MODBUS / BACnet Adapter Installation Instructions

Size: px
Start display at page:

Download "MODBUS / BACnet Adapter Installation Instructions"

Transcription

1 MODBUS / BACnet Adapter Installation Instructions Part # 7350P-636 For Use with BIC-928 Control Based EnduroTI and Elite Premier Boilers BIC-926 Control Based Modcon, Modcon VWH, Pioneer, and Versa Flame Products Manufactured On or After July 1, 2011, and BIC-926 Control Based Elite, Elite VWH, and Phoenix Water Heaters Manufactured On or After August 1, 2011 STOP! Follow these instructions or warranty will be void! This manual must only be used by a qualified heating installer / service technician. Read all instructions in this manual before installing. Failure to comply could result in property damage or improper appliance operation. Such damages or service calls to correct operation ARE NOT covered by warranty. The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important product information. CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage. NOTE: Contains additional information important to a procedure. Foreword This manual provides guidelines for the use and installation of the MODBUS/BACnet communication system with HTP appliances. For the Installer The installer should be guided by the instructions furnished with the MODBUS/BACnet, local codes and utility company requirements. Preference should be given to codes and requirements where they differ from the furnished instructions. Additional publications which should guide the installer include: 1. The latest version of the National Electrical Code, NFPA No. 70. In Canada, refer to Canadian Electrical Code C 22.1, from Canadian 2. Standards Association, 5060 Spectrum Way, Suite 100, Mississauga, Ontario, Canada L4W 5N6. 3. Local, state, provincial, and national codes, laws, regulations, and ordinances. Table of Contents Part 1 - General Information 2 A. What s in the Box 2 B. Minimum System Requirements 2 C. Definitions 2 Part 2 - Installation 2 A. BMS Wiring Requirements 3 B. Jumper Setting 3 Part 3 - Communication Configuration 4 A. MODBUS/BACnet Enable 4 B. MODBUS Address 4 C. BACnet Address 4 D. Baud Rate 5 E. Parity and Stop Bits 5 Part 4 - MODBUS Registers and BACnet Objects 5 A. Primary Data Tables 5 B. Appliance Memory Map 6 C. Configuration Bits 8 Part 5 - Appliance Operation 9 A. Appliance Operation with MODBUS and BACnet Communications 9 B. Example #1 - Enable / Disable CH and DHW Demand 9 C. Example #2 - Sending DHW Setpoint Via Direct Write Method 9 D. Example #3 - Sending Setpoint or Firing Rate from BMS 9 1. Sending Desired Setpoint from BMS to Appliance Via Simulated 0-10V Method 9 2. Send Firing Rate Command from BMS to Appliance 10 E. Example #4 - Hot Water Generation 11 F. Cascade 11 G. Temperature Conversions (MODBUS Only) 11 Part 6 - Troubleshooting 12 A. MODBUS/BACnet Board Diagnostics 12 B. Physical Layer 12 C. Communications 12 D. Error Codes 13 E. Appliance 0-7 Status Codes 13 F. Appliance 0 and Appliance 1 Blocking Codes 13 G. Appliance 0-7 Lockout Codes 14 Limited Warranty 15 Installation and Maintenance Notes 16 The manufacturer reserves the right to make changes or updates without notice and will not be held liable for errors in literature. NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE. 272 Duchaine Blvd. New Bedford, MA

2 2 Part 1 - General Information This adapter is capable of supporting either the MODBUS or BACnet protocols. The protocol selection is accomplished via dipswitch 10. MODBUS and BACnet communication systems utilize a master-follower format where connected HTP appliances follow commands from a building management system or other MODBUS or BACnet master device linked over an RS-485 serial connection. CAUTION If any system components are exposed to the following, do not operate until the affected components have been inspected by a qualified serviceman. 1. FIRE 2. DAMAGE 3. SUBMERSION IN WATER Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee. A. What s in the Box One (1) MODBUS / BACnet Adapter One (1) Bag of Mounting Hardware One (1) Mounting Template Ensure all components are included in the shipping crate. Move components to the installation location. Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee. B. Minimum System Requirements 1. A MODBUS or BACnet master device, such as a Building Management System (BMS) or computer with MODBUS or BACnet master software, and an RS-485 serial port or USB port with a converter to RS HTP MODBUS/BACnet adapter (this kit), and an HTP appliance/ water heater equipped with a BIC-926 control with firmware revision MTSA-P or greater. To determine whether your BIC- Figure 1 - BIC-926 Controller Revision Label Location 926 based product is compatible with this adapter, refer to Figure This MODBUS/BACnet adapter is also designed to work on the new BIC-928 control. There are no firmware limitations with this new control. 4. Shielded twisted pair communication cable. C. Definitions Table 1 includes a list of definitions used throughout this manual. Abbreviation or Acronym ASCII BACnet Baud (Baud Rate) BMS EMS FDX HDX Hex I/O LSB MODBUS MSB RS232 RS485 RTU PG MB American Standard Code for Information Interchange Definition BACnet is a communications protocol for Building Management and Control networks. It is an ASHRAE, ANSI, and ISO standard protocol. Number of data bits transmitted per second (bps) Building Management System Energy Management System Full-Duplex Half-Duplex Hexadecimal Number (0-9, A-F) Input/Output Least Significant Byte A serial, half-duplex transmission protocol developed by AEG Modicon Most Significant Byte RS232 serial, full-duplex (FDX) transmission of data standard RS485 serial transmission of data standard Remote Terminal Unit Industry Standard liquid-tight wiring entry connector MODBUS Table 1 - Definitions Part 2 - Installation The MODBUS/BACnet adapter should be mounted to a solid surface. The adapter has two tabs with four mounting holes designed specifically for this purpose.

3 CAUTION Use the mounting template and screws provided with the adapter. Damage to the MODBUS/BACnet adapter or appliance due to installation with other mounting screws IS NOT covered by warranty. When mounting the unit, keep in mind that the top cover must be removed to connect the RS-485 communication cable, and that the appliance communication wire must reach the control inside the appliance. The MODBUS/BACnet adapter can be mounted on the side of the appliance OR the wall next to the appliance, as long as care is taken to avoid components behind the mounting surface. The mounting location must be within 3 feet of the appliance controller in order to be plugged into the controller input port. In BIC-926 based appliances, the four pin connector from the adapter must be plugged into the white connector labeled X3 on the control. In BIC-928 based appliances, the four pin connector from the adapter must be plugged into the black connector labeled X4 on the control. NOTE: It is not recommended to install the MODBUS/BACnet adapter inside the appliance housing. Doing so may affect appliance operation or damage the MODBUS/BACnet adapter. CAUTION Damage to MODBUS/BACnet adapter or appliance due to improper installation IS NOT covered by warranty. 3 A. BMS Wiring Requirements RS-485 Communication Bus Maximum length: 4000 feet Cable specification: 24 AWG / A,B (twisted pair) and GND shielded, with characteristic impedance: 120 ohm Maximum load: 32 units (32 nodes) Wires will be passed through the PG connector on the side of the adapter, then connected to the three position connector marked X5 on the circuit board inside the adapter. A label is provided inside the adapter to ensure proper connections of A, B, and GND. Two wires (MB IN and MB OUT) may be attached to each X5 screw. See Figure 2 for an example wiring diagram. Figure 2 - Jumper Configurations in a MODBUS / BACnet Network B. Jumper Setting The appliance display handles most of the MODBUS/BACnet adapter configuration. There is one jumper on the MODBUS/BACnet adapter. When this jumper is in place (factory default) it connects a termination resistor across the data lines of the RS-485 connection. Leave the jumper in if the MODBUS/BACnet adapter is at the end of the RS- 485 bus. Remove the jumper if the MODBUS/BACnet adapter is one of many connections and not at the end of the bus. See Figures 2 and 3. Figure 3 - MODBUS Termination Jumper Location (Highlighted in Grey)

4 4 Part 3 - Communication Configuration A. MODBUS/BACnet Enable In order to enable either MODBUS or BACnet, push dipswitch 10 into the ON position to enable BAC, and the OFF position to enable MODBUS. See the dipswitch matrix below for a detailed description. Final Baud Rate Protocol x4 BACNET OFF OFF OFF OFF OFF OFF OFF OFF x1 MODBUS Table 2 - Dipswitch Matrix LCD Display: 1. On the LCD display press and hold ENTER until you see the screen at the right. 2. Use the RIGHT arrow to select a character, then use the UP and DOWN arrows to select the desired Parameter 3 Character LED Display Setting LCD Text Display Setting Description ENTER MENU CODE 925 character value. RIGHT arrow over to the next character and repeat the selection. Once code 925 or 975 is on the screen (Installer Menu code depends on the appliance - See appliance Installation Manual for details), press and hold ENTER on the display to enter the Installer Menu. 3. Once in the Installer Menu, use the RIGHT or LEFT arrow to navigate to Parameter 37-MODBUS MODE. When at Parameter 37, press ENTER, then use UP or DOWN to select the desired setting from Table Press ENTER to store the MODBUS Configuration. Press the RIGHT button to advance to Parameter 38 - Address. LED Display: 1. On the LED display, press and hold TEMP and RESET simultaneously. Use the + and - arrows to show 925 on the display, then press and hold TEMP to enter the installer menu. 2. Once in the Installer Menu, use the TEMP button to navigate to Parameter 37. When at Parameter 37, use + or - to select the desired setting from Table Press the TEMP button to advance to Parameter 38 - Address OFF MODBUS/BACnet DISABLED (factory default) 37 1 AUTOMATIC MODBUS/BACnet AUTO (enables automatic detection of a PC or Adapter) 37 2 ON MODBUS/BACnet ON Table 3 - MODBUS MODE Settings Please do not leave the Installer Menu after making this selection. Continue to configure the Address, Baud Rate, and Parity settings. B. MODBUS Address NOTE: MODBUS must be enabled on the appliance as outlined above for the following parameters to be viewed and changed. The MODBUS address space is comprised of 256 addresses. These are defined as follows: Address 0 is a broadcast address. The master can send data to address 0 and all followers will process the data. Addresses are free to be assigned to MODBUS devices on the bus. Each address can be assigned to only one MODBUS device on the bus. Addresses are not available for use. C. BACnet Address BACnet Device Instance The unique BACnet Device instance number will consist of three (3) parts: Base Number: Family: BIC BIC The local address will be set by the MODBUS menu on the BIC. This address is the same as the address on the RS485 bus. Example: A BIC928 with the RS485 address of 65 will have a device ID of A BIC926 with the RS485 address of 31 will have a device ID of NOTE: MODBUS must be enabled on the appliance as outlined above for the following parameters to be viewed and changed. The BACnet address space is comprised of 256 addresses. These are defined as follows: Address 255 is a broadcast address. The master can send data to address 0 and all followers will process the data. Addresses are free to be assigned to both Master and Follower BACnet nodes. Each address can be assigned to only one BACnet device on the bus. Addresses are valid only for Follower nodes. ADDRESSING SUGGESTIONS* Each device must have a unique address. In order to keep track of addresses for future maintenance purposes, record all device addresses in the Installation and Maintenance Notes section included in this manual. *SAVE THIS DOCUMENT IN A SECURE LOCATION FOR FUTURE REFERENCE. To set the MODBUS/BACnet adapter address in the appliance installer menu: LCD Display: 1. When at Parameter 38, press ENTER, then use UP or DOWN to select the desired address. 2. Press ENTER to store the MODBUS Address. 3. Press the RIGHT button to advance to Parameter 39 Baud Rate.

5 5 LED Display: 1. When at Parameter 38, press TEMP, then use + or - to select the desired address. 2. Press the TEMP button to advance to Parameter 39 Baud Rate. D. Baud Rate The baud rate (communication speed) can be set on the control display to either 9600 or baud. All HTP appliances, as well as any other device on the same bus and the MODBUS/BACnet master, must have the same baud rate setting. Select the highest baud rate that offers the most reliable communication performance over the bus. Some things that can affect communications are: Long wire runs Wire quality A noisy electrical environment The number of devices on the bus. These conditions may require using a lower baud rate. LCD Display: 1. When at Parameter 39, press ENTER, then use UP or DOWN to select the desired setting from Table Press ENTER to store the Baud Rate. 3. Press the RIGHT button to advance to Parameter 40 Parity. LED Display: 1. When at Parameter 39, press TEMP, then use + or - to select the desired setting from Table Press the TEMP button to advance to Parameter 40 Parity. Parameter 3 Character LED Display Setting LCD Text Display Setting Description BAUD RATE = 9600 (factory default) BAUD RATE = Table 4 - Parameter 39 Settings The final (RS-485) baud rate is determined by this setting in Control Baud Rate Setting Dipswitch 9 Position Final RS-485 Baud Rate conjunction with dipswitch 9 on the adapter. Table 5 shows all possible final baud rate selections OFF OFF E. Parity and Stop Bits 9600 ON (9600 X 4) NOTE: This setting only applies to MODBUS operation. The BACnet protocol does not utilize parity for communication and ON (19200 X 4) this setting will have no effect. Table 5 - Final Baud Rate Settings The parity/stop bits parameter of the MODBUS/BACnet adapter must be set to match the rest of the devices on the bus. Although it is common to set serial devices to use no parity, setting the parity to even or odd may improve communications reliability on all connected devices on the bus. This parameter has 4 possible selections which should be sufficient to establish communication with other devices. These selections are outlined in Table 6. LCD Display: 1. When at Parameter 40, press ENTER, then use UP or DOWN to select the desired setting from the table below. 2. Press ENTER to store the Parity. 3. Press and Hold the RESET button to store all parameters and exit the Installer Menu. LED Display: 1. When at Parameter 40, press TEMP, then use + or - to select the desired setting from Table Press and Hold the RESET button to store all parameters and exit the Installer Menu. Part 4 - MODBUS Registers and BACnet Objects A. Primary Data Tables Parameter 3 Character LED Display Setting LCD Text Display Setting Description ST No parity 1 stop bit (factory default) ST No parity 2 stop bits 40 2 E PA Even parity 1 stop bit 40 3 O PA Odd parity 1 stop bit Table 6 - Parameter 40 Settings Table Data Type Read / Write Description Discrete Inputs Single bit Read only Data can be provided by an I/O system. Coils Single bit Read / Write Data can be altered by an application program. Input Registers 16-bit word Read only Data can be provided by an I/O system. Holding Registers 16-bit word Read / Write Data can be altered by an application program. Table 7 - Supplementary Information

6 6 B. Appliance Memory Map NOTE: BOLD ITALICS indicate objects that apply only to appliances equipped with BIC-928 operating systems. MODBUS Heating Appliance Water Heater BACNET Address Description Description Object Type Object Instance Unit Resolution Discrete Inputs Discrete Inputs En / Room Th1 / Stg 1 N/A BV 0 1 = on, 0 = off Tank thermostat N/A BV 4 1 = on, 0 = off MHRL High temp safety switch / High flue temp switch BI 0 1 = on, 0 = off Flow switch N/A BI 1 1 = on, 0 = off Gas Press. Switch N/A BI 2 1 = on, 0 = off Air Press Switch N/A BI 4 1 = on, 0 = off Blocked drain Blocked vent pressure switch BI 5 1 = on, 0 = off ARHL High temp safety switch / High flue temp switch BI 6 1 = on, 0 = off Flame 1 Flame rectification probe BI 7 1 = on, 0 = off Enable / STG1 N/A BI 8 1 = on, 0 = off Tank th N/A BI 9 1 = on, 0 = off STG2 / APS N/A BI 10 1 = on, 0 = off Run-time cont. 1 Run-time cont. 1 BI 32 1 = on, 0 = off Alarm cont. 1 (EXCEPT Versa Hydro) Alarm output BI 33 1 = on, 0 = off CH pump 1 N/A BI 34 1 = on, 0 = off DHW pump 1 N/A BI 35 1 = on, 0 = off Gas valve 1 Gas valve BI 37 1 = on, 0 = off Sys pump N/A BI 38 1 = on, 0 = off Boiler 1 Run (same as 11118) Boiler 2 Run (same as 10023) Run status BI 48 1 = on, 0 = off 1 N/A BI 49 1 = on, 0 = off Boiler 3 Run N/A BI 50 1 = on, 0 = off Boiler 4 Run N/A BI 51 1 = on, 0 = off Boiler 5 Run N/A BI 52 1 = on, 0 = off Boiler 6 Run N/A BI 53 1 = on, 0 = off Boiler 7 Run N/A BI 54 1 = on, 0 = off Boiler 8 Run N/A BI 55 1 = on, 0 = off Lockout 1 (same as 10034) Lockout 2 (same as 10042) Lockout Status BI 56 1 = on, 0 = off 1 N/A BI 57 1 = on, 0 = off Lockout 3 N/A BI 58 1 = on, 0 = off Lockout 4 N/A BI 59 1 = on, 0 = off Lockout 5 N/A BI 60 1 = on, 0 = off Lockout 6 N/A BI 61 1 = on, 0 = off Lockout 7 N/A BI 62 1 = on, 0 = off Lockout 8 N/A BI 63 1 = on, 0 = off Alarm relais ecs (Versa Hydro ONLY) Input Registers Input Registers BI 64 1 = on, 0 = off Discrete Inputs 1-16 N/A AI 0 N/A Discrete Inputs N/A AI 1 N/A Discrete Inputs N/A AI 2 N/A *System / Cascade Setp. N/A AI 3 Deg F, Off =

7 7 MODBUS Heating Appliance Water Heater BACNET Address Description Description Object Type Object Instance Unit Resolution Input Registers Input Registers System Pump 4 speed N/A AI 4 % Cascade Total Power N/A AI 5 % Cascade Current Power N/A AI 6 % *Outlet Setp. 1 N/A AI 7 Deg F, Off = Outlet Temp. 1 Upper Temp Sensor AI 8 Deg F Inlet Temp. 1 Lower Temp Sensor AI 9 Deg F Flue Temp. 1 N/A AI 10 Deg F Firing Rate 1 Firing Rate 1 AI 11 % Boil. 1 Pump speed 5 N/A AI 12 % Boil. 1 Status Code Status Code 1 AI 13 N/A Boil. 1 Blocking Code Blocking Code 1 AI 14 N/A Boil. 1 Lockout Code Lockout Code 1 AI 15 N/A Outlet Temp 2 N/A AI 17 Deg F Firing Rate 2 N/A AI 20 % Boil. 2 Pump 4 speed N/A AI 21 % Boil. 2 Status Code N/A AI 22 N/A Boil. 2 Blocking Code N/A AI 23 N/A Boil. 2 Lockout Code N/A AI 24 N/A Boiler Outlet 3 N/A AI 25 Deg F Boiler 3 Firing Rate N/A AI 26 % Boiler 3 Status N/A AI 27 N/A Boiler 3 Lockout N/A AI 28 N/A Boiler Outlet 4 N/A AI 29 Deg F Boiler 4 Firing Rate N/A AI 30 % Boiler 4 Status N/A AI 31 N/A Boiler 4 Lockout N/A AI 32 N/A Boiler Outlet 5 N/A AI 33 Deg F Boiler 5 Firing Rate N/A AI 34 % Boiler 5 Status N/A AI 35 N/A Boiler 5 Lockout N/A AI 36 N/A Boiler Outlet 6 N/A AI 37 Deg F Boiler 6 Firing Rate N/A AI 38 % Boiler 6 Status N/A AI 39 N/A Boiler 6 Lockout N/A AI 40 N/A Boiler Outlet 7 N/A AI 41 Deg F Boiler 7 Firing Rate N/A AI 42 % Boiler 7 Status N/A AI 43 N/A Boiler 7 Lockout N/A AI 44 N/A Boiler Outlet 8 N/A AI 45 Deg F Boiler 8 Firing Rate N/A AI 46 % Boiler 8 Status N/A AI 47 N/A Boiler 8 Lockout N/A AI 48 N/A Discrete Inputs N/A AI 49 N/A NTC 6 temperature N/A AI 50 Deg F NTC 7 temperature N/A AI 51 Deg F NTC 9 temperature N/A AI 52 Deg F Vortex 1 flow N/A AI 53 LPM Vortex 1 temp N/A AI 54 Deg F 0.1

8 8 MODBUS Heating Appliance Water Heater BACNET Address Description Description Object Type Object Instance Unit Resolution Input Registers Input Registers Vortex 2 flow N/A AI 55 LPM Vortex 2 temp N/A AI 56 Deg F Total Faults N/A AI Total Last Faults N/A AI Run Hours CH AI 92 x Run Hours DHW AI 93 x Run Hours Cas CH N/A AI 94 x Run Hours Cas DHW N/A AI 95 x Power Hours AI 96 x Start Counter AI Start Counter AI 99 1 Holding Registers Configuration Configuration AV 0 See 1 Configuration Coils Coils AV 1 Bits Section volt / rate / setp 0-10 volt / rate / set AV 2 V DHW setpoint DHW set AV 3 Deg F DHW temperatur DHW temp AV 4 Deg F Outdoor temp. Outdoor Sensor AV 5 Deg F Sys supply temp. N/A AV 6 Deg F Sys rtn temp. N/A AV 7 Deg F I4 for direct N/A AV 8 Deg F CH post purge N/A AV 9 Seconds DHW post purge N/A AV 10 Seconds Pump 4 Speed N/A AV 11 % Extra out ECS N/A AV 13 % 0.1 Table 8 - MODBUS and BACnet Memory Map - *Only Valid Valves During Heating Cycle C. Configuration Bits Address 40001/AV0 contains configuration bits sent from the BMS to the appliance. These bits tell the appliance to use its own internal inputs, or inputs from the BMS. When a bit is set to 1, the appliance will ignore the corresponding value contained internally and expect the BMS to write that value into the holding registers. The configuration bits are as follows: Holding Register / AV0 Decimal Value HEX Value Selected Signal (Register) to Write to 0 = Taken from Control 1 = Taken from MODBUS B0 (LSB) 1 01 Boiler enable (40002 / AV1) 0/1 B Tank enable (40002 / AV1) 0/1 B Rate command / 0-10V input / setpoint command (40003 / AV2) B DHW setpoint (40004 / AV3)* 0/1 Holding Register / AV0 Decimal Value HEX Value Selected Signal (Register) to Write to 0/1 0 = Taken from Control 1 = Taken from MODBUS B DHW temperature (40005 / AV4) 0/1 B Outdoor temperature (40006 / AV5) 0/1 B System supply temperature (40007 / AV6) 0/1 B System return temperature (40008 / AV7) 0/1 B I4 offset (40009 / AV8) 0/1 B CH post purge (40010 / AV9) 0/1 B DHW post purge (40011 / AV10) 0/1 B Pump 4 speed (40012 / AV11) 0/1 B Pump 5 speed (40013 / AV12) 0/1 B13 (MSB) Extra 0-10V output (40014 / AV13) 0/1

9 9 Holding Register / AV1 Selected Signal (Register) to Write to) Coil 01 b Room thermostat Coil 05 b Tank thermostat Table 9 - MODBUS Holding Registers *The appliance will not respond to the internal DHW limit while the Tank Temperature AND Tank Enable is being written from MODBUS/BACnet! Part 5 - Appliance Operation A. Appliance Operation with MODBUS and BACnet Communications The appliance is equipped with a communication timer. Timeout is set for four minutes. The purpose of the timer is to ensure proper temperature data is communicated to the appliance in a timely manner. Additionally, the communication timer will provide fail safe operation should communication be lost. This timer will cause the appliance to revert back to internal appliance controls should the communication be interrupted longer than the timer. The timer resets every time a write command is received with updated temperatures or commands. The master should update temperature registers at least once per minute, but no more than once per second. Monitoring Only Any appliance can be equipped with the MODBUS or BAC/net communication accessory and then be set up to operate with its own internal controls. The master can then poll the MODBUS or BAC/net accessory for the read only variables. Refer to the following examples for configuring the writable Holding Registers. B. Example #1 - Enable / Disable CH and DHW Demand In this configuration, the appliance is controlled by setting the setpoints locally on the appliance and providing an enable signal through MODBUS or BAC/net communications. All sensors and limiting devices (excluding the thermostat enable and tank thermostat enable signals, which will be sent to the appliance) should be hardwired to the proper terminals in the appliance. The holding registers need to be set as follows: Holding Registers Definition Decimal Value HEX Value Action / AV0 Configuration Set configuration to read / AV1 Coils Enables CH Demand (00 00 disables demand) (boilers only) / AV1 Coils Enables DHW demand on appliance (00 00 disables demand) / AV1 Coils Enables both CH and DHW demand. DHW demand will have priority. Table 10 - Example #1 C. Example #2 - Sending DHW Setpoint Via Direct Write Method Holding Registers Definition Decimal Value HEX Value Action / AV0 Configuration Set configuration to read 40004/AV / AV3 Coils Setpoint Setpoint Directly writes setpoint to water heater Table 12 - Example #2 *The appliance will not respond to the internal DHW limit while the Tank Setpoint is being written from MODBUS/BACnet! D. Example #3 - Sending Setpoint or Firing Rate from BMS 1. Sending Desired Setpoint from BMS to Appliance Via Simulated 0-10V Method In this configuration, the appliance setpoint is indirectly controlled by sending a 0 to 10v signal to it. All sensors and limiting devices (excluding the 0 10 Vdc signal, which will be sent to the MODBUS/BACnet Appliance Parameter I16 Parameter I17 adapter) should be hardwired to the correct locations on the Phoenix, Munchkin, MODCON rev2 and earlier 2 0 appliance. For this command to function, configure the appliance Elite, Elite Premier, EnduroTi 0-10 Volt Temperature according to the corresponding row in the table to the right. Table 11 - Send Desired Setpoint from BMS to Appliance To send a desired CH setpoint on an appliance, or DHW setpoint on a water heater via 40003/AV2, the value (which equates to voltage applied) must be determined through linear interpolation of programmable parameters on the BMS setup menu. Appliance temperature setpoint at low analog input = MIN BOILER TEMP (I12) in the 925 Installer Menu Appliance temperature setpoint at high analog input = CENTRAL HEAT in the 600 User Menu or PHOENIX in the User Menu These variables set the temperature values corresponding to the minimum and maximum voltage settings of the 0 10 volt signal. The defaults are as follows:

10 10 Parameter For example: Send a setpoint of 110 o F. The formula to use for the interpolation is: Voltage to be applied = (Desired setpoint BMS temp at low analog input) (High voltage low voltage) + Low voltage (BMS temp at high analog input BMS temp at low analog input) From the default values: Desired setpoint = 110 BMS temp at low analog input = 68 BMS temp at high analog input = 180 High voltage = 10 Low voltage = 1.6 [(110-68)(10-1.6)/(180-68)] = 4.75 volts (4.75/10) x 100 = = 30 Hexadecimal A value of [00] [30] in hexadecimal would be written to holding register 40003/AV2 to issue a command for a 110 o F setpoint. NOTE: If your particular BMS supports DECIMAL inputs, then the desired voltage level can be sent directly. In the above example, you would send 48 (4.8v) to 40003/AV2. The holding registers need to be set as follows: Holding Registers Definition Decimal Value HEX Value Action / AV0 Configuration 4 04 Set configuration to read / AV2 Setpoint Enables CH Demand (00 00 disables demand) Table 14 - Setting Holding Registers for Setpoint Register 40003/AV2 needs to receive the setpoint command as follows: Acceptable range is 0 to 100. Value needs to be greater than 15 for the appliance to fire. 10V When the command is 16, the appliance will run with the setpoint controlled by the 925 menu parameter I12 (MIN BOILER TEMP). When the command is 100 the appliance will run with the setpoint controlled by the 600 menu parameter CENTRAL HEAT on appliances or the PHOENIX setting in the water heater user menu. 1.5V If the command value is anywhere between 16 and 100, the appliance will run at a setpoint proportional to the command sent between minimum and maximum setpoints. NOTE: To ensure proper operation, resend the configuration bits to holding register / AV0 prior to issuing a command. Figure 4 - Setpoint Curve 2. Send Firing Rate Command from BMS to Appliance In this configuration, the appliance is controlled by setting the modulation from 0 100%. Rate command will be 0 100% of the modulation range. All sensors and limiting devices (excluding the 0 10 Vdc signal, which will be sent to the MODBUS/BACnet adapter) should be hardwired to the correct locations on the appliance. For this command to function, configure the appliance according to the corresponding row in the following table. Default Values Appliance Parameter I16 Parameter I17 Phoenix, Munchkin, MODCON rev2 and earlier 2 2 Elite, Elite Premier, EnduroTi 0-10 Volt Fan Speed Table 15 - Send Firing Rate from BMS to Appliance The holding registers need to be set as follows: Holding Registers Definition Decimal Value HEX Value Action / AV0 Configuration 4 04 Set configuration to read / AV2 Rate Command Sets Modulation % Table 16 - Setting Holding Registers for Firing Rate Default Deg C Deg F Voltages Appliance temperature setpoint at low analog input Appliance temperature setpoint at high analog input Table Volt Temperature Values for Setpoint

11 11 Register 40003/AV2 needs to receive the rate command as follows: Acceptable range is 0 to 100. Value needs to be greater than 15 for the appliance to fire. When the command is 16, the appliance will run at minimum fan speed (firing rate). When the command is 100 the appliance will run at max fan speed (firing rate) If the command value is anywhere between 16 and 100, the appliance will run at a fan speed proportional to the command sent between minimum and maximum firing rates. NOTE: To ensure proper operation, resend the configuration bits to holding register / AV0 prior to issuing a command. E. Example #4 - Hot Water Generation Hot water generation can be accomplished using one of two methods when an appliance is Figure 5 - Firing Rate Curve connected to a BMS system, DHW with direct control, and DHW with remote control. DHW with Direct Control This is the typical installation with a hot water generator in close proximity to the appliance with the tank thermostat, or tank temperature sensor, wired to the terminal strip or Customer Connection Board of the appliance. DHW with Remote Control This installation may or may not have the hot water generator in close proximity to the appliance. Its sensors and thermostat values are only available through the MODBUS communication bus. *The appliance will not respond to the internal DHW limit while the Tank Temperature AND Tank Enable is being written from MODBUS/BACnet! To ensure that the appliance can properly respond to a call for hot water generation, the following holding registers must be set in addition to other commands: Holding Registers Definition BACnet Decimal Value MODBUS Decimal Value HEX Value / AV0 Configuration A Set configuration to read 40002, 4 and / AV1 Coils Enables Tank Tstat (00 00 disables appliance) Action / AV3 Tank setpoint Sets setpoint to 130.0F Tank / AV Passes tank temp from remote sensor (ex: 150.5F) to tank temperature Table 17 - Example #3 NOTE: To ensure proper operation, resend the configuration bits to holding register 40001/AV0 prior to issuing a command. For proper hexadecimal conversion of rate percentage, please refer to the rate and temperature conversion section of this manual. F. Cascade In order to operate the appliance in cascade with MODBUS or BAC/net communications, configure the master appliance. Connect the remaining appliances in the cascade through the normal cascade communications wiring. Cascade control can then be accomplished automatically through the master appliance. NOTE: With MODBUS or BAC/net communication connected only to the master appliance, only total cascade information can be seen through the communications link. Information from the follower appliances is limited to follower appliance rate command, supply temperature, fault code, and fault status. If you want to see complete data from each follower, or use the master to control cascading of multiple appliances, each appliance will need a MODBUS or BAC/net communication board. If this is implemented, remember that each appliance will present its data as Appliance 1. You must then use the Appliance s address to determine which follower you are accessing. G. Temperature Conversions (MODBUS Only) The MODBUS adapter passes temperature data to the appliance in degrees Fahrenheit. Also, to accommodate decimal places, the decimal value must be divided by 10. In some BMS systems, the data sent over the MODBUS is passed as an unsigned 16-bit integer (16BIT UINT). This poses no problem unless the data becomes negative, such as temperatures below zero. In this case, the compliment has to be calculated as follows: Example for WRITING negative temperature values to the appliance: Temperature to be sent over MODBUS = -22 o F. First multiply by X 10 = Calculate compliment = Data to be sent is a decimal value of

12 12 Example for READING negative temperature values from the appliance: To read the outdoor temperature from the appliance, do the opposite. Read register 40006/AV5 and get Since this value is greater than 32767, the temperature is negative. To calculate the negative value: = 220, then 220/10 = X -1 = -22 o F. NOTE: If your particular BMS supports DECIMAL outputs, then the desired temperature can be read and written directly. More examples Sending positive outdoor temperature from remote sensor on BMS system to appliance (40006/AV5) = 80.5 o F Value 16BIT Unit BMS HEX BMS Signed Decimal BMS 80.5 F Table 18 - MODBUS Positive Outdoor Temperature Conversions Sending negative outdoor temperature from remote sensor on BMS system to appliance (40006/AV5) = -25 o F. Data that needs to be transmitted is: -25 X 10 = =65286 OR -250 if supported. Value 16BIT Unit BMS HEX BMS Signed Decimal BMS -25 F FF Table 19 - MODBUS Negative Outdoor Temperature Conversions Positive outlet temperature from System sensor connected to BMS to appliance (40007/AV6) = 155 o F. 155 o F x 10 = Value 16BIT Unit BMS HEX BMS Signed Decimal BMS 155 F E 1550 Table 20 - MODBUS Positive Outlet Temperature Conversions Part 6 - Troubleshooting Should you encounter problems communicating over MODBUS/BAC/net, the following items should be checked in this order. 1. Physical layer 2. Communications configuration and port settings 3. Error codes 4. Appliance status / blocking / lockout codes A. MODBUS/BACnet Board Diagnostics The MODBUS/BACnet board is equipped with three LEDs for visual diagnostics: Two yellow and one green. These LEDs are located under the MODBUS/BACnet cover. One yellow LED (D5) is used to indicate transmission of data. The other yellow LED (D6) is used to indicate reception of data. The green LED (D7) shows internal faults. See Figure 6 for LED locations. Internal Faults (Green LED): Normal Operation = 1 second on, 1 second dim Controller Fault = Continuously on No Burner Control Communication = 0.5 seconds on, 1.5 seconds off No MODBUS/BACnet Communication = 1.5 seconds on, 0.5 seconds off B. Physical Layer 1. Adapter and Serial Port a. Ensure adapter is plugged into the correct four pin connector i. It plugs into the WHITE connector on the BIC-926 control. ii. It plugs into the BLACK connector on the BIC-928 Figure 6 - MODBUS/BACnet Diagnostic LEDs control. b. Confirm dipswitch 10 is in the correct position for the desired protocol. c. Check for terminating resistors (120 ohms) at each end of the RS-485 bus only. 2. RS-485 a. Verify the correct MODBUS communication cable (twisted pair) is being used. b. Check A, B terminal connections and polarity c. Check for broken wires. d. Check all wire lengths. Are any drops too long? e. Check proper shield grounding. 3. Network Check that all components have power (appliance, MODBUS/BACnet adapter, gateway, BMS master). C. Communications 1. Verify controller is configured for MODBUS (AUTO or ON) 2. Confirm dipswitch 9 is in the correct position for the desired final baud rate. 3. Check baud rate (9600, 19200). 4. Check parity. 5. Check MODBUS/BACnet address.

13 13 6. Check port setting on master, gateway, and computers. 7. Check the status of the LEDs. Refer to Figure 6. D. Error Codes 1. Check MODBUS communication error codes below. 2. Check Follower ID. 3. Check MODBUS command. 4. Check configuration bits for holding register 40001/AV0. 5. Check commands and data for holding registers 40002/AV1 through 40007/AV6. NOTE: Use Status Codes, Blocking Codes and Lockout Codes to interpret remote appliance operating conditions. E. Appliance 0-7 Status Codes The appliance displays an appliance state code on the building screen to help aid in troubleshooting. The appliance state indicates what the appliance is actually doing. This state should be compared to the command issued and what is expected. If the appliance state does not agree with the command, check communication and configuration. Status Codes (Input Registers 30014, 30023, 30028, 30032, 30036, 30040, 30044, and Points AI13, 22, 26, 30, 34, 38, 42, and 46) Number Definition Number Definition Number Definition 0 Standby 16 Service 1 31 CH None 1 Blocking Sensor Short/Interrupt 17 Water Low 1 32 DHW Post -Circulation Pump 2 Blocking Water Pressure 18 Water High 1 33 CH Post -Circulation Pump 4 Blocking 24V Low 19 Water Low 2 34 None 5 Blocking Temperature 20 Water High 2 35 Service Pump 6 DHW Function Internal 21 CH On/Off Thermostat 40 Lockout 7 DHW Function Internal 22 CH Zone Demand 51 Frost Protection Pump 8 DHW Indirect 23 CH Cascade Demand 52 Frost Protection Burner 9 DHW Direct 24 CH Pool Demand 60 Summer-Kick 10 DHW Phoenix 25 CH 61 Save EEPROM Blocking 11 DHW Spa 26 CH 96 Running 12 DHW 27 CH 100 DHW Mode or Blocking for Cascade 13 DHW 28 CH 101 Low Water Blocking 14 DHW 29 CH 15 DHW 30 CH Table 21 - Appliance 0-7 Status Codes F. Appliance 0 and Appliance 1 Blocking Codes Blocking Codes (Input Registers and 30024, AI14 and AI23) Number Appliance Fault Definition Number Appliance Fault Definition 0 None 25 Max Temperature Increase Limiting CH 11 Water Pressure Low 26 24V too Low 12 S1 Temperature High 30 Water Level Low 1 13 S2 Temperature High 31 Water Level High 1 14 Flue Temperature High 32 LEO Water Level Low 2 16 Regulation Temperature High 33 Water Level High 2 17 Not Enough Water Flow 44 Common Flue Blocking 21 Anti-Cycling CH 50 Burner Sensor Blocking 23 FLU Max Flue Pressure Switch / Max Start Cycles 60 Blocking Flue Temperature Modulation Table 22 - Appliance 0 and Appliance 1 Blocking Codes

14 14 G. Appliance 0-7 Lockout Codes Lockout Codes - (Input Registers 30016, 30025, 30029, 30033, 30037, 30041, 30045, and Points AI15, 24, 28, 32, 36, 40, and 44) Number Fault Definition Number Fault Definition 0 None 206 Error During Programming 177 AD Error 207 Parameter EEPROM Failure 178 LWCO 1 Error 230 Fan LOW Error 179 LWCO 2 Error 231 Fan HIGH Error 185 ECS6 Temperature Lockout 232 No Flame During Running 186 ECS7 Temperature Lockout 233 F09 No Flame After Ignition 190 F05 S1 Maximum Temperature 235 APS Stuck Closed 191 F06 S2 Maximum Temperature 236 APS Stuck Open 192 S1 Shorted 237 F11 False Flame 193 F02 S1 Interrupted 239 F01 Safety Thermostat Open 194 S2 Shorted 240 F00 Flue Thermostat Open 195 S2 Interrupted 241 External LWCO 196 Low Water Lockout 243 Gas Pressure 197 Flue Sensor Shorted 243 Target Wall 198 Flue Sensor Interrupted 244 Burner Sensor MAX Recycling 199 Low Water Lockout Burner Sensor Short 204 Parameters Damaged 246 Burner Sensor Interrupt 205 Parameters Programmed Table 23 - Appliance 0-7 Lockout Codes

15 15 Communication Adapter Limited Warranty One year warranty to assure your complete satisfaction. HTP warrants each Communication Adapter to be free from defects in material and workmanship according to the following terms, conditions, and time periods. UNLESS OTHERWISE NOTED THESE WARRANTIES COMMENCE ON THE DATE OF INSTALLATION. This limited warranty is only available to the original consumer purchaser (herinafter Owner ) of this product, and is non-transferable. COVERAGE A. Should a defect or malfunction occur within the above-stated warranty period due to defective material or workmanship, malfunction, or failure to comply with the above warranty, with such defects or malfunctioning having been verified by an authorized HTP representative, then HTP will replace the defective or malfunctioning adapter with a replacement of the nearest comparable model available at the time of replacement. Replacement adapters will be warranted for ninety (90) days. B. In the event of a failure of a replacement adapter due to defective material or workmanship, malfunction, or failure to comply with the above warranty, HTP reserves the right to refund to the Owner the published wholesale price available at the date of manufacture of the original adapter. C. If, at the time of a request for service the Owner cannot provide a copy of the original sales receipt, the warranty period for the adapter shall then be deemed to have commenced thirty (30) days after the date of manufacture of the adapter and NOT the date of installation, and be covered by the unexpired portion of the warranty detailed above. D. It is expressly agreed between HTP and the Owner that repair, replacement, or refund are the exclusive remedies of the Owner. WARRANTY EXCLUSIONS This limited warranty will not cover: 1. Any adapter purchased from an unauthorized dealer. 2. Any adapter not installed by a qualified heating installer/service technician, or installations that do not conform to ANSI, CSA, and/ or UL standards, as well as any applicable national or local building codes / ordinances and electrical trade practices. 3. Any damages, malfunctions, or failures due to improper installation. 4. Service trips to teach the Owner how to install, use, maintain, or to bring the adapter installation into compliance with local building codes and regulations. 5. Any failed components not manufactured by HTP as part of the adapter. 6. Adapters repaired or altered without the prior written approval of HTP. 7. Damages, malfunctions, or failures resulting from failure to operate and maintain the adapter in accordance with the manufacturer s provided instructions. 8. Failure caused by improper sizing of the electric service voltage, wiring or fusing. 9. Damages, malfunctions, or failures caused by operating the adapter with modified, altered, or unapproved components, or any component / attachment not supplied by HTP. 10. Damages, malfunctions, or failures caused by abuse, accident, fire, flood, freeze, lightning, acts of God, electrical spikes and the like. 11. Failures (leaks) caused by operating the adapter in a corrosive or contaminated atmosphere, as well as any damage or failure resulting from contaminated air, including, but not limited to, dirt, dust, or water being introduced into the adapter or its components. 12. Adapters replaced for cosmetic reasons. 13. Adapters that are not defective, but must be replaced during the warranty period as a result of reasonable wear and tear. 14. Components of the adapter that are subject to warranties, if any, given by their manufacturers; HTP does not adopt these warranties. 15. Damages, malfunctions, or failures resulting from the use of any attachment(s) not supplied by HTP. 16. Adapters installed outside the fifty states (and the District of Columbia) of the United States of America and Canada. PROCEDURES FOR WARRANTY SERVICE REQUESTS Any claim for warranty assistance must be made promptly. Determine if the adapter is in-warranty (that is, within the applicable warranty period) by reviewing a copy of the original sales receipt or warranty registration. The Owner must present a copy of the original sales receipt or warranty registration for a warranty service request. If the adapter is in-warranty, contact the retailer from whom the adapter was purchased (or the installer) for assistance. Be prepared to provide the retailer or installer with a copy of the original receipt, complete model and serial numbers, and the date of installation of the adapter, in addition to an explanation of the adapter problem. Warranty coverage is subject to validation of in-warranty coverage by HTP claims department personnel. All alleged defective or malfunctioning adapters must be returned to HTP via the local distribution channels where the original purchase was made. NOTE: Any adapters returned to HTP for warranty analysis will become the property of HTP and will not be returned, even if credit is denied. If all warranty conditions are satisfied, HTP will provide a replacement adapter to the retailer. For questions about the coverage of this warranty, please contact HTP at the following address or phone number: HTP, 272 Duchaine Blvd., New Bedford, MA, 02745, Attention: Warranty Service Department, 1(800) SERVICE, LABOR AND SHIPPING COSTS This limited warranty does not extend to shipping charges, delivery expenses, or administrative fees incurred by the Owner in repairing or replacing the Communication Adapter. This warranty does not extend to labor costs beyond the coverage specified in this warranty document. All such expenses are the Owner s responsibility. LIMITATIONS OF THIS HTP WARRANTY AND REMEDIES THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE GIVEN AND ACCEPTED TO THE FURTHEST EXTENT UNDER APPLICABLE LAW IN LIEU OF ANY AND ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ANY OBLIGATION, LIABILITY, RIGHT, CLAIM OR REMEDY IN CONTRACT OR TORT, WHETHER OR NOT ARISING FROM HTP S NEGLIGENCE, ACTUAL OR IMPUTED. THE REMEDIES OF THE OWNER SHALL BE LIMITED TO THOSE PROVIDED HEREIN TO THE EXCLUSION OF ANY OTHER REMEDIES INCLUDING WITHOUT LIMITATION, INCIDENTAL OR CONSEQUENTIAL DAMAGES, SAID INCIDENTAL AND CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, PROPERTY DAMAGE, LOST PROFIT OR DAMAGES ALLEGED TO HAVE BEEN CAUSED BY ANY FAILURE OF HTP TO MEET ANY OBLIGATION UNDER THIS AGREEMENT INCLUDING THE OBLIGATION TO REPAIR AND REPLACE SET FORTH ABOVE. NO AGREEMENT VARYING OR EXTENDING THE FOREGOING WARRANTIES, REMEDIES OR THIS LIMITATION WILL BE BINDING UPON HTP. UNLESS IN WRITING AND SIGNED BY A DULY AUTHORIZED OFFICER OF HTP. THE WARRANTIES STATED HEREIN ARE NOT TRANSFERABLE AND SHALL BE FOR THE BENEFIT OF THE ORIGINAL OWNER ONLY. NO OTHER EXPRESS WARRANTIES This warranty gives the Owner specific legal rights. The Owner may also have other rights that vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation or exclusion may not apply to the Owner. These are the only written warranties applicable to this adapter manufactured and sold by HTP. HTP neither assumes nor authorizes anyone to assume for it any other obligation or liability in connection with said adapters. HTP reserves the right to change specifications or discontinue models without notice.

16 16 Installation and Maintenance Notes

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Installation Manual NPE-180A/240A WARNING. Add-on Controller Installation Kit

Installation Manual NPE-180A/240A WARNING. Add-on Controller Installation Kit Installation Manual Add-on Controller Installation Kit NPE-180A/240A This device is designed to work with NPE-180A/240A models ONLY. WARNING All Installations should be done only by a qualified expert

More information

Superstor Pro Pool Heaters

Superstor Pro Pool Heaters Superstor Pro Pool Heaters Installation Start-Up Maintenance Parts Warranty SSP-20PH Model CAUTION The use of a salt chlorine generator is prohibited in a system serviced by this pool heater. Salinated

More information

Installation Manual WARNING. Add-on Controller Installation Kit NPE-180A/210A/240A

Installation Manual WARNING. Add-on Controller Installation Kit NPE-180A/210A/240A Installation Manual Add-on Controller Installation Kit NPE-180A/210A/240A This device is designed to work with NPE-180A/210A/240A water heaters ONLY. WARNING All Installations should be done only by a

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

Multiple Boilers Electro TS Series Application EB-C-STG5

Multiple Boilers Electro TS Series Application EB-C-STG5 Multiple Boilers Electro TS Series Application EB-C-STG5 Drawings: BC025 BX404 BH504 XX017 Information All Electro-Boilers, except Mini-Boiler, have the same control board (EB5623**). The plug-in control

More information

Installation Instructions

Installation Instructions P700U -21NHP Base Non -Programmable Thermostats Installation Instructions Designed and Assembled in the USA. US patents: US20060165149 A1, USD578026 SI, US6205041 B1 A14005 Base Non---Programmable Thermostat

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual H-IM-LLC February 2018 Part No. 25092501 Replaces H-IM-LLC (01/2014) Lead Lag Control System Table of Contents General Safety Information 2 Inspection 2 Warranty Statement

More information

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc. Installation Manual 000 Version.0 EXP-000 HBX Control s Inc. Control s Inc. HBX EXP 000 Version.0 HBX EXP-000 EXPANSION MODULE INTRODUCTION The EXP-000 is designed to be integrated with the HBX CPU-000

More information

- User Brochure tekmarnet 4 Setpoint Control 161

- User Brochure tekmarnet 4 Setpoint Control 161 - User Brochure tekmarnet 4 Setpoint Control 161 U 161 08/07 Congratulations on the purchase of your tekmar setpoint control with communication. The setpoint control combines easy-to-use programming with

More information

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc.

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc. Installation Manual M-000 Setpoint Thermostat Version.04 M-000 HBX Control Systems Inc. TABLE OF CONTENTS Introduction Index Safety symbols and Warnings Index Receipt and Inspection Description Technical

More information

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL INSTALLATION AND OPERATION GUIDE INTRODUCTION The NSI 804CP and 808CP represents a key part of a state of the art, total lighting control system. Combined with

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in

More information

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Page 1 of 8 General Overview Thank you for purchasing an Ion Genesis controller. Take the time to read the instructions carefully before using this appliance. We strongly recommend that you keep this instruction

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Keep these instructions with the boiler at all times. BOYERTOWN FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450 www.boyertownfurnace.com 5-25-12 2 Danger Warning Caution

More information

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm Ion Endeavor Controller Digital Level Control with Alternation Page 1 of 8 General Overview The Ion Endeavor is a pump controller that senses a water level of up to 72", has a configurable water level/pump

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL INSTALLATION & OPERATION MANUAL Model TME- * * Balance of model number is determined by customer specifi ed limits and Setbacks. AUTOMATIC SETBACK THERMOSTAT LIGHT SENSING OR CONTACT CLOSURE FOR LOW VOLTAGE

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Instruction Bulletin

Instruction Bulletin Instruction Bulletin 435-54-26A 9/99 Monroe, NC, USA MODEL 98 Digital Temperature Controller For Medium Voltage Transformers Class 3, 4 Retain for future use. NOTICE Read these instructions carefully and

More information

Isolated Thermocouple Module

Isolated Thermocouple Module User Manual for the HE693THM665, HE693THM666, HE693THM667, HE693THM668 Isolated Thermocouple Module Twelfth Edition 19 April 2004 PREFACE 19 APR 2004 PAGE 3 PREFACE This manual explains how to use the

More information

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0)

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0) F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0) Approvals: Suitable for use in Hazardous Locations CL II Div 1 GPS E, F & G (CANADA ONLY) CL II Div 2 GPS

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Thermostat Series. Installation Manual TSTBM-RRS--TW-A Revised 02-13

Thermostat Series. Installation Manual TSTBM-RRS--TW-A Revised 02-13 Installation Manual Thermostat Series TSTBM-RRS--TW-A Remote Temperature Sensor (Requires TSTBM3H2CPH6W-A) TSTBM-RRS--TW-A 2 TSTBM-RRS--TW-A Table Of Contents Table of Contents Thermostat Quick Reference...

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

- Data Brochure. This brochure is for Thermostats 510 and 511 (with sensor). The section on the 079 slab sensor installation is for the 511 only!

- Data Brochure. This brochure is for Thermostats 510 and 511 (with sensor). The section on the 079 slab sensor installation is for the 511 only! - Data Brochure Programmable Thermostat 510 and 511 D 510 02/12 Table of Contents Display / Keypad Operation... pg 1 Display Symbols... pg 2 General... pg 2-3 Sequence of Operation... pg 4 Installation

More information

OPERATION & INSTALLATION MANUAL

OPERATION & INSTALLATION MANUAL OPERATION & INSTALLATION MANUAL Model: SIO 14 & SIO 18 Electric Tankless Hot Water Generators Table of Contents SAFETY INFORMATION... 1 INTRODUCTION... 2 Unit Operation:... 2 Unit Freezing:... 3 Maintenance:...

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

- User Brochure Programmable Thermostat 510

- User Brochure Programmable Thermostat 510 - User Brochure Programmable Thermostat 510 U 510 09/09 Congratulations on the purchase of your tekmar programmable thermostat. This thermostat combines easy-to-use programming with advanced features to

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions KNCT2-808 KN Series Gas-fired direct vent Cast iron boilers Models KN-6, -10, -20 only (HeatNet control firmware edition 45 ) Control manual Control adjustment and Operation instructions Also read and

More information

Blade Series Heat Exchanger Operation and Installation

Blade Series Heat Exchanger Operation and Installation Blade Series Heat Exchanger Operation and Installation *IMPORTANT* For safe and satisfactory operation, please read the following instructions. Keep these instructions for future reference. Some information

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

ProTalk. Expander. Operating Manual Model B1292. July 28, 2009 Rev. 1.01

ProTalk. Expander. Operating Manual Model B1292. July 28, 2009 Rev. 1.01 ProTalk Expander Operating Manual Model B1292 July 28, 2009 Rev. 1.01 TABLE OF CONTENTS 1. Introduction... 1 2. Installation... 2 2.1 Wiring Diagram... 3 3. Operations... 4 4. Programming (B1225 Mode)...

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

Compact Equipment Warranty Policy

Compact Equipment Warranty Policy 006 07.15 Compact Equipment Warranty Policy 07/2015 Table of Contents Preface Page 1 Distributor s Warranty Responsibilities Page 1 Standard Warranties Page 2 Warranty Coverage Page 2 Warranty Limitations

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

Custom Control Systems Inc. Ellis Dryer Control Configuration and Operation Manual

Custom Control Systems Inc. Ellis Dryer Control Configuration and Operation Manual Ellis Dryer Control Configuration and Operation Manual Revised 1/19/2004 Table of Contents 1 Introduction... 7 1.1 Hardware Specifications... 7 1.2 Software Features... 7 1.3 Warranty... 8 1.3.1 Terms...

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

PodView Level Indicator LI40 Series Manual

PodView Level Indicator LI40 Series Manual PodView Level Indicator LI40 Series Manual Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598 3015 Fax: (562) 431 8507 www.flowline.com Rev A MN204260 1 of 16 INTRODUCTION / TABLE

More information

Owner s Manual. Model 8800 Universal Communicating Thermostat. Includes Operating Instructions and Warranty Information

Owner s Manual. Model 8800 Universal Communicating Thermostat. Includes Operating Instructions and Warranty Information Model 8800 Universal Communicating Thermostat Owner s Manual Includes Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS 61000762A 8800 Tstat Owners.indd 1 3/28/11 4:19:57

More information

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date: Trinity Tft/Lx Model #s: Tft60-399/Lx150-800 Version Date: 2013-07-26 NEW FEATURES Second Central Heat Input Internal Lead-Lag Control System Sensor Modulation Sensor Alternatives Warm Weather Shutdown

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

Pump-Down Controller MODEL 4052

Pump-Down Controller MODEL 4052 Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down

More information

Owner s Manual. 5+2 Day Programmable Digital Thermostat

Owner s Manual. 5+2 Day Programmable Digital Thermostat Model Air Conditioning & Heating 5+2 Programmable Digital Thermostat 1-Heat & 1-Cool Heat Pump Compatible Battery or System Powered Backlit Digital Display Fahrenheit or Celsius Service Filter Indicator

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

VX SERIES Wireless Thermostat with Occupancy Sensor

VX SERIES Wireless Thermostat with Occupancy Sensor VX SERIES Wireless Thermostat with Occupancy Sensor INSTRUCTION MANUAL Table of Contents Thermostat Installation... 7 Installing the Wireless Control Card...8 Mounting the thermostat to the wall...9 Thermostat

More information

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit January 2008 WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit Installation Operation Maintenance The units are designed for permanent up flow, counter flow, or horizontal left or right airflow

More information

Pump-Up Controller MODEL 4062

Pump-Up Controller MODEL 4062 Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up

More information

INSTRUCTION MANUAL P Heating and 1 Cooling

INSTRUCTION MANUAL P Heating and 1 Cooling REPLACEMENT COMPONENTS DIVISION CARRIER CORPORATION www.totaltouch.info Technical Support: 1-866-90TOUCH (1-866-908-6824) INSTRUCTION MANUAL P286-1200 2 Heating and 1 Cooling Physical Dimensions Case:

More information

Installation & Operation Manual

Installation & Operation Manual Installation & Operation Manual Radiant Thermostat 519 519_D 06/16 Zoning Replaces: 03/13 Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating

More information

Operating Instructions READ AND SAVE THESE INSTRUCTIONS

Operating Instructions READ AND SAVE THESE INSTRUCTIONS Operating Instructions READ AND SAVE THESE INSTRUCTIONS Aprilaire Communicating Thermostat Model 8870 CAUTION: Do not set to OFF mode during periods when freezing temperatures could occur. Thank you for

More information

Installation & Operation Manual

Installation & Operation Manual Humidity & Temperature Sensor 086 Accessories 086_D 08/12 Replaces: New Installation & Operation Manual Introduction The Humidity & Temperature Sensor 086 can be connected to select tekmar thermostats

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Thermostats. Digital Non-Programmable. GEAppliances.com. Owner s Manual & Installation Instructions RAK148D2 RAK164D2

Thermostats. Digital Non-Programmable. GEAppliances.com. Owner s Manual & Installation Instructions RAK148D2 RAK164D2 GEAppliances.com Digital Non-Programmable Thermostats Owner s Manual & Installation Instructions RAK148D2 RAK164D2 Configuration Mode... 8 9 Important Safety Information... 2 Installation Instructions...

More information

RK Transmitter Technical Notice

RK Transmitter Technical Notice 65-2450RK Transmitter Technical Notice Although this Operator s Manual was written for the 65-2400RK combustible gas LEL transmitter, the operational instructions are the same for the 65-2450RK hydrogen

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first totally integrated multiple boiler management control. USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE Follow

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. 273 Branchport Avenue Long Branch, NJ 07740 (732) 222-6880 Thank you for using our products. INSTALLATION INSTRUCTIONS REMOTE MICROPHONE (SINGLE CIRCUIT) Use this product according to this instruction

More information

I/O logger box. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT!

I/O logger box. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! I/O logger box User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! H i g h E f f i c i e n c y S o l u t i o n s WARNING DISPOSAL CAREL bases the development of its products on decades

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FOR AQUECOIL HYDRONIC HEATING UNITS GENERAL INFORMATION The AQUECOIL Hydronic Heating Unit is offered in many different capacities and physical configurations in order to match

More information

FOR EASY, FAST INSTALLATION AND FOR RESULTS

FOR EASY, FAST INSTALLATION AND FOR RESULTS Page 1 INSTALLATION & OPERATING INSTRUCTIONS FOR FEDERAL FLOOR FURNACE OFB-100 AND OFB100L UNPACK SHIPMENT CAREFULLY AND INSPECT FOR DAMAGE. ALL GOODS ARE CAREFULLY MANUFACTURED, INSPECTED, CHECKED, AND

More information

INSTRUCTION MANUAL TS21. 2 Heating and 1 Cooling

INSTRUCTION MANUAL TS21. 2 Heating and 1 Cooling INSTRUCTION MANUAL TS21 2 Heating and 1 Cooling WELCOME TO Flexible applications - Universal and easy to install in residential or commercial environments. Advanced features - Precision electronics provide

More information

5+2 DAY. OWNER S MANUAL Venstar Inc. 05/08

5+2 DAY. OWNER S MANUAL Venstar Inc. 05/08 Digital Thermostat residential THERMOSTAT 5+2 DAY PROGRAMMABLE up to 1-heat & 1-cool PUMP Stages: 1-Heat, 1-Cool Battery or System Powered Back-Lit Digital Display Fahrenheit or Celsius Service Filter

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Service Manual Models: 1.0, 1.3, and 1.5

Service Manual Models: 1.0, 1.3, and 1.5 AWX2-SER_100160837_2000000360_Rev F Service Manual Models: 1.0, 1.3, and 1.5 LOW LEAD CONTENT WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

ALM100 Alarm Module. User s Manual

ALM100 Alarm Module. User s Manual ALM100 Alarm Module User s Manual Revision 1.0 Copyright 2008 Maretron, LLP All Rights Reserved Maretron, LLP 9014 N. 23 rd Ave #10 Phoenix, AZ 85021-7850 http://www.maretron.com Maretron Manual Part #:

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

Chore-Tronics Load Cell Indicator

Chore-Tronics Load Cell Indicator Chore-Tronics Load Cell Indicator June 2008 CTB Inc. Warranty Load Cell Indicator CTB Inc. Warranty CTB Inc. warrants each new product manufactured by it to be free from defects in material or workmanship

More information

Safety, Installation, and Operation Manual

Safety, Installation, and Operation Manual Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and

More information

RK Combustible Gas Transmitter Operator s Manual

RK Combustible Gas Transmitter Operator s Manual 65-2400RK Combustible Gas Transmitter Operator s Manual Part Number: 71-0060RK Revision: C Released: 1/31/13 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.

NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE. Superstor Glass Lined Storage Tanks Installation Start-Up Maintenance Parts Warranty For Residential and Commercial Use GL Models* *Available in Metal Jacketed ASME and Non-ASME Models The surfaces of

More information

Digital Non-Programmable

Digital Non-Programmable Digital Non-Programmable THERMOSTAT OWNER S MANUAL & INSTALLATION INSTRUCTIONS RAK148F2 RAK164F2 SAFETY INFORMATION... 2 OVERVIEW... 3 INSTALLATION... 4 7 CONFIGURATION MODE...8, 9 OPERATING FUNCTIONS...

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

FW-RA-LED Remote Multiplex Annunciator Panels

FW-RA-LED Remote Multiplex Annunciator Panels FW-RA-LED Remote Multiplex Annunciator Panels WIRING and INSTALLATION INSTRUCTION LNOTICE All information, documentation, and specifications contained in this manual are subject to change without prior

More information

Owner s Manual. PIR-1 IR Learner

Owner s Manual. PIR-1 IR Learner Owner s Manual PIR-1 IR Learner PIR-1 Owner s Manual 2010-2013 Universal Remote Control, Inc. The information in this owner s manual is copyright protected. No part of this manual may be copied or reproduced

More information

Installation & Operation Manual

Installation & Operation Manual 519_D Radiant Thermostat 519 03/13 Zoning Replaces: New Installation & Operation Manual Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating

More information

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3-2% AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3-2% Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

Series: MBC1-TC Mini Benchtop Temperature Controller

Series: MBC1-TC Mini Benchtop Temperature Controller User s Guide Series: MBC1-TC Mini Benchtop Temperature Controller Imagine Instruments LLC:: 4500 Williams Drive, Ste 212-318 :: Georgetown, TX 78633 :: p. 855.574.6243 e-mail: info@imagineinstruments.com

More information

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8 KN-2/4-CM2-313 42-9452 Cast Iron Condensing Boilers Models KN-2 and KN-4 HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8 Also read and follow: KN Boiler

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector CAUTION & SYMBOL DEFINITIONS: CAUTION: Gives detailed description of different situations to avoid or not avoid for the proper operation of the

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

SPI Communications Option

SPI Communications Option www.conairnet.com USERGUIDE IMD021/1297 SPI Communications Option Corporate Office: 412.312.6000 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and Service: 814.437.6861 The SC Carousel

More information

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual GG-VL-R REFRIGERANT VENT LINE SENSOR Installation and Operation Manual 2 GG-VL-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

Figure 1. Figure 2. See notes 1 and 2 below.

Figure 1. Figure 2. See notes 1 and 2 below. 273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc. com INSTALLATION INSTRUCTIONS HORN SPEAKER WITH AMPLIFIER Use this product according to this

More information

IAQ Series. Bosch IAQ Photo Catalytic Oxidizer (PCO) Residential Application. Installation Manual and Owner s Guide

IAQ Series. Bosch IAQ Photo Catalytic Oxidizer (PCO) Residential Application. Installation Manual and Owner s Guide Installation Manual and Owner s Guide IAQ Series Bosch IAQ Photo Catalytic Oxidizer (PCO) Residential Application PCOB-09012-0--A - 9" PCO BULB PCOB-14024-0--A - 14" PCO BULB 67202220344 Revised 07-12

More information

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual GG-EM ENTRANCE MONITOR Installation and Operation Manual 2 GG-EM Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information