Optimisation of cooling coil performance during operation stage for improved humidity control
|
|
- Lynette French
- 5 years ago
- Views:
Transcription
1 Indoor Air 2008, August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National University of Singapore, Singapore * Corresponding bdgscs@nus.edu.sg SUMMARY In hot and humid climates, indoor humidity levels are usually high and this is a matter of concern from Thermal Comfort and IAQ perspectives. This phenomenon can be attributed to the inadequate dehumidifying performance of the cooling coil. Amongst other factors, poor dehumidifying coil performance results from the selection and installation of an oversized coil and the conventional strategy of modulating the chilled water flow rate as the only available control method. It is not uncommon to find that operating conditions demand a reduced chilled water flow rate not just during part-load conditions but even during the actual peakload condition. Based on a simulation method that involves selection of coils for different conditions, this paper presents the findings of the performance evaluation of an oversized coil at different conditions during the operation stage. The findings show that the dehumidifying performance of the oversized coil at reduced loads during normal operation can be significantly enhanced by changing the effective surface area of the coil through a simple manipulation of the effective number of rows of coil operation. KEYWORDS Cooling coil, Dehumidifying performance, Design and operation, Thermal comfort and IAQ, Hot humid climates INTRODUCTION In hot and humid climates, the performance of the cooling and dehumidifying coil has a strong bearing on the eventual indoor environmental conditions, which in turn, has a tremendous impact on the indoor air quality. It is important to recognize that the primary function of the cooling coil is not just cooling but the ability to cool and dehumidify in the correct proportion of sensible and latent loads in which they occur in a dynamically changing operation stage (Sekhar et al., 1989). Thus, the room sensible heat ratio (RSHR) and the sensible heat ratio (SHR) of the coil are key design considerations. Notwithstanding the design of the coil, its operation is typically controlled by attempting to match the actual cooling load in operation with the required coil capacity. The only way to achieve this is by modulating the chilled water flow rate. Some control strategies include the use of air-bypass around the coils or temperature reset (Mathews et al., 2001). Often, the cooling coils are oversized due to an over estimation of the anticipated cooling loads and this would have a detrimental effect on the cooling and dehumidifying performance at part load operating conditions. Inevitably, conventional HVAC control strategies would inhibit the ability of the coil to dehumidify exactly when the opposite is desired. This paper deals with the issues associated with overdesigning, commonly prevalent in typical design practice, and recommends a solution that can result in improving the cooling and dehumidifying performance of the oversized coils in a dynamically fluctuating operation stage.
2 METHODS A simulation approach is adopted in this study that involves an evaluation of the coil performance for various operating conditions and through the use of various coil geometries. A standard coil selection program, freely downloadable from the internet, is used in performing the simulations (SPC 2000, 2007). A hypothetical building with an actual maximum cooling load of 100 kw supplied with a 200 kw design capacity (oversized) cooling coil is considered. The required indoor air condition for the entire simulation is set at 24.5 C with an expected relative humidity of 60%, resulting in the upstream coil conditions of 26 C DBT and 65% RH. The psychrometric state points, associated with the design conditions of 200 kw, are shown in Figure 1. The simulations at other anticipated operating conditions are then performed and this process involves the use of the oversized coil as well as coils with other geometries that are customized to the prevailing cooling loads. Based on the evaluation of the various simulation results, a solution is recommended that could result in an improved performance of the oversized coil during the normal operation stage. No Parameter Values 1 Outside Air 32 C DBT & 75% RH 2 Enteringcoil condition 26 C DBT & 65% RH 3 Return air condition 24.5 C DBT & 60% RH 4 Space condition 24 C DBT & 63% RH 5 Leaving coil condition 13 C DBT & 12.5 C WBT 6 Chilled water supply temperature 6 C 2 1 DBT Dry Bulb Temperature WBT Wet Bulb Temperature RH Relative Humidity Coil Condition Curve Room Sensible Heat Ratio Figure 1. Psychrometric state points for the base-case simulation of the oversized coil. RESULTS AND DISCUSSION Coil selected for design capacity Operating at design capacity Since the simulation exercise aims at comparing between the various cooling coil operating conditions, the first step is to simulate the coil at design capacity (also known as base case). Both Table 1 and Table 2 show the configuration of the cooling coil at its design capacity (base case). Table 1 shows the conditions that are required to remain constant throughout the entire simulation while Table 2 shows the required conditions, with some having the ability to be manipulated to simulate the effectiveness of the various operating conditions. The different simulated conditions can then be used to determine the difference in coil performance as compared to the base condition.
3 Table 1. Fixed configuration of the cooling coil at design capacity. Air Side Air on DB Temp 26 C RH (%) 65% Standard Air Yes Fluid Side Fluid on Temp 6 C Max Pressure Drop 50kPa Physical Fin Material/type Aluminium 0.15 rippled Coil Type water Tube Diameter 16mm Tubes High 30 Finned Height 1218mm Finned Length 2100mm No. of sections 1 Surface Margins 1 Table 2. Adjustable configuration of the cooling coil at design capacity. Air Side Air Flow (m3/s) 6.45 Face Velocity 2.52 Air off DB 13 Air off WB 12.5 Capacity ( kw) 200 SHR (%) 52% Physical Rows 6 Fin Density 9 Circuit type F Fluid Fluid on Temp 6 Side Fluid off Temp 12 Fluid flow rate (l/s) 7.96 Actual PD 56.5 Oversized coil - Operating at actual maximum peak load While the coil design capacity is 200 kw, the actual maximum peak load is only 100 kw and thus, the coil is now oversized. Series A1 simulates the oversized coil operating at actual peak load condition. To understand the effectiveness of operating the design capacity coil operating at half its design load, a comparison between base condition (Design load) and Series A1 (Actual Peak load) is shown in Table 3.
4 The basic performance criterion for any typical cooling coil is often judged by its cooling capacity (sensible) and its dehumidification (latent) capability, which is measured in terms of SHR. As seen in Table 3, operating a coil at half its design capacity (from 200 kw to 100 kw) increases the SHR by 10%. Kavanaugh (2006) elaborated that coils with higher SHR may reduce temperature too quickly for adequate moisture removal to occur, while coils with low SHR may dry out the air too much and indoor air may become too dry. This 10% increase in SHR could affect the air quality that is produced as the efficiency of the dehumidification process is reduced, i.e. the coil is able to achieve the required temperature but at a higher humidity. This higher humidity could affect both the indoor air quality and thermal comfort. Table 3. Comparison between coils operating at design and peak load. Base Series A1 Air Side Air Flow (m3/s) Face Velocity Air off DB Air off WB Capacity ( kw) SHR (%) 52% 62% Physical Rows 6 6 Fin Density 9 9 Circuit type F F Fluid Side Fluid on Temp 6 6 Fluid off Temp Fluid flow rate (l/s) Actual PD In order to improve the dehumidifying performance through a reduction of the SHR, a simulation was performed to match the actual maximum cooling load with the correct heat transfer surface area. This, naturally, leads to a reduction of the overall heat transfer surface area, and therefore, leads to the exploration of 4-row and 3-row coils. The simulated series A1, B1 and C1 in Table 4 were simulated while keeping the coil duty and air flow rate constant at 100 kw and 6.45 m 3 /s respectively. Meanwhile, the effective number of rows in the coil was reduced from 6 to 4 and eventually to 3. Figure 2 shows the analyzed results from Table 4, and it can be clearly seen that by reducing the effective number of operating coil rows, from a 6-row to a 4-row and finally to a 3-row configuration, SHR could be reduced thus increasing the coil efficiency.
5 Table 4. Simulation of coils operating at peak load with reduced coil rows. Base Series A1 Series B1 Series C1 Air Side Air Flow (m3/s) Face Velocity Air off DB Air off WB Capacity( kw) SHR (%) 52% 62% 61% 58% Physical Rows Fin Density Circuit type F F F F Fluid Side Fluid on Temp Fluid off Temp Fluid flow rate (l/s) Actual PD Reduction of SHR with a reduction in number of Coil Rows 62% 61% 60% SHR (%) 59% 58% 57% 56% Series A1 Series B1 Series C1 6 row s 4 row s 3 row s Simulated Conditions Figure 2. Coil SHR performance with respect to reducing rows. Oversized coil - Operating between actual maximum and part loads If the actual maximum cooling load ie the actual peak load is only 100 kw, the part load operating conditions would experience an even further reduction in coil capacity. In order to explore the performance of the oversized coil at actual part loads, a simulation is performed at a part load capacity of 50 kw (Series A3). A simulation is also performed to evaluate the performance of a 3-row coil with reduced total surface area (Series C3). It is seen from Table
6 5 that the lower capacity of 50 kw increases the SHR by well over 30% for the oversized 6- row coil. The performance, in terms of SHR, is significantly improved with a 3-row coil. It is, therefore, recommended that a simple chilled water by-pass strategy be adopted to reduce the effective surface area of the coil from a 6-row coil to a 4-row or a 3-row coil during operation stage. Table 5. 6-row and 3-row coils operating at a part load of 50 kw. Base Series A3 Series C3 Air Side Air Flow (m3/s) Face Velocity Air off DB Air off WB Capacity ( kw) SHR (%) 52% 87% 75% Physical Rows Fin Density Circuit type F F F Fluid Side Fluid on Temp Fluid off Temp Fluid flow rate (l/s) Actual PD CONCLUSIONS This paper has addressed an important practical challenge related to the operation of an oversized cooling and dehumidifying coil. The impact of such a coil at various operating conditions including those at design, actual peak and part load has been evaluated through a simulation approach. The Sensible Heat Ratio has been used as an indicator of the dehumidifying performance of the coil and, for the worst case scenario of 50 kw cooling load, it is observed that changing the effective surface area of the coil from 6-rows to 3 rows results in a reduction of SHR from 87% to 75%. This is a significant improvement in the dehumidifying performance of the oversized coil.
7 REFERENCES Kavanaugh, Stephen P HVAC Simplified. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Mathews, E.H., C.P.Botha, D.C.Arndt, A.Malan HVAC control strategies to enhance comfort and minimize energy usage. Energy and Buildings, Volume 33, No.8, pp SPC 2000: Version 4.7, Coil selection and rating (self-selection software, free download from S&P Coil Products Limited, United Kingdom. Sekhar, S.C., R.E. Luxton and A. Shaw Design methodology for cost-effective air conditioning in humid climates. In Far East Conference on Air Conditioning in Hot Climates, October 1989, Shangri-La Hotel, Kuala Lumpur, Malaysia, edited by ASHRAE, pp Atlanta: American Society of Heating, Refrigerating and Airconditioning Engineers, October 1989.
CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationAvailable online at Energy Procedia 6 (2011) MEDGREEN 2011-LB
Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration
More informationFeasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System
Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang
More informationGEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion
Close Climate Control for IT Environments GEA Ultra-Denco Reliability with low power consumpstion GEA Heat Exchangers / HVAC Systems Numerical Flow simulation Velocity / Pressure field / Turbulence high
More informationImpact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System
4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W
More informationChilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2
Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding
More informationMODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
More informationArticle Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms
Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Min Suk Jo, Jang Hoon Shin, Won Jun Kim and Jae Weon Jeong * Department of Architectural
More informationMODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS
MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS Clayton Miller 1,* and Chandra Sekhar 1 1 National University of Singapore, Singapore * Corresponding email: miller.clayton@nus.edu.sg
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationWhite Paper Dehumidification in Humid Climates - A Theoretical Case Study
White Paper Dehumidification in Humid Climates - A Theoretical Case Study This white paper provides details of a theoretical comparison of operating costs associated with mechanical dehumidification systems
More informationComparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti
More informationHAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001
This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.
More informationA/C Cooling Load calculation and measurement
Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying
More informationAdding More Fan Power Can Be a Good Thing
This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of
More informationActive desiccant integration with packaged rooftop HVAC equipment
Applied Thermal Engineering 25 (2005) 3138 3148 www.elsevier.com/locate/apthermeng Active desiccant integration with packaged rooftop HVAC equipment James R. Sand a, *, John C. Fischer b a Oak Ridge National
More informationEnergy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More informationEnergy Consumption Reduction of AHU using Heat Pipe as Dehumidifier
Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Rohit R. Parab Mechanical Engineering Department Vishwakarma Institute of Technology, Pune, India Laxmikant D. Mangate Mechanical Engineering
More informationMSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)
MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
More informationFor an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.
1 PSYCHROMETICS Psychrometry is the study of the characteristics of moist air. We will see soon that evaporation of moisture from the skin can have a significant impact on thermal comfort. The rate of
More informationNumerical study of heat pipe application in heat recovery systems
Numerical study of heat pipe application in heat recovery systems *Song Lin, John Broadbent, Ryan McGlen Thermacore Europe, 12 Wansbeck Business Park Ashington, Northumberland NE3 QW, UK E-mail: song.lin@thermacore.com
More informationSIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong
More informationVH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control
VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Unit with Enhanced Humidity Control Motorized Bypass Damper Temperature and Humidity Controller Reheat Control Elastomeric Foam Insulation High Efficiency,
More informationHVAC Myths and Realities Trane Engineers Newsletter Live Series
HVAC Myths and Realities Trane Engineers Newsletter Live Series AGENDA Low delta T is unavoidable 55 F supply air temperature is adequate for today s loads ASHRAE Standard 15 has to be updated before new
More informationOIL AND GAS INDUSTRY
FIRED HEATER DESIGN This case study demonstrates the implementation of an API 560 fired heater compound component in Flownex. It also shows how Flownex has been used during the process design and preliminary
More informationEXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY
EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,
More informationClemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART II: VALIDATION
More informationDesign Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System
Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,
More informationCOMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal
By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal Summary Refrigeration air coolers (evaporators) are widely
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationA New Dedicated Outdoor Air System with Exhaust Air heat recovery
12 th IEA HEAT PUMP Conference Paper number O1.2.4 A New Dedicated Outdoor Air System with Exhaust Air heat recovery GREATLAB Zi-Yang Zhang, Xiang Cao, Zhi Yang, Liang-Liang Shao, Chun-Lu Zhang, Yue Yu
More informationAir Conditioning Clinic
Air Conditioning Clinic Psychrometry One of the Fundamental Series D C B A C B D A July 2012 TRG-TRC001-EN Psychrometry One of the Fundamental Series A publication of Trane Preface Psychrometry A Trane
More informationDesigning Energy Efficient Outdoor Air Systems
Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work
More informationPsychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International
Psychrometrics: The Science of Moisture in Air Presented by Tom Peterson, CEO and Founder Climate by Design International www.cdihvac.com Owatonna, MN 507-451-2198 4 02/2014 1 Psychrometrics or psychrometry
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationTemperature. In the HVAC area, we talk about two kinds of temperatures.
HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading
More informationHumidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China
Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China Xiaoping Yu Doctoral Candidate Chongqing University of Science & Technology Chongqing, China, 400042 xiaoyup@163.com
More informationDesign Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationDon t Turn Active Beams Into Expensive Diffusers
This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationPerformance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU
Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang
More informationFeasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationRadiant Cooling Nonresidential HVAC Stakeholder Meeting #2
1 Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Abhijeet Pande Heschong Mahone Group, Inc. Kristin Heinemeier Western Cooling Efficiency
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura
More informationDehumidification at Part Load
Dehumidification at Part Load Authors Shirey III, Don Henderson Jr., Hugh Original Publication Don Shirey III, Hugh Henderson Jr., Dehumidification at Part Load, ASHRAE Journal, April 2004. This article
More informationImplications of GHP Fan Control Strategies on Humidity Control in Commercial Applications
Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications ASHRAE Winter Meeting February 9, 2005 Hugh I. Henderson, Jr., P.E. CDH Energy Corp. Cazenovia, NY DOE/NETL Project
More informationHeat pump and energy recovery systems
SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air
More informationAir Cooled Packaged Systems AIRAH Back to Basics
Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability
More informationThe Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa
Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009
More informationAchieving Dry Outside Air in an Energy-Efficient Manner
AT-01-7-2 Achieving Dry Outside Air in an Energy-Efficient Manner Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE Kurt M. Shank Student Member ASHRAE ABSTRACT The central thrust of this paper is to develop
More informationEFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM
- 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationOpen and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator
18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.
More informationSIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY
SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,
More informationINTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011
Performance evaluation of two stage indirect/direct evaporative cooler with alternative shapes and cooling media in direct stage Kulkarni.R.K 1, Rajput S.P.S 2 1 SVPM College of Engineering, Malegaon(bk),
More informationTechnical Development Program
Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationCOLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd
COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing
More informationBasic Principals of Air conditioning By Dr. Esam Mejbil Abed
REPUBLIC OF IRAQ Ministry of Higher Education & Scientific Research University of Babylon College of Engineering Mechanical Engineering Department Basic Principals of Air conditioning By Dr. Esam Mejbil
More informationseasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former
A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*
More informationDehumidification: Energy Efficiency Comparisons
Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,
More informationFlexible and efficient: Close Climate Control for IT equipment
GEA Multi-DENCO Flexible and efficient: Close Climate Control for IT equipment engineering for a better world GEA Heat Exchangers GEA Multi-Denco at a glance: Multiple functions and applications High flexibility
More informationTheoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates
INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 3, ISSUE 4, APRIL 214 ISSN 2277-8616 Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates Ibrahim U. Haruna,
More informationOpen Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System
Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 215, 9, 7-14 7 Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning
More informationDEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM
DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM Hantz, D., Gulyas, G., Bensafi, A. Centre Technique des Industries Aéraulique et Thermique (CETIAT) BP 2042
More informationInternational Forum on Energy, Environment Science and Materials (IFEESM 2015)
The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,
More informationME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes
More informationBest Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System
International Conference on Civil, Transportation and Environment (ICCTE 201) Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System Pengjie Fan1, a, Caihua Liang1,
More information100% Outdoor Air Dehumidification Methods
Technical Bulletin 16 100% Outdoor Air ehumidification Methods I NTROUCTION As consulting engineers and end users implement the ASHRAE 6 ventilation code, they are faced with selecting an appropriate method
More informationDevelopment of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering
Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric
More informationA STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE
A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE NH Wong, BRJ Huang, KW Tham, C Sekhar and DKW Cheong Dept. Of Building, School of Design and Environment, National University of Singapore, Singapore
More informationIn Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market
In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market Eric Urban Senior Energy Data Analyst Staengl Enginering Note: This presentation takes
More informationDesign of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible
More informationHEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1
HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil
More informationExperimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer
GRD Journals- Global Research and Development Journal for Engineering Volume 2 Issue 6 May 2017 ISSN: 2455-5703 Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer Gokul G Nair Dr. Jeoju
More informationLaboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings
Downloaded from orbit.dtu.dk on: May 5, 218 Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Fang, Lei; Yuan, Shu;
More informationHumidity Control in Tropical Climate with Heat Pipes - The GREEN Way
TROPICAL SUBTROPICAL GREEN BUILDING ALLIANCE CONFERENCE 2012 Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way Case Study: Cheras Rehab Hospital, Kuala Lumpur By Mohan Dhingra Managing
More informationDaikin VRV Systems Plugin VE2012 User Guide
www.iesve.com Integrated Environmental Solutions Ltd Developers of the IES May 2012 Contents 1 - Introduction... 3 The... 3 2 - System Types... 4 2 Pipe Heat Pump Systems... 4 3 Pipe
More informationEnergy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017
Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM 13 th May 2017 0 1 Portion of Inverter Residential Air Conditioners Worldwide (2015) and in Vietnam (Mar 2017) What is "Inverter"?
More informationDrying principles and general considerations
Drying principles and general considerations Drying Mechanisms In the process of drying heat is necessary to evaporate moisture from the grain and a flow of air is needed to carry away the evaporated moisture.
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationAR/IA/UP 241 Lecture 5: Psychrometrics
Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is
More informationDADANCO Technical Paper
DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the
More informationACHEIVING COMFORT IN SUBTROPICAL CLIMATES: BUILDING A MICROCLIMATE IN THE GUANGZHOU SCIENCE MUSEUM
ACHEIVING COMFORT IN SUBTROPICAL CLIMATES: BUILDING A MICROCLIMATE IN THE GUANGZHOU SCIENCE MUSEUM Jeewon Paek HENN GmbH jeewon.paek@henn.com Moritz Fleischmann HENN GmbH moritz.fleischmann@edl.henn. com
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationExperimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant
Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More informationEFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING
EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING DA Hindoliya and SC Mullick * Centre for Energy Studies, Indian
More informationSPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE
SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE www.addison-hvac.com Creating a New Project 1. Open the ACE Interface within the web browser. ACE performs best using the Google Chrome browser. Do not use
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationComparison of radiant and convective cooling of office room: effect of workstation layout
Downloaded from orbit.dtu.dk on: Apr 27, 2018 Comparison of radiant and convective cooling of office room: effect of workstation layout Bolashikov, Zhecho Dimitrov; Melikov, Arsen Krikor; Rezgals, Lauris;
More informationInvestigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings
Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings Melanie T. Fauchoux, PhD Student University of Saskatchewan http://www.engr.usask.ca/dept/mee melanie.fauchoux@usask.ca
More informationMulti-Denco. » Precision Climate Control. Air Conditioning & Heating. Multi-DENCO
Air Conditioning & Heating Multi-DENCO Multi-Denco» Precision Climate Control Promise Precision control is more than just an industry term, it is a promise. A promise we sustain using our extensive experience.
More informationASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes
ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes In Humid Climates BY DAVID A. JOHN, P.E., MEMBER ASHRAE; DREW ELSBERRY, MEMBER ASHRAE Designing g a building s HVAC system requires designers
More informationIn Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/ Dehumidification Devices on the US Market
In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/ Dehumidification Devices on the US Market Eric Urban Senior Energy Data Analyst Staengl Enginering Definition Crossover Device:
More informationOptimizing Electric Humidifier Operation with an Air Side Economizer
Optimizing Electric Humidifier Operation with an Air Side Economizer Usama F. Shami, P.E. Senior Project Engineer Savage Engineering, Inc. Foster City, CA Abstract Air side economizer cycle is a control
More informationDesign Based Comparative Study of Several Condensers Komal B. Dabhi 1, Prof. S. B. Thakore 2 1 Chemical Engg. Dept., L. D. College of Engineering, Ahmedabad 380015 2 Chemical Engg. Dept., L. D. College
More informationK.F. Fong *, C.K. Lee, T.T. Chow
Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building
More informationMAXIMIZING FACILITY PERFORMANCE WITH INNOVATIVE HVAC & IRRIGATION SYSTEMS
MAXIMIZING FACILITY PERFORMANCE WITH INNOVATIVE HVAC & IRRIGATION SYSTEMS Moderator: Michael Thomas, Denver Water Panelists: Keith Coursin, Desert Aire Brandy Keen, Surna Lucas Targos, urban-gro SESSION
More information