid Climates

Passive building in Hot and Humid Climates 9 th Annual North American Passive House Conference Passive building in Hot and Humid Climates Lisa White 1 Overview 1. Thermal Comfort 2. Drivers of sensible and latent cooling loads 3. Passive cooling

More information

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian

More information

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue

More information

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER 2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot

More information

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT Ashak Nathwani AM Adjunct Senior Lecturer ashak.nathwani@sydney.edu.au PRESENTATION THREE SESSIONS This presentation will be in three parts addressing

More information

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART II: VALIDATION

More information

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION - 1 - PERFORMANCE ANALYSIS OF GROUND SOURCE HEA PUMPS FOR DOMESIC HO WAER SUPPLY IN HE LOW ENERGY HOUSE AND IS APPLICAION akao Katsura, Fujiwara Environmental Science Institute Ltd, Sapporo, Japan Katsunori

More information

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Yoshiyuki Shimoda, Osaka University Takuro Fujii, Osaka University Takao Morikawa, Osaka University Minoru

More information

The Shortwave Reflectance of the Yankee Environmental Systems Hotplate

The Shortwave Reflectance of the Yankee Environmental Systems Hotplate 1 - Introduction The Shortwave Reflectance of the Yankee Environmental Systems Hotplate David Siuta, Jefferson R. Snider and Bujidmaa Borkhuu University of Wyoming September 2010 (Updated September 2017)

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

How to ensure Thermal Comfort in buildings with CFD

How to ensure Thermal Comfort in buildings with CFD How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD

More information

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials YUKO TSUKIYAMA 1, NOBUYUKI SUNAGA 2, AKIKO SUZUKI 2, TAMAKI FUKAZAWA 2, YOSUKE

More information

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity COOLING AND HEATING OF BUILDINGS BY ACTIVATING THE THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS EMBEDDED PIPE SYSTEMS Bjarne W. Olesen, Ph.D., Head of R&D, Wirsbo-VELTA, Germany Professor, Technical

More information

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

More information

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida Case Study of an Innovative HVAC System with Integral Dehumidifier Richard A. Raustad Don B. Shirey, III Senior Research Engineer Program Manager Florida Solar Energy Center Cocoa, Florida ABSTRACT In

More information

The Use Of Attic Space For Cooling and Dehumidification

The Use Of Attic Space For Cooling and Dehumidification Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Use Of Attic Space For Cooling and Dehumidification H. F. Abaza Virginia

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland Paper ID 0009 ISBN: 978-83-7947-232-1 Evaluation of task air conditioning system with convection, conduction, and radiation Misa Imazu 1,*,

More information

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts Article Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts Building Serv. Eng. Res. Technol. 206, Vol.

More information

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Yasushi Kondo 1, Shin-ichi Akabayashi 2, Osamu Nagase 3 and Akihiko Matsuda 4 1 Dept of Architecture, Musashi Institute of Technology,

More information

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets Bill Rittelmann, IBACOS Building Enclosure Technology and

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN

More information

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review FSEC-PF-454-11 May 2011 Author Carlos Colon Copyright 2011 Florida Solar Energy Center/University

More information

Dynamic performance of a novel dew point air conditioning for the UK buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings *Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 217 Europe July 2-5, 217, Lublin, Poland Paper ID 95 ISBN: 978-83-7947-232-1 Verification of gymnasium designed by high thermal insulation considering elderly people in disaster Koki

More information

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM K. Yokoo 1, S. Tanabe 1, Y. Aizawa 2, K. Inagaki 2, D. Kawamata 2, H. Amai 1, K. Watanabe 1, and T. Nishimasu 1 1 Waseda University,

More information

Comparison of radiant and convective cooling of office room: effect of workstation layout

Comparison of radiant and convective cooling of office room: effect of workstation layout Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;

More information

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI International Journal of Scientific & Engineering Research Volume 9, Issue 4, April-2018 238 ANALYSIS OF RADIANT COOLING IN CONCRETE SLABS WITH EMBEDDED PIPES ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA

More information

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER , Volume 6, Number 4, p.168-172, 2005 STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER Zhaohui Qi School of Energy Science and Engineering, Centralsouth University, Changsha,

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang

More information

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS Masaya Saito*, Satoshi Nasu*, Moto Nakano** and Kouko Miyakawa*** *Sapporo School of The Arts Geijustu-no-mori

More information

The Art of Building Science

The Art of Building Science The Art of Building Science What is Building Science? Building Science seeks to apply the scientific fundamentals of building dynamics to the functional relationships between the house s components and

More information

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE Conference on Sustainable Building South East Asia, -7 November 27, Malaysia GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE G. REIMANN IEN Consultants,

More information

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION 2597, Page 1 Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump Ian H. BELL 1 *, James E. BRAUN 2 1 Bell Thermal Consultants ian.h.bell@gmail.com 2 Purdue

More information

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Takuya Hasegawa 1,* and Osamu Senbu 1 1 Hokkaido University, Japan * Kita 13, ishi 8, Kita-ku, Sapporo 060-8628,

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0232 ISBN: 978-83-7947-232-1 Experimental study of a novel dew point indirect evaporative cooler Wenhua Chen, Zhiwei Zhang, Jiayu Li,

More information

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN -9 The 5 World Sustainable Building Conference, Tokyo, 7-9 September 5 (SB5Tokyo) ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN Kahori GENJO Dr.Eng. Shin-ichi MATSUMOTO Dr.Eng

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

,Chaojian He6, f. School of Guangxi University, Nanning , China.

,Chaojian He6, f. School of Guangxi University, Nanning , China. 5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) The Research on Running Characteristics of A New Type of Radiant Air Conditioning Combined with Fresh

More information

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM - 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,

More information

Variable far infrared radiation (VFIR) technique for cubic carrot drying

Variable far infrared radiation (VFIR) technique for cubic carrot drying International Journal of Renewable Energy, Vol. 7, No. 2, July - December 2012 Variable far infrared radiation (VFIR) technique for cubic carrot drying Sirinuch Chindaruksa a *, Pisit Maneechot b, Seishu

More information

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,

More information

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES Third Southern African Solar Energy Conference 11 13 May 2015 Kruger National Park, South Africa SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES Shahmohamadi M., Shafii, M.B.and

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: marts 27, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

Study of solar-thermal collector assisted hybrid split air conditioner

Study of solar-thermal collector assisted hybrid split air conditioner Study of solar-thermal collector assisted hybrid split air conditioner Chetan Brahmankar 1, Hrishikesh Bhushan 2, Akshay Ghule 3, Himanshu Ranjan 4 1,2,3,4 Dept. of mechanical engineering, Dr. D.Y Patil

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS Clayton Miller 1,* and Chandra Sekhar 1 1 National University of Singapore, Singapore * Corresponding email: miller.clayton@nus.edu.sg

More information

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS Klaus Ellehauge SolEnergi Center Danmark, Danish Technological Institute, Energy, Teknologiparken, DK-8 Aarhus C, Tel.: +45 722 137, Fax:

More information

System Modeling of Gas Engine Driven Heat Pump

System Modeling of Gas Engine Driven Heat Pump Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov

More information

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect A Numerical Investigation on the Effect of Operation Control of a Multi-Split Air-Conditioning System on Indoor Thermal Environment H. Matsunaga 1,*, S. Iizuka 1, M. Okumiya 1, G. Yoon 2, and H. Niwa 3

More information

Space Air Diffusion II

Space Air Diffusion II MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

Thermal Environment Evaluation in Commercial Kitchens of United States

Thermal Environment Evaluation in Commercial Kitchens of United States Downloaded from orbit.dtu.dk on: Jul 25, 2018 Thermal Environment Evaluation in Commercial Kitchens of United States Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation

More information