GEN II -VVT COMMERCIAL ZONING - SIMPLIFIED. Installation and Applications Manual V V T. GEN II System Controller

Size: px
Start display at page:

Download "GEN II -VVT COMMERCIAL ZONING - SIMPLIFIED. Installation and Applications Manual V V T. GEN II System Controller"

Transcription

1 GEN II -VVT V O T E S E D U T O H N G E O V E R M O D U L T I N G V V T S Y S T E M OMMERIL ZONING - SIMPLIFIED GEN II System ontroller Installation and pplications Manual 58

2 QUIK STRT ND OMMISSIONING GEN II QUIK STRT ND OMMISSIONING Follow these Quick steps for a successful job If you need additional information, please read the GEN II Manual 1. Install GEN II controller in an easily accessible location for your customer. 2. Install an independent 24 volt 40 V transformer, and connect to the and terminals on the GEN II controller. 3. Install the LT sensor in the supply air, ahead of any bypass takeoffs. Wire sensor to the S S terminals on the GEN II controller. 4. Install Dampers and ypass Dampers. 5. Install all thermostat sub-bases. 6. Wire and terminals from the GEN II controller to the first sub-base and - only (18 ga thermo stat wire). 7. Wire & terminals from GEN II controller using elden 8740 twisted pair wire or Zonex supplied equal to the first thermostat sub-base & - only. Note: terminal is optional. If using, use Zonex wire 3-TWP 8. Damper wiring - connect, R, M wires from each thermostat to its damper using 18 ga thermostat wire. 9. ttach the first MOTT to it s sub-base. 10. ddress the thermostat as #1- see page for MOTT installation, addressing and operation. 11. Turn on GEN II controller switch E. Power light should light up and look at the display G on the GEN II controller, and the #01 should appear on the display. This indicates you are communicating with the first thermostat. 12. If you don t see the #01 and 00 is displayed, check the address. If the address is #01, then check wires for & polarity and & for correct connections. 13. If #01 is displayed on the GEN II controller, then daisy chain wires from thermostat #1 to the next thermostat and address it #2; then repeat the ON-OFF switch operation and confirm the #02 shows up on the display indicating the system is now communicating with 2 thermostats. 14. ontinue adding MOTT s; and confirm communication by repeating the ON-OFF switch operation until all thermostats are wired and the total number of thermostats on the job show up on the display on the GEN II controller. 15. Go to any MOTT and make a ool all. Look at the GEN II controller and confirm Y1 (yellow LED) and G (green LED) lights are on. 17. Turn OFF the ool all to be sure Y1 and G turn OFF at the GEN II controller. 18. Repeat with a Heat all for W1 (red LED). 19. Wire GEN II controller to the / unit. 20. Set thermostat to call for cooling, and check register to be sure each damper opens and closes as you make and satisfy the call. For dvanced Feature onfiguration or additional operating information, review the attached GEN II manual.

3 QUIK STRT ND OMMISSIONING GEN II QUIK STRT ND OMMISSIONING E H DY UP SET F J DN K EH TIME/TMP ON Y2 UTO I W1 TIME W2 G O/ HP S PRI Y1 NIGHT G S G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE D IN 72 ON OUT T T OFF UNLOK LOK GEN II-VVT L M The GEN II is equipped with a Digital Display (G) that constantly displays Leaving ir Temperature from the unit. t startup, this display also reports the number of thermostats communicating with the GEN II controller. The display and 3 buttons (H) beneath the display provide the installing contractor the ability to tailor the system to your specific application. The GEN II controller is shipped from the factory configured for basic Gas/Electric operation. However, the following should be checked as part of the initial installation setup procedures: 1. EH jumper (F) is installed by the factory on one pin for normal gas heat operation where the fan is controlled by the HV system fan control. When a fan output is required from the GEN II controller on a call for heat, place the EH jumper over both pins for several seconds and then remove. Place the jumper tab on one pin. 2. O/ and HP jumpers (F) should both be on one pin or removed for GE operation. 3. PRIORITY (PRI) jumper (F) should be on one pin. Note: If the Priority opposing zone strategy is to be used, this jumper position will be changed after the initial system start-up is completed. See dvanced Feature onfiguration on page Set the Power Switch (E) to ON. 5. Set the NIGHT DY switch (J) to the DY position. 6. Set the fan jumper (I) to UTO for intermittent operation or ON for constant ON operation in the Occupied mode. 7. Place the LOK UNLOK switch (K) in the UNLOK position. 8. Place the TIME/TEMP jumper (I) on the middle and upper pins to control Y2 and W2 staging on run time and supply air temperature.

4 TLE OF ONTENTS OVERVIEW 1 SYSTEM System Overview Diagram General Sequence of Operation ELETRI OPERTION 2 GSontroller ID Diagram Installation ontroller GE ontroller onfiguration GE dvanced onfiguration Heat and ool ut-out Temperatures Electric Heat Fan 2nd Stage Operation Heat Pump Installation asic onfiguration Heat Pump dvanced onfiguration Heat and ool ut-out Temperatures 2nd Stage Operation Wiring Diagram Modstat onfiguration Modstat onfiguration Menu Supplemental Heat pplications PUMP OPERTION 3 HET ontroller ID Diagram THERMOSTT - MOTT 4 ZONE Modstat Installation 5 GEN II WIRING SHEMTI LONE THERMOSTT 6 STND G-STT Universal Thermostat Installation Instructions G-STT onfiguration and Operation G-STT onfigation Menu GEN II Wiring Schematic with G-STT s 7 REMOTE SENSOR ND VERGING SENSOR INSTLLTION 8 SYSTEM STRT UP ND TESTING 9 TULESHOOTING ONFIGURTION 10 DVNED Gas Electric and Heat Pump Occupied / Unoccupied Fan Opposing all hangeover Priority Demand Thermostat Security - LOK ir alance Default Thermostat Set Points Time lock (GLK) D-Fuser Sizing Slaving Zone Dampers DMPERS 11 ZONE Round and Rectangular Damper Selection DMPERS 12 YPSS ypass Dampers Slaving ypass Dampers ypass Installation IP Static Pressure ontroller

5 SYSTEM OVERVIEW GEN II-VVT 24V / 40V TRNSFORMER STTI PRESSURE SENSOR LEVING IR SENSOR 1 ZONE DMPER YPSS DMPER 24 TR V / NSF 40V OR ME R 2 ZONE DMPER System Features 3 ZONE DMPER 4 ZONE DMPER UP TO 17 DMPERS SYSTEM OVERVIEW PULL 24V POWER ND UNSHIELDED TWISTED PIR DISY HINED FM MOTT TO MOTT - Universal for G/E or H/P Units - Fully Modulating Zone Dampers - Up to 17 Zones Per Unit - uto- hangeover Operation - Selectable Priority - On-board apacity ontrol - Night Setback Included - 2-Hour Override - Lock Stats Remotely - Start Up Diagnostic - 2 Data Wires - 2 Power Wires - 3 Wire Stat to Damper - No Home Run Wiring - No omputer Required For Setup The GEN II is a commercial modulating zone control system controlling 2-17 independent zones per unit. The GEN II controller is designed for uto hangeover, multi-stage Heat Pump (2/3H) and Gas Electric (2/2H) applications. The GEN II system uses the Zonex ModStat, which modulates and controls the ST series, 3-wire, 24-volt, power open / power close round and rectangular dampers. Sophisticated, integrated software allows for a wide range of system control and changeover strategies, allowing the contractor to tailor the GEN II system to your specific application. dditional features include LED status indication of all system functions, digital LT display, fully adjustable capacity control with on-board limit settings, and optional staging strategies. Night setback operation is standard, with selectable 2-hour override at each stat, along with a unique feature to remotely lock thermostats in the system. The system provides the installing contractor with a simple startup diagnostic to minimize wiring errors and speed installation. GEN II is recognized as the Industry s easiest commercial zone control system to install and wire. The GEN II system operates over an unshielded two-wire data link, along with two 24v power wires all daisy chained from stat to stat with no home run wiring required. Three wires from the stat to actuator control a modulating damper in each zone. The GEN II system does not require a computer to set up or operate. 1

6 GENERL SEQUENE OF OPERTION GEN II offers the following additional control features: Set ooling and Heating capacity cut-out set points nd djustable timing to initiate 2 stage operation djustable opposing call changeover timing Priority demand votes on a stat-by-stat basis Provide default occupied and unoccupied set points on every stat utomatically open all dampers for air balancing GEN II components: GEN II controller (includes integrated capacity control) Zone thermostats Modulating power open / power close 24vac supply dampers Modulating power open / power close 24vac bypass damper with static pressure control ommunication cable (elden 8740) twisted pair or Zonex supplied equal Time lock 24vac 40va transformers: 1 to control system and all supply dampers 1 for bypass damper and static pressure control GENERL SEQUENE OF OPERTION When the GEN II controller is powered up, the total number of addressed thermostats (ModStats) are determined and verified on the display. This confirms the controller is communicating with all thermostats in the system. If there are no active heat or cool calls detected, the supply dampers will modulate to 40% open for ventilation mode. The system blower operation can be configured for constant ON or intermittent uto. The controllers are shipped from the factory for uto fan. The GEN II systems can be field configured for adjustable time based opposing call changeover, vote based majority changeover, or priority vote changeover by thermostat assignment. The GEN II controller is shipped from the factory for 10-minute opposing call changeover. The GEN II controller polls the thermostats once per minute to determine the thermostat demand status for heat and cool. The heat and cool changeover functions will operate by the type of changeover selected on the controller. When the GEN II controller changes modes, a 5-minute purge cycle is initiated before the changeover is completed. On active heat or cool calls, the non-calling zones will modulate to the closed position. When the last calling zone is satisfied in either heat or cool mode, the GEN II controller terminates the HV outputs after the next poll and the blower output will be de-energized (unless controller is configured for constant fan) for a 5-minute purge cycle. During the purge cycle no heat or cool calls are recognized. When the system is in the heating mode and calls for cooling are received, an opposing call timer strategy operates. This timer is adjustable from minutes. The factory default is 10 minutes. t the end of the selected time period, if the opposing call is 3 away from set point, heating is turned off. fter a 5-minute purge mode, ooling is turned on until the cool call is satisfied. If necessary, GEN II will return to the heating mode, If all calls have been satisfied, dampers will modulate to the 40% open position for ventilation. If the opposing zone strategy is not desired, this feature may be disabled. This mode may be enhanced by adding Priority votes to each thermostat in the system, thereby weighting certain zones more than others. This Priority mode allows you to select 0, 1, or 2 additional votes for a thermostat that has unusual loads, like a conference room. Minimum / Maximum damper positions can be set to provide ventilation. Each thermostat has uxiliary contacts support and control a supplemental heat source i.e., baseboard, reheat, or hot water coil, to meet the temperature requirements of any commercial application. 2

7 GS ELETRI OPERTION GEN II-VVT H F DY K EH TIME/TMP ON I W1 W2 G Y2 UTO O/ TIME Y1 J DN HP D E F UP SET PRI & Power out to Modstat & (18 ga thermostat wire) UNLOK LOK E S G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE D G S 72 ON NIGHT OUT IN T T OFF LEGEND L M G H I TERMINL FUNTIONS / ONNETIONS TX- / RX- - Data Transmit / Receive S S Leaving / Supply ir Sensor Input G Fan Output W2 Stage 2 Heat Output W1 Stage 1 Heat Output Y2 Stage 2 ool Output Y1 Stage 1 ool Output R 24vac from Unit Transformer J K L M & 24-Volt Transformer T T Time lock Terminals Unit Terminals On / Off Switch Priority Jumper (llows for Priority Vote Setup) H/P Jumper (Jump for Heat Pump Operation) O/ Jumper (Heat Pump Only Reversing Valve Operation) EH Jumper (Set Up Fan Operation for Electric Heat) Digital Display (Leaving ir Temperature and configuration) Up / Down / Set uttons (High Limit, Low Limit, Set) Fan Jumper (ontinuous or uto) Staging Strategy (Time / Temperature or Time Only) Day / Night Switch Lock / Unlock (Lock Thermostats) / / ommunications Wire S S Terminals Leaving ir Sensor (LT) T / T Time lock Input for Occupied / Unoccupied Operation / 24vac Power Input / ommon / - Stat Power Daisy hain Stat to Stat (18G Thermostat wire) General Installation Instructions GEN II ontroller 1. Install the GEN II controller on an interior wall where the ambient temperature is between F (0-48 ) non-condensing. This controller is to be installed in an accessible interior area; not in attics or above ceilings. 2. The controller is to be powered by a dedicated 24vac 40va transformer. The transformer secondary is wired to on the controller (). The secondary voltage to the controller must be 24 to 28vac. 3

8 GS ELETRI SI ONTLLER ONFIGURTION 3. Install the leaving air sensor (LT) in the supply air, ahead of the bypass take-off. Sensor wires are connected to the S S terminals on the controller (M). The LT sensor leads may be extended using standard 18/2 thermostat wire. 4. The leaving air sensor (LT) is calibrated to the controller at the factory. However, the calibration should be checked as part of the system setup procedure. If adjustments are required, use the lue potentiometer labeled R44 located in the upper right hand corner of the GEN II controller. Screw the pot clockwise to lower the display temperature and counter clockwise to raise the temperature. NOTE: The display will update every 10 seconds. 5. onfirm you have connected the and communication wires and and from the thermostats to the Gen II controller ( & L), =(, ), L=(,, & ). (ommunication wire maxmum is 4,000 ft. from the Gen II controller to the farthest Modstat). 6. onnect the output wires from the controller to the HV system using standard 18 G thermostat wire. The LT sensor leads may be extended using standard 18/2 thermostat wire. H DY UP SET F J DN EH TIME/TMP ON Y2 UTO I W1 TIME W2 G O/ HP K S PRI Y1 NIGHT E 72 S G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE D G IN ON OUT T T OFF GEN II-VVT UNLOK LOK Gas Electric - asic GEN II ontroller onfiguration L M The GEN II is equipped with a Digital Display (G) that constantly displays Leaving ir Temperature from the unit. The display and 3 buttons beneath the display provide the installing contractor the ability to tailor the system to your specific application. The GEN II controller is shipped from the factory configured for basic Gas/Electric operation. However, the following should be checked as part of the initial installation setup procedures: 1. EH jumper (F) is installed by the factory on one pin for normal gas heat operation where the fan is controlled by the HV system fan control. When a fan output is required from the GEN II controller on a call for heat, place the EH jumper over both pins for several seconds and then remove. Place the jumper tab on one pin. 4

9 GS ELETRI DVNED FETURE ONFIGURTION 2. O/ and HP jumpers (F) should both be on one pin or removed, for GE operation. 3. PRIORITY jumper (F) should be on one pin. Note: If the Priority opposing call strategy is to be used, this jumper position will be changed after the initial system start-up is completed. See dvanced Feature onfiguration. 4. Set the power switch (E) to ON. 5. Set the NIGHT DY switch (J) to the DY position. 6. Set the fan jumper (I) to UTO for intermittent operation or ON for constant ON operation in the Occupied mode. 7. Place the LOK UNLOK switch (K) in the UNLOK position. 8. Place the TIME/TEMP jumper (I) on the middle and upper pins to control Y2 and W2 staging on run time and supply air temperature. GEN II Gas Electric dvanced Feature onfiguration Gas Electric apacity ontrol - ool and Heat cut-out temperature adjust The factory setting for the ool and Heat cut-out temperatures is F (7-62 ). This can be easily changed with the following procedure: 1. ool cut-out temp Press the DN button (H); will be displayed and then the cut-out temperature. 2. LOWER Press the DN button; after the is displayed, continue to hold the DN button until the desired temperature is displayed; then release. NOTE: The controller will not change the ool cut-out lower than 40 F (4 ). 3. RISE Press the DN button; after is displayed, immediately release the DN button and press the UP button. Hold until the desired temperature reading is displayed and release. 4. Press the DN button to verify the new cool cut-out temperature. Heat cut-out temperature - Press and hold the UP button; after the H is displayed, use the same procedure as above to raise or lower the displayed temperature. Electric Heat - Fan onfiguration EH jumper (F) is installed by the factory on one pin for normal gas heat operation where the fan is controlled by the HV system fan control. When a fan output is required from the GEN II controller on a call for heat, place the EH jumper over both pins for several seconds and then remove. Place the jumper tab on one pin. 2nd Stage Heat and ool ut-in / ut-out onfiguration The GEN II controller is set up at the factory to stage Y2 and W2 cut-in operation based on a 3-minute time delay and supply air temperature. This is done using the TIME/TEMP (I) jumper. Time may be field configured from 3-20 minutes by the contractor during system configuration. The cut-in temperatures are fixed in the controller program at 58 F (14 ) and higher for Y2 and 120 F (48 ) and lower for W2. The GEN II controller second stage cut-out temperature is fixed in the controller program at 50 F (10 ). Y2 will de-energize when it drops below 50 F and re-energize when it rises above 58 F. If the air temperature drops below the low cut-out (45 F) Y1 and Y2 are de-energized and the controller will go into a 5 minute purge mode. fter 5 minute purge, if the temperature has risen above the low cut-out Y1 is re-energized. Heat W1 and W2 will de-energize if leaving air temperature rises above heat cutout and will be locked out for 5 minutes. fter 5 minute lockout, if a heat call remains and leaving air temperature is lower than heat cutout, W1 will re-energize. y placing jumper on bottom two pins, a time only strategy may be configured into the system. ( see below); djust 2nd Stage ut-in Time Delay 1. To increase the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (H) simultaneously. When 03 appears in the display, release the buttons and immediately press the UP button and hold until the desired delay time is displayed, and release. The time delay is fully adjustable from 3-20 minutes. To verify the change, press and hold the SET and DN buttons simultaneously until the delay time is shown, and release. 5

10 HET PUMP OPERTION 2. To decrease the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (H) simultaneously. When delay time appears in the display, release the buttons and immediately press the DN button and hold until the desired delay time is displayed, and release. To verify the change, press and hold the SET and DN buttons until the delay time is shown, and release. onfigure 2nd Stage ut-in for Time Delay and Thermostat Demand Only nd 1. Place the 2 stage configuration jumper (I) on the middle and lower pins - TIME. 2. If the cut-in time delay must be changed from the factory setting of 03 (3 min), follow the above procedures to raise or lower the time delay value. 3. Verify time delay value by pressing the SET and DN buttons simultaneously. HET PUMP OPERTION H F DY K EH TIME/TMP ON I W1 W2 G Y2 UTO O/ TIME Y1 J DN HP D E F UP SET PRI & Power out to Modstat & (18 ga thermostat wire) UNLOK LOK E S G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE D 72 G S ON LEGEND NIGHT OUT IN T T OFF GEN II-VVT L M G H TERMINL FUNTIONS / ONNETIONS TX- / RX- - Data Transmit / Receive S S Leaving / Supply ir Sensor Input G Fan Output W2 uxiliary / Emergency Heat O/ Reversing Valve Output Y2 Stage 2 ool Output Y1 Stage 1 ool Output R 24vac from Unit Transformer I J K L M & 24-Volt Transformer T T Time lock Terminals Unit Terminals On / Off Switch Priority Jumper (llows for Priority Vote Setup) H/P Jumper (Jump for Heat Pump Operation) O/ Jumper (Heat Pump Only Reversing Valve Operation) EH Jumper (Set Up Fan Operation for Electric Heat) Digital Display (Leaving ir Temperature and configuration) Up / Down / Set uttons (High Limit, Low Limit, Set) Fan Jumper (ontinuous or uto) Staging Strategy (Time / Temperature or Time Only) Day / Night Switch Lock / Unlock (Lock Thermostats) / / ommunications Wire S S Terminals Leaving ir Sensor (LT) T / T Time lock Input for Occupied / Unoccupied Operation / 24vac Power Input / ommon / - Stat Power Daisy hain Stat to Stat (18G Thermostat wire) 6

11 GENERL INSTLLTION INSTRUTIONS General Installation Instructions GEN II ontroller Install the GEN II controller on an interior wall where the ambient temperature is between F (0-48 ) non-condensing. This controller is to be installed in an accessible interior area; not in attics or above ceilings. The controller is to be powered by a dedicated 24vac 40va transformer. The transformer secondary is wired to on the controller (). The secondary voltage to the controller must be 24 to 28vac. Install the LT air sensor in the supply air between the indoor coil and electric strip heat elements. The leaving air sensor (LT) is calibrated to the controller at the factory. However, the calibration should be checked as part of the system setup procedures. If adjustments are required, use the lue potentiometer labeled R44 located in the upper left hand corner of the GEN II controller. Screw the pot clockwise to lower the display temperature and counter clockwise to raise the temperature. NOTE: The display will update every 10 seconds. onfirm you have connected the and communication wires and and from the thermostats to the Gen II controller ( & L), =(, ), L=(,, ). (ommunication wire maximum is 4,000 ft. from the Gen II controller to the farthest Modstat). onnect the output wires from the controller to the HV system using standard 18 G thermostat wire. The LT sensor leads may be extended using standard 18/2 thermostat wire. Heat Pump operation O reversing valve ool all When a majority active cool call is received by the GEN II controller, Y1, O/ and G LEDs are illuminated; and the outputs are energized (within 1.5 to 3 minutes). fter 3 minutes, if the leaving air temperature is 58 F (14 ) or above, Y2 will energize for 2-stage systems. Y2 will de-energize when it drops below 50 F and re-energize when it rises above 58 F. If the supply air temperature drops one degree below the ool cut-out temperature, Y1 and Y2 will de-energize for 5 minutes. reversing valve Sequence of operation is the same: O/ is energized in the heat mode. Heat all - When a majority active heat call is received by the GEN II controller, Y1 and G LEDs are illuminated; and the outputs are energized (within 1.5 to 3 minutes). If after 3 minutes the leaving air temperature is 94 F (34 ) or less, Y2 will energize. If after 6 minutes of run time the leaving air temperature is 91 F (32 ) or less, W2 will energize. If the supply air temperature exceeds 126 F (52 ), Y1, Y2 and W2 (if energized) will drop out; and Y1 can then energize after a 5-minute time delay. NOTE: If the system fan is configured for UTO on the GEN II controller, the G output will be de-energized in the temperature cut-out mode. When the last active call satisfies, the GEN II controller goes into a 5-minute purge cycle with all supply dampers closing; then all dampers modulate open for ventilation. Heat Pump operation reversing valve y placing the O/ jumper () on both pins, the GEN II controller is configured for reversing valve operation. The operation and setup procedures are the same as with O mode reversing valve, except the reversing valve will be energized for heat operation. 7

12 HET PUMP SI ONTLLER ONFIGURTION E H 72 J K EH TIME/TMP ON UTO TIME G O/ HP S PRI S G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE UP 1. Switch controller to OFF (E). SET 2. Set the O/ jumper (F) on one pin for O DN F reversing valve (energizes for cool) or Set the O/ jumper (F) on both pins for reversing valve (energizes for heat). 3. Set the HP jumper (F) on both pins for Heat I Pump operation. Y2 Y1 W2 W1 D 4. Set the Priority jumper (F) on one pin. 5. Set the TIME / TEMP jumper (I) on the middle and upper pins. 6. Set NIGHT / DY switch (J) for DY position. 7. Set LOK / UNLOK switch (K) to UNLOK. 8. Switch the controller to ON (E). 9. Press the UP button (H), and verify the H (cut-out) temperature reads 126 F (52 ) on the controller display (G). NOTE: The heat cut-out temperature must not be changed from the factory setting. DY G NIGHT GEN II-VVT ON IN OFF OUT T T The GEN II controller is shipped from the factory for Gas Electric operation. The controller must be field configured for Heat Pump operation. Heat Pump configuration: UNLOK LOK GEN II Heat Pump asic onfiguration L M 8

13 HET PUMP DVNED FETURE ONFIGURTION GEN II Heat Pump dvanced Feature onfiguration Heat Pump apacity ontrol - ool and Heat cut-out temperature adjustment When the GEN II controller is configured for Heat Pump (HP jumper (F) on both pins), the ool and Heat cut-out temperatures are F (7-52 ). The cut-out temperatures can be changed with the following procedure: Heat cut-out temp To eliminate the possibility of the Heat Pump tripping out on high head pressure or short cycling in the heat mode, the heat cut-out temperature should never be changed from the factory setting of 126 F (52 ). 1. ool cut-out temp Press the DN button (H); will be displayed, then the cut-out temperature. 2. LOWER Press the DN button. fter the is displayed, continue to hold the DN button until the desired temperature is displayed; then release. NOTE: The controller will not change the ool cut-out lower than 40 F (4 ). 3. RISE Press the DN button. fter is displayed, immediately release the DN button, and press the UP button. Hold until the desired temperature reading is displayed; then release. 4. Press the DN button to verify the new cool cut-out temperature. 2nd Stage Heat and ool ut-in / ut-out onfiguration The GEN II controller is set up at the factory to stage Y2 and W2 cut-in operation based on a 3-minute time delay and supply air temperature. This is done using the TIME/TEMP (I) jumper. Time may be field configured from 3-20 minutes by the contractor during system configuration. The cut-in temperatures are fixed in the controller program at 58 F (14 ) and higher for Y2 and 120 F (48 ) and lower for W2. The GEN II controller second stage cut-out temperature is fixed in the controller program at 50 F (10 ). Y2 will de-energize when it drops below 50 F and re-energize when it rises above 58 F. If the air temperature drops below the low cut-out (45 F) Y1 and Y2 are de-energized and the controller will go into a 5 minute purge mode. fter 5 minute purge, if the temperature has risen above the low cut-out Y1 is re-energized. Heat W1 and W2 will de-energize if leaving air temperature rises above heat cutout and will be locked out for 5 minutes. fter 5 minute lockout, if a heat call remains and leaving air temperature is lower than heat cutout, W1 will re-energize. y placing jumper on bottom two pins, a time only strategy may be configured into the system. ( see below); djust 2nd Stage ut-in Time Delay 1. To increase the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (H) simultaneously. When 03 appears in the display, release the buttons and immediately press the UP button and hold until the desired delay time is displayed, and release. The time delay is fully adjustable from 3-20 minutes. To verify the change, press and hold the SET and DN buttons simultaneously until the delay time is shown, and release. 2. To decrease the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (H) simultaneously. When delay time appears in the display, release the buttons and immediately press the DN button and hold until the desired delay time is displayed, and release. To verify the change, press and hold the SET and DN buttons until the delay time is shown, and release. onfigure Y2 and W2 ut-in for Time Delay and Thermostat Demand Only nd 1. Place the 2 stage configuration jumper (I) on the middle and lower pins - TIME. 2. If the Y2 cut-in time delay must be changed from the factory setting of 03 (3 min), follow the above procedures to raise or lower the time delay value. NOTE: The cut-in delay timing for W2 (ux Heat) is set for approximately 3 minutes in the control program and cannot be manually changed. 3. Verify time delay value by pressing the SET and DN buttons simultaneously. 9

14 ZONE THERMOSTT - MOTT IN UNLOK LOK OUT MOTT 72 GEN II-VVT DY ON NIGHT OFF UP SET T T DN PRI HP O/ EH TIME/TMP ON G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE 1 UTO TIME G W2 S S W1 Y2 Y1 GLK M 11:25 Mo Tu We Th Fr Sa Su OVR _UTO Mode Menu OK +1h M T-1 R M R M UX Power ommunication R = RX = = TX = R MODULTING DMPER DM-3 T-2 Terminal onnections M R MODULTING DMPER DM-2 MODULTING DMPER DM-1 UX 5 M 4 R 3 2 M 1 T-3 R M R M UX R M R M DISY HIN 24V ND DTLINK LE (ELDEN 8740) TO LL ZONE MOTTS EXPNDLE TO 17 ZONES Installation Wiring ll 24-volt and communication wiring connections are made to terminal blocks on the thermostat sub-base. The communication terminal block (// / //) is designed as a junction for two sets of 22 ga tinned copper, twisted pair communications cable. The cable should be daisy chained from thermostat to thermostat (use elden 8740 or Zonex supplied equal). 1. Install the thermostat sub-base on an interior wall away from direct sunlight, supply air currents, or any heat generating source. Mounting screws and anchors are provided. The sub-base may be installed on a horizontal 2x4 electrical box. 2. onnect the control wires from the Modstat s &, to the GEN II controller & (). Verify & polarity is the same on each thermostat (18 ga Thermostat wire). 3. On the ModStat, connect the damper output wires from M, R and to the actuator motor terminals. 4. onnect the / communication wires on the left hand terminal block; there are 2 sets of / terminals to make the daisy chain wiring easier. Note: terminal is optional. NOTE: The communication wire must be twisted pair elden 8740, 8450 (shielded), (plenum rated) or Zonex supplied equal. 10

15 MOTT ONFIGURTION ddressing Zone Thermostats Every thermostat in the system needs a unique ID ranging from They must be in numerical order the way the communication wire is daisy chained. onfirm no duplicate addresses. 1.To access the Thermostat onfiguration Menu, hold MENU button followed by the UTO button. 2. Once in the Thermostat onfiguration Menu, press SELET on. SET STT ID. 3. Use the UP and DOWN buttons to give the zone thermostat an ID ranging from Press SVE to save ID setting. urrent Room Temperature urrent Temperature Set Point Up utton Down utton hange From Heat to ool uto / Off Menu utton Display Temperature alibration Thermostats are calibrated at the factory and should require no further adjustment. However, the display space temperature may be field calibrated by the following procedure: 1. ccess the Thermostat onfiguration Menu, hold MENU button followed by the UTO button. 2. Once in the Thermostat onfiguration Menu, press SELET on. LIRTE. 3. Use the UP and DOWN buttons to adjust the temperature. 4. Press EXIT to save the temperature changes. djusting Set Points The Heat or ool set points can be displayed by pressing the SET button; the set point will be indicated on the upper right of the display. The Heat and ool set points can be individually set for the Occupied and Unoccupied modes. Occupied Mode: Heat and ool settings - Functions with (J) in the DY position, or time clock in Occupied. Unoccupied Mode: Heat and ool settings - Functions with (J) in the NIGHT position, or time clock in Unoccupied. 11

16 MOTT ONFIGURTION Heat - If Heat Setting is displayed on the top right of the display, simply press the UP or DOWN button to change the heat set point. If ool Setting is displayed and you want to change the Heat set point, press the SET button to change from ool Setting to Heat Setting. Then press the UP or DOWN button to change the set point. ool - If ool Setting is displayed on the top right of the display, simply press the UP or DOWN button to change the cool set point. If Heat Setting is displayed and you want to change the ool set point, press the SET button to change from Heat Setting to ool Setting. Then press the UP or DOWN button to change the set point. hanging Mode The thermostats are auto changeover, but specific modes may be selected. uto mode is the default. System Off - Press and hold the uto button for 10 seconds the UTO will change to OFF. System uto - Press and hold the Off button for 10 seconds the OFF will change to UTO. Override Operation When the thermostat displays UNOUPIED, a 2-hour temporary override may be initiated by pressing the UTO button. When additional override time is required, press the UTO button again. uxiliary Heat / Reheat The zone thermostat provides uxiliary Heat options; aseboard, aseboard W1 and Reheat options are configured using the menu screen on the thermostat. When zone temperature drops 2 degrees below heat set point, auxiliary heat operations are energized. If configured for Reheat operation when zone temperature drops 2 degrees below thermostat set point, damper will modulate to approximately 40% open providing air flow over electric heat strips, the UX terminal will energize and strip heat will provide reheat. Note: When using electric strip heater, an airflow switch is required to prove airflow for safe operation. If the Thermostat is configured for aseboard heat operation, auxiliary output will energize at 2 degrees below heat set point. uxiliary operations will remain energized until heat call is satisfied. If you desire the uxiliary heat to energize before the unit heat, you will want to configure the thermostat for aseboard W1 heat operation auxiliary output energizes first at 1 degree below set point and at 2 degrees below set point, the unit heater will energize and remain energized until the heat call is satisfied. 12

17 MOTT ONFIGURTION MENU THERMOSTT ONFIGURTION MENU To access the Thermostat onfiguration Menu, hold MENU button followed by the UTO button. The THERMOSTT ONFIGURTION MENU allows you to:. Set stat ID. alibrate. Set uxiliary Heat D. Temperature Format E. Diagnostic Up Down. SET STT ID. LIRTE. SET UXILIRY HET D. TEMPERTURE FORMT E. DIGNOSTI SELET SET STT ID Every thermostat in the system needs a unique ID. They must be in numerical order the way the communication wire is daisy chained. onfirm no duplicate addresses. While in the Thermostat onfiguration Menu, press STT ID STT ID : 001 SVE EXIT LIRTE LIRTE THERMOSTT 74.1 EXIT EXIT Select on. SET STT ID. Use the Up and Down buttons to give the thermostat an ID ranging from Press Press Exit to return to the Thermostat onfiguration Menu. Save to save settings. Thermostat is equipped with an accurate temperature sensor. If you require field calibration, follow the steps below. While in the Thermostat onfiguration Menu, press. LIRTE Down and press Select on Use the Up and Down buttons to calibrate the temperature display with your EXIT to save changes. external temperature probe; press onfirm temperature display now reports the updated room temperature you provided. 13

18 MOTT ONFIGURTION MENU SET UXILIRY HET SET UXILIRY HET SEORD SEORD W1 REHET SELET EXIT ccess the Zone Setup Menu select item. SET UXILIRY HET press Select. Select SEORD, SEORD W1 or REHET using the Up and Down buttons. Then press Select and enter the temperature range you would like to energize base board or reheat. Default settings initiate supplemental heat 2 degrees below the heat set point. You can select 2,3,or 4 degrees using the Up and Down buttons. UX HET ND UX HET ND 2F O EXIT D TEMPERTURE FORMT The MOTT may be configured for F or operation. From the Thermostat onfiguration menu toggle the UP or DOWN button to highlight TEMPERTURE FORMT. When desired temperature format is displayed press SVE. While in Thermostat onfiguration Menu, press D. TEMPERTURE FORMT menu item. Toggle Press Press E DIGNOSTI Up and OMMUNITION...OK Select on Down to set the desired Temperature Format. Exit to return to the Thermostat onfiguration Menu. Save to save the settings. The MOTT Diagnostic screen will allow you to confirm communication with the GEN II controller. While in Thermostat onfiguration Menu, press E. DIGNOSTI menu item. DIGNOSTI Down and press Press Down and press Select on Exit to return to the Thermostat onfiguration Menu. EXIT 14

19 SUPPLEMENTL HET PPLITIONS SEORD ELETRI HET Wire from UX/ terminals to the 24v coil on a field supplied SPDT relay. Wire baseboard heat to the load side of the relay to the baseboard heater. UX ONTL RELY HETING OIL R M R M VV DUT REHET Wire one UX terminal to the air proving switch from the air proving switch complete wiring to the terminal on the 24v coil relay. Wire the terminal to the 24v coil on the relay. Isolated control power should be provided to power baseboard heater. H E T I N G ONTL DMPER IRFLOW PVING SWITH O I L UX R M R M HET RELY DUT FN REHET Wire from the UX/ to the 24v coil on a field supplied SPDT relay. Wire from one contact terminal to the 24v coil of the fan relay and to the air proving switch then wire the leaving side of the air proving switch to the 24v coil relay on the Elect. Strip heater. Now wire the other contact to the transformer. Wire the other transformer leg to the fan and and Elect. Strip heater 24v coil terminals to complete the circuit. Isolated control power should be provided to power the fan and Elect. Strip heater. H E T I N G IRFLOW PVING SWITH O I L HET RELY UX FN RELY FN 24 VOLT TRNSFORMER ONTL RELY R M R M SEORD HYDNI HET Wire from UX/ to 24v coil on SPDT relay then wire from one contact terminal to the transformer and from the other transformer leg to the valve. On the other relay contact terminal wire to the valve to complete the circuit. Isolated control power should be provided to power the valve. HYDNI VLVE HETING OIL ONTL RELY 24 VOLT TRNSFORMER UX R M R M 15

20 1 M 2 M OVR _UTO 3 +1h Menu 11:25 4 OK HP GLK PRI ON Mode + Mo Tu We Th Fr Sa Su Y1 OFF 5 TIME UTO EH TIME/TMP ON Y2 O/ SET DN UP UX W1 GEN II-VVT R G T-1 MODULTING DMPER DM-1 W R M R M UNLOK LOK T T S IN S DY NIGHT OUT M UX M R T-2 MODULTING DMPER DM-2 R M R M UX M R T-3 MODULTING DMPER DM-3 VOTE SED UTO HNGEOVER YPSS VV ZONEX GEN II-VVT R M R M SPT STTI PRESSURE TUE USE 18/3 THERMOSTT WIRE FM THE MOTT TO THE DMPER MOTOR 24VOLT WIRING FM MOTT TO DMPER MOTOR DISY HIN 24V ND DTLINK LE (ELDEN 8740) TO LL ZONE MOTTS EXPNDLE TO 17 ZONES FOR PPLITIONS SSISTNE LL VISIT OUR ON-LINE TLOG T ZONEXPDUTS.OM USE 18G THERMOSTT WIRE TO DISY HIN THE 24VOLTS FM MOTT TO MOTT 2 WIRE TWISTED PIR DISY HINED MOTT TO MOTT 7-DY TIME LOK SUPPLIED WITH YPSS DMPER (FTORY PRE-WIRED) SUPPLIED WITH THE YPSS DMPER (FTORY PRE-WIRED) LOTED FTER THE YPSS EFORE THE FIRST SUPPLY TKEOFF SUPPLY LT LOTED EFORE THE YPSS 24VOLT WIRING TO MOTTS RS485 OMMUNITION LINK GLK IP INTEGRTED STTI PRESSURE ONTL TIME LOK LT SUPPLY IR LT DISHRGE SENSOR P-DM YPSS TRNSFORMER YPSS DMPER TUTOR 24V/40V TRNSFORMER (2V PER ZONE DMPER) DISY HINED MOTT TO MOTT SYSTEM TRNSFORMER IND. 24V/40V TRNSFORMER TO POWER THE YPSS DMPER SUPPLIED WITH ZONE DMPER DM DESRIPTION GEN II ONTLLER ONTLS 2-17 MODULTING DMPERS 1 ONLY 1 24V 40V TRNSFORMER POWERS LL SUPPLY DMPERS T1 -T17 MOTT II ID ZONE DMPER TUTOR THERMOSTT ONTL ORD DEVIE Power ommunication R = RX = = TX = Terminal onnections GEN II WIRING SHEMTI G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE 16

21 G-STT UNIVERSL THERMOSTT DESRIPTION The G-STT (Part# G-STT) is a universal programmable G/E or H/P thermostat, microprocessor based, auto changeover, stand alone thermostat used to control stand alone units in the GEN II system. The G-STT is configured for Gas/Electric (2H, 2) or Heat Pump (3H, 2) with selectable fan operation. The G-STT reports the supply and return air temperatures and has a large, easy to read LD display. The G-STT is very easy to configure by manually adjusting settings at the thermostat. The G-STT features an on board thermistor for precise temperature measurement. In the event of power loss, the Heat and ool set points are stored in non-volatile memory, without the need for battery backup. Space ambient temperature is continually displayed with large, easy-to-read numbers. G-STT temperature display range is F. Heat and ool set points and operation modes are all indicated on the display. Programmed set points can be manually adjusted at the thermostat or electronically locked through the mobile app to provide limited manual set point adjustment. During unoccupied hours, temporary operation can be overridden with a touch of a button. INSTLLTION Thermostat and Terminal base 1. Install the thermostat on an interior wall, away from drafts, supply air currents and direct sunlight or any heat generating source. 2. Screw in retaining screw at the bottom center of the G-STT 3. To remove the thermostat from its sub-base, grasp the cover at the top and bottom and pull straight off; do not pivot the cover from the base. 4.. Install the thermostat sub-base to the wall using the provided anchors and screws. 17

22 INSTLLTION INSTRUTIONS WIRING THE UNIT, SUPPLY ND RETURN IR SENSORS TO THE G-STT Using 18/6 thermostat wire, wire from RTU to G-STT. Make sure to match up unit terminals R, Y1, Y2, W1/O/, W2, G to the G-STT terminals R, Y1, Y2, W1/O/, W2, G. Wire in the Supply and Return air sensors using 18/4 thermostat wire. Install the Supply and Return air sensors 18 to 24 downsteam of the unit. HV UNIT 24v IN 24v OUT RTN RTN LV LV SUPPLY RETURN DISY HIN THE OMMUNITION WIRE 24v IN 24v OUT Using Zonex 2 wire communication wire. Wire to,, IN and,, OUT, to and from G-STT's in a daisy chain configuration. Wiring to ommunication Terminals Red- = TX lack- = RX RTN RTN LV LV 24v IN 24v OUT DISY HIN 24V POWER FM GEN II G-STT is powered by the independent transformer connected to the GEN II. Using 18/2 wire for the 24vac power, daisy chain from, IN and OUT to and from the G-STT's. RTN RTN LV LV Daisy hain Multiple G-STT's 24v IN 24v OUT 24v IN 24v OUT RTN RTN LV LV RTN RTN LV LV 24v IN 24v OUT RTN RTN LV LV 18

23 G-STT ONFIGURTION ND OPERTION Thermostat onfiguration 1. Set a unique ID for each thermostat ranging from (See Thermostat onfiguration Menu on the next page on how to set) 2. onfigure the thermostat for the type of unit operation you would like. Gas, Heat Pump or Electric. (Factory set for Gas) 3. onfigure Fan mode for uto or On operation. (Factory set for uto) 4. onfigure 2nd stage delay. Temperature range is 2-8 F. ( Factory set 2 F) Manual djustments Heat and ool set point Display Press the SET button to toggle between the Heat or ool set points. Temperature Set Points OOL SET POINT 1. Press the SET button to display the ool set point in the upper right. 2. Press the UP or DN buttons to change the ool set points. Up Down HET SET POINT 1. Press the SET button to display the Heat set point in the upper right. 2. Press the UP or DN buttons to change the Heat set points. Thermostat Operation OOL - The thermostat will make a Y1 cool call when the space temperature rises 1 above set point. Y2 will energize when the space temperature rises 2 above the cool set point or whatever the 2nd stage temperature is set for. When the room temperature reaches set point Y1 and Y2 will de-energize. O or energize for the reversing valve circuit, depending on configuration. The G circuit is energized for fan. HET - Gas / Electric - The thermostat will make a W1 heat call when the space temperature is 1 below the heat set point. W2 will energize when the space temperature is 2 below the heat set point or whatever the 2nd stage temperature is set for. When the room temperature reaches set point W1 and W2 will de-energize. Note: When the thermostat is configured for GS operation the fan circuit is not energized in heat mode. Note: When the thermostat is configured for ELETRI operation the fan circuit is energized in heat mode. HET - Heat Pump - The thermostat will make a Y1 heat call when the space temperature is 1 below the heat set point. Y2 will energize when the space temperature is 2 below the heat set point or whatever the 2nd stage temperature is set for. W2 (ux Heat) will energize when the space temperature is 1 below what the 2nd stage temperature is set for. When the room temperature reaches set point Y1,Y2 and W2 will de-energize. EMERGENY HET - When Emergency Heat is selected in the configuration menu on the thermostat on a call for heat, there is an output signal on W2 for backup heat and G for the fan. The compressor circuits Y1 and Y2 are locked out during heat calls, until the emergency heat function has been turned off in the configuration menu. FN MODE - Factory set for UTO, to configure the thermostat to run the fan constant ON you will need to go into the configuration menu and select fan mode and change it from UTO to ON. OVERRIDE - When the system is in the Unoccupied mode, the thermostat provides a 2 hour override for after-hours system operation. To select the override function, press the uto button and note Override is indicated on the display. When additional override is required, press the uto button again. To disable override push UTO button again to return to unoccupied mode. 19

24 G-STT ONFIGURTION MENU THERMOSTT ONFIGURTION MENU To access the System onfiguration Menu, Hold MENU and UTO at the same time. The THERMOSTT ONFIGURTION MENU allows you to:. Set stat ID D. Fan Mode G. Temperature Format. alibrate E. Set 2nd Stage H. Diagnostic. Set Unit Type F. Emergency Heat Up Down. SET STT ID. LIRTE. SET UNIT TYPE D. FN MODE E. SET 2ND STGE F. EMERGENY HET SELET SET STT ID Every thermostat in the system needs a unique ID. Must be in numerical order the way the communication wire is daisy chained. onfirm no duplicate addresses. While in the Thermostat onfiguration Menu, press STT ID : 001 SVE EXIT LIRTE LIRTE THERMOSTT 74.1 EXIT Select on. Set Stat ID. Use the Up and Down buttons to give the thermostat an ID ranging from STT ID EXIT Press Press Exit to return to the Thermostat onfiguration Menu. Save to save settings. Thermostat is equipped with an accurate temperature sensor. If you require field calibration follow the steps below. While in the Thermostat onfiguration Menu, press. alibrate Down and press Use the Up and Down buttons to calibrate the temperature display with your EXIT to save changes. external thermostat, press onfirm temperature display now reports the updated room temperature you provided. SET UNIT TYPE The G- STT is designed as a universal GS/ELETRI/HET PUMP thermostat. Factory default is set for GS operations, and may require field configuration when applying this product to Electric or Heat Pump applications. While in Thermostat onfiguration Menu, press Down and press. Unit Type menu item. SET UNIT TYPE Select on GS ELETRI HET PUMP OO HET PUMP O SVE EXIT Select on Use the Up or Down to set the desired Unit Type for each thermostat. Select Gas, Heat Pump OO, Heat Pump O, Electric. Press Press Exit to return to the Thermostat onfiguration Menu. Save to save settings. Note: Some heat pump units use GS/ELETRI inputs - confirm your unit s operation to ensure proper configuration. 20

25 G-STT ONFIGURTION MENU D FN MODE Fan operation is configured for either Fan ON or UTO. When system is configured for ON operation, the Fan will run during Occupied schedule and will revert to uto operations during Unoccupied schedule. When thermostat is configured for uto operation, Fan will only run when there is a call for heating or cooling. While in Thermostat onfiguration Menu, press Down and press D. FN MODE menu item. FN MODE FN MODE: UTO SVE E EXIT SET 2ND STGE Use the Press Press Down to set the Fan mode to UTO or ON. Exit to return to the Thermostat onfiguration Menu. Save to save settings. The G-STT s 2nd stage operation is based on room temperature. Staging is adjustable from 2-8 from thermostat room temperature. While in Thermostat onfiguration Menu, press Down and press E. Set 2nd Stage menu item. SET 2ND STGE 2ND STGE : 02 SVE EXIT EMERGENY HET EMERGENY HET EMERGENY HET : YES SVE While in Thermostat onfiguration Menu, press F. Emergency Heat menu item. Use the Up and operation. Press Press G Exit to return to the Thermostat onfiguration Menu. Save to save settings. The G-STT has an emergency heat function that will lock out the compressor, and energize the ux heat in the unit. EXIT TEMPERTURE FORMT Select on Use the Up and Down buttons to select the desired staging temperature range. Press Press F Up or Select on Down and press Select on Down buttons to select Yes or No for Emergency Heat Exit to return to the Thermostat onfiguration Menu. Save to save settings. The G-STT may be configured for F or operation. From the Thermostat onfiguration menu toggle the UP or DOWN button to highlight TEMPERTURE FORMT. When desired temperature format is displayed press SVE. While in Thermostat onfiguration Menu, press G. TEMPERTURE FORMT menu item. Toggle Press Press Up and Down and press Select on Down to set the desired Temperature Format. Exit to return to the Thermostat onfiguration Menu. Save to save the settings. 21

26 G-STT ONFIGURTION MENU H DIGNOSTI The G-STT Diagnostic screen will allow you to confirm communication with the GEN II controller. nd display the RH, Supply ir, and Return ir temperatures. While in Thermostat onfiguration Menu, press H. DIGNOSTI menu item. DIGNOSTI OMM. HUMIDITY LEVING IR RETURN IR OK Press Down and press Select on Exit to return to the Thermostat onfiguration Menu. EXIT 22

27 1 M OVR _UTO h Menu 11:25 M OK Mode + Mo Tu We Th Fr Sa Su GLK Y1 OFF 5 PRI ON HP UX UTO TIME EH TIME/TMP ON Y2 O/ SET DN UP R W2 1 T-1 M R M R 72 MODULTING DMPER DM-1 W1 GEN II-VVT G DY NIGHT Power ommunication R = RX = = TX = UX R F 71.9 T-2 MODULTING DMPER DM-2 R M R M F LV LV RTN RTN LV LV RTN RTN 70 R D3 24VOLT WIRING FM MOTT TO DMPER MOTOR D4 TO LL THERMOSTTS EXPNDLE TO 17 ZONES DISY HIN 24V ND DTLINK LE (ELDEN 8740) FOR PPLITIONS SSISTNE LL USE 18/3 THERMOSTT WIRE FM THE MOTT TO THE DMPER MOTOR 24VOLT WIRING TO MOTTS VISIT OUR ON-LINE TLOG T ZONEXPDUTS.OM USE 18G THERMOSTT WIRE TO DISY HIN THE 24VOLTS FM MOTT TO MOTT ND G-STT S RS485 OMMUNITION LINK 7-DY TIME LOK SUPPLIED WITH YPSS DMPER (FTORY PRE-WIRED) SUPPLIED WITH THE YPSS DMPER (FTORY PRE-WIRED) LOTED FTER THE YPSS EFORE THE FIRST SUPPLY TKEOFF SUPPLY LT LOTED EFORE THE YPSS IND. 24V/40V TRNSFORMER TO POWER THE YPSS DMPER 2 WIRE TWISTED PIR DISY HINED MOTT TO MOTT TO G-STT GLK SPT STTI PRESSURE TUE TIME LOK IP INTEGRTED STTI PRESSURE ONTL P-DM LT SUPPLY IR LT DISHRGE SENSOR YPSS DMPER TUTOR SYSTEM TRNSFORMER YPSS TRNSFORMER SUPPLIED WITH ZONE DMPER 24V/40V TRNSFORMER (2V PER ZONE DMPER) DISY HINED MOTT TO MOTT DM ZONE DMPER TUTOR 24v OUT 24v IN 70 DESRIPTION GEN II ONTLLER ONTLS 2-17 MODULTING DMPERS ONLY 1 24V 40V TRNSFORMER POWERS LL SUPPLY DMPERS T1 -T17 MOTT 1 ID ONTL STND-LONE UNIT D3 - D4 G-STT ZONE THERMOSTT ONTL ORD DEVIE 24v OUT 24v IN F R-1 ONTLLING ONE ZONED UNIT WITH ONE OR MORE STND-LONE UNITS GEN II M Terminal onnections G W2 O/ Y2 Y1 R HP G W2 W1 Y2 Y1 R GE M UNLOK LOK S S OUT IN T T 23

28 REMOTE ND VERGING SENSOR INSTLLTION REMOTE SENSOR The following wiring diagram is used when remote temperature sensing is desired on a job. Zonex Systems MOTT-RS or GSTT-RS is required, as is a remote sensor (part # RS). Thermostats and sensors are wired in parallel. W1 REHET Install thermostat per installation instructions. ll remote sensors include a wiring harness. Plug wiring harness into the J4 plug on the back of the thermostat, this will provide two wires to connect the remote sensor to the thermostat. Per the drawing above, wire the remote sensor in parallel, one wire from the thermostat will connect to + terminal on the sensor, the second wire will connect to - terminal using 18WG thermostat wire. Verify sensor operations. TEMPERTURE VERGING The following wiring diagram is used when temperature averaging is desired on a job. This wiring diagram is to average two areas of a building for one thermostat. Zonex Systems MOTT-RS or GSTT-RS is required, as are two VG averaging sensors (part # VG). Thermostats and sensors are wired in parallel VG 2 VG 1 W1 W1 REHET REHET Install thermostat per installation instructions. ll averaging sensors include a wiring harness. Plug wiring harness into the J4 plug on the back of the thermostat, this will provide two wires to connect the averaging sensor to the thermostat. Per the drawing above, wire the VG averaging sensor in parallel, one wire from the thermostat will connect to + terminal on the sensor, the second wire will connect to - terminal using 18WG thermostat wire. Extend these wires to + and - terminals on the second VG sensor. Verify sensor operations. 24

29 SYSTEM STRT UP ND TEST System Start Up and Test 1. Plug all thermostats into sub-bases. Turn GEN II power switch (E) to ON. 2. Find the first Thermostat in the Daisy chain and change its address from 20 to 001. (See ModStat installation instructions onfiguration ddressing). 3. Turn GEN II power switch OFF and then ON. The Display should flash 01 and then show the leaving air temperature. This confirms your successful wiring and communication with that thermostat. 4. If 01 is displayed, change the next thermostat s address from 20 to 002. Turn the GEN II power switch OFF and then ON. Th e display should flash 02 and then show the temperature. Readdress thermostats one at a time. 5. fter each stat is re-addressed, turn the power switch off and then on. This will verify that the re-addressed stat has been found by the GEN II ontroller. This procedure will simplify your installation and will confirm your wiring is correct and that the GEN II controller can communicate over the 2-wire twisted pair data link with every thermostat in your system. Troubleshooting When stat #1 is not found: 1. heck thermostat to verify that it is addressed as heck all and wiring for proper color-to-color connections. Even if the stats are lighted, all wires at the thermostat must be connected to the GEN II terminal. ll wires must be connected to the GEN II terminal. onfirm the daisy chain wiring is correct at this time. 3. heck,, & wires for proper color code and connections; polarity is imperative. ll connections must land on terminal on the following thermostat, and all connections must connect to terminal on each thermostat, and all connections must connect to terminal on each thermostat if used. 4. heck and wires for opens or shorts. hecking the Daisy hain for opens or shorts: Start from the GEN II board, and follow,, & wires to the first sub-base. Remove the,, & wires going to the next sub-base in the link. Plug a stat into the first sub-base, and address it as #1. Turn the GEN II power switch Off, then On, to see if the display flashes 01, at the GEN II controller. 1. If 01 is displayed, the first link of the daisy chain is OK. Reconnect the wires going to sub-base. 2. Repeat these steps with a stat numbered 02. If the number 02 is displayed, then communication is confirmed. When the correct number does not appear for a link, that link is either shorted or open. link of the daisy chain, which is open or shorted, must be repaired before the next thermostat is checked. When the thermostats are correctly addressed, wired and linked, the total number of stats on your job connected to the GEN II control board will be displayed when the board is turned on. fter the correct number of connected thermostats is displayed, complete the wiring of the unit or heat pump connections, next make heat and cool calls to the GEN II controller. 25

30 DVNED FETURE ONFIGURTION Occupied / Unoccupied fan operation The factory setting for FN operation is UTO, with the FN jumper (I) on the middle and lower pins. In this setting, the fan circuit on G is only energized on an active cool call in Gas/Electric mode or on an active heat call or cool call in Heat Pump mode. This applies to both Occupied and Unoccupied modes. When the FN jumper is in UTO, there is no output on G with an active heat call in Gas/Electric mode. onstant Fan in the Occupied (DY) mode Place the FN jumper (I) on the center and upper pins on ON. The fan output on G will be constant in the Occupied (DY) mode and will revert to auto in the Unoccupied (NIGHT) mode. Opposing all hangeover The GEN II controllers are configured at the factory for Opposing all hangeover with a time delay setting of 10 minutes. With this configuration, any number of thermostats can make a like active call (heat or cool). During this time, if a single thermostat makes an opposite call, a timer is started at the next poll. This timer starts a time delay operation to allow the initial calling thermostats to satisfy. If the initial active thermostats do not completely satisfy after 10 minutes, the dampers all close and the controller drops out the HV outputs and goes into a 5 minute purge cycle. When the purge cycle times out, the opposing thermostat call is initiated; and the appropriate HV outputs are energized, and the supply damper opens. The thermostat with the opposing call must now satisfy before the GEN II controller will recognize any of the initially calling thermostats. The opposing call timer is factory adjusted for 10 minutes. However, the delay time can be field adjusted from 5 to 30 minutes, or disabled. To increase the opposing call time delay: 1. Press the SET and UP buttons. 2. Release the SET button when the display changes, and continue to hold down the UP button. 3. Release the UP button when the desired time is displayed. To lower the time delay: 4. Press the SET and UP buttons. 5. Release the SET button, and immediately press and hold the DN (down) button until the desired time is indicated; then release. The Opposing all feature can be disabled by performing steps 1 through 3 and then releasing the UP button when the display indicates 32. With this feature disabled, the GEN II controller will operate changeover by majority vote from the zone thermostats. Priority active Heat and ool call operation The GEN II controller may be configured in the field for majority vote changeover but also assign multiple votes for selected thermostats to enhance the changeover operation for special requirements. Each thermostat represents one vote for heat or cool operation; a majority of active calls will determine which mode the controller will operate in. With the Priority feature, any thermostat may be assigned one or more additional votes to allow it to have priority to bring a mode changeover more quickly. To keep proper overall temperature control, this priority vote change should be limited to as few zones as possible. Follow the procedure to implement Priority vote operation: 26

31 DVNED FETURE ONFIGURTION 1. Determine which thermostat address is to have an additional one or two votes. 2. Place the PRIORITY jumper (F) on both pins. 3. Press and hold the SET and UP buttons (H), and the LED display will scroll through the number of zones starting with When the display indicates the address (01 to 17) of the thermostat you want to add votes to, release both buttons and press the DN button. The display will scroll through 00, 01, 02. To add one additional vote, release the DN button when the display indicates 01 (this assigns a total of 2 votes). To increase the votes by two, press the DN button and wait until the display indicates 02 and then release the DN button (this assigns a total of 3 votes maximum). 5. To change the votes back to a single vote, press the DN button on the selected address and release when the display indicates To review the vote status of all of the thermostats in the system, press the UP button; and the display will first indicate the address number starting with 01and then the vote status for that address. 00 = 1 vote 01 = 2 votes 02 = 3 votes. Upon review, if stat #1 has 2 votes, the display will show Stat 01 followed by 02 signifying the number of Priority votes assigned to Stat 1. Stat 02 will appear followed by a blank display, indicating only 1 vote; and Stat 03 will appear followed by a blank screen, indicating no priority votes have been added to Stats 02 or e certain to Place the PRIORITY jumper on one pin to put the controller back into normal operation with the changes that were made. Thermostat security - Set Point LOK The GEN II system provides the ability to electronically lock all of the zone thermostats (global). When the thermostats are in the LOK mode, there will be a padlock icon on each thermostat display. The LOK mode limits the manual changing of the heat and cool set points to a maximum of 2 above or below the initial heat and cool set point temperatures. To set the thermostats for the LOK mode, simply change the switch position (K) from UNLOK to LOK. ll of the thermostats will change to LOK on the next system poll. To unlock, set the switch to the UNLOK position; and the thermostats will drop the icon after the next system poll and revert to normal operation. ir alance - Force Dampers Open When performing an air balance on the supply air outlets, the GEN II controller provides a unique feature to simplify this procedure. The GEN II controller will put all thermostats in a cool call which will open the dampers 100% and bring on the system blower. 1. Place the EH jumper (F) over both pins 2. Press the SET and UP buttons (H) simultaneously This puts a global cool set point of 58 F (14 ) on all of the zone thermostats, and the controller energizes the G fan output only; Y1 is not energized. 3. When the air balance procedure is completed, press the SET and DN buttons simultaneously, which will assign 70 F (21 ) Heat and 75 F (23 ) ool set points on all of the zone thermostats. 4. Press and hold the SET and DN buttons; and while holding these buttons, remove the EH jumper tab and place it on one pin. Release the SET and DN buttons. This procedure returns the GEN II controller to normal operation. For Electric Heat fan configuration, see Page 5. 27

32 TIME LOK INSTLLTION Default Thermostat Set Point Programming Global default set points can be established from the GEN II controller. The following procedure will provide a 75 F (23 ) ool and 70 F (21 ) Heat occupied set point along with Unoccupied 58 F (14 ) Heat and 85 F (29 ) ool set point for every thermostat in the system. This handy feature minimizes visits to the thermostats. To establish these default set points: EH jumper (F) - place the jumper over both pins. Press the SET and DN button (H) simultaneously to engage default set points. Remove the EH jumper, and place on one pin to put controller back into normal operation. To view the unoccupied set points place the Night / Day switch (L) to the NIGHT position. Following a poll, the thermostat backlights will turn off; and the unoccupied set points will be displayed. Time lock The GLK is a 24vac 7-Day programmable time clock offered by Zonex Systems, exclusively for the GEN II control system. This digital time clock will enable the control system to operate with Global Occupied and Unoccupied schedules in a 7-day format. The GLK is powered from the GEN II controller power supply, and there is a backup battery to protect the time clock program for up to 100 hours. Installation The GLK must be installed on an interior wall next to the GEN II controller. oth the GEN II controller and GLK time clock must be easily accessible to monitor status and to make program and function changes. 1. Remove the clear dust cover lens and loosen two screws on opposite corners of the clock module. 2. Remove the housing that surrounds the time clock and the wire terminal cover. 3. Remove the clock module by pulling straight out from the base. Install the backing plate to the wall with 3 screws (provided). 4. The GLK is powered from and on the GEN II controller to terminals 1 and 2 on the time clock terminal base. 5. The Normally Open switch contacts on the time clock 3 and 5 are wired to the T terminals on the GEN II controller. 6. Press the clock module back into place in the base, making certain that it is seated correctly. 7. Install the wire terminal cover and the clock housing with the 2 screws. 8. Install the clear dust cover lens in place. Programming See Programming and onfiguration included with the GLK. 28

33 ZONE DMPERS Zonex Systems zone dampers are used in cooling/heating systems to provide room by room zone control. The damper is provided with a factory mounted actuator. Each zone damper is controlled by a zone thermostat. More than one damper can be controlled by one zone thermostat. Use this table to determine which zone dampers to use. DMPER MODEL STMPD Round Med. Pressure STMRTD Rect. Med. Pressure STD Rect. Heavy Duty STRD Round Heavy Duty D-FUSER MXIMUM DIFFERENTIL PRESSURE MXIMUM SYSTEM SIZE ny Size 5 Tons ny Size ny Size ny Size MXIMUM DUT SIZE W x 20 H 48 W x 48 H Maximum Differential Pressure refers to the maximum static pressure drop in inches of water column between the input (upstream) of the zone damper and the output (downstream) when the damper is closed. UND MEDIUM PRESSURE ZONE DMPERS Zonex Systems round medium pressure zone dampers are recommended for systems with a maximum differential static pressure up to This modulating power open/power close damper is manufactured from gauge galvanized steel with rolled-in stiffening beads for superior rigidity. Mechanical minimum and maximum set stops are provided and are easily adjustable. The damper is elliptical, which allows the airflow to be tracked linearly. The damper pipe is furnished with one crimped end and one straight end for easy installation. Do not install damper in an inverted position. hat section supports a reversing 24vac, 60Hz, 2 V motor. magnetic clutch allows for continuous power to the motor and longer motor life. Motor drive time from full open to full close is 90 seconds. UND MEDIUM PRESSURE DMPER PRT NUMERS ND SIZES L D W MEDIUM PRESSURE (STMPD) UND DIM ENSI O N L D T PRT # SIZE D L W STMPD06 STMPD08 STMPD10 STMPD12 STMPD14 STMPD16 STMPD18 STRD20 STRD22 STRD Note: Round dampers over 18 will be heavy duty style STRD dampers. Part # STRD size TYPIL UND PITIES These air quantities were derived from a duct sizing chart 0.1 friction loss per 100 of duct. ll FMs listed are approximate. For accurate selection, use duct sizing table or device. DUT DIMETER NOMINL FM DUT VELOITY FPM DMPER P W

34 ZONE DMPERS RETNGULR ZONE DMPERS The rectangular zone dampers are available in either medium pressure or heavy duty. For systems under 5 tons, use medium pressure dampers. For systems 5 tons or over, use heavy duty dampers. Motor drive time open and close is 90 seconds. RETNGULR MEDIUM PRESSURE ZONE DMPERS (STMRTD) Zonex Systems rectangular medium pressure dampers are recommended for systems under 5 tons with a maximum differential static pressure of 1. These are fully modulating, power open, power close dampers. They are constructed from heavy duty aluminum and stainless steel. The damper is an opposed blade type that slips into a 3¼-inch wide cutout in the existing duct and attaches with screws via a duct mounting plate. The duct mounting plate is 5 inches wide. hat section supports a reversing 24vac, 60Hz, 2 V motor. magnetic clutch allows for continuous power to the motor and longer motor life. Two set screws connect the motor to the damper shaft, allowing quick motor replacement if necessary. Motor drive time from full open to full close is 90 seconds. MEDIUM PRESSURE RETNGULR DIMENSIONL DT Part Number STMRTD W x H Sizes available from 8 x 6 up to 24 x ½ 2¼ W H HEVY DUTY RETNGULR DIMENSIONL DT Part Number STD W x H Sizes available from 8 x 8 up to 48 x 48 MOTOR 48 MXIMUM WIDTH 2 ½ D H D RETNGULR HEVY DUTY ZONE DMPERS (STD) Zonex Systems rectangular heavy duty dampers are recommended for systems 5 tons or larger with a maximum differential static pressure of These are fully modulating, power open / power close dampers made of 20 gauge snaplock steel frame with S & Drive duct connections. llow a 16 gap in the duct for the damper. Formed steel blade stops incorporate a gasket for quiet operation and improved structural rigidity. Rectangular dampers under 10 in height incorporate a single blade design. Dampers 10 or over use opposed blade design. full stall motor, drawing 2 V, drives the motor from full open to full close in 90 seconds. 30

35 ZONE DMPERS Rectangular Damper apacities* HEIGHT IN INHES WIDTH IN INHES * These air quantities were derived from duct sizing chart.1" friction loss per 100' of duct. ll FMs listed are approximate. For accurate selection use duct sizing table or D-FUSER ZONE DMPER Zonex Systems D-Fuser is a combination zone damper and diffuser. It mounts in a standard 2 x 2 T-bar ceiling opening, providing for simple installation and easy maintenance access. The D-Fuser is a cone shaped fluidic nozzle with a platen that modulates up and down to control air flow. s the platen moves up, the air volume is reduced; but the air velocity and throw remain constant. This keeps the air hugging the ceiling, which maximizes room air mixing and minimizes the waterfall effect. The D-Fuser is a fully modulating power open / power close damper using a 24vac 60Hz 2 V motor. Motor drive time from full open to full close is 90 seconds. The D-Fuser connects to round duct either on the side or top. ollars are available for 6, 7, 8, 9 and 10 duct. 12 OLLR: PLE ON SIDE PLE ON TOP T NEK VELOITIES UP TO 700 FPM N LESS THN Neck Vel P FM Throw 50 FPM Neck Vel P FM Throw 50 PM Neck Vel P FM Throw 50 FPM

36 SIZING ZONE DMPERS SIZING ZONE DMPERS If the ductwork already exists, simply size the damper to fit the ductwork. For new systems or retrofit jobs:. Determine FM from heat gain or loss calculations.. Select damper size using either the round capacities chart, the rectangular capacities chart or by using a duct sizing table or calculator.. Select a Zonex Systems damper to fit the duct size selected for that zone. Make sure your zone dampers match the type specified in the table showing Maximum Differential Pressure. INSTLLTION NOTES 1. Do not exceed 700 FPM in a register/diffuser branch duct. 2. If a damper is installed within 3 feet of a register/diffuser, install sound attenuating flex duct between damper and outlet. 3. Zone dampers should be preceded by 2 4 of straight pipe where possible. 4. In attic installations and high humidity areas, the Zonex Systems damper should be insulated along with the ductwork. The hat section on the round damper is delivered with insulation between the hat section and pipe. Therefore, insulation should be applied to the round pipe and be butted against the hat section (do not insulate the motor). The motor generates enough heat so that no condensation will develop on it. 5. Remember to allow a 16 gap in the duct for heavy duty rectangular dampers. 6. Medium pressure rectangular dampers slide into a 3¼ wide cutout in the side of the preexisting ductwork. 7. Minimum open and close positioning is field adjustable on the actuator. The damper is shipped from the factory to close 100%. NOTE: Dampers should not be installed with motor upside down in the 6:00 position. SLVING UP TO THREE ZONE DMPERS Up to three dampers can be directly controlled by one zone thermostat. To wire two or three dampers for a zone, use the following wiring diagram. Remember to size the power transformer for the total number of zone dampers in the system, 2va per damper. UX R M R M R M ZONE DMPER 1 STMPD or STD damper R M ZONE DMPER 2 STMPD or STD damper R M ZONE DMPER 3 STMPD or STD damper SLVING MORE THN THREE ZONE DMPERS When slaving more than three zone dampers, use the following diagram. n additional 24-volt transformer and control relays are needed for these applications. Note: ll slave dampers need to be model STMPD / STD ONTL RELY SPST UX R M ZONE DMPER 1 R M ZONE DMPER 2 STMPD or STD damper STMPD or STD damper ZONE DMPER 3 R M ZONE DMPER 4 STMPD or STD damper STMPD or STD damper M R R M R 24 VOLT TRNSFORMER M ONTL RELY SPST 32

37 YPSS DMPERS- ELETNI ELETNI YPSS DMPERS ypass dampers are used to provide constant air delivery through the air handling unit. This is done by bypassing excess air from the supply duct back to the return duct. s a zone is satisfied, its zone damper closes. When this happens, the bypass damper opens just enough to bypass the excess air. This will control static pressure and noise at the diffusers. The Electronic ypass Damper is used on any size system over 5 tons. The damper can be round (STP) or rectangular (STDP) with integrated static pressure control; and multiple dampers can be slaved together. SIZING ELETNI YPSS DMPERS The bypass damper is to be sized for the total system 1500 FPM. System FM should be calculated at 400 FM per ton. Example: 5-ton system is rated at 2000 FM (5x400 = 2000). When calculated at 1500 FPM, the bypass damper should be 16. Never undersize the bypass damper. UND YPSS SELETION TLE Diameter FM PRT # SIZE D L W STP08 STP10 STP12 STP14 STP16 STP18 STRDP20 STRDP22 STRDP UND YPSS DMPER SELETION The Zonex Systems STP damper is used for round bypass applications. When you know the bypass FM requirements, use the UND YPSS SELETION TLE to confirm the round damper size. NOTE: Multiple round dampers can be slaved from one static pressure control to provide the correct capacity. One large rectangular bypass damper may be used instead of multiple round dampers. See below. RETNGULR YPSS DMPER SELETION The Zonex Systems STDP WxH damper is used for rectangular bypass applications. These dampers are also sized for the total system FM rated at 1500 FPM. Multiple dampers can be slaved from a single static pressure control. L D W 48 MXIMUM WIDTH 4 W H D RETNGULR YPSS DMPERS SELET FM 8 x 8 thru 48 x 48 33

38 RETNGULR YPSS SELETION TLE HEIGHT IN INHES RETNGULR YPSS SELETION TLE WIDTH IN INHES ypass air in FM. alculated at 1500 FPM. Formula used: = W x H / 144 x 1500, where = ypass air in FM, W = damper width in inches, H = damper height in inches, 144 = 144 sq. inches per sq. ft., 1500 = 1500 FPM. UND ND RETNGULR YPSS DMPER MOTORS SLVING YPSS DMPERS Use only one Pressure Sensor when slaving two or more ypass Dampers together. onnect the Pressure Sensor to one damper as described above. onnect the slave dampers in parallel as shown. Up to 4 dampers can be slaved to one Sensor. The slaved dampers will selfsynchronize each time the dampers reach full open or full close. DMPER TUTOR SLVE DMPER TUTOR R M R M * * * * * * TO NEXT SLVE YPSS DMPER IF PPLILE R M To Static Pressure ontrol, as shown on the ypass Wiring Diagram on the next page. 34

39 YPSS INSTLLTION INSTLLTION The round and rectangular bypass damper can be installed in any position. Do not run speed screws into damper housing. Screws may interfere with damper travel. 1. Install the bypass damper between the supply and return plenums of the unit. It must be the first tap off the supply plenum. (ypass damper sizing is recommended for 100% of system FM.) 2. e sure the air flows through the damper in the proper direction as indicated by the arrow on the damper. irflow is always from supply to return plenum. 3. Do not install the bypass damper outside. 4. ypass damper and controller are powered by a dedicated 24vac 40V transformer. 5. Follow the steps on the next page for Integrated Pressure ontroller installation and set up. OFTOP INSTLLTION Down Discharge pplication HORIZONTL PPLITION IRFLOW SHEET METL PIPE RETURN / UNIT OR FURNE YPSS / UNIT OR FURNE OF LINE SUPPLY PLENUM YPSS IRFLOW IRFLOW SUPPLY PLENUM RETURN PLENUM SHEET METL PIPE OPEN RETURN PLENUM ND YPSS PPLITION YPSS DMPER IR ONDITIONING UNIT RETURN IR GRILLE SUPPLY DUT TTI SPE OPEN RETURN PLENUM YPSS PPLITION YPSS DMPER IR ONDITIONING UNIT To prevent bypass air from flowing out the return grill, use a short open ended return air plenum to connect the bypass damper to the unit. RETURN IR GRILLE SUPPLY DUT TTI SPE 35

40 INTEGRTED PRESSURE ONTL SETUP ypass Damper with Integrated Pressure ontrol is used to control bypass operations. The bypass damper modulates to maintain static pressure as zone dampers open and close. The bypass system reduces air noise from the supply registers caused by excessive air velocity. If the system is configured for intermittent fan mode and the system satisfies, there will be a 3-minute delay to allow for system purge, after which the bypass damper will open to 25%, preventing noisy rush of air through supply registers when fan starts up on a call for heat or cool. If the system is configured for fan continuous operation, the STP (Round) or STDP (Rectangular) Electronic ypass will monitor static pressure continuously, providing constant control of system static. Integrated Pressure ontrol Description... D. E. F. Supply air tube 24vac R and Damper Terminal, R, M LED lights djustable Potentiometer TP1 Test Point IP Installation Fig. 1 Fig Locate the Integrated Pressure ontrol (IP) and air tube on the bypass damper. Drill hole into the side of the supply duct 2 after the bypass and before the 1st supply take-off. 2. Mount pressure supporting block over hole, align hole in block with hole in duct. Use provided sheet metal screws. 3. Install air tube into supply air duct by slipping supplied plastic tubing into holes in support block and duct. Slip tube 3 into the duct. Pickup tubing fits snugly into provided hole. 4. onnect pressure tube from static air pickup to Integrated Pressure ontroller (port closest to you). ypass Damper With Integrated ypass ontrol Setup 1. Run all supply dampers to the full open position and have blower motor running at 100% fan speed. (See Note #1) 2. Manually close the bypass damper by pressing in the release lever on the motor side of the actuator. With the release lever pressed, rotate the damper actuator collar to close the damper and release the lever to lock the damper closed. 3. Quick Set Option: Turn the potentiometer on the damper control board to the full left position and slowly rotate RIGHT, until the R RED LED turns on. Now rotate LEFT just slightly, until R LED turns off. The IP is ready for operation. R RED LED means damper closing. GREEN LED means damper opening. 36

41 INTEGRTED PRESSURE ONTL SETUP 4. Static Pressure Option: The Integrated Pressure ontrol oard can be field configured for specified static pressure using a multi meter and the static pressure voltage chart. (Exhibit ). This chart shows voltage (D) to inches of W.. (static pressure) relationship. Use a multi meter set on VD and place the leads on the terminal and TP1 (test point one) next to the potentiometer. The Voltage reading translates to inches of W.. Static Pressure Voltage hart STTI PRESSURE INH W TP1 VOLTGE (D) STTI PRESSURE INH W N/ ypass heckout For Static Pressure ontroller 1. Make cool call at the zone thermostat of the smallest zone. 2. Verify all zone dampers are closed except for calling zone. 3. Verify noise at zone registers is not excessive. djust the Integrated Pressure ontrol LEFT to lower noise (airflow) or RIGHT to increase airflow until too noisy. TP1 VOLTGE (D) N/ ypass Damper Wiring Diagram With Integrated ypass ontrol YPSS DMPER WITH INTEGRTED YPSS ONTL EXHIIT Note # 1: To open all dampers, it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats. This will modulate dampers fully open and lock out compressor. R M R 24 volt 40va Transformer Primary 24 volt Secondary ctuator Motor R M IP ontroller On GEN II use air balance mode on the mobile pp for simplified bypass setup. 37

42 GEN II-VVT Hot Line: (800) Engineer Drive Huntington each, Factory: (714) Fax: (714) Visit our Web Site Quick Quote Web Site: The easy way to Get Quotes Fast PTENTED PDUT Zonex Systems reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. opyright 2018 by Zonex Systems Part #GENIIMN March 2019

GEN II -VVT COMMERCIAL ZONING - SIMPLIFIED. Installation and Applications Manual VOT E BASED AUTO CHANG E OVE R V V T A MODULA TING S Y S T E M

GEN II -VVT COMMERCIAL ZONING - SIMPLIFIED. Installation and Applications Manual VOT E BASED AUTO CHANG E OVE R V V T A MODULA TING S Y S T E M GEN II -VVT VOT E SED UTO HNG E OVE R V V T MODUL TING S Y S T E M OMMEIL ZONING - SIMPLIFIED GEN II System ontroller Installation and pplications Manual 58 GEN II QUIK STRT ND OMMISSIONING QUIK STRT ND

More information

INSTALLATION AND APPLICATIONS MANUAL

INSTALLATION AND APPLICATIONS MANUAL NETWORK LL YOUR HV EQUIPMENT Monitor, update and control System Information from the mobile app entralized DD ommunications for Stand-lone HV and Zoned Modulating Systems INSTLLTION ND PPLITIONS MNUL PRT

More information

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment ZonexCommander ZonexCommander(Plus) Network All Your HVAC Equipment Centralized DDC Communications for Stand-Alone HVAC and Zoned Systems Installation and Applications Manual Part #ZCMAN Rev. Oct 2014

More information

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment ZonexCommander ZonexCommander(Plus) Network All Your HVAC Equipment Centralized DDC Communications for Stand-Alone HVAC and Zoned Systems Installation and Applications Manual Part #ZCMAN Rev. July 2010

More information

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications Installation Guide DIGIU Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications -Zone Controller for the RNC Market Part #DMAN October 004 Zoning Systems That s all we do. INTRODUCTION

More information

T-32-TS Touchscreen Thermostat. Installation Manual

T-32-TS Touchscreen Thermostat. Installation Manual T-32-TS Touchscreen Thermostat Installation Manual TABLE OF CONTENTS Introduction...4 Getting Started...5 Installing the Thermostat...6, 8 Disassembly...6 Thermostat Location...6 Mounting the Subbase...6,

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor Model TFH24FXYZ2 Stand-alone with Internal Humidity Sensor Description The TFH24FXYZ2 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications. No additional

More information

Commercial Touchscreen Thermostat

Commercial Touchscreen Thermostat 55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

HEAT COOL. Meets Commercial California Title 24

HEAT COOL. Meets Commercial California Title 24 Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands

More information

W7100G Discharge Water Temperature Control

W7100G Discharge Water Temperature Control W700G Discharge Water Temperature ontrol FETURES PRODUT DT PPLITION Up to six stages of cooling provided. Expandable system up to 0 cooling stages using a W70. dvanced proportional plus integral microprocessor

More information

EnviroZone-4 & EnviroZone-2 Quick-Start Guide

EnviroZone-4 & EnviroZone-2 Quick-Start Guide EnviroZone-4 & EnviroZone-2 Quick-Start Guide This guide is intended to give the installer a brief set of instructions about how to set up the FHP EnviroZone System. For more detailed information about

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...

More information

Design & Installation for. Zonex Systems. System Zone Auto Changeover. System Zone Manual Changeover

Design & Installation for. Zonex Systems. System Zone Auto Changeover. System Zone Manual Changeover Design & Installation for Zonex Systems System 2000 2-20 Zone Auto hangeover System 1000 2-7 Zone Manual hangeover Part #101ASIM ev. September 2003 TABLE OF ONTENTS System 2000 System Operation...1 omponents...1

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat commercial SCHOOL THERMOSTAT T2900SCH MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Energy Saving Operation Morning Warm-up Period Programmable Override Unoccupied until button press

More information

CP-6 Installation and Operation Instructions 3 Heat / 2 Cool Heat Pump with Fossil Fuel option Auto Changeover - Cooling Priority or Majority Wins

CP-6 Installation and Operation Instructions 3 Heat / 2 Cool Heat Pump with Fossil Fuel option Auto Changeover - Cooling Priority or Majority Wins P-6 Installation and Operation Instructions 3 Heat / 2 ool Heat Pump with Fossil Fuel option Auto hangeover - ooling Priority or Majority Wins Sequence of Operation: Each zone damper is controlled by its

More information

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE OWNER S MANUAL COMMERCIAL THERMOSTAT P/N P374-2800 I 2 : 0 0 Su AUTO Pm 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL 7-DAY HEAT PUMP PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2

More information

HEAT HEAT HEAT COOL COOL

HEAT HEAT HEAT COOL COOL OWNER S MANUAL AUTO 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL COMMERCIAL THERMOSTAT P/N P374-2700 HEAT PUMP NON-PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2 Heat & 2 Cool Stages

More information

Smart Temp. ApolloP/n Installation Manual. Version 1.0

Smart Temp. ApolloP/n Installation Manual. Version 1.0 Smart Temp ApolloP/n 44-800 Installation Manual Version 1.0 TABLE OF CONTENTS Introduction...6 Getting started...7 Installing the thermostat...8 Disassembly...8 Thermostat location...8 Mounting the subbase...8,

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 800 7-DAY PROGRAMMABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers

More information

Installation, Service, and Troubleshooting Instructions

Installation, Service, and Troubleshooting Instructions 33CS TEMP System Unitary Controller Thermostat Installation, Service, and Troubleshooting Instructions Page GENERAL........................................ 2 TEMP System Components......................

More information

Comfort System T-21-P Touchscreen Thermostat Installation Manual

Comfort System T-21-P Touchscreen Thermostat Installation Manual Comfort System T-21-P Touchscreen Thermostat Installation Manual Version 1.40 INTRODUCTION The Comfort System T-21-P is a feature-rich touchscreen thermostat that can be battery powered or hardwired to

More information

Installation and Setup Guide

Installation and Setup Guide Installation and Setup Guide Color Touchscreen Programmable Commercial Thermostat ComfortSense 7500 Model: C0STAT06FF1L Cat: 13H15 507506-01 3/2016 Supersedes 10/2015 Table of Contents Shipping and Packing

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTLLTION INSTRUTIONS LOW VOLTE ONTROL IRUIT WIRIN W** W**D W*S W*S Models: W**L WL*S Bard Manufacturing ompany, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual No.: 00-507L Supersedes: 00-507K Date: -5-7

More information

Fan Coil Unit (FCU) Application Guide

Fan Coil Unit (FCU) Application Guide Fan Coil Unit (FCU) Series Room Controllers TABLE OF CONTENTS and SCs Fan coil terminal equipment controllers 2 A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves

More information

CONTROLS THERMOSTATS Bulletin No November 2001 Supersedes September 2001 INNOVATOR PROGRAMMABLE THERMOSTATS ENGINEERING DATA

CONTROLS THERMOSTATS Bulletin No November 2001 Supersedes September 2001 INNOVATOR PROGRAMMABLE THERMOSTATS ENGINEERING DATA ENGINEERING DATA CONTROLS THERMOSTATS Bulletin No. 210125 November 2001 Supersedes September 2001 INNOVATOR PROGRAMMABLE THERMOSTATS L21 SERIES THERMOSTATS HEAT/COOL SYSTEMS Features (All Models): Extra

More information

User s Manual

User s Manual 997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8620 Thermostat with Event-Based Air leaning and Humidity or Ventilation ontrol Safety & Installation Instructions READ AND SAVE THESE INSTRUTIS Table of contents Installation Installation location

More information

LOW VOLTAGE CONTROL CIRCUIT WIRING

LOW VOLTAGE CONTROL CIRCUIT WIRING INSTALLATION INSTRUTIONS LOW VOLTAGE ONTROL IRUIT WIRING W**A W**AD WA*S* MODELS W**L WL*S* Bard Manufacturing ompany, Inc. Bryan, Ohio 506 Since 9...Moving ahead just as planned. Manual : 00-58 Supersedes:

More information

WHITE-RODGERS COMFORT-SET 90 SERIES

WHITE-RODGERS COMFORT-SET 90 SERIES INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE/HEAT PUMP INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise

More information

SmartZone TM System Manual

SmartZone TM System Manual SmartZone TM System Manual Rev C3 June 1, 2007 Page 0 of 21 Table of Contents SmartZone TM System Manual Rev C3. April 23, 2007 Introduction..2 o Why Use Residential Zoning?..2 Architectural Challenges...

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

TP-Z-955W VIVE Comfort 1111 S. Glenstone Ave., Suite Springfield, MO 65804

TP-Z-955W VIVE Comfort 1111 S. Glenstone Ave., Suite Springfield, MO 65804 INSTALLATION MANUAL OM F O R T TP-Z-955W VIVE omfort S. lenstone Ave., Suite -00 Springfield, MO 65804 Thermostat Applications uide Description as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP with HUMIDITY CONTROL Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd &

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Conventional and Heat Pump Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE READ ALL

More information

Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems

Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems PRODUCT SPECIFICATIONS ZONING IHARMONY Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems Bulletin No. 20663 November 207 Supersedes August 205 COMPONENTS AND EQUIPMENT

More information

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction. Introduction The UL listed Phone-A-Stat (model # 7632 ) is designed and approved for the safe operation of remotely controlling four independent loads, such as a sprinkler system or a water heater via

More information

RC-2000 Thermostat Installation Instructions

RC-2000 Thermostat Installation Instructions RC-2000 Thermostat Installation Instructions DESCRIPTION The RC-2000 is a precision digital thermostat designed for 24 VAC heating and cooling systems. The RC-2000 will support the following systems: Single

More information

Install guide Caution ENGLISH

Install guide Caution ENGLISH OOL OFF HET Install guide 606 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the appliance befe installing servicing thermostat any part of the system. Do

More information

INTRODUCTION Thank you for purchasing your new Comfort-Set 90 Series thermostat. Your new White-Rodgers Thermostat uses solid state microcomputer

INTRODUCTION Thank you for purchasing your new Comfort-Set 90 Series thermostat. Your new White-Rodgers Thermostat uses solid state microcomputer INTRODUCTI Thank you for purchasing your new Comfort-Set 90 Series thermostat. Your new White-Rodgers Thermostat uses solid state microcomputer technology to provide precise time/temperature control. This

More information

RCS Residential Control Systems Inc.

RCS Residential Control Systems Inc. RCS Residential Control Systems Inc. Model TZ16 Z-Wave Communicating Thermostat with Rev P HVAC Control Unit INSTALLATION AND OPERATION MANUAL DCN: 141-00882 Rev 02 5/18/06 This manual applies to the following

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS CONTROLLER INSTALLATION, OPERATION & QUICK START GUIDE Bard CompleteStat TM CS9B-THO CS9B-THOC Models: CS9BE-THO CS9BE-THOC Bard Manufacturing Company, Inc. Bryan, Ohio 43506

More information

INSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS

INSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS R INSTALLATI/OPERATING INSTRUTIS SEQUENING PANELS SEQ-6, SEQ-6P and SEQ-12 Panels to Sequence up to 12 Individual Stages with Lead-Lag and Manual Override apabilities TENTS SEQ FUNTI HART... 2 DIP SWITH

More information

Product Instructions. Viega Programmable Heat/Cool Thermostat. Technical data

Product Instructions. Viega Programmable Heat/Cool Thermostat. Technical data Programmable Heat/ool Thermostat The programmable heat/cool thermostat is easy to install, easy to wire, and easy to program. It can be used for single stage heating and cooling applications, making it

More information

Installation, Operation, and Troubleshooting Instructions

Installation, Operation, and Troubleshooting Instructions Installation, Operation, and Troubleshooting Instructions 48/50HJ004-024 48/50TJ004-028 Apollo Control GENERAL The Apollo control is a relay pack which is factory wired and mounted in the Carrier rooftop

More information

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions - Brochure tekmarnet 4 Thermostat 542 D 542 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring

More information

Z24 Wireless Zone Controller Professional Installation Guide

Z24 Wireless Zone Controller Professional Installation Guide Pelican Wireless Systems Pelican Wireless Systems Wireless Zone ontroller Professional Installation Guide Pelican Wireless Systems, 2655 ollier anyon Rd. Livermore, A 94551 Phone: 888.512.0490 Email: support@pelicanwireless.com

More information

Model CZ-4. Installation and Operating Instructions. FORM White-Rodgers by Permission B

Model CZ-4. Installation and Operating Instructions. FORM White-Rodgers by Permission B Model Z-4 Installation and Operating Instructions FOM 2045-2 1306 2013 White-odgers by Permission 37-6864B Z-4 ZONIN SSTM FATUS Purge Override Button Adjustable Second Stage Timer System Mode Indicator

More information

Safety & Installation Instructions

Safety & Installation Instructions Premium Programmable Thermostat Safety & Installation Instructions Model 8570 READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PAGE SPECIFICATIONS............................. 1 WIRE REQUIREMENTS.........................

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Heat Pump or 2 Heat / 2 Cool Conventional Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE

More information

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE DM2 Digital Heat Pump Controller Rev: 3 November 2017 DM2 Overview 3 Physical Dimensions and Layout 4 Layout and Connections 5 Field Selectable Inputs 6 Safety Features 8 Unit Operation Description 10

More information

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS VENSTAR FAN COIL THERMOSTAT FAN COIL THERMOSTAT T1075 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS 3 Occupied, 1 Unoccupied Override capable 3 speed fan control Auto 2-pipe changeover when used with accessory

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T905. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T905. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T905 Thermostat Applications uide Description as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

7-Day. Digital Thermostat. residential. & 2-cool

7-Day. Digital Thermostat. residential. & 2-cool Digital Thermostat residential THERMOSTAT T1100FS 7-Day PROGRAMMABLE up to 2-heat & 2-cool PUMP Control up to 2 Heat & 2 Cool Stages 7-Day Programmable 4 Settings/Day Auto Changeover 5 minute Built-In

More information

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents Table of Contents DXM CONTROLS DXM Electronic Controls Features Comparison 2 DXM Electronic Heat Pump Controls 3 DXM Physical Dimensions & Layout 4 DXM Controls 5 DXM Service & Application Notes 13 Troubleshooting

More information

Wiring: All wiring should be conventional 18 gauge thermostat wire. Thermostats and zone dampers may be located up to 300 feet from the Z-300 panel.

Wiring: All wiring should be conventional 18 gauge thermostat wire. Thermostats and zone dampers may be located up to 300 feet from the Z-300 panel. THE EEN Z NE Z EE THE NE N Sequence of Operation: The reen Zone Z-300-HPS is a residential / light commercial zone control system that allows a single HVA unit to have up to three separate zones. Each

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

(-)HC-TST213UNMS 5/1/1 Day 5/2 Day Non-Programmable. Yes

(-)HC-TST213UNMS 5/1/1 Day 5/2 Day Non-Programmable. Yes Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. Universal Thermostat

More information

INSTALLATION, OPERATION & QUICK START GUIDE

INSTALLATION, OPERATION & QUICK START GUIDE INSTALLATION, OPERATION & QUICK START GUIDE Controller CS9B-THOA CS9B-THOCA Models: CS9BE-THOA CS9BE-THOCA Bard Manufacturing Company, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual: 00-684 Supersedes:

More information

Installation Guide ProR221J, ProR212J, ProR321J and ProR312J

Installation Guide ProR221J, ProR212J, ProR321J and ProR312J ProZone I n t e l l i g e n t Z o n i n g Zones See table below. ompatible Equipment All panels operate with gas/electric systems, conventional heat pumps and dual fuel heat pumps. Equipment Selection

More information

1 For All Programmable Digital Thermostat

1 For All Programmable Digital Thermostat OWNER'S MANUAL P/N P374-2300FM 1 For All Programmable Digital Thermostat Am OFF OVERRIDE Meets California Title 24 unts flush to the wall 7 Day Programmable 3 Occupied, 1 Unoccupied Auto-Changeover Large,

More information

WARNING Important Safety Information

WARNING Important Safety Information Premier Series Programmable Thermostats MODEL 5200 1 2 3 4 5 Specifications Installation Programming Installer Settings Testing Your New Thermostat Programming User Settings WARNING Important Safety Information

More information

Installation Instructions

Installation Instructions T2 -PAC01 -A, T2 -NAC01 -A T2 -PHP01 -A, T2 -NHP01 -A LEGACYt SERIES THERMOSTATS Installation Instructions A07047 Legacy Series Programmable Thermostat A07046 Legacy Series Non-Programmable Thermostat

More information

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat.

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat. Peak Partners Web-Programmable Thermostat Homeowner s Manual Look inside for a complete guide to the setup and operation of your new thermostat. Table of Contents Step 1: Getting Started...4-6 A. Thermostat

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers. CXM/DXM CXM/DXM Digital Heat Pump Controllers Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05 Table of Contents CXM / DXM Control Features Comparison 2 Part I - CXM Control

More information

Installation, Start-Up, and Operating Instructions

Installation, Start-Up, and Operating Instructions Installation, Start-Up, and Operating Instructions IMPORTANT: Read entire instructions before starting the installation. SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully. Follow

More information

RS332N BUTTON OPERATION INTRODUCTION. Installation and Operation Instructions for REMOVING THE THERMOSTAT FROM THE BACKPLATE

RS332N BUTTON OPERATION INTRODUCTION. Installation and Operation Instructions for REMOVING THE THERMOSTAT FROM THE BACKPLATE Installation and Operation Instructions for RS332N 3-Heat / 2-Cool Non-Programmable Setback Thermostat with the Industry s Most Advanced Remote Sensor Bus for Gas, Electric, & Heat Pump Systems www.robertshawclimate.com

More information

Networkable Fan Coil Controller Specification and Installation Instructions

Networkable Fan Coil Controller Specification and Installation Instructions Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T805. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T805. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T805 Thermostat Applications uide Des cription as or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

Smart thermostat with Humidification/De-humidification control

Smart thermostat with Humidification/De-humidification control x Smart thermostat with Humidification/De-humidification control Enter/Confirm Scroll Right = Increase Left = Decrease Back/Cancel TABLE OF CONTENTS Everyday Use 1. Adjusting Temperature...3 2. Adjusting

More information

USER MANUAL MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat

USER MANUAL MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat WARNING! Important Safety Information Builder MODEL 2200 Series 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat USER MANUAL Compatible with low voltage multi stage heat/cool

More information

FP EZ4F 4 Zone Controller

FP EZ4F 4 Zone Controller 4 Zone Controller READ THIS GUIDE BEFORE INSTALLING CONTROLLER Zone Controller Installa on and Start up Guide Rev 20170801 Ver 16 Input Ra ngs: Voltage: 18 40 VAC 50/60 HZ transformer of 40 VA or more

More information

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins Table of Contents Parts Diagram........................................................... 1 Icon Descriptions......................................................... 2 Specifications...........................................................

More information

NCU Mounting Details

NCU Mounting Details Revision Date December 4, 2013 RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units Installation and Operation Instructions Dimensions in mm Power Control Unit Display Control Unit

More information

- Data Brochure tekmarnet 4 Thermostat 542e

- Data Brochure tekmarnet 4 Thermostat 542e - Data Brochure tekmarnet 4 Thermostat 542e D 542e 03/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in

More information

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS VENSTAR FAN COIL THERMOSTAT FAN COIL THERMOSTAT T1070 NON- PROGRAMMABLE 2 OR 4 PIPE SYSTEMS Remote sensor ready 3 speed fan control Self-prompting adjustment Auto 2-pipe changeover when used with ACC-SENFC

More information

Control Equipment PTC PTC. modulating wall thermostat. NEP04/

Control Equipment PTC PTC. modulating wall thermostat. NEP04/ modulating wall thermostat NEP04/03 www.hvaquik.om 877-711-4822 PAGE 1 speifiations: power input: power onsumption: signal outputs: output impedane: ambient temp: setpoint range: deadband: proportional

More information

CONTROL UNIT FOR UNDERFLOOR HEATING SYSTEMS

CONTROL UNIT FOR UNDERFLOOR HEATING SYSTEMS ST.04.04.00 ONTROL UNIT FOR UNERFLOOR HETING SYSTEMS Low temperature control unit Low+high temperature control unit 1. ONTROL UNIT PPLITION The FR control unit is suitable for systems combining both high

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION. Premier Series

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION. Premier Series Premier Series MODEL 5000 USER MANUAL 5-2 Day Programmable Single Stage Heat/Cool Digital Thermostat Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including

More information

Premier 2-Zone Controller model Installer Guide

Premier 2-Zone Controller model Installer Guide Premier 2-Zone ontroller model 140202 Installer uide ONTENTS 1 Specifications 4 onfiguration 2 Suitable Mounting Locations 5 System heckout 3 Wiring Diagrams 6 Operation Warning Read all of the instructions

More information

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions DESCRIPTION The RC-90 is a precision digital thermostat designed for 24 VAC single stage heating and

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F81-51 Programmable Electronic Digital Multi-stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Installation, Service, and Troubleshooting Instructions

Installation, Service, and Troubleshooting Instructions Installation, Service, and Troubleshooting Instructions GENERAL...2 INSTALLATION...2-11 Thermostat Placement...2 Wiring Requirements...2 VVT Relay Packs...4 Wiring Connections for Monitor Thermostat...4

More information

EL-TSTAT-8820 Safety & Installation Instructions

EL-TSTAT-8820 Safety & Installation Instructions EL-TSTAT-8820 Safety & Installation Instructions TABLE OF CONTENTS WI-FI SETUP Wi-Fi Setup 2 INSTALLATION Installation location recommendations 3 Outdoor temperature sensor (included) 3 Remote temperature

More information

Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0

Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0 Comfort System HG-122 Universal Thermostat Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0 More Ah ha! Less Uhhh? For easy to follow programming instructions visit: www.heatinggreen.com/thermostatinstructions-wiring-diagrams/

More information

TH146-P-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.

TH146-P-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1. TH146-P-2H1C Installation Guide Programmable 2H1C Controller Removable Connector * Removable Connector * TH146-P User Console CT280-2H1C Control Module AC144-03 Outdoor Temperature Sensor * To remove a

More information

Installation Manual for Hot Yoga Studio Electric Radiant Heating

Installation Manual for Hot Yoga Studio Electric Radiant Heating 105 Comfort System HG-122 Universal Thermostat Installation Manual for Hot Yoga Studio Electric Radiant Heating Version 3.0 More Ah ha! Less Uhhh? For easy to follow programming instructions visit: www.heatinggreen.com/thermostatinstructions-wiring-diagrams/

More information

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M Litho U.S.A. 26 L SERIES UNITS 55,191M 4/26 Supersedes 54,98M M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL USED IN L SERIES AND S CLASS 3 THROUGH

More information

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only Marvel S MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED For Reference Only ***Interactive PDF*** Contents General Purpose...3 Standard And

More information

WARNING Important Safety Information

WARNING Important Safety Information Premier Series Programmable Thermostats MODEL 5000 1 2 3 Specifications Installation Testing Your New Thermostat Programming User Settings WARNING Important Safety Information Additional Operation Features

More information

Digi-Zone Model MDP3 Ver.04

Digi-Zone Model MDP3 Ver.04 Digi-Zone Model MDP3 Ver.04 Installation and Operating Instructions Controlling Your Comfort Room By Room System Indicator LEDs MDP3 Panel Features Power Indicator LED Leaving & Outdoor Air Sensors Zone

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F72 5/2 Day Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information