Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

Size: px
Start display at page:

Download "Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts"

Transcription

1 Article Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts Building Serv. Eng. Res. Technol. 206, Vol. 37() 66 84! The Chartered Institution of Building Services Engineers 205 DOI: 0.77/ bse.sagepub.com Xuemin Sui and Xu Zhang 2 Abstract This paper proposed to discuss some issues about indoor microclimate parameters design in radiant cooled residential buildings. Based on the thermal comfort model, the relationships between low mean radiant temperature and other thermal microclimate parameters such as indoor air temperature, air velocity, and relative humidity were analyzed. The improved and reasonable combinations of four thermal microclimate parameters including radiant cooling surface temperature, air temperature, air velocity, and relative humidity were further derived. Furthermore, a number of new thermal comfort charts using radiant cooling surface temperature and air temperature as dominant parameters were drawn. The results show that the air temperature can be increased 3 C within the recommended thermal comfort range when the mean radiant temperature is reduced 3 C. Under the design goal of thermal neutral, when the chilled ceiling surface temperature is in the range of 6 26 C, the air temperature should be set at C; when the chilled floor surface temperature is in the range of 9 26 C, the air temperature should be set at C. The design values of air velocity and relative humidity are not recommended to be changed, and still can follow the design standards for conventional all-air systems. Practical application: In this paper, some issues about indoor microclimate parameters design in radiant cooled buildings were discussed. A number of new thermal comfort charts using radiant cooling surface temperature and air temperature as dominant parameters were provided, and the design values of indoor air temperature, mean radiant temperature, air velocity, and relative humidity for radiant cooling system in residential buildings were also suggested. The research results can provide a more intuitive reference for the design of radiant cooling systems in residential buildings. Keywords Residential building, radiant cooling, thermal comfort, thermal microclimate parameter, thermal comfort chart School of Environmental Science and Engineering, Chang an University, Xi an, PR China 2 HVAC&Gas Institute, School of Mechanical Engineering, Tongji University, Shanghai, PR China Corresponding author: Xuemin Sui, School of Environmental Science and Engineering, Chang an University, Xi an 70054, China. suixuemin@63.com

2 Sui and Zhang 67 Introduction Radiant cooling system was first seriously investigated in European countries in the late 980s, and has become one of the popular design alternatives for space cooling in north-west Europe. In the early 2000s, radiant cooling systems began to be used in China. Since then, this technology has been increasingly applied in public buildings, 2 4 and has received increasing attention. Compared with conventional all-air systems, radiant cooling systems exhibit the superiority of thermal comfort and energy saving potential. The advantages of this system are as follows: 5 0 () reducing indoor vertical temperature gradient, almost no air flow, avoiding local discomfort; (2) decrease in air supply volume reduces cooling feeling due to cold air, and thus reduces the discomfort caused by draft; (3) reduction in air supply volume minimizes air transport energy consumption; (4) employing water to eliminate heat load instead of air greatly reduces energy consumption of cooling transport; (5) radiant cooling reduces the sensing temperature of human body and accordingly reduces system energy consumption; (6) high temperature of chilled water allows the use of natural resources and natural cooling in some seasons; (7) reducing indoor noise. In recent years, the indoor thermal environment and energy consumption problems of China s urban residential buildings have become severe. Summer air-conditioning devices have become increasingly prevalent, mainly dominated by convective air-conditioners. Of course, split air-conditioning unit will give better control of indoor air temperature and then improve human comfort and productivity. But there also exist many examples of discomfort due to draught, uniform temperature, noise, and sick building syndrome. On the other hand, the rapid increase of China s urban residential area objectively causes the rapid growth of residential building energy consumption. 2 Due to the shortcomings of current residential air-conditioning system, there is an urgent need for a new air-conditioning system to replace the traditional system. Many heating, ventilation, and air conditioning (HVAC) engineers and occupants turned their eyes to radiant cooling system, and it began to be gradually used in residential buildings of China. Currently, the residential applications of radiant cooling cases are mainly the technical systems of radiant cooling combined with ground-source heat pump, and the district buildings are centralized cooled. 3 5 However, centralized cooling cannot achieve occupants flexible adjustments and cannot meet occupants individual needs. In view of the above problems, the authors and their research team conducted a lot of studies on residential temperature humidity separate control air-conditioners. 6 2 These airconditioners used air source heat pump as the hot and cold sources, used radiant floor for heating in winter, used radiant ceiling for cooling in summer, and also employed outdoor air supply system to meet both indoor health requirements and dehumidification needs. Air-conditioning demand and air-conditioning usage patterns of residential buildings are different from that of public buildings. For the applications and promotions of radiant cooling systems in residential buildings to achieve good thermal comfort and energy saving, there are many design questions to be solved, including indoor thermal environment design, flexible system control, anti-condensation control, etc. In this study, we investigated the indoor thermal microclimate parameters design of residential buildings with radiant cooling systems. The determination of indoor design parameters is the first step of load calculation process in designing any HVAC system. There are four basic thermal microclimate parameters affecting human thermal sensations including indoor air temperature, relative humidity of indoor air, air velocity near human body, and mean radiant temperature. 22 The thermal comfort zone of the ASHRAE standard does not directly give the design ranges of indoor air temperature and mean radiant temperature, but it recommends the design range of operative temperature, which combines the effects of air temperature and mean radiant temperature.

3 68 Journal of Building Services Engineering Research & Technology 37() Relevant specifications in early Chinese design codes and manuals commonly take the first three parameters as the indoor design parameters, which based on the assumption that indoor environment is uniform, and indoor air temperature is equal to mean radiant temperature In the conventional air-conditioning design, there is no distinction between indoor air temperature and operative temperature or between indoor air temperature and indoor surface temperature in wall conduction load calculation. But this idea can not be used for radiant cooling systems, because indoor air temperature is not equal to mean radiant temperature in radiant cooled environment. Xuemin Sui et al. 9,27 took a large number of field measurements on the practical application of radiant cooling systems in residential buildings and evaluated the indoor thermal environment. The field measurement data showed that the mean radiant temperature was about 3 C lower than the air temperature. It is concluded that the mean radiant temperature is reduced due to the presence of radiant terminal device, and its value is lower than indoor air temperature. If the design values and ranges of the microclimate parameters combinations for traditional all-air systems were used for radiant cooling systems, it is bound to cause a certain bias between the design value and the actual value of human thermal comfort index. However, so far, the current radiant standards do not clearly give the indoor design thermal environment parameters for radiant cooling system. The international radiant cooling/heating standard ISO pointed out that compared with a convective heating and cooling system, a radiant heating system could achieve the same level of operative temperature at a lower air temperature and a radiant cooling system at a higher air temperature, but it did not give quantitative analysis and quantitative values. The European radiant cooling/heating standard EN pointed out that the operative temperature should be considered as relevant for thermal comfort assessment and heat loss calculations. But for current cooling load calculation method, indoor air temperature is needed for wall conduction load calculation. The new Chinese design code GB supplemented the design air temperature range for radiant cooling system based on the design temperature of C for civil buildings with convective air-conditioning system, and proposed the indoor design air temperature should increase C. However, this specification is not comprehensive enough, because low mean radiant temperature can also be compensated by some other measures to achieve the same comfort, such as changing the air velocity or the relative humidity. Therefore, for radiant cooling system, it is necessary to further combine and design the four basic microclimate parameters and to determine the appropriate combinations of them within the thermal comfort range. In addition, this provision can not provide a precise reference for designers because the increase of indoor design air temperature depends on the value of mean radiant temperature. Under what conditions should the indoor design temperature be increased 0.5 C, and under what conditions should be increased.5 C? This question does not be clearly solved. However, even if the difference is only C, it still has a non-negligible effect on building energy consumption. Previous research show the indoor design air temperature is increased by C, energy consumption can be reduced by 8 0% in the cooling conditions. 3 For different application cases, the mean radiant temperature values are different and difficult to be evaluated. The reduction of mean radiant temperature is mainly caused by the presence of radiant cooling panel surface, if some new thermal comfort charts taking radiant cooling surface temperature as dominant parameter could be drawn, it would provide a more intuitive reference for the design and application of radiant cooling system. The purpose of this study is to address these issues. In the present article, based on the thermal comfort model, the thermal microclimate parameters combinations in residential buildings were derived within the recommended thermal comfort range. The relationships between low

4 Sui and Zhang 69 mean radiant temperature and other thermal microclimate parameters including indoor air temperature, air velocity, and relative humidity were analyzed. Then the reasonable combinations of four microclimate parameters including radiant cooling surface temperature, indoor air temperature, air velocity, and relative humidity were further derived. In addition, a number of thermal comfort charts using radiant cooling surface temperature and air temperature as dominant parameters were drawn, and the reasonable range of the design value of each parameter was determined. The research results can provide a more intuitive reference for the design of radiant cooling system in residential buildings. Thermal comfort model Thermal comfort model is the base of thermal comfort evaluation methods and thermal environment standards. The purpose of this section is to describe the selection of thermal comfort model used in the study. According to the simplified method of human thermal system, there are mainly three types of thermal comfort models including single-node model, two-node model, and multi-node model. 32 In addition, there is another model called adaptive model mainly for non-airconditioned buildings. 33 The Predicted Mean Vote/Predicted Percentage Dissatisfied (PMV/ PPD) model is the most widely used singlenode model at present. Based on human thermal equilibrium theory, it is mainly used to predict human thermal responses and evaluate the overall thermal sensation in steady-state thermal environment controlled by air-conditioning systems. 34 The two-node and multi-node models all consider the physiological parameters and thermoregulatory mechanisms of human body, and they can be used to predict human thermal comfort in dynamic and non-uniform environments. 32 The so-called adaptive model is mainly used for naturally ventilated buildings It is not actually used to predict people s comfort responses, but is used to predict thermal environment parameters which can make people feel comfortable. It reflects the indoor comfort temperature variation trends along with the mean monthly outdoor air temperature. As for the determination of indoor design thermal parameters in air-conditioning system design, it is based on such a steady-state thermal environment well controlled by air-conditioning system. A lot of standards such as ISO 7730, 38 ASHRAE Standard , 23 Chinese Standard GB , 24 JGJ34-200, 25 and GB , 30 all use the PMV/PPD indices to describe and evaluate thermal environment, and also give the suggested design parameters of indoor thermal environment based on these indices. However, those provisions are aimed at conventional convectional air conditioning systems. The purpose of this study is to determine the design thermal environment parameters of residential buildings which employ radiant cooling systems. The thermal environment is well controlled and belongs to steadystate thermal environment, so the PMV/PPD model was also be used to derive the reasonable indoor thermal microclimate parameters combinations in the paper. The PMV/PPD model has been validated by many laboratory and field studies around the world since many years ago Besides, early researchers conducted a large number of experimental studies on thermal comfort in radiant cooled environment and proposed that the PMV/PPD model was also applicable to radiant cooled environment. 44 Factors that affect the PMV are metabolic rate, clothing insulation, air temperature, mean radiant temperature, air speed, and relative humidity. PPD is an index expressing the thermal comfort level as a percentage of thermally dissatisfied people, and is directly determined from PMV. Much more details including calculation methods of PMV and PPD are described in ISO It recommends the values of PMV/ PPD indices to be adopted: 0.5 PMV 0.5; PPD 0%. The main methodology of the paper is using MATLAB programming for determining combinations of microclimate parameters, based on the PMV/PPD model.

5 70 Journal of Building Services Engineering Research & Technology 37() When considering the dynamic or uneven effects of thermal environment, the two-node model or multi-node model should be selected. As for the issue on human thermal comfort in non-uniform radiant cooled thermal environment, it will be addressed in the follow-up studies. Effect of low mean radiant temperature on thermal comfort In this section, based on the PMV/PPD model, 38 programming with MATLAB, the effect of low mean radiant temperature on human thermal comfort was analyzed. The following calculating background conditions were considered: () indoor human activities commonly are sitting and resting, and the body metabolism rates are met; (2) residents generally are used to wearing shorts, blouses, pajamas, slippers, and other household clothing in summer, which have low insulation values in range of clo. In order to correspond to the summer condition of ASHRAE , 23 the I cl ¼ 0.5 clo condition was selected for analysis; (3) the indoor relative humidity is 50%, and the air velocity is 0. m/s. In practical applications, the difference between mean radiant temperature and indoor air temperature is often used to reflect the relative relationship between these two parameters. Figure shows the variation trends of the PMV index along with the temperature difference (4t, 4t ¼ t r t a ). It can be seen that, under different constant air temperature conditions, the variation of temperature difference causes a significant change of the PMV index. For example, under the condition with the indoor air temperature of 26 C, when the temperature difference is 0 C, the PMV index is 0.03, which means human thermal sensation is neutral. But when the temperature difference is 3 C, the PMV index is 0.55, which means human thermal sensation is slightly cool, and this value has exceeded the thermal comfort standard limit. 38 It is concluded that low mean radiant temperature makes the PMV index lower, and causes a cold sensation of human body. So the comfort environment design of radiant cooled room should consider not only the indoor air temperature but also the effect of mean radiant temperature. The design of indoor thermal microclimate parameters should attach importance to mean radiant temperature, and re-analyze the 3 ta=24 C ta=26 C ta=28 C ta=30 C 2 PMV Δt ( C) Figure. PMV index variation trends along with the difference between mean radiant temperature and air temperature.

6 Sui and Zhang 7 (a) 40 PMV=-0.5 PMV=-0.2 PMV=0 PMV=0.2 PMV=0.5 (b) 40 PMV=-0.5 PMV=-0.2 PMV=0 PMV=0.2 PMV=0.5 Air temperature ( C) Air temperature ( C) Mean radiant temperature ( C) Mean radiant temperature ( C) Figure 2. Air temperature variation trends along with low mean radiant temperature within thermal comfort range. (a) I cl ¼ 0.3 clo; (b) I cl ¼ 0.5 clo. appropriate combinations of indoor microclimate parameters. Relationships between low mean radiant temperature and other thermal microclimate parameters The analysis in Effect of low mean radiant temperature on thermal comfort section shows that the mean radiant temperature has a significant impact on the PMV index, and the decrease of mean radiant temperature caused a decrease of it. Whether the effects caused by low mean radiant temperature can be compensated by other thermal microclimate parameters such as air temperature, air velocity, and relative humidity? It was discussed based on MATLAB program for the PMV-PPD model. The relationships between low mean radiant temperature and these other thermal microclimate parameters were analyzed by the corresponding derivation procedure, respectively. Relationship between low mean radiant temperature and indoor air temperature Figure 2 shows the air temperature variation trends along with low mean radiant temperature within the thermal comfort range under the condition of v ¼ 0. m/s. It can be seen from Figure 2(a) and (b) that air temperature should be increased to reach the same thermal comfort when mean radiant temperature decreases. That means low mean radiant temperature can be compensated by higher air temperature. Neutral temperature is the temperature at which human body feels neither hot nor cold. 23 At this temperature, human body does not need to take additional physiological regulation to maintain its thermal equilibrium. In a thermal neutral condition, the value of PMV is 0. Whether in climate chamber experiments or in on-site investigations, neutral temperature is most often studied as an indicator. 45,46 So in this article, the relationship between low mean radiant temperature and air temperature was discussed when thermal sensation of human body was in thermal neutral or thermal comfort. Figure 2(a) shows the condition of I cl ¼ 0.3 clo. Under the thermal neutral conditions, when the mean radiant temperature is 26 C, the corresponding air temperature is 28.3 C; when the mean radiant temperature is 23 C with a reduced value of 3 C, the corresponding air temperature is 3 C with an increasing value of 2.7 C; when the mean radiant temperature is 20 C with a reduced value of 6 C, the corresponding air temperature is 33.6 C with an

7 72 Journal of Building Services Engineering Research & Technology 37() increasing value of 5.3 C. Figure 2(b) shows the condition of I cl ¼ 0.5 clo. Under the thermal neutral conditions, when the mean radiant temperature is 26 C, the corresponding air temperature is 26.2 C; when the mean radiant temperature is 23 C with a reduced value of 3 C, the corresponding air temperature is 28.9 C with an increasing value of 2.7 C; when the mean radiant temperature is 20 C with a reduced value of 6 C, the corresponding air temperature is 3.5 C with an increasing value of 5.3 C. Thus, it can be concluded that the design value of indoor air temperature for radiant cooling systems increases compared to all-air systems, and the increase level depends on the decrement of the mean radiant temperature. The increment of the design air temperature recommended by the current Chinese design code GB is low when used for residential buildings. The recommended increment should be increased by C when the mean radiant temperature is about 3 C lower than the air temperature. Relationship between low mean radiant temperature and air velocity Figure 3 shows the air velocity variation trends along with low mean radiant temperature within the thermal comfort range at constant air temperature of 26 C and constant relative humidity of 50%. Figure 3(a) and (b) shows the conditions of I cl ¼ 0.3 clo and I cl ¼ 0.5 clo, respectively. As can be seen from the two figures, each curve has an inflection point. These inflection points have zero air velocities. The position of inflection point depends on the PMV value, and it decreases with decreasing PMV value. On the right of inflection point, in order to reach the same thermal comfort, the lower the mean radiant temperature is, the lower the air velocity is. While on the left of inflection point, it shows an opposite variation trends that the lower the mean radiant temperature is, the higher the air velocity is. For example, in Figure 3(a), under the thermal neutral conditions, the mean radiant temperature of 20 C results in an air velocity of 0.02 m/s to reach the same thermal comfort, while the mean radiant temperature of 6 C results in an air velocity of 0.3 m/s. However, in actual situations, lower mean radiant temperature combining with higher air velocity will increase the cold sensation of human body. In this case, the solution derived from the thermal comfort model apparently departs from practical common sense. From the above discussion, it can be concluded that the effect of the reduction of mean (a) 0.4 PMV=-0.5 PMV=0 PMV=0.5 (b) 0.4 PMV=-0.5 PMV=0 PMV=0.5 Air velocity (m/s) Air velocity (m/s) Mean radiant temperature ( C) Mean radiant temperature ( C) Figure 3. Air velocity variation trends along with low mean radiant temperature within thermal comfort range. (a) I cl ¼ 0.3 clo; (b) I cl ¼ 0.5 clo.

8 Sui and Zhang 73 (a) Relative humidity (%) PMV=-0.5 PMV=0 PMV=0.5 (b) PMV=-0.5 PMV=0 PMV= Relative humidity (%) Mean radiant temperature ( C) Mean radiant temperature ( C) Figure 4. Relative humidity variation trends along with low mean radiant temperature under the thermal neutral condition. (a) I cl ¼ 0.3 clo; (b) I cl ¼ 0.5 clo. radiant temperature on thermal sensation can be compensated by lower air velocity. But the air velocity can only be reduced within a limited range. When air velocity drops to 0, if the mean radiant temperature continues to drop, it needs to be compensated by higher air velocity, which is contrary to the traditional common sense of thermal sensation. The reason for this result is that Fanger s thermal comfort model can only predict thermal sensation in a limited range. Outside this range, it may lead to a disagreement between the equation solution and common sense. Accordingly, the conclusion can be drawn that in order to reach the same comfort, low mean radiant temperature can be compensated by lower air velocity within a limited range. Relationship between low mean radiant temperature and relative humidity Figure 4 shows the relative humidity variation trends along with low mean radiant temperature within thermal comfort range at constant air temperature of 26 C and air velocity of 0. m/s. It can be seen from the figure, at different values of PMV, the relative humidity increases with the decrease of mean radiant temperature. However, the capability of using higher relative humidity to compensate for the effect of low mean radiant temperature is limited, because the value of relative humidity cannot be unlimitedly increased. Taking the thermal neutral condition of I cl ¼ 0.5 clo for example, a mean radiant temperature of 27 C corresponds to a relative humidity of 34.7%, while a mean radiant temperature of 24 C corresponds to a relative humidity of 94.6%. When the mean radiant temperature continues to drop below 24 C, the relative humidity value solved by the model equation has exceeded the maximum admissible value, and therefore the relative humidity can not be increased to compensate for the effect of low mean radiant temperature. It also can be seen from the figure that the compensating capability of relative humidity improves with the decrease of PMV. Using high relative humidity to compensate for low mean temperature can play a positive role in reducing energy consumption of air conditioning system. Especially in some high humid regions, increasing indoor design relative humidity can reduce dehumidification load, and thus reduce energy consumption of air conditioning system. But for indoor relative humidity design, in addition to considering the human thermal comfort, another important issue is the condensation of radiant cooling panel. Anti-condensation of radiant panel restricts the design range of indoor relative humidity. When the indoor control parameters such as air temperature and relative humidity are constant, the common

9 74 Journal of Building Services Engineering Research & Technology 37() Table. Dew point temperatures under different relative humidities at a constant air temperature of 27 C. Dry bulb temperature ( C) Relative humidity (%) anti-condensation measure is to control the water supply temperature of radiant panel to keep the panel surface temperature higher than the dew point temperature of indoor air. Table shows the values of dew point temperature under different relative humidities at a constant air temperature of 27 C. High relative humidity results in a high dew point temperature, which limits the surface temperature of radiant cooling panel. It can be seen from the table that the control surface temperature has been close to indoor air temperature when relative humidity is very high. For these conditions, the use of radiant cooling has lost its practical significance. Therefore, despite the conclusion that low mean temperature can be compensated by high relative humidity is significant to be recommended in view of climate characteristics of high humidity regions, the design range of relative humidity should not be increased due to the limited range of relative humidity for compensating, coupled with the constraints to relative humidity due to anti-condensation of radiant cooling panel. Improved combinations of parameters and new thermal comfort charts Dew point temperature ( C) According to the analysis in Relationships between low mean radiant temperature and other thermal microclimate parameters section, to reach the same thermal comfort, low mean radiant temperature can be compensated by higher air temperature, but should not be compensated by changing air velocity and relative humidity. The reduction of mean radiant temperature is caused by the radiant cooling panel surface, so the thermal microclimate parameters that affect human thermal sensation in radiant cooled environment can be further summarized as: indoor air temperature, indoor air relative humidity, air velocity near human body, and radiant cooling surface temperature. If the combination relationship of these four parameters in thermal comfort could be found, it would provide a more intuitive reference for the design and application of radiant cooling system. The following section aims to address this issue. In order to quantify the relationship between radiant cooling surface temperature and mean radiant temperature, the composition of mean radiant temperature should be first analyzed. The mean radiant temperature can be calculated by equation (): 22 T 4 mrt,p ¼ XN i¼ F p i T 4 i ðþ where, F p i is the view factor between body (denoted as p) and plane (denoted as i); T i is the surface temperature (K). Equation () shows that the value of mean radiant temperature depends on the temperature of each wall as well as the view factor between human body and each wall surface. Therefore, in order to get the values of mean radiant temperature of different radiant cooling surface temperatures, the temperature of each interior wall surface of different radiant cooling surface temperatures should be firstly found. The wall surface temperatures and their distribution characteristics can be determined by experiments. To study the thermal environment characteristics of radiant cooled residential building, a lot of field measurements have been conducted. 9,27 The residential building tested is a three-layer linking row villa located in Shanghai City. The testing period was 20 August 2008 to September 205, during which the outdoor temperature was 7 34 C.

10 Sui and Zhang Outdoor air Chilled ceiling surface Interior surface of south window Interior surface of west wall Interior surface of north wall Interior surface of east wall Floor surface Indoor air Mean radiant temperature Temperature ( C) :00 :09 :8 :27 :39 :48 :57 2:06 2:5 2:24 2:33 2:42 2:5 3:00 Time Figure 5. Indoor and outdoor air temperatures and interior wall surface temperatures. The layout of the measured building, the thermal properties of building envelopes, the tested radiant cooling system, the measurement equipment, and methodology have been elaborated in Sui et al. 9 Figure 5 shows the test data on indoor thermal environment at :00 3:00 on September 2008, which shows the relative relationship of the various parameters such as outdoor air temperature, indoor air temperature, interior wall surface temperatures, and mean radiant temperature. For the tested radiant chilled ceiling system, the cooling radiant terminal device was designed with a concrete core structure with pipes embedded in concrete slabs between each story, similar to radiant floor heating systems. The cooling surface covered the whole surface of the ceiling. In the testing phase, the chilled ceiling surface temperature is about 23 C, and the indoor air temperature is about 28 C. The south exterior wall is a large floor-toceiling window with a good exterior shading device. Its temperature is about 30.3 C due to the effect of outdoor air temperature. The surface temperatures of interior walls are lower than indoor air temperature due to the presence of chilled ceiling, and the mean radiant temperature is about 26.5 C. Due to the limitations of experimental conditions, the thermal storage of chilled ceiling, as well as the effect of outdoor meteorological parameters, the interior wall surface temperatures of different chilled ceiling surface temperatures under the same design condition cannot be obtained by experiments. This problem can be solved by thermal radiation heat transfer network. The geometry of the tested room is 4.6 m 3.4 m 2.8 m. Because the interior surface temperature of exterior wall mainly depends on the outdoor meteorological parameters, its value of different chilled ceiling surface temperatures under the same outdoor meteorological parameters condition can be considered as a

11 76 Journal of Building Services Engineering Research & Technology 37() E b3 ε3 ε A 3 3 X A, 3 J 3 X A 2,3 2 J J 2 E b ε ε A X A,2 ε 2 ε A 2 2 E b2 Figure 6. Radiation heat transfer network of a closed cavity with three gray surfaces. constant value. According to the experimental results, it is 30.3 C. The adjacent rooms are all air-conditioned rooms, so the temperature difference between the interior wall surface and the adjacent rooms can be negligible. As can be seen from the measured data, the interior surface temperatures of four interior walls have little difference. And further, because each interior surface has the same emitting rate, for simplicity, they may be regarded as equated with a wall with uniform surface temperature. Thus the radiant heat transfer between the wall surfaces of radiant cooled room can be simplified as a radiant heat transfer between three gray surfaces of a closed cavity including the exterior wall, the chilled ceiling, and the simplified interior wall. The radiation heat transfer network is shown in Figure 6. According to Kirchhoff s Current Law, the node equations of the radiation heat transfer network are listed as following: 47 Node : Node 2: Node 3: E b2 J 2 " 2 þ J 2 J þ J 3 J 2 ¼ 0 ð3þ " 2 A 2 X,2 A X 2,3 A 2 E b3 J 3 " 3 þ J J 3 þ J 2 J 3 ¼ 0 ð4þ " 3 A 2 X,3 A X 2,3 A 2 The net rate of radiation heat transfer from the interior wall surface can be calculated by equation (5): 3 ¼ E b3 J 3 " 3 ¼ 0 ð5þ " 3 A 3 Derived from the above equations, the calculation formula of the interior surface temperature of interior wall can be expressed by: E b J " þ J 2 J þ J 3 J ¼ 0 ð2þ " A X,2 A X,3 A T 2 3 ¼ X 3T 2 þ X 32T 2 2 T 2 3 ¼ 0:45T2 þ 0:55T2 2 ð6þ ð7þ

12 Sui and Zhang 77 Table 2. Comparison between experimental and calculated values. Outdoor air temperature ( C) Chilled ceiling surface temperature ( C) Interior wall surface temperature ( C) Experimental values Calculated values where A, A 2, and A 3 are the surface areas of the exterior wall, chilled ceiling, and interior wall, respectively (m 2 ); ", " 2, and " 3 are the surface emissivities of the exterior wall, chilled ceiling, and interior wall, respectively; E b, E b2, and E b3 are the emissive powers of the exterior wall, chilled ceiling, and interior wall, respectively (W/m 2 ); T, T 2, and T 3 are the surface temperatures of the exterior wall, chilled ceiling, and interior wall, respectively (K); J, J 2, and J 3 are the effective radiation rates of the exterior wall, chilled ceiling, and interior wall, respectively (W/m 2 ); X 2 is the view factor from the exterior wall to the chilled ceiling; X 3 is the view factor from the exterior wall to the interior wall; X 23 is the view factor from the chilled ceiling to the interior wall; X 3 is the view factor from the interior wall to the exterior wall; X 32 is the view factor from the interior wall to the chilled ceiling. Because some simplifications about the room and the wall conditions are made in the radiation network method described above, the applicability of equation (7) needs to be validated. This article validated it with experimental data. Table 2 gives the comparison between the experimental data and the calculated values at the experimental conditions that the chilled Table 3. Interior wall surface temperature of different chilled ceiling surface temperatures. Chilled ceiling surface temperature ( C) Interior surface temperature of exterior wall ( C) Interior surface temperature of interior wall ( C) ceiling surface temperature is about 23.3 C. It can be seen that the calculated and experimental values are basically consistent. Therefore, the interior surface temperature of the interior wall under different radiant cooling surface temperatures can be calculated by equation (7). The calculation results are shown in Table 3. It shows that the interior surface temperature of the interior wall increases with the increase of the chilled ceiling surface temperature. Because the internal heat gain is relatively small during the experimental period, only from the point of view on radiant heat transfer between wall surfaces, the chilled floor condition has the same interior wall surface temperature with the chilled ceiling condition. Therefore, the interior surface temperature of interior wall of different chilled floor surface temperatures can also use the data in Table 3. Another key parameter for the calculation of mean radiant temperature is the view factor between human body and each wall surface. The view factor between body (denoted as p)

13 78 Journal of Building Services Engineering Research & Technology 37() c b a b a c a b c a Figure 7. Geometric meanings of a, b, c. Table 4. View factors between human body and surrounding surfaces of the room. Surrounding surfaces of the room Surface Ceiling Floor East wall West wall South exterior window North wall View factor and plane (denoted as i) can be calculated by the following formula: 48 F p i ¼ X pffiffiffiffiffiffiffiffiffiffiffiffiffiffi tan Y p ffiffiffiffiffiffiffiffiffiffiffiffiffiffi 4 þ X 2 þ X 2 ð8þ Y þ pffiffiffiffiffiffiffiffiffiffiffiffiffiffi tan X p ffiffiffiffiffiffiffiffiffiffiffiffiffiffi þ Y 2 þ Y 2 where X ¼ a/.8c and Y ¼ b/.8c; meanings of a, b, and c are defined in ASHARE Handbook, 22 just as shown in Figure 7. Based on the geometrical dimensions of the room, the view factors between the human body and the surrounding surfaces of the room were calculated, as shown in Table 4. When the radiant terminal device employs chilled ceiling, its surface temperature can be set at 6 26 C within the range allowed by actual projects. But when chilled floor is employed, the floor surface temperature limit should be considered due to thermal comfort requirements. According to ASHRAE standard, 23 the acceptable floor temperature range for people wearing lightweight indoor shoes is 9 29 C within the comfortable requirements. So the acceptable chilled floor surface temperature range is 9 29 C. Based on the data in Table 3, using equation (), the mean radiant temperatures of different radiant cooling surface temperatures under chilled ceiling and chilled floor conditions were calculated, and the results are listed in Table 5. Because the view factor between human body and chilled floor is larger than that between human body and chilled ceiling, the radiation heat transfer between the human body and the chilled floor is larger than that between the human body and the chilled ceiling under the same cooling surface temperature conditions; therefore, the mean radiant temperature of human body in chilled floor condition is lower than that in chilled ceiling condition even though these two types of cooling surfaces have the same surface temperature. Based on the calculated results in Table 5 as well as Fanger s thermal comfort model, by Programming with MATLAB, the relationship between radiant cooling surface temperature and indoor air temperature under thermal neutral conditions was derived. In the derivation analysis, both the relative humidity and the air

14 Sui and Zhang 79 speed were constant with a value of 50% and 0.5 m/s, respectively. The thermal resistances of clothing were taken three sets of values of 0.25 clo, 0.5 clo and 0.65 clo, which respectively represented three types of representative summer dresses such as lightweight pajamas, Table 5. Mean radiant temperature of human body at different cooling surface temperatures. Surface temperature of radiant cooling ( C) Mean radiant temperature ( C) Radiant ceiling cooling ( C) Radiant floor cooling ( C) short-sleeved T-shirt + suit pants, long-sleeved shirt + dress pants. The derivation results are shown in Figure 8. In order to correspond to the summer condition of ASHRAE , the I cl ¼ 0.5 clo condition was selected for analysis. As can be seen from Figure 8(a), an indoor air temperature of C should be taken when the chilled ceiling surface temperature is in the range of 6 26 C. Similarly, as can be seen from Figure 8(b), when the chilled floor surface temperature is in the range of 9 26 C, an indoor air temperature of C should be taken. Figure 9 shows a comparison between the chilled ceiling condition and the chilled floor condition. As can be seen from the figure, at the same radiant cooling surface temperature, under thermal neutral conditions, the indoor air temperature required in the chilled floor condition is higher than that in the chilled ceiling condition; the temperature difference is greater with the decrease of the cooling surface temperature, and the difference is up to C when the cooling surface temperature is 9 C. This is because the lower the cooling surface temperature is, the greater the radiant heat exchange between the human body and the cooling surface in chilled floor condition is and the lower the mean radiant temperature of human body is, compared with the chilled ceiling condition. (a) (b) Icl=0.25clo Icl=0.5clo Icl=0.65clo Icl=0.25clo Icl=0.5clo Icl=0.65clo Chilled ceiling surface temperature ( C) Chilled floor surface temperature ( C) Air temperature ( C) Air temperature ( C) Figure 8. Thermal comfort charts of different clothes resistances (v ¼ 0.5 m/s, ¼ 50%). (a) Chilled ceiling; (b) chilled floor.

15 80 Journal of Building Services Engineering Research & Technology 37() 30 Air temperature ( C) I cl =0.5clo Chilled ceiling Chilled floor Cooling surface temperature ( C) Figure 9. Comparison between chilled ceiling condition and chilled floor condition. (a) 30 (b) 30 v=0. v=0.2 v=0.3 v=0. v=0.2 v= Chilled ceiling surface temperature ( C) Chilled floor surface temperature ( C) Air temperature ( C) Air temperature ( C) Figure 0. Thermal comfort charts of different air velocities (I cl ¼ 0.5 clo, ¼ 50%). (a) Chilled ceiling; (b) chilled floor. It leads to higher indoor air temperature required in chilled floor condition. Figure 0(a) and (b) respectively shows thermal comfort charts of chilled ceiling condition and chilled floor condition under different air velocities, which respectively presents the relationship between air temperature and chilled ceiling surface temperature or chilled floor surface temperature of different air velocities, under thermal neutral conditions. Taking into account that high air velocity will cause local thermal discomfort, its range in this paper is taken in accordance with the recommended range for traditional all air conditioning system in summer, and the air velocities of 0., 0.3, and 0.5 m/s were taken. Different combinations of parameters can achieve the same thermal comfort. Taking the data in Figure 0(a) for example, human body in the thermal environment with air temperature of 29. C, cooling surface temperature of 6 C, and air velocity of 0. m/s, has the same thermal comfort with that in the thermal environment with air temperature of 27.7 C, cooling surface temperature of 23 C, and air velocity of 0.3 m/s. In addition, it can be seen from Figure 0 that the lower the cooling surface temperature is, the smaller the effect of air velocity is.

16 Sui and Zhang 8 (a) 3 Air temperature ( C) % 40% 50% 60% 70% Chilled ceiling surface temperaure ( C) (b) 3 Air temperature ( C) % 40% 50% 60% 70% Chilled floor surface temperature ( C) Figure. Thermal comfort charts of different relative humidities (I cl ¼ 0.5 clo, v ¼ 0.5 m/s). (a) Chilled ceiling; (b) chilled floor. Figure (a) and (b) respectively shows thermal comfort charts of chilled ceiling condition and chilled floor condition at different relative humidities, which respectively presents the relationship between air temperature and chilled ceiling surface temperature or chilled floor surface temperature of different relative humidities, under thermal neutral conditions. The relative humidity range is not particularly limited in ASHRAE s thermal comfort standard. 23 But from the point of view of thermal comfort, extreme values of relative humidity should be avoided. The recommended level for relative humidity in ISO standard is between 30% and 70%, and this range is appropriate to avoid some uncomfortable problems including skin dryness or wetness, eye irritation, and respiratory inflammation. Therefore, a 30 70% relative humidity range was used in this section. From Figure (a) and (b) it can be seen that under the conditions of the same cooling surface temperature, when the relative humidity increases, the indoor air temperature should be reduced to achieve thermal neutral condition. Conclusions Based on the thermal comfort model, the relationships between low mean radiant temperature and other thermal microclimate parameters such as indoor air temperature, air velocity, and relative humidity, were analyzed, and the improved and reasonable combinations of four thermal microclimate parameters including radiant cooling surface temperature, indoor air temperature, air velocity, and relative humidity were further derived. Furthermore, a number of new thermal comfort charts taking radiant cooling surface temperature and air temperature as dominant parameters were drawn, which can provide a more intuitive reference for the design of radiant cooling systems. The main conclusions were drawn as follows:. Under the constant indoor air temperature conditions, low mean radiant temperature makes the PMV index drop. A 3 C drop of mean radiant temperature can cause a PMV index drop of In order to reach the same thermal comfort, low mean radiant temperature can be compensated by increasing air temperature. Within the recommended thermal comfort range, when the mean radiant temperature is reduced by 3 C, the indoor air temperature should be increased by 3 C; when the mean radiant temperature is reduced by 6 C, the indoor air temperature should be increased by C. Under thermal neutral conditions, when the mean radiant temperature is reduced by 3 C, the indoor air temperature should be increased by 2.7 C; when the

17 82 Journal of Building Services Engineering Research & Technology 37() mean radiant temperature is reduced by 6 C, the indoor air temperature should be increased by 5.3 C. The increase of design air temperature recommended by the current Chinese design code GB is low when used for residential buildings. 3. In order to reach the same thermal comfort, low mean radiant temperature can be compensated by lower air velocity. But because the air velocity can only be reduced within a limited range, the compensating capability is limited. Low mean radiant temperature can also be compensated by higher relative humidity. This method is very useful from the energysaving view point, but it will increase the possibility of condensation of radiant devices and is not recommended to be used. 4. Radiant cooling surface temperature and indoor air temperature are the two most important parameters in radiant cooling system design. The new thermal comfort charts taking these two parameters as dominant parameters can provide a more intuitive reference for the design of radiant cooling systems. Under the design goal of thermal neutral, when the chilled ceiling surface temperature is in the range of 6 26 C, the indoor air temperature should be taken as C; when the chilled floor surface temperature is in the range of 9 26 C, the indoor air temperature should be taken as C. The design values of air velocity and relative humidity are not recommended to be changed, and still can follow the design standards for conventional all-air systems. 5. The results of this study apply only to residential buildings. The research methods used in the paper applies equally to public buildings, but the results may show different patterns. Due to the lack of test data about the indoor thermal environment in public buildings cooled by radiant systems at present, the relations between the radiant cooling surface temperature and the mean radiant temperature cannot be established. So this study does not extend to public buildings. It will be addressed in the follow-up studies. Declaration of conflicting interests The author(s) declared no potential conflicts of interest with respect to the research, authorship, and/or publication of this article. Funding The author(s) disclosed receipt of the following financial support for the research, authorship, and/or publication of this article: the Key Project of the National Eleventh Five Year Research Program of China (Grant No. 2006BAJ0A05), the National Natural Science Foundation of China (Grant No ), the Postdoctoral Science Foundation of China (Grant No. 203M532002), the Construction Scientific Project of Xi an City (Grant No. SJW20323), and the Natural Science Foundation of Shanxi Province (Grant No. 205JQ553). References. Wilkins CK and Kosonen R. Cool ceiling system: a European air-conditioning alternative. ASHRAE J 992; Chao C and Zhang Y. Feasibility analysis of energy efficiency reformation of an existing office build in glob by with floor panel cooling and heating system. Heat Ventilating Air Cond 200; 40: Zou ZS and Li GF. Design of air conditioning system for Tianjin Railway Station. Heat Ventilating Air Cond 200; 40: Fan L and He KJ. Study and application of floor panel heating/cooling system in lobbies of Wukesong Gymnasium. Heat Ventilating Air Cond 2005; 35: Memon RA, Chirarattananon S and Vangtook P. Thermal comfort assessment and application of radiant cooling: a case study. Build Environ 2008; 43: Imanari T, Omori T and Bogaki K. Thermal comfort and energy consumption of the radiant ceiling panel system: comparison with the conventional all-air system. Energ Build 999; 30: Tian Z and Love JA. Energy performance optimization of radiant slab cooling using building simulation and field measurements. Energ Build 2009; 4: Niu JL and Zhang LZ. Energy savings potential of chilled-ceiling combined with desiccant cooling in hot and humid climates. Energ Build 2002; 34: Wang S and Morimoto M. Evaluating the low exergy of chilled water in a radiant cooling system. Energ Build 2008; 40: Oxizidis S and Papadopoulos AM. Performance of radiant cooling surfaces with respect to energy consumption and thermal comfort. Energ Build 203; 57: Yang W. The investigation of thermal comfort and thermal adaptation in residential buildings during the summer

Experimental study of fan coil assisting radiant floor heating system

Experimental study of fan coil assisting radiant floor heating system Journal of Scientific Research and Studies Vol. 4(12), pp. 394-401, December, 2017 ISSN 2375-8791 Copyright 2017 Author(s) retain the copyright of this article http://www.modernrespub.org/jsrs/index.htm

More information

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING Vladimír Zmrhal 1, Jan Hensen 2 and František Drkal 1 1

More information

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER 2000 Elsevier Science Ltd. All rights reserved. Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 731 IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

More information

Experimental study of space cooling using ceiling panels equipped with capillary mats

Experimental study of space cooling using ceiling panels equipped with capillary mats Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding email: tiberiu.catalina@insa-lyon.fr SUMMARY

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

,Chaojian He6, f. School of Guangxi University, Nanning , China.

,Chaojian He6, f. School of Guangxi University, Nanning , China. 5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) The Research on Running Characteristics of A New Type of Radiant Air Conditioning Combined with Fresh

More information

A study of radiant cooling for a room with daytime application in tropical climate

A study of radiant cooling for a room with daytime application in tropical climate International Journal of Smart Grid and Clean Energy A study of radiant cooling for a room with daytime application in tropical climate Satinee Wongkee, Surapong Chirarattananon, Pipat Chaiwiwatworakul

More information

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room Yanli Ren 1 ; Deying Li 2 ; Yufeng Zhang 1 1 School of Environment Science and Engineering, Tianjin University, Tianjin 300072,

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

International Forum on Energy, Environment Science and Materials (IFEESM 2015) The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,

More information

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM Available online at www.sciencedirect.com ScienceDirect Energy Procedia 61 (2014 ) 882 886 The 6 th International Conference on Applied Energy ICAE2014 INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 215, 9, 7-14 7 Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning

More information

Human response to thermal environment in rooms with chilled beams

Human response to thermal environment in rooms with chilled beams Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment

More information

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen * Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement

More information

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Comparison of Thermal Comfort by Radiant Heating and Convective Heating Journal of Engineering, Project, and Production Management 2015, 5(1), 26-35 Comparison of Thermal Comfort by Radiant Heating and Convective Heating Shigeru Imai 1 and Shoichi Kojima 2 1 MSc Student, Department

More information

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING G. COURRET, P. W. EGOLF, O. SARI Haute école spécialisée de Suisse occidentale, Institut de Génie Thermique, Rte de Cheseaux 1, CH

More information

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling Aleksandra Cichoń,*, Anna Pacak, Demis Pandelidis, and Sergey Anisimov Department of

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between

More information

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM STUDY ON A FLOOR SULY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED CM S. Takeda, K. Nagano, K. Nakayama, K. Shimakura Hokkaido University Sapporo, 060-8628 Japan Tel: +81-11-706-7597

More information

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Journal of Electronics and Information Science (2018) 3: 22-33 Clausius Scientific Press, Canada Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics Lian-Tuu Yeh, ASME Fellow

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Thermal Comfort with Convective and Radiant Cooling Systems

Thermal Comfort with Convective and Radiant Cooling Systems Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with

More information

Comparison of radiant and convective cooling of office room: effect of workstation layout

Comparison of radiant and convective cooling of office room: effect of workstation layout Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM Yoshihiro Aizawa 1, Shin-ichi Tanabe 2, Kanako Yokoo 2, Kentaro Watanabe 3, and Hideki Amai 4 1 Tokyo Gas Co. Ltd., Tokyo, Japan 2 Waseda

More information

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures Advanced Materials Research Online: 2013-06-27 ISSN: 1662-8985, Vols. 712-715, pp 1614-1618 doi:10.4028/www.scientific.net/amr.712-715.1614 2013 Trans Tech Publications, Switzerland The Energy Consumption

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection Finned s for Cooling Outdoor Electronics under Natural Convection Lian-Tuu Yeh, Ph D & PE Thermal Consultant, Dallas, TX, 75252 USA Abstract For tower or poled mounted electronics, the heat sink weight

More information

Optimisation of cooling coil performance during operation stage for improved humidity control

Optimisation of cooling coil performance during operation stage for improved humidity control Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National

More information

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi

More information

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY Proceedings of BS5: 4th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 5. AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN

More information

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne

More information

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI

ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI International Journal of Scientific & Engineering Research Volume 9, Issue 4, April-2018 238 ANALYSIS OF RADIANT COOLING IN CONCRETE SLABS WITH EMBEDDED PIPES ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA

More information

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan

More information

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss Experimental Study on the Effects of Compression arameters on Molding Quality of Dried Fish Floss Hongmei Xu, Li Zong, Ling Li, and Jing Zhang College of Engineering and Technology, Huazhong Agricultural

More information

Monetization of Thermal Comfort in Residential Buildings

Monetization of Thermal Comfort in Residential Buildings Monetization of Thermal Comfort in Residential Buildings Xia Fang, Marcus V. Bianchi, Craig Christensen, National Renewable Energy Laboratory ABSTRACT Building energy simulations can help us determine

More information

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION 2597, Page 1 Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump Ian H. BELL 1 *, James E. BRAUN 2 1 Bell Thermal Consultants ian.h.bell@gmail.com 2 Purdue

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0232 ISBN: 978-83-7947-232-1 Experimental study of a novel dew point indirect evaporative cooler Wenhua Chen, Zhiwei Zhang, Jiayu Li,

More information

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170

More information

Unit 4: Science and Materials in Construction and the Built Environment. Thermal Comfort

Unit 4: Science and Materials in Construction and the Built Environment. Thermal Comfort 2.1 Introduction Thermal Comfort The thermal comfort of human beings is governed by many physiological mechanisms of the body and these vary from person to person. In any particular thermal environment

More information

Thermal Environment Evaluation in Commercial Kitchens of United States

Thermal Environment Evaluation in Commercial Kitchens of United States Downloaded from orbit.dtu.dk on: Jul 25, 2018 Thermal Environment Evaluation in Commercial Kitchens of United States Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation

More information

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian

More information

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System International Conference on Civil, Transportation and Environment (ICCTE 201) Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System Pengjie Fan1, a, Caihua Liang1,

More information

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil B,L.A. Isaka 1, B.C. Madushanka 1 and N.H. Priyankara 1 1 Department of Civil and Environmental Engineering Faculty of Engineering University

More information

Center for the Built Environment October 2013

Center for the Built Environment October 2013 Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research

More information

ω = (1) Kirby S. Chapman Ph.D.

ω = (1) Kirby S. Chapman Ph.D. White Paper: Relative Humidity Impacts of the AirFloor System in the Built Environment Kirby S. Chapman Ph.D. kirby.chapman@scavengetech.com Introduction Relative humidity is specified as one of the seven

More information

Dynamic performance of a novel dew point air conditioning for the UK buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings *Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

European Researcher, 2014, Vol.(75), 5-2

European Researcher, 2014, Vol.(75), 5-2 Copyright 2014 by Academic Publishing House Researcher Published in the Russian Federation European Researcher Has been issued since 2010. ISSN 2219-8229 E-ISSN 2224-0136 Vol. 75, No. 5-2, pp. 932-939,

More information

American Society of Heating, Refrigerating and Air-Conditioning Engineers

American Society of Heating, Refrigerating and Air-Conditioning Engineers Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:

More information

Design of Multi-Sensors Cooperation Control System for Intelligent Building

Design of Multi-Sensors Cooperation Control System for Intelligent Building Energy and Power Engineering, 2017, 9, 495-502 http://www.scirp.org/journal/epe ISSN Online: 1947-3818 ISSN Print: 1949-243X Design of Multi-Sensors Cooperation Control System for Intelligent Building

More information

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca

More information

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP

More information

Recent Advances in Energy, Environment and Economic Development

Recent Advances in Energy, Environment and Economic Development Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar

More information

A Study on Landscape Design Paradigm from the Perspective of Visual Impact and Experience

A Study on Landscape Design Paradigm from the Perspective of Visual Impact and Experience 2017 3rd International Conference on Social Science, Management and Economics (SSME 2017) ISBN: 978-1-60595-462-2 A Study on Landscape Design Paradigm from the Perspective of Visual Impact and Experience

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

*Corresponding author # Presenting author DOI: /jki th International Working Conference on Stored Product Protection

*Corresponding author # Presenting author DOI: /jki th International Working Conference on Stored Product Protection Study on in-store drying technology of paddy in China Guo, D., Yang, J., Luo, H.#, Fu, P., Wang, S., Li, Y.* Chengdu Grain Storage Research Institute, No.95 Huapaifang Street, Chengdu, Sichuan, 610031,

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura

More information

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE NH Wong, BRJ Huang, KW Tham, C Sekhar and DKW Cheong Dept. Of Building, School of Design and Environment, National University of Singapore, Singapore

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

Investigation of Thermal Environments in Humid Tropical Classroom in Indonesia

Investigation of Thermal Environments in Humid Tropical Classroom in Indonesia Journal of Engineering and Architecture June 2017, Vol. 5, No. 1, pp. 1-14 ISSN: 2334-2986 (Print), 2334-2994 (Online) Copyright The Author(s). All Rights Reserved. Published by American Research Institute

More information

Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings

Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings L. Georges*, K. Wen*,c, M.J. Alonso b, M. Berge*, J. Thomsen b and R. Wang c *Energy and Process Engineering

More information

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2 01-014 The 2005 World Sustainable Building Conference, DEVELOPMENT OF A PASSIVE COOLING STRATEGY USING DOUBLE-ROOFING SYSYTEM WITH RAINWATER SPRAYING AND ITS FIELD TESTING IN TERMS OF THE INDOOR THERMAL

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort

The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort International Journal of Research in Engineering and Science (IJRES) ISSN (Online): -9364, ISSN (Print): -9356 Volume 4 Issue 1 ǁ January. 16 ǁ PP.56-61 The Low-Temperature Radiant Floor Heating System

More information

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek

More information

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY M Kojima, T Saito Graduate School of Environmental Studies, NAGOYA University, Chikusa, Nagoya, 464-8603

More information

How to ensure Thermal Comfort in buildings with CFD

How to ensure Thermal Comfort in buildings with CFD How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model Yoshiyuki Shimoda, Osaka University Takuro Fujii, Osaka University Takao Morikawa, Osaka University Minoru

More information

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Impact of indirect evaporative air cooler type on the performance of desiccant systems Impact of indirect evaporative air cooler type on the performance of desiccant systems Anna Pacak 1,*, Aleksandra Cichoń 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of Science and

More information

Analysis of the performance profile of the NCERD thermosyphon solar water heater

Analysis of the performance profile of the NCERD thermosyphon solar water heater Analysis of the performance profile of the NCERD thermosyphon solar water heater Solomon Agbo National Centre for Energy Research and Development, University of Nigeria, Nsukka Abstract The work reported

More information

A Simulation Study on the Energy Efficiency of Gas-Burned Boilers in Heating Systems

A Simulation Study on the Energy Efficiency of Gas-Burned Boilers in Heating Systems International Journal of Energy and Power Engineering 2015; 4(6): 327-332 Published online December 5, 2015 (http://www.sciencepublishinggroup.com/j/ijepe) doi: 10.11648/j.ijepe.20150406.11 ISSN: 2326-957X

More information

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling The cooling capacity of the Thermo Active Building System combined with acoustic ceiling Peter Weitzmann, Technical consultant, BuildDesk A/S; peter.weitzmann@builddesk.dk Emanuele Pittarello, MSc, International

More information

Cooling load calculations of radiant and all-air systems for commercial buildings

Cooling load calculations of radiant and all-air systems for commercial buildings Downloaded from orbit.dtu.dk on: Aug 17, 2018 Cooling load calculations of radiant and all-air s for commercial buildings Bourdakis, Eleftherios; Bauman, Fred; Schiavon, Stefano; Raftery, Paul; Olesen,

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE

Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE 10 2018 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TABS VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested

More information

Study on an environmental simulation system of low/high temperature. for great space

Study on an environmental simulation system of low/high temperature. for great space International Conference on Advances in Energy and Environmental Science (ICAEES 2015) Study on an environmental simulation system of low/high temperature for great space Weike Pang1, a*, Tianping Liu1,

More information

Analysis of Heating Systems and Scale of Natural Gas-Condensing Water Boilers in Northern Zones

Analysis of Heating Systems and Scale of Natural Gas-Condensing Water Boilers in Northern Zones Analysis of Heating Systems and Scale of Natural Gas-Condensing Water Boilers in Northern Zones Yuanyuan Wu Suilin Wang Shuyuan Pan Yongzheng Shi Postgraduate Professor Engineer Assistant Urban Construction

More information

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue

More information

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS Masaya Saito*, Satoshi Nasu*, Moto Nakano** and Kouko Miyakawa*** *Sapporo School of The Arts Geijustu-no-mori

More information