VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

Size: px
Start display at page:

Download "VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors"

Transcription

1 Installation and service instructions for contractors VIESMANN Vitocal 200-S Type AWB 201.B04 to B13, C10, C13 Air source heat pump, split version for heating operation Type AWB-AC 201.B04 to B13, C10, C13 Air source heat pump, split version for heating and cooling operation For applicability, see the last page VITOCAL 200-S 2/2013 Please keep safe.

2 Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained 2 Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively intended for qualified contractors. Work on the refrigerant circuit may only be carried out by authorised refrigeration engineers. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Observe the following when working on this system: National installation regulations Statutory regulations regarding the prevention of accidents Statutory regulations regarding environmental protection Codes of practice of the relevant trade associations. All current safety regulations as defined by DIN, EN, DVGW, VDE and all locally applicable standards a ÖNORM, EN and ÖVE c SEV, SUVA, SVTI, SWKI and SVGW Working on the system Isolate the system from the power supply (e.g. by removing the separate fuse or by means of a mains isolator) and check that it is no longer 'live'. Note In addition to the control circuit, there may be several power circuits. Danger Contact with 'live' components can result in severe injuries. Some components on the PCBs will remain 'live' even after the power supply has been switched off. Prior to removing equipment covers, wait at least 4 min. to allow the voltage to dissipate. Safeguard the system against reconnection.

3 Safety instructions Safety instructions (cont.)! Please note Electronic assemblies can be damaged by electrostatic discharge. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads. Repair work! Please note Repairing components that fulfil a safety function can compromise the safe operation of your system. Defective components must be replaced with genuine Viessmann spare parts. Auxiliary components, spare and wearing parts Please note! Spare and wearing parts that have not been tested together with the system can compromise its function. Installing non-authorised components and making non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only spare parts supplied or approved by Viessmann. 3

4 Index Installation instructions Preparing for installation Intended use... 6 Requirements regarding on-site connections... 7 Installation sequence Installing the external unit Installing the internal unit Connecting the refrigerant lines Connecting a secondary circuit Connecting a cooling circuit if required Electrical connections Power supply Closing the heat pump Service instructions Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance Further details regarding the individual steps Troubleshooting Repairs Parts lists, internal unit Parts lists, internal unit Overview of assemblies, internal unit Parts not shown, internal unit Casing, internal unit Electrical equipment, internal unit Hydraulics, internal unit, type AWB Hydraulics, internal unit, type AWB-AC Parts lists for external unit 230 V~, type AWB/AWB-AC 201.B04 Ordering individual parts External unit Parts lists for external unit 230 V~, type AWB/AWB-AC 201.B07 Ordering individual parts External unit Parts lists for external unit 230 V~, type AWB/AWB-AC 201.B10, B13 Ordering individual parts Index

5 Index Index (cont.) Overview of the assemblies External unit casing Electrical equipment, external unit Hydraulics, external unit Parts lists for external unit 400 V~, type AWB/AWB-AC 201.C10, C13 Ordering individual parts Overview of the assemblies External unit casing Electrical equipment, external unit Hydraulics, external unit Commissioning/service reports Hydraulic parameter report Control parameters report Specification Appendix Commissioning order Declaration of conformity Keyword index

6 Preparing for installation Intended use The appliance is only intended to be installed and operated in sealed unvented heating systems that comply with EN 12828, with due attention paid to the associated installation, service and operating instructions. Depending on the version, the appliance can only be used for the following purposes: Central heating Central cooling DHW heating The range of functions can be extended with additional components and accessories. Intended use presupposes that a fixed installation in conjunction with permissible, system-specific components has been carried out. Commercial or industrial usage for a purpose other than central heating/cooling or DHW heating shall be deemed inappropriate. Any usage beyond this must be approved by the manufacturer for the individual case. Incorrect usage or operation of the appliance (e.g. the appliance being opened by the system user) is prohibited and results in an exclusion of liability. Incorrect usage also occurs if the components in the heating system are modified from their intended function. Note The appliance is intended exclusively for domestic use, i.e. even users who have not had any instruction are able to operate the appliance safely. 6

7 Requirements regarding on-site connections Preparing for installation Internal unit A B AB / Installation 7

8 Preparing for installation Requirements regarding on-site connections (cont.) Symbol Meaning Connection Refrigerant lines from/to the external unit: Type AWB/ AWB-AC Pipe 7 UNF thread Hot gas line 201.B04 12 mm ⅞ Reducer ⅞ x ¾ B B B C C13 16 mm 16 mm 16 mm 16 mm 16 mm Liquid line 201.B04 6 mm ⅝ Reducer ⅝ x ⁷ ₁₆ DHW cylinder flow (heating water side) Heating water return and DHW cylinder return Heating water flow 201.B B B C C13 10 mm 10 mm 10 mm 10 mm 10 mm ⅞ ⅞ ⅞ ⅞ ⅞ ⅝ ⅝ ⅝ ⅝ ⅝ G 1¼ G 1¼ G 1¼ A Cable entry < 42 V B Cable entry 400 V~/230 V~, > 42 V 1. Prepare the connections on the heating water and the DHW side. Flush the heating system. 2. Prepare the electrical connections. 8

9 Requirements regarding on-site connections (cont.) Preparing for installation Cable lengths in the internal/external unit plus wall clearance Cables Internal unit External unit Power cables: Heat pump control unit (230 V~) 2.0 m Compressor (230 V~/400 V~) 1.5 m Other connecting cables: 230 V~, e.g. for circulation pumps 2.0 m < 42 V, e.g. for sensors 2.0 m Internal/external unit connecting cable: 12 V BUS 2.5 m 1.5 m 43 V BUS 2.5 m 1.5 m Recommended power cables Type AWB, AWB-AC 201.B04 to B13, C10, C13 Heat pump control unit (internal unit) 230 V~ Cable cross-section Without power-off 3 x 1.5 mm 2 With power-off 5 x 1.5 mm 2 Instantaneous heating water heater Cable cross-section 400 V~ 5 x 2.5 mm V~ 7 x 2.5 mm 2 Max. cable length 25 m Installation Type AWB, AWB-AC 201.B B B B13 External unit 230 V~ (compressor) Cable cross-section 3 x 2.5 mm 2 3 x 2.5 mm 2 3 x 2.5 mm 2 3 x 4.0 mm 2 Max. cable length 29 m 25 m 20 m 20 m or or Cable cross-section 3 x 4.0 mm 2 3 x 6.0 mm 2 Max. cable length 32 m 30 m Type AWB, AWB-AC 201.C C13 External unit 400 V~ (compressor) Cable cross-section 5 x 2.5 mm 2 5 x 2.5 mm 2 Max. cable length 30 m 30 m 9

10 Installation sequence Installing the external unit! Please note Avoid damaging the appliance during transport. Never put weight on top of the appliance.! Please note If the compressor in the external unit is strongly tilted, lubricant will enter the refrigerant circuit and damage the appliance. Note the max. tilting angle of 45. Installation requirements Installation site Select a site with good air circulation, so that the cooled air can dissipate and be replaced by warm air. Avoid direct insolation. When siting the unit in a location exposed to wind, ensure that the wind does not affect the fan area. This could result in an "air short circuit" between the air being discharged and the air being drawn in. Strong wind can have a negative influence on the evaporator ventilation. Please note! An "air short circuit" during heating operation will result in the cooled discharged air reentering the unit. This can result in reduced heat pump efficiency and defrosting problems. Avoid "air short circuits". Please note! An "air short circuit" during cooling operation will result in the heated discharged air reentering the unit. This can lead to high pressure faults. Avoid "air short circuits". Take the lengths of the refrigerant lines into account (see "Connecting refrigerant lines"). Select the installation site so that the evaporator cannot be blocked by leaves, snow etc. Select the installation site with due consideration of the physical laws of sound dissipation and reflection. Technical guide "Heat pump principles" Never site in corners, recesses or between walls. Never install next to or below bedroom windows. Never install closer than 3 m to pathways, downpipes or sealed surfaces. The cooled air in the discharge area creates a risk of ice forming when outside temperatures fall below 10 C. The installation site should be easily accessible, for example for maintenance work (see "Minimum clearances"). 10

11 Installation sequence Installing the external unit (cont.) Types of installation Floorstanding installation with cable entry above ground level Floorstanding installation with cable entry below ground level Wall mounting Technical guide Installation information Floorstanding installation: Use supports (accessories) for floorstanding installation. Where such supports cannot be used, install the external unit freestanding on a solid base of at least 100 mm height (provide on site). In difficult climatic circumstances (temperatures below zero, snow, humidity) install the appliance on a plinth of approx. 300 mm height. Take account of the weight of the external unit (see following table). Wall mounting: Use the wall mounting bracket set (accessories). The wall must meet the structural requirements. Never install with the discharge side facing the main wind direction. Observe wind loads when installing the unit on sites exposed to wind. Provide wall ducts and protective pipes for the refrigerant lines and electrical cables without moulded parts and change of direction. Incorporate the external unit into the lightning protection system. Consider the heat emitted by the unit when planning your weatherproofing or an enclosure. Ensure the condensate can drain freely, and create a permanent gravel bed below the external unit as a soakaway. In regions with prolonged cold seasons (e.g. in Germany), provide an electric supplementary heating facility (accessories) for the condensate pan. For insulating against structure-borne noise and vibrations between the building and the external unit, consider the following measures: When cable entry is above ground level, fit pipe bends in the refrigerant lines for vibration compensation (see "Connecting refrigerant lines"). Route electrical cables/leads between the internal and external units free of stress. Installation only on walls with high weight per area (> 250 kg/m 2 ), in other words not on lightweight walls, roof structures etc. When installing the unit on the floor, use only the rubber mounts supplied; for wall mounting use the antivibration mounts supplied with the wall mounting bracket set; never use additional anti-vibration mounts, springs, rubber buffers etc. Weight of external units Type Weight in kg AWB/AWB-AC 201.B B B B Installation

12 Installation sequence Installing the external unit (cont.) Type Weight in kg AWB/AWB-AC 201.C C Minimum clearances b A a c d B Example type AWB/AWB-AC 201.B04 A Air intake B Air discharge Type AWB/ AWB-AC 12 Dimensions in mm a b c d Cable entry above ground level below ground level 201.B B B B C C

13 Installation sequence Installing the external unit (cont.) Floor mounting Installation 2. 4x E 1. 4x A B C D A Support for floorstanding installation (accessory) 13

14 Installation sequence Installing the external unit (cont.) B Gravel bed as condensate soakaway C Concrete foundations (see technical guide) D Drainage pipe DN 100 (only with entries below ground level) E Rubber mounts (supplied) Note We recommend letting condensate drain away freely (without condensate pipe). Wall mounting Installation must only be performed with the bracket set suitable for wall mounting (accessory). Separate installation instructions Installing the internal unit! Please note Avoid damaging the appliance during transportation. Never put weight on top of the appliance. Installation room requirements Please note! The installation room must be dry and free from the risk of frost. Safeguard ambient temperatures between 0 and 35 C. Please note! Avoid the risk of explosion due to dust, gases and vapours in the installation room. Minimum room volume (to EN 378): Type AWB/AWB- AC Minimum room volume in m B B B B C C

15 Installation sequence Installing the internal unit (cont.) Minimum clearances A B A Cable entry <42 V B Cable entry 400 V~/230 V~, >42 V Installation 15

16 Installation sequence Installing the internal unit (cont.) Fitting the internal unit to the wall x 16

17 Installation sequence Connecting the refrigerant lines The external unit is pre-filled with refrigerant R 410A. In the following cases, fit oil lift bends in the vertical pipe (see diagram below): In heating mode, if the internal unit is installed higher than the external unit. In cooling mode, if the internal unit is installed lower than the external unit. Routing refrigerant lines Type AWB/AWB-AC 201.B B B C B C13 Refrigerant lines Min. line length 3 m 3 m 3 m 3 m Max. line length 20 m 30 m 30 m 30 m Max. height differential, internal unit external unit 10 m 15 m 15 m 15 m Note No topping up is required for line lengths between 3 and 12 m. A C Liquid line D Hot gas line E Oil lift bends, Flow direction in heating mode, Flow direction in cooling mode Installation B C E 5000 D 5000 Example type AWB/AWB-AC 201.B07 A B Internal unit External unit 17

18 Installation sequence Connecting the refrigerant lines (cont.) Sound and vibration isolation when cable entry is above ground level Note Route connecting cables and refrigerant lines separately. A B C D A Pipe bends as vibration compensators B Pipe clips with EPDM lining C Cable entry, e.g. drainage pipe with thermal insulation D Electrical cables/leads, internal/ external unit 18

19 Installation sequence Connecting the refrigerant lines (cont.) Connection to the external unit 1. Type AWB/AWB-AC 201.B04 and 201.B07: Remove the side cover; see page D C 3. 2x Installation D C 4. Example type AWB/AWB-AC 201.B04 C Liquid line D Hot gas line 19

20 Installation sequence Connecting the refrigerant lines (cont.) 2.! Please note Contamination (e.g. metal swarf) or moisture must not enter the copper pipes. Therefore, hold the pipe openings down or plug them. 3. Flare the pipe ends. 4. Secure the pipes. Remove the nuts from connections C (liquid line) and D (hot gas line) of the refrigerant lines. Type AWB/AWB-AC 201.B04: Slide the nuts onto the refrigerant lines prepared on site. Type AWB/AWB-AC 201.B07 to B13, C10, C13: Replace nuts with the supplied union nuts (internal unit) (⅝ UNF for liquid line, ⅞ UNF for hot gas line). Tighten the nuts with the following torque: Type Line Connection to Torque in Nm AWB/ AWB-AC external unit 201.B04 Liquid line 7 6 mm ⁷ ₁₆ UNF Hot gas line 7 12 mm ¾ UNF B07 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF B10 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF B13 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF C10 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF C13 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF

21 Installation sequence Connecting the refrigerant lines (cont.) Connection to the internal unit 2x 2. D C Installation 1. D C D C 3. C Liquid line Please note! Contamination (e.g. metal swarf) or moisture must not enter the copper pipes. Therefore, hold the pipe openings down or plug them. Note The refrigerant lines of the internal unit are filled with nitrogen; overpressure 1 to 2 bar (0.1 to 0.2 MPa). D Hot gas line 1. Remove the nuts from refrigerant connections C and D. Type AWB/AWB-AC 201.B04: Replace nuts with union nuts supplied (⁷ ₁₆ UNF for liquid line, ¾ UNF for hot gas line). Connect supplied reducer with copper sealing ring. Type AWB/AWB-AC 201.B07 to B13, C10, C13: Push the nuts onto the relevant refrigerant lines from the external unit. 21

22 Installation sequence Connecting the refrigerant lines (cont.) 2. Flare the pipe ends of the refrigerant lines. Note If solder fittings are used, solder the fittings using a shielding gas. 3. Fit refrigerant lines and insulate them to provide protection from heat and vapour diffusion. Tighten the nuts with the following torque: Type Line Connection to Torque in Nm AWB/ AWB-AC internal unit 201.B04 Liquid line 7 6 mm ⅝ UNF with reducer ⅝ x ⁷ ₁₆ Hot gas line 7 12 mm ⅞ UNF with reducer ⅞ x ¾ B07 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF B10 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF B13 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF C10 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF C13 Liquid line 7 10 mm ⅝ UNF Hot gas line 7 16 mm ⅞ UNF

23 Installation sequence Connecting a secondary circuit + Installation Refrigerant lines from/to the external unit Symbol Meaning Connection DHW cylinder flow (heating water side) G 1¼ + Heating water return and DHW cylinder return Heating water flow G 1¼ G 1¼ 1. Equip the secondary circuit on site with an expansion vessel and safety assembly (in accordance with DIN 4757). Fit the safety assembly to the on-site line in the heating water return (see page 64). 2. Connect the secondary circuit lines to the heat pump. Please note! To prevent appliance damage, connect on-site secondary circuit lines to the heat pump so that they are free of load and torque stress. Make tight hydraulic connections on the secondary side. 3. Fill and vent secondary circuit. 23

24 Installation sequence Connecting a secondary circuit (cont.) 4. Thermally insulate pipes inside the building. 5. Connect the drain hose to the safety valve. Connect the drain hose to the public sewage system with a fall and a pipe vent. Note In underfloor heating circuits, install a temperature limiter to restrict the maximum temperature for underfloor heating systems (see page 31). Safeguard the minimum flow rate, e.g. with an overflow valve (see specification on page 129). Connecting a cooling circuit if required For area cooling systems (e.g. underfloor heating circuit, chilled ceiling), a contact humidistat (accessory) is required. Requirements for the contact humidistat: Electrical connection: 230 V~, 0.5 A Installation inside the room to be cooled at the cooling water flow (remove thermal insulation if required) If several rooms with different relative humidity are part of the cooling circuit, fit and connect several contact humidistats in series: Switching contacts as N/C contacts Electrical connections Danger Damaged cable insulation can cause injury and damage to the appliance. Route cables so that they cannot touch very hot, vibrating or sharpedged components. Danger Incorrectly routed wiring can lead to serious injury from electrical current and result in equipment damage. Route LV leads < 42 V and cables > 42 V/230 V~/400 V~ separately. Strip the insulation from the cables as close to the terminals as possible, and bundle tightly to the corresponding terminals. Secure cables with cable ties. 24

25 Installation sequence Electrical connections (cont.) This ensures that, should there be an error, for example when detaching a wire, the wires cannot drift into the adjacent voltage area. Note If two components are connected to the same terminal, press both cores together into a single wire ferrule. Note Make all connections on the control panel, (see page 28) with flexible cables to ensure that the control panel can be placed in the service position (see page 81).! Please note In terms of safety, the BUS cable for the internal/external unit (12 V or 43 V) does not count as a LV lead. The BUS cable must be routed together with the 230 V cables. Installation 25

26 Installation sequence Electrical connections (cont.) Internal unit: Routing electrical cables to the wiring chamber < 42V > 42V 400V 230V! B A 26

27 Installation sequence Electrical connections (cont.) A Type AWB/AWB-AC 201.B10, B13, C10, C13: 12 V BUS cable: Routing in the 230 V~ voltage range (connection, see page 45) B Type AWB/AWB-AC 201.B04 and 201.B07: 43 V BUS cable: Routing in the 230 V~ voltage range (connection, see page 45) Installation 27

28 Installation sequence Electrical connections (cont.) Internal unit: Overview of connections F101 A P202 12V COM P203 COM 43V B X D F L1? N C? X1 N X2 X15 avg X24 F0 F6 F8 F27 F4 F11 F7 F13 F12 F16 F14 F21 F20 F26 F23 J4 X18 J3 sva F3 sxf sys sya sxs X25 F G X31 E 28

29 Installation sequence Electrical connections (cont.) A AVI PCB (see page 43) F101 MCB/fuse 1.0A (slow) B Switching module and power supply for instantaneous heating water heater (see from page 50) C Power supply 230 V~ (see page 46) F1 MCB/fuse 6.3 A (slow) D Luster terminals (see page 37) X1 Terminals for earth conductor of all associated system components X2 Terminals for neutral conductor of all associated system components E Controller and sensor PCB (see page 39) F Main PCB (see page 29) F3 MCB/fuse 6.3 A (slow) G Expansion PCB on main PCB (see page 33) Installation Internal unit: Main PCB (function components 230 V~) Information regarding the connection values The specified output is the recommended connected load. The total output of all components connected directly to the heat pump control unit must not exceed 1000 W (e.g. pumps, valves, message facilities, contactors). If the total output is < 1000 W, the individual rating of a component (e.g. pump, valve, message facility, contactor) can be greater than specified. However, the breaking capacity of the corresponding relay must not be exceeded. The specified current indicates the max. switching current of the switching contact (observe the total current of 5 A). Set the required parameters during commissioning; see from page

30 Installation sequence Electrical connections (cont.) Plug sya Terminals Function Explanation AC Type AWB-AC: Cooling control 3-way diverter valves for heating water buffer cylinder bypass in cooling mode Connection values Max. output: 10 W Voltage: 230 V~ Max. switching current: 4(2) A Connect the 3-way diverter valves for the bypass circuit in parallel. Plug sys Terminals Function Explanation A1 Heating circuit pump for heating circuit without mixer (A1/HC1) This pump is connected in addition to the secondary pump if a heating water buffer cylinder is installed. Connect the temperature limiter to restrict the maximum temperature for underfloor heating systems (if installed) in series (see the following chapter) Connection values Output: 100 W Voltage: 230 V~ Max. switching current: 4(2) A DHW circulation pump Connection values Output: 50 W Voltage: 230 V~ Max. switching current: 4(2) A 30

31 Installation sequence Electrical connections (cont.) Connecting a temperature limiter as a maximum temperature limiter for underfloor heating Connecting a general temperature limiter B Connecting the temperature limiter, part no , B X2.N X1.? A B X2.N X1.? A B sö Installation C M 1~ C M 1~ Heating circuit without mixer A1/ HC1 Connection Circulation pump C A to control unit Secondary pump Without heating water buffer cylinder With heating water buffer cylinder Heating circuit pump A1/ HC1 31

32 Installation sequence Electrical connections (cont.) Connecting the temperature limiter, part no , B to mixer extension kit A sö B sö C M 1~ A Connect plug sö to mixer extension kit B Temperature limiter C Heating circuit pump for heating circuit with mixer 32

33 Installation sequence Electrical connections (cont.) Internal unit: Expansion PCB on main PCB (function components 230 V~) Information regarding the connection values The specified output is the recommended connected load. The total output of all components connected directly to the heat pump control unit must not exceed 1000 W (e.g. pumps, valves, message facilities, contactors). If the total output is < 1000 W, the individual rating of a component (e.g. pump, valve, message facility, contactor) can be greater than specified. However, the breaking capacity of the corresponding relay must not be exceeded. The stated current indicates the max. switching current of the switching contact (observe the total current of 5 A). Safety LV is unsuitable for controlling external heat sources. Set the required parameters during commissioning; see from page 68. Installation Plug sxs Terminals Function Explanation Mixer motor control for external heat source Signal mixer CLOSED Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A Mixer motor control for external heat source Signal mixer OPEN Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A 33

34 Installation sequence Electrical connections (cont.) Plug sxs Terminals Function Explanation Floating contact Control of external heat sources and 1 high limit safety cut-out each (on site, max. 70 C), to switch off or switch between the following components: Central heating: Secondary pump, heat pump External heat source DHW reheating: 3-way diverter valve for "Central heating/dhw heating" Note The switching contact is a zero volt N/O contact that is closed when a heat demand is issued. Never route low voltage via this contact; for that fit a relay on-site. The boiler water temperature sensor in the external heat source (plug F20) must capture the average temperature of the external heat source. Connection values (contact loads): Voltage: 230 V~ Max. switching current: 4(2) A Connect the high limit safety cut-out: Central heating In series to the secondary pump (terminal on the main PCB). In series for controlling external heat sources. DHW reheating In series to the 3-way diverter valve (terminal on the main PCB). 34

35 Installation sequence Electrical connections (cont.) High limit safety cut-out for heat pump in conjunction with an external heat source D A K1 X2.N X3.1 B C C Connection on the external heat source at terminals for external demand D High limit safety cut-out (max. 70 C) as heat pump protection K1 Relay; sizing in accordance with the external heat source; observe safety instructions Installation A Terminals on extension PCB B Move jumper from X3.1 to Plug sxf Terminals Function Explanation Circulation pump for DHW reheating or Connection values Max. output: 100 W Voltage: 230 V~ Max. switching current: 4(2) A Control of the immersion heater EHE (for connection, see the following diagram) 35

36 Installation sequence Electrical connections (cont.) Immersion heater (400 V~) L1 L2 L3 N? B X2.N A A Immersion heater, power supply 3/N/PE 400 V/50 Hz B Terminals of the heat pump control unit Immersion heater (230 V~, on site) L1 L1 L1 N N N? B X2.N A A Immersion heater, power supply 1/N/PE 230 V/50 Hz B Terminals of the heat pump control unit 36

37 Installation sequence Electrical connections (cont.) Internal unit: Luster terminals (signal and safety connections) Set the required parameters during commissioning; see from page 68. Terminals Function Explanation X3.1 Switched phase Via control unit ON/OFF switch. X3.3 X3.4 Flow switch Note Observe the total load (1000 W) for all connected components. Requires zero volt N/O contact: Closed: Heat pump in operation Open: Heat pump shut down Breaking capacity 230 V~, 0.15 A Installation X3.6 X3.7 G Power-OFF (jumper fitted at the factory) Remove jumper when connecting. Requires zero volt N/C contact: Closed: Heat pump in operation Open: Heat pump shut down Breaking capacity 230 V~, 0.15 A Remove jumper when connecting. 37

38 Installation sequence Electrical connections (cont.) Terminals Function Explanation Note No parameters need to be set. The compressor is "forced" off as soon as the contact opens. The supply voltage to the relevant function components is switched off by the power-off contact signal. For the instantaneous heating water heater, the stages to be switched off can be selected (parameter "Output for instant. heating water heater at power-off 790A"). The power supply for the heat pump control unit (3 x 1.5 mm 2 ) and the cable for the power-off signal can be combined in a 5-core cable. For further information regarding power-off, see chapter "Power supply". X3.8 X3.9 X40.L1 Type AWB-AC: Frost stat and/or contact humidistat, cooling or Jumper Type AWB: Jumper Heat pump control unit power supply: Phase L1 X40.? Earth conductor connection X40.N Neutral conductor connection Requires zero volt N/C contact: Closed: Safety chain has continuity Open: Safety chain interrupted; heat pump shut down Breaking capacity 230 V~, 0.15 A Connection: Connected in series, if both safety components are installed. Insert jumper if no safety components are installed. Power supply 230 V~, see from page

39 Installation sequence Electrical connections (cont.) Terminals Function Explanation Secondary pump Connection values Max. output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A r M 3-way diverter valve for "Central heating/dhw heating" In systems without a heating water buffer cylinder, no other heating circuit pump is required (see terminal 212.2). Connect the temperature limiter to restrict the maximum temperature for underfloor heating systems in series (see page 31). Secondary pump connected at the factory; the temperature limiter must be connected on site. Connection values Max. output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A Installation In conjunction with the primary store system: Cylinder primary pump 3-way diverter valve connected at the factory; connect the cylinder primary pump on site in parallel. 2-way shut-off valve M Internal unit: Controller and sensor PCB (sensors) Set the required parameters during commissioning; see from page 68. Sensors Plug Sensor Type F0.1/F0.2 Outside temperature sensor NTC 10 kω F0.2/F0.3 Radio clock receiver DCF F4 Buffer temperature sensor NTC 10 kω F6 (X25.5/X25.6) Cylinder temperature sensor, top NTC 10 kω 39

40 Installation sequence Electrical connections (cont.) Plug Sensor Type F7 Cylinder temperature sensor, bottom NTC 10 kω (X25.7/X25.8) F11 Contact humidistat 24 V Note If a 230 V~ contact humidistat (connection to X3.8/X3.9) is used for cooling, insert a jumper, otherwise the heat pump will not start (message "Protectn device primry"). F13 F14 F16 F20 avg System flow temperature sensor (downstream of the heating water buffer cylinder and external heat source) Flow temperature sensor, cooling circuit (heating circuit without mixer A1/HC1 or separate cooling circuit SKK) Room temperature sensor for separate cooling circuit SKK (required) or for heating/cooling circuit without mixer A1/HC1 (recommended) Boiler water temperature sensor, external heat source KM BUS (wires interchangeable) Use the KM BUS distributor (accessories) if several devices are connected. NTC 10 kω NTC 10 kω NTC 10 kω NTC 10 kω KM BUS subscribers (examples): Extension kit for one heating circuit with mixer M2/HC2 Remote control for Vitotrol 200A or Vitotrol 300B (set the heating circuit assignment at the remote control) Extension EA1, extension AM1 Vitocom communication interface sva Modbus 2 (wires not interchangeable) Connection for 1-phase or 3-phase electricity meter J3 Jumper for terminator Modbus 2 Terminator enabled (delivered condition) Terminator disabled 40

41 Installation sequence Electrical connections (cont.) Plug Sensor Type J4 Jumper for setting master/slave Modbus 2 Heat pump control unit is slave Heat pump control unit is master (delivered condition) X18 Modbus 1 Connection for Vitovent 300-F X24 Connection for LON communication module (see LON communication module installation instructions) X31 Coding card slot Swimming pool heating Note Swimming pool heating is controlled via extension EA1 with KM BUS. Make connections to extension EA1 only according to the following diagram. A filter circuit pump cannot be controlled via the heat pump control unit. Installation 41

42 Installation sequence Electrical connections (cont.) L1 B N C D L1 N A 0-10V f-]a [{A DE [{S DE [{D DE [{{] E H F G M 1~ 1 2 K A Extension EA1 B Power supply 1/N/PE 230 V/50 Hz C Junction box (on site) D Fuses and contactor for circulation pump for swimming pool heating (accessories) E Jumper F 3-way diverter valve for "Swimming pool" (zero volt: heating the heating water buffer cylinder) G Circulation pump for swimming pool heating (accessory) H Thermostat for swimming pool temperature control (floating contact: 230 V~, 0.1 A, accessories) K Connection on controller and sensor PCB 42

43 Installation sequence Electrical connections (cont.) Internal unit: AVI PCB Interface internal unit external unit Plug Component F101 Fuse 1.0 A (slow, L) P202 BUS connection (12 V) to the external unit (type AWB/AWB-AC 201.B10, B13, C10, C13) P203 BUS connection (43 V) to the external unit (type AWB/AWB-AC 201.B04, B07) Note Only one BUS connection should be connected. Do not interchange the BUS connection wires between the internal and external units. Route the BUS connecting cable in the 230 V~ voltage area. Installation External unit: Overview of connections 230 V~: Opening the external unit wiring chamber Type AWB/AWB-AC 201.B B B10 and B13 A A A 43

44 Installation sequence Electrical connections (cont.) 400 V~: Opening the external unit wiring chamber Type AWB/AWB-AC 201.C10 and C13 A A Wiring chamber: BUS connection to the internal unit Note Do not interchange the BUS connection wires between the internal and external units. Compressor power supply 44

45 Installation sequence Electrical connections (cont.) Connecting internal and external units 230 V~ Type AWB/AWB-AC 201.B B B10 and B13 C N L? COMNi? Li? N0 L0 C2 C1 N L?? N L A B C C A B A B C Installation 12V COM COM 43V 12V COM COM 43V 12V COM COM 43V 400 V~ Type AWB/AWB-AC 201.C10 and C13 C2 C1 N L?? N L3 L2L1 A B A External unit wiring chamber (see page 43) B BUS cable between the external and internal unit Recommended cable: 3 x 1.5 mm 2 The cores are not interchangeable. C AVI PCB in the internal unit (see page 29) Note Route BUS cable for internal/external unit in the 230 V~ voltage area. C 12V COM COM 43 V 45

46 Installation sequence Power supply Isolators for non-earthed conductors The mains isolator (if installed) must simultaneously isolate from the mains all non-earthed conductors with a minimum contact separation of 3 mm. We additionally recommend installing an AC/DC-sensitive RCD, type B, for DC (fault) currents that can occur with energy efficient equipment. RCDs of type A must not be used or installed upstream of the RCD type B. If no mains isolator is installed, all nonearthed conductors must be isolated from the mains by the upstream circuit breakers with a minimum contact separation of 3 mm. Danger Incorrectly executed electrical installations can result in injuries from electrical current and in appliance damage. Connect the power supply and implement all safety measures (e.g. RCD circuit) in accordance with the following regulations: IEC VDE regulations [IEE or local regulations] Technical connection requirements specified by the local power supply utility Danger The absence of component earthing can lead to serious injury from electric current if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the building in question. Danger Incorrect core allocation can result in serious injury and damage to the appliance. Never interchange cores "L" and "N". In negotiations with your power supply utility, different supply tariffs for the main power circuits may be offered. Observe the technical connection conditions of the power supply utility. If the compressor and/or instantaneous heating water heater are operated at an economy tariff (power-off), either provide an additional cable (e.g. 3 x 1.5 mm 2 ) for the power-off signal from the distribution board (meter box) to the heat pump control unit or combine the cable for the power-off signal and for the heat pump control unit power supply (3 x 1.5 mm 2 ) in a 5- core cable. The allocation of the power-off (for compressor and/or instantaneous heating water heater) is made via the type of connection and by setting parameters in the heat pump control unit. In Germany, the power supply can be cut off for up to 3 x 2 hours per day (24 h). The heat pump control unit/pcb must be supplied without power-off; tariffs that are subject to possible shutdown must not be used here. 46

47 Installation sequence Power supply (cont.) In conjunction with on-site energy consumption (use of power generated by the PV system to meet own requirements): Note During the power-off period, it is not possible to operate the compressor with power generated on site. Protect the power supply to the heat pump control unit with a fuse of 16 A (max.). For accessories and external components that are not connected to the heat pump control unit, connect the power supply with the same phase as the heat pump control unit, ideally using the same fuse/mcb. Connection to the same fuse/mcb provides additional safety when the power is switched off. Observe the power consumption of the connected consumers. Installation Heat pump control unit power supply (230 V~) 1/N/PE 230 V/50 Hz A F1 T6,3 AH L1 L1?? N N X40 Note This supply must never be blocked. Max. fuse rating 16 A Standard tariff (no optional economy tariff with power-off) Recommended power cable: 3 x 1.5 mm 2 (5 x 1.5 mm 2 with power- OFF) 47

48 Installation sequence Power supply (cont.) External unit power supply (230 V~/400 V~) Economy tariff and power-off can be used. No parameters need to be set when using economy tariff with power-off. The compressor is shut down during the power-off period. During power-off, the diagnostic functions for the external unit are not supported. Note Free terminals for internal use. External unit power supply 230 V~ Type AWB/AWB-AC 201.B B B10 and B13 C N L? COMNi? Li? N0 L0 C2 C1 N L?? N L A A A N L1? B? N L1 B? N L1 B A External unit wiring chamber (see page 43) B Power supply 230 V/50 Hz Type AWB/AWB-AC 201.B B B B13 Recommended power 3 x 2.5 mm 2 3 x 2.5 mm 2 3 x 2.5 mm 2 cable (max. 29 m) (max. 25 m) (max. 20 m) 48 or 3 x 4.0 mm 2 (max. 32 m) 3 x 4.0 mm 2 (max. 20 m) 3 x 6.0 mm 2 (max. 30 m) Fuse protection B20A B20A B20A B32A

49 Installation sequence Power supply (cont.) External unit power supply 400 V~ Type AWB/AWB-AC 201.C10 and C13 A External unit wiring chamber (see page 43) B Power supply 230 V/50 Hz C2 C1 N L?? N L3 L2L1 A? N L3 L2 L1 B Installation Type AWB/AWB-AC 201.C C13 Recommended power cable 5 x 2.5 mm 2 (max. 30 m) 5 x 2.5 mm 2 (max. 30 m) Fuse protection B20A B20A 49

50 Installation sequence Power supply (cont.) Connecting the power cable of the instantaneous heating water heater (only type AWB-AC) Internal unit L1 L1 L1 1/N/PE 230 V/50 Hz A Recommended power cable: 400 V~: 5 x 2.5 mm V~: 7 x 2.5 mm 2 Fuse rating max. 16 A Economy tariff and power-off can be used N N N L3 L2 L1 B 3/N/PE 400 V/50 Hz A N N B A Internal unit wiring chamber (see chapter "Overview of connections":" Internal unit") B Jumpers 50

51 Installation sequence Power supply (cont.) Power supply with power-off Power-OFF without on-site load disconnection The power-off signal is connected directly to the heat pump control unit. The compressor is "forced" off when power-off is enabled. Parameter "Output for instant. heating water heater at power-off 790A" determines whether and at what stage an instantaneous heating water heater (if installed) remains operational during power-off. A X40 X3.7 X3.6 B Note Observe the technical connection conditions of the relevant power supply utility. C Installation D 3 5 (400 V~) 7 (230 V~) 3 3 kwh E 3/N 4 G F 3 kwh 3/N H 4 K 4 Diagram excluding fuses and RCD A Heat pump control unit (internal unit, luster terminals, see chapter "Overview of connections: Internal unit") B Instantaneous heating water heater (if installed) C Heat pump compressor (external unit) D Heat pump control unit power supply (see chapter "Heat pump control unit power supply (230 V~)") E Standard tariff meter F Backup fuse ripple control receiver G Ripple control receiver (contact open: power-off enabled), feed: TNC system 51

52 Installation sequence Power supply (cont.) H Economy tariff meter K Feed: TNC system Power-OFF with on-site load disconnection The power-off signal is connected to the on-site contactor of the economy tariff power supply and to the heat pump control unit. The compressor and instantaneous heating water heater (if installed) are "forced" off when power-off is enabled. Note Observe the technical connection conditions of the relevant power supply utility. A X40 D L 3 X3.7 X3.6 B C 5 (400 V~) 7 (230 V~) kwh kwh 3/N E G 3/N H F K Diagram excluding fuses and RCD A Heat pump control unit (internal unit, luster terminals, see chapter "Overview of connections: Internal unit") B Instantaneous heating water heater (if installed) C Heat pump compressor (external unit) D Heat pump control unit power supply (see chapter "Heat pump control unit power supply (230 V~)") 52 E Standard tariff meter F Backup fuse ripple control receiver G Ripple control receiver (contact open: power-off enabled) with backup fuse H Economy tariff meter K Feed: TNC system L Mains isolator

53 N E1E2 D /D L1 L1 L2 L2 L3 L3 Installation sequence Power supply (cont.) Power supply in conjunction with own energy consumption Without power-off B A A ~ = D F F C F E F Installation G H K kwh kwh kwh L L M M N N A Heat pump B Additional consumers in the household (powered by self-generated electricity) C Electricity meter D Inverter E Isolator for the PV system F Terminal G Double-tariff meter (for special tariff for heat pump) Not permissible in conjunction with PV systems for own energy consumption. 53

54 Installation sequence Power supply (cont.) H Bi-directional meter (for PV systems for own energy consumption): Energy taken from power supply utility and energy fed into power supply utility K Meter with reverse block: For energy generated by PV system L Isolator for the domestic power supply connection (distribution panel) M Distribution panel N Domestic distribution box Closing the heat pump! Please note Seal the appliance so it is soundproof and diffusion-proof. On pipe and hose outlets, ensure the thermal insulation is seated correctly. Danger The absence of component earthing can lead to serious injury from electric current if an electrical fault occurs. Attach earth conductor to front panel and side panel. 54

55 Installation sequence Closing the heat pump (cont.) Fitting the front panel of the internal unit x Note Ensure that the locking screws are tightened before operating. Fitting the side cover of the external unit In reverse order to "Opening the external unit wiring chamber" (see page 43). Installation 55

56 Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance For further information regarding the individual steps, see the page indicated Commissioning steps Inspection steps Maintenance steps Page 1. Opening the heat pump Compiling reports Purging the refrigerant lines and the internal unit with nitrogen (internal unit is filled with nitrogen; positive pressure 1 to 2 bar/0.1 to 0.2 MPa) Check tightness and pressure with dry nitrogen with at least 20 bara/2.0 MPa (max. 43 bara/4.3 MPa) 5. Evacuating the refrigerant lines and internal unit Filling the refrigerant lines and internal unit Checking the refrigerant circuit for leaks Filling and venting on the secondary side Checking expansion vessel and heating circuit pressure Checking electrical connections of the internal unit for firm seating 11. Checking that condensate can drain away freely from the external unit condensate pan 12. Checking the free running of the fan in the external unit Cleaning the external unit heat exchanger (evaporator) Checking thermal insulation of flared connections 15. Checking electrical connections of the external unit for firm seating Closing the heat pump; resetting the circuit breaker/ main fuse 17. Starting the heat pump Commissioning the system... 68

57 Commissioning, inspection, maintenance Steps - commissioning, inspection and (cont.) Commissioning steps Inspection steps Maintenance steps Page 19. Ticking the heat pump type on the type plate of the internal unit (as per external unit type plate) 20. Checking the heat pump for unusual noises (e.g. operating noise of fan, compressor or pump); venting again if required 21. Checking the system function (e.g. actuators, temperatures, heat meter if applicable) Instructing the system user Service 57

58 Commissioning, inspection, maintenance Further details regarding the individual steps Opening the heat pump Danger Contact with 'live' components can lead to serious injury from electric current. Do not touch wiring chambers (heat pump control unit and power connections for internal and external units; see chapter "Overview of connections: Internal unit" and "Overview of connections: External unit"). Before working on the appliances (internal/external unit), isolate the system from the power supply (e.g. by removing a separate mains fuse or by means of a mains isolator) and safeguard against unauthorised reconnection.! Please note Wait at least 30 min between installing and commissioning the appliance to prevent equipment damage. Work on the refrigerant circuit may only be carried out by certified personnel (in accordance with EC Directives 842/2006 and 303/2008). 1. Remove front panel; see page When work is complete, close the heat pump; see page 54. For commissioning the appliance, see also the operating instructions. Danger The absence of component earthing can result in serious injury from electrical current and in component damage in the event of an electrical fault. All earth connectors must be reconnected. Compiling reports Enter the actual values recorded during the commissioning process described below into the reports from page 121 and into the operator's log (if available). 58

59 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Evacuating the refrigerant lines and internal unit! Please note Commissioning is weatherdependent. In the case of high relative humidity or outside temperatures below 0 C, please observe the following: Use nitrogen 5.0 for the pressure test. During evacuation, take suitable steps to keep the surface temperature of the refrigerant lines above 0 C.! Please note Before evacuating the refrigerant lines and the internal unit, check all connections for tightness with leak detection spray. Keep the valves on the external unit shut, and fill the system with nitrogen through the service valve. The test pressure is the max. permissible operating pressure. Danger Direct contact with refrigerant can cause skin damage. Wear safety goggles and protective gloves when working on the refrigerant circuit. Service 59

60 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) A B C E D D F G H K L N O M Example type AWB/AWB-AC 201.B04 A Internal unit B External unit C Hot gas line D Fill valve E Service valve (Schrader valve) For AWB/AWB-AC, type 201.B07, the service valve is located at the liquid line connection. F Liquid line G Fill hose between pressure gauge set and external unit Please note! Do not subject vacuum gauge to positive pressure. 60 H Pressure gauge set K Connection hose between pressure gauge set and vacuum pump L Vacuum pump M Connection hose between pressure gauge set and vacuum gauge N Valve for vacuum gauge O Vacuum gauge 1. Close all valves at the pressure gauge set.

61 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 2. Make all connections, as shown above. Please note! Fill valve D must remain closed. Lastly, connect the end of the fill hose to service valve E. For all connections, counterhold with a second openended spanner. 3. Start the vacuum pump. At the pressure gauge set, open the valve to the vacuum pump and the valve to the hot gas connection. 5. On the pressure gauge set, close the valve to the vacuum pump. Stop the vacuum pump and wait approx. 5 min. If the indication on the vacuum gauge rises, there is a leak. Remove the leak and repeat the process. 6. Close all valves at the pressure gauge set. 7. Remove the vacuum pump and vacuum gauge. 4. After approx. 5 min, open the valve to the vacuum gauge. Leave the vacuum pump running until the indication on the vacuum gauge is almost at "0" (at least 30 min). Note The vacuum pump runtime will depend on the ambient conditions. Filling the refrigerant lines and internal unit Note The external unit is pre-filled with refrigerant R 410A. No topping up is required for line lengths from 3 to 12 m. For lengths of refrigerant lines, see page 17. Refrigerant R 410A may only be topped up in a liquid state. Danger Direct contact with refrigerant can cause skin damage. Wear safety goggles and protective gloves when working on the refrigerant circuit. Service 61

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-A Type AWO-AC 301.B11 to B14 Air/water heat pump with electric drive, 400 V~ For applicability, see the last page VITOCAL 300-A

More information

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer Installation instructions for contractors VIESMANN Mixer extension kit For one heating circuit with mixer Mixer extension kit 5/2017 Safety instructions Please follow these safety instructions closely

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors Installation instructions for contractors VIESMANN Vitodens 200-W Type WB2C, 45 and 60 kw Wall mounted gas condensing boiler Natural gas and LPG version VITODENS 200-W 1/2010 Dispose after installation.

More information

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B

More information

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A Installation instructions for contractors VIESMNN Vitocell 300-V/W Type EVI- DHW cylinder with internal indirect coil 160 to 500 l VITOCELL 300-V/W 3/2017 Dispose after installation. Safety instructions

More information

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation. Installation instructions for contractors PYROMAT ECO PYROMAT ECO 8/2012 Dispose after installation. Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 5/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMNN Extension E1 Part no. 7429 151 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMANN Extension AM1 Part no. 7429 152 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner VITOCROSSAL 300 2/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-G Type BW/BWS 301.A06 to A17, 5.9 to 17.0 kw Type WW 301.A06 to A17, 7.9 to 23.0 kw Heat pump, single and two-stage Type BWC 301.A06

More information

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no Installation and service instructions for contractors VIESMANN Vitotrol 300A Remote control, part no. 7438 364 VITOTROL 300A 3/2010 Please keep safe. Safety instructions Safety instructions Please follow

More information

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater Installation and service instructions for contractors VIESMNN EHE immersion heater 6 kw and 12 kw For installation in HW cylinders For applicability, see the last page EHE immersion heater 9/2014 Please

More information

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner VITOCROSSAL 200 2/2007 Dispose after installation. Safety instructions

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 6/2011 Please keep safe. Safety

More information

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit Installation and service instructions for contractors VIESMANN Vitotrol 200 RF Wireless remote control for one heating circuit For applicability, see the last page VITOTROL 200 RF 3/2011 Please keep safe.

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA Installation and service instructions for contractors VIESMANN Vitocell 340-M/360-M Type SVKA Type SVSA Combi cylinder 750 and 950 litre capacity VITOCELL 340-M/360-M 4/2009 Please keep safe. Safety instructions

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 6/2011 Dispose after installation. Safety instructions Please

More information

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser Vitocal 300-A, type AWC-I and AW-O.1 Product description A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser & High operational reliability,

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 111-W Type B1LA, 6.5 to 35.0 kw Gas condensing storage combi boiler Natural gas and LPG version Gas Council no.: 47-819-23; 47-819-24;

More information

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 2/2013 Please keep safe. Safety

More information

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 100 Type SD1 For applicability, see the last page VITOSOLIC 100 4/2009 Please keep

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITODENS 200-W. for contractors Service instructions for contractors VIESMANN Vitodens 200-W Type WB2B, 4.8 to 35.0 kw Wall mounted gas fired condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJD, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council Number: 47 819 31, 47 819

More information

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O VIESMANN VITOCAL Air/water heat pumps Technical guide VITOCAL 300-A Type AWC-I and AW-O Up to 60 C flow temperature Modulating output range 3 to 9 kw Reversible air source heat pump with electric drive

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJC, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council no.: 47 819 31, 47 819 32

More information

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 111-W 4/2012 Please keep safe. Safety instructions For

More information

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and Installation and service instructions for contractors VIESMANN Solar-Divicon SR Part no. 7419 520 and 7419 521 Safety instructions Please follow these safety instructions closely to prevent accidents and

More information

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service Service instructions Function module FM443 solar module For contractors Read carefully prior to commissioning or service 6 720 615 516-03/2008 GB/IE Contents 1 Safety........................................

More information

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw VIESMANN VITOCAL 00-G Brine/water and water/water heat pump Single and two-stage, from 21 kw Technical guide Heat pump with electric drive for DHW and central heating in mono-mode or dual mode heating

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses. Installation and service instructions for contractors VIESMANN Solar-Divicon and solar pump assembly Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe.

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 200 Type SD4 For applicability, see the last page VITOSOLIC 200 1/2012 Please keep

More information

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 01 CONTENTS Special information 2 General information 3 Safety 5 Appliance description, cleaning, care & maintenance 7 Appliance

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 200-W Type B2HA, B2KA, 3.2 to 35 kw Gas council no. System boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 Combi boilers: 47-819-28;

More information

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 100-W 1/2012 Please keep safe. Safety instructions For

More information

Installation Instructions VITOTRONIC 300

Installation Instructions VITOTRONIC 300 Installation Instructions Vitotronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Part No. Z001 231 VITOTRONIC 300 Certified

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors Installation instructions for contractors VIESMANN Vitomax 200-HW Type M238 Oil/gas fired high pressure hot water boiler Combustion output 4.0 to 18.2 MW VITOMAX 200-HW 6/2007 Dispose after installation.

More information

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. Service instructions. MatriX radiant burner. for contractors Service instructions for contractors VIESMANN MatriX radiant burner Type VMIII Pressure-jet gas burner for the Vitocrossal 300, type CT3B Rated heating output 187 to 314 kw For applicability, see the last

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE 780EN www.caleffi.com Recess Mounted Heat Interface Unit - SATK series SATK0-60 series INSTRUCTIS FOR INSTALLATI, COMMISSIING AND MAINTENANCE Function The SATK series HIU allows independent control of

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro

Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro 2006/01 Content Important Information 1. Notes... 3 1.1 CE - Labeling... 3 1.2

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

SD2. Differential Controller. Operating and Installation Instructions F2 72.3 SD2 Differential Controller Operating and Installation Instructions F2 72.3 i Please follow the safety information and read these Instructions carefully before putting the system into operation. Safety

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA. OWNER S MANUAL Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750 Proudly Made in the USA support@aquacomfort.com 888-475-7443 Manufacturing High Quality, High Efficiency Heat

More information

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

VIESMANN. Operating instructions VITOTRONIC 200. for the system user Operating instructions for the system user VIESMANN Heating system with weather-compensated control unit Vitotronic 200, type KO1B, KO2B or KW6B VITOTRONIC 200 12/2012 Please keep safe. Safety instructions

More information

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery Datasheet For part no. and prices: see pricelist VITOVENT 300-F Mechanical ventilation system with heat recovery for demanddependent

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

NIBE SPLIT ACVM 270 Air/water heat pump

NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 system with complete indoor module NIBE SPLIT ACVM 270 is a complete modern heat pump system that offers effective technical energy saving and

More information

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200 Series FCU1x00 Installation instructions and operating manual Sauna control system FCU1000 / FCU1200 only sauna FCU1000 additional humidity FCU1200 Doc-ID: B_M_FCU1xxx-A5_EN Version: V 1.06 certificated

More information

Installation Instructions VITOTRONIC 200

Installation Instructions VITOTRONIC 200 Installation Instructions Please file in Service Binder Vitotronic 200 Model KW2 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits VITOTRONIC

More information

Installation plan Commercial Washing Machine PW 413 PW 418

Installation plan Commercial Washing Machine PW 413 PW 418 Installation plan Commercial Washing Machine PW 413 PW 418 To avoid the risk of accidents or damage to the machine, it is essential to read these instructions before it is installed and used for the first

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

3-way switching valve

3-way switching valve Operating Manual UK 3-way switching valve for domestic hot water charging USV 1" AG USV 5/4" AG USV 6/4" IG UK805189 / 201109 Translation of the original instruction manual Please read first This operating

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first totally integrated multiple boiler management control. USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE Follow

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. Edition 06.14 GB Operating and installation instructions Lago FB digital remote control Translation from the German 2014 Elster GmbH Safety Please read and keep in a safe place Please read through these

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

Planning guide. Atec.

Planning guide. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Starting current with soft starter Fuse protection

Starting current with soft starter Fuse protection Data sheet LIH 26TE High temperature air-to-water heat pump Max. flow temperature: 75 C Casing colour: White (similar to RAL 9003) Brown-red design screen (RAL 3011) Heat pump for heating purposes for

More information

Friwa Compact. Operating instructions EN

Friwa Compact. Operating instructions EN Operating instructions EN Version 1.1 / Edition 09/2013 Contents 1 Key background information... 3 1.1 Limitation of liability... 3 1.2 Responsibilities of the operator... 3 1.3 Documentation... 3 1.3.1

More information

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time Operating instructions Page 14 Refrigerator Read the operating instructions before switching on for the first time 7085 039-00 LKv 5710 Content Disposal notes... 14 Description of the appliance... 14 Safety

More information

EN Z Subject to change due to technical improvements! Operating instructions

EN Z Subject to change due to technical improvements! Operating instructions SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE Operating instructions Temperature differential controller 3 inputs, 1 output These operating instructions are part of the product. Read

More information

PCR-300 PCR-300 RC. Installation and Operating Instructions

PCR-300 PCR-300 RC. Installation and Operating Instructions PCR-300 PCR-300 RC Installation and Operating Instructions Electronic refrigeration control EB-PCR-04 EN1H-1924GE23 R1207 TABLE OF CONTENTS 11 Unpacking the unit and conditions of use 3 12 General instructions

More information

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors Installation and service instructions for contractors VIESMANN Vitodens 343-F Type WS4A Compact Energy Tower with a gas fired condensing boiler as compact model Natural gas and LPG version (GC no) 47-819-08

More information

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until)

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until) Data sheet LA 16MS Air-to-water heat pump with deflector hoods Max. flow temperature: 58 C Casing colour: White aluminium (similar to RAL 9006) Air-to-water heat pump for outdoor installation with external

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B VIESMANN VITOLIGNO 300-P Pellet boiler 4to48kW Datasheet For part no. and prices: see pricelist File in: Vitotec folder, register 12 VITOLIGNO 300-P Type VL3B Boiler for wood pellets 8/2007 Product information

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

O CRC100. Comfort Room Controller (2015/01) en

O CRC100. Comfort Room Controller (2015/01) en 6 720 906 767-00.1O Comfort Room Controller 100 6 720 806 769 (2015/01) en 2 Contents Contents 1 Explanation of symbols and safety instructions..................... 3 1.1 Explanation of symbols.....................................

More information

SUN EQUINOX HEATING SYSTEMS

SUN EQUINOX HEATING SYSTEMS SUN EQUINOX HEATING SYSTEMS HIGH-EFFICIENCY HOT WATER SOLUTIONS INSTALLATION & OPERATION MANUAL Production Number: Customer Contact Information Other Resources 260-65-5605 http://www.solarusagenow.com

More information

Operating instructions Page 12

Operating instructions Page 12 Operating instructions Page 12 Refrigerator with explosion-proof interior container Read the operating instructions before switching on for the first time 7082 271-00 LKEXv 910 Disposal notes The appliance

More information

Alpha CombiMax 350 and 600

Alpha CombiMax 350 and 600 Installation and Servicing Instructions Alpha CombiMax 350 and 600 Unvented Hot Water Store for use with the Alpha 240/280 Range of Gas Fired Combination Boilers For Technical help or for Service call...

More information

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user Operating instructions for the system user VIESMANN Heating system with the Vitotronic 200 control unit, type HO1B, for weathercompensated mode VITODENS VITOLADENS VITOPEND 10/2013 Please keep safe. Safety

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout c. All contestants are required to remain in the contest area until the contest has been torn down and excused by the Chairperson. Note: Your contest may also require a hard copy of your résumé as part

More information