1 Healthy Buildings 217 Europe July 2-5, 217, Lublin, Poland Paper ID 95 ISBN: Verification of gymnasium designed by high thermal insulation considering elderly people in disaster Koki Kikuta 1,*, Hiroshi Kikuchi 2, Shiho Aoyagi 1, Hirofumi Hayama 1 1 Hokkaido University, Sapporo, Japan 2 Kona Sapporo Co., Ltd., Sapporo, Japan * Corresponding k-kikuta@eng.hokudai.ac.jp SUMMARY The aim of this study is to quantitatively clarify the effects of building envelope performance improvement of gymnasium designed by high thermal insulation that will contribute to the strengthening of disaster prevention. Gymnasium designed by high thermal insulation considering elderly people in a disaster was verified through a comparison with conventional gymnasiums. As a result, it was confirmed that gym H for high thermal insulation type designed by external insulation and SRC structure had the thermal insulation performance of more than twice of a present standard specification. Furthermore, it was calculated for the performance values of air leakage coefficient, air leakage exponent and effective leakage area by airtightness measurement. KEYWORDS Evacuation shelter, Room temperature, Airtightness measurement, ACH5 1 INTRODUCTION Immediately after the Great East Japan Earthquake, 622 school facilities, in particular, gymnasiums were performing the function as evacuation shelters. However, the problems such as ensuring of power and water, shortage of heating equipment, and so on occurred. On the other hand, as a measure against cold in Sapporo, Japan, it has been stockpiling a lot of sleeping bag, blanket, portable kerosene stove. Moreover, an approach to high thermal insulation for gymnasiums was shown in June 211, and it has actually been attempted from FY214. The aim of this study is to quantitatively clarify the effects of building envelope performance improvement of gymnasium designed by high thermal insulation that will contribute to the strengthening of disaster prevention. Gymnasium designed by high thermal insulation considering elderly people in a disaster is verified through a comparison with conventional gymnasiums. 2 OVERVIEW OF SCHOOL SUBJECT TO INVESTIGATION Table 1 lists overview of gymnasiums. Four gymnasiums of elementary school in Sapporo are subject to investigation. Gym H for high thermal insulation type was completed in March 214. Even if the heating at gymnasium is stopped by winter disaster, the target was set for ensuring minimum indoor environment with the only calorific value from evacuees. Concretely, it is

2 designed to keep room temperature more than 1 ºC during outside air temperature -1 ºC (inside-outside temperature difference more than 2 K). The calorific value from evacuees assumes about 35 kw ( kw = 48 person 72 W/person). Solar radiation heat from window or heat from lighting and equipment contributing to the safety are not considered. Air changes per hour at the design target is expected to be.1 h -1. Gym S for standard type of subject to be compared was completed in March 212. Because the number of children is too large, total floor area is planned to be the widest. It has building envelope performance the same as a present standard specification. In addition, for the heating consumption rate of gymnasium among all school facilities, gym I for old standard type that is as low as 22 % and gym A for old standard type that is as high as 52 % are also subject to be compared. Although it is common in terms of warm air heating by city gas, it is different in terms of gym H and S of SRC structure in the 21s and gym I and A of steel structure in the 198s. Table 1. Overview of gymnasiums. Type High thermal insulation Standard Old standard Name Gym H Gym S Gym I Gym A Completed year Total floor area 1,394 m 2 1,738 m 2 1,363 m 2 1,319 m 2 Structure SRC Steel Thermal Wall PF 6 mm XPS 3 mm 25 mm * Insulation spec. Roof PUF 12 mm 12 mm * 25 mm ** Window Double glazing Double glazing Single glazing spec. Investigation period (low-e Ar) (double) 7/2/214-7/17/214-1/13/212-1/1/212-3/2/215 3/12/215 5/1/213 5/1/213 * Foamed thermal insulating material, ** Cemented excelsior board 3 VERIFICATION OF THERMAL INSULATION PERFORMANCE Minimum room temperature in a severe winter season At school subject to investigation where thermal insulation performance is greatly different, minimum room temperature in a severe winter season is verified in order to compare how room temperature fell immediately after stopping heating. In the case of gym I and A for old standard type, room temperature fluctuation was very large according to intermittent heating regardless of weekdays and holidays. Room temperature remained at the high level compared to the heating temperature setting (18 ºC in gym I, 15 ºC gym A). After that, the service that gymnasium is open to the public was finished. Room temperature was rapidly dropped soon after stopping heating. A typical characteristic to be easily heated and cooled appeared. Minimum room temperature in a severe winter season of early February was recorded by 5 ºC in gym I and below the freezing point at early morning in gym A (Fig.1 (a)). In the case of gym H for high thermal insulation type and gym S for standard type, room temperature remained at the heating temperature setting around 15 ºC, and also its fluctuation range was small. Average inside-outside temperature difference on weekdays was 16.4 K in gym H and 15.1 K in gym S. However, there was no case that room temperature fell below 1 ºC in gym H (Fig.1 (b)).

3 3 Weekdays 3 Weekdays 2 2 Temperature ºC 1 Temperature ºC /29 1/3 1/31 2/1 2/2 2/3 2/4-2 2/1 2/2 2/3 2/4 2/5 2/6 2/7 Gym I (room) Gym A (room) Gym H (room) Gym S (room) Gym I (outside air) Gym A (outside air) (a) Gym H (outside air) Gym S (outside air) (b) Figure 1. Room temperature fluctuation in severe winter. a) Gym I and A, b) Gym H and S Room temperature fluctuation rate Room temperature fluctuation rate from 22: to 6: the next morning after the service that gymnasium is open to the public is verified in order to compare thermal insulation performance at school subject to investigation. This rate is the value dividing overall heat transmission coefficient by heat capacity. In general, it is considered desirable that this rate is as small as possible, because overall heat transmission coefficient is small when thermal insulation performance is high, and also heat capacity is large when heat storage performance is high. In gym H designed by external insulation and SRC structure, although the immediate effect of starting heating is inferior, both thermal insulation performance and heat storage performance are superior. Room temperature fluctuation rate while stopping heating equipment and ventilation equipment was On the other hand, this rate in gym A was more than five times as large as that in gym H. In addition, overall heat transmission coefficient and heat capacity cannot be identified. However, it was confirmed that gym H had the thermal insulation performance of more than twice of a present standard specification in comparison with gym S (Fig. 2). 1 y=e -.3t.9 y=e -.7t y (-).8 y=e -.11t.7 y=e -.16t Figure 2. Room temperature fluctuation rate..6 7,2 14,4 21,6 28,8 Elapsed time (22:-6: the next morning) t (s) Gym H (Feb ) Gym S (Feb ) Gym I (Feb ) Gym A (Feb ) Design target The design target that inside-outside temperature difference more than 2 K was kept by only human body heat is verified. Therefore, it is necessary to evacuate many people or to input heat quantity corresponding to human body heat to a gymnasium. Then, human body heat is simulated with kerosene stoves based on grasping the effect of heating by these that are assumed to be used at an evacuation shelter. A simple method of evaluating the design target is attempted through the relationship between calorific value and inside-outside temperature difference.

4 For three days of January 9, 13 and 15, 215 in winter vacation, while changing the number of kerosene stoves to be used (maximum calorific value 6.59 kw/unit) to 6, 2 and 8 units, the stoves were burning for seven hours from 9:3 to 16:3. Room temperature gently rose according to the number to be used and was stable after that (Fig. 3 (a)). In particular, it became more than 15 ºC with 8 units. At that time, CO concentration and CO2 concentration were separately measured in consideration of safety. However, incomplete combustion did not occur, and 2.4 ppm and 3,69 ppm were recorded at 16:3. As a result, inside-outside temperature difference based on human body heat ensured by calorific value kw from evacuees was 19.1 K, so it can be determined that the design target was almost achieved (Fig. 3 (b)). Temperature ºC :3 Room Outside air 1: 1:3 11: 11:3 12: 12:3 13: 13:3 Using the average values 14: 6 units (1/9) 2 units (1/13) 8 units (1/15) 6 units (1/9) 2 units (1/13) 8 units (1/15) (a) (b) Figure 3. Results on design target. a) Room temperature fluctuation during heating with stove, b) Relationship between calorific value and inside-outside temperature difference 4 VERIFICATION OF AIRTIGHTNESS PERFORMANCE 14:3 15: 15:3 16: 16: kw Calorific value kw Overview of airtightness measurement Each performance value is verified by airtightness measurement in gymnasiums specified as an evacuation shelter. In that case, maximum four air blowers are simultaneously controlled on an airtightness measurement device, which is devised so that it can be measured in large-scale space. Two straightening cylinders with the pipe diameter of 2 mmφ are used in gym H and S of SRC structure, and four straightening cylinders with the pipe diameter of 154 mmφ are used in gym I and A of steel structure. The grating through the underfloor, the door connected to the school, and so on are sealed up (Fig. 4). Inside-outside temperature difference K K Gym H Gym I Figure 4. Airtightness measurement of gym H and I. Effective leakage area and ACH5 When airtightness measurement based on reduced pressure method was performed, the relation of pressure difference and volume flow rate was plotted (Fig. 5). Although the number of plots

5 was different, it was calculated for air leakage coefficient, air leakage exponent and effective leakage area using these measured results. Table 2 lists results on airtightness measurement. If gym A for old standard type where air leakage coefficient was the highest was used as the base, it decreased by 18 % in gym I for old standard type. Whereas, it decreased by 81 % in gym I for standard type and 86 % in gym H for high thermal insulation type. Air leakage exponent was included in the range of 1 to 2. It was as small as around 1.25 in gym H and I, so it can be determined that each air leakage was extremely narrow compared to gym I and A. Furthermore, as a result of the calculated effective leakage area, it was 85 cm 2 in gym H and 1,14 cm 2 in gym I, which is equivalent to about one-fifth and one-quarter of gym A where it was the largest. Therefore, since the performance value was almost same in gym H and S where thermal insulation performance was different, it was considered that the difference of airtight performance was greatly influenced by the differences such as mainly structure type or window sash type. On the other hand, air changes per hour at 5 Pa (ACH5) was very small, about.4 h -1 in gym H and S. In contrast, it was very large, about.9 h -1 in gym I and about 1.5 h -1 in gym A. 1, Volume flow rate m 3 /h 1, Pressure difference Pa Gym H Gym S Gym I Gym A Figure 5. Relation of pressure difference and volume flow rate. Table 2. Results on airtightness measurement. Type High thermal insulation Standard Old standard Name Gym H Gym S Gym I Gym A Measurement date 1/23/214 8/8/214 2/2/212 2/27/212 Room temp. ºC Outside air temp. ºC Wind velocity m/s Air leakage coefficient m 3 /(h Pa 1/n ) ,5.5 1,288.4 Air leakage exponent Effective leakage area cm ,14 2,886 4,66 ACH5 h Ventilation rate Assuming that the gaps obtained by airtight measurement are uniformly distributed, the estimation of ventilation rate (leakage rate) using wind force and temperature difference as driving force was attempted. It was simply assumed that wind direction was perpendicular to the long side direction, wind pressure coefficients were +.6 on the windward side and -.4 on the leeward side, and the gaps were only in the long side direction. The windward and leeward side are divided into 2 at.5 m intervals in the up and down direction. The convergence calculation with room pressure as a variable is performed in order to determine ventilation rate by the influence of the gaps. By the way, in the case of wind velocity more than 4 m/s, the air

6 flowed in only through the windward side gaps and flowed out only through the leeward side gaps. As a result, ventilation rate was about 7-3, m 3 /h in gym H and about 2,6-1,6 m 3 /h in gym I. In reference to this rate, less than 3 m/s in gym I was almost equal to that of 1 m/s in gym H (Fig. 6). Based on the estimated ventilation rate, it was confirmed that the calculated infiltration heat loss under inside-outside temperature difference 2 K was kw in gym H. Volume flow rate m 3 /h 12, 1, 8, 6, 4, 2, Room temp. 1 ºC Outside air temp.: -1 ºC Wind pressure coefficient (windward side): +.6 Wind pressure coefficient (leeward side): Infiltration heat loss kw Wind velocity m/s Gym H Gym I Gym H Figure 6. Volume flow rate and infiltration heat loss. 5 CONCLUSIONS 1) There was no case that room temperature fell below 1 ºC in gym H for high thermal insulation type designed by external insulation and SRC structure. Gym H had the superior temperature characteristics of minimum room temperature and room temperature fluctuation rate compared to gym I and A for old standard type. It was confirmed that gym H had the thermal insulation performance of more than twice of a present standard specification. 2) Inside-outside temperature difference based on human body heat ensured by calorific value kw from evacuees in gym H was 19.1 K, it can be determined that the design target was almost achieved. 3) The performance values of air leakage coefficient, air leakage exponent and effective leakage area were verified by airtightness measurement. It was considered that the difference of airtight performance was greatly influenced by the differences such as mainly structure type or window sash type. 4) Equivalent leakage area was 85 cm 2, and also ACH5 was.41 h -1 in gym H. It was confirmed that infiltration heat loss was kw under inside-outside temperature difference 2 K and wind velocity -1 m/s. 6 REFERENCES ISO 9972: 215. Thermal performance of buildings - Determination of air permeability of buildings - Fan pressurization method JIS A 221: 23. Test method for performance of building airtightness by fan pressurization

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0141 ISBN: 978-83-7947-232-1 Prediction of exhaust gas stagnation in common corridor of apartments with gas water heater Takuro Nakamura

More information

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings - 1 - Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings Mamoru Hamada, Living Environment Systems Laboratory, Mitsubishi Electric Co., Kamakura, Kanagawa, Japan Naomichi

More information

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

High-Performance, High-Reliability Gas Heat Pump

High-Performance, High-Reliability Gas Heat Pump 62 High-Performance, High-Reliability Gas Heat Pump Hideaki Kasahara* 1 Atsushi Yoshimura* 1 Ryuuji Morishima* 2 Hisao Iwata* 2 In order to response to annually increasing customer needs for economic efficiency

More information

Figure 1: Low energy dwellings testsite

Figure 1: Low energy dwellings testsite Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 SIMULATION OF DEMAND CONTROLLED VENTILATION IN A LOW-ENERGY HOUSE Netherlands Energy Research Foundation J.C. Römer P.O.

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, 450-0003, JAPAN ABSTRACT In large

More information

ZERO Heating Power Vending Machine Hybrid ZERO

ZERO Heating Power Vending Machine Hybrid ZERO ZERO Heating Power Vending Machine Hybrid ZERO ISHIDA, Shin ABSTRACT Fuji Electric has adopted the concept of achieving extensive energy savings while reducing peak power consumption to decrease environmental

More information

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Indoor Thermal Environment of Residential Buildings in Three Cities of China Indoor Thermal Environment of Residential Buildings in Three Cities of China Hiroshi Yoshino 1 and Haihong Lou 2 1 Prof, Laboratory of Building Environmental Engineering, Department of Architecture & Building

More information

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES Hiroko Kaji 1, Shin-ichi Akabayashi 1, and Jun Sakaguchi 2 1 Division of Science and Technology, Graduate

More information

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN -9 The 5 World Sustainable Building Conference, Tokyo, 7-9 September 5 (SB5Tokyo) ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN Kahori GENJO Dr.Eng. Shin-ichi MATSUMOTO Dr.Eng

More information

Special edition paper

Special edition paper Proving Tests for Countermeasures Against Localized Torrential Downpours at Stationhouses Hideki Osumi* Kiyoshi Sakamoto* Localized torrential downpours have been tending to increase in recent years, notably

More information

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland Paper ID 0009 ISBN: 978-83-7947-232-1 Evaluation of task air conditioning system with convection, conduction, and radiation Misa Imazu 1,*,

More information

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials YUKO TSUKIYAMA 1, NOBUYUKI SUNAGA 2, AKIKO SUZUKI 2, TAMAKI FUKAZAWA 2, YOSUKE

More information

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect A Numerical Investigation on the Effect of Operation Control of a Multi-Split Air-Conditioning System on Indoor Thermal Environment H. Matsunaga 1,*, S. Iizuka 1, M. Okumiya 1, G. Yoon 2, and H. Niwa 3

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION Kuklane, Kalev Published in: [Host publication title missing] Published: 2014-01-01 Link to publication Citation for published

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials Takuya Hasegawa 1,* and Osamu Senbu 1 1 Hokkaido University, Japan * Kita 13, ishi 8, Kita-ku, Sapporo 060-8628,

More information

Drink Showcase Equipped with Inverter Freezer

Drink Showcase Equipped with Inverter Freezer Drink Showcase Equipped with Inverter Freezer MURABAYASHI, Kenji KAGEYAMA, Toshiyuki CHOU, Ikou ABSTRACT In recent years, the impact of earthquakes has increased the demand for replacing products with

More information

Lifting of evacuation orders and subsequent efforts in Japan

Lifting of evacuation orders and subsequent efforts in Japan Lifting of evacuation orders and subsequent efforts in Japan N. Arima Support Team for Residents Affected by Nuclear Incidents, Cabinet Office of Japan (at the time of presentation), Embassy of Japan in

More information

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Koji Fujita, Graduate Student, Graduate School of Science and Technology, Kobe University; 039d892n@stu.kobe-u.ac.jp Atsushi

More information

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps Søren Østergaard Jensen February 2017 1 Preface The present document

More information

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan 23rd World Gas Conference, Amsterdam 2006 Verwijderd: DRD HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% Main Author Atsuya Tajima Japan ABSTRACT In Japan, electric heat pump water heaters

More information

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Connect North and South Korean Separated Families Higher Comfort Lower Energy Transsolar Academy 2016-2017 Final Project Summary Connect North and South Korean Separated Families Higher Comfort Lower Energy SUIN KIM 1, ELMIRA REISI 2 1 Transsolar Academy, Transsolar Energietechnik

More information

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

More information

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION PERFORMANCE EVALUAION OF CO 2 HEA PUMP HEAING SYSEM O. KUWABARA (a), M. KOBAYASHI (a), H. MUKAIYAMA (a) M. ISHIKAWA (b), K. MUKUNOKI (b), N. HONMA (b) (a) R&D Headquarters, Sanyo Electric Co., Ltd. 1-1-1,

More information

PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR

PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR Hiroshi Miyazaki 1, Hiromasa Tanjyoh 2, Kengo Suzuki 3, Tomoaki Iwami 4 1 New cosmos electric, co., ltd., Osaka, 543-0036,

More information

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Daisuke Ogura 1, Masahide Inuzuka 2, Shuichi Hokoi 1, Takeshi Ishizaki 2, Hiroyuki Kitahara

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating Vladimír Zmrhal Czech Technical University in Prague, Faculty of Mechanical Engineering Corresponding email: Vladimir.Zmrhal@fs.cvut.cz

More information

APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES

APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES Numbers of Abstract/Session (given by NOC) - 1 - APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES Toshihisa Kondo, Acting Manager, Future Systems Designing Group, Automotive Thermal Systems Department,

More information

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance June 2018 Residential Air Leakage (Blower Door) Testing for Florida Code Compliance Infiltration or uncontrolled air leakage into buildings is a result of the number and size of cracks and gaps in the

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

The Art of Building Science

The Art of Building Science The Art of Building Science What is Building Science? Building Science seeks to apply the scientific fundamentals of building dynamics to the functional relationships between the house s components and

More information

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor 2C-1 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor Soo-Young Kim *, Eung-Sik

More information

Heat transfer enhancement in an air process heater using semi-circular hollow baffles

Heat transfer enhancement in an air process heater using semi-circular hollow baffles Available online at www.sciencedirect.com Procedia Engineering 56 ( 2013 ) 357 362 5 th BSME International Conference on Thermal Engineering Heat transfer enhancement in an air process heater using semi-circular

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

Evaluation of a Support System for Large Area Tourist Evacuation Guidance: Kyoto Simulation Results

Evaluation of a Support System for Large Area Tourist Evacuation Guidance: Kyoto Simulation Results Evaluation of a Support System for Large Area Tourist Evacuation Guidance: Kyoto Simulation Results Seiki Kinugasa, Tomoko Izumi and Yoshio Nakatani Abstract Most studies on providing evacuation guidance

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Eco-Friendly LPG Vaporization. by Efficient Use of Atmospheric Heat

Eco-Friendly LPG Vaporization. by Efficient Use of Atmospheric Heat TOPIC: No.8, Environment Eco-Friendly LPG Vaporization Eco-Friendly LPG Vaporization by Efficient Use of Atmospheric Heat Motonori Shinagawa,Senior Manager Engineering Dept, ITO KOKI CO., LTD. Co-Author:

More information

WATER VAPOR IN THE FUNCTIONAL GAP OF WINDOW. MILAN PALKO, SLOVAK UNIVERSITY OF TECHNOLOGY IN BRATISLAVA, Faculty of Civil Engineering,

WATER VAPOR IN THE FUNCTIONAL GAP OF WINDOW. MILAN PALKO, SLOVAK UNIVERSITY OF TECHNOLOGY IN BRATISLAVA, Faculty of Civil Engineering, WATER VAPOR IN THE FUNCTIONAL GAP OF WINDOW MILAN PALKO, SLOVAK UNIVERSITY OF TECHNOLOGY IN BRATISLAVA, Faculty of Civil Engineering, Abstract: The paper deals with thermal-moisture performance of a wooden

More information

HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL

HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL M. Oda*, M. Shimizu*, N. Kumagai*, H. Kanai**, M. Tanabe** *Nuclear Fuel Cycle Group, Power & Industrial Systems R&D

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0232 ISBN: 978-83-7947-232-1 Experimental study of a novel dew point indirect evaporative cooler Wenhua Chen, Zhiwei Zhang, Jiayu Li,

More information

Development of CO2 Compressor and Its Application Systems

Development of CO2 Compressor and Its Application Systems Development of CO2 Compressor and Its Application Systems Hiroshi MUKAIYAMA, Tetsuya MASUDA, Kazuaki MIZUKAMI, Satoshi IMAI, Toshiyuki EBARA, Toshikazu ISHIHARA, Ichiro KAMIMURA, Kikuo TAKIZAWA SANYO Electric

More information

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING M. POIRIER, D. GIGUÈRE, Z. AIDOUN, M. OUZZANE Natural Resources Canada, CANMET Energy Technology Centre-Varennes 1615, Lionel

More information

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY Aivars Aboltins, Janis Palabinskis Latvia University of Agriculture aivars.aboltins@inbox.lv Abstract. The paper describes the results

More information

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM *

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM * TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM * Krishna R. Reddy, Aravind Marella and Prasanth Ala University of Illinois at Chicago, Department of Civil and Materials

More information

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing Vipac Engineers & Scientists DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption The physical testing Sydney 16 August 2016 Introduction to Vipac AGENDA

More information

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings research highlight October 2005 Technical Series 05-112 Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings INTRODUCTION The provision of airtight interior

More information

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine Technical Report Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine Yasuaki MIURA Plant & Machinery Division Steel Plant Engineering Department Ⅱ Continuous Caster

More information

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award Instructions Answer FIVE questions, All questions carry equal marks. (NFQ Level 6) Autumn 2006 Building

More information

Effects of Smoke on Evacuation Martin Lopušniak 1, a

Effects of Smoke on Evacuation Martin Lopušniak 1, a Advanced Materials Research Online: 2014-02-27 ISSN: 1662-8985, Vol. 899, pp 539-542 doi:10.4028/www.scientific.net/amr.899.539 2014 Trans Tech Publications, Switzerland Effects of Smoke on Evacuation

More information

Department for Communities and Local Government Research Report:

Department for Communities and Local Government Research Report: Department for Communities and Local Government Research Report: BD 2890 Investigation of real fires - Electrical consumer unit fire experiments 293761 (E3V2) CPD/04/102/027 Prepared for: Brian Martin

More information

EVACUATION SIMULATION FOR BUILDING DAMAGE CAUSED. Shiori KUBO Rei FUJITA Hidenori YOSHIDA Lalith WIJERATHNE Muneo HORI

EVACUATION SIMULATION FOR BUILDING DAMAGE CAUSED. Shiori KUBO Rei FUJITA Hidenori YOSHIDA Lalith WIJERATHNE Muneo HORI EVACUATION SIMULATION FOR BUILDING DAMAGE CAUSED Shiori KUBO Rei FUJITA Hidenori YOSHIDA Lalith WIJERATHNE Muneo HORI BACKGROUND Starting evacuation time for the people escaping from Tsunami Death by the

More information

Are you Getting Your Fan Flows Right?

Are you Getting Your Fan Flows Right? Are you Getting Your Fan Flows Right? Eurihea Speciale, Building Efficiency Resources (The BER) Agenda To discuss HERS rater specific methods for identifying and determining correct ventilation test methodology

More information

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL GROUP 1 HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL Daniel Abrahamson Department of Architecture University of Oregon Eugene, Oregon 97403 dva@uoregon.edu Dijon Jones Department of Architecture

More information

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report D M T G m b H & C o. K G B u i l d i n g S a f e t y Expert Body for Fire Protection Tremoniastraße 13 44137 Dortmund GERMANY Phone +49 231-5333-0 Fax +49 231-5333-299 Emaill: gs@dmt.de http://www.dmt.de

More information

Date and Time of Incident. March 10, 1975

Date and Time of Incident. March 10, 1975 Building Name Address Sennari Hostel 1-8-20 Oginochaya, Nishinari-ku, Osaka City, OSAKA Use (as per FSA Annexed Table 1) Hostel (5) a Date and Time of Incident March 10, 1975 Breakout at 06:16 (approx)

More information

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE NH Wong, BRJ Huang, KW Tham, C Sekhar and DKW Cheong Dept. Of Building, School of Design and Environment, National University of Singapore, Singapore

More information

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Date: February 15, 2018 Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Grantee Name: University of Central

More information

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming 88 KENJI UEDA *1 YOSHINORI SHIRAKATA *2 YASUSHI HASEGAWA *3 NORIYUKI MATSUKURA *4 NAOYA MIYOSHI

More information

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster , pp.97-101 http://dx.doi.org/10.14257/astl.2015.100.21 Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster Ji-Soo Lee 1, Won-Hwa Hong 2 1 Assistant Professor, Departments of

More information

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM STUDY ON A FLOOR SULY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED CM S. Takeda, K. Nagano, K. Nakayama, K. Shimakura Hokkaido University Sapporo, 060-8628 Japan Tel: +81-11-706-7597

More information

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd. Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Refrigeration Lubricant Based on Polyolester for Use With HFCs and Prospect

More information

Development of Large Size Hybrid Fan

Development of Large Size Hybrid Fan Technical Paper Toshihiko Nishiyama Kengo Koshimizu Keiichi Inaba A lot of small fans with three-dimensional, wide chord length, forward swept figure, and/or shroud ring have been developed and manufactured

More information

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS Peter Y. S. Chen North Central Forest Experiment Station Carbondale, Illinois and Wayne A. Helmer Southern

More information

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017 Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM 13 th May 2017 0 1 Portion of Inverter Residential Air Conditioners Worldwide (2015) and in Vietnam (Mar 2017) What is "Inverter"?

More information

DEVELOPMENT OF LARGE AREA PLASTIC SCINTILLATION DETECTOR FOR RADIOACTIVE CONTAMINATION MONITOR

DEVELOPMENT OF LARGE AREA PLASTIC SCINTILLATION DETECTOR FOR RADIOACTIVE CONTAMINATION MONITOR DEVELOPMENT OF LARGE AREA PLASTIC SCINTILLATION DETECTOR FOR RADIOACTIVE CONTAMINATION MONITOR Katsuhito Ito, Ryohei Yanagishima, Daisuke Inui*, Tomoya Minagawa Fuji Electric Systems Co., Ltd. Fuji-machi

More information

A Novel Approach for the Thermal Management. of PC Power Supply

A Novel Approach for the Thermal Management. of PC Power Supply ISTP-16, 005, PRAGUE 16 TH INTERNATIONAL SYMPOSIUM ON TRANSPORT PHENOMENA A Novel Approach for the Thermal Management of PC Power Supply Fu-Sheng Chuang*, Sheam-Chyun Lin, Jon-Ting Kuo, Chien-An Chou Department

More information

The Corbioli House is a single-family house situated

The Corbioli House is a single-family house situated All-in-one high-performing system for ZEB houses Maria Ferrara Grant researcher TEBE Research Group Energy Department Politecnico di Torino at Turin, Italy maria.ferrara@polito.it Frederic Kuznik Full

More information

Safety research of A2L/A3 refrigerants and risk assessment in Japan. Eiji Hihara The University of Tokyo

Safety research of A2L/A3 refrigerants and risk assessment in Japan. Eiji Hihara The University of Tokyo Safety research of A2L/A3 refrigerants and risk assessment in Japan Eiji Hihara The University of Tokyo 1 Trade-off relationship between GWP and flammability To reduce the emission of greenhouse gases

More information

SIMULATION STUDY ON A NET-ZERO ENERGY HOUSE WITH SOLAR AIR COLLECTORS

SIMULATION STUDY ON A NET-ZERO ENERGY HOUSE WITH SOLAR AIR COLLECTORS SIMULAION SUDY ON A NEZERO ENERGY HOUSE WIH SOLAR AIR COLLECORS akafumi Kusunoki 1, Mitsuhiro Udagawa 1, Kanade Hirayanagi 1, Yasuyo Matoba 1 Hyunwoo Roh 2 and Makoto Satoh 3 1 Kogakuin University, okyo(japan),

More information

RESEARCH HIGHLIGHT. Arviat E/2 Northern Sustainable House Energy Consumption Performance Assessment

RESEARCH HIGHLIGHT. Arviat E/2 Northern Sustainable House Energy Consumption Performance Assessment RESEARCH HIGHLIGHT Arviat E/2 Northern Sustainable House Energy Consumption Performance Assessment April 216 Technical Series INTRODUCTION The Arviat E/2 Northern Sustainable House () was designed and

More information

Secador Automatic Desiccator. vs. Comparable Competitor

Secador Automatic Desiccator. vs. Comparable Competitor Secador Automatic Desiccator vs. Comparable Competitor March 2011 Bel-Art Products Engineering Department Wayne, NJ Page 1 of 6 Table of Contents Table of Contents... 2 Objective... 3 Test Conditions and

More information

Villa Bagatelle Technical Report

Villa Bagatelle Technical Report Downloaded from orbit.dtu.dk on: Dec 27, 2018 Villa Bagatelle Technical Report Cox, Rimante Andrasiunaite Publication date: 2015 Document Version Publisher's PDF, also known as Version of record Link back

More information

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke

More information

Adelaide Homes Design Guide 4 - Winter warming

Adelaide Homes Design Guide 4 - Winter warming Adelaide Homes Design Guide 4 - Winter warming Adelaide's temperate climate means home warming is required during winter. There are many efficient heating systems. The most economical method, however,

More information

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist BSC Building America High Performance Homes: Today & Tomorrow Peter Yost Senior Building Scientist Building America homes... create energy efficient environments that: - are affordable to operate - use

More information

Heat pump supplemental heating system for motor vehicles

Heat pump supplemental heating system for motor vehicles 1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance

More information

Seismic Countermeasures for Environmental Radiation Monitoring System

Seismic Countermeasures for Environmental Radiation Monitoring System Seismic Countermeasures for Environmental Radiation Monitoring System Osamu Maekawa Takeshi Miyairi Teruo Ebato ABSTRACT Environmental radiation monitoring system continually measures and monitors the

More information

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE Conference on Sustainable Building South East Asia, -7 November 27, Malaysia GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE G. REIMANN IEN Consultants,

More information

WHAT S CHANGED WITH ANSI/RESNET/ICC STANDARD 380. Iain Walker, Residential Building Systems Group

WHAT S CHANGED WITH ANSI/RESNET/ICC STANDARD 380. Iain Walker, Residential Building Systems Group WHAT S CHANGED WITH ANSI/RESNET/ICC STANDARD 380 Iain Walker, Residential Building Systems Group Contributors: Dean Gamble Bruce Harley Gary Nelson Dennis Stroer Joe Medosch Kristof Irwin Pat Murphy Warren

More information

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc.

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc. 1 High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A Hitachi Appliances, Inc. 2 Introduction The situation faced by the refrigeration / air conditioning industry

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

QUALITY CONTROL Passive House Checklist

QUALITY CONTROL Passive House Checklist 09.01 QUALITY CONTROL - PH Checklist 09.01_PH-SUMMER SCHOOL QUALITY CONTROL Passive House Checklist Composition: Passive House Institut, Darmstadt (DE), Date: 2007-07-03 This presentation is being used

More information

Cardinal Coated Glass Superior glass products for residential windows and doors G L A R E C O N T R O L G L A S S

Cardinal Coated Glass Superior glass products for residential windows and doors G L A R E C O N T R O L G L A S S G L A R E C O N T R O L G L A S S Cardinal Coated Glass Superior glass products for residential windows and doors Wherever glare is a problem, Cardinal Loå 2-240 glass is the ideal solution. It s a specially

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

Keywords biomass boiler, biomass resource, Small scale sewage treatment plant, twin drum type dryer,

Keywords biomass boiler, biomass resource, Small scale sewage treatment plant, twin drum type dryer, Practical Research on a Sewage Sludge Fuelization System for Small-scale Sewage Treatment Plants Eiji Tochioka 1,Hidekazu Nagasawa 1, Shuichi Ochi 1 Tsuneo Nishida 2, Kazuya Hibino 2 1 Japan Institute

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura

More information

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater Gurpreet Singh and Satwant Singh Lala Lajpat Rai Institute of Engineering and Technology, Moga (Punjab) 142001 Abstract : Artificial

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling New technologies Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling Yasuhito Suzuki* Masahiro Shimizu* Abstract In these years there is an increasing

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure Validation of an Energy Demand Model of Residential Buildings Yohei Yamaguchi 1*, Yoshiyuki Shimoda 1 1 Graduate School of Engineering Osaka University, S4 Building, 2-1 Yamadaoka, Suita, Osaka, 565-871,

More information

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection Finned s for Cooling Outdoor Electronics under Natural Convection Lian-Tuu Yeh, Ph D & PE Thermal Consultant, Dallas, TX, 75252 USA Abstract For tower or poled mounted electronics, the heat sink weight

More information

Orientalmotor Thermal Management

Orientalmotor Thermal Management Thermal Management In recent years, the demand for equipment powered by natural energy sources such as solar and wind power, as well as the electric chargers for electric vehicles, has been rapidly increasing.

More information

Residential Building Walls and Environment in Amman, Jordan

Residential Building Walls and Environment in Amman, Jordan Int. J. of Thermal & Environmental Engineering Volume 3, No. 2 (211) 1-7 Residential Building Walls and Environment in Amman, Jordan S. J. Sulaiman*, N. Beithou Department of Mechanical Engineering, Applied

More information

Institute of Industrial Science, University of Tokyo Bulletin of ERS, No. 45 (2012) FAILURE OF CEILINGS IN AN AIRPORT BUILDING DURING THE 2011 OFF THE

Institute of Industrial Science, University of Tokyo Bulletin of ERS, No. 45 (2012) FAILURE OF CEILINGS IN AN AIRPORT BUILDING DURING THE 2011 OFF THE Institute of Industrial Science, University of Tokyo Bulletin of ERS, No. 45 (2012) FAILURE OF CEILINGS IN AN AIRPORT BUILDING DURING THE 2011 OFF THE PACIFIC COAST OF TOHOKU EARTHQUAKE AND ESTIMATION

More information