VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors

Size: px
Start display at page:

Download "VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors"

Transcription

1 Installation and service instructions for contractors VIESMANN Vitocal 300-G Type BW/BWS 301.A06 to A17, 5.9 to 17.0 kw Type WW 301.A06 to A17, 7.9 to 23.0 kw Heat pump, single and two-stage Type BWC 301.A06 to A17, 5.9 to 17 kw Type WWC 301.A06 to A17, 7.9 to 23 kw Heat pump, single stage For applicability, see the last page VITOCAL 300-G 12/2010 Please keep safe.

2 Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Observe the following when working on this system National installation requirements All legal instructions regarding the prevention of accidents, All legal instructions regarding environmental protection, The Code of Practice of relevant trade associations All current safety regulations as defined by DIN, EN, DVGW, VDE and all locally applicable standards a ÖNORM, EN and ÖVE c SEV, SUVA, SVTI and SWKI Working on the system Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing the separate fuse or by means of a main isolator. Note In addition to the control circuit, there may be several power circuits. Safeguard the system against unauthorised reconnection. Please note! Electronic modules can be damaged by electrostatic discharges. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads. 2

3 Safety instructions Safety instructions (cont.) Repair work! Please note Repairing components that fulfil a safety function can compromise the safe operation of your system. Replace faulty components only with original Viessmann spare parts. Auxiliary components, spare and wearing parts Please note! Spare and wearing parts that have not been tested together with the system can compromise its function. Installing non-authorised components and making non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only original spare parts supplied or approved by Viessmann. 3

4 Index Installation instructions Preparing for installation General information - electrical connection... 6 Installation... 6 Overview of possible system schemes Primary circuit, type BW 301.A, BWC 301.A (brine/water) Primary circuit, type WW 301.A, WWC 301.A (water/water) Primary circuit, type BW 301.A + BWS 301.A (two-stage, brine/water) Primary circuit, type WW 301.A + BWS 301.A (two-stage, water/water) DHW heating Integration of the two-stage version in the system examples Integrating a heat pump cascade into the system examples System example 1, ID: _1008_ System example 2, ID: _1008_ System example 3, ID: _1008_ Installation sequence Siting the heat pump Hydraulic connections Electrical connections Power supply Connecting to terminals X3.8/X Closing the heat pump Checking diaphragm grommets Service instructions Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance Further details regarding the individual steps Troubleshooting Repairs Parts lists Parts lists Overview of the assemblies Parts not shown Assembly, casing Assembly, hydraulics Assembly, heat pump module Assembly, electrical equipment Index

5 Index Index (cont.) Commissioning/service reports Specification Appendix Heat pump commissioning order Certificates Declaration of conformity Keyword index

6 Preparing for installation General information - electrical connection Connecting cables, heat pump stage 1 stage 2: See page 71. Electrical connection of system components (pumps, mixers, valves, alarm facilities, contactors, function extensions, sensors, etc.): These connections are made inside the heat pump control unit. Observe information from page 72. Power supply: The number of power cables from the distribution board (meter box) to the heat pump control unit and to the control panel depends on the system version and tariffs used. These connections are made inside the heat pump control panel. Observe information from page 94. Installation! Please note Avoid damaging the appliance during transportation. Never put weight on top of the appliance.! Please note If the compressor is at a steep angle in the heat pump, lubricant will enter the refrigerant circuit and damage the appliance. Max. tilting angle 45. Installation room requirements Please note! The installation room must be dry and free from the risk of frost. Ensure ambient temperatures of 0 to 35 ºC. Please note! Avoid risk of explosion due to dust, gases and vapours in the installation room. 6 Please note! Observe the permissible floor load. Total weight BW 301.A kg BWS 301.A kg BWC 301.A kg BW 301.A kg BWS 301.A kg BWC 301.A kg BW 301.A kg BWS 301.A kg BWC 301.A kg BW 301.A kg BWS 301.A kg BWC 301.A kg

7 Preparing for installation Installation (cont.) BW 301.A17 BWS 301.A17 BWC 301.A kg 144 kg 158 kg To prevent structure-borne noise, never site the appliance on ceilings with wooden joists (e.g. in the attic). Level the appliance horizontally. If the adjustable feet are used to compensate for an uneven floor (max. 10 mm), the pressure load on the feet must be distributed evenly. Observe the required floor area and minimum room volume (to DIN EN 378). Type BW 301.A06 BWS 301.A06 BWC 301.A06 BW 301.A08 BWS 301.A08 BWC 301.A08 BW 301.A10 BWS 301.A10 BWC 301.A10 BW 301.A13 BWS 301.A13 BWC 301.A13 BW 301.A17 BWS 301.A17 BWC 301.A17 Min. space requirement 3.5 m m m m m 3 Observe required minimum clearances: Single stage (type BW 301.A, BWC 301.A) B 1500 A 400 Installation 7

8 Preparing for installation Installation (cont.) Two-stage (type BW 301.A + BWS 301.A) A B = A With hydraulic module (accessory, for installation above the heat pump): 340 mm Without hydraulic module: subject to on-site installation and location B With AC-Box (accessory, for installation to the left of the heat pump): 400 mm (+ width of the AC-Box) Without AC-Box: 100 mm 8

9 Preparing for installation Installation (cont.) Information on the use of accessories for a heating/cooling circuit or separate cooling circuit AC-Box for active cooling function The AC-Box can only be used up to a rated heating output of 17.6 kw. For higher rated heating outputs, install all the components required on site (with correspondingly sized plate heat exchanger) for the heating/cooling circuit or the separate cooling circuit. NC-Box for natural cooling function The NC-Box can only be used up to a rated heating output of 16 kw. For higher rated heating outputs, install all the components required on site (with correspondingly sized plate heat exchanger) for the heating/cooling circuit or the separate cooling circuit. In two-stage heat pumps, the NC-Box cannot be installed immediately above the heat pump. The hydraulic connection lines between heat pump stage 1 and heat pump stage 2 are installed above the heat pumps. Installation 9

10 Preparing for installation Installation (cont.) Requirements for on-site connections Single stage (type BW 301.A, BWC 301.A) V < 42 V

11 Preparing for installation Installation (cont.) Two-stage (type BW 301.A + BWS 301.A) V < 42 V V < 42 V Installation Install hydraulic connections on site stress-free. Line lengths in the heat pump plus wall clearance: Type BW 301.A and BWC BWS 301.A 301.A Heat pump control unit power supply (230 V~) 1.0 m A connecting cable is used for the power supply Compressor power supply 1.0 m 1.0 m (400 V~) Additional power cables 1.0 m Connecting cable 11

12 Preparing for installation Installation (cont.) Recommended power cables for all types: Heat pump control unit (230 V~): 3 x 1.5 mm 2 (5 x 1.5 mm 2 with power- OFF) Compressor (400 V~): 5 x 2.5 mm 2 Max. lead length: 50 m Instantaneous heating water heater (400 V~, if installed): 5 x 2.5 mm 2 Max. lead length: 50 m Overview of possible system schemes The following table provides an overview of all possible system schemes. Selected system schemes are explained using system examples (see from page 42). Components System scheme (parameter 7000) Heating circuit A1 X X X X X X M2 X X X X X X X X M3 X X X X DHW cylinder X X X X X X Heating water buffer cylinder 0 0 X X X X X X X X External heat source 0 0 *1 0 * Instantaneous heating water heater Swimming pool Solar thermal system (with integral solar control module of the Vitotronic or with the Vitosolic 200) Cooling A M M Sep. cooling circuit *1 Only in conjunction with a heating water buffer cylinder. 12

13 Preparing for installation Overview of possible system schemes (cont.) X Components selected. 0 Components can be added. Installation 13

14 P1 Hydraulic installation scheme KM BUS X3.8; V-- P1 Preparing for installation Primary circuit, type BW 301.A, BWC 301.A (brine/water) P--2/X3.8;3.9-- Note Type BWC 301.A is shown. The circulation pumps are installed and connected at the factory (primary pump qt, secondary pump 6, circulation pump for cylinder heating 7, instantaneous heating water heater 4 optional). In type BW 301.A, no circulation pumps are installed at the factory. For the connection of primary pump qt, see "Primary circuit, type BW 301.A + BWS 301" (page 19). 14

15 Primary circuit, type BW 301.A, BWC 301.A (cont.) Preparing for installation Required equipment Pos. Description 1 Heat pump 2 Heat pump control unit qt Primary pump wp Brine accessory pack wq Pressure switch, primary circuit ww Brine distributor for geothermal probes/collectors wu Geothermal probes/collectors Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. Installation 230 V / 50 Hz X3.9 X1. X V; 0.15 A 21 15

16 Hydraulic installation scheme /X3.8; X3.8; KM BUS V-- P1 P1 Preparing for installation Primary circuit, type WW 301.A, WWC 301.A (water/water) /X3.8;3.9-- P /X3.3; / X3.3;3.4-- Note Type WWC 301.A is shown. The circulation pumps are installed and connected at the factory (primary pump qt, secondary pump 6, circulation pump for cylinder heating 7, instantaneous heating water heater 4 optional). In type WW 301.A, no circulation pumps are installed at the factory. For the connection, see "Electrical installation scheme". 16

17 Primary circuit, type WW 301.A, WWC 301.A (cont.) Preparing for installation Equipment required Pos. Description 1 Heat pump 2 Heat pump control unit qt Primary pump qo Frost stat, primary circuit wp Brine accessory pack wq Pressure switch, primary circuit ww Separating heat exchanger, primary circuit we Flow limiter, well circuit (remove jumper when connecting) wr Dirt trap wz Well pump (suction pump for groundwater; connect via on-site contactor with fuse protection) 230 V connection: See page V connection: See page 18 wu Delivery well wi Return well Installation Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 17

18 Preparing for installation Primary circuit, type WW 301.A, WWC 301.A (cont.) With well pump connection 230 V~ X1. X2.N L N 200 W M 1~ UP 15 L1 N 230 V / 50 Hz X3.3 X1. X3.4 K1 M 1~ UP V; 2 ma 23 X3.9 X1. X V; 0.15 A v; 0.15 A 19 Well pump on-site connection 400 V~ 230 V / 50 Hz X1. X2.N L N L1 L2 200 W M 1~ L3 UP 15 K1 M 3~ UP 26 18

19 P1 P1 P1 P1 Preparing for installation Primary circuit, type BW 301.A + BWS 301.A (two-stage, brine/water) With two primary pumps Hydraulic installation scheme /X3.8;3.9-- P 16 --F F / / Installation X3.8; F F V-- --KM BUS

20 Preparing for installation Primary circuit, type BW 301.A + BWS 301.A (cont.) Equipment required Pos. Description 1 Heat pump stage 1 2 Heat pump control unit 9 Heat pump stage 2 qt Primary pump, heat pump stage 1 qz Flow temperature sensor, primary circuit qu Return temperature sensor, primary circuit wp Brine accessory pack wq Pressure switch, primary circuit ww Brine distributor, geothermal probes/collectors wt Primary pump, heat pump stage 2 wu Geothermal probes/collectors Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 2 X1. X2.N W M 1~ UP V / 50 Hz X1. X2.N W M 1~ UP 25 X3.9 X1. X V; 0.15 A 21 Low voltage PT500 F PT500 F3 17

21 P1 P1 P1 P1 Primary circuit, type BW 301.A + BWS 301.A (cont.) With a common primary pump Note If heat pumps stage 1 and 2 (types BW 301.A + BWS 301.A) are installed with different rated heating outputs, the different flow rates mean that two primary pumps must be used (see page 19). Hydraulic installation scheme Preparing for installation /X3.8;3.9-- P 16 --F2-- Installation --F / X3.8; F F V-- --KM BUS-- 21

22 Preparing for installation Primary circuit, type BW 301.A + BWS 301.A (cont.) Equipment required Pos. Description 1 Heat pump stage 1 2 Heat pump control unit 9 Heat pump stage 2 qt Common primary pump qz Primary circuit flow temperature sensor (for installation, see page 90) qu Primary circuit return temperature sensor (for installation, see page 90) wp Brine accessory pack wq Pressure switch, primary circuit ww Brine distributor, geothermal probes/collectors wu Geothermal probes/collectors Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 22

23 Primary circuit, type BW 301.A + BWS 301.A (cont.) Preparing for installation V / 50 Hz X1. X2.N W M 1~ UP 15 X3.9 X1. X V; 0.15 A 21 Installation Low voltage 12 PT500 F PT500 F

24 P1 P1 P1 P1 P1 P1 Preparing for installation Primary circuit, type WW 301.A + BWS 301.A (two-stage, water/water) With two primary pumps Hydraulic installation scheme /X3.8;3.9-- P 16 --F /X3.3; F / / /X3.8; /211.1; X3.3: X3.8; F F V-- --KM BUS

25 Primary circuit, type WW 301.A + BWS 301.A (cont.) Preparing for installation Equipment required Pos. Description 1 Heat pump stage 1 2 Heat pump control unit 9 Heat pump stage 2 qt Primary pump, heat pump stage 1 qz Primary circuit flow temperature sensor (for installation, see page 90) qu Primary circuit return temperature sensor (for installation, see page 90) qo Frost stat, primary circuit wp Brine accessory pack wq Pressure switch, primary circuit ww Heat exchanger, primary circuit we Flow limiter, well circuit (remove jumper before connecting) wr Dirt trap wt Primary pump, heat pump stage 2 wz Well pump (suction pump for groundwater; connect via on-site contactor with fuse protection) 230 V connection: See page V connection: See pages 31, 27 wu Delivery well wi Return well Installation Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 25

26 Preparing for installation Primary circuit, type WW 301.A + BWS 301.A (cont.) Well pump on-site connection 230 V~ 2 X1. X2.N W M 1~ UP V / 50 Hz X1. X2.N W M 1~ UP 25 L1 N X3.1 X2.N K1 K2 K3 M 1~ UP 26 26

27 Primary circuit, type WW 301.A + BWS 301.A (cont.) Preparing for installation Well pump on-site connection 400 V 2 X1. X2.N W M 1~ UP V / 50 Hz X1. X2.N W M 1~ UP 25 X3.1 X2.N K1 K2 L1 L2 L3 Installation K1 M 3~ UP 26 Connecting the sensors and limiters V / 50 Hz X3.3 X1. X3.4 X3.8 X1. X V; 2 ma V; 0.15 A v; 0.15 A 19 Low voltage 12 PT500 F PT500 F

28 Preparing for installation Primary circuit, type WW 301.A + BWS 301.A (cont.) With a common primary pump Note If heat pumps stage 1 and 2 (types WW 301.A + BWS 301.A) are installed with different rated heating outputs, the different flow rates mean that two primary pumps must be used (see page 24). 28

29 Hydraulic installation scheme P1 P1 --2/X3.8; P1 P1 P1 P1 Primary circuit, type WW 301.A + BWS 301.A (cont.) Preparing for installation P 16 --F /X3.3; / F Installation /X3.8; /211.1; F2-- --X3.8; F V-- --KM BUS-- 29

30 Preparing for installation Primary circuit, type WW 301.A + BWS 301.A (cont.) Equipment required Pos. Description 1 Heat pump stage 1 2 Heat pump control unit 9 Heat pump stage 2 qt Common primary pump qz Primary circuit flow temperature sensor (for installation, see page 90) qu Primary circuit return temperature sensor (for installation, see page 90) qo Frost stat, primary circuit wp Brine accessory pack wq Pressure switch, primary circuit ww Heat exchanger, primary circuit we Flow limiter, well circuit (remove jumper before connecting) wr Dirt trap wz Well pump (suction pump for groundwater; connect via on-site contactor with fuse protection) 230 V connection: See page V connection: See pages 31, 27 wu Delivery well wi Return well Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 30

31 Primary circuit, type WW 301.A + BWS 301.A (cont.) Preparing for installation Well pump on-site connection 400 V V / 50 Hz X1. X2.N X2.N M 1~ 200 W UP L1 L2 L3 M 3~ UP 26 Installation Connecting the sensors and limiters V / 50 Hz X3.3 X1. X3.4 X3.8 X1. X V; 2 ma V; 0.15 A v; 0.15 A 19 Low voltage 12 PT500 F PT500 F

32 Preparing for installation DHW heating DHW cylinder with internal indirect coil Hydraulic installation scheme WW / / /F /F KW 1 --F F V-- --KM BUS-- Note Type BWC 301.A is shown. The circulation pumps are installed and connected at the factory (primary pump qt, secondary pump 6, circulation pump for cylinder heating 7, instantaneous heating water heater 4 optional). In type BW 301.A, no circulation pumps are installed at the factory. For the connection, see "System examples" (from page 42). 32

33 Preparing for installation DHW heating (cont.) Required equipment Pos. Description 6 Secondary pump 7 Circulation pump for cylinder heating ep DHW cylinder eq Cylinder temperature sensor, bottom (optional) ew Cylinder temperature sensor, top eu DHW circulation pump (optional) rp Immersion heater (create electrical circuit on site. Can only be used as an alternative to the external heat source for DHW reheating.) Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. Installation 2 X1. X2.N W M 1~ ZP V / 50 Hz X2.N A L1 L2 L3 N 40 Low voltage F6 PT500 STS 31 PT500 F7 STS 32 A On-site contactor 33

34 Preparing for installation DHW heating (cont.) DHW cylinder with primary store system Hydraulic installation scheme WW / /F / X / KW 1 --F V-- --KM BUS-- Note Type BWC 301.A is shown. The circulation pumps are installed and connected at the factory (primary pump qt, secondary pump 6, circulation pump for cylinder heating 7, instantaneous heating water heater 4 optional). In type BW 301.A, no circulation pumps are installed at the factory. For the connection, see "System examples" (from page 42). 34

35 Preparing for installation DHW heating (cont.) Required equipment Pos. Description 6 Secondary pump 7 Circulation pump for cylinder heating ep DHW cylinder ew Cylinder temperature sensor ee Cylinder primary pump (DHW side) er Plate heat exchanger et Flow limiter ez Motorised two-way valve, normally closed eu DHW circulation pump Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. Installation 2 X1. X2.N W M 1~ ZP V / 50 Hz X1. X2.N L N 130 W M 1~ 130 W M 1~ UPSB UP 7 33 M 1~ 36 Low voltage F6 PT500 STS 32 35

36 Preparing for installation DHW heating (cont.) Required parameter settings for DHW heating Set the required parameters during commissioning; see from page 108. Parameter Setting "System definition" "System scheme 7000" "0" / "2" / "4" / "6" / "8" / "10" DHW heating: "Time program DHW" Set time program (see operating instructions) "Time prog. DHW circ." Set time program (see operating instructions) "DHW" "Enable booster heaters for DHW heating 6014" "1" "Enable electric heaters for DHW heating 6015" "1" "External heat source" "Enable external heat source for DHW heating "0" 7B0D" Integration of the two-stage version in the system examples Note A two-stage heat pump comprises the heat pump stage 1 (type BW 301.A or WW 301.A) and the heat pump stage 2 (type BWS 301.A). Connect return DHW cylinder only to heat pump stage 1. The partial scheme can be integrated into the system examples via the interfaces indicated. 36

37 P1 P1 Integration of the two-stage version in the (cont.) Hydraulic installation scheme Preparing for installation C H W / / /F / / P --2/F / / /F X3.8; F0-- --F2-- --F V-- --KM BUS-- Installation 37

38 Preparing for installation Integration of the two-stage version in the (cont.) C Interface to the separate cooling circuit or heating/cooling circuit H Interface to the heating circuits or the heating water buffer cylinder P Interface to the primary circuit W Interface to the DHW cylinder Equipment required Pos. Description Heat source 1 Heat pump stage 1 2 Heat pump control unit 3 Outside temperature sensor 5 Circulation pump for cylinder heating (heating water side), heat pump stage 1 6 Secondary pump, heat pump stage 1 9 Heat pump stage 2 qp Secondary pump, heat pump stage 2 qq Circulation pump for cylinder heating (heating water side), heat pump stage 2 qw Safety equipment block with safety assembly qe Expansion vessel qt Primary pump, heat pump stage 1 qz Flow temperature sensor, primary circuit qu Return temperature sensor, primary circuit wt Primary pump, heat pump stage 2 Integrating a heat pump cascade into the system examples A heat pump cascade consists of a lead appliance and lag heat pumps. Each lag heat pump has a heat pump control unit. Both lead appliance and lag heat pumps can have 2 stages. The lead appliance regulates the heat pump operation within the cascade. Up to max. 3 lag heat pumps when connecting via KM-BUS in conjunction with the external extension H1 (see page 92 and separate service instructions for heat pump control unit Vitotronic 200). Up to max. 4 lag heat pumps when connecting via LON (see separate service instructions for heat pump control unit Vitotronic 200). 38

39 Preparing for installation Integrating a heat pump cascade into the system (cont.) The following communication modules (accessories) must be fitted in the heat pump control units: LON communication module for the cascade in the lead appliance LON communication module in lag heat pumps The partial scheme can be integrated into the system examples via the interfaces indicated. Installation 39

40 Preparing for installation Integrating a heat pump cascade into the system (cont.) Hydraulic installation scheme example: Heat pump cascade with two-stage heat pumps W H P C qp 6 qp 6 qp 6 qp 6 qq 5 qq 5 qq 5 qq qz qz qz qz qu qu qu qu wt qt wt qt wt qt wt qt IV III II I 5 40

41 Preparing for installation Integrating a heat pump cascade into the system (cont.) C H P Interface to the separate cooling circuit or heating/cooling circuit Interface to the heating circuits or the heating water buffer cylinder Interface to the primary circuit W I Interface to the DHW cylinder Lead appliance (two-stage) of the heat pump cascade II to IV Lag heat pumps 1 to 3, each two-stage Equipment required Pos. Description Heat source 1 Heat pump stage 1 2 Heat pump control unit 3 Outside temperature sensor 5 Circulation pump for cylinder heating (heating water side), heat pump stage 1 6 Secondary pump, heat pump stage 1 9 Heat pump stage 2 qp Secondary pump, heat pump stage 2 qq Circulation pump for cylinder heating (heating water side), heat pump stage 2 (optional) qt Primary pump, heat pump stage 1 qz Primary circuit flow temperature sensor (for installation, see page 90) qu Primary circuit return temperature sensor (for installation, see page 90) wt Primary pump, heat pump stage 2 Installation Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. 41

42 Preparing for installation Integrating a heat pump cascade into the system (cont.) 2 X1. X2.N W M 1~ UP V / 50 Hz X1. X2.N X1. X2.N X1. X2.N W M 1~ 130 W M 1~ 200 W M 1~ UP 5 UP 6 UP 15 X1. X2.N W M 1~ UP 25 X1. X2.N W M 1~ UP Pt500 F2 16 Low voltage 13 Pt500 F3 17 Ni500 F0 ATS 3 System example 1, ID: _1008_01 Note Type BW 301.A is shown. In types BWC 301.A and WWC 301.A, the circulation pumps (primary pump, secondary pump and circulation pump for cylinder heating) are installed and connected at the factory. Setting system scheme 2 Single stage heat pump, type BW 301.A 1 underfloor heating circuit without mixer (A1) DHW heating Natural cooling function at heating circuit A1 42

43 System example 1, ID: _1008_01 (cont.) Preparing for installation Note This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for local engineering. Installation 43

44 P1 Preparing for installation System example 1, ID: _1008_01 (cont.) Hydraulic installation scheme / / /X3.8; A / WW --4/ KW /F / /F / B/ / /X3.8; X3.8; F KM BUS V F

45 System example 1, ID: _1008_01 (cont.) Preparing for installation Pos. Description 1 Heat pump Vitocal 300-G 2 Instantaneous heating water heater, 3, 6, or 9 kw 4 Heat pump control unit Vitotronic 200, type WO1A 5 Primary pump (integrated in type BWC) 6 Secondary pump (integrated in type BWC) 7 Circulation pump for cylinder heating UPSB (integrated in type BWC) 8 Safety equipment block with safety assembly (in standard delivery for type BWC) 9 Expansion vessel qp Outside temperature sensor ATS qq KM BUS distributor qw Geothermal probe/geothermal collector qe Brine distributor for geothermal probes/geothermal collectors qr Brine accessory pack qt Brine circuit pressure switch DHW heating wp DHW cylinder wq Cylinder temperature sensor STS ww DHW circulation pump ZP Heating circuit without mixer A1 ep Underfloor heating circuit A1 eq Vitotrol 200A remote control ew Overflow valve ee Temperature limiter to limit the maximum temperature of underfloor heating systems Natural cooling function (NC) rp NC-Box with mixer rq Primary cooling circuit pump rw Secondary cooling circuit pump re Contact humidistat rr 3-way diverter valve rt 2-way valve rz 3-way diverter valve Installation 45

46 Preparing for installation System example 1, ID: _1008_01 (cont.) Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. For information regarding the power supply, see page X1. NC 40 X2.N 200 W M X1. UP 5 1~ X2.N 130 W X1. M 1~ UPSB 7 X2.N 230 V/ 50 Hz W M X1. ZP 22 1~ X2.N W M X1. UP 6 1~ X2.N X2.N A B A L1 L2 L3 N 400 V, 50 Hz 3 / N / PE 2 X3.18 X2.1 X1.1 <16 A L1 N 230 V / 50 Hz X X1. X Low voltage H1 HK A1 31 A Plug ach connected to the cable harness B Control module for instantaneous heating water heater 46

47 System example 1, ID: _1008_01 (cont.) Preparing for installation 4 Low voltage PT500 F6 STS 21 F0 Ni500 ATS 10 Control unit power supply Compressor power supply A X3.18 X2.1 X1.1 L1 N 1 / N / PE 230 V, 50 Hz A Mains terminals on the cross connect PCB L1 L2 L3 PE 3 / PE 400 V, 50 Hz Installation Required parameter setting Set the required parameters during commissioning; see from page

48 Preparing for installation System example 1, ID: _1008_01 (cont.) Parameter Setting "System definition" "System scheme 7000" "6" "Cooling" "Cooling 7100" "2" "Cooling circuit 7101" "1" DHW heating: "Time program DHW" Set time program (see operating instructions) "Time prog. DHW circ." Set time program (see operating instructions) "DHW" "Enable booster heaters for DHW heating 6014" "1" "Electr booster heater" "Enable instantaneous heating water heater 7900" "1" If required, "Enable instant. heating water heater for "1" central heating 7902" "Output for instant. heating water heater at power- OFF 790A" Remote control: "Heating circuit 1" "Remote control 2003" "1" "1" for 3 kw "2" for 6 kw "3" for 9 kw System example 2, ID: _1008_01 Note Type BW 301.A is shown. In types BWC 301.A and WWC 301.A, the circulation pumps (primary pump, secondary pump and circulation pump for cylinder heating) are installed and connected at the factory. Setting system scheme 6 Single stage heat pump, type BW 301.A 1 heating circuit without mixer (A1) 1 heating circuit with mixer (M2) DHW heating Heating water buffer cylinder Active cooling function on separate cooling circuit Note This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for local engineering. 48

49 ---4/ P1 - System example 2, ID: _1008_01 (cont.) Hydraulic installation scheme Preparing for installation / / /F /F / / /F A1 M / /225.2; / /F13-- Installation WW / / /F / /F /F B/137-- KW /X3.8; F F6-- --F0-- --F F X3.8; V-- --KM BUS F4-- --F ;

50 Preparing for installation System example 2, ID: _1008_01 (cont.) Pos. Description 1 Heat pump Vitocal 300-G 2 Instantaneous heating water heater, 3, 6, or 9 kw 4 Heat pump control unit Vitotronic 200, type WO1A 5 Primary pump (integrated in type BWC) 6 Secondary pump (integrated in type BWC) 7 Circulation pump, cylinder heating UPSB (integrated in type BWC) 8 Safety equipment block with safety assembly (in standard delivery for type BWC) 9 Expansion vessel qp Outside temperature sensor ATS qq KM BUS distributor qw Geothermal probe/geothermal collector qe Brine distributor for geothermal probes/geothermal collectors qr Brine accessory pack qt Brine circuit pressure switch DHW heating wp DHW cylinder wq Cylinder temperature sensor STS ww DHW circulation pump ZP Heating water buffer cylinder ep Heating water buffer cylinder eq Buffer temperature sensor PTS ew Flow temperature sensor, system VTS Active cooling function (AC) qz AC-Box (active cooling) rp Separate cooling circuit rq Room temperature sensor, separate cooling circuit RTS rw Flow temperature sensor, separate cooling circuit VTS re Fan convector rr Condensate drain rt Circulation pump, UP AC Heating circuit with mixer M2 tp Underfloor heating circuit tq Vitotrol 200A remote control te Flow temperature sensor VTS M2 tr Temperature limiter to limit the maximum temperature of underfloor heating systems tt Heating circuit pump, UP M2 tz Mixer motor M2 Heating circuit without mixer A1 50

51 System example 2, ID: _1008_01 (cont.) Preparing for installation Pos. zp zq ze Description Radiator heating circuit Vitotrol 200A remote control Heating circuit pump, UP A1 Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. For information regarding the power supply, see page 94. Installation 51

52 Preparing for installation System example 2, ID: _1008_01 (cont.) L1 N 230 V, 50 Hz 4 16 M 1~ UP AC 45 X1. X2.N E 2 L 40 N 230 V, 50 Hz X1. X2.N D 2 X3.9 X1. X DW V/ 50 Hz 200 W X1. M 1~ UP X2.N 100 W X1. M 1~ UP A1 X2.N 130 W X1. M 1~ UPSB 7 X2.N 50 W X1. M 1~ ZP 22 X2.N 130 W X1. M 1~ UP 6 X2.N A B 16 A L1 400 V, 50 Hz L2 X2.N L3 3 / N / PE N X1. X2.N OPEN M 1~ M2 CLOSE W M X1. UP M2 1~ X2.N <16 A X3.18 L1 X2.1 N 230 V, 50 Hz X A Plug ach connected to the cable harness B Control module for instantaneous heating water heater 52

53 System example 2, ID: _1008_01 (cont.) Preparing for installation 4 11 Low voltage H1 1 2 H2 HK A1 61 HK M PT500 F6 STS 21 Low voltage PT500 F4 PTS 31 Ni500 F14 VTS 42 PT500 F13 VTS 32 Ni500 F0 ATS 10 Installation F12 PT500 VTS M2 53 F16 Ni500 RTS 41 Control unit power supply Compressor power supply A X3.18 X2.1 X1.1 L1 N 1 / N / PE 230 V, 50 Hz L1 L2 L3 PE 3 / PE 400 V, 50 Hz A Mains terminals on the cross connect PCB Required parameter setting Set the required parameters during commissioning; see from page

54 Preparing for installation System example 2, ID: _1008_01 (cont.) Parameter Setting "System definition" "System scheme 7000" "6" "External extension 7010" "1" "Common flow temperature sensor system "1" 701B" "Cooling" "Cooling 7100" "3" "Cooling circuit 7101" "4" DHW heating: "Time program DHW" Set time program (see operating instructions) "Time prog. DHW circ." Set time program (see operating instructions) "DHW" "Enable booster heaters for DHW heating 6014" "1" "Electr booster heater" "Enable instantaneous heating water heater 7900" "1" If required, "Enable instant. heating water heater for "1" central heating 7902" "Output for instant. heating water heater at power- OFF 790A" "Heating water buffer cylinder" "Enable buffer cylinder / low loss header 7200" "1" Remote control units: "Heating circuit 1" "Remote control 2003" "1" "Heating circuit 2" "Remote control 3003" "1" "1" for 3 kw "2" for 6 kw "3" for 9 kw System example 3, ID: _1008_01 Note Type BW 301.A is shown. In types BWC 301.A and WWC 301.A, the circulation pumps (primary pump, secondary pump and circulation pump for cylinder heating) are installed and connected at the factory. Setting system scheme 10 Single stage heat pump, type BW 301.A 1 heating circuit without mixer (A1) 2 heating circuits with mixer (M2, M3) External heat source for heating and DHW DHW heating with solar backup 54

55 P1 System example 3, ID: _1008_01 (cont.) Preparing for installation Solar thermal system Heating water buffer cylinder Natural cooling function at heating circuit M2 Swimming pool Note This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for local engineering. Hydraulic installation scheme /S / R1-- --S V-- -KM BUS- --S / / / /F / / M2 A1 M /X / /225.2; / / /52-- Installation /S /F /R KW /R WW /F /222.1; /F / / / / /F / / / B/ / / / /F / / KM BUS V /X X3.8; F F F V-- --KM BUS ;2-- --F F4-- --F ; KM BUS V

56 Preparing for installation System example 3, ID: _1008_01 (cont.) Pos. Description Heat pump 1 Vitocal 300-G 2 Instantaneous heating water heater, 3, 6, or 9 kw 4 Heat pump control unit Vitotronic 200, type WO1A 5 Primary pump, UP (integrated in type BWC) 6 Secondary pump, UP (integrated in type BWC) 7 Circulation pump for cylinder heating UPSB (integrated in type BWC) 8 Safety equipment block with safety assembly (in standard delivery for type BWC) 9 Expansion vessel qp Outside temperature sensor ATS qq KM BUS distributor qw Geothermal probe/geothermal collector qe Brine distributor for geothermal probes/geothermal collectors qr Brine accessory pack qt Brine circuit pressure switch External heat source wp External heat source (e.g. Vitola 200) wq External heat source demand ww Mixer motor we Flow temperature sensor VTS system wr High limit safety cut-out STB 70 C (for switching off secondary pump 6) wt High limit safety cut-out STB 70 C (for switching off external heat source wp) wz Circulation pump for cylinder heating UPSB wu Boiler water temperature sensor KTS (in the external heat source for connection to the heat pump) DHW heating (primary store system) ep Dual mode DHW cylinder eq Cylinder temperature sensor STS top (for connection to heat pump control unit 4) ew DHW circulation pump ZP ee Two-way motorised valve (N/C, on the DHW side) er Flow limiter et Plate heat exchanger Vitotrans 100 ez Cylinder primary pump SLP (on the DHW side) DHW heating with solar backup rp Solar-Divicon with solar circuit pump R1 rq Solar control unit Vitosolic 100, type SD1 56

57 System example 3, ID: _1008_01 (cont.) Preparing for installation Pos. Description rw Collector temperature sensor KOL re Solar collector rr Cylinder temperature sensor STS (for connection to solar control unit rq) rt High limit safety cut-out STB solar Heating water buffer cylinder tp Heating water buffer cylinder tq Buffer temperature sensor PTS Heating circuit with mixer M2 zp Underfloor heating circuit with mixer M2 zq Vitotrol 200A remote control ze Flow temperature sensor VTS M2 zr Temperature limiter to limit the maximum temperature of underfloor heating systems zz Mixer motor (regulated by control unit 4) zu Heating circuit pump, UP M2 Natural cooling function (NC) up NC-Box with mixer zi 3-way diverter valve uq Primary cooling circuit pump uw Secondary cooling circuit pump ue Contact humidistat ur 3-way diverter valve ut 2-way valve Heating circuit without mixer A1 ip Radiator heating circuit iq Vitotrol 200A remote control ie Heating circuit pump, UP A1 Heating circuit with mixer M3 op Radiator heating circuit oq Vitotrol 200A remote control oe Flow temperature sensor VTS M3 ot Extension kit for heating circuit with mixer oz Heating circuit pump, UP M3 ou Mixer motor M3 Swimming pool q-p Swimming pool q-q Thermostat for controlling the swimming pool temperature TST q-w Circulation pump for swimming pool heating UP q-e Plate heat exchanger 57 Installation

58 Preparing for installation System example 3, ID: _1008_01 (cont.) Pos. q-r q-t Description 3-way diverter valve External extension H1 Note The additional parameters for two-stage operation are set during commissioning by the certified heat pump contractor. Electrical installation scheme For an overview of the electrical connections and more information on the PCBs, see from page 72 and the separate service instructions, Vitotronic 200 heat pump control unit. For information regarding the power supply, see page

59 System example 3, ID: _1008_01 (cont.) Preparing for installation X1. NC 70 X2.N 200 W M X1. UP 5 1~ X2.N 100 W M X1. UP A1 83 1~ X2.N 130 W X1. M 1~ UPSB 7 X2.N W M X1. ZP 32 1~ X2.N 230 V/ 50 Hz STB W X1. M 1~ UP 6 X2.N A B 16 A X2.N L1 L2 L3 N 400 V, 50 Hz 3 / N / PE 100 W X1. M 1~ UPSB X2.N X1. X2.N W M 1~ SLP Installation X1. X2.N OPEN M 1~ M2 CLOSE W M X1. UP M2 1~ X2.N M 1~ X3.1 X1. X2.N X1. X2.N X3.18 X2.1 X C < 16 A D OPEN M 1~ CLOSE L1 N STB V / 50 Hz X X1. X3.9 59

60 Preparing for installation System example 3, ID: _1008_01 (cont.) A Plug ach connected to the cable harness B Control module for instantaneous heating water heater C Move jumper from X3.1 to D On-site contactor relay 60

61 System example 3, ID: _1008_01 (cont.) Preparing for installation 4 11 Low voltage H1 1 2 H3 1 2 H2 HK A1 81 HK M3 91 HK M N L N L 230 V/ 50 Hz 1 / N / PE Installation 20 N L M 1~ UP M3 96 N 52 M 1~ M NTC VTS M L 21 N R119 N M 1~ 230 V/ 50 Hz UP S2 3 S STB STS KOL N L N L 230 V/ 50 Hz 1 / N / PE 50 N 104 L1 L2 L3 400 V, 50 Hz L D M 3~ UP TST 101 D On-site contactor relay 61

62 Preparing for installation System example 3, ID: _1008_01 (cont.) 4 PT500 F6 STS 31 PT500 F4 PTS 51 Low voltage F20 F13 PT500 PT500 KTS 27 VTS 23 F0 Ni500 ATS 10 F12 PT500 VTS M2 63 Control unit power supply Compressor power supply A X3.18 X2.1 X1.1 L1 N 1 / N / PE 230 V, 50 Hz L1 L2 L3 PE 3 / PE 400 V, 50 Hz A Mains terminals on the cross connect PCB Required parameter setting Set the required parameters during commissioning; see from page

63 System example 3, ID: _1008_01 (cont.) Preparing for installation Parameter Setting "System definition" "System scheme 7000" "6" "Swimming pool 7008" "1" "External extension 7010" "1" "Common flow temperature sensor system "1" 701B" "Cooling" "Cooling 7100" "2" "Cooling circuit 7101" "2" DHW heating: "Time program DHW" Set time program (see operating instructions) "Time prog. DHW circ." Set time program (see operating instructions) "DHW" "Enable booster heaters for DHW heating 6014" "1" "Electr booster heater" "Enable instantaneous heating water heater 7900" "1" If required, "Enable instant. heating water heater for "1" central heating 7902" "Output for instant. heating water heater at power- OFF 790A" "External heat source" "Enable external heat source 7B00" "1" "Enable external heat source for DHW heating "1" 7B0D" "Heating water buffer cylinder" "Enable buffer cylinder / low loss header 7200" "1" Remote control units: "Heating circuit 1" "Remote control 2003" "1" "Heating circuit 2" "Remote control 3003" "1" "Heating circuit 3" "Remote control 4003" "1" "1" for 3 kw "2" for 6 kw "3" for 9 kw Installation 63

64 Installation sequence Siting the heat pump Removing the transport brackets and levelling the heat pump 4x 1. 4x 2. Position and level the heat pump as Please note described on page 6.! Operating the appliance without first removing the transport brackets may cause vibrations and excessive noise. Remove the transport brackets. 64

65 Installation sequence Siting the heat pump (cont.) Removing the top panel 1. Installation 65

66 Installation sequence Hydraulic connections For the arrangement of the hydraulic connections, see page 10. Connecting the primary circuit! Please note The components used must be resistant to the heat transfer medium. Never use zinc-plated/galvanised pipes. 1. Equip the primary circuit with an expansion vessel and safety valve (in accordance with DIN 4757). Note Expansion vessel must be approved to DIN Diaphragms of expansion vessel and safety valve must be suitable for the heat transfer medium. Blow-off and drain lines must exit into one container that can hold the maximum possible expansion volume of the heat transfer medium. 2. Ensure adequate thermal and sound insulation of all pipes routed through walls. 3. Connect primary lines to heat pump. Please note! To prevent equipment damage, connect on-site primary lines to the heat pump so that they are free of load and torque stresses. Please note! Make tight hydraulic connections on the primary side. In the case of hose outlets, ensure diaphragm grommets are seated correctly. If necessary, seal with sealing tape. 4. Insulate lines inside the building to provide protection from heat and vapour diffusion. 5. Fill the primary circuit with Viessmann heat transfer medium and vent. Note Viessmann heat transfer medium is a ready-mixed ethylene glycol-based medium, for down to 15 C, containing inhibitors for corrosion protection. Note For diaphragm grommets, see page

67 Installation sequence Hydraulic connections (cont.) Connecting the secondary circuit 1. Equip the secondary circuit on site with an expansion vessel and safety assembly (in accordance with DIN 4757). Fit the safety assembly to the on-site line in the heating water return. 2. Connect secondary lines to heat pump (7 28 mm). Please note! To prevent equipment damage, connect on-site secondary lines to the heat pump so that they are free of load and torque stresses. Please note! Make tight hydraulic connections on the secondary side. In the case of hose outlets, ensure diaphragm grommets are seated correctly. If necessary, seal with sealing tape. 3. Fill and vent secondary circuit. 4. Thermally insulate pipes inside the building. Note For diaphragm grommets, see page 104. In underfloor heating circuits, integrate a temperature limiter on site for limiting the maximum temperature of underfloor heating systems. Safeguard minimum flow rate, e.g. with overflow valve (see Specification on page 152). Installation 67

68 Installation sequence Electrical connections Installing the programming unit (type BW 301.A and BWC 301.A) x x [XÖ X 68

69 Installation sequence Electrical connections (cont.) Routing cables to the connection area Danger Damaged cable insulation can cause injury and damage to the appliance. Route cables so that they cannot touch very hot, vibrating or sharpedged components. When routing the on-site power cables, observe the location of the cable entries into the appliance via its back panel (see page 10). Danger Incorrectly routed wiring can lead to serious injury from electrical current and result in equipment damage. Route LV leads < 42 V and cables > 42 V/230 V~/400 V~ separately. Strip the insulation from the cables as close to the terminals as possible, and bundle tightly to the corresponding terminals. Secure cables with cable ties. This ensures that, should there be an error, for example when detaching a wire, the wires cannot drift into the adjacent voltage area. Installation 69

70 Installation sequence Electrical connections (cont.) < 42 V 230 V 1. Route LV leads through the aperture "< 42 V" to the heat pump control unit connection area and apply strain relief using the cable ties provided. 2. Route 230 V~ leads and power cables for the compressor through the aperture "230 V~" to the heat pump control unit connection area and apply strain relief using the cable ties provided. For power supply, see from page 94. Note Route LV leads and 230 V~ cables as far apart as possible. 70

71 Installation sequence Electrical connections (cont.) Connecting electrical connecting cables from the heat pump stage 2 (type BWS 301.A) to heat pump stage 1 (type BW 301.A) B C ajb avg 1. < 42 V B C 230 V~ 2. Installation A BC < 42 V 230 V~ D [H X avg avg abh [G X BC [C-Ö X 3. 71

72 Installation sequence Electrical connections (cont.) A Connection area, heat pump stage 2 (type BWS 301.A) B Connecting cables, LV < 42 V: With plugs ajb and avg for the connection area for heat pump stage 2 (type BWS 301.A). With plugs "X6" and avg for the connection area for heat pump stage 1 (type BW 301.A). C 230 V~ connecting cables: With plugs without ID for the connection area for heat pump stage 2 (type BWS 301.A). With plugs "X300" and abh for the connection area for heat pump stage 1 (type BW 301.A). D Connection area, heat pump stage 1 (type BW 301.A) Overview of the electrical connections of the heat pump control unit (type BW 301.A and BWC 301.A) Note Route 230 V~ cables and LV cables separately and bundle them tightly together at the terminals. This ensures that, in case of failure, for example when detaching a wire, the wires cannot drift into the adjacent voltage area. Strip the insulation as close to the terminals as possible. If two components are connected to the same terminal, press both wires together into a single wire ferrule. 72

73 Installation sequence Electrical connections (cont.) X2 X3 A X1 F1 X6 avg X5 F2 F0 X24 F4 F3 F7 F6 F8 F12 D F14 F13 F16 F20 F18 F21 C F3 sxg sxf B sys sya sxdsxs Installation X31 A Cross connect PCB F1 Fuse 6.3 A (slow) B Extension PCB on main PCB C Main PCB F3 Fuse 6.3 A (slow) D Controller and sensor PCB 73

74 Installation sequence Electrical connections (cont.) Main PCB Information regarding the connection values The output given is the recommended connected load. The total output of all components connected directly to the heat pump control unit (e.g. pumps, valves, message facilities, contactors) must not exceed 1000 W. If the total output is < 1000 W, the individual output of a component (e.g. pump, valve, messaging facility, contactor) may be selected larger than specified. However, the breaking capacity of the corresponding relay must not be exceeded. The stated current indicates the max. switching current of the switching contact (observe the total current of 5 A). Controls for external heat source and central fault message are unsuitable for safety LV. Set the required parameters during commissioning; see from page

75 Installation sequence Electrical connections (cont.) Operating components 230 V~ Plug sya Terminals Function Explanation Primary pump (heat pump stage 1 or common primary pump), well pump control Connection values Output: 200 W Voltage: 230 V~ Max. switching current: 4(2) A Secondary pump (heat pump stage 1) Connect on site. In type BWC, the primary pump is connected at the factory. In systems without a heating water buffer cylinder, no other heating circuit pump is required (see terminal 212.2) Connect temperature limiter as maximum temperature limiter for underfloor heating circuit (if installed) in series (see the following chapter) Connection values Output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A Installation r Instantaneous heating water heater control, stage 1 Type BW: Connect on site. Type BWC: Connected at the factory. Connection values Output: 10 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. 75

76 Installation sequence Electrical connections (cont.) Plug sya Terminals Function Explanation way diverter valve for heating/dhw r M Circulation pump for cylinder heating Cylinder primary pump 2-way shut-off valve Connection values Output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. In type BWC, the circulation pump for cylinder heating is connected at the factory. M NC/AC Cooling control NC function (natural cooling) Circuit on site Connection values Output: 10 W Voltage: 230 V~ Max. switching current: 4(2) A Plug sys Terminals Function Explanation Cooling control AC function (active cooling) AC Circuit on site Connection values Output: 10 W Voltage: 230 V~ Max. switching current: 4(2) A 76

77 Installation sequence Electrical connections (cont.) Plug sys Terminals Function Explanation A1 Heating circuit pump for heating circuit without mixer (A1) This pump is installed in addition to the secondary pump if a heating water buffer cylinder is connected. Connect temperature limiter as maximum temperature limiter for underfloor heating circuit (if installed) in series (see the following chapter) Connection values Output: 100 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site DHW circulation pump Connection values Output: 50 W Voltage: 230 V~ Max. switching current: 4(2) A Installation Connect on site. 77

78 Installation sequence Electrical connections (cont.) Connecting a temperature limiter as maximum temperature limiter for underfloor heating system General connection X2.N X1.? A B Connection with temperature limiter (part no , ) X2.N X1.? A B sö C M 1~ C M 1~ A Connection on the main PCB (211.2 or in accordance with the table above) B Temperature limiter C Heating circuit pump A Connection on the main PCB (211.2 or in accordance with the table above) B Temperature limiter C Heating circuit pump 78

79 Installation sequence Electrical connections (cont.) Connection with temperature limiter (part no , ) to extension kit for heating circuit with mixer A sö B sö Installation C M 1~ A Plug sö for extension kit B Temperature limiter C Heating circuit pump 79

80 Installation sequence Electrical connections (cont.) Extension PCB on main PCB Information regarding the connection values The output given is the recommended connected load. The total output of all components connected directly to the heat pump control unit (e.g. pumps, valves, message facilities, contactors) must not exceed 1000 W. If the total output is < 1000 W, the individual output of a component (e.g. pump, valve, messaging facility, contactor) may be selected larger than specified. However, the breaking capacity of the corresponding relay must not be exceeded. The stated current indicates the max. switching current of the switching contact (observe the total current of 5 A). Controls for external heat source and central fault message are unsuitable for safety LV. Set the required parameters during commissioning; see from page 108. Function components 230 V~ Plug sxs Terminals Function Explanation Mixer motor control for external heat source Signal mixer CLOSED Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A Mixer motor control for external heat source Signal mixer OPEN Connect on site. Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A Connect on site. 80

81 Installation sequence Electrical connections (cont.) Plug sxs Terminals Function Explanation Zero volt contact Switching external heat source with two high limit safety cut-outs (max. 70 C) to protect the heat pump and to stop the secondary pump Note The switching contact is a zero volt N/O contact that is closed when a heat demand is issued. Never route low voltage via this contact; that requires an on-site relay. The boiler water temperature sensor in the external heat source (plug F20) must capture the average temperature of the external heat source. Connection values (contact loads): Voltage: 230 V~ Max. switching current: 4(2) A Installation Connect the high limit safety cut-out on site: In series to the secondary pump (terminal on the main PCB). In series to the switching of external heat sources. 81

82 Installation sequence Electrical connections (cont.) High limit safety cut-out for heat pump in conjunction with an external heat source D A X3.1 B C C Connection on the external heat source at terminals for external demand D High limit safety cut-out (max. 70 C) as heat pump protection K1 Relay; sizing in accordance with the external heat source; observe safety instructions K1 X2.N A Terminals on extension PCB B Move jumper from X3.1 to Plug sxd Terminals Function Explanation U Central fault message Zero volt contact: Closed: Fault Open: No fault Unsuitable for safety LV. Connection values (contact loads): Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. Note No parameters need to be set. The contact issues a short pulse when the power supply is switched on. Observe the pulse when processing the message via communication tools. 82

83 Installation sequence Electrical connections (cont.) Central fault message A L1 230 V~, 0.5 A N A Terminals on extension PCB Plug sxf Terminals Function Explanation Primary pump for heat pump stage 2 (if installed) Connection values Output: 200 W Voltage: 230 V~ Max. switching current: 4(2) A Installation Connect on site r Secondary pump for heat pump stage 2 (if installed) Control of instantaneous heating water heater, stage 2 Connection values Output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. Connection values Output: 10 W Voltage: 230 V~ Max. switching current: 4(2) A Circulation pump for cylinder heating (on the heating water side) for heat pump stage 2 (if installed) Connect on site. Connection values Output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. 83

84 Installation sequence Electrical connections (cont.) Plug sxf Terminals Function Explanation Cylinder primary pump Switch cylinder primary pump and twoway (DHW side) shut-off valve in parallel 2-way shut-off valve Connection values Output: 130 W Voltage: 230 V~ Max. switching current: 4(2) A M Connect on site Circulation pump for DHW reheating or Immersion heater control Connection values Output: 100 W Voltage: 230 V~ Max. switching current: 4(2) A Connect on site. Immersion heater (400 V~) L1 L2 L3 N? B X2.N A A Immersion heater, power supply 3/N/PE 400 V/50 Hz 84 B Terminals of the heat pump control unit

85 Installation sequence Electrical connections (cont.) Plug sxg Terminals Function Explanation Heating circuit pump of the heating circuit with mixer M2 M2 r Connect temperature limiter as maximum temperature limiter for underfloor heating circuit (if installed) in series. Connection values: Output: 100 W Voltage: 230 V~ Max. switching current: 4(2) A M2 Switching the mixer motor for heating circuit M2 Signal mixer CLOSED Connect on site. Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A Installation Connect on site M2 Switching the mixer motor for heating circuit M2 Signal Mixer OPEN Connection values: Output: 10 W Voltage: 230 V~ Max. switching current: 0.2(0.1) A Connect on site. Cross connect PCB Set the required parameters during commissioning; see from page 108. Message and safety connections Terminals Function Explanation F1 Fuse 6.3 A (slow) X1 Earth conductor X1.? Earth terminals for all associated system components X2 Neutral conductor X2.N Terminals for neutral conductor for all associated system components 85

86 Installation sequence Electrical connections (cont.) Terminals Function Explanation X3 Power supply terminals of the control unit "L1" and auxiliary components Switched phase L1: X3.1, X3.2, X3.3, X3.7, X3.11, X3.13 X3.1 Phase switched X3.2 Signal "External blocking" X3.14 (external blocking of compressor and pumps, mixer or at external extension H1 in control operation or CLOSED) Note The system may no longer be protected against frost. Terminals for message and safety connections Note Switched phase can be used for on-site system components. Observe max. load. Requires floating N/O contact: Closed: Blocking enabled Open: No blocking Breaking capacity 230 V~, 2 ma Note These and further external functions, such as swimming pool water heating, cascade or external set value default can alternatively be connected via external extension H1. Installation instructions "External extension H1" If a swimming pool water heating facility is connected to external extension H1, no other external function can be connected to external extension H1. X3.3 X3.4 Flow limiter, well circuit Floating contact required: Closed: heat pump operational Open: Heat pump shut down Breaking capacity 230 V~, 0.15 A With a connected flow limiter, no jumpers should be installed. 86

87 Installation sequence Electrical connections (cont.) Terminals Function Explanation X3.6 X3.7 G Power-OFF Requires floating N/C contact: Closed: No blocking (safety chain has continuity) Open: Blocking enabled Breaking capacity 230 V~, 0.15 A With a connected power-off contact, no jumpers should be installed. Note No parameters need to be set. The compressor is shut down "hard" as soon as the contact opens. The supply voltage to the relevant components (subject to power supply utility) is switched off by the power-off contact signal. For the instantaneous heating water heater, the stages to be switched off can be selected (parameter "Output for instant. heating water heater at power-off"). The power supply to the heat pump control unit (3 x 1.5 mm 2 ) and the cable for the power-off signal can be combined in a 5-core cable. For further information regarding power- OFF, see chapter "Power supply". Installation X3.8 X3.9 P Primary circuit pressure switch and/or frost stat or Jumper Floating contact required: Closed: Safety chain has continuity Open: Safety chain interrupted; heat pump shut down Breaking capacity 230 V~, 0.15 A On-site connection: Connected in series if both safety components are installed Insert jumper if no safety components are installed 87

88 Installation sequence Electrical connections (cont.) Terminals Function Explanation X3.10 X3.11 Fault message, lag heat pump in a cascade or Jumper Floating contact required: Closed: No faults Open: Fault Breaking capacity 230 V~, 0.15 A X3.12 X3.13 or at external extension H1 Signal "External demand" (external starting of compressor and pumps, mixer in control operation or OPEN, changeover of operating mode of several system components) With a connected message contact, no jumpers should be installed. Requires floating N/O contact: Closed: Requirement Open: no demand Breaking capacity 230 V, 2 ma Note These or other external functions, such as swimming pool water heating, cascade or external set value default can alternatively be connected via external extension H1. Installation instructions "External extension H1" If a swimming pool water heating facility is connected to external extension H1, no other external function can be connected to external extension H1. X3.17 X3.18 Fuse F1 6.3A (slow) Controller and sensor PCB Set the required parameters during commissioning; see from page Note Plug F11: Nothing must be connected to plug F11 on site. Flow temperature sensor for heating circuit with mixer (M3): The flow temperature sensor for one heating circuit with mixer (M3) is connected to the extension kit for heating circuit with mixer (accessory).

89 Installation sequence Electrical connections (cont.) Sensors Plug Sensor Type F0 Outside temperature sensor, connect on site Ni 500 (PTC) F2 (X5.2/X5.3) Primary circuit flow temperature sensor, connect on site with two-stage heat pump (see the following chapter) Pt 500 (PTC) F3 (X5.4/X5.5) F4 (X5.6/X5.7) F6 (X6.1/X6.2) F7 (X6.1/X6.3) F12 F13 F14 F16 F17 (X6.4/X6.5) F18 (X6.6/X6.7) F20 (X6.8/X6.9) avg Primary circuit return temperature sensor, connect on site with two-stage heat pump (see the following chapter) Pt 500 (PTC) Buffer temperature sensor, top; connect on site Pt 500 (PTC) Cylinder temperature sensor, top; connect on site Pt 500 (PTC) Cylinder temperature sensor, bottom; connect on site Pt 500 (PTC) Flow temperature sensor, heating circuit with mixer (M2); Ni 500 connect on site (PTC) System flow temperature sensor (with sensor well, downstream Pt 500 of heating water buffer cylinder), connect on site (PTC) Flow temperature sensor, cooling circuit (direct heating Ni 500 circuit A1 or separate cooling circuit); connect on site (PTC) Room temperature sensor for separate cooling circuit Ni 500 (requirement) or for direct heating/cooling circuit (recommendation); (PTC) connect on site Do not connect anything here Pt 500 (PTC) Return temperature sensor, secondary circuit for heat Pt 500 pump stage 2 (if installed), connect on site (PTC) Boiler temperature sensor, external heat source, connect Pt 500 on site (PTC) KM BUS Installation On-site component connection (wires interchangeable); for several appliances, use the KM BUS distributor (accessory). Extension kit for one heating circuit with mixer M3 Vitotrol 200A remote control (assign the heating circuits at the remote control) External extension H1 Vitocom 100 communication interface Vitosolic 100/200 solar control units 89

90 Installation sequence Electrical connections (cont.) Plug Sensor Type X24 Connection of the LON communication module (plug in on site, see LON communication module installation instructions) X31 Coding card slot Connection of primary circuit flow/return temperature sensor, two-stage heat pump as 2. as ad [G X ad < 42 V as as ad ad ad as as Flow temperature sensor, primary circuit ad Return temperature sensor, primary circuit 90

91 Installation sequence Electrical connections (cont.)! Please note Identify sensor leads. Fasten sensor leads and dismantled leads (with plug as/ad) together with the other LV leads using the cable ties provided. Swimming pool water heating Note Swimming pool water heating is switched via external extension H1 with KM BUS. Make connections at external extension H1 only in accordance with the following diagram. At plug gö connect only the circulation pump for swimming pool water heating F in accordance with the following diagram. A filter circuit pump must be connected separately. If the components for swimming pool water heating are connected to external extension H1, no other external function (e.g. changeover of operating mode) can be connected. Installation 91

92 Installation sequence Electrical connections (cont.) B A avg fö L? N avg avd gö N? L L1? N C D L2? L1 L3 E G F M 3~ A Connection to controller and sensor PCB B External extension H1 C Thermostat for swimming pool temperature control (zero volt contact, 230 V~; 0.1 A; accessory) D Junction box (on site) E Fuses and contactor for circulation pump for swimming pool heating (accessory) F Circulation pump for swimming pool water heating (accessory) G 3-way diverter valve "swimming pool" (at zero volt: heating of the heating water buffer cylinder) Cascade control via KM BUS Make connections at external extension H1 only in accordance with the following diagram. 92

93 Installation sequence Electrical connections (cont.) A 2 avg 1 X3.10 X3.11 L D X3.12 X3.13 F E X3.12 X3.13 B 230V 230V C avg N? L sa L? N fö N? L sk L1? N Installation G H X3.12 X V N? L sö K N L1 A Heat pump 1 (lead appliance) B KM BUS C External extension H1 D Zero volt contact "External demand " E Lag heat pump 1 Connection at contact for "External demand " F Zero volt contact "External demand " 93

94 Installation sequence Electrical connections (cont.) G Lag heat pump 2 Connection at contact for "External demand " H Zero volt contact "External demand " K Lag heat pump 3 L Central fault message input, lag heat pump N/C contact X3.10 / X3.11 triggers a message. Power supply Isolators for non-earthed conductors The mains isolator (if installed) must simultaneously isolate all non-earthed conductors from the power supply with a minimum contact separation of 3 mm. We additionally recommend installing an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can occur with energy efficient equipment. If no mains isolator is installed, all nonearthed conductors must be isolated from the power supply by the upstream circuit breaker with at least 3 mm contact separation. Danger Incorrectly executed electrical installations can lead to injury from electrical current and result in equipment damage. Make the power supply connection and implement all protective measures (e.g. RCD circuit) in accordance with the following regulations: IEC VDE regulations Technical connection requirements specified by your local power supply utility Protect the power supply to the heat pump control unit with 16 A max. Danger An absence of component earthing in the system can lead to serious injury from electrical current if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the house in question. 94

95 Installation sequence Power supply (cont.) Danger Incorrect wire allocation can cause severe injury and damage the appliance. Never interchange wires "L" and "N". In negotiations with your power supply utility, different supply tariffs for the main power circuits may be offered. Observe the technical connection requirements of the power supply utility. If the compressor and/or instantaneous heating water heater (if installed) are operated at an economy tariff (power-off), provide an additional cable (e.g. 3 x 1.5 mm 2 ) for the power- OFF signal from the distribution board (meter box) to the heat pump control unit. The allocation of the power-off (for compressor and/or instantaneous heating water heater) is made via the type of connection and by setting parameters in the heat pump control unit. In Germany, the power supply can be cut off for up to 3 x 2 hours per day (24 h). The heat pump control unit/pcb must be supplied without blocking by the power supply utility; tariffs that are subject to possible shutdown must not be used here. The power supply to the heat pump control unit (3 x 1.5 mm 2 ) and the cable for the power-off signal can be combined in a 5-core cable. Protect the power supply to the heat pump control unit with 16 A max. For accessories and external components that are not to be connected to the heat pump control unit, make the power connection with the same phase as the heat pump control unit; we recommend using the same fuse/ MCB. Connection to the same fuse/mcb provides additional safety when the power is switched off. Observe the power consumption of the consumers connected. Information regarding the compressor power supply Please note! An incorrect phase sequence can cause damage to the appliance. Make the compressor power supply only in the phase sequence specified (see terminal) with a clockwise rotating field. Characteristics of the compressor power fuses: see "Specification". Installation 95

96 Installation sequence Power supply (cont.) Heat pump control unit power supply (230 V~) A X3.18 X2.1 X1.1 max.16 A L1 N? 1/N/PE 230 V / 50 H A Mains terminals inside the heat pump control unit Note This supply must never be blocked. Max. fuse rating 16 A Standard tariff (no optional low tariff with power-off) Recommended cable: 3 x 1.5 mm 2 (5 x 1.5 mm 2 with power-off) Compressor power supply (400 V~)? N L3 L2 L1 A? L3 L2 L1 3 / PE 400 V, 50 Hz Fuse protection in accordance with the compressor output (see specification). Low tariff and power-off can be used. No parameters need to be set when using economy tariff with power-off facility. During the power-off period, the compressor is shut down. Recommended power cable: 5 x 2.5 mm 2 Max. lead length: 50 m Power supply with power-off Power-OFF without on-site load disconnection The power-off signal is connected directly to the heat pump control unit. When power-off is enabled, the compressor is "forced" off, and in the twostage version (type BW 301.A + BWS 301.A), both compressors. Parameter "Stage at power-off" is used to determine whether and at what stage the instantaneous heating water heater (if installed) remains operational during the power-off. Service instructions for Vitotronic 200 heat pump control unit Note Observe the technical connection conditions of the relevant power supply utility. 96

97 Installation sequence Power supply (cont.) Single stage A X3.7 X3.6 B C Installation kwh kwh D 3/N E 3/N H 4 F 4 G 4 Diagram excluding fuses and RCD. A Heat pump control unit (connection on cross connect PCB) B Instantaneous heating water heater (accessory) C Compressor D High tariff meter E Ripple control receiver (contact open: power-off enabled) F Backup fuse ripple control receiver G TNC system feed H Economy tariff meter 97

98 Installation sequence Power supply (cont.) Two-stage (type BW 301.A + BWS 301.A) A X3.7 X3.6 B C K kwh kwh 3/N D E 3/N H 4 F 4 G 4 Shown excluding fuses and RCD. A Heat pump control unit (connection on cross connect PCB) B Instantaneous heating water heater (on site) C Compressor, heat pump stage 1 (type BW 301.A) D High tariff meter E Ripple control receiver (contact open: power-off enabled) F Backup fuse ripple control receiver G TNC system feed H Economy tariff meter K Compressor, heat pump stage 2 (type BWS 301.A) 98

99 Installation sequence Power supply (cont.) Power-OFF with on-site load disconnection The power-off signal is connected to the on-site contactor of the economy tariff power supply and in the heat pump control unit. When power-off is enabled, the compressor and the instantaneous heating water heater (if installed) are "forced" off, and in the two-stage version (type BW 301.A + BWS 301.A), both compressors and the instantaneous heating water heater. Single stage Note Observe the technical connection conditions of the relevant power supply utility. Installation A X3.7 X3.6 B C D E kwh 3 kwh 3/N F G 3/N H 4 4 K 4 Diagram excluding fuses and RCD. 99

100 Installation sequence Power supply (cont.) A Heat pump control unit (connection on cross connect PCB) B Instantaneous heating water heater (on site) C Compressor D Control unit power supply E Mains isolator F High tariff meter G Ripple control receiver (contact open: power-off enabled) with backup fuse H Economy tariff meter K TNC system feed Two-stage (type BW 301.A + BWS 301.A) A X3.7 X3.6 B C L D E 3 kwh 3 kwh 3/N F 3/N G 4 4 H K 4 Shown excluding fuses and RCD. A Heat pump control unit (connection on cross connect PCB) B Instantaneous heating water heater (on site) C Compressor, heat pump stage 1 (type BW 301.A) 100 D Control unit power supply E Mains isolator F High tariff meter G Ripple control receiver (contact open: power-off enabled) with backup fuse

101 Installation sequence Power supply (cont.) H Economy tariff meter K TNC system feed L Compressor, heat pump stage 2 (type BWS 301.A) Phase monitor (if installed) The phase monitor is used to monitor the mains power supply to the compressor. The following different mains supplies (if adjustable) are permissible in the delivered condition: Over/undervoltage 15 % Phase asymmetry 15 % Switching delay 4 s Version 1 The phase monitor switches off (switching contact opens) if these tolerances are exceeded. The phase monitor automatically re-enables the power supply if the values return to within the specified tolerance range. Remove the cause if the relay has responded. The relay does not need to be reset. Installation A B C <>U Asy 10 2 % 10 % t L3 L2 L1 A2 A <>U Asy Ph Rel H G F E D D A Over/undervoltage in % B Phase asymmetry in % C Switching delay in s D Contact used in safety chain (N/O) E ON/OFF indicator ("Rel") F Fault display phase failure/phase sequence ("Ph") G Fault display asymmetry ("Asy") H Fault display over/undervoltage ("<>U") LEDs explained LED "Rel" illuminates green: All voltages and the rotating field (clockwise) are healthy. LED "Ph" illuminates red: The relay has responded; the rotating field is anticlockwise. All LED's off: One or several phases have dropped out. LED "<>U" illuminates red: Incorrect voltage on one/several phase(s). LED "Asy" illuminates red: Asymmetry on one/several phase(s). 101

102 Installation sequence Power supply (cont.) Version 2 A B N L1 L2 L3 L1 L3 L2 L1 L3 L2 L1 L3 L2 L1 L3 L2 LEDs explained A Voltage "U": Illuminates green if voltage is applied. B Relay "R": Illuminates yellow if the phase sequence is correct. Does not illuminate if the phase sequence is incorrect Connecting to terminals X3.8/X3.9 After connecting the power supply, one of the following components must be connected at terminals X3.8 and X3.9: Primary circuit pressure switch and/or frost stat or Jumper from the pack 102

103 Installation sequence Closing the heat pump Please note! Seal the appliance so it is soundproof and diffusion-proof. Check tightness of internal hydraulic connections. Please note! To prevent the formation of condensate and the excessive development of noise, tightly seal the shield. Danger An absence of component earthing in the system can lead to serious injury from electrical current if an electrical fault occurs. Attach earth conductor to front panel, top panel and side panels. Installation

104 Installation sequence Checking diaphragm grommets! Please note Seal the appliance so it is soundproof and diffusion-proof. With hose outlets, ensure diaphragm grommets A are seated correctly. Seal diaphragm grommets A with adhesive tape. A 104

105 Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance For further information regarding the individual steps, see the page indicated Commissioning steps Inspection steps Maintenance steps Page 1. Opening the heat pump Writing reports Checking the refrigerant circuit for leaks Filling and venting on the primary side Filling and venting on the secondary side Checking expansion vessels and the primary circuit/ heating circuit pressure Commissioning the system Closing the heat pump 9. Instructing the system user Service 105

106 Commissioning, inspection, maintenance Further details regarding the individual steps Opening the heat pump Danger Contact with 'live' components can lead to severe injury from electric current. Never touch terminal areas (heat pump control unit and power connections; see page 72). Danger The absence of component earthing can lead to serious injury from electrical current and to component damage if an electrical fault occurs. Always reconnect the earth conductors. 1. Remove front panel in reverse order; see page When work is complete, close the heat pump; see page 103. Regarding commissioning this appliance, see also the operating instructions.! Please note Wait at least 30 min between the installation and commissioning of the appliance to prevent equipment damage. Work on the refrigerant circuit must only be carried out by a qualified refrigeration engineer. Writing reports Enter measurements taken during commissioning (described in the following) into the reports from page 146 onwards. 106

107 Checking the refrigerant circuit for leaks Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 1. Check the floor area, valves and all visible solder joints for traces of oil. Note Traces of oil indicate a leaking refrigerant circuit. Have your heat pump checked over by a refrigeration engineer. 2. Check the heat pump interior with a refrigerant leak detector or leak detecting spray for refrigerant leaks. Filling and venting on the primary side! Please note To prevent equipment damage, fill the primary circuit before connecting the power supply. 3. Check the connections for possible leaks. Replace faulty or displaced gaskets. 1. Check the pre-charge pressure of the expansion vessel. 2. Fill the primary circuit with Viessmann heat transfer medium and vent. Note The system must be protected against frost down to 15 C. Viessmann heat transfer medium is a ready-mixed ethylene glycol-based medium, for down to 15 C, containing inhibitors for corrosion protection. Service Filling and venting on the secondary side! Please note To prevent equipment damage, protect electrical components on the shield from escaping liquids. Note Before filling the system, observe VDI 2035 sheet Open any on-site non-return valves installed. 107

108 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 2. Check the pre-charge pressure of the expansion vessel. 3. Fill (flush) and vent secondary circuit. Note Type BWC has integral non-return valves, which means that there is flow in only one direction in the secondary circuit. 4.! Please note To prevent equipment damage, check the flow and return connections of the secondary heat pump circuit for leaks. In case of leaks, immediately shut off the equipment, drain the water and check the seating of the seal rings. Replace any seal rings that may have become dislodged. 5. Check the system pressure and top up with water if required. Minimum system pressure: 0.8 bar Permiss. operating pressure: 2.5 bar Checking expansion vessels and the primary circuit/heating circuit pressure Observe design information. Vitocal technical guide Commissioning the system Commissioning (configuration, setting parameters and function checks) can be carried out with or without the commissioning assistant (see the following chapter and the separate service instructions for the Vitotronic 200 heat pump control unit). Note Type and extent of parameters depends on the heat pump type, on the selected system scheme and the accessories employed. Commissioning with the commissioning assistant The commissioning assistant guides you automatically through all the menus where settings have to be made. For this, "Coding level 1" is automatically active.! Please note Incorrect operation at "Coding level 1" may result in damage to the appliance and the heating system. 108

109 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Always observe the instructions in the separate service instructions of the Vitotronic 200 heat pump control unit, otherwise the appliance will no longer be under warranty. Switch on the ON/OFF switch on the heat pump control unit. The prompt "Start commissioning?" appears automatically on first commissioning. Note The commissioning assistant can also be started manually: When starting the heat pump control unit (progress bar visible), hold down. When the unit is first commissioned, the display is in German: Sprache Deutsch Cesky Dansk English Wählen mit Ø DE CZ DK GB ç Manually switching some appliance components during commissioning enables the heat pump control unit to display messages. These do not indicate appliance faults. Service 109

110 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Language set OK Date / time set OK Date set OK OK Time set NO Start commissioning? YES Programming level 1 OK Parameter group select OK Parameter set Temperature sensors OK Sensor values display Signal inputs OK Signal inputs display Actuator test OK Actuator test carry out Subscriber check LON OK Subscriber check carry out Function check OK Function select OK Function check start Commissioning terminated OK Control mode 110

111 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Commissioning without the commissioning assistant Activating the service menu The service menu can be enabled from any menu. Press OK + å simultaneously for approx. 4 s. Disabling the service menu The service menu remains active until it is disabled with "Terminate service?", or if no operation takes place for 30 minutes. Parameter setting, using example "System scheme" To set a parameter, first select the parameter group and then the parameters. All parameters are displayed as plain text. A parameter code is also assigned to each parameter. Service menu: 1. Press OK + å simultaneously for approx. 4 s. 2. Select "Coding level 1". 3. Select parameter group: "System definition" 4. Select parameter: "System scheme 7000" 5. Adjust system scheme: "6" Alternatively, if the service menu was already activated: Extended menu 1. å 2. "Service" 3. Select "Coding level 1". 4. Select parameter group: "System definition" 5. Select parameter: "System scheme" 6. Confirm parameter code: "7000" 7. Adjust system scheme: "6" Required parameters for components connected on site Detailed explanations regarding the parameters Service instructions for Vitotronic 200 heat pump control unit Service 111

112 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Pumps and other components Pump/component Parameter Setting Secondary pump (for heating circuit A1 without heating water buffer cylinder; no additional heating circuit pump required) "System definition" Ó "System scheme 7000" "1" to "11" Heating circuit pump A1 (in conjunction with heating water buffer cylinder in addition to the secondary pump) Heating circuit pump and mixer M2 Heating circuit pump and mixer M3 (control via extension kit for one heating circuit with mixer) "System definition" Ó "System scheme 7000" "System definition" Ó "System scheme 7000" "System definition" Ó "System scheme 7000" With heating circuit A1 (for heating circuit without mixer A1) With heating circuit M2 (for heating circuit with mixer M2) With heating circuit M3 (for heating circuit with mixer M3) Note Set rotary switch S1 in the extension kit to "2" (see extension kit installation instructions). Circulation pump for cylinder heating DHW heating with primary store system: Cylinder primary pump 2-way shut-off valve DHW circulation pump 112 "System definition" Ó "System scheme 7000" "Internal hydraulics" Ó "Enable three-way diverter valve heating/ DHW 730D" "External heat source" Ó "Enable external heat source for DHW heating 7B0D" "System definition" Ó "System scheme 7000" Extended menu: "Time prog. DHW circ." With DHW heating "0" "1" With DHW heating Setting a time program

113 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Pump/component Parameter Setting Circulation pump for "External heat source" Ó "1" DHW reheating "Enable external heat source 7B00" "External heat source" Ó "1" Solar thermal system Remote control (e.g. Vitotrol 200A) "Enable external heat source for DHW heating 7B0D" "Solar" Ó "Type solar control unit 7A00" "Heating circuit 1" Ó "Remote control 2003" or "Heating circuit 2" Ó "Remote control 3003" or "Heating circuit 3" Ó "Remote control 4003" "1" (with Vitosolic 100) "2" (with Vitosolic 200) "1" Note Set code at the Vitotrol 200A to assign heating circuits: H1 for heating circuit A1 H2 for heating circuit M2 H3 for heating circuit M3 (see Vitotrol 200 A installation instructions) Vitocom 100 External extension H1 "System definition" Ó "Vitocom " "System definition" Ó "External extension 7010" "1" "1" Note For parameters for external functions, see separate table. Service 113

114 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Two-stage heat pump Parameter Setting Compressor 2: "Enable compressor 5100" "1" "Output compressor stage " Value corresponding to the rated heating output of heat pump stage 2, see type plate External functions External functions Parameter Setting External demand Poss. "Internal hydraulics" Ó "Flow temperature for external demand 730C" Set flow temperature for external demand External starting of the compressor; mixer in control mode or OPEN External changeover of the operating mode of various system components External blocking of compressor and pumps "System definition" Ó "Effect of external demand on heat pump/heating circuits 7014" "System definition" Ó "System components for external changeover 7011" "System definition" Ó "Operating status for external changeover 7012" "System definition" Ó "Duration of external changeover 7013" "System definition" Ó "Effect of external blocking on pumps/compressor 701A" "0" to "7" (Observe parameter "Flow temperature for external demand 730C") "0" to "10" "0" to "3" "0" to "12" "0" to "31" 114

115 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) External functions Parameter Setting External blocking of the compressor; "System definition" Ó "0" to "8" mixer in control mode or CLOSED "Effect of external blocking on heat pump/heating circuits 7015" "System definition" Ó "0" to "31" "Effect of external blocking on pumps/compressor 701A" Central fault message No parameters need to be set. Cooling function Cooling function parameters "Cooling" Ó "Cooling function 7100" "Cooling" Ó "Cooling circuit 7101" Setting "0" (no cooling) "2" (natural cooling on cooling circuit without mixer) "3" (natural cooling on cooling circuit with mixer) "4" (active cooling) "1" (heating circuit A1) "2" (heating circuit M2) "3" (heating circuit M3) "4" (separate cooling circuit) Instantaneous heating water heater Parameters for Instantaneous heating water heater "Electr booster heater" Ó "Enable instantaneous heating water heater 7900" Poss. "Electr booster heater" Ó "Enable instant. heating water heater for central heating 7902" "Electr booster heater" Ó "Output for instant. heating water heater at power-off 790A" Poss. "DHW" Ó "Enable electric heaters for DHW heating 6015" Setting "1" "1" "1" for 3 kw "2" for 6 kw "3" for 9 kw "1" Service 115

116 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) External heat source External heat source parameters "External heat source" Ó "Enable external heat source 7B00" With circulation pump for DHW reheating: "External heat source" Ó "Enable booster heaters for DHW heating 6014" Setting "1" "1" Swimming pool water heating Parameters for swimming pool water heating "System definition" Ó "External extension 7010" "System definition" Ó "Swimming pool 7008" Setting "1" "1" Heat pump cascade Cascade via external extension H1 Parameter "System definition" Ó "System scheme 7000" "System definition" Ó "External extension 7010" "System definition" Ó "Cascade control 700A" "System definition" Ó "Number of lag heat pumps in cascade 5735" "System definition" Ó "Output lag heat pump 700B" "System definition" Ó "Use of heat pump in a cascade 700C" "System definition" Ó "Flow temperature for external demand 730C" Setting Lead appliance Lag heat pump "0" to "10" "11" "1" "0" "1" "0" "1" to "3" "0" to "255" "0" to "3" "0" to "700" ( 0 to 70 C) 116

117 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Cascade via LON Parameter "System definition" Ó "System scheme 7000" "System definition" Ó "Cascade control 700A" "System definition" Ó "Number of lag heat pumps in cascade 5735" "System definition" Ó "Output lag heat pump 700B" "System definition" Ó "Use of heat pump in a cascade 700C" "System definition" Ó "Flow temperature for external demand 730C" "Communication" Ó "Heat pump number in cascade (LON) 5707" "Communication" Ó "Enable LON communication module 7710" "Communication" Ó "LON subscriber number 7777" "Communication" Ó "LON system number 7798" "Communication" Ó "LON fault manager 7779" Setting Lead appliance Lag heat pump "0" to "10" "11" "2" "0" "1" to "4" "0" to "255" "0" to "31" "0" to "31" "0" to "700" ( 0 to 70 C) "1" to "4" (unique) "1" "1" to "99" (unique) "1" to "99" (unique) "1" to "5" "1" to "5" (as per lead appliance) "1" to "99" (unique) "1" to "99" (unique) Service The additional parameters for the heat pump cascade are set during commissioning by the certified heat pump contractor. 117

118 Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Instructing the system user The system installer must hand the operating instructions to the system user and instruct him/her in the operation of the system. 118

119 Troubleshooting Repairs Overview of electrical connection area Type BW 301.A and BWC 301.A H K LM N O G F E D C B A Service 119

120 Troubleshooting Repairs (cont.) Type BWS 301.A N Q R G F E D B A A Transformer EEV PCB B EEV PCB (electronic expansion valve) C Phase monitor D Compressor contactor E Thermal relay F Cable channel G Full wave soft starter H Programming unit K Controller and sensor PCB L Main PCB M Extension PCB on main PCB N Compressor power supply O Cross connect PCB Q Plug for connecting cable stage 1/2, low voltage < 42 V R Plug for connecting cable stage 1/2 230 V~ 120

121 Troubleshooting Repairs (cont.) Opening the shield Service 121

122 Troubleshooting Repairs (cont.) Overview of internal components A B C D E F P G O N + I J K L M 122

123 Troubleshooting Repairs (cont.) D X Q R T S D C Q R S T U P X F K J V W A Condenser B Evaporator C Primary circuit flow temperature sensor (heat pump brine inlet) D Schrader low pressure valve E Schrader high pressure valve F Instantaneous heating water heater (accessory) G Primary pump (accessory for type BW 301.A) I Electronic expansion valve (EEV) J Compressor K Flow temperature sensor, secondary circuit L Return temperature sensor, secondary circuit M Drain valve on the secondary side N Circulation pump for cylinder heating (accessory for type BW 301.A) 123 Service

124 Troubleshooting Repairs (cont.) O Secondary pump (accessory for type BW 301.A) P Air vent valve on the secondary side Q Low pressure sensor EEV R Suction gas temperature sensor S Safety high pressure switch T High pressure sensor EEV U Filter dryer V Primary circuit return temperature sensor (heat pump brine outlet) W Drain valve, primary side X Hot gas temperature sensor Draining the heat pump on the primary/secondary side 1. Shut off the connection to the heating network. 2. Drain heat pump at drain valve on primary/secondary side (see page 122). Checking sensors Sensor connections to the controller and sensor PCB. Temperature sensors type Ni For the position of the sensors in the heat pump, see diagram on page 122. Capturing element: "Ni 500" Outside temperature sensor (F0) Flow temperature sensor, heating circuit M2 (F12) Flow temperature sensor, separate cooling circuit Room temperature sensors Resistance in Temperature in C 124

125 Troubleshooting Repairs (cont.) Temperature sensors type Pt Resistance in Temperature in C Capturing element "Pt 500" System flow temperature sensor (F13) Buffer temperature sensor (F4) Cylinder temperature sensor (F6) Flow/return temperature sensor, secondary circuit (F8/F9) All sensors inside the heat pump Boiler temperature sensor, external heat source Checking the fuse Fuse locations (see page 72): Fuse F1 is located on the cross connect PCB. Fuse F3 is located on the main PCB. Fuse F1 and F3: 6.3 A (slow), 250 V~ Max. power loss 2.5 W Danger Contact with 'live' components can lead to severe injury from electric current. Before working on the equipment, always ensure that the power circuit is also at zero volt. Removing the fuse does not switch the power circuit to zero volt. Appliance too noisy Possible causes: Transport locking bracket not removed: See page 64. Hose outlets in diaphragm grommets not watertight: See page 104. Control unit door not tightly sealed: See page 121. Service 125

126 Parts lists Parts lists Ordering parts The following information is required: Serial no. (see type plate A) Assembly (from this parts list) Position number of the individual part within the assembly (from this parts list) Obtain standard parts from your local supplier. 126

127 Parts lists Overview of the assemblies A B E D C Service A Type plate B Assembly, casing C Assembly, hydraulics D Assembly, heat pump module E Assembly, electrical equipment 127

128 Parts lists Parts not shown 0005 Pack, casing 0006 Touch-up paint stick, Vitosilver 0007 Touch-up paint spray, Vitosilver 0008 Operating instructions for Vitotronic 200, type WO1A 0009 Service instructions for Vitotronic 200, type WO1A 0010 Vitocal installation and service instructions Assembly, casing Type BW 301.A, BWC 301.A, WW 301.A, WWC 301.A 0001 Rubber cushion D 42 x 40, M8 x Hinge, upper part 0003 Hinge, lower part 0004 Adjustable foot M12 x 19, foot cap D Side panel, left 0006 Side panel, right 0007 Top panel, back 0008 Back panel 0009 Control panel 0010 Anti-vibration mount 0011 Bottom panel 0012 Lower panel 0013 Floor mat 0014 Rail 0015 Cable cover set 0016 Top panel, front 0017 Front panel 0018 Shield 0019 Vitocal 300 logo 0020 Diaphragm grommet DG Decorative cap 0022 Location stud M5 128

129 Parts lists Assembly, casing (cont.) Type BW 301.A, BWC 301.A, WW 301.A, WWC 301.A Service

130 Parts lists Assembly, casing (cont.) Type BWS 301.A 0001 Rubber cushion D 42 x 40, M8 x Hinge, upper part 0003 Hinge, lower part 0004 Adjustable foot M12 x 19, foot cap D Side panel, left 0006 Side panel, right 0007 Top panel, back 0008 Back panel 0009 Control panel 0010 Anti-vibration mount 0011 Bottom panel 0012 Lower panel 0013 Floor mat 0014 Rail 0015 Cable cover set 0016 Top panel, front 0017 Front panel 0018 Shield 0020 Diaphragm grommet DG Decorative cap 0022 Location stud M5 130

131 Parts lists Assembly, casing (cont.) Type BWS 301.A Service

132 Parts lists Assembly, hydraulics Type BW 301.A, BWS 301.A, WW 301.A 0001 Spring clip 0002 Air vent valve G⅜ 0003 Gasket A 30 x 44 x Drain & fill valve G⅜ 0005 Spring clip D Clip for threaded pipe D 31 35, M8, EPDM insert 0007 Secondary flow hose 0008 Hose, heating water return/dhw cylinder return 0009 Tee 0010 Hose, primary return (brine outlet) 0011 Hose, primary flow (brine inlet) 0012 Hose, heating water flow 0013 Hose, DHW cylinder flow 0014 Retainer 0016 Temperature sensor Pt O-ring 28.0 x

133 Parts lists Assembly, hydraulics (cont.) Type BW 301.A, BWS 301.A, WW 301.A Service 133

134 Parts lists Assembly, hydraulics (cont.) Type BWC 301.A, WWC 301.A 0001 Gasket A 35 x 45 x Spring clip 0003 Air vent valve G⅜ 0004 Temperature sensor Pt Gasket A 30 x 44 x Drain & fill valve G⅜ 0007 Spring clip D Hose, heating water return/dhw cylinder return 0009 Hose, primary flow (brine inlet) 0010 Line 0011 Secondary flow hose 0012 Hose, primary return (brine outlet) 0013 Check valve G 1½ 0014 Hose, DHW cylinder flow 0015 Hose, heating water flow 0016 Circulation pump VIRS25/ Circulation pump head VIRS / High efficiency circulation pump 0019 High efficiency circulation pump 0020 Clip for threaded pipe D 31 35, M8, EPDM insert 0021 O-ring 28.0 x Retainer 0023 Safety assembly 134

135 Parts lists Assembly, hydraulics (cont.) Type BWC 301.A, WWC 301.A Service

136 Parts lists Assembly, heat pump module All types 0001 Compressor 0002 Evaporator 0003 Condenser 0004 Electronic expansion valve EXL B1G 0005 Filter dryer DML Pressure sensor PT5-18T 0007 Pressure sensor PT5-50T 0008 Pressure switch CC Sealing cap B Cooling panel 0011 Retainer, heat exchanger 0012 Rubber cushion D 40 x 40, M8 x Schrader valve 0014 Line, hot gas 0015 Spacer 0016 Line, electronic expansion valve - evaporator 0017 Compressor fixing 0018 Line, filter dryer - electronic expansion valve 0019 Line, condenser - filter 0020 Primary flow line 0021 Line, suction gas 0022 Union nut, Schrader valve 0023 Air vent valve G⅜ 0024 Cheese head screws M8 (2 pce) 0025 Spring clip 0026 Temperature sensor Pt

137 Parts lists Assembly, heat pump module (cont.) All types Service

138 Parts lists Assembly, electrical equipment Type BW 301.A06, WW 301.A06, BWC 301.A06, WWC 301.A Base carrier CU PCB CU401 with cover 0003 Base carrier MB PCB MB761 with cover 0005 PCB SA135 with cover 0011 Cable harness, PCB 230 V~ 0012 Cable channel 0014 Control module 400 V~, 6-9 A 0015 PCB IU210-A10 H_1 S_ Expanding rivets 0017 Transformer pin contactor, K2-12A10, 230 V~ 0023 Thermal relay ( A) 0024 Mains terminals 0025 Phase monitor EMD-SL-PH Casing, programming unit 0030 Coding card 0033 Programming unit Parts not shown 0006 Connecting cable, compressor 0007 Cable harness 230 V~ 0008 Cable harness X5, low voltage 0009 Cable kit EEV 4-17 kw pin connecting cable, length 85 mm 0019 Ribbon cable AWG 28, 24x0.09 folded 0020 Cable harness, power supply EEV 0021 Cable harness, EEV module 0026 Only type BWC/WWC: Plug sh (white) 0027 Only type BWC/WWC: Plug sg (white) 0028 Only type BWC/WWC: Plug lj (black) 138

139 Parts lists Assembly, electrical equipment (cont.) Type BW 301.A06, WW 301.A06, BWC 301.A06, WWC 301.A Service

140 Parts lists Assembly, electrical equipment (cont.) Type BW 301.A08 to 301.A17, WW 301.A08 to 301.A17, BWC 301.A08 to 301.A17, WWC 301.A08 to 301.A Base carrier CU PCB CU401 with cover 0003 Base carrier MB PCB MB761 with cover 0005 PCB SA135 with cover 0011 Cable harness, PCB 230 V~ 0012 Cable channel 0013 Full wave soft starter 0014 Control module 400 V~, 6-9 A 0015 PCB IU210-A10 H_1 S_ Expanding rivets 0017 Transformer pin contactor, K2-12A10, 230 V~ 0023 Thermal relay ( A) 0024 Mains terminals 0025 Phase monitor EMD-SL-PH Casing, programming unit 0030 Coding card 0033 Programming unit Parts not shown 0006 Connecting cable, compressor 0007 Cable harness 230 V~ 0008 Cable harness X5, low voltage 0009 Cable kit EEV 4-17 kw pin connecting cable, length 85 mm 0019 Ribbon cable AWG 28, 24x0.09 folded 0020 Cable harness, power supply EEV 0021 Cable harness, EEV module 0026 Only type BWC/WWC: Plug sh (white) 0027 Only type BWC/WWC: Plug sg (white) 0028 Only type BWC/WWC: Plug lj (black) 140

141 Parts lists Assembly, electrical equipment (cont.) Type BW 301.A08 to 301.A17, WW 301.A08 to 301.A17, BWC 301.A08 to 301.A17, WWC 301.A08 to 301.A Service

142 Parts lists Assembly, electrical equipment (cont.) Type BWS 301.A Cable channel 0014 Control module 400 V~, 6-9 A 0015 PCB IU210-A10 H_1 S_ Expanding rivets 0017 Transformer pin contactor, K2-12A10, 230 V~ 0023 Thermal relay ( A) 0024 Mains terminals Parts not shown 0006 Connecting cable, compressor 0007 Cable harness 230 V~ 0008 Cable harness X5, low voltage 0009 Cable kit EEV 4-17 kw 0020 Cable harness, power supply EEV 0021 Cable harness, EEV module 142

143 Parts lists Assembly, electrical equipment (cont.) Type BWS 301.A Service 143

144 Parts lists Assembly, electrical equipment (cont.) Type BWS 301.A08 to 301.A Cable channel 0013 Full wave soft starter 0014 Control module 400 V~, 6-9 A 0015 PCB IU210-A10 H_1 S_ Expanding rivets 0017 Transformer pin contactor, K2-12A10, 230 V~ 0023 Thermal relay ( A) 0024 Mains terminals Parts not shown 0006 Connecting cable, compressor 0007 Cable harness 230 V~ 0008 Cable harness X5, low voltage 0009 Cable kit EEV 4-17 kw 0020 Cable harness, power supply EEV 0021 Cable harness, EEV module 144

145 Parts lists Assembly, electrical equipment (cont.) Type BWS 301.A08 to 301.A Service 145

146 Commissioning/service reports Commissioning/service reports Hydraulic parameters report Setting and test values Set value Commissioning Frost protection (brine medium) C 15 Testing the external heating circuit pumps Circulation pump type Circulation pump stage Overflow valve setting Primary circuit commissioning Primary circuit flow temperature C Primary circuit return temperature C Temperature differential ΔT: Secondary circuit flow temperature = K 3 to 5 35 C when primary circuit flow temperature = 10 C Secondary circuit flow temperature = 35 C when primary circuit flow temperature = 0 C K 2 to 4 Testing the mixer, heat pump and cylinder heating Checked under the following conditions: Room temperature C Outside temperature C Temperature "Cylinder temp. top" constant? Yes (±1 K) Secondary circuit flow temperature C rising from to Temperature differential ΔT "Flow temp. secondary" / "Return temp. sec." 6 to 8 K Control parameters report For a description of parameters, see separate service instructions, heat pump control unit Vitotronic

147 Commissioning/service reports Commissioning/service reports (cont.) Parameter Code Delivered condition System definition System scheme (see chapter "Overview of possible system schemes") Temperature differential for calculating ( 4 K) the heating limit Temperature differential for calculating ( 4 K) the cooling limit Swimming pool External extension Cascade control 700A 0 Number of lag heat pumps in cascade Output lag heat pump 700B 10 kw Use of heat pump in a cascade 700C 0 System components for external changeover Operating status for external changeover Effect of external blocking on pumps/ 701A 0 compressor Duration of external changeover h Effect of external demand on heat pump/ heating circuits Effect of ext. blocking on heat pump/heating circuits Vitocom Effect of external blocking on pumps/ 701A 0 compressor Common flow temperature sensor system 701B 1 Compressor Enable compressor Output compressor stage Rated heating output acc. to type plate Enable compressor Output compressor stage Rated heating output acc. to type plate Commissioning 147 Service

148 Commissioning/service reports Commissioning/service reports (cont.) Parameter Code Delivered condition Ext. heat source Enable external heat source 7B00 0 Priority ext. heat source/instant. heating 7B01 1 water heater Dual mode temperature external heat 7B ( 10 C) source Enable external heat source for DHW 7B0D 0 heating DHW Set DHW temperature ( 50 C) Min. DHW temperature ( 10 C) Max. DHW temperature ( 60 C) Hysteresis DHW temperature heat pump ( 7 K) Hysteresis DHW temperature instant ( 10 K) heating water heater Start optimisation for DHW heating Stop optimisation for DHW heating 600A 0 Set DHW temperature 2 600C 600 ( 60 C) Temperature sensor at bottom of DHW 600E 0 cylinder Enable booster heaters for DHW heating Enable electric heaters for DHW heating Priority DHW heating with combi cylinder Start attempts for DHW after high pressure shutdown Operating mode cylinder primary pump 6020 Never adjust! Solar Type solar control unit 7A00 0 Commissioning 148

149 Commissioning/service reports Commissioning/service reports (cont.) Parameter Code Delivered condition Electric booster heater Enable instantaneous heating water heater Enable instant. heating water heater for central heating Max. output instantaneous heating water heater Output for instant. heating water heater at 790A 0 power-off Dual mode temp. instant. heating water 790B 100 ( 10 C) heater Internal hydraulics Heat pump for drying a building Time program for screed drying Set flow temperature, external demand 730C 500 ( 50 C) Operating mode primary pump 7320 Never adjust! Operating mode secondary pump 7340 Never adjust! Heating water buffer cylinder Enable buffer cylinder / low loss header Temp. in operating status fixed value for ( 50 C) buffer cyl Hysteresis temperature heating buffer ( 5 K) cylinder Max. temperature buffer cylinder ( 60 C) Temp. limit op. status fixed value for buffer ( 10 C) cylinder Heating circuit 1 Standard room temperature ( 20 C) Reduced room temperature ( 16 C) Remote control Heating curve level ( 0 K) Heating curve slope ( 0.6) Influence room temperature hook-up 200A 10 Room temperature hook-up 200B 3 Max. flow temperature heating circuit 200E 400 ( 40 C) Room temperature in party mode ( 20 C) Commissioning Service 149

150 Commissioning/service reports Commissioning/service reports (cont.) Parameter Code Delivered condition Heating circuit 2 Standard room temperature ( 20 C) Reduced room temperature ( 20 C) Remote control Heating curve level ( 0 K) Heating curve slope ( 0.6) Influence room temperature hook-up 300A 10 Room temperature hook-up 300B 3 Max. flow temperature heating circuit 300E 400 ( 40 C) Room temperature in party mode ( 16 C) Heating circuit 3 Standard room temperature ( 20 C) Reduced room temperature ( 20 C) Remote control Heating curve level ( 0 K) Heating curve slope ( 0.6) Influence room temperature hook-up 400A 10 Room temperature hook-up 400B 3 Max. flow temperature heating circuit 400E 400 ( 40 C) Room temperature in party mode ( 16 C) Cooling Cooling function Cooling circuit Set room temperature separate cooling ( 20 C) circuit Min. flow temperature cooling ( 10 C) Influence room temperature hook-up cooling circuit Cooling curve level ( 0 K) Cooling curve slope ( 1.2) Active cooling function on site 71FE 0 Commissioning 150

151 Commissioning/service reports Commissioning/service reports (cont.) Parameter Code Delivered condition Time Automatic changeover summertime - 7C00 1 wintertime Start summertime - month 7C01 3 Start summertime - week 7C02 5 Start summertime - day 7C03 7 Start wintertime - month 7C04 10 Start wintertime - week 7C05 5 Start wintertime - day 7C06 7 Communication Heat pump number in cascade Enable LON communication module LON subscriber number LON fault manager Outside temperature LON system number Interval for data transfer via LON 779C 20 min Time via LON 77FF 0 Control Lock out controls Commissioning Service 151

152 Specification Specification Type BW 301.A/BWS 301.A Output data to DIN EN (B0/ W35 C, 5 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Output data to DIN EN (B0/ W35 C, 10 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Brine (primary circuit) Content l Min. flow rate (spread 5 K) l/h Pressure drop (at min. flow mbar rate) Max. flow temperature C Min. flow temperature C Heating water (secondary circuit) Content l Min. flow rate (spread 10 K) l/h Pressure drop (at min. flow mbar rate) Max. flow temperature C

153 Specification Specification (cont.) Type BW 301.A/BWS 301.A Electrical values, heat pump Rated voltage, compressor 3/N/PE 400 V/50 Hz Rated current, compressor A Starting current, compressor A (with starting current limiter, not in type BW/BWS/BWC 301.A06) Starting current, compressor A with stalled armature Compressor fuse A C16A B16A B16A 3-pole 3-pole 3-pole Protection class I Electrical values, control unit (only for type BW 301.A) Rated voltage 1/N/PE 230 V/50 Hz Fuse protection B16A Fuses 2 x 6.3 AH slow/250 V Max. power consumption W 1000 B16A 3-pole C20A 3-pole Power consumption in operation W 5 Refrigerant circuit Refrigerant R 410 A Fill volume kg Compressor Type Hermetic scroll Permiss. operating pressure Primary circuit bar 28 Secondary circuit bar 43 Dimensions Total length mm 844 Total width mm 600 Total height (programming unit open) mm 1155 Service 153

154 Specification Specification (cont.) Type BW 301.A/BWS 301.A Connections Primary flow and return G 1½ Heating flow and return G 1½ Weight Heat pump stage 1 (type kg BW 301.A) Heat pump stage 2 (type kg BWS 301.A) Sound power level at B0/W35 C (test with reference to DIN EN ISO ) db(a) Type WW 301.A/BWS 301.A in conjunction with "conversion kit for water/water heat pump" Output data to DIN EN (W10/ W35 C, 5 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Brine (primary circuit) Content l Min. flow rate (spread 4 K) l/h Pressure drop (at min. flow mbar rate) Max. flow temperature C Min. flow temperature C Heating water (secondary circuit) Content l Min. flow rate (spread 10 K) l/h Pressure drop (at min. flow mbar rate) Max. flow temperature C

155 Specification Specification (cont.) Type WW 301.A/BWS 301.A in conjunction with "conversion kit for water/water heat pump" Electrical values, heat pump Rated voltage, compressor 3/N/PE 400 V/50 Hz Rated current, compressor A Starting current, compressor A (with starting current limiter, not in type BW/BWS/BWC 301.A06) Starting current, compressor A with stalled armature Compressor fuse A C16A B16A B16A 3-pole 3-pole 3-pole Protection class I Electrical values, control unit (only for type WW 301.A) Rated voltage 1/N/PE 230 V/50 Hz Fuse protection B16A Fuses 2 x 6.3 AH slow/250 V Max. power consumption W 1000 B16A 3-pole C20A 3-pole Power consumption in operation W 5 Refrigerant circuit Refrigerant R 410 A Fill volume kg Compressor Type Hermetic scroll Permiss. operating pressure Primary circuit bar 28 Secondary circuit bar 43 Dimensions Total length mm 844 Total width mm 600 Total height (programming unit open) mm 1155 Service 155

156 Specification Specification (cont.) Type WW 301.A/BWS 301.A in conjunction with "conversion kit for water/water heat pump" Connections Primary flow and return G 1½ Heating flow and return G 1½ Weight Heat pump stage 1 (type kg WW 301.A) Heat pump stage 2 (type kg BWS 301.A) Sound power level at B0/W35 C (test with reference to DIN EN ISO ) db(a) Type BWC 301.A Output data to DIN EN (B0/ W35 C, 5 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Output data to DIN EN (B0/ W35 C, 10 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Brine (primary circuit) Content l Min. flow rate (spread 5 K) l/h Residual head (at min. flow mbar rate) Max. flow temperature C Min. flow temperature C

157 Specification Specification (cont.) Type BWC 301.A Heating water (secondary circuit) Content l Min. flow rate (spread 10 K) l/h Residual head (at min. flow mbar rate) Max. flow temperature C Electrical values, heat pump Rated voltage, compressor 3/N/PE 400 V/50 Hz Rated current, compressor A Starting current, compressor A (with starting current limiter, not in type BW/BWS/BWC 301.A06) Starting current, compressor A with stalled armature Compressor fuse A C16A B16A B16A 3-pole 3-pole 3-pole Protection class I Electrical values, control unit Rated voltage 1/N/PE 230 V/50 Hz Fuse protection B16A Fuses 2 x 6.3 AH slow/250 V Max. power consumption W 1000 B16A 3-pole C20A 3-pole Power consumption in operation W 5 Refrigerant circuit Refrigerant R 410 A Fill volume kg Compressor Type Hermetic scroll Permiss. operating pressure Primary circuit bar 28 Secondary circuit bar 43 Service 157

158 Specification Specification (cont.) Type BWC 301.A Dimensions Total length mm 844 Total width mm 600 Total height (programming mm 1155 unit open) Connections Primary flow and return G 1½ Heating flow and return G 1½ Weight kg Sound power level at B0/W35 C (test with reference to DIN EN ISO ) db(a) Type WWC 301.A Output data to DIN EN (W10/ W35 C, 5 K spread) Rated heating output kw Cooling capacity kw Power consumption kw Coefficient of performance ε (COP) Brine (primary circuit) Content l Min. flow rate (spread 4 K) l/h Residual head (at min. flow mbar rate) Max. flow temperature C Min. flow temperature C Heating water (secondary circuit) Content l Min. flow rate (spread 10 K) l/h Residual head (at min. flow mbar rate) Max. flow temperature C

159 Specification Specification (cont.) Type WWC 301.A Electrical values, heat pump Rated voltage, compressor 3/N/PE 400 V/50 Hz Rated current, compressor A Starting current, compressor A (with starting current limiter, not in type BW/BWS/BWC 301.A06) Starting current, compressor A with stalled armature Compressor fuse A C16A B16A B16A 3-pole 3-pole 3-pole Protection class I Electrical values, control unit Rated voltage 1/N/PE 230 V/50 Hz Fuse protection B16A Fuses 2 x 6.3 AH slow/250 V Max. power consumption W 1000 B16A 3-pole C20A 3-pole Power consumption in operation W 5 Refrigerant circuit Refrigerant R 410 A Fill volume kg Compressor Type Hermetic scroll Permiss. operating pressure Primary circuit bar 28 Secondary circuit bar 43 Dimensions Total length mm 844 Total width mm 600 Total height (programming unit open) mm 1155 Service 159

160 Specification Specification (cont.) Type WWC 301.A Connections Primary flow and return G 1½ Heating flow and return G 1½ Weight kg Sound power level at B0/W35 C (test with reference to DIN EN ISO ) db(a)

161 Appendix Heat pump commissioning order Please send the following order, together with the enclosed system scheme, by fax to your local Viessmann sales office. We would ask that a competent employee of yours be present during commissioning. System details: Client System location Please tick these check points: = Hydraulic scheme for system example included: = System example 1 = System example 2 = Sketch for alternative hydraulic scheme = Heating circuits fully installed and filled = Electrical installation completed = Hydraulic lines fully thermally insulated = All windows and external doors sealed = Geothermal probes/well and connection lines fully installed = Components for cooling mode fully installed (option) Preferred appointment: 1. Date Time 2. Date Time All work ordered from Viessmann will be charged to me/us in accordance with the current Viessmann pricelist. Service Place/date Signature 161

162 Certificates Declaration of conformity We, Viessmann Werke GmbH&Co KG, D Allendorf, declare as sole responsible body that the product Vitocal 300-G, type BW, WW, BWS, BWC, WWC incl. Vitotronic 200, type WO1A complies with the following standards: DIN 7003 DIN EN ; DIN 8901 DIN EN ; DIN 8975 DIN EN ; DIN EN ; DIN EN (VDE ) DIN EN ; DIN EN Rep (VDE ) DIN EN ; EN 292/T1/T2 DIN EN ; EN 294 DIN EN ; EN 349 DIN EN with A1; EN 378; DIN EN ; BGR 500, Chapter 2.35 In accordance with the following Directives, this product is designated with _: 2004/108/EC 97/23/EC 2006/42/EC 2006/95/EC Details according to the Pressure Equipment Directive (92/93/EC): Category II, module A1 The product characteristics determined as system values for the product Vitocal 300-G (see technical guide) can be utilised to assess the energy consumption of heating and ventilation systems to DIN V specified by the EnEV [Germany]. Allendorf, 15 September 2010 Viessmann Werke GmbH&Co KG pp. Manfred Sommer 162

163 Keyword index Keyword index A Activating, service menu Appliance fuse Appliance too noisy Assembly B Brine pressure switch C Cascade Control version Number of lag heat pumps...116, 117 Switching version Use of heat pump...116, 117 Checking Fuse Sensors Commissioning...106, 161 Commissioning assistant Commissioning order Connections...10 Hydraulic...66 Primary circuit...66 Secondary circuit...67 Connection values Function components...80 Operating components...75 Control parameters reports Control unit...68 Control unit door Cylinder With primary store system...32 D Declaration of conformity DHW cylinder With internal indirect coil...32 DHW heating...32 Dimensions...10 Draining secondary side heat pump 124 E Electrical connection 68 General information...6 Heat pump control unit...72 Electrical connections Inserting cables...69 Electrical installation scheme DHW heating...33, 35 Enable External extension Expansion vessel, checking Extended menu Extension kit for heating circuit with mixer...79, 112 External extension Enable External functions F Filling Primary side Secondary side Flow temperature With external demand...116, 117 Fuse, checking H Heat pump cascade...38 Heat pump module Installation Hydraulic connections...66 Hydraulic parameters I ID: _1008_ ID: _1008_01, type AWS...48 ID: _1008_01, type AWS...54 Immersion heater...84 Inspection Installation...6, 10 Installation room...6 Instructing the system user

164 Keyword index Keyword index (cont.) Internal components Overview Isolators...94 L Lag heat pump...38 LON communication module...39 LON module...39 M Maintenance Maximum temperature limiter...78 Minimum clearances...7 Minimum room volume...7 N Ni Noise Noise volume O On-site connections...10 Output Lag heat pump...116, 117 Overview Internal components Pumps Sensors Valves P Parameter Setting example Parameters Cascade via H Cascade via LON Cooling function External functions External heat source Instantaneous heating water heater On-site components Pumps Report Swimming pool water heating Parts lists...126, 128 Phase monitor Power-OFF...96 Power supply...94 Pressure, checking Primary circuit Connecting...66 Filling and venting Type BW...14 Type WW...16 Primary circuit pressure switch Primary store system...32 Pt Pumps...112, 122 R Refrigerant circuit, checking for leaks Remote control Repairs Repair work Reports Control parameters Required equipment...15, 33, 35 Resistance curves of sensors Room height...6 Room volume

165 Keyword index Keyword index (cont.) S Sealing faces Secondary circuit Connecting...67 Filling and venting Sensors Sensors, checking Service menu Activating Calling up Disabling Swimming pool...91 System example...42, 48, 54 System pressure, checking System scheme...42, 48, 54, 116, 117 System schemes Overview...12 T Temperature limiter...78 Terminating service Three phase monitor Tilting angle...6 Transport brackets...64 Transport locking bracket U Underfloor heating circuit...78 Underfloor heating system...78 Use of heat pump in a cascade116, 117 V Venting Primary side Secondary side Vitocom W Wall clearances

166 166

167 167

168 Printed on environmentally friendly, chlorine-free bleached paper Applicability Serial No.: Viessmann Werke GmbH&Co KG D Allendorf Telephone: Fax: Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: Fax: Subject to technical modifications.

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw VIESMANN VITOCAL 00-G Brine/water and water/water heat pump Single and two-stage, from 21 kw Technical guide Heat pump with electric drive for DHW and central heating in mono-mode or dual mode heating

More information

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe.

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 200 Type SD4 For applicability, see the last page VITOSOLIC 200 1/2012 Please keep

More information

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer Installation instructions for contractors VIESMANN Mixer extension kit For one heating circuit with mixer Mixer extension kit 5/2017 Safety instructions Please follow these safety instructions closely

More information

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 100 Type SD1 For applicability, see the last page VITOSOLIC 100 4/2009 Please keep

More information

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors Installation and service instructions for contractors VIESMANN Vitocal 200-S Type AWB 201.B04 to B13, C10, C13 Air source heat pump, split version for heating operation Type AWB-AC 201.B04 to B13, C10,

More information

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors Installation instructions for contractors VIESMANN Vitodens 200-W Type WB2C, 45 and 60 kw Wall mounted gas condensing boiler Natural gas and LPG version VITODENS 200-W 1/2010 Dispose after installation.

More information

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no Installation and service instructions for contractors VIESMANN Vitotrol 300A Remote control, part no. 7438 364 VITOTROL 300A 3/2010 Please keep safe. Safety instructions Safety instructions Please follow

More information

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and Installation and service instructions for contractors VIESMANN Solar-Divicon SR Part no. 7419 520 and 7419 521 Safety instructions Please follow these safety instructions closely to prevent accidents and

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B

More information

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-A Type AWO-AC 301.B11 to B14 Air/water heat pump with electric drive, 400 V~ For applicability, see the last page VITOCAL 300-A

More information

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors Installation and service instructions for contracrs VIESMANN Vitronic 00 Type KOB, KOB Weather-compensated, digital boiler control unit For applicability, see the last page VITOTRONIC 00 /0 Please keep

More information

VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors Installation and service instructions for contracrs VIESMANN Vitronic 00 Type GWB Vitronic 300 Type GWB Weather-compensated, digital boiler control units For applicability, see the last page VITOTRONIC

More information

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit Installation and service instructions for contractors VIESMANN Vitotrol 200 RF Wireless remote control for one heating circuit For applicability, see the last page VITOTROL 200 RF 3/2011 Please keep safe.

More information

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A Installation instructions for contractors VIESMNN Vitocell 300-V/W Type EVI- DHW cylinder with internal indirect coil 160 to 500 l VITOCELL 300-V/W 3/2017 Dispose after installation. Safety instructions

More information

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA Installation and service instructions for contractors VIESMANN Vitocell 340-M/360-M Type SVKA Type SVSA Combi cylinder 750 and 950 litre capacity VITOCELL 340-M/360-M 4/2009 Please keep safe. Safety instructions

More information

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation. Installation instructions for contractors PYROMAT ECO PYROMAT ECO 8/2012 Dispose after installation. Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracrs Vitronic 100 Type GC1B Digital boiler control unit For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 100 Product may not be exactly

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 5/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMANN Extension AM1 Part no. 7429 152 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner VITOCROSSAL 300 2/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner VITOCROSSAL 200 2/2007 Dispose after installation. Safety instructions

More information

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference.

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracr Vitronic 300 Type GW2B Weather-compensated, digital boiler control units For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 300

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 6/2011 Please keep safe. Safety

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 6/2011 Dispose after installation. Safety instructions Please

More information

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O VIESMANN VITOCAL Air/water heat pumps Technical guide VITOCAL 300-A Type AWC-I and AW-O Up to 60 C flow temperature Modulating output range 3 to 9 kw Reversible air source heat pump with electric drive

More information

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMNN Extension E1 Part no. 7429 151 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITODENS 200-W. for contractors Service instructions for contractors VIESMANN Vitodens 200-W Type WB2B, 4.8 to 35.0 kw Wall mounted gas fired condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater Installation and service instructions for contractors VIESMNN EHE immersion heater 6 kw and 12 kw For installation in HW cylinders For applicability, see the last page EHE immersion heater 9/2014 Please

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 100-W 1/2012 Please keep safe. Safety instructions For

More information

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses. Installation and service instructions for contractors VIESMANN Solar-Divicon and solar pump assembly Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser Vitocal 300-A, type AWC-I and AW-O.1 Product description A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser & High operational reliability,

More information

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 111-W 4/2012 Please keep safe. Safety instructions For

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 200-W Type B2HA, B2KA, 3.2 to 35 kw Gas council no. System boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 Combi boilers: 47-819-28;

More information

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 111-W Type B1LA, 6.5 to 35.0 kw Gas condensing storage combi boiler Natural gas and LPG version Gas Council no.: 47-819-23; 47-819-24;

More information

WZS 82(H)(K)3M 20 I B0W I I I (263) (288) 7.0

WZS 82(H)(K)3M 20 I B0W I I I (263) (288) 7.0 WZS 4(H)(K)M WZS 6(H)(K)M WZS 8(H)(K)M WZS (H)(K)M WZS 1(H)(K)M 0 I 60-5 5 B0W65 1 4 I I I -1 50 (58) 178 58 65 50 60 0 I 60-5 5 B0W65 1 4 I I I -1 55 (6) 178 58 65 50 60 0 I 60-5 5 B0W65 1 4 I I I -1

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contracrs VIESMANN Videns 200-W Type B2HA, 80 and 100 kw Wall mounted gas condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

Heating with airborne and geothermal energy making the best possible use of renewables

Heating with airborne and geothermal energy making the best possible use of renewables Heat pumps 2/3 Heating with airborne and geothermal energy making the best possible use of renewables This brochure provides detailed information on sustainable and environmentally responsible heat generation

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 2/2013 Please keep safe. Safety

More information

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service Service instructions Function module FM443 solar module For contractors Read carefully prior to commissioning or service 6 720 615 516-03/2008 GB/IE Contents 1 Safety........................................

More information

Heating with airborne and geothermal heat

Heating with airborne and geothermal heat Heating with airborne and geothermal heat 2/3 Heating with airborne and geothermal heat making the best possible use of renewables This brochure provides detailed information on sustainable and environmentally

More information

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors Installation and service instructions for contractors VIESMANN Vitodens 343-F Type WS4A Compact Energy Tower with a gas fired condensing boiler as compact model Natural gas and LPG version (GC no) 47-819-08

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJC, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council no.: 47 819 31, 47 819 32

More information

Data sheet SI 24TE. Brine-to-water heat pump with two performance levels

Data sheet SI 24TE. Brine-to-water heat pump with two performance levels Data sheet SI 24TE Brine-to-water heat pump with two performance levels Order reference: SI 24TE Installation location: Indoors Flow temperature max 60 C Casing, powder-coated Heat pump for heating purposes

More information

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation Operating instructions for system users VIESMANN Heating system with control unit for constant temperature operation VITODENS 100 2/2005 Please keep safe Safety instructions For your safety Please follow

More information

ADVANCE ELECTRIC THERMAL STORE

ADVANCE ELECTRIC THERMAL STORE ISSUE 13 1118 INSTALLATION AND USER GUIDE ADVANCE ELECTRIC THERMAL STORE ADVANCE APPLIANCES LTD HOUSEHOLDER PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. 2 INTRODUCTION Advance thermal

More information

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW VIESMANN VITOMAX 200-WS Hot water boiler for permissible flow temperatures up to 110 C 1.75 to 11.63 MW Datasheet Part no.: see pricelist, prices on request VITOMAX 200-WS Type M250 Oil/gas fired hot water

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJD, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council Number: 47 819 31, 47 819

More information

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors Installation instructions for contractors VIESMANN Vitomax 200-HW Type M238 Oil/gas fired high pressure hot water boiler Combustion output 4.0 to 18.2 MW VITOMAX 200-HW 6/2007 Dispose after installation.

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

Heating with natural heat

Heating with natural heat Heating with natural heat 2/3 Heat pumps: Heating and cooling with natural energy The purpose of this brochure is to give you detailed information about one of the most futureproof and environmentally

More information

Heat pumps. Heating systems Industrial systems Refrigeration systems

Heat pumps. Heating systems Industrial systems Refrigeration systems Heat pumps Heating systems Industrial systems Refrigeration systems 2/3 Heating with airborne and geothermal heat making the best possible use of renewables This brochure provides detailed information

More information

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe. Service instructions for contractors VIESMANN Vitoplex 200 Type SX2A, 90 to 560 kw Oil/gas boiler For applicability, see the last page VITOPLEX 200 3/2013 Please keep safe. Safety instructions Safety instructions

More information

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler Service instructions for contractors VIESMANN Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler For applicability, see the last page VITOCROSSAL 300 4/2009 Please keep safe. Safety

More information

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B VIESMANN VITOLIGNO 300-P Pellet boiler 4to48kW Datasheet For part no. and prices: see pricelist File in: Vitotec folder, register 12 VITOLIGNO 300-P Type VL3B Boiler for wood pellets 8/2007 Product information

More information

Installation Instructions VITOTRONIC 300

Installation Instructions VITOTRONIC 300 Installation Instructions Vitotronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Part No. Z001 231 VITOTRONIC 300 Certified

More information

Starting current with soft starter Fuse protection

Starting current with soft starter Fuse protection Data sheet LIH 26TE High temperature air-to-water heat pump Max. flow temperature: 75 C Casing colour: White (similar to RAL 9003) Brown-red design screen (RAL 3011) Heat pump for heating purposes for

More information

Planning guide. (2010/09) en

Planning guide. (2010/09) en Planning guide (2010/09) en 1 Planning guide for Greenline HE E 21, 28 and HE D 36, 43 Page Contents 3 Documentation and VPW2100 4 Technical data of heatpump 5 Dimensioning of DHW systems 6 Symbol explanations

More information

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250 VIESMANN VITOMAX -WS Rated heating output 1.75 to 11.63 MW Datasheet VITOMAX -WS Type M250 Oil/gas low pressure hot water boiler CE designation in accordance with the Gas Appliances Directive Permissible

More information

Type summary Albatros 2

Type summary Albatros 2 OEM Type summary lbatros 2 The lbatros 2 family is a comprehensive range of controls. It offers solutions for basic to complex heating plant. Uniform and integral operating philosophy with clear-text display

More information

Starting current with soft starter Fuse protection

Starting current with soft starter Fuse protection Data sheet SI 14ME Brine-to-water heat pump Max. flow temperature: 58 C Casing colour: White (similar to RAL 9003) Brown-red design screen (RAL 3011) Heat pump for heating purposes for indoor installation

More information

Starting current with soft starter Fuse protection. Heat source connection

Starting current with soft starter Fuse protection. Heat source connection Data sheet SI 17TE Brine-to-water heat pump max. flow temperature: 58 C Casing colour: white Brown-red design screen (RAL 3011) Heat pump for indoor installation with integrated regulation WPM 2007 plus.

More information

BWL air heat pumps BWS brine heat pumps

BWL air heat pumps BWS brine heat pumps BWL air heat pumps BWS brine heat pumps Wolf - Heat pumps Benefits offered by Wolf heat pumps From each 1 kwh power, heat pumps generate between 3 and 5 kwh heat Free environmental energy from the ground

More information

KOSPEL S.A. UL. OLCHOWA KOSZALIN

KOSPEL S.A. UL. OLCHOWA KOSZALIN Used product can't be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment for recycling. Appropriate utilisation

More information

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: 560955 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) 1 CONTENTS Page 1) INTRODUCTION 1.1) Description 3 1.2) Dimensions & connections

More information

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 0 l capacity Datasheet Part no. and prices: see pricelist VITOCELL 300-V Type EVA and EVI Vertical DHW cylinder made from stainless steel 5/2012 Product

More information

Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 200-W

Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 200-W Technical Data Manual Model Nos. and pricing: see Price List For Natural Gas and Liquid Propane Gas Gas-fired wall-mounted condensing boiler 12 to 285 MBH (3.5 to 83.5 kw) Multi-boiler installation 480

More information

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 01 CONTENTS Special information 2 General information 3 Safety 5 Appliance description, cleaning, care & maintenance 7 Appliance

More information

Multi-Elec COMPACTE BOILER

Multi-Elec COMPACTE BOILER Multi-Elec COMPACTE BOILER TECHNICAL MANUAL 03/2013 CODE: 560956 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) FOR TECHNICAL HELP/ADVICE Call 0161 621 5960 or email info@atlanticboilers.com

More information

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. Service instructions. MatriX radiant burner. for contractors Service instructions for contractors VIESMANN MatriX radiant burner Type VMIII Pressure-jet gas burner for the Vitocrossal 300, type CT3B Rated heating output 187 to 314 kw For applicability, see the last

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass HM model. With a suitable

More information

H o t Wa te r Syste m s. Senator Electric Flow Boilers. Making Life Simpler

H o t Wa te r Syste m s. Senator Electric Flow Boilers. Making Life Simpler H o t Wa te r Syste m s Senator Electric Flow Boilers Making Life Simpler Electric Wet Central Heating The Range Senator electric flow boiler is designed to heat re-circulated water used in wet central

More information

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until)

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until) Data sheet LA 16MS Air-to-water heat pump with deflector hoods Max. flow temperature: 58 C Casing colour: White aluminium (similar to RAL 9006) Air-to-water heat pump for outdoor installation with external

More information

Installation instructions. For the heating engineer. Installation instructions. geotherm. Heat pump

Installation instructions. For the heating engineer. Installation instructions. geotherm. Heat pump Installation instructions For the heating engineer Installation instructions geotherm Heat pump GB Contents Contents 1 otes on the documentation...4 1.1 Observing other applicable documents...4 1.2 Document

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service.

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service. Strategy module FM458/CMC 930 For contractors Read carefully prior to commissioning or service. 6 720 803 196 (2011/06) GB / IE / AU Service instructions 2 1 Safety........................................

More information

WIRING GUIDE. Form rev.1. Certified to CSA C22-2 No.24 Conforms to UL Standard 873

WIRING GUIDE. Form rev.1. Certified to CSA C22-2 No.24 Conforms to UL Standard 873 WIRIG GUIDE The ZSR101 is a versatile single relay control with two outputs for operating a 120 VAC with boiler enable, or two 120 VAC devices without boiler enable. Features include rear knock outs for

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features Comfort Module Range for Monobloc Heat Pumps Quality Management Systems Comfort module with two-zone kit Single-zone comfort module 8HMA Nominal heating capacity 4- kw Nominal cooling capacity 4- kw The

More information

GHP AWO 38 Technical overview

GHP AWO 38 Technical overview Gas absorption heat pump 9 Technical overview single unit G&' &(')*ption heat pump components. 1 7 2 8 9 3 4 10 8 5 6 1 +),-.&/012 &0* ')-*34 5&1 2 G414*&/)* 3 G&' (-*ner 4 6)1,41'4* 5 6)7(-'/0)1 38&7(4*

More information

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17 VIESMANN VITOCELL 300-V Vertical DHW cylinder 130to500litrecapacity Datasheet Part numbers and prices: see pricelist File in: Vitotec folder, register 17 VITOCELL 300-V Type EVA and EVI Vertical DHW cylinder

More information

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler. VIESMANN VITOROND 100 Cast iron low temperature oil and gas fired boiler 40 to 100 kw Datasheet Part numbers and prices: see pricelist File in: Vitotec folder, register 1 VITOROND 100 Type VR2B Cast iron

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery Datasheet For part no. and prices: see pricelist VITOVENT 300-F Mechanical ventilation system with heat recovery for demanddependent

More information

NIBE SPLIT ACVM 270 Air/water heat pump

NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 system with complete indoor module NIBE SPLIT ACVM 270 is a complete modern heat pump system that offers effective technical energy saving and

More information

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B Operating instructions for the system user VIESMANN Digital time switch for the Vitodens 100-W, type WB1B DIGITAL TIME SWITCH 5/2008 Please keep safe. Safety instructions For your safety Please follow

More information

VITOSOL r DHW SOLAR PACK

VITOSOL r DHW SOLAR PACK Installation Instructions for use by contractors Vitosol 200-F, SVK Flat-plate collector for sloping roofs; above roof installation Vitocell 100-W, CVBA Dual coils DHW tank with Solar-Divicon Vitocell

More information

Installation Instructions VITOTRONIC 200

Installation Instructions VITOTRONIC 200 Installation Instructions Please file in Service Binder Vitotronic 200 Model KW2 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits VITOTRONIC

More information

MULTI ELEC. Electric Boilers TECHNICAL MANUAL

MULTI ELEC. Electric Boilers TECHNICAL MANUAL MULTI ELEC Electric Boilers TECHNICAL MANUAL PO Box 11 Ashton Under Lyne OL6 7TR +44. (0) 161 621 5960 Fax +44. (0) 161 621 5966 info@atlantic2000.co.uk www.atlanticboilers.com 2 CONTENTS DESCRIPTION....

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

Service Instructions for use by heating contractor

Service Instructions for use by heating contractor Service Instructions for use by heating contracr Please file in Service Binder Vitronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating

More information

Installation and operating instructions

Installation and operating instructions Installation and operating instructions Cascade module KM Wolf GmbH Postfach 1380 84048 Mainburg Tel. 08751/74-0 Fax 08751/741600 Internet: www.wolf-heiztechnik.de Part no. 30 62 449 Subject to modifications

More information

Operating instructions

Operating instructions Operating instructions Solar thermal controller 7747006071-00.1 SD Solar thermal system with Logamatic SC40 For the Owner Please read carefully before operation. 7 747 017 474 GB (2007/08) OSW Contents

More information