VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors

Size: px
Start display at page:

Download "VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors"

Transcription

1 Installation and service instructions for contracrs VIESMANN Vitronic 00 Type GWB Vitronic 300 Type GWB Weather-compensated, digital boiler control units For applicability, see the last page VITOTRONIC 00 VITOTRONIC 300 8/0 Please keep safe.

2 Safety instructions Safety instructions Please follow these safety instructions closely prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. Work on gas equipment must only be carried out by a qualified gas fitter. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Observe the following when working on this system all legal instructions regarding the prevention of accidents, all legal instructions regarding environmental protection, the Code of Practice of relevant trade associations, all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards, Gas Safety (Installation & Use) Regulations the appropriate Building Regulation either the Building regulations, the Building Regulation (Scotland), Building Regulations (Northern Ireland), the Water Fittings Regulation or Water Bylaws in Scotland, the current I.E.E. Wiring Regulations. If you smell gas Danger Escaping gas can lead explosions which may result in serious injury. Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appliances ON or OFF. Close the gas shut-off valve. Open windows and doors. Remove all people from the danger zone. Notify your gas or electricity supplier from outside the building. Shut off the electricity supply the building from a safe place (outside the building).

3 Safety instructions Safety instructions (cont.) If you smell flue gas Danger Flue gas can lead life-threatening poisoning. Shut down the heating system. Ventilate the boiler room. Close all doors leading the living space. Working on the system When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening. Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolar. Safeguard the system against unauthorised reconnection. Ancillary components, spare and wearing parts Please note! Spare and wearing parts which have not been tested gether with the heating system can compromise its function. Installing non-authorised components and non-approved modifications/conversion can compromise safety and may invalidate our warranty. For replacements, use only original spare parts from Viessmann or those which are approved by Viessmann.! Please note Electronic modules can be damaged by electro-static discharges. Touch earthed objects, such as heating or water pipes, discharge static loads. Repair work! Please note Repairing components which fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. 3

4 Index Installation instructions Preparing for installation Designations in the system examples... 7 System example, ID: System example, ID: System example 3, ID: System example 4, ID: System extension Installation sequence Overview of electrical connections Inserting cables and applying strain relief Inserting the boiler coding card Changing the high limit safety cut-out setting (if required) Adjusting the temperature controller (if required) Connecting sensors Connecting pumps Connecting servomors Connecting the central fault message facility... 5 External demand via switching contact... 5 External demand via 0 0 V input... 5 External blocking via switching contact External "Mixer close"/"mixer open" External changeover of multi stage/modulating burners External heating program changeover Connecting the external safety equipment Provisional burner operation Connecting an AC burner Connecting a three-phase burner Power supply Power supply in conjunction with Vicrossal, type CT Fitting the front part of the control unit Opening the control unit Service instructions Commissioning Changing the language... 7 Setting the date and time... 7 Testing the high limit safety cut-out... 7 Matching coding addresses the system version... 7 Checking actuars and sensors Adjusting heating curves Index

5 Index Index Connecting the control unit the LON Service scans Calling up the service menu... 8 Exit service menu... 8 Scanning operating data... 8 Brief scan... 8 Scanning and resetting the "Service" display Troubleshooting Fault display Function description Boiler water temperature control Heating circuit control Cylinder temperature control... 3 Code Calling up coding level... 8 "General" group... 9 "Boiler" group... "DHW" group... 3 "Solar" group... 3 "Heating circuit ", "Heating circuit ", "Heating circuit 3" group... 5 Code Calling up coding level "General" group "Boiler" group... 4 "DHW" group "Solar" group "Heating circuit ", "Heating circuit ", "Heating circuit 3" group Designs Connection and wiring diagram, type GWB Connection and wiring diagram, type GWB Components Boiler coding card Sensors Plug-in adapr for ext. safety equipment, part no Radio clock receiver, part no Extension kit, mixer, part no

6 Index Index (cont.) Mixer mor, part no Mixer mor, part no. Z Temperature limiter for limiting the maximum temperature Extension EA, part no Secondary air device Viair, part no , Parts lists Parts list, type GWB... 9 Parts list, type GWB Specification Keyword index

7 Preparing for installation Designations in the system examples qe / /5M ee M /5M rr M qe / M /8 qw / M, M Installation qq /5 qr /5Sol 6/S /5 qq X M 5M 5M M,4 5 M M (5Sol) (6) In the following system examples, the Vitronic 300, type GWB, is used as the control unit. The heating circuits in Vitronic 00, type GWB, must be controlled by a heating circuit control unit Vitronic 00- H. 7

8 Preparing for installation System example, ID: Single boiler system: Boiler with Therm-Control Hydraulic installation scheme /M /M3-- --/0M-- --/0M /5M-- --/5M WW 8 --/ / /5A /-- --/3/ /7A-- KW 6 --M3-- --M-- --5A V M-- --0M-- --5M M3-- --KM-BUS-- --7A-- --3/-- Note: This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for professional planning on site. 8

9 Preparing for installation System example, ID: (cont.) Equipment required Pos. Designation Boiler Vitronic 3 Outside temperature sensor ATS 4 Boiler water temperature sensor KTS 5 Therm-Control temperature sensor rr ON/OFF switch (on site) 6 DHW cylinder 7 Cylinder temperature sensor STS 8 Circulation pump for cylinder heating UPSB 9 DHW circulation pump ZP qp Heating circuit (only for Vitronic 300, type GWB) qw Heating circuit pump M Mixer extension kit: qq Flow temperature sensor M as contact temperature sensor and qe Mixer mor M or Flow temperature sensor M as qq Contact temperature sensor or Immersion temperature sensor and qe Mixer mor for flanged mixer M qr Heating circuit 3 (only for Vitronic 300, type GWB) qz Heating circuit pump M3 Mixer extension kit: qt Flow temperature sensor M3 as contact temperature sensor and qu Mixer mor M3 or Flow temperature sensor M3 as qt Contact temperature sensor or Immersion temperature sensor and qu Mixer mor for flanged mixer M3 Installation 9

10 Preparing for installation System example, ID: (cont.) Pos. Designation Accessories qi Plug-in adapr for external safety equipment qo Minimum pressure switch or limiter SDB wp Maximum pressure limiter SDB wq Water level limiter (low water indicar) WB ww Central fault message system S we Flue gas temperature sensor AGS wr Vitrol 00A or Vitrol 300A wt Radio clock receiver wz Contacr relay wu Downstream heating circuit controller, switching contact closed: Signal for mixer "Close" ep Extension EA eq analogue input (0 0 V) Specification of the set boiler water temperature ew 3 digital inputs External heating program changeover, separately adjustable for heating circuits 3 External demand External blocking with fault message input Fault message input Short term operation of DHW circulation pump ee switching output (floating changeover contact) Switching a feed pump a substation Signalling reduced mode for a heating circuit External hook-ups er External demand et External changeover of stepped/modulating burners ez External blocking/mixer closed eu External changeover of heating program/external mixer open eo Vicom 00 rp KM BUS distribur, for several KM BUS subscribers rq LON communication module for communication with the following components: Vitronic 00-H Vicom 00 and 300 Vigate 00, type EIB 0

11 Preparing for installation System example, ID: (cont.) Electrical installation scheme Main PCB 30 V 30 V / 50 Hz Main PCB N L N L L N N L N L PCB ME P P SDB 9 SDB 0 WB 30 V/ 50 Hz S Installation 0 A N L N 5 A N L M ~ UPSB 8 8 N L M ~ ZP 9

12 Preparing for installation System example, ID: (cont.) Main PCB LV connections Main PCB AGS 3 Low voltage 7B 7A 5B 5A T 5 STS 7 3/ KTS KM BUS distribur ATS KM BUS 4 LON KM BUS N L 30 EA 40 N 40A L 57 P Ö S V 3 3 DE3 DE DE

13 Preparing for installation System example, ID: (cont.) Mixer extension PCB PCB ME Low voltage M VTS M M3 VTS M3 5 0 M N L M ~ HKP M 30 V / 50 Hz 0 M3 5 M 5 M3 N L N N M ~ M ~ M ~ HKP M3 6 M 3 M3 7 Installation 40 L N 56 Main PCB Wiring diagram Closing mixers installed downstream via temperature sensor T in heating systems with heating circuit control units that are not connected the boiler control unit via LON. N 0 L 0 A wz K cl. cl. cl. wu n 3

14 Preparing for installation System example, ID: (cont.) Required code 4C: "General" group Use of plug sö A close the downstream mixers. 0d: "Boiler" group Temperature sensor Therm-Control affects the mixers of downstream heating circuits (delivered condition). 4

15 Preparing for installation System example, ID: Single boiler system: Boiler with shunt pump for return temperature raising Hydraulic installation scheme /M /M /0M /0M /5M /5M3-- 9 Installation 0 --3/-- WW 6 --3/7B-- --3/ / /3/-- --3/7A /5A-- --3/-- KW V M-- --0M-- --5M M M3-- --M-- --5A KM-BUS-- --7A-- --3/-- --7B-- Note: This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for professional planning on site. 5

16 Preparing for installation System example, ID: (cont.) Equipment required Pos. Designation Boiler Boiler water temperature sensor KTS 3 Vitronic 4 Outside temperature sensor ATS 5 Shunt pump BP 6 Temperature sensor T Contact temperature sensor or Immersion temperature sensor 7 Temperature sensor T Contact temperature sensor or Immersion temperature sensor rr ON/OFF switch (on site) 8 DHW cylinder 9 Cylinder temperature sensor STS qp Circulation pump for cylinder heating UPSB qq DHW circulation pump ZP qw Heating circuit (only for Vitronic 300, type GWB) qr Heating circuit pump M Mixer extension kit: qe Flow temperature sensor M as contact temperature sensor and qt Mixer mor M or Flow temperature sensor M as qe Contact temperature sensor or Immersion temperature sensor and qt Mixer mor for flanged mixer M qz Heating circuit 3 (only for Vitronic 300, type GWB) qi Heating circuit pump M3 Mixer extension kit: qu Flow temperature sensor M3 as contact temperature sensor and qo Mixer mor M3 or Flow temperature sensor M3 as 6

17 Preparing for installation System example, ID: (cont.) Pos. Designation qu Contact temperature sensor or Immersion temperature sensor and qo Mixer mor for flanged mixer M3 Accessories wp Plug-in adapr for external safety equipment wq Minimum pressure switch or limiter SDB ww Maximum pressure limiter SDB we Water level limiter (low water indicar) WB wr Central fault message system S wt Flue gas temperature sensor AGS wz Vitrol 00A or Vitrol 300A wu Radio clock receiver wi Contacr relay wo Downstream heating circuit controller, switching contact closed: Signal for mixer "Close" ep Extension EA eq analogue input (0 0 V) Specification of the set boiler water temperature ew 3 digital inputs External heating program changeover, separately adjustable for heating circuits 3 External demand External blocking with fault message input Fault message input Short term operation of DHW circulation pump ee switching output (floating changeover contact) Switching a feed pump a substation Signalling reduced mode for a heating circuit External hook-ups er External demand et External changeover of stepped/modulating burners ez External blocking/mixer closed eu External changeover of heating program/external mixer open eo Vicom 00 Installation 7

18 Preparing for installation System example, ID: (cont.) Pos. rp rq Designation KM BUS distribur, for several KM BUS subscribers LON communication module for communication with the following components: Vitronic 00-H Vicom 00 and 300 Vigate 00, type EIB Temperature sensor T 7 For the Viplex (not type SX from 535 kw) and the Virond 00 (5 70 kw), the immersion temperature sensor supplied as standard can be used. Remove the sensor well from the boiler. Seal the port with a plug. 8

19 Preparing for installation System example, ID: (cont.) Electrical installation scheme Main PCB 30 V 3 30 V / 50 Hz Main PCB N L N L L N N L N L PCB ME P P M ~ SDB SDB WB 3 30 V/ 50 Hz S 4 BP 5 Installation 0 A N L N 5 A N L M ~ UPSB 0 8 N L M ~ ZP 9

20 Preparing for installation System example, ID: (cont.) Main PCB LV connections 3 Main PCB AGS 5 Low voltage 7B 7A 5B 5A T 6 T 7 STS 9 3/ KTS 3 40 KM BUS distribur ATS KM BUS 6 LON KM BUS N L 30 EA 40 N 40A L 57 P Ö S V 3 3 DE3 DE DE

21 Preparing for installation System example, ID: (cont.) Mixer extension PCB 3 PCB ME Low voltage M VTS M 3 M3 VTS M3 7 0 M N L M ~ HKP M 4 30 V / 50 Hz 0 M3 5 M 5 M3 N L N N M ~ M ~ M ~ HKP M3 8 M 5 M3 9 Installation 40 L N 3 56 Main PCB Wiring diagram Closing mixers installed downstream via temperature sensor T in heating systems with heating circuit control units that are not connected the boiler control unit via LON. söa L N 0 K wo wi cl. cl. cl.... n Required code 4C: "General" group Use of plug sö A close the downstream mixers. 0d: "Boiler" group Temperature sensor T/Therm-Control affects the mixers of downstream heating circuits (delivered condition).

22 Preparing for installation System example 3, ID: Single boiler system: Boiler with shunt pump and 3-way mixing valve for return temperature control Hydraulic installation scheme /M /M /0M /0M /5M-- --3/5M WW --3/ /5A /7B-- --3/ / /3/-- --3/7A /5A-- --4/-- KW V M-- --0M-- --5M M M3-- --M-- --5A KM-BUS-- --7A-- --3/-- --7B-- --5A Note: This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for professional planning on site.

23 Preparing for installation System example 3, ID: (cont.) Equipment required Pos. Designation Boiler Boiler water temperature sensor KTS 3 Vitronic 4 Outside temperature sensor ATS 5 Shunt pump BP 6 3-way mixing valve 7 Temperature sensor T Contact temperature sensor or Immersion temperature sensor 8 Temperature sensor T Contact temperature sensor or Immersion temperature sensor rr ON/OFF switch (on site) 9 DHW cylinder qp Cylinder temperature sensor STS qq Circulation pump for cylinder heating UPSB qw DHW circulation pump ZP qe Heating circuit (only for Vitronic 300, type GWB) qt Heating circuit pump M Mixer extension kit: qr Flow temperature sensor M as contact temperature sensor and qz Mixer mor M or Flow temperature sensor M as qr Contact temperature sensor or Immersion temperature sensor and qz Mixer mor for flanged mixer M qu Heating circuit 3 (only for Vitronic 300, type GWB) qo Heating circuit pump M3 Mixer extension kit: qi Flow temperature sensor M3 as contact temperature sensor and wp Mixer mor M3 or Installation 3

24 Preparing for installation System example 3, ID: (cont.) Pos. Designation Flow temperature sensor M3 as qi Contact temperature sensor or Immersion temperature sensor and wp Mixer mor for flanged mixer M3 Accessories wq Plug-in adapr for external safety equipment ww Minimum pressure switch or limiter SDB we Maximum pressure limiter SDB wr Water level limiter (low water indicar) WB wt Central fault message system S wz Flue gas temperature sensor AGS wu Vitrol 00A or Vitrol 300A wi Radio clock receiver ep Extension EA eq analogue input (0 0 V) Specification of the set boiler water temperature ew 3 digital inputs External heating program changeover, separately adjustable for heating circuits 3 External demand External blocking with fault message input Fault message input Short term operation of DHW circulation pump ee switching output (floating changeover contact) Switching a feed pump a substation Signalling reduced mode for a heating circuit External hook-ups er External demand et External changeover of stepped/modulating burners ez External blocking/mixer closed eu External changeover of heating program/external mixer open eo Vicom 00 rp KM BUS distribur, for several KM BUS subscribers rq LON communication module for communication with the following components: Vitronic 00-H Vicom 00 and 300 Vigate 00, type EIB 4

25 Preparing for installation System example 3, ID: (cont.) Temperature sensor T 7 For the Viplex (not type SX from 535 kw) and the Virond 00 (5 70 kw), the immersion temperature sensor supplied as standard can be used. Remove the sensor well from the boiler. Seal the port with a plug. Electrical installation scheme Main PCB 30 V 3 Main PCB N L N L PCB ME P P SDB SDB WB 3 4 Installation 30 V / 50 Hz L N N L N L M ~ 30 V/ 50 Hz S 5 BP 5 0 A N L 5 A N M ~ A 6 N L M ~ UPSB 8 N L M ~ ZP 5

26 Preparing for installation System example 3, ID: (cont.) Main PCB LV connections 3 Main PCB AGS 6 Low voltage 7B 7A 5B 5A T 7 T 8 STS 0 3/ KTS 3 40 KM BUS distribur ATS KM BUS 7 LON KM BUS N L 30 EA 40 N 40A L 57 P Ö S V 3 3 DE3 DE DE

27 Preparing for installation System example 3, ID: (cont.) Mixer extension PCB 3 PCB ME Low voltage M VTS M 4 M3 VTS M3 8 0 M N L M ~ HKP M 5 30 V / 50 Hz 0 M3 5 M 5 M3 N L N N M ~ M ~ M ~ HKP M3 9 M 6 M3 0 Installation 40 L N 3 56 Main PCB Required code 0C: "Boiler" group Constant return temperature control. 4E: "General" group Connection plug gs A mor for 3-way mixing valve for return temperature control. 7

28 Preparing for installation System example 4, ID: Single boiler system with Vicrossal Hydraulic installation scheme /M /M3-- --/0M-- --/0M /5M-- --/5M WW 8 --/ / /3/ /5A-- --/-- KW M3-- --M-- --5A V M-- --0M-- --5M M KM-BUS-- --3/-- Note: This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for professional planning on site. 8

29 Preparing for installation System example 4, ID: (cont.) Equipment required Pos. Designation Boiler Vitronic 3 Outside temperature sensor ATS 4 Boiler water temperature sensor KTS 5 Neutralising system rr ON/OFF switch (on site) 6 DHW cylinder 7 Cylinder temperature sensor STS 8 Circulation pump for cylinder heating UPSB 9 DHW circulation pump ZP qp Heating circuit (only for Vitronic 300, type GWB) qw Heating circuit pump M Mixer extension kit: qq Flow temperature sensor M as contact temperature sensor and qe Mixer mor M or Flow temperature sensor M as qq Contact temperature sensor or Immersion temperature sensor and qe Mixer mor for flanged mixer M qr Heating circuit 3 (only for Vitronic 300, type GWB) qz Heating circuit pump M3 Mixer extension kit: qt Flow temperature sensor M3 as contact temperature sensor and qu Mixer mor M3 or Flow temperature sensor M3 as qt Contact temperature sensor or Immersion temperature sensor and qu Mixer mor for flanged mixer M3 Installation 9

30 Preparing for installation System example 4, ID: (cont.) Pos. Designation Accessories qi Plug-in adapr for external safety equipment qo Minimum pressure switch or limiter SDB wp Maximum pressure limiter SDB wq Water level limiter (low water indicar) WB ww Central fault message system S we Flue gas temperature sensor AGS wr Vitrol 00A or Vitrol 300A wt Radio clock receiver ep Extension EA eq analogue input (0 0 V) Specification of the set boiler water temperature ew 3 digital inputs External heating program changeover, separately adjustable for heating circuits 3 External demand External blocking with fault message input Fault message input Short term operation of DHW circulation pump ee switching output (floating changeover contact) Switching a feed pump a substation Signalling reduced mode for a heating circuit External hook-ups er External demand ez External blocking/mixer closed eu External changeover of heating program/external mixer open eo Vicom 00 rp KM BUS distribur, for several KM BUS subscribers rq LON communication module for communication with the following components: Vitronic 00-H Vicom 00 and 300 Vigate 00, type EIB 30

31 Preparing for installation System example 4, ID: (cont.) Electrical installation scheme Main PCB 30 V 30 V / 50 Hz Main PCB N L N L L N N L N L PCB ME P P SDB 9 SDB 0 WB 30 V/ 50 Hz S Installation 0 A N L N 5 A N L M ~ UPSB 8 8 N L M ~ ZP 9 3

32 Preparing for installation System example 4, ID: (cont.) Main PCB LV connections Main PCB AGS 3 Low voltage 7B 7A 5B 5A STS 7 3/ KTS KM BUS distribur ATS KM BUS 4 LON KM BUS N L 30 EA 40 N 40A L 57 P Ö S V 3 3 DE3 DE DE

33 Preparing for installation System example 4, ID: (cont.) Mixer extension PCB PCB ME Low voltage M VTS M M3 VTS M3 5 0 M N L M ~ HKP M 30 V / 50 Hz 0 M3 5 M 5 M3 N L N N M ~ M ~ M ~ HKP M3 6 M 3 M3 7 Installation 40 L N 56 Main PCB Required code 0d:0 "Boiler" group Without Therm-Control temperature sensor. System extension DHW heating with primary sre system; ID: In systems with temporarily high DHW demand and large cylinder capacity with offset draw-off times. 33

34 Preparing for installation System extension (cont.) Hydraulic installation scheme WW --/8-- --/5A /5B-- 6 -/- -/5A /7B KW V A-- --0A-- --7B-- --5A-- --5B-- --/0A-- Equipment required Pos. Designation Boiler Vitronic 3 Vitrans (heat exchanger set) 4 3-way mixing valve (standard delivery of mixer assembly, accessory for Vitrans ) 5 Primary pump in the primary sre system 6 Secondary pump in the primary sre system UPSB 7 Temperature sensor (standard delivery of mixer assembly, accessory for Vitrans ) 8 DHW cylinder 9 Cylinder temperature sensor STS, botm (standard delivery of mixer assembly, accessory for Vitrans ) qp Cylinder temperature sensor STS, p (standard delivery of control unit) qq DHW circulation pump ZP 34

35 Preparing for installation System extension (cont.) Electrical installation scheme Standard LP L 40 N N 50 L 30 V/ 50 Hz 30 V/ 50 Hz 9 0 A N L N L M ~ 5 5 A N N L M ~ M ~ 4 UPSB 6 Installation 8 N L M ~ ZP Low voltage 7B 7A 5B 5A STS 9 STS 0 3/

36 Preparing for installation System extension (cont.) Required code 4C: "General" group Primary pump connection at plug sö A. 4E: "General" group Mor connection for 3-way mixing valve at plug gs A. 55:3 "DHW" group Cylinder temperature controller, primary sre system. Servomor runtime, heat exchanger set mixing valve: 6A:75 "DHW" group Vitrans, 80 and 0 kw 6A:3 "DHW" group Vitrans, 40 kw In conjunction with shunt pump for raising the return temperature (system example ) L 9 N 9 M ~ Sensor input ajb is used control the Vitrans. Therefore, the shunt pump must be switched by a separate temperature controller. Required code: "4d:" in the "General" group. E Junction box (on site) F Shunt pump G Control thermostat, Part no. Z In conjunction with constant return temperature control (system example 3) A separate Vitronic 00-H must be used for regulating the Vitrans. The boiler control unit affects the constant return temperature control. 36

37 Preparing for installation System extension (cont.) System with flue gas/water heat exchanger, ID: Hydraulic installation scheme 4 3 Note: This scheme is a basic example without shut-off devices or safety equipment. This does not replace the need for professional planning on site. Equipment required Pos. Designation Boiler Shunt pump BP 3 Vitrans Circulation pump 5 Contacr relay Installation 37

38 Preparing for installation System extension (cont.) Wiring diagram Connection of circulation pump for the flue gas/water heat exchanger If the circulation pump power consumption is above A, use a contacr relay. The circulation pump is started in parallel with the burner. 0 0 A N L N L K6 M ~ Required code Group Function 4C:3 "General" Flue gas/water heat exchanger circulation pump connection at plug söa. System versions where output sö A must be used as a switching contact or heating circuit pump connection Use extension AM A (accessory). A [] A [] A f-]a sösask sösask L?N L?N L?N fö N? L M ~ 4 Rated current 4() A~ Recommended connecting cable H05VV-F3G 0.75 mm or H05RN-F3G 0.75 mm If the circulation pump power consumption is above A, use a contacr relay. 38

39 Preparing for installation System extension (cont.) Required code Group Function 33:3 "General" Function output A at extension AM: Circulation pump flue gas/water heat exchanger. Installation 39

40 Installation sequence Overview of electrical connections Note When connecting plugs avd, avh, sa, sk,? M/M3 and sö M/M3, bundle the individual wires of the cables close the terminals. This ensures that, should there be a fault, for example when detaching a wire, the wires cannot drift in the adjacent voltage area. Type GWB / 5 A 5 B 7 A 7 B A 0 A

41 Installation sequence Overview of electrical connections (cont.) Type GWB 5 M3 5 M 0 M3 0 M M3 M / 5 A 5 B 7 A 7 B A 0 A Installation Extension for heating circuits and 3 with mixer (only with type GWB)?M/M3 Flow temperature sensor söm/m3 Heating circuit pump gsm/m3 Mixer mor Main PCB, LV! Outside temperature sensor /? Boiler temperature sensor %A Cylinder temperature sensor %B Cylinder temperature sensor for primary sre system (accessory) ) Flow temperature sensor, low loss header (accessory) ag Flue gas temperature sensor (accessory) aja Therm-Control temperature sensor or Return temperature sensor T (accessory) 4

42 Installation sequence Overview of electrical connections (cont.) ajb avd avg avh Return temperature sensor T (accessory) or Temperature sensor, primary sre system (accessory) External hook-up KM BUS subscriber (accessory) External hook-up When connecting external switching contacts or components the low voltage circuit of the control unit, please observe the safety requirements of protection class II, i.e. 8.0 mm air and creep path or.0 mm insulation thickness wards 'live' components. For all on-site components (incl. PC/ lapps), ensure safe electrical separation EN or IEC 65. sk DHW circulation pump (on site) sl Shunt pump or boiler circuit pump (on site) fö Power supply fa Burner stage gö Central fault message gsa Mor for 3-way mixing valve, return temperature control or Mor for 3-way mixing valve, primary sre system lö Burner stage /mod. abö External connections, e.g. supplementary safety equipment aba Safety chain, potential-free abh Power supply for accessories Main PCB 30 V~ söa Heating circuit pump or Primary pump, primary sre system or Circulation pump, flue gas/water heat exchanger or Switching output sa Circulation pump for cylinder heating (accessory) 4

43 Installation sequence Inserting cables and applying strain relief Control unit fitted the boiler: Route cables from below through the front panel of the boiler in the wiring chamber of the control unit. Control unit fitted the side of the boiler: Route cables from below out of the cable trunking in the control unit. A D Installation C D B A Cables with moulded strain relief B On-site cables; strip up 00 mm insulation. C Plug connection diagram D Cover for plug connection diagram 43

44 Installation sequence Inserting the boiler coding card Only use the boiler coding card supplied with the boiler (see table in chapter "Components"). Insert the boiler coding card through the recess in the cover in slot "X7". Changing the high limit safety cut-out setting (if required) The high limit safety cut-out is supplied with a facry setting of 0 C. 44

45 Changing the high limit safety cut-out setting (cont.) Installation sequence Adjustment 00 C Installation C Adjusting the temperature controller (if required) The temperature controller is supplied with a facry setting of 95 C. 45

46 Installation sequence Adjusting the temperature controller (if (cont.) Adjustment 00 C! Please note Excessive DHW temperatures can damage the DHW cylinder. If the system is operated in conjunction with a DHW cylinder, ensure that the maximum permissible water temperature is not exceeded. If necessary, install suitable safety equipment for this purpose. A.. 3. A C. Remove rotary selecr "R".. Using a pair of pointed pliers, break the cam A identified in the illustration out of the sp dial. 3. Fit rotary selecr "R" so that the marking lies at the centre of the selected range. Turn rotary selecr "R" fully clockwise. 46

47 Installation sequence Connecting sensors / 5A 5B 7A 7B 5 9! Outside temperature sensor /? Boiler temperature sensor %A Cylinder temperature sensor %B Cylinder temperature sensor for primary sre system (accessory) aja Therm-Control temperature sensor or Return temperature sensor T (accessories) Installation point for outside temperature sensor North or north-western wall,.5 m above ground level; in multisrey buildings, in the upper half of the second floor Not above windows, doors or ventilation outlets ajb ag Return temperature sensor T or Temperature sensor, primary sre system (accessory) Flue gas temperature sensor (accessory) ) Flow temperature sensor, low loss header (accessory) Not immediately below balconies or gutters Never render over Outside temperature sensor connection -core lead, up 35 m long with a crosssection of.5 mm Installation 47

48 Installation sequence Connecting pumps Available pump connections sö A Heating circuit pump or Primary pump, primary sre system or Circulation pump, flue gas/water heat exchanger sa Circulation pump for cylinder heating Pumps 30 V~ sk sl DHW circulation pump Shunt pump or boiler circuit pump M ~ A Rated current 4() A~ Recommended connecting cable H05VV-F3G 0.75 mm or H05RN-F3G 0.75 mm B A Pump B To the control unit 48

49 Installation sequence Connecting pumps (cont.) Pumps with power consumption greater than A N L L D N L N C B External ON/OFF L N PE A Installation A Pump B To the control unit C Contacr D Separate power connection (observe manufacturer's details) Pumps 400 V~ N C L L L L3 N PE For switching the contacr Rated current 4() A~ Recommended connecting cable H05VV-F3G 0.75 mm or H05RN-F3G 0.75 mm B A 3~ M A Pump B To the control unit C Contacr 49

50 Installation sequence Connecting pumps (cont.) Pumps in the underfloor heating circuit N L 0 sö B Temperature limiter C Secondary pump (downstream of the system separation) The tal power consumption of both pumps must not exceed A. M ~ M ~ A B C sö Control unit A Primary pump Connecting servomors Available connections gsa Mor for 3-way mixing valve for return temperature control or Mor for 3-way mixing valve, primary sre system 50

51 Installation sequence Connecting servomors (cont.) M ~ Open Close 5 Rated voltage 30 V~ Rated current max. 0. (0.) A~ Recommended Connecting cable H05VV-F4G 0.75 mm or H05RN-F4G 0.75 mm Runtime 5 99 s, adjustable via coding address "40" Installation Connecting the central fault message facility L 50 N Rated voltage 30 V~ Rated current max. 4 () A~ Recommended connecting cable H05VV-F3G 0.75 mm or H05RN-F3G 0.75 mm External demand via switching contact Optional connections: Plug avh Extension EA (accessory, see page 87) 5

52 Installation sequence External demand via switching contact (cont.) Connection! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. Plug avh Extension EA A [{A DE [{S DE B [{D DE 3 46 B A A Floating contact B Plug avh of the control unit A Floating contact B Extension EA When the contact is closed, the burner is operated subject load. The boiler water is heated the value set in the coding address "9b" in the "General" group. The boiler water temperature is limited by this set value and the electronic maximum limit (coding address "06" in the "Boiler" group). Codes Plug avh Extension EA No code required. Set "5d", "5E" or "5F" in the "General" group. External demand via 0 0 V input Connection input 0 0 V at extension EA (see page 87). Ensure DC separation between the negative pole and the earth conducr of the on-site voltage source. 5

53 Installation sequence External demand via 0 0 V input (cont.) [{{] abj 0-0V f-]a SÖ P L?N fö N? L 0 - V No default set boiler water temperature V set value 0 C 0 V set value 00 C Observe coding address "E" in the "General" group. = 0-0 V + 30 V~ Installation External blocking via switching contact Optional connections: Plug abö Plug avd Extension EA (accessory, see page 87) Connection! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. 53

54 Installation sequence External blocking via switching contact (cont.) Plug abö Plug avd Extension EA A A [{A DE [{S DE B [{D DE 3 43 STB EIN EIN N STB TR TR B A Floating contact B Plug avd of the control unit A A Floating contact B Extension EA B A Floating contact B Remove jumper "TR" "ON/TR" Opening this contact leads a controlled burner shutdown. Any connected shunt or boiler circuit pump is spped. Note Connect only safety shutdown equipment, e.g. temperature limiter, these terminals. Closing this contact leads a controlled burner shutdown. Any connected shunt or boiler circuit pump is spped.! Please note The heating system has no frost protection during blocking. The boiler is not held at the lower boiler water temperature. 54

55 Installation sequence External blocking via switching contact (cont.) Codes Plug avd Set coding address "99" in the "General" group. Extension EA Set "5d", "5E" or "5F" in the "General" group 3 or 4. External "Mixer close"/"mixer open" Only for type GWB. Connection at plug avd A! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. Installation B 3 43 A External "Mixer open" (floating contact) B External "Mixer closed" (floating contact) Codes External "Mixer open" This function is assigned the heating circuits via coding address "9A" in the "General" group. External "Mixer closed" This function is assigned the heating circuits via coding address "99" in the "General" group. 55

56 Installation sequence External changeover of multi stage/modulating burners Connection via plug avh A 3 46 Contact open: modulating mode Contact closed: two stage mode Note When scanning the burner version, the address for modulation appears even after an external changeover (no rewriting). A External changeover (floating contact) Please note! 'Live' contacts lead short circuits or phase failure. The external connection must be floating. Code Set code "0:" in the "Boiler" group. External heating program changeover Optional connections: Plug avd Extension EA (accessory, see chapter "Components") Connection! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. 56

57 Installation sequence External heating program changeover (cont.) Plug avd A Extension EA The changeover can be achieved separately for heating circuits 3. DE DE DE3 B 3 43 B A Floating contact B Plug avd of the control unit A A A A Floating contact B Extension EA Installation Preselected heating program (Contact open) Central heating OFF/ DHW OFF or or Central heating OFF/ DHW heating ON Central heating ON/ DHW heating ON Code "d5:0" in the "Heating circuit..."grou p (Delivered condition) "d5:" in the "Heating circuit..."grou p Changed heating program (Contact closed) Constant operation with reduced room temperature/dhw heating OFF Constant operation with standard room temperature, DHW heating in accordance with coding address "64" in the "DHW" group 57

58 Installation sequence External heating program changeover (cont.) Codes Plug avd Via coding address "9" in the "General" group, the function can be assigned the heating circuits. Extension EA Set "5d", "5E" or "5F" in the "General" group. Via coding address "d8" in the "Heating circuit..." group, the function can be assigned the heating circuits. Connecting the external safety equipment Connection via plug abö. The plug-in adapr for external safety equipment (accessory, see chapter "Components") can be used for connecting several pieces of safety equipment.! Please note 'Live' contacts lead short circuits or phase failure. The external connections must be potential-free. Note Plug abö must remain plugged in, even if no connection is made. 58

59 Connecting the external safety equipment (cont.) Installation sequence B P STB ON ON N STB TR TR A 50 C P Installation D P A Jumper "STB" "STB" B Low water indicar, minimum pressure limiter C Maximum pressure limiter D Further safety equipment. Remove jumper "STB" "STB".. Connect the external safety equipment in series plug abö. 59

60 Installation sequence Provisional burner operation STB EIN EIN N STB TR TR Insert jumper "TR" "ON/TR" at "TR" "ON". The boiler is heated up with burner stage or the lower heating output. Shutdown takes place via the temperature controller. A A Jumper "TR" "ON/TR" Connecting an AC burner Pressure-jet oil/gas burners The burner cables are included in the standard boiler delivery. Connect the burner in accordance with DIN 479 [or local regulations]. Max. current consumption 6 (3) A. 60

61 Installation sequence Connecting an AC burner (cont.) L STB 4 L N T T S3 B4 PE N 4 TR Störung H BZ L N T T S3 B4 A To the control unit B To the burner Terminal codes L Phase via high limit safety cuut the burner PE Earth conducr burner N Neutral conducr burner T, T Control chain S3 Connection for burner fault B4 Connection for hours run meter Signal pass direction: Control unit burner Signal pass direction: Burner control unit Equipment codes High limit safety cut-out Control unit high limit safety cut-out TR Control unit temperature controller H Burner fault signal BZ Hours run meter Installation Burner without plug Install the mating plug from Viessmann or from the burner manufacturer; connect the burner cable. 6

62 Installation sequence Connecting an AC burner (cont.) T6 T7T8 90 BN BK BU Terminal codes T6, T8 Control chain burner stage "ON" or modulation controller "OPEN" T6, T7 Control chain burner stage "OFF" or modulation controller "CLOSE" Signal pass direction: Control unit burner Signal pass direction: Burner control unit Colour coding DIN IEC BK black BN brown BU blue A To the control unit B To the burner Viessmann Unit burner The burner cables are included in the Vicrossal standard delivery. Max. current consumption 6 (3) A. 6

63 Installation sequence Connecting an AC burner (cont.) A L N T T S3 B4 4 B4 S3T T N L Terminal codes L Phase via high limit safety cuut the burner PE Earth conducr burner N Neutral conducr burner T, T Control chain S3 Connection for burner fault B4 Connection for hours run meter Signal pass direction: Control unit burner Signal pass direction: Burner control unit Installation 4 B A To the control unit B To the burner 63

64 Installation sequence Connecting an AC burner (cont.) 90 T6T7T8 90 T6T7T8 A BN BK BU BN BK BU Terminal codes T6, T8 Control chain burner stage "ON" or modulation controller "OPEN" T6, T7 Control chain burner stage "OFF" or modulation controller "CLOSE" Colour coding DIN IEC BK black BN brown BU blue B A To the control unit B To the burner Connecting a three-phase burner Safety chain, potential free Note If there is a jumper from the external conducr the control voltage in the burner, it may have be removed. Always observe the burner manufacturer's details. 64

65 Installation sequence Connecting a three-phase burner (cont.) F TR K A T6 T7 T8 a Installation B C D E F G H K L A Control unit B Main contacr (on site) C Three-phase burner D Three-phase burner power supply E Main contacr control F Safety chain (high limit safety cuut), potential-free G Control chain stage /base load H Burner fault message K Hours run meter stage L Base load/full load fö Control unit power supply connection fa Burner, stage lö Burner, stage abö Plug for external connections a External safety equipment; remove jumper when connecting aba Safety chain, potential-free, remove jumper when making this connection 65

66 Installation sequence Connecting a three-phase burner (cont.) Safety chain not potential-free Note If there is a jumper from the external conducr the control voltage in the burner, it may have be removed. Always observe the burner manufacturer's details. F TR K A T6 T7 T8 a B C D E F G H K A Control unit B Main contacr (on site) C Three-phase burner D Three-phase burner power supply E Main contacr control F Control chain stage /base load G Burner fault message H Hours run meter stage K Base load/full load fö Control unit power supply connection fa Burner, stage lö Burner, stage abö Plug for external connections a External safety equipment; remove jumper when connecting aba Safety chain (STB) 66

67 Installation sequence Power supply Directives Regulations Carry out the power supply connection and all earthing measures (i.e. RCD circuit) in accordance with IEC 60364, the requirements of your local power supply utility, and VDE or national regulations. Protect the power cable the control unit with an appropriate fuse/mcb. For oil and gas combustion equipment over 00 kw, according the Sample Combustion Ordinance "FeuVO", an "emergency shutdown" must be installed on site outside the installation room. The national combustion equipment ordinance for your local region must be observed. For combustion equipment EN 5056-, the "emergency shutdown" installed on site must comply with the requirements of EN Install the "emergency shutdown" outside the installation room; it must be able separate all non-earthed conducrs simultaneously with a gap of 3 mm at least. We additionally recommend installing an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can occur with energy-efficient equipment. Recommended power cable 3-core cable selected from the following options: H05VV-F3G.5 mm H05RN-F3G.5 mm Installation 67

68 Installation sequence Power supply (cont.) L PE N. Check whether the power cable the control unit has appropriate fuse protection.. Connect the power cable at the junction box and plug fö (on-site). BU GNYE BN N L 40 Danger Incorrect core allocation can cause severe injury and can damage the appliance. Take care not interchange wires "L" and "N": L BN (brown) N BU (blue) PE GNYE (green/yellow) 3. Insert plug fö in the control unit. A Power supply 30 V~ B Fuse C Mains isolar, two-pole (on-site) D Junction box (on site) Power supply in conjunction with Vicrossal, type CT The power supply is connected at the boiler burner control unit. Boiler installation instructions 68

69 Installation sequence Fitting the front part of the control unit.. A Installation Route the ribbon cable through the retainer A. 69

70 Installation sequence Opening the control unit

71 Commissioning Changing the language The following is displayed during commissioning (delivered condition German). Sprache Deutsch Bulgarski Cesky Dansk Wählen mit êç DE BG ê CZ ê DK ê ( Setting the date and time The time and date need be reset during commissioning or after prolonged time out of use. Time and date Setting Continue with OK Testing the high limit safety cut-out The minimum circulation volume should be 0 % of the circulation volume at rated load. Reduce the heat consumption as far as possible.. Hold down the "TEST" key until the burner has shut down: Thermostat is bridged. The high limit safety cut-out must shut down the burner at the latest when the safety temperature has been reached.. Release the "TEST" key. 3. Wait until the boiler water temperature has dropped approx. 5 0 K below the selected safety temperature. 4. Reset the high limit safety cut-out by pressing reset butn. Operating instructions Service 7

72 Commissioning Matching coding addresses the system version Check all addresses in Code and adjust if required. Check the following coding addresses and adjust accordingly in Code : Group Function "0C" "Boiler" Return temperature control "0d" "Boiler" Therm-Control "4C" "General" Function plug sö "4d" "General" Function plug sl "4E" "General" Function plug gs "98" "General" Viessmann system number "9C" "General" Moniring LON subscribers Matching the control unit a two-stage burner Matching coding addresses according the burner used Address Meaning Setting 03:... Fuel Gas operation: 0 (delivered condition) Oil operation: (irreversible) 08:... Units and tens of the maximum burner output Example: Max. burner output: 5 kw select: 5 Note Values up and including 99 kw can be entered directly. 09:... Hundreds of the maximum burner output Example: Max. burner output: 5 kw select: 0A:... Ratio of output burner stage maximum burner output in percent Example: Output burner stage 35 kw Max. burner output: 5 kw (35 kw : 5 kw) 00 % = 60 % Matching the control unit a modulating burner Note The burner must be fully adjusted. To achieve a wide modulating range, set the minimum output as low as possible (take the chimney and flue system in account). 7

73 Matching coding addresses the system version (cont.) Commissioning Matching coding addresses according the burner used Address Meaning Setting 03:... Fuel Gas operation: 0 (delivered condition) Oil operation: (irreversible) 08:... Units and tens of the maximum burner output Example: Max. burner output: 5 kw select: 5 Note Values up and including 99 kw can be entered directly. 09:... Hundreds of the maximum burner output Example: Max. burner output: 5 kw select: 5:... Modulation range runtime Calculate runtime (s) of servomor between base load and max. burner output 0A:... Ratio of output base load maximum burner output in percent 05:... Ratio of partial output at ⅓ of the servomor runtime maximum burner output in percent Example: Base load output: 7 kw Max. burner output: 5 kw (7 kw: 5 kw) 00 % = 3 % Example: Partial output: 7 kw Max. burner output: 5 kw (7 kw: 5 kw) 00 % = 76 % Checking actuars and sensors Testing relays. Press OK and simultaneously for approx. 4 s.. "Actuar test" The following relay outputs can be controlled subject the system equipment level: Display Explanation "All actuars" OFF All actuars have been switched off. "Base load" ON Mod. burner operates at min. output. "Burner" ON Burner stage is switched on. Service 73

74 Commissioning Checking actuars and sensors (cont.) Display Explanation "Burner stage " ON Burner stage is switched on. "Full load" ON Mod. burner operates at max. output. "Burner stage + " ON Burner stages and are switched ON. "Burner modulation" Open Modulating burner. "Burner modulation" Neutral Modulating burner. "Burner modulation" Closed Modulating burner. "Output 0" ON Output 0 enabled. "Output 5" Open "Output 5" Neutral "Output 5" Closed "Cylinder prim pump" ON Output for circulation pump for cylinder heating enabled. "DHW circ pump" ON Output for DHW circulation pump enabled. "Output 9" ON Output 9 enabled. "Central fault mess." ON "Htg circ pump HC" ON Output for heating circuit pump enabled (heating circuit with mixer M). "Mixer HC" Open Output "Mixer open" enabled (heating circuit with mixer M). "Mixer HC" Closed Output "Mixer closed" enabled (heating circuit with mixer M). "Htg circ pump HC3" ON Output for heating circuit pump enabled (heating circuit with mixer M3). "Mixer HC3" Open Output "Mixer open" enabled (heating circuit with mixer M3). "Mixer HC3" Closed Output "Mixer open" enabled (heating circuit with mixer M3). "EA output " ON Contact" P - S" on plug abj for extension EA closed. "AM output " ON Output enabled. "AM output " ON Output enabled. "Solar circuit pump" ON Output for solar circuit pump sf at solar control module, type SM enabled. "Solar circ pmp min" ON Output for solar circuit pump sf at solar control module, type SM, switched minimum speed. "Solar circ pmp max" ON Output for solar circuit pump sf at solar control module, type SM, switched maximum speed. "SM output " ON Output ss at solar control module, type SM, enabled. 74

75 Commissioning Checking actuars and sensors (cont.) Note During burner operation, the pumps connected the control unit are started. Checking sensors. Press OK and simultaneously for approx. 4 s.. "Diagnosis" 3. Select group (see page 8). 4. Scan actual temperature of the relevant sensor. Adjusting heating curves The heating curves illustrate the relationship between the outside temperature and the boiler water or flow temperature. To put it simply: The lower the outside temperature, the higher the boiler water or flow temperature. The room temperature, in turn, depends on the boiler water or flow temperature. Settings in the delivered condition: Slope =.4 Level = 0 Service 75

76 Commissioning Adjusting heating curves (cont.) Slope Boiler water or flow temperature in C Set room temperature in C C B A Outside temperature in C Example of outside temperature 4 C A Underfloor heating system, slope B Low temperature heating system, slope C Heating systems with a boiler water temperature in excess of 75 C, slope greater than.6 Selecting the set room temperature Individually adjustable for each heating circuit. The heating curve is offset along the axis of the set room temperature. When the heating circuit pump logic function has been enabled, it modifies the starting and spping characteristics of the heating circuit pump. 76

77 Commissioning Adjusting heating curves (cont.) Standard set room temperature 0 A 6 C 0 C Reduced set room temperature 0 A 4 C C 6 0 B -0 C C B -0 D E D E Changing the standard room temperature from 0 6 C A Boiler water temperature or flow temperature in C B Outside temperature in C C Set room temperature in C D Heating circuit pump OFF E Heating circuit pump ON Changing the standard set room temperature Operating instructions Changing the reduced room temperature from 3 4 C A Boiler water temperature or flow temperature in C B Outside temperature in C C Set room temperature in C D Heating circuit pump OFF E Heating circuit pump ON Changing the reduced set room temperature Operating instructions Changing the slope and level Individually adjustable for each heating circuit. Service 77

78 Commissioning Adjusting heating curves (cont.) Extended menu:. Boiler water or Flow temperature in C A B +0-0 Outside temperature in C "Heating" 3. Select heating circuit. 4. "Heating curve" 5. "Slope" or "Level" 6. Select heating curve according the system requirements. A Changing the slope B Changing the level (vertical parallel offset of the heating curve) Example: Heating curve setting with slope.5: Heating curve HC 00 C 3 C 4 C 55 C 68 C 8 C Slope.5 Change with ( Connecting the control unit the LON The LON communication module (accessory) must be plugged in. Installation instructions LON communication module Note The data transfer via the LON system can take several minutes. 78

79 Commissioning Connecting the control unit the LON (cont.) Single boiler system with Vitronic 00-H and Vicom 00 (example) Set the LON subscriber numbers and further functions via code (see the following table). Note In the same LON system, the same subscriber number cannot be allocated twice. Only one Vitronic may be programmed as fault manager. Boiler control unit Vitronic 00-H Vitronic 00-H Vicom LON LON LON Subscriber no. Code "77:" Control unit is fault manager Code "79:" Control unit transmits the time Code "7b:". Control unit transmits outside temperature Set code "97:". Viessmann system number Code "98:" LON subscriber fault moniring Code "9C:0" Subscriber no. 0 Code "77:0" Subscriber no. Set code "77:". Subscriber no. 99 Control unit is not Control unit is not Device is fault fault manager fault manager manager. Code "79:0". Code "79:0". The control unit The control unit Device receives the time receives the time receives the Set code "8:3". Set code "8:3". time. Control unit receives Control unit receives the outside temperaturture the outside tempera- Set code "97:". Set code "97:". Viessmann system Viessmann system number number Code "98:" Code "98:" LON subscriber fault LON subscriber fault moniring moniring Code "9C:0" Code "9C:0" Service Carrying out the LON subscriber check Communication with the system devices connected the fault manager is tested by means of a subscriber check. Preconditions: The control unit must be programmed as fault manager (code "79:"). The LON subscriber number must be programmed in all control units. The LON subscriber list in the fault manager must be up date. 79

80 Commissioning Connecting the control unit the LON (cont.) Performing the subscriber check:. Press OK and å simultaneously for approx. 4 s.. "Service functions" 3. "Subscriber check" 4. Select subscriber (e.g. subscriber 0). The subscriber check for the selected subscriber is initiated. Successfully tested subscribers are designated with "OK". Unsuccessfully tested subscribers are designated with "Not OK". Note To carry out a new subscriber check, create a new subscriber list with "Delete list?" (subscriber list is updated). Note During the subscriber check, the display for the relevant subscriber shows the subscriber no. and "Wink" for approx. min. 80

81 Service scans Calling up the service menu Press OK and å simultaneously for approx. 4 s. Service menu overview Service Diagnosis Actuar test Coding level Coding level Fault hisry Service functions Terminate service? General Heating circuit HC Heating circuit HC Heating circuit 3 HC3 DHW Solar Brief scan Reset data Subscriber check Service PIN Vicom PIN input Service reset "Coding level " is only displayed if this level has been enabled: Press OK and approx. 4 s. simultaneously for Exit service menu. Select "Terminate service?".. Select "Yes". 3. Confirm with OK. Note The system exits the service menu aumatically after 30 min. Service Scanning operating data Operating data can be scanned in six areas (see "Diagnosis" in the overview "Service menu"). Operating data on heating circuits with mixers and solar can only be scanned if the components are installed in the system. For further information on operating data, see chapter "Brief scan". 8

82 Service scans Scanning operating data (cont.) Note "- - -" appears on the display if a sensor that has been scanned is faulty. Calling up operating data. Press OK and å simultaneously for approx. 4 s. 3. Select required group, e.g. "General".. "Diagnosis" Resetting operating data Saved operating data (e.g. hours run) can be reset 0. The value "Adjusted outside temp" is reset the actual value.. Press OK and å simultaneously for approx. 4 s.. "Diagnosis" 3. "Reset data" 4. Select required value (e.g. "Burner") or "All details". Brief scan In the brief scan, you can scan temperatures, software versions and connected components, for example.. Press OK and simultaneously for approx. 4 s.. "Diagnosis" 3. "Brief scan". 4. Press OK. The display shows lines with 6 fields each. Diagnosis brief scan : : 3: 4: 0 0 A A 0 Select with 0 A Ø 8

83 Service scans Brief scan (cont.) For an explanation of the relevant values in the individual lines, see the following table: Line (brief Field scan) : System schemes 0 0 Control unit software version Programming unit software version : Burner type 0 0 Appliance identification ZE-ID 0: Single stage : Twostage : Modulating 3: 0 0 Number of KM BUS subscribers Software version Solar control module 4: : Software version, extension AM Software version, extension EA 6: : Subnet address/system number Node address 0 0 8: SNVT config. 0: Au : Tool Software version Communic. coproc. Software version Neuron Chip Number of LON subscribers Service 83

84 Service scans Brief scan (cont.) Line (brief scan) 9: Remote control 0: none : Vitrol 00A or Vitrol 00RF : Vitrol 300A or Vihome 300 Field Heating circuit HC Heating circuit HC Heating circuit HC3 Software Software Software version version version Remote Remote Remote control control control Remote control 0: none : Vitrol 00A or Vitrol 00RF : Vitrol 300A or Vihome 300 Remote control 0: none : Vitrol 00A or Vitrol 00RF : Vitrol 300A or Vihome 300 0: : 0 0 Software 0 Software 0 version, extension for heating circuits and 3 with mixer version, extension for heating circuits and 3 with mixer Note The displays in fields 3 and 5 are the same. Scanning and resetting the "Service" display When the limits specified in the "Boiler" group have been reached via coding addresses "F", "" and "3", "Service" is displayed and flashes. Note Set code "4:" and then code "4:0" in the "Boiler" group if a service is carried out before "Service" is displayed. The selected service parameters for hours run and intervals are reset 0. 84

85 Service scans Scanning and resetting the "Service" display (cont.) Acknowledging a service Press OK acknowledge a service message. Note The service message is transferred the menu. An acknowledged service message that was not reset reappears the following Monday.. Press OK and å simultaneously for approx. 4 s. 3. "Service functions" 4. "Service reset" Note The selected service parameters for hours run and time interval restart at 0. After a service has been carried out (reset service). Reset code "4:" "4:0" in the "Boiler" group. Note If coding address "4" is not reset, "Service" will be displayed again on the following Monday. Calling up acknowledged maintenance messages Extended menu:.. "Service" Service 85

86 Troubleshooting Fault display If there is a fault, the red fault display on the control unit flashes. "Fault" is displayed and flashes. The fault code is displayed with OK. Note If a central fault message facility is connected, this is started. For an explanation of the fault code, see the chapter "Fault codes". For some faults, the type of fault is also displayed in plain text. Acknowledging a fault Follow the instructions on the display. Note The fault message is transferred the menu. A fault messaging facility, if connected, will be switched off. If an acknowledged fault is not remedied, the fault message will be re-displayed the following day and the fault message facility restarted. Calling up acknowledged fault messages Extended menu:.. "Fault" Calling up fault codes from the fault memory (fault hisry) The 0 most recent faults (including those remedied) are saved and can be called up. Faults are sorted by date.. Press OK and å simultaneously for approx. 4 s.. "Fault hisry" 3. "Display?" Fault codes Displayed fault code System characteristics Cause 0F Control mode Service "0F" is only displayed in the fault hisry 0 Controls as if the outside temperature was 0 C 86 Short circuit, outside temperature sensor Measures Service required Note After servicing, set code "4:0". Check the outside temperature sensor (see page 78).

87 Troubleshooting Fault display (cont.) Displayed fault code System characteristics Cause 8 Controls as if the outside temperature was 0 C sensor 9 Controls as if the outside temperature was 0 C. 30 With DHW cylinder: Circulation pump for cylinder heating on; boiler is maintained at set cylinder temperature. Without DHW cylinder: Boiler is regulated by the temperature controller. 38 With DHW cylinder: Circulation pump for cylinder heating on; boiler is maintained at set cylinder temperature. Without DHW cylinder: Boiler is regulated by the temperature controller. 40 Mixer is being closed. Lead break, outside temperature Communication fault, outside temperature sensor RF Short circuit, boiler water temperature sensor Lead break, boiler water temperature sensor Short circuit, flow temperature sensor, heating circuit with mixer M (heating circuit ) Measures Check the outside temperature sensor (see page 78). Check the wireless connection (place the outside temperature sensor RF close the wireless base). Deregister and then re-register the outside temperature sensor. Replace if necessary (see separate installation and service instructions). Check the boiler water temperature sensor (see page 77). Check the boiler water temperature sensor (see page 77) Check the flow temperature sensor (see page 77). Service 87

88 Troubleshooting Fault display (cont.) Displayed System characteristics fault code 44 Mixer is being closed. 48 Mixer is being closed. 4C 88 Mixer is being closed. 50 Cylinder primary pump "ON": Set DHW temperature = Set boiler water temperature Priority control is cancelled. or With primary sre system: Cylinder heating is started and spped via cylinder temperature sensor. 5 With primary sre system: Cylinder heating is started and spped via cylinder temperature sensor. Cause Short circuit, flow temperature sensor, heating circuit with mixer M3 (heating circuit 3) Lead break, flow temperature sensor, heating circuit with mixer M (heating circuit ) Lead break, flow temperature sensor, heating circuit with mixer M3 (heating circuit 3) Short circuit, cylinder temperature sensor Short circuit, cylinder temperature sensor 5 Control mode. Short circuit, flow temperature sensor low loss header Measures Check the flow temperature sensor (see page 77). Check the flow temperature sensor (see page 77). Check the flow temperature sensor (see page 77). Check the cylinder temperature sensor (see page 77). Check the cylinder temperature sensor (see page 77). Check the flow temperature sensor (see page 77).

89 Troubleshooting Fault display (cont.) Displayed fault code System characteristics Cause 58 Cylinder primary Lead break, cylinder pump "ON": temperature Set DHW temperature sensor = Set boiler water temperature Priority control is cancelled. or With primary sre system: Cylinder heating is started and spped via cylinder temperature sensor. 59 With primary sre Lead break, cylinder system: temperature Cylinder heating is sensor started and spped via cylinder temperature sensor. 5A Control mode. Lead break, low loss header flow temperature sensor 60 Boiler with maximum temperature, no output reduction, mixer return temperature control "Open". 68 Boiler with maximum temperature, no output reduction, mixer return temperature control "Open". Short circuit, temperature sensor aja Lead break, temperature sensor aja Measures Check the cylinder temperature sensor (see page 77). Check the cylinder temperature sensor (see page 77). Check the flow temperature sensor (see page 77). Without flow temperature sensor: Set code "5:0" in the "General" group. Check temperature sensor (see page 77). Check temperature sensor (see page 77). Without temperature sensor: Set code "4A:0" in the "General" group. Service 89

90 Troubleshooting Fault display (cont.) Displayed fault code System characteristics Cause 70 Shunt pump constantly Short circuit, tem- "ON". perature sensor With primary sre ajb system: Mixer primary circuit "Closed", no DHW heating. 78 Shunt pump constantly Lead break, tem- "ON". perature sensor With primary sre ajb system: Mixer primary circuit "Closed", no DHW heating. 90 Control mode. Short circuit, temperature sensor /, Connection at the solar control module. 9 Control mode. Short circuit, temperature sensor aö, Connection at the solar control module. 9 No solar DHW heating. 90 Short circuit, collecr temperature sensor, temperature sensor connection & at solar control module or sensor at S of the Visolic. 93 Control mode. Short circuit, temperature sensor, connection at S3 of the Visolic. Measures Check temperature sensor (see page 77). Check temperature sensor (see page 77). Without temperature sensor: Set code "4b:0" in the "General" group. Check temperature sensor / (see separate installation and service instructions). Check temperature sensor aö (see separate installation and service instructions). Check sensor at the solar control unit (see separate installation and service instructions). Check sensor at the solar control unit (see separate installation and service instructions).

91 Troubleshooting Fault display (cont.) Displayed System characteristics fault code 94 No solar DHW heating. Cause Short circuit, cylinder temperature sensor, temperature sensor connection % at solar control module or sensor at S of the Visolic. 98 Control mode. Lead break, temperature sensor /, Connection at the solar control module. 99 Control mode. Lead break, temperature sensor aö, Connection at the solar control module. 9A No solar DHW heating. Lead break, collecr temperature sensor, temperature sensor connection & at solar control module or sensor at S of the Visolic. 9b Control mode. Lead break, temperature sensor, connection at S3 of the Visolic. Measures Check sensor at the solar control unit (see separate installation and service instructions). Check temperature sensor / (see separate installation and service instructions). Set coding address "0" in the "Solar" group. Check temperature sensor aö (see separate installation and service instructions). Set coding address "0" in the "Solar" group. Check sensor at the solar control unit (see separate installation and service instructions). Check sensor at the solar control unit (see separate installation and service instructions). Service 9

92 Troubleshooting Fault display (cont.) Displayed fault code 9C System characteristics No solar DHW heating. Cause Lead break, cylinder temperature sensor, temperature sensor connection % at solar control module or sensor at S of the Visolic. 9E Control mode. No flow rate in solar circuit or flow rate o low, or temperature limiter has responded. 9F Control mode. Solar control module or Visolic fault. Displayed if a fault occurs at these appliances that has no fault code in the Vitronic. A0 Boiler cools down. Fault, safety equipment at "X7" of plug-in adapr for external safety equipment. A Boiler cools down. Fault, safety equipment at "X3" of plug-in adapr for external safety equipment. A Boiler cools down. Fault, safety equipment at "X" of plug-in adapr for external safety equipment. Measures Check sensor at the solar control unit (see separate installation and service instructions). Check solar circuit. Acknowledge fault message (see separate installation and service instructions). Check solar control unit (see separate installation and service instructions). Check safety equipment, and reset if required. Check safety equipment, and reset if required. Check safety equipment, and reset if required. 9

93 Troubleshooting Fault display (cont.) Displayed System characteristics Cause Measures fault code A3 Boiler cools down. Fault, safety equipment at "X" of plug-in adapr for external safety equipment. AA Control mode. Therm-Control configuration fault: Plug aja not plugged in. Ab Control operation; DHW cylinder may be cold. Primary sre system configuration error: Code "55:3" has been selected, but plug ajb is not plugged in and/or Codes "4C:" and "4E:" have not been set. AC Control mode. Return temperature control configuration error: Code "0C:" has been selected, but plug aj is not plugged in and/or Code "4E:" has not been set. b0 Control mode. Short circuit, flue gas temperature sensor b Control mode. Communication error, programming unit Check safety equipment, and reset if required. Insert plug aja. For Vicrossal, code "0d: 0" must be selected. Insert plug ajb and check codes. Insert plug aja and check codes. Check the flue gas temperature sensor (see page 78). Check connections and replace the programming unit if required. b5 Control mode. Internal fault Check PCB (see parts list) is plugged in correctly. Service 93

94 Troubleshooting Fault display (cont.) Displayed fault code System characteristics Cause b6 Constant mode. Invalid hardware recognised Measures Check coding address "9" in the "General" group; "9:66" must be set. b7 94 Boiler is regulated by the temperature controller. Boiler coding card faulty b8 Control mode. Lead break, flue gas temperature sensor ba Mixer "Closed". Communication error, PCB extension for heating circuits and 3 with mixer bc bd Control mode without remote control. Control mode without remote control. Communication error, remote control Vitrol heating circuit without mixer A (heating circuit ) Communication error, Vitrol remote control, heating circuit with mixer M (heating circuit ) Note Code "8A:76" in the "General" group must be selected for coding address "9" be displayed. Plug in or replace the boiler coding card (see page 44). Check the flue gas temperature sensor (see page 78). Without flue gas temperature sensor: Set code "F:0" in the "Boiler" group. Check that the PCB and ribbon cable are plugged in, and replace PCB if required. Check connections, lead (see separate installation and service instructions) and coding address "A0" in the "Heating circuit..." group. Check connections, lead (see separate installation and service instructions) and coding address "A0" in the "Heating circuit..." group.

95 Troubleshooting Fault display (cont.) Displayed fault code be bf System characteristics Control mode without remote control. Control mode. No communication via LON. Cause Communication fault, remote control Vitrol with mixer M3 (heating circuit 3) Incorrect LON communication module C Boiler cools down. External safety equipment at plug abö C Control mode. Lead break, KM BUS solar control module or Visolic C3 Control mode. Communication fault, extension AM C8 Boiler cools down. Fault, low water indicar at "X7" of plug-in adapr for external safety equipment (see page 80). C9 Boiler cools down. Fault, maximum pressure limiter at "X3" of plug-in adapr for external safety equipment (see page 80). Measures Check connections, lead (see separate installation and service instructions) and coding address "A0" in the "Heating circuit..." group. Replace LON communication module. Check connection and external safety equipment (see page 58) Check KM BUS cable and appliance. Without solar control unit: Set code "54:0" in the "General" group. Check connections. Without extension AM: Set code "3:0" in the "General" group. Check the water level of the system; reset low water indicar. Check the system pressure and reset the maximum pressure limiter. Service 95

96 Troubleshooting Fault display (cont.) Displayed System characteristics Cause Measures fault code CA Boiler cools down. Fault, minimum or maximum pressure limiter at "X" of plug-in adapr for external safety equipment (see page 80). Cb Boiler cools down. Additional high limit safety cut-out fault or Temperature limiter at "X" of plug-in adapr for external safety equipment (see page 79). Cd Control mode. Vicom 00 communication fault CE Control mode. Communication fault, plug-in adapr for external safety equipment CF 96 Control mode. No communication via LON. Communication error, LON communication module of control unit Check system pressure and reset minimum or maximum pressure limiter. Check the system temperature and reset the high limit safety cut-out. Check connections and Vicom 00 (see separate installation and service instructions). Without Vicom 00: Set code "95:0" in the "General" group. Check plug-in adapr (see page 79). Without plug-in adapr: Set code "30:0" in the "General" group. Check LON communication module and replace if required. If no LON communication module is installed, set code "76:0" in "General" group. d Boiler cools down. Burner fault Check the burner.

97 Troubleshooting Fault display (cont.) Displayed fault code System characteristics Cause d Control mode. Communication error. Plug-in adapr for external safety equipment d3 Control mode. Communication error, extension EA d4 Boiler cools down. The high limit safety cut-out has responded or fuse F has blown d6 Control mode. Input DE at extension EA reports a fault d7 Control mode. Input DE at extension EA reports a fault d8 Control mode. Input DE3 at extension EA reports a fault da db dc Control mode without room influence. Control mode without room influence. Control mode without room influence. Short circuit, room temperature sensor, heating circuit without mixer A (heating circuit ) Short circuit, room temperature sensor, heating circuit with mixer M (heating circuit ) Short circuit, room temperature sensor, heating circuit with mixer M3 (heating circuit 3) Measures Check plug-in adapr (see page 79). Without plug-in adapr: Set code "3:0" in the "General" group. Check connections (see page 87). Without extension EA: Set code "5b:0" in the "General" group. Check the high limit safety cut-out or the burner, burner loop and fuse F. Remove fault at appliance concerned. Remove fault at appliance concerned. Remove fault at appliance concerned. Check the room temperature sensor (see page 77). Check the room temperature sensor (see page 77). Check the room temperature sensor (see page 77). 97 Service

98 Troubleshooting Fault display (cont.) Displayed fault code dd de df System characteristics Control mode without room influence. Control mode without room influence. Control mode without room influence. Cause Lead break, room temperature sensor, heating circuit without mixer A (heating circuit ) Lead break, room temperature sensor, heating circuit with mixer M (heating circuit ) Lead break, room temperature sensor, heating circuit with mixer M3 (heating circuit 3) Measures Check the room temperature sensor (see page 77). Check the room temperature sensor (see page 77). Check the room temperature sensor (see page 77). Note In case of subscriber faults, "Fault subscriber"... is displayed. 98

99 Function description Boiler water temperature control Brief description The boiler water temperature is regulated by starting and spping the burner or through modulation. The set boiler water temperature is determined from the following parameters: Set flow temperature of the heating circuits connected the control unit and the heating circuits connected via the LON BUS External demand Set DHW temperature The boiler coding card defaults a minimum boiler water temperature that must be maintained protect the boiler. In conjunction with Therm-Control: The set boiler water temperature will be increased when the actual temperature at the Therm-Control sensor falls below the set temperature. When the DHW cylinder is heated up, the default set boiler water temperature is 0 K above the set DHW temperature (adjustable via coding address "60" in the "DHW" group). Functions The boiler water temperature is captured by the following equipment: High limit safety cut-out STB (liquid expansion) Temperature controller TR (liquid expansion) Boiler water temperature sensor NTC 0 kω Lower control range limits In standard mode and when frost protection is enabled, the boiler water temperature will be regulated subject the respective boiler. Upper control range limits High limit safety cut-out STB 0/00 ºC Temperature controller TR 95/00/0 ºC Electronic maximum temperature limit: Setting range: 0 7 ºC Changed via coding address "06" in the "Boiler" group. Service 99

100 Function description Boiler water temperature control (cont.) Switching hysteresis, burner Permanent switching hysteresis Code "04:0" Burner ON OFF + Time set - low heat demand average heat demand high heat demand Heat demand-dependent switching hysteresis The heat demand-dependent switching hysteresis takes the boiler load in account. The switching hysteresis, i.e the burner runtime varies subject actual heat demand. ERB50 function Code "04:" Subject heat demand, values between 6 and K result. OFF Burner ON Time set -3 low heat demand average heat demand high heat demand ERB80 function Code "04:" Subject heat demand, values between 6 and 0 K result. 00

101 Function description Boiler water temperature control (cont.) OFF Burner ON Time set -3 low heat demand average heat demand high heat demand Boiler protection functions Therm-Control (Start-up system) For heating systems with distribur installed close the boiler. Requirement: The boiler water flow rate in the startup phase (e.g. after a weekend shutdown) must be able be reduced by at least 50 %. Also affects the heating circuits of a Vitronic 00-H installed downstream. Therm-Control in conjunction with heating systems that are not connected with the Vitronic via LON Plug söa of the Vitronic is used as switching contact for the Therm-Control. Required code: "4C:" in the "General" group. Function The Therm-Control sensor, installed near the return connecr, captures the return temperature. The burner is ramped up full load if the facry-selected set temperature (defaulted by the boiler coding card) is not being achieved. The flow rate is reduced via the mixer. When the set temperature is exceeded, the mixers are opened and the flow rate gradually increased 00 %. Service 0

102 Function description Boiler water temperature control (cont.) 0 0 A N L A K cl. cl. cl. B n söa Closing the mixers A Contacr relay, part no B Downstream heating circuit controller, switching contact closed: Signal for mixer "Close" Raising the return temperature via a shunt pump For heating systems with distribur installed close the boiler. Requirement: The boiler water flow rate must be able be reduced by at least 50 %. Shunt pump sized approx. 30 % of the tal throughput. Also affects the heating circuits of a Vitronic 00-H installed downstream. The shunt pump is started via temperature sensor T if the facry-selected minimum return temperature (defaulted by the boiler coding card) is not being achieved. The flow rate will be reduced via the mixer if the minimum return temperature captured by temperature sensor T is not achieved despite the return temperature raising. Function Temperature sensors T and T capture the return temperature at different test points. 0

103 Function description Boiler water temperature control (cont.) Return temperature raising in conjunction with heating systems that are not connected with the Vitronic via LON Plug söa of the Vitronic is used as switching contact. Required code: "4C:" in the "General" group. 0 N L K 0 A A cl. cl. cl. B n söa Closing the mixers A Contacr relay, part no B Downstream heating circuit controller, switching contact closed: Signal for mixer "Close" Return temperature control via shunt pump and 3-way mixing valve For heating systems where downstream heating circuits cannot be controlled, e.g. older heating systems or commercial nurseries. Function Temperature sensors T and T capture the return temperature at different test points. Control sequence The shunt pump is started via temperature sensor T if the facry-selected minimum return temperature (defaulted by the boiler coding card) is not achieved. The flow rate will be reduced via the 3- way mixing valve if, in spite of the return temperature raising facility, the minimum return temperature captured by temperature sensor T is not achieved. Service Boiler goes cold (set value K) 03

104 Function description Boiler water temperature control (cont.) The burner start signal is selected as the set boiler water temperature minus K, and the burner starts its own moniring program. Note The burner start may be delayed by a few minutes subject the number of auxiliary circuits and the combustion type. Boiler heats up The burner spping point is determined by the shutdown differential (coding address "3" in the "boiler" group. Heating circuit control Brief description Type GWB: The control unit has a control circuit for one heating circuit without mixer A (heating circuit ). Type GWB: The control unit has control circuits for one heating circuit without mixer A (heating circuit ) and two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). The set flow temperature of every heating circuit is determined from the following parameters: Outside temperature Set room temperature Operating mode Heating curve slope and level The boiler coding card defaults a minimum boiler water temperature that must be maintained protect the boiler. The flow temperature of heating circuits without mixer is equal the boiler water temperature. The flow temperature of the heating circuits with mixer is regulated by the stepped opening or closing of the mixers. The mixer mor control changes the actuating and pause times subject the control differential (control deviation). Functions The heating circuit without mixer is subject the boiler water temperature and its control range limits. The heating circuit pump is the only actuar. The flow temperature of the heating circuits with mixer is recorded by the flow temperature sensor of the relevant heating circuit. 04

105 Function description Heating circuit control (cont.) Time program In accordance with the time program in the "Heating and DHW" heating program, the control unit regulates between "Central heating with standard room temperature" and "Central heating with reduced room temperature". Every operating mode has its own set level. 4 time phases per day can be selected. Outside temperature A heating curve must be set for matching the control unit the building and the heating system. The heating curve characteristics determine the set boiler water temperature subject outside temperature. The control unit uses an average outside temperature. This comprises the actual and the adjusted outside temperature. Room temperature In conjunction with the remote control and room temperature hook-up (coding address "b0" in the "Heating circuit..." group): Compared with the outside temperature, the room temperature has a greater influence on the set boiler water temperature (changed via coding address "b" in the "Heating circuit..." group). In conjunction with heating circuits with mixer: For control differentials (actual value deviation) above K room temperature, the influence can be increased again (coding address "b6" in the "Heating circuit..." group): Quick heat-up The set room temperature must be raised by at least K by the following measures: Activating party mode Changeover from central heating with reduced temperature central heating with standard temperature Start optimisation (coding address "b7" in the "Heating circuit..." group) Quick heat-up will sp when the set room temperature has been reached. Quick setback The set room temperature must be reduced by at least K by the following measures: Activating economy mode Changeover from central heating with standard temperature central heating with reduced temperature Sp optimisation (coding address "C" in the "Heating circuit..." group) Quick setback will end when the set room temperature has been reached. 05 Service

106 Function description Heating circuit control (cont.) DHW temperature Priority control With priority control: (code "A:" in the "Heating circuit..." group): The set flow temperature is set 0 C during cylinder heating. The mixer closes and the heating circuit pump is switched off. Without priority control: The heating circuit control unit continues operate with the same set value. With modulating priority control in conjunction with heating circuits with mixer: The heating circuit pump remains switched on. The set flow temperature of the heating circuits will be reduced, for as long as the set boiler water temperature has not been reached during cylinder heating. The set flow temperature is determined from the following parameters: Outside temperature Differential between the set and the actual boiler water temperature Heating curve slope and level Setting of coding address "A" in the "Heating circuit..." group Heating circuit pump logic (economy mode) The heating circuit pump is switched off (set flow temperature set 0 C) if the outside temperature exceeds the value selected via coding address "A5" in the "Heating circuit..." group. Extended economy mode The heating circuit pump is switched off (set flow temperature set 0 C) if one of the following criteria is met: The adjusted outside temperature exceeds the value selected via coding address "A6" in the "Heating circuit..." group. The heating circuit pump can be switched off for a time calculated by the control unit when changing over from heating mode reduced mode. Requirement: There is no risk of frost. Coding address "b0" in the "Heating circuit..." group must be set 0. The idle period can be individually adjusted via coding address "A9" in the "Heating circuit..." group. Note If, during the pump idle period, the system is switched over heating mode or the set room temperature is increased, the heating circuit pump is switched on, even if the period has not yet expired. The actual room temperature exceeds the value selected via coding address "b5" in the "Heating circuit..." group. The mixer has been closed for min. (mixer economy function, coding address "A7" in the "Heating circuit..." group). 06

107 Function description Heating circuit control (cont.) Screed drying function In conjunction with a heating circuit with mixer. For drying screeds (observe the information provided by the screed manufacturer). The heating circuit pump of the heating circuit with mixer is switched on and the flow temperature is maintained in accordance with the selected profile. After completion (30 days), the mixer circuit will again be regulated aumatically via the set parameters. Observe EN 64. The report be provided by the heating contracr must contain the following heat-up details: Heat-up data with respective flow temperatures Max. flow temperature achieved Operating conditions and outside temperature during handover of the heating system The various temperature profiles are adjustable via coding address "F" in the "Heating circuit..." group. The function continues after power failure or after the control unit has been switched off. The "Heating and DHW" heating program will be enabled if the screed drying function is terminated or if code "F:0" is manually adjusted. Temperature profile : (EN 64-4) code "F:" Flow temperature C Days Service 07

108 Function description Heating circuit control (cont.) Temperature profile : (ZV parquet and flooring technology) code "F:" Flow temperature C Days Temperature profile 3: Code "F:3" Flow temperature C Days Temperature profile 4: Code "F:4" Flow temperature C Days Temperature profile 5: Code "F:5" Flow temperature C Days 08

109 Function description Heating circuit control (cont.) Temperature profile 6: Code "F:6" Flow temperature C Days Temperature profile 7: Code "F:5" Flow temperature C Days System dynamics You can influence the control characteristics of the mixers via coding address "C4" in the "Heating circuit..." group. Central control Central control for a heating circuit can be programmed via coding address "7A" in the "General" group. The heating and holiday program then applies all additional heating circuits of the system. For these heating circuits, when the heating and holiday program is enabled, "Central control" is displayed. Any holiday programs that may have been set will be deleted. Party and economy modes cannot be enabled on all control units. Therm-Control The output is reduced if the actual temperature at the Therm-Control sensor falls below the set temperature. This closes the heating circuit mixers. Frost protection The flow temperature is maintained in accordance with the heating curve for the reduced set room temperature, but at min. 0 C. A variable frost limit can be set in accordance with coding address "A3" in the "Heating circuit..." group. 09 Service

110 Function description Heating circuit control (cont.) Flow temperature control Boiler water or flow temperature in C 0 +8K 87 A D 8K B C E +0-0 Outside temperature in C A Max. boiler water temperature B Slope =.8 for heating circuit without mixer C Slope =. for heating circuit with mixer D Boiler water temperature (with a differential temperature = 8 K) E Lower boiler water temperature, defaulted by the boiler coding card Differential temperature: The differential temperature is adjustable via coding address "9F" in the "General" group, delivered condition: 8 K. The differential temperature is the minimum value by which the boiler water temperature should be higher than the highest currently required flow temperature of the heating circuit with mixer. System with only one heating circuit with mixer: The set boiler water temperature will be aumatically regulated 8 K above the set flow temperature. System with heating circuit without mixer and heating circuit with mixer: The set boiler water temperature operates in accordance with a special heating curve. The differential temperature of 8 K wards the set flow temperature is set at the facry. Raising the reduced room temperature During operation with reduced room temperature, the reduced set room temperature can be aumatically raised subject the outside temperature. The temperature is raised in accordance with the selected heating curve, but no higher than the set standard room temperature. The outside temperature limits for the start and end of the temperature raising can be adjusted via coding addresses "F8" and "F9" in the "Heating circuit..." group. 0

111 Function description Heating circuit control (cont.) Example using the settings in the delivered condition 90 Boiler water or Flow temperature in C A B Set room temperature in C Outside temp. in C A Heating curve for operation with standard room temperature B Heating curve for operation with reduced room temperature Reducing the heat-up time During the transition from operation with reduced room temperature operation with standard room temperature, the boiler water or flow temperature will be raised in accordance with the selected heating curve. The boiler water or flow temperature increase can be aumatically raised. The value and duration of the additional increase of the set boiler water or flow temperature can be adjusted in coding addresses "FA" and "Fb" in the "Heating circuit..." group. Service

112 Function description Heating circuit control (cont.) Example using the settings in the delivered condition C B D Set boiler water or flow temperature in C A Time in h A Start of operation with standard room temperature B Set boiler water or flow temperature in accordance with the selected heating curve C Set boiler water or flow temperature in accordance with coding address "FA": 50 C + 0 % = 60 C D Duration of operation with raised set boiler water or flow temperature in accordance with coding address "Fb": 60 min Control sequence Mixer circuit The mixer mor will not be controlled within the "neutral zone" (± K). Flow temperature drops (Set value K) The mixer mor receives the signal "Mixer open". The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential.

113 Function description Heating circuit control (cont.) Flow temperature rises (Set value + K) The mixer mor receives the signal "Mixer closed". The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential. Cylinder temperature control Brief description The cylinder temperature control is a constant temperature control. This is the result of starting and spping the circulation pump for cylinder heating. The switching differential is ±.5 K. When the DHW cylinder is heated, the default set boiler water temperature is 0 K above the set DHW temperature (adjustable via coding address "60" in the "DHW" group). Functions Time program An aumatic or an individual time program may be selected for DHW heating and the DHW circulation pump. Compared with the heating circuit heatup phase, DHW heating starts 30 min earlier in aumatic mode. The individual time program enables up 4 time phases per day be set for DHW heating and the DHW circulation pump for every day of the week. All cylinder heating sequences will be completed independently of the time program. In conjunction with coding address "7F" in the "General" group Detached house Code "7F:": Aumatic mode The heating times for heating circuit are applied systems with two or three heating circuits. Individual time program The time phases for DHW heating and the DHW circulation pump have the same effect on all heating circuits. 3 Service

114 Function description Cylinder temperature control (cont.) Apartment building Code "7F:0": Aumatic mode For systems with two or three heating circuits, the heating times for the relevant heating circuit will be applied. Individual time program The time phases for DHW heating and the DHW circulation pump can be adjusted individually for each heating circuit. Priority control With priority control: (code "A:" in the "Heating circuit..." group): The set flow temperature is set 0 C during cylinder heating. The mixer closes and the heating circuit pump is switched off. Without priority control: The heating circuit control unit continues operate with the same set value. With modulating priority control in conjunction with heating circuits with mixer: The heating circuit pump remains switched on. The set flow temperature of the heating circuits will be reduced, for as long as the set boiler water temperature has not been reached during cylinder heating. The set flow temperature is determined from the following parameters: Outside temperature Differential between the set and the actual boiler water temperature Heating curve slope and level Setting of coding address "A" in the "Heating circuit..." group Frost protection The DHW cylinder will be heated 0 C if the DHW temperature sinks below 5 ºC. Auxiliary function for DHW heating This function is activated by providing a second set DHW temperature via coding address "58" in group "DHW" and activating the fourth DHW phase for DHW heating. Set DHW temperature The set DHW temperature can be adjusted between 0 and 60 C. The set value range can be extended 95 ºC via coding address "56" in the "DHW" group. The set default value of the programming unit and/or the Vitrol 300A remote control units can be assigned via coding address "66" in the "DHW" group. DHW circulation pump This delivers hot water the draw-off points at adjustable times. Four time phases can be selected at the control unit for every day. Auxiliary circuits DHW heating in conjunction with the heating circuits can be disabled or enabled by changing over the heating program (see coding address "d5" in the "Heating circuit..." group). 4

115 Function description Cylinder temperature control (cont.) System with primary sre The above functions also apply in conjunction with primary sre systems. Set the following codes: "55:3" in the "DHW" group; "4C:", "4E: " in the "General" group. System with solar control unit A third set DHW temperature can be specified via coding address "67" in the "DHW" group. The DHW cylinder is only reheated by the boiler if the temperature falls below this value. Control sequence Code "55:0" in the "DHW" group, cylinder heating The DHW cylinder goes cold (set value.5 K, adjustable via coding address "59"): The set boiler water temperature is set 0 K higher than the set DHW temperature (adjustable via coding address "60"). Pump on: Starting the circulation pump for cylinder heating subject the boiler water temperature (code "6:0"). The circulation pump starts when the boiler water temperature is 7 K higher than the DHW temperature. Immediate start of the circulation pump for cylinder heating (code "6:"). The DHW cylinder is hot (set value +.5 K): The set boiler water temperature is returned the weather-compensated set value. Pump run-on: The cylinder primary pump runs on after cylinder heating until the following criteria are met: The difference between the boiler water temperature and the DHW temperature is less than 7 K. The weather-compensated set boiler water temperature has been reached. The set DHW temperature is exceeded by 5 K. The set max. run-on time has been reached (coding address "6"). Without pump run-on (code "6:0"). Code "55:" in the "DHW" group, adaptive cylinder heating With adaptive cylinder heating, the speed of the temperature rise during DHW heating is taken in account. Service 5

116 Function description Cylinder temperature control (cont.) The DHW cylinder goes cold (set value.5 K, adjustable via coding address "59"): The set boiler water temperature is set 0 K higher than the set DHW temperature (adjustable via coding address "60"). Pump on: Starting the circulation pump for cylinder heating subject the boiler water temperature (code "6:0"): The circulation pump starts when the boiler water temperature is 7 K higher than the DHW temperature. Immediate start of the circulation pump for cylinder heating (code "6:"). The DHW cylinder is hot: The control unit checks whether the boiler will be required supply heat after the cylinder has been heated up or whether residual boiler heat should be transferred the DHW cylinder. Accordingly, the control unit determines the burner and circulation pump shutdown points prevent the set DHW temperature being substantially exceeded after the cylinder has been heated up. Code "55:" in the "DHW" group, cylinder temperature control with cylinder temperature sensors The cylinder heating will be switched ON early if a large amount of hot water is drawn off. Cylinder heating will terminate early if no hot water is drawn off. DHW cylinder goes cold: Set value.5 K, adjustable via coding address "59" or Actual DHW temperature at sensor < set DHW temperature x facr for start time (adjustment via coding address "69") The DHW cylinder is hot: Set value +.5 K and Actual DHW temperature at sensor > set DHW temperature x facr for sp time (adjustment via coding address "68") Code "55:3" in the "DHW" group, cylinder temperature control, primary sre system The DHW cylinder goes cold (set value.5 K; change via coding address "59"): The set boiler water temperature is adjusted 0 K higher than the set DHW temperature (adjustable via coding address "60"). The primary pump in the primary sre system starts. Cylinder temperature sensor enables the circulation pump for cylinder heating and is evaluated for sp conditions during the pump run-on time. Cylinder temperature sensor : 6

117 Function description Cylinder temperature control (cont.) The 3-way mixing valve opens and then regulates the defaulted set value. The circulation pump for cylinder heating cycles (short term ON and OFF) until the set flow temperature has been reached (set DHW temperature + 5 K). Then it runs constantly. If, during heating, the actual value falls below the required set temperature, the circulation pump for cylinder heating will temporarily cycle again. The DHW cylinder is hot: Cylinder temperature sensor : Actual value set value and Cylinder temperature sensor : Actual value > set value.5 K: The set boiler water temperature is returned the weather-compensated set value. The circulation pump for cylinder heating sps immediately when the 3-way mixing valve is fully opened. or The circulation pump for cylinder heating sps after expiry of the run-on time that is selected via code "6". Service 7

118 Code Calling up coding level Note The codes are displayed as plain text. Codes that have no function, due the heating system equipment level or the setting of other codes, are not displayed. Heating systems with one heating circuit without mixer and one or two heating circuits with mixer: The heating circuit without a mixer is designated "Heating circuit " and the heating circuits with a mixer as "Heating circuit " or "Heating circuit 3". If the heating circuits were given individual designations, the selected designation and "HC", "HC" or "HC3" appear instead. 4. Select coding address. 5. Select value according the following tables and confirm with OK. 6. If you want reset all codes their delivered condition: Select "Standard setting" in "Coding level ". Note This also resets codes from coding level.. Press OK and å simultaneously for approx. 4 s.. "Coding level " 3. Select group of required coding address: "General" "Boiler" "DHW" "Solar" "Heating circuit //3" "All codes std device" In this group, all coding addresses from coding level (except the coding addresses from the "Solar" group) are displayed in ascending order. 8

119 Code "General" group Coding Coding in the delivered condition Possible change System design 00: One heating circuit without mixer A (heating circuit ), without DHW heating 00: 00:0 For system schemes, see the following table. Note Only codes "00:" and "00:" can be set with type GWB. Value Description address 00:... One heating circuit without mixer A (heating circuit ) with DHW heating; aumatic recognition. 3 One heating circuit with mixer M (heating circuit ) without DHW heating 4 One heating circuit with mixer M (heating circuit ) with DHW heating 5 One heating circuit without mixer A (heating circuit ) One heating circuit with mixer M (heating circuit ) without DHW heating; aumatic recognition. 6 One heating circuit without mixer A (heating circuit ) One heating circuit with mixer M (heating circuit ) with DHW heating; aumatic recognition. 7 Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) without DHW heating 8 Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) with DHW heating 9 One heating circuit without mixer A (heating circuit ) Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) without DHW heating; aumatic recognition. 0 One heating circuit without mixer A (heating circuit ) Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) with DHW heating; aumatic recognition. Service 9

120 Code "General" group (cont.) Coding in the delivered condition Possible change Servomor runtime 40:... Runtime, servomor at plug gsa. Delivered condition defaulted by boiler coding card. 40:5 40:99 Internal circulation pump function 53: With low loss header: Boiler circuit pump only runs when there is demand if the burner is operational (with run-on time). User no. 77: LON subscriber number. 77: 77:99 Runtime adjustable from 5 99 s. 53:0 Boiler circuit pump always runs when there is demand. LON subscriber number, adjustable from 99: = boiler control unit 0-97 = Vitronic 00-H 98 = Vigate 99 = Vicom Note Each number must only be assigned once. Detached house/apartment building 7F: Detached house 7F:0 Apartment building Separate adjustment of holiday program and time program for DHW heating possible. 0

121 Code "General" group (cont.) Coding in the delivered condition Possible change General 8F:0 Operation in the standard menu and extended menu enabled. Note The respective code is only activated when you exit the service menu (see page 8). 8F: Operation in the standard menu and extended menu blocked. 8F: Operation enabled in the standard menu; blocked in the extended menu. Set flow temperature for external demand 9b:70 Set minimum boiler water temperature for external demand 70 C. 9b:0 9b:7 Set value adjustable from 0 7 C (limited by boilerspecific parameters). "Boiler" group Coding Coding in the delivered condition Possible change Burner type 0: Two-stage burner. 0:0 Single stage burner. 0: Modulating burner. Gas/oil operation 03:0 Gas operation. 03: Oil operation (irreversible). Burner curve 05:... Modulating burner: 05:0 Linear burner curve. Burner curve. Delivered condition 05: Non-linear burner curve. (P T : P max ) 00 % defaulted by boiler coding 05:99 P T in kw: Partial output at card. ⅓ of the servomor runtime P max in kw: Maximum output Service

122 Code "Boiler" group (cont.) Coding in the delivered condition Possible change Boiler water temperature maximum limit 06:87 Set 87 C. 06:0 06:7 Maximum limit adjustable from 0 7 C. Note Observe the thermostat "R" setting (see page 45). Flue gas monir F:0 With flue gas temperature sensor: Flue gas temperature is not monired for burner service display. Burner service in 00 hours :0 No service interval (hours run) selected. F: F:50 C : :00 Service interval in months 3:0 No interval for service. 3: 3:4 When the limit for the flue gas temperature is exceeded, "Service" is displayed. The number of hours run before the burner should be serviced is adjustable from h; step 00 h Interval adjustable from 4 months. Service status 4:0 No "Service" display. 4: "Service" display (the address is aumatically set and must be manually reset after a service has been carried out).

123 Code "DHW" group Coding Coding in the delivered condition Possible change DHW 67:40 For solar DHW heating: 67:0 No set value 3. Set DHW temperature 40 C. Reheating is suppressed above the selected set temperature (DHW heating by the boiler only if solar energy is not sufficient). 67:0 67:95 Enable DHW circulation pump 73:0 DHW circulation pump: 73: "ON" according time program. 73:6 Set DHW temperature adjustable from 0 95 C (limited by boilerspecific parameters). Observe the setting of coding address "56". "ON" from once per hour for 5 min up 6 times per hour for 5 min during the time program"." 73:7 Constantly "ON". "Solar" group Only in conjunction with solar control module, type SM. Coding Coding in the delivered condition Possible change Speed control solar circuit pump 0:0 Solar circuit pump (multi stage) without speed control by solar control module 0: Solar circuit pump (multi stage) is speed-controlled with wave pack control. SM. 0: Solar circuit pump is speed-controlled with PWM control. Cylinder maximum temperature 08:60 The solar circuit pump sps when the actual DHW temperature reaches the maximum cylinder temperature (60 C). 08:0 08:90 The maximum cylinder temperature is adjustable from 0 90 C. Service 3

124 Code "Solar" group (cont.) Coding in the delivered condition Possible change Stagnation time reduction 0A:5 To protect system components and heat transfer 0A:0 Stagnation time reduction is disabled. medium: the speed of the solar circuit pump is reduced if the actual DHW temperature is 5 K below the maximum cylinder temperature. 0A: 0A:40 Value for stagnation time reduction is adjustable from 40 K. Flow rate solar circuit 0F:70 The solar circuit flow rate at maximum pump speed is 7 l/min. 0F: 0F:55 Flow rate adjustable from l/min; step 0. l/min. Extended solar control functions 0:0 No extended control functions enabled. 0: Additional function for DHW heating. 0: Differential temperature control. 0:3 Differential temperature control and auxiliary function. 0:4 Differential temperature control for central heating backup. 0:5 Thermostat function. 0:6 Thermostat function and auxiliary function. 0:7 Solar heating via external heat exchanger without additional temperature sensor. 0:8 Solar heating via external heat exchanger with additional temperature sensor. 0:9 Solar heating of two DHW cylinders. 4

125 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group Coding Coding in the delivered condition Priority DHW heating A: Cylinder priority applicable heating circuit pump and mixer. Possible change A:0 Without cylinder priority applicable heating circuit pump and mixer. A: Cylinder priority applies only the mixers. A:3 A:5 Modulating priority applied mixer, i.e. the heating circuit receives a reduced amount of heat. Economy function outside temperature A5:5 With heating circuit pump logic function (economy A5:0 Without heating circuit pump logic function. mode): Heating circuit pump "OFF" when the outside temperature (AT) is K higher than the set room temperature (RT set ) AT > RT set + K A5: A5:5 With heating circuit pump logic function: Heating circuit pump "OFF"; see the following table. Parameter address With heating circuit pump logic function: Heating circuit A5:... pump "OFF" AT > RT set + 5 K AT > RT set + 4 K 3 AT > RT set + 3 K 4 AT > RT set + K 5 AT > RT set + K 6 AT > RT set 7 AT > RT set - K 5 AT > RT set - 9 K Service 5

126 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Extended economy function mixer A7:0 Only for heating circuits with mixer: Without mixer economy function. Possible change A7: With mixer economy function (extended heating circuit pump logic): Heating circuit pump also "OFF": If the mixer has been attempting close for more than 0 min. Heating circuit pump "ON": If the mixer changes control function. If there is a risk of frost. Pump idle time, transition reduced mode A9:7 With pump idle time A9:0 Without pump idle time. (heating circuit pump "OFF") (see function description on page 06). A9: A9:5 With pump idle time; adjustable from 5. : short idle time 5: long idle time Weather-compensated/room temperature hook-up b0:0 With remote control: * Heating mode/reduced mode: weather-compensated. Economy function room temperature b5:0 With remote control: * No room temperaturedependent heating circuit pump logic function. b0: Heating mode: weathercompensated Reduced mode: with room temperature hook-up b0: Heating mode: with room temperature hook-up Reduced mode: weathercompensated b0:3 Heating mode/reduced mode: with room temperature hook-up b5: b5:8 Heating circuit pump logic function, see the following table. * Only change the code for the heating circuit without mixer A for boilers without lower temperature limit or for the heating circuits with mixer if a remote control is connected them. 6

127 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Parameter With heating circuit pump logic function: address b5:... Heating circuit pump "OFF" Heating circuit pump "ON" RT actual > RT set + 5 K RT actual < RT set + 4 K RT actual > RT set + 4 K RT actual < RT set + 3 K 3 RT actual > RT set + 3 K RT actual < RT set + K 4 RT actual > RT set + K RT actual < RT set + K 5 RT actual > RT set + K RT actual < RT set 6 RT actual > RT set RT actual < RT set - K 7 RT actual > RT set - K RT actual < RT set - K 8 RT actual > RT set - K RT actual < RT set - 3 K Coding in the delivered condition Possible change Min. flow temperature heating circuit C5:0 Electronic minimum flow temperature limit 0 C (only in operation with standard room temperature). C5: C5:7 Max. flow temperature heating circuit C6:75 Electronic maximum flow C6:0 temperature limit set 75 C. C6:7 Heating program changeover d5:0 With external heating program changeover (observe setting for coding addresses "5d", "5E" and "5F" in the "General" group). Heating program switches "Constant central heating with reduced room temperature" or "Standby mode" (subject the settings of the set reduced room temperature). Minimum limit adjustable from 7 C (limited by boiler-specific parameters). Maximum limit adjustable from 0 7 C (limited by boiler-specific parameters). d5: The heating program changes "Constant operation with standard room temperature". Service 7

128 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change Ext. heating program changeover heating circuit d8:0 No heating program changeover via extension EA. d8: Heating program changeover via input DE at extension EA. d8: Heating program changeover via input DE at extension EA. d8:3 Heating program changeover via input DE3 at extension EA. Screed function F:0 Screed function disabled. Party mode time limit F:8 Time limit for party mode or external heating program changeover via pushbutn: 8 h *. Note Observe settings of coding addresses "5d", "5E", "5F" in the "General" group, as well as "d5" and "d8" in the "Heating circuit..." group. F: F:6 Only for heating circuits with mixer: Screed function adjustable in accordance with 6 optional temperature/time profiles (see page 07). F:5 Constant flow temperature 0 C (see page 07). F:0 No time limit *. F: Time limit adjustable from h *. F: * Party mode ends aumatically in the "Heating and DHW" heating program when the system changes over operation with standard room temperature. 8

129 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change Start temperature raising F8:-5 Temperature limit for raising reduced mode -5 ºC; F8:+0 see example on page 0. Observe the setting of coding address "A3". F8:-60 F8: C. Function disabled. End temperature raising F9:-4 Temperature limit for raising F9:+0 the reduced set room temperature -4 ºC, see F9:-60 example on page 0. Set flow temperature increase FA:0 Raising the set boiler water or flow temperature by 0 % when changing from operation with reduced room temperature operation with standard room temperature. See example on page. FA:0 FA:50 Duration set flow temperature increase Fb:30 Duration of the set boiler Fb:0 water or flow temperature rise (see coding address Fb:50 "FA") 60 min. See example on page. Temperature limit adjustable from Limit for raising the set room temperature the value selected for standard mode adjustable from C. Temperature rise adjustable from 0 50 %. Duration adjustable from min; step min. Service 9

130 Code Calling up coding level Note In coding level, all codes are accessible, including the codes from coding level. Codes that have no function, due the heating system equipment level or the setting of other codes, are not displayed. Heating systems with one heating circuit without mixer and one or two heating circuits with mixer: The heating circuit without mixer is designated "Heating circuit " and the heating circuits with mixer as "Heating circuit " or "Heating circuit 3". If the heating circuits were given individual designations, the selected designation and "HC", "HC" or "HC3" appear instead.. Press OK and å simultaneously for approx. 4 s.. Press OK and ä simultaneously for approx. 4 s. 4. Select group of required coding address: "General" "Boiler" "DHW" "Solar" "Heating circuit //3" "All codes std device" In this group, all coding addresses (except the coding addresses from the "Solar" group) are displayed in ascending order. 5. Select coding address. 6. Select value according the following tables and confirm with "OK". 7. If you want reset all codes their delivered condition: Select "Standard setting" in "Coding level ". Note This also resets codes from coding level. 3. "Coding level " "General" group Coding Coding in the delivered condition Possible change 00: One heating circuit without mixer A (heating circuit ), without DHW heating. 00: 00:0 For system schemes, see the following table. 30

131 Code "General" group (cont.) Coding in the delivered condition Possible change Note Only codes "00:" and "00:" can be set with type GWB. Value Description address 00:... One heating circuit without mixer A (heating circuit ) with DHW heating; aumatic recognition. 3 One heating circuit with mixer M (heating circuit ) without DHW heating 4 One heating circuit with mixer M (heating circuit ) with DHW heating 5 One heating circuit without mixer A (heating circuit ) One heating circuit with mixer M (heating circuit ) without DHW heating; aumatic recognition. 6 One heating circuit without mixer A (heating circuit ) One heating circuit with mixer M (heating circuit ) with DHW heating; aumatic recognition. 7 Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) without DHW heating 8 Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) with DHW heating 9 One heating circuit without mixer A (heating circuit ) Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) without DHW heating; aumatic recognition. 0 One heating circuit without mixer A (heating circuit ) Two heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3) with DHW heating; aumatic recognition. Service Coding in the delivered condition Possible change :5 With extension EA: : Runtime adjustable from 60 min. 3

132 Code "General" group (cont.) Coding in the delivered condition DHW circulation pump runtime for brief operation: 5 min E:0 With extension EA (analogue input 0-0 V): Temperature demand from 0 00 C: V 0 C 0 V 00 C 0:... Controller integral time for low loss header in s Delivered condition specified by the boiler coding card. The greater the integral action time, the more accurate but slower the controller. :... Controller integral time for low loss header in min. Time between burner start and controller start. Delivered condition specified by the boiler coding card. E:0 Without outside temperature sensor RF. F:0 Do not adjust 30:0 Without plug-in adapr for external safety equipment. 3:0 Without plug-in adapr for external safety equipment. 3 Possible change :60 E: Temperature demand from 30 0 C: V 30 C 0 V 0 C 0: 0:99 : :99 Controller integral time adjustable from s; step 0 s Controller integral time adjustable from 99 min E: With outside temperature sensor; aumatic recognition E: Outside temperature sensor RF is not used. 30: With plug-in adapr for external safety equipment; aumatic recognition. 3: With plug-in adapr for external safety equipment; aumatic recognition. 3:0 Without extension AM. 3: With extension AM; aumatic recognition.

133 Code "General" group (cont.) Coding in the delivered condition Possible change 33: Function output A at extension AM: Heating circuit pump, heating circuit without mixer A (heating circuit ). 34: Function output A at extension AM: Heating circuit pump, heating circuit without mixer A (heating circuit ). 40:... Runtime, servomor at 40:5 plug gsa. Delivered condition 40:99 defaulted by boiler coding card. 4A:0 Sensor aja not installed. 4b:0 Sensor ajb not installed. 4C:0 Connection at plug söa: Switching contact, heating circuit pump. 4d: Connection at plug sl: Shunt pump. 4E: Connection at plug gsa: Mor for 3-way mixing valve for return temperature control. 4F:5 Run-on time, shunt or boiler circuit pump 5 min. 33:0 DHW circulation pump. 33: Cylinder primary pump. 33:3 Circulation pump, neutralising system or flue gas/ water heat exchanger. 34:0 DHW circulation pump. 34: Cylinder primary pump. 34:3 Circulation pump, neutralising system or flue gas/ water heat exchanger. Runtime adjustable from 5 99 s. 4A: Sensor aja available (e.g. Therm-Control temperature sensor); aumatic recognition. 4b: Sensor ajb installed (e.g. temperature sensor T); aumatic recognition. 4C: Primary pump, primary sre system. 4C: Switching contact, Therm- Control. 4C:3 Circulation pump flue gas/water heat exchanger. 4d: Boiler circuit pump. 4E: Mor for 3-way mixing valve, primary sre system. 4F:0 No pump run-on. 4F: Run-on time adjustable from 60 min. 33 Service

134 Code "General" group (cont.) Coding in the delivered condition 5:0 Without flow temperature sensor for low loss header. 53: With low loss header: Boiler circuit pump only runs when there is demand if the burner is operational (with run-on time). 54:0 Without solar thermal system. 34 Possible change 4F:60 5: With flow temperature sensor for low loss header; aumatic recognition. 53:0 Boiler circuit pump always runs when there is demand. 54: With Visolic 00; aumatic recognition. 54: With Visolic 00; aumatic recognition. 54:3 With solar control module, type SM, without auxiliary function; aumatic recognition. 54:4 With solar control module, type SM, with auxiliary function, e.g. central heating backup; aumatic recognition. 5b:0 Without extension EA. 5b: With extension EA; au- 5C:0 Function output abj at extension EA: Central fault message. 5d:0 Function input DE at extension EA: No function. matic recognition. 5C: Feed pump. 5C: No function. 5C:3 Heating circuit pump A is switched low speed (reduced mode). 5C:4 Heating circuit pump M is switched low speed (reduced mode). 5C:5 Heating circuit pump M3 is switched low speed (reduced mode). 5d: Heating program changeover. 5d: External demand with set minimum boiler water temperature.

135 Code "General" group (cont.) Coding in the delivered condition 5E:0 Function input DE at extension EA: No function. 5F:0 Function input DE3 at extension EA: No function. Possible change Set value selected in coding address "9b". 5d:3 External blocking. 5d:4 External blocking with fault message. 5d:5 Fault message input. 5d:6 Brief operation, DHW circulation pump (pushbutn function). Setting of runtime for DHW circulation pump in coding address "" in the "General" group. 5E: Heating program changeover. 5E: External demand with set minimum boiler water temperature. Set value selected in coding address "9b". 5E:3 External blocking. 5E:4 External blocking with fault message. 5E:5 Fault message input. 5E:6 Brief operation, DHW circulation pump (pushbutn function). Setting of runtime for DHW circulation pump in coding address "" in the "General" group. 5F: Heating program changeover. 5F: External demand with set minimum boiler water temperature. Set value selected in coding address "9b". 5F:3 External blocking. 5F:4 External blocking with fault message. Service 35

136 Code "General" group (cont.) Coding in the delivered condition 6C:0 Run-on time for circulation pump, neutralising system at output A at extension AM: None. 6d:0 Run-on time for circulation pump, neutralising system at output A at extension AM: None. 6E:50 No display correction of the outside temperature. 76:0 Without LON communication module. Possible change 5F:5 Fault message input. 5F:6 Brief operation, DHW circulation pump (pushbutn function). Setting of runtime for DHW circulation pump in coding address "" in the "General" group. 6C: 6C:55 6d: 6d:55 6E:0 6E:49 6E:5 6E:99 77: LON subscriber number. 77: 77:99 Run-on time adjustable from 55 s. Run-on time adjustable from 55 s. Display correction 5 K Display correction 0. K Display correction +0. K Display correction +4.9 K 76: With LON communication module (aumatic recognition). LON subscriber number, adjustable from 99: = boiler control unit 0-97 = Vitronic 00-H 98 = Vigate 99 = Vicom Note Each number must only be assigned once. 78: LON communication enabled :0 LON communication disabled.

137 Code "General" group (cont.) Coding in the delivered condition 79: With LON communication module: Control unit is fault manager. 7A:0 Without central control of heating circuits. 7b: With LON communication module: Control unit transmits the time. Possible change 79:0 Control unit is not fault manager. 7A: With central control (see page 09): Heating circuit without mixer A (heating circuit ). 7A: Heating circuit with mixer M (heating circuit ). 7A:3 Heating circuit with mixer M3 (heating circuit 3). 7b:0 No time transmission. 7F: Detached house. 7F:0 Apartment building. Separate adjustment of holiday program and time program for DHW heating possible. 80:6 A fault message is displayed if a fault occurs for at least 30 s. 8: Aumatic summer/wintertime changeover. 8:3 Summer time starts: March 83:5 Summer time starts: 83: 80:0 Immediate fault message. 80: The minimum fault duration until a fault message is 80:99 issued is adjustable from s; step 5 s 8:0 Manual summer/wintertime changeover. 8: Use of the radio clock receiver (aumatic recognition). 8:3 With LON communication module: The control unit receives the time. 8: January December 8: Week week 5 of the selected month 37 Service

138 Code "General" group (cont.) Coding in the delivered condition Possible change Week 5 of the selected 83:5 month. 84:7 Summer time starts: 84: Monday Sunday Last Sunday of the selected month. 84:7 85:0 Wintertime starts: 85: January December Ocber. 85: 86:5 Wintertime starts: Week 5 of the selected month. 86: 86:5 Week week 5 of the selected month 87:7 Summer time starts: Last Sunday of the selected month. 88:0 Temperature displayed in C (Celsius). 8A:75 Do not adjust 8F:0 Operation in the standard menu and extended menu enabled. Note The respective code is only activated when you exit the service menu (see page 8). 87: 87:7 Monday Sunday 88: Temperature displayed in F (Fahrenheit). 8F: Operation in the standard menu and extended menu blocked. 8F: Operation enabled in the standard menu; blocked in the extended menu. 90:8 Time constant for calculating adjusted outside temperature.3 h. 9:0 Connection at terminals and in plug avd disabled (external heating program changeover) (see page 55). 90: 90:99 Fast (low values) or slow (high values) matching of the flow temperature, subject the set value when the outside temperature changes. step 0 min 9: Contact affects the following heating circuits: Heating circuit without mixer A (heating circuit ). 9: Heating circuit with mixer M (heating circuit ). 38

139 Code "General" group (cont.) Coding in the delivered condition 93:0 Central fault message during emissions test function/service display does not affect central fault. 95:0 Without Vicom 00 communication interface. 96: With extension for heating circuits and 3 with mixer. 97: With LON communication module: The control unit sends the outside temperature the Vitronic 00-H. 98: With LON communication module: Possible change 9:3 Heating circuits without mixer A (heating circuit ) and heating circuit with mixer M (heating circuit ). 9:4 Heating circuit with mixer M3 (heating circuit 3). 9:5 Heating circuits without mixer A (heating circuit ) and heating circuit with mixer M3 (heating circuit 3). 9:6 Heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 9:7 Heating circuit without mixer A (heating circuit ) and heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 93: Central fault message during emissions test function/ service display does affect central fault. 95: With Vicom 00 communication interface; aumatic recognition. 96:0 Without extension for heating circuits and 3 with mixer. 97:0 The outside temperature of the sensor connected the control unit is only utilised internally. 97: The control unit receives the outside temperature from the Vitronic 00-H. 98: 98:5 System number adjustable from Service

140 Code "General" group (cont.) Coding in the delivered condition Possible change Viessmann system number (in conjunction with moniring several systems via Vicom 300). 99:0 Connection at terminals 99: No function. and 3 in plug avd disabled (external blocking/ external "Mixer closed") 99: External "Mixer closed" Heating circuit with mixer M (heating circuit ). (see page 55). 99:3 No function. 99:4 External "Mixer closed" Heating circuit with mixer M3 (heating circuit 3). 99:5 No function. 99:6 External "Mixer closed" Heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 99:7 No function. 99:8 External blocking. 99:9 No function. 99:0 External blocking/external "Mixer closed" Heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 99: No function. 99: External blocking/external "Mixer closed" Heating circuit with mixer M3 (heating circuit 3). 99:3 No function. 99:4 External blocking/external "Mixer closed" Heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 99:5 No function. 9A:0 Connection at terminals 9A: No function. and in plug avd disabled (external "Mixer open") (see page 55). 9A: External "Mixer open" Heating circuit with mixer M (heating circuit ). 40

141 Code "General" group (cont.) Coding in the delivered condition 9b:70 Set minimum boiler water temperature for external demand 70 C. 9C:0 With LON communication module: Moniring LON subscribers. If there is no response from a subscriber after 0 min, the values specified inside the control unit are used. Only then will a fault message be issued. 9d:0 Do not adjust 9F:8 Differential temperature 8 K; only in conjunction with heating circuits with mixer M and M3. Possible change 9A:3 No function. 9A:4 External "Mixer open" Heating circuit with mixer M3 (heating circuit 3). 9A:5 No function. 9A:6 External "Mixer open" Heating circuits with mixer M (heating circuit ) and M3 (heating circuit 3). 9A:7 No function. 9b:0 9b:7 Set value adjustable from 0 7 C (limited by boilerspecific parameters). 9C:0 No moniring. 9C:5 9C:60 9F:0 9F:40 Time adjustable from 5 60 min. Differential temperature adjustable from 0 40 K. "Boiler" group Service Coding Coding in the delivered condition Possible change 0: Two-stage burner. 0:0 Single stage burner. 0: Modulating burner. 03:0 Gas operation 03: Oil operation (irreversible) 4

142 Code "Boiler" group (cont.) Coding in the delivered condition Delivered condition specified by the boiler coding card. 04:... Switching hysteresis, burner: Delivered condition specified by the boiler coding card. 05:... Modulating burner: Burner curve. Delivered condition specified by the boiler coding card. 06:87 Maximum limit of the boiler water temperature set 87 C. Delivered condition specified by the boiler coding card. Possible change 03: This occurs aumatically, if an incorrect boiler coding card is inserted or none is present 04:0 Switching hysteresis 4 K (see page 00) 04: Switching hysteresis, heat demand-dependent (see page 00) ERB50 function (values from 6 K). 04: ERB80 function (values from 6 0 K). 05:0 Linear burner curve. 05: Non-linear burner curve. (P T : P max ) 00 % 05:99 P T in kw: Partial output at ⅓ of the servomor runtime P max in kw: Maximum output 06:0 06:7 Maximum limit adjustable from 0 7 C. Note Observe the thermostat "R" setting (see page 45). 08:... Maximum burner output in kw. Delivered condition defaulted by boiler coding card. 09:... Maximum burner output in kw. Delivered condition defaulted by boiler coding card. 4 08:0 08:99 09:0 09:99 0A:... Burner base load in kw. 0A:0 Maximum output adjustable from 0 99 kw. Maximum output adjustable from 0 9,900 kw. step 00 kw Non-linear burner curve. (P G :P max ) 00 %

143 Code "Boiler" group (cont.) Coding in the delivered condition Possible change Delivered condition defaulted by boiler coding card. 0A:00 P G in kw: Base output P max in kw: Maximum output 0C:0 No function. 0C: Constant return temperature control. Observe coding address "4E" in the group. 0d: With Therm-Control, 0d:0 Without Therm-Control. controls the mixers of downstream heating circuits. 3:... Shutdown differential in K. 3:0 Without shutdown differential. The burner is switched off when the set boiler water temperature is exceeded. Delivered condition defaulted by boiler coding card. 3: 3:0 Shutdown differential adjustable from 0 K. 4:... Minimum burner runtime in min. Delivered condition defaulted by boiler coding card. 5:... Runtime servomor mod. burner. Delivered condition defaulted by boiler coding card. 6:... Burner offset with start optimisation in K (temporary reduction of the set boiler water temperature after burner start). Delivered condition defaulted by boiler coding card. 4:0 4:5 5:5 5:99 6:0 6:5 A:... Start optimisation in min. A:0 A:60 Minimum runtime adjustable from 0 5 min. Runtime adjustable from 5 99 s. Offset adjustable from 0 5 K. Duration of start optimisation adjustable from 0 60 min. 43 Service

144 Code "Boiler" group (cont.) Coding in the delivered condition Possible change Delivered condition defaulted by boiler coding card. b:... Time from burner ignition the start of control. Delivered condition defaulted by boiler coding card. b:0 b:99 C:0 Signal B4 at plug fa is C: not available: Compensation of signal C:99 delay for hours run meter. Time from burner start signal initiation at T in plug fa opening of the solenoid valve. At each burner start, 0 s will be taken off the runtime. d:... Function, shunt pump. Delivered condition defaulted by boiler coding card. F:0 With flue gas temperature sensor: Flue gas temperature is not monired for burner service display. :0 No service interval (hours run) selected. 44 Regulation delay adjustable from 99 s. Delay adjustable from 99 s. This time is deducted from the operating time for every burner start. E.g. operating situations in which the burner is shut down via the mechanical temperature controller, but a burner demand is still present (hours run continue be counted). If required, change coding address "06". d:0 Function according boiler coding card. d: Shunt pump always runs when the burner is active. F: F:50 C : :00 3:0 No interval for service. 3: 3:4 When the limit for the flue gas temperature is exceeded, "Service" is displayed. The number of hours run before the burner should be serviced is adjustable from 00 0,000 h; step 00 h Interval adjustable from 4 months.

145 Code "Boiler" group (cont.) Coding in the delivered condition Possible change 4:0 No "Service" display. 4: "Service" display (the address is aumatically set and must be manually reset after a service has been carried out). 6:0 Burner fuel consumption (stage ): No count if "6:0" and "7:0" are programmed. 6: 6:99 Input of ; step 0. l/h or gallons/ h Note Values of coding addresses "6" and "7" are added gether. 7:0 Burner fuel consumption (stage ): No count if "6:0" and "7:0" are programmed. 8:0 No burner interval ignition. 9:0 Burner fuel consumption (stage ); no count if "9:0" and "A:0" are programmed. A:0 Burner fuel consumption (stage ): no count if "9:0" and "A:0" are programmed. d:0 Shunt pump "ON" only in case of demand. 7: 7:99 8: 8:4 9: 9:99 A: A:99 Input of 0 990; step 0 l/h or gallons/h Time interval adjustable from 4 h. The burner is force-started for 30 s each time. Input of ; step 0. l/h or gallons/ h Note Values of coding addresses "9" and "7" are added gether. Input of 0 990; step 0 l/h or gallons/h d: Shunt pump constantly "ON". Service 45

146 Code "DHW" group Coding Coding in the delivered condition 55:0 Cylinder heating, Hysteresis ±.5 K. 56:0 Set DHW temperature adjustable from 0 60 C. Possible change 55: Adaptive cylinder heating enabled (see page 5). 55: Cylinder temperature control with cylinder temperature sensors (see page 6). 55:3 Cylinder temperature control, primary sre system (see page 6). 56: Set DHW temperature adjustable from 0 95 C. 58:0 Without auxiliary function for DHW heating. 59:0 Cylinder heating: Set start point.5 K Set sp point +.5 K 5A:0 For DHW heating: The set boiler water temperature is determined by the highest system flow temperature demand. Scan of the temperature in the "Diagnosis" menu, "General" ("Common dem. temp"), see page :0 58:60 59: 59:0 Note Observe the max. permissible DHW temperature. Adjust the temperature controller "R". Input of a second set DHW temperature, adjustable from 0 95 C (observe coding addresses "56" and "63") Start point adjustable from 0 K below set value. 5A: For DHW heating: The set boiler water temperature is determined by the DHW cylinder flow temperature demand. Scan of the temperature in the "Diagnosis" menu, "General" ("Common dem. temp"), see page 8.

147 Code "DHW" group (cont.) Coding in the delivered condition Possible change 60:0 During DHW heating, the boiler water temperature is up 0 K higher than the set DHW temperature. 60:0 60:50 The differential between the boiler water temperature and the set DHW temperature is adjustable from 0 50 K. 6: The circulation pump for cylinder heating is started immediately. 6:0 The circulation pump for cylinder heating is started depending on the boiler water temperature. 6:0 Circulation pump with a run-on time after cylinder heating of up 0 min. 6:0 Circulation pump without run-on. 64: During party mode and after external changeover constant operation with the standard room temperature: Constant DHW heating enabled and DHW circulation pump "ON". 66:4 Input of the set DHW temperature: At the control unit programming unit and all installed Vitrol 300A remote controls. 6: 6:5 Run-on time adjustable from 5 min. 64:0 No DHW heating, DHW circulation pump "OFF". 64: DHW heating and DHW circulation pump according time program. 66:0 At the control unit programming unit. 66: At the control unit programming unit and remote control heating circuit without mixer A (heating circuit ). 66: At the control unit programming unit and remote control, heating circuit with mixer M (heating circuit ). 66:3 At the control unit programming unit and remote control, heating circuit with mixer M3 (heating circuit 3). 66:5 At the remote control heating circuit without mixer A (heating circuit ). 47 Service

148 Code "DHW" group (cont.) Coding in the delivered condition 67:40 For solar DHW heating: Set DHW temperature 40 C. Reheating is suppressed above the selected set temperature (DHW heating by the boiler only if solar energy is not sufficient). 68:8 With cylinder temperature sensors (code "55:"): Cylinder heating sp point at set value x :7 With cylinder temperature sensors (code "55:"): Cylinder heating start point at set value x A:75 Runtime, servomor, mixing valve, heat exchanger set, Vitrans, (80 and 0 kw): 75 s. 70:0 DHW circulation pump "ON" according time program if DHW heating is enabled. 7:0 DHW circulation pump: "ON" according time program. 7:0 DHW circulation pump: "ON" according time program. 48 Possible change 66:6 At the remote control, heating circuit with mixer M (heating circuit ). 66:7 At the remote control, heating circuit with mixer M3 (heating circuit 3). 67:0 No set value 3. 67:0 67:95 68: 68:0 69: 69:9 6A:0 6A:55 Set DHW temperature adjustable from 0 95 C (limited by boilerspecific parameters). Observe the setting of coding address "56". Facr adjustable from 0. ; step 0. Facr adjustable from ; step 0. For heat exchanger set Vitrans (40 kw): set 3 s. Runtime adjustable from 0 55 s. 70: DHW circulation pump "ON" according time program. 7: "OFF" during DHW heating the first set value. 7: "ON" during DHW heating the first set value. 7: "OFF" during DHW heating the second set value. 7: "ON" during DHW heating the second set value.

149 Code "DHW" group (cont.) Coding in the delivered condition 73:0 DHW circulation pump: "ON" according time program. 75:0 DHW circulation pump "ON" during economy mode according time program. Possible change 73: "ON" from once per hour for 5 min up 6 times per 73:6 hour for 5 min during the time program. 73:7 Constantly "ON". 75: DHW circulation pump "OFF" during economy mode. "Solar" group Only in conjunction with solar control module, type SM. Coding Coding in the delivered condition Possible change 00:8 The solar circuit pump starts when the collecr temperature exceeds the actual DHW temperature by 8 K. 00: 00:30 The differential between the actual DHW temperature and the start point for the solar circuit pump is adjustable from 30 K. 0:4 The solar circuit pump sps when the differential between the collecr temperature and the actual DHW temperature 0: 0:9 The differential between the actual DHW temperature and the sp point of the solar circuit pump is adjustable from 9 K. is less than 4 K. 0:0 Solar circuit pump (multi stage) without speed control by solar control module 0: Solar circuit pump (multi stage) is speed-controlled with wave pack control. SM. 0: Solar circuit pump is speed-controlled with PWM control. Service 49

150 Code "Solar" group (cont.) Coding in the delivered condition 03:0 The temperature differential between the collecr temperature and actual DHW temperature is regulated 0 K. 04:4 Controller amplification of the speed control 4 %/K. 05:0 Minimum speed of the solar circuit pump 0 % of the maximum speed. 06:75 Maximum speed of the solar circuit pump 75 % of the maximum possible speed. 07:0 Interval function of the solar circuit pump switched off. 08:60 The solar circuit pump sps when the actual DHW temperature reaches the maximum cylinder temperature (60 C). 09:30 The solar circuit pump sps if the collecr temperature reaches 30 C (maximum collecr temperature protect the system components). 0A:5 To protect system components and heat transfer medium: 50 Possible change 03:5 The differential temperature control between the 03:0 collecr temperature and actual DHW temperature is adjustable from 5 0 K. 04: 04:0 05: 05:00 06: 06:00 Controller amplification adjustable from 0 %/K. Minimum speed of the solar circuit pump is adjustable from 00 %. Maximum speed of the solar circuit pump is adjustable from 00 %. 07: Interval function of the solar circuit pump switched on. To capture the collecr temperature more accurately, the solar circuit pump starts for short cycles. 08:0 08:90 09:0 09:00 The maximum cylinder temperature is adjustable from 0 90 C. The temperature is adjustable from 0 00 C. 0A:0 Stagnation time reduction is disabled. 0A: Value for stagnation time reduction is adjustable from 40 K.

151 Code "Solar" group (cont.) Coding in the delivered condition Possible change The solar circuit pump 0A:40 speed is reduced when the actual cylinder temperature is 5 K below the maximum cylinder temperature. 0b:0 Frost protection function for solar circuit switched off. 0b: Frost protection function for solar circuit switched on (not required with Viessmann heat transfer medium). 0C: Delta T moniring switched on. No flow rate captured in the solar circuit, or flow rate o low. 0C:0 Delta T moniring switched off. 0d: Night circulation moniring switched on. Unintentional flow rate is captured in the solar circuit (e.g. at night). 0E: Calculation of solar yield with Viessmann heat transfer medium. 0F:70 The solar circuit flow rate at maximum pump speed is 7 l/min. 0:0 Target temperature control switched off (see coding address ""). :50 Set solar DHW temperature 50 C. 0d:0 Night circulation moniring switched off. 0E: Calculation of solar yield with water as heat transfer medium (never adjust, as operation is only possible with Viessmann heat transfer medium). 0E:0 Calculation of solar yield switched off. 0F: 0F:55 Flow rate adjustable from l/min. step 0. l/min 0: Target temperature control switched on. :0 :90 The set solar DHW temperature is adjustable from 0 90 C. Service 5

152 Code "Solar" group (cont.) Coding in the delivered condition Possible change Target temperature control switched on (code "0:"): Temperature at which the solar heated water in the DHW cylinder is be stratified. Extended control functions set heat two DHW cylinders (code "0:8"): The second DHW cylinder is heated when one DHW cylinder reaches its set DHW temperature. :0 Minimum collecr temperature 0 C. :0 Minimum collecr temperature function disabled. The solar circuit pump will only start when the set minimum collecr temperature : :90 The minimum collecr temperature is adjustable from 90 C. is exceeded. 0:0 No extended control function enabled. 0: Additional function for DHW heating. 0: Differential temperature control. 0:3 Differential temperature control and auxiliary function. 0:4 Differential temperature control for central heating backup. 0:5 Thermostat function. 0:6 Thermostat function and auxiliary function. 0:7 Solar heating via external heat exchanger without additional temperature sensor. 5

153 Code "Solar" group (cont.) Coding in the delivered condition :8 Start temperature differential for central heating backup: 8 K. Switching output ss is switched on when the temperature at sensor / exceeds the temperature at sensor aö by the selected value. 3:4 Sp temperature differential for central heating backup: 4 K. Switching output ss is switched off when the temperature at sensor / falls below the sp point. The sp point is the sum of the temperature at sensor aö and the value selected for the sp temperature differential. 4:40 Start temperature for thermostat function 40 C. Start temperature for thermostat function sp temperature for thermostat function: Thermostat function, e.g. for reheating. Switching output ss is switched on when the temperature at sensor / falls below the start temperature for the thermostat function. Possible change 0:8 Solar heating via external heat exchanger with additional temperature sensor. 0:9 Solar heating of two DHW cylinders. : :30 3: 3:30 4:0 4:00 Start temperature differential for central heating backup is adjustable from 30 K. Sp temperature differential for central heating backup is adjustable from 9 K. Start temperature for thermostat function is adjustable from 0 00 K. 53 Service

154 Code "Solar" group (cont.) Coding in the delivered condition Possible change Start temperature for thermostat function > sp temperature for thermostat function: Thermostat function, e.g. for utilising excess heat. Switching output ss is switched on when the temperature at sensor / exceeds the start temperature for the thermostat function. 5:50 Sp temperature for thermostat function 50 C. Start temperature for thermostat function sp temperature for thermostat function: Thermostat function e.g. for reheating. Switching output ss is switched off when the temperature at sensor / exceeds the start temperature for the thermostat function. Start temperature for thermostat function > sp temperature for thermostat function: Thermostat function e.g. for utilising excess heat. Switching output ss is switched off when the temperature at sensor / falls below the start temperature for the thermostat function. 5:0 5:00 6: Priority for DHW cylinder with alternate heating. 54 Sp temperature for thermostat function is adjustable from 0 00 K. 6:0 Priority for DHW cylinder without alternate heating.

155 Code "Solar" group (cont.) Coding in the delivered condition Only when setting code "0:8". 7:5 Alternate heating time 5 min. The DHW cylinder without priority is heated at most for the duration of the set alternate heating time if the DHW cylinder with priority is heated up. 8:3 Alternate pause time 3 min. After the selected alternate heating time for the DHW cylinder without priority has expired, the rise in collecr temperature is captured during the alternate pause time. Possible change 6: Priority for DHW cylinder without alternate heating. 6:3 Priority for DHW cylinder with alternate heating. 6:4 Alternate heating without priority for one of the DHW cylinders. 7:5 The alternate heating time is adjustable from 5 7:60 60 min. 8: 8:60 The alternate pause duration is adjustable from 60 min. "Heating circuit ", "Heating circuit ", "Heating circuit 3" group Coding Service Coding in the delivered condition Possible change A0:0 Without remote control. A0: With Vitrol 00A or Vitrol 00RF; aumatic recognition. A0: With Vitrol 300A or Vihome 300; aumatic recognition. 55

156 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change A:0 Only with Vitrol 00A or Vitrol 00RF: All possible settings at the remote control can be accessed. A: Cylinder priority applicable heating circuit pump and mixer. A3: Outside temperature below C: Heating circuit pump "ON". Outside temperature above 3 C: Heating circuit pump "OFF". A: Only party mode can be set at the remote control. A:0 Without cylinder priority applicable heating circuit pump and mixer. A: Cylinder priority applies only the mixers. A:3 A:5 A3:-9 A3:5 Modulating priority applied mixer, i.e. the heating circuit receives a reduced amount of heat. Heating circuit pump "ON/ OFF" (see the following table).! Please note If a value below C is selected, there is a risk that pipes outside the thermal envelope of the building could freeze up. The standby mode in particular should be taken in consideration, e.g. during holidays. Parameters Heating circuit pump Address A3:... "ON" "OFF" -9-0 C -8 C -8-9 C -7 C -7-8 C -6 C -6-7 C -5 C -5-6 C -4 C -4-5 C -3 C -3-4 C - C - -3 C - C - - C 0 C 0 - C C 0 C C 56

157 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Parameters Heating circuit pump Address A3:... "ON" "OFF" C 3 C 5 4 C 6 C Coding in the delivered condition Possible change A4:0 With frost protection. A4: No frost protection; this setting is only possible if code "A3:-9" has been selected. Please note! Observe information regarding coding address "A3". A5:5 With heating circuit pump logic function (economy mode): Heating circuit pump "OFF" when the outside temperature (AT) is K higher than the set room temperature (RT set ) AT > RT set + K. A5:0 Without heating circuit pump logic function. A5: With heating circuit pump logic function: A5:5 Heating circuit pump "OFF"; see the following table. Parameter address With heating circuit pump logic function: Heating circuit A5:... pump "OFF" AT > RT set + 5 K AT > RT set + 4 K 3 AT > RT set + 3 K 4 AT > RT set + K 5 AT > RT set + K Service 6 AT > RT set 7 AT > RT set - K 5 AT > RT set - 9 K 57

158 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition A6:36 Extended economy control disabled. A7:0 Only for heating circuits with mixer: Without mixer economy function. A9:7 With pump idle time (heating circuit pump "OFF") (see function description on page 06). AA: With output reduction by temperature sensor aja. b0:0 With remote control: * Heating mode/reduced mode: weather-compensated. 58 Possible change A6:5 Extended economy mode enabled, i.e. the burner and A6:35 heating circuit pump will be spped and the mixer closed at a variable value, adjustable between 5 and 35 C plus C. The base value is the adjusted outside temperature. This value is based on the actual outside temperature and a time constant that takes the cooling down of an average building in consideration. A7: With mixer economy function (extended heating circuit pump logic): Heating circuit pump also "OFF": If the mixer has been attempting close for more than min. Heating circuit pump "ON": If the mixer changes control function. If there is a risk of frost. A9:0 Without pump idle time. A9: A9:5 With pump idle time; adjustable from 5. : short idle time 5: long idle time Without output reduction. No function. AA:0 AA: b0: Heating mode: weathercompensated Reduced mode: with room temperature hook-up * Only change the code for the heating circuit without mixer A for boilers without lower temperature limit or for the heating circuits with mixer if a remote control is connected them.

159 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition b:8 With remote control and for the heating circuit, operation with room temperature hook-up must be programmed: * Room influence facr 8. b5:0 With remote control: * No room temperaturedependent heating circuit pump logic function. Possible change b0: Heating mode: with room temperature hook-up Reduced mode: weathercompensated b0:3 Heating mode/reduced mode: with room temperature hook-up b:0 Without room influence. b: b:64 b5: b5:8 Room influence facr adjustable from 64. Heating circuit pump logic function, see the following table. Parameter With heating circuit pump logic function: address b5:... Heating circuit pump "OFF" Heating circuit pump "ON" RT actual > RT set + 5 K RT actual < RT set + 4 K RT actual > RT set + 4 K RT actual < RT set + 3 K 3 RT actual > RT set + 3 K RT actual < RT set + K 4 RT actual > RT set + K RT actual < RT set + K 5 RT actual > RT set + K RT actual < RT set 6 RT actual > RT set RT actual < RT set - K 7 RT actual > RT set - K RT actual < RT set - K 8 RT actual > RT set - K RT actual < RT set - 3 K Coding in the delivered condition Possible change b6:0 With remote control: * b6: With quick heat-up/quick setback (see function description on page 05). Service * Only change the code for the heating circuit without mixer A for boilers without lower temperature limit or for the heating circuits with mixer if a remote control is connected them. 59

160 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change Without quick heat-up/ quick setback. b7:0 With remote control and for the heating circuit, operation with room temperature hook-up must be programmed: * Without start optimisation. b8:0 With remote control and b8: for the heating circuit, operation with room temperature b8:55 hook-up must be programmed: * Heat-up gradient, start optimisation 0 min/k. b9:0 With remote control and for the heating circuit, operation with room temperature hook-up must be programmed: * Without learning start optimisation. C0:0 With remote control: * Without sp optimisation. C:0 With remote control: * Without sp optimisation. C:0 With remote control: * Without learning sp optimisation. C3:5 Only for heating circuits with mixer: b7: With start optimisation, max. heat-up time offset h 30 min. b7: With start optimisation, max. heat-up time offset 5 h 50 min. Heat-up gradient, adjustable from 55 min/k. b9: With learning start optimisation. C0: With sp optimisation, max. setback time offset h. C0: With sp optimisation, max. setback time offset h. C: C: With sp optimisation of setback time offset, adjustable from 0 0 min; step 0 min C: With learning sp optimisation. C3:0 Runtime adjustable from 0 55 s. * Only change the code for the heating circuit without mixer A for boilers without lower temperature limit or for the heating circuits with mixer if a remote control is connected them. 60

161 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change Mixer runtime 5 s. C3:55 C4: System dynamics: Mixer control characteristics C4:0 C4:3 Controller responds o quickly (cycles between "Open" and "Close"): select a lower value. Controller responds o slowly (temperature is not held sufficiently): select a higher value. C5:0 Electronic minimum flow temperature limit 0 C (only in operation with standard room temperature). C6:75 Electronic maximum flow temperature limit set 75 C. C8:3 With remote control and for the heating circuit, operation with room temperature hook-up must be programmed: * No room influence limit. d5:0 With external heating program changeover (observe setting of coding address "5d", "5E", "5F" and "9" in the "General" group): Heating program switches "Constant central heating with reduced room temperature" or "Standby mode" (subject the settings of the set reduced room temperature). C5: C5:7 C6:0 C6:7 C8: C8:30 Minimum limit adjustable from 7 C (limited by boiler-specific parameters). Maximum limit adjustable from 0 7 C (limited by boiler-specific parameters). Room influence limit adjustable from 30 K. d5: The heating program changes "Constant operation with standard room temperature". Service * Only change the code for the heating circuit without mixer A for boilers without lower temperature limit or for the heating circuits with mixer if a remote control is connected them. 6

162 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Possible change d8:0 No heating program changeover via extension EA. d8: Heating program changeover via input DE at extension EA. d8: Heating program changeover via input DE at extension EA. d8:3 Heating program changeover via input DE3 at extension EA. E: With remote control Vitrol 00 and 300: E:0 Set day temperature adjustable from 3 3 ºC. Set day temperature adjustable at the remote control unit from 0 30 ºC. E: Set day temperature adjustable from 7 37 ºC. E:50 With remote control: No display correction of the actual room temperature. F:0 Screed function disabled. F:8 Time limit for party mode or external heating program changeover via pushbutn: 8 h *. E:0 E:49 E:5 E:99 F: F:6 Display correction 5 K Display correction 0. K Display correction +0. K Display correction +4.9 K Only for heating circuits with mixer: Screed function adjustable in accordance with 6 optional temperature/time profiles (see page 07). F:5 Constant flow temperature 0 C (see page 07). F:0 No time limit *. F: Time limit adjustable from h *. * Party mode ends aumatically in the "Heating and DHW" heating program when the system changes over operation with standard room temperature. 6

163 Code "Heating circuit ", "Heating circuit ", "Heating circuit 3" group (cont.) Coding in the delivered condition Note Observe settings of coding addresses "5d", "5E", "5F" in the "General" group, as well as "d5" and "d8" in the "Heating circuit..." group. Possible change F: F8:-5 F9:-4 FA:0 Fb:60 Temperature limit for raising reduced mode -5 ºC; see example on page 0. Observe the setting of coding address "A3". Temperature limit for raising the reduced set room temperature -4 ºC, see example on page 0. Raising the set boiler water or flow temperature by 0 % when changing from operation with reduced room temperature operation with standard room temperature; see example on page. Duration of the set boiler water or flow temperature rise (see coding address "FA") 60 min. See example on page. F8:+0 F8:-60 F8:-6 F9:+0 F9:-60 FA:0 FA:50 Fb:0 Fb:50 Temperature limit adjustable from C. Function disabled. Limit for raising the set room temperature the value selected for standard mode adjustable from C. Temperature rise adjustable from 0 50 %. Duration adjustable from min; step min. Service 63

164 Designs Connection and wiring diagram, type GWB Overview 64

165 Designs Connection and wiring diagram, type GWB (cont.) A A3 A6 A7 A8 PCB, low voltage PCB 30 V Programming unit Oplink PCB/emissions test switch PCB A9 Boiler coding card A0 LON communication module (accessory) A Power supply unit PCB A Programming unit ON/OFF switch X Electrical interfaces Service 65

166 Designs Connection and wiring diagram, type GWB (cont.) PCB 30 V 66

167 Designs Connection and wiring diagram, type GWB (cont.) sö sa sk sl fö fa gö gs Heating circuit pump or Primary pump, primary sre system or Circulation pump, flue gas/ water heat exchanger or Switching output Circulation pump for cylinder heating (accessory) DHW circulation pump (on site) Shunt pump or boiler circuit pump (on site) Power supply, 30 V/50 Hz Oil/gas burners Output for multiple fault messages Mor for 3-way mixing valve, return temperature control or Mor for 3-way mixing valve, primary sre system lö Burner stage /modulating abö External connections (remove jumper when connecting) a External safety equipment b External blocking aba Safety chain (potential-free) abh Power supply for accessories F, F Fuse F6 High limit safety cut-out 0 C (00 C) F7 Temperature controller 95 C (00 C, 0 C) K-K0 Relay S ON/OFF switch S TEST key X Electrical interfaces Service 67

168 Designs Connection and wiring diagram, type GWB (cont.) PCB, low voltage! Outside temperature sensor/radio clock receiver Boiler temperature sensor %A Cylinder temperature sensor %B Cylinder temperature sensor for primary sre system aja Therm-Control temperature sensor or Return temperature sensor T 68

169 Designs Connection and wiring diagram, type GWB (cont.) ajb Return temperature sensor T or Temperature sensor primary sre system ag Flue gas temperature sensor ) Flow temperature sensor, low loss header avd External hook-up avg KM BUS subscriber avh External hook-up LON Cable for data exchange between control units (accessories) S3 Emissions test switch V Fault indicar (red) V ON indicar (green) X Electrical interfaces Service 69

170 Designs Connection and wiring diagram, type GWB Overview 70

171 Designs Connection and wiring diagram, type GWB (cont.) A A A3 A6 A7 PCB, extension for heating circuits and 3 with mixer PCB, low voltage PCB 30 V Programming unit Oplink PCB/emissions test switch A8 PCB A9 Boiler coding card A0 LON communication module (accessory) A Power supply unit PCB A Programming unit ON/OFF switch X Electrical interfaces Service 7

172 Designs Connection and wiring diagram, type GWB (cont.) PCB 30 V 7

173 Designs Connection and wiring diagram, type GWB (cont.) sö sa sk sl fö fa gö gs Heating circuit pump or Primary pump, primary sre system or Circulation pump, flue gas/ water heat exchanger or Switching output Circulation pump for cylinder heating (accessory) DHW circulation pump (on site) Shunt pump or boiler circuit pump (on site) Power supply, 30 V/50 Hz Oil/gas burners Output for multiple fault messages Mor for 3-way mixing valve, return temperature control or Mor for 3-way mixing valve, primary sre system lö Burner stage /modulating abö External connections (remove jumper when connecting) a External safety equipment b External blocking aba Safety chain (potential-free) abh Power supply for accessories F, F Fuse F6 High limit safety cut-out 0 C (00 C) F7 Temperature controller 95 C (00 C, 0 C) K-K0 Relay S ON/OFF switch S TEST key X Electrical interfaces Service 73

174 Designs Connection and wiring diagram, type GWB (cont.) PCB, low voltage 74

175 Designs Connection and wiring diagram, type GWB (cont.)! Outside temperature sensor/radio clock receiver Boiler temperature sensor %A Cylinder temperature sensor %B Cylinder temperature sensor for primary sre system aja Therm-Control temperature sensor or Return temperature sensor T ajb Return temperature sensor T or Temperature sensor primary sre system ag Flue gas temperature sensor ) Flow temperature sensor, low loss header avd External hook-up avg KM BUS subscriber avh External hook-up LON Cable for data exchange between control units (accessories) S3 Emissions test switch V Fault indicar (red) V ON indicar (green) X Electrical interfaces PCB, extension for heating circuits and 3 with mixer Service 75

176 Designs Connection and wiring diagram, type GWB (cont.)? Flow temperature sensors sö Heating circuit pumps fö Power supply gs Mixer mors K-K6 Relay X Electrical interfaces 76

177 Components Boiler coding card Boiler Boiler coding card Service menu display "Diagnosis" category"general" Identification Spare part no. Vicrossal 300, type CT Vicrossal 00, type CM Vicrossal 300, type CR3, CR3B Vicrossal 300, type CM Vicrossal 00, type CT Vimax 300-LT Viplex 00, type SXA Viplex 300, type TX3A Viradial 300-T Virond 00, type VD, VDA Sensors Boiler water, cylinder, flow, return (Therm-Control sensor) and room temperature sensor Note The flow temperature sensor can be used as a contact or immersion temperature sensor. Note The flow temperature sensor in the mixer extension kit is a contact temperature sensor. Service The room temperature sensor is connected terminals 3 and 4 in the Vitrol 300A. Installation and service instructions for Vitrol 300A 77

178 Components Sensors (cont.) Viessmann NTC 0 kω (blue marking) Resistance in kω Temperature in C. Pull corresponding plug.. Check the sensor resistance and compare it with the curve. 3. In the case of severe deviation, check the installation and replace the sensor if required. Outside temperature sensor Viessmann NTC 0 kω Resistance in kω Temperature in C. Pull plug!.. Check the sensor resistance across plug terminals "" and "" and compare with the curve. 3. If the results are very different from the curve, disconnect the wires from the sensor and repeat the test on the sensor. 4. Depending on the result, replace the lead or the outside temperature sensor. Flue gas temperature sensor, part no When an entered limit is reached (see coding address "F" in the "Boiler") group, a service display appears. 78

179 Components Sensors (cont.) Viessmann NTC 0 kω (orange identification) Resistance in kω Temperature in C. Disconnect plug ag.. Check the sensor resistance and compare it with the curve. 3. In the case of severe deviation, check the installation and replace the sensor if required. Plug-in adapr for ext. safety equipment, part no Connecting one plug-in adapr The plug-in adapr is aumatically recognised by the control unit as a KM BUS subscriber. The following external safety equipment can be connected EN 88: Low water indicar Maximum pressure limiter Minimum pressure limiter Additional high limit safety cut-out Controlled external burner shutdown External burner demand (stage ) Service 79

180 Components Plug-in adapr for ext. safety equipment, part (cont.) B B B B D D D C 50 E X7 Ein TR Ein TR 50 E X3 Ein TR Ein TR 50 E X Ein TR Ein TR X8 50 F X Ein TR Ein TR STB STB STB STB N N N N X6 STB X4 STB X5 STB STB H G A A Connection area B External safety equipment X Additional high limit safety cuut or Temperature limiter X Minimum or maximum pressure limiter X3 Maximum pressure limiter X7 Low water indicar or Plug abö of a second plug adapter Observe the order of the connections shown in the diagram. Remove the jumper in plug abö when connecting the external safety equipment. 80 C External burner start (stage ) D Controlled external shutdown E Plug abö F Plug abö of the control unit G Connection for cable with plug abö the control unit H To the control panel or the message facility Note A plug must be inserted in every socket "X", "X", "X3" and "X7" abö.

181 Plug-in adapr for ext. safety equipment, part (cont.) Connecting two plug-in adaprs Components Separate installation instructions Make the connections in plug-in adapr as described in the previous chapter. In plug-in adapr, the connections can be made in any order. Rotary selecr setting The rotary selecr is located in the upper part of the plug-in adapr. Delivered condition: Setting Plug-in adapr : Setting Plug-in adapr : Setting Radio clock receiver, part no The radio clock receiver sets the time at the control unit and any remote control that may be connected, fully aumatically. A B E 3 C D Service A Outside temperature sensor B Radio clock receiver C Green LED D Red LED E Aerial 8

182 Components Radio clock receiver, part no (cont.) Connection -core lead, length max. 35 m with a cross-section of.5 mm. Check reception During reception, the green LED on the radio clock receiver flashes. If the red LED flashes, rotate the aerial until reception is confirmed by the flashing of the green LED. Specification IP rating IP 43 Permissible ambient temperature during operation, 40 + srage and transport 70 C Extension kit, mixer, part no Components: Mixer mor, with 4.0 m connecting cable (not for flanged mixer) Plug for connecting the heating circuit pump Flow temperature sensor as contact temperature sensor for capturing the flow temperature, with 5.8 m long lead. 8

183 Components Extension kit, mixer, part no (cont.) Changing the rotational direction (if required). Pull 3-PIN plug A from the mixer mor and reinsert turned through 80.. Check the rotational direction. A Mixer "Open" Mixer "Closed" Manual mixer adjustment Lift the mor lever, unhook the mixer handle and pull plug A. Specification for the mixer mor Rated voltage 30 V~ Rated frequency 50 Hz Power consumption 4 W Safety category II IP rating Permissible ambient temperature during operation C during srage and transport C IP 4 EN 60 59; ensure through design/installation Service 83

184 Components Mixer mor, part no For heating mixer DN 40 and 50. Y Y N 5? N AUTO M ~ MAN A Mixer mor B Coupling switch Changing the rotational direction Interchange cores at terminals "Y" and "Y". Checking the rotational direction The mixer is moved "Open" and "Closed" using the control unit relay test. Mixer open Mixer closed Specification Rated voltage 30 V Rated frequency 50 Hz Power consumption 3 W IP rating IP 4 Torque 5 Nm Runtime for s Manual mixer adjustment Coupling switch B set "MAN". 84

185 Components Mixer mor, part no. Z For heating mixer DN 65 and 00. Y Y N 00% 0% M ~ 5? N AUTO A Mixer mor B Coupling switch MAN Mixer open Mixer closed Changing the rotational direction Interchange cores at terminals "Y" and "Y". Checking the rotational direction The mixer is moved "Open" and "Closed" using the control unit relay test. Manual mixer adjustment Coupling switch B set "MAN". Specification Rated voltage 30 V Rated frequency 50 Hz Power consumption 4 W IP rating IP 4 Torque Nm Runtime for 90 5 s Service 85

186 Components Temperature limiter for limiting the maximum temperature Immersion thermostat, part no Contact thermostat, part no C L? N L? N Electromechanical temperature limiter according the liquid expansion principle. Switches the heating circuit pump off when the set value has been exceeded. In such cases, the flow temperature reduces only slowly, i.e. it may be several hours before the system restarts again aumatically. B Specification Setting range C Screw terminals for.5 mm Terminals Switching differential Immersion thermostat max. K Contact thermostat max. 4 K A M ~ A Heating circuit pump B Control thermostat (temperature limiter) C Plug sö of the thermostat (temperature limiter) the control unit 86

187 Components Extension EA, part no DE Digital input DE Digital input DE3 Digital input V 0-0 V input fö Power supply fö A abj avg Power supply for additional accessories Switching contact (floating) KM BUS Service Digital data inputs DE DE3 Functions: External heating mode changeover, separate for heating circuits 3 External blocking External blocking with fault message input External demand with minimum boiler water temperature 87

188 Components Extension EA, part no (cont.) Fault message input Brief operation of the DHW circulation pump When connecting external contacts, observe the requirements of safety category II, i.e. 8.0 mm air-gap and creep path or maintain a.0 mm insulation thickness against 'live' parts. Input function assignment Select the input functions by means of the following codes in the "General" group at the boiler control unit: DE: Coding address "5d" DE: Coding address "5E" DE3: Coding address "5F" Assigning the heating program changeover function the heating circuits The effect of the heating program changeover is selected via coding address "d5" in the "Heating circuit..." group. Duration of the changeover Contact permanently closed: The changeover is enabled as long as the contact is closed. Contact only closed briefly via pushbutn: The changeover is enabled for the time selected in coding address "F" in the "Heating circuit..." group. DHW circulation pump runtime for brief operation The runtime is adjusted via coding address "" in the "General" group. The allocation of the heating program changeover the relevant heating circuit is selected via coding address "d8" in the "Heating circuit..." group: Code "d8:": Changeover via input DE Code "d8:": Changeover via input DE Code "d8:3": Changeover via input DE3 Analogue input 0-0 V The 0-0 V hook-up provides an additional set boiler water temperature: 0 - V is taken as "no default for set boiler water temperature". Note Ensure DC separation between the negative pole and the earth conducr of the on-site voltage source. 88

189 Components Extension EA, part no (cont.) Coding address "E" in the "General" group: "E:0" temperature demand adjustable in the range from 0 00 C V 0 C set value modification 0 V 00 C set value modification "E:" temperature demand adjustable in the range from 30 0 C V 30 C set value modification 0 V 0 C set value modification Output abj Connection of a central fault message facility or signalling reduced mode (reduction of the heating circuit pump speed). Select the function of output abj via coding address "5C" in the "General" group. Secondary air device Viair, part no , A To the burner B To the control unit Service 89

190 Components Secondary air device Viair, part no (cont.) Colour coding DIN IEC BK black GN/YE green/yellow Function check Emergency mode Press the rotary selecr on the mor and turn clockwise the limit, i.e. beyond position "3". Press the rotary selecr at the mor and simultaneously turn it its central position. Enable burner from the control unit The rotary selecr should turn wards "3". Burner OFF The rotary selecr should turn wards "5". 90

191 Parts lists Parts list, type GWB Ordering parts The following information is required: Serial no. (see type plate A) Position number of the part (from this parts list) Standard parts are available from your local supplier. Parts 000 Hinge 0004 Temperature controller rotary selecr 0006 Temperature controller sp dial 0008 Supporting stay 00 Safety valve with wiring 003 Casing front with frame 004 PCB cover 005 Front flap 006 Rear section of enclosure 008 Programming unit 009 Fascia, left 000 Fascia, right 00 Ribbon cable, 4-pole 003 Connecting cable, emissions test switch 004 Fuse holder cap for control fuse 005 Fuse holder for control fuse 0030 High limit safety cut-out 003 Temperature controller 0037 Emissions test switch, single-pole 0038 ON/OFF switch, -pole 0039 "TEST" key, single-pole 0040 Outside temperature sensor! 004 Temperature sensor with plug 0045 Contact temperature sensor with plug (flow temperature sensor) 0049 PCB, low voltage 0050 PCB 005 PCBs, Oplink and emissions test switch 005 PCB 30 V~ 0054 Power supply unit PCB 0056 LON communication module 0057 LON cable 0058 Terminar ( pce) 0065 Burner connecting cable with plug fa (for boilers with pressure-jet oil/gas burners) and burner connecting cable with plug lö 0066 Burner connecting cable with plug fa and burner connecting cable with plug lö for Vicrossal 0074 Connection line 0080 Installation and service instructions 008 Operating instructions 009 Fuse 6.3 A (slow)/50 V 000 Plug for LV (7 pce) 00 Plug for pumps (3 pce) 00 Plug gs (3 pce) 003 Plug abh (3 pce) 004 Power supply plug fö (3 pce) 005 Plug abö 006 Plug gö (3 pce) 008 Plugs avd, avg, avh (3-pole) 009 Burner plugs fa, lö, aba and a:a Service 9

192 Parts lists Parts list, type GWB (cont.) A

193 Parts lists Parts list, type GWB Ordering parts The following information is required: Serial no. (see type plate A) Position number of the part (from this parts list) Standard parts are available from your local supplier. Parts 000 Hinge 0004 Temperature controller rotary selecr 0006 Temperature controller sp dial 0008 Supporting stay 00 Safety valve with wiring 003 Casing front with frame 004 PCB cover 005 Front flap 006 Rear section of enclosure 008 Programming unit 009 Fascia, left 000 Fascia, right 00 Ribbon cable, 4-pole 00 Connecting cable for extension for heatings circuit and 3 with mixer 003 Connecting cable, emissions test switch 004 Fuse holder cap for control fuse 005 Fuse holder for control fuse 0030 High limit safety cut-out 003 Temperature controller 0037 Emissions test switch, single-pole 0038 ON/OFF switch, -pole 0039 "TEST" key, single-pole 0040 Outside temperature sensor! 004 Temperature sensor with plug 0045 Contact temperature sensor with plug (flow temperature sensor) 0048 PCB, extension heating circuits and 3 with cover 0049 PCB, low voltage 0050 PCB 005 PCBs, Oplink and emissions test switch 005 PCB 30 V~ 0054 Power supply unit PCB 0056 LON communication module 0057 LON cable 0058 Terminar ( pce) 0065 Burner connecting cable with plug fa (for boilers with pressure-jet oil/gas burners) and burner connecting cable with plug lö 0066 Burner connecting cable with plug fa and burner connecting cable with plug lö for Vicrossal 0074 Connection line 0080 Installation and service instructions 008 Operating instructions 009 Fuse 6.3 A (slow)/50 V 000 Plug for LV (7 pce) 00 Plug for pumps (3 pce) 00 Plug gs (3 pce) 003 Plug abh (3 pce) 004 Power supply plug fö (3 pce) 005 Plug abö 006 Plug gö (3 pce) 008 Plugs avd, avg, avh (3-pole) 009 Burner plugs fa, lö, aba and a:a Service 93

194 Parts lists Parts list, type GWB (cont.) A

195 Specification Specification Rated voltage Rated frequency Rated current Power consumption Safety category IP rating 30 V 50 Hz x 6 A 0 W I IP 0 D EN 6059, ensure through design/installation Function Type B EN Permiss. ambient temperature during operation C Installation in living spaces or boiler rooms (standard ambient conditions) during srage and transport C Rated relay output breaking capacity at 30 V sö Heating circuit pump or Primary pump, primary sre system or Circulation pump, flue gas/water heat exchanger or Switching output 4 () A *3 sa Circulation pump for cylinder heating 4 () A *3 sk DHW circulation pump 4 () A *3 sl Shunt pump/boiler circuit pump 4 () A *3 gö Central fault message 4 () A *3 gs Mor, 3-way mixing valve, return temperature control or Mor, 3-way mixing valve, primary sre system 0. (0.) A *3 or Mixer mor, extension kit, mixer fa Burner 6 (3) A lö Burner (two-stage) (0.5) A lö Burner (modulating) 0. (0.) A Service *3 Total max. 6 A 95

196 Keyword index Keyword index...4 A AC burner...60 Acknowledging a fault display...86 Actuars, checking...73 Adaptive cylinder heating...5 Adjusting the temperature controller..45 Apartment building...4 Aumatic mode...3 Auxiliary function for DHW heating..4 B Boiler coding card...44, 77 Boiler water temperature control...99 Boiler water temperature sensor47, 77 Brief scans...8 Buffer temperature sensor...47, 77 Burner Base load...4 Connecting...60 Maximum output...4 Minimum runtime...43 Offset...43 Shutdown differential...43 Switching hysteresis...00 Burner curve... Burner fuel consumption...45 C Calling up a fault message...86 Calling up the service menu...8 Central control...09 Central fault message...39 Central fault message facility...5 Changing the language...7 Checking sensors...75 Code Calling up...8 Coding addresses...9 Code Calling up...30 Coding addresses...30 Coding addresses, matching...7 Commissioning...7 Components...77 Connecting mixing valve...50 Connecting servomors...50 Connecting the external safety equipment...58 Connection and wiring diagram Type GWB...64 Type GWB...70 Controlled external shutdown...80 Control unit Assembling...69 Opening...70 Cylinder priority control...06, 4, 5, 56 Cylinder temperature control...3 Cylinder temperature sensor...47, 77 D Date, setting...7 Detached house...3 DHW circulation pump...4 DHW heating...3, 4 DHW temperature...06 Differential temperature...0 E Economy mode...06 Electrical connections, overview...40 Emergency mode...90 Ending the service...8 ERB50 function...00 ERB80 function...00 Extended economy mode...06 Extension EA...87 Extension for heating circuits and 3 4 Extension kit, mixer...8 External blocking...53 External changeover of multi stage/modulating burners

197 Keyword index Keyword index (cont.) External demand Via 0 0 V input...5 Via switching contact...5 External heating program changeover56 External mixer close...55 External mixer open...55 F Fault codes...86 Fault display...86 Fault hisry...86 Fault manager...79 Fault memory...86 Flow temperature control...0 Flow temperature sensor...77 Flue gas temperature sensor...47, 78 Frost protection...09 Fuel consumption...45 H Heating circuit, PCB...4 Heating circuit control...04 Heating circuit pump logic...06 Heating circuit pump logic function..06 Heating curve...75, 05 Heating curve level...77 Heating curve slope...77 Heating program changeover...56 Heat-up time reduction... High limit safety cut-out Additional...80 Changing...44 Testing...7 L LON...78 Fault moniring...79 Setting subscriber numbers...79 LON communication module...78 LON subscriber check...79 Low water indicar...59, 80 M Main PCB 30V~...4 LV...4 Maximum pressure limiter...80 Minimum pressure limiter...59, 80 Mixer economy function...06 Mixer mor 84, 85 Connecting...50 Mixer mor, rotational direction84, 85 Modulating burner...56 Modulating burner, matching the control unit...7 Multi stage burner...56 O Outside temperature...05 Outside temperature sensor...47, 78 P Parts list Type GWB...9 Type GWB...93 PCB, mixer extension...4 PCBs...4, 4 Type GWB...64 Type GWB...70 Plug abö...80 Plug-in adapr for external safety equipment...79 Power cable...67 Power supply...67 Primary sre system...33, 5, 6 Priority control...06, 4 Provisional burner operation...60 Pumps Connecting...48 Run-on...5 Q Quick heat-up...05 Quick setback

198 Keyword index Keyword index (cont.) R Radio clock receiver...8 Raising the reduced room temperature...0 Reduced room temperature, raising 0 Reduced set room temperature...77 Relay test...73 Removing a fault display...86 Resetting codes...8, 30 Return temperature control...43 Room temperature...05 Room temperature sensor...77 S Screed drying...07 Screed drying function...07 Secondary air device Viair...89 Selecting the set room temperature...76 Sensors...47 Service display Resetting...84 Scanning...84 Service level Calling up...8 Exiting...8 Servomor, mixing valve, heat exchanger set...48 Servomor mod. burner...43 Set DHW temperature...4 Solar control module...5 Solar control unit...5 Specification...95 Standard set room temperature...77 Start optimisation...43, 60 Sp optimisation...60 Strain relief...43 Switching hysteresis Heat demand-dependent...00 Permanent...00 System dynamics...09 System dynamics, mixer...6 System schemes...8 T Temperature limiter...86 Therm-Control...0, 09, 43 Three-phase burner Safety chain, potential-free...64 Safety chain not potential-free...66 Time, setting...7 Time program Central heating...05 DHW heating...3 Two-stage burner, matching the control unit...7 V Viair...89 Vicom Visolic...5 Vitronic 00-H...79 W Wiring diagram Type GWB...64 Type GWB

199 99

200 Printed on environmentally friendly, chlorine-free bleached paper Applicability Serial No.: Viessmann Werke GmbH&Co KG D-3507 Allendorf Telephone: Fax: Viessmann Limited Hornwood 30, Telford Shropshire, TF 7YP, GB Telephone: Fax: Subject technical modifications.

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference.

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracr Vitronic 300 Type GW2B Weather-compensated, digital boiler control units For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 300

More information

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors Installation and service instructions for contracrs VIESMANN Vitronic 00 Type KOB, KOB Weather-compensated, digital boiler control unit For applicability, see the last page VITOTRONIC 00 /0 Please keep

More information

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracrs Vitronic 100 Type GC1B Digital boiler control unit For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 100 Product may not be exactly

More information

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no Installation and service instructions for contractors VIESMANN Vitotrol 300A Remote control, part no. 7438 364 VITOTROL 300A 3/2010 Please keep safe. Safety instructions Safety instructions Please follow

More information

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit Installation and service instructions for contractors VIESMANN Vitotrol 200 RF Wireless remote control for one heating circuit For applicability, see the last page VITOTROL 200 RF 3/2011 Please keep safe.

More information

Installation and Service Instructions for use by heating contractor. VITOTRONIC r 200 VITOTRONIC r 300-K IMPORTANT

Installation and Service Instructions for use by heating contractor. VITOTRONIC r 200 VITOTRONIC r 300-K IMPORTANT Installation and Service Instructions for use by heating contracr Vitronic 200, Type KW6B/HO1B Digital boiler control unit Vitronic 300-K, Type MW2C Weather-compensated, digital cascade control unit VITOTRONIC

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contracrs VIESMANN Videns 200-W Type B2HA, 80 and 100 kw Wall mounted gas condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer Installation instructions for contractors VIESMANN Mixer extension kit For one heating circuit with mixer Mixer extension kit 5/2017 Safety instructions Please follow these safety instructions closely

More information

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-G Type BW/BWS 301.A06 to A17, 5.9 to 17.0 kw Type WW 301.A06 to A17, 7.9 to 23.0 kw Heat pump, single and two-stage Type BWC 301.A06

More information

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors Installation instructions for contractors VIESMANN Vitodens 200-W Type WB2C, 45 and 60 kw Wall mounted gas condensing boiler Natural gas and LPG version VITODENS 200-W 1/2010 Dispose after installation.

More information

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMANN Extension AM1 Part no. 7429 152 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe.

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 200 Type SD4 For applicability, see the last page VITOSOLIC 200 1/2012 Please keep

More information

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMNN Extension E1 Part no. 7429 151 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 100 Type SD1 For applicability, see the last page VITOSOLIC 100 4/2009 Please keep

More information

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

Service Instructions for use by heating contractor

Service Instructions for use by heating contractor Service Instructions for use by heating contracr Please file in Service Binder Vitronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating

More information

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation. Installation instructions for contractors PYROMAT ECO PYROMAT ECO 8/2012 Dispose after installation. Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITODENS 200-W. for contractors Service instructions for contractors VIESMANN Vitodens 200-W Type WB2B, 4.8 to 35.0 kw Wall mounted gas fired condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 111-W 4/2012 Please keep safe. Safety instructions For

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 200-W Type B2HA, B2KA, 3.2 to 35 kw Gas council no. System boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 Combi boilers: 47-819-28;

More information

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 100-W 1/2012 Please keep safe. Safety instructions For

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 6/2011 Please keep safe. Safety

More information

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner VITOCROSSAL 200 2/2007 Dispose after installation. Safety instructions

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA Installation and service instructions for contractors VIESMANN Vitocell 340-M/360-M Type SVKA Type SVSA Combi cylinder 750 and 950 litre capacity VITOCELL 340-M/360-M 4/2009 Please keep safe. Safety instructions

More information

Installation Instructions VITOTRONIC 300

Installation Instructions VITOTRONIC 300 Installation Instructions Vitotronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Part No. Z001 231 VITOTRONIC 300 Certified

More information

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and Installation and service instructions for contractors VIESMANN Solar-Divicon SR Part no. 7419 520 and 7419 521 Safety instructions Please follow these safety instructions closely to prevent accidents and

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 6/2011 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 111-W Type B1LA, 6.5 to 35.0 kw Gas condensing storage combi boiler Natural gas and LPG version Gas Council no.: 47-819-23; 47-819-24;

More information

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B

More information

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT Operating Instructions for use by heating contractor Vitotronic 100, type GC1B Multi boiler system with control unit for constant temperature operation For use with Boiler models VD2A, VD2 and CT3 Vitotronic

More information

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

VIESMANN. Operating instructions VITOTRONIC 200. for the system user Operating instructions for the system user VIESMANN Heating system with weather-compensated control unit Vitotronic 200, type KO1B, KO2B or KW6B VITOTRONIC 200 12/2012 Please keep safe. Safety instructions

More information

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation Operating instructions for system users VIESMANN Heating system with control unit for constant temperature operation VITODENS 100 2/2005 Please keep safe Safety instructions For your safety Please follow

More information

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner VITOCROSSAL 300 2/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 5/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors Installation instructions for contractors VIESMANN Vitomax 200-HW Type M238 Oil/gas fired high pressure hot water boiler Combustion output 4.0 to 18.2 MW VITOMAX 200-HW 6/2007 Dispose after installation.

More information

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors Installation and service instructions for contractors VIESMANN Vitodens 343-F Type WS4A Compact Energy Tower with a gas fired condensing boiler as compact model Natural gas and LPG version (GC no) 47-819-08

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJC, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council no.: 47 819 31, 47 819 32

More information

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw VIESMANN VITOCAL 00-G Brine/water and water/water heat pump Single and two-stage, from 21 kw Technical guide Heat pump with electric drive for DHW and central heating in mono-mode or dual mode heating

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 2/2013 Please keep safe. Safety

More information

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors Installation and service instructions for contractors VIESMANN Vitocal 200-S Type AWB 201.B04 to B13, C10, C13 Air source heat pump, split version for heating operation Type AWB-AC 201.B04 to B13, C10,

More information

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user Operating instructions for the system user VIESMANN Heating system with the Vitotronic 200 control unit, type HO1B, for weathercompensated mode VITODENS VITOLADENS VITOPEND 10/2013 Please keep safe. Safety

More information

Installation Instructions VITOTRONIC 200

Installation Instructions VITOTRONIC 200 Installation Instructions Please file in Service Binder Vitotronic 200 Model KW2 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits VITOTRONIC

More information

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B VIESMANN VITOLIGNO 300-P Pellet boiler 4to48kW Datasheet For part no. and prices: see pricelist File in: Vitotec folder, register 12 VITOLIGNO 300-P Type VL3B Boiler for wood pellets 8/2007 Product information

More information

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B Operating instructions for the system user VIESMANN Digital time switch for the Vitodens 100-W, type WB1B DIGITAL TIME SWITCH 5/2008 Please keep safe. Safety instructions For your safety Please follow

More information

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler Service instructions for contractors VIESMANN Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler For applicability, see the last page VITOCROSSAL 300 4/2009 Please keep safe. Safety

More information

Installation and operating instructions

Installation and operating instructions Installation and operating instructions Cascade module KM Wolf GmbH Postfach 1380 84048 Mainburg Tel. 08751/74-0 Fax 08751/741600 Internet: www.wolf-heiztechnik.de Part no. 30 62 449 Subject to modifications

More information

BM Programming Module. For the heating engineer Installation instructions

BM Programming Module. For the heating engineer Installation instructions For the heating engineer Installation instructions BM Programming Module WOLF GmbH Postfach 1380 84048 Mainburg Tel. 08751/74-0 www.wolf-heiztechnik.de Document no.: 3062612_201509 Subject to modifications

More information

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. Service instructions. MatriX radiant burner. for contractors Service instructions for contractors VIESMANN MatriX radiant burner Type VMIII Pressure-jet gas burner for the Vitocrossal 300, type CT3B Rated heating output 187 to 314 kw For applicability, see the last

More information

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-A Type AWO-AC 301.B11 to B14 Air/water heat pump with electric drive, 400 V~ For applicability, see the last page VITOCAL 300-A

More information

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A Installation instructions for contractors VIESMNN Vitocell 300-V/W Type EVI- DHW cylinder with internal indirect coil 160 to 500 l VITOCELL 300-V/W 3/2017 Dispose after installation. Safety instructions

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW VIESMANN VITOMAX 200-WS Hot water boiler for permissible flow temperatures up to 110 C 1.75 to 11.63 MW Datasheet Part no.: see pricelist, prices on request VITOMAX 200-WS Type M250 Oil/gas fired hot water

More information

Installation and servicing instructions

Installation and servicing instructions Installation and servicing instructions Programming unit RC35 For qualified professionals Please read carefully prior to commissioning and servicing 7 747 006 341-12/2006 GB Contents Contents Contents

More information

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service Service instructions Function module FM443 solar module For contractors Read carefully prior to commissioning or service 6 720 615 516-03/2008 GB/IE Contents 1 Safety........................................

More information

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw Datasheet Part no. and prices: see pricelist VITOCROSSAL 300 Type CT3B Gas condensing boiler for natural gas E, LL and LPG With modulating MatriX

More information

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250 VIESMANN VITOMAX -WS Rated heating output 1.75 to 11.63 MW Datasheet VITOMAX -WS Type M250 Oil/gas low pressure hot water boiler CE designation in accordance with the Gas Appliances Directive Permissible

More information

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater Installation and service instructions for contractors VIESMNN EHE immersion heater 6 kw and 12 kw For installation in HW cylinders For applicability, see the last page EHE immersion heater 9/2014 Please

More information

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw Datasheet Part no. and prices: see pricelist VITOCROSSAL 300 Type CR3B Gas condensing boiler for natural gas E, LL and LPG 9/2011 Benefits

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJD, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council Number: 47 819 31, 47 819

More information

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW. VIESMANN VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW Datasheet Part no. and prices on request VITOMAX 200-LW Type M64A

More information

WOLF GAS CONDENSING BOILERS COMFORTLINE

WOLF GAS CONDENSING BOILERS COMFORTLINE WOLF GAS CONDENSING BOILERS COMFORTLINE CGB-35/50 / CGB-75/100 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build

More information

Operating instructions

Operating instructions Operating instructions Control unit - CGL Zone 0.0 C Friday 3/0/08 : 6 Wolf GmbH Postfach 380 D-84048 Mainburg Tel. +49 (0)875/74-0 Fax +49 (0)875/74600 Internet: www.wolf-heiztechnik.de Document no.:

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

Boiler controller Lambdatronic S 3200

Boiler controller Lambdatronic S 3200 Operating Instructions Boiler controller Lambdatronic S 3200 Version 50.04 - Build 05.04 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

Mixer module VR 61. Operating and Installation Manual. Mixer module for VRC 430 / VRC 430f

Mixer module VR 61. Operating and Installation Manual. Mixer module for VRC 430 / VRC 430f For the heating engineer/for the owner Operating and Installation Manual Mixer module VR 61 Mixer module for VRC 430 / VRC 430f VR 61 GB Contents Contents 1 Notes on the documentation 3 1.1 Storage of

More information

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28 The competent brand for energy saving systems NEW Gas-combi boiler CGG-1K-24/28 Gas-combi boiler CGG-1K Technical data room sealed fannned flue model gas combi boiler for low temperature heating and d.h.w.

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1535-3 031403 Table of Contents 1 English, IHB - ELK 213 General Component positions Pipe connections 2 2 3 5 Disturbances in comfort Accessories Technical data Electrical

More information

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS... User Manual Contents 1 DOCUMENT REVISION... 4 2 SOFTWARE VERSION... 4 3 BASIC DESCRIPTION... 4 4 BASIC OVERVIEW OF HYDRAULIC DIAGRAMS... 5 4.1 BOILER NOT CONTROLLED BY THE CONTROLLER:... 5 4.2 BOILER CONTROLLED

More information

Operating Instructions VITOTRONIC 200 VITOTRONIC 300-K IMPORTANT. Read and save these instructions for future reference. for use by heating contractor

Operating Instructions VITOTRONIC 200 VITOTRONIC 300-K IMPORTANT. Read and save these instructions for future reference. for use by heating contractor Operating Instructions for use by heating contractor Vitotronic 200, type H01B Digital boiler control unit Vitotronic 300-K, type MW2B Weather-compensated, digital cascade control unit VITOTRONIC 200 VITOTRONIC

More information

Operating instructions

Operating instructions Operating instructions Control unit Logamatic 4211 For users Read carefully before use 7 747 016 927-03/2008 GB/IE Contents 1 Introduction................................................ 4 2 What you should

More information

Operating instructions

Operating instructions Operating instructions Room controller 6 720 618 477-00.1RS Logamatic EMS RC35 programming unit For users Read carefully before use. 6 720 642 272 (10/2009) GB Overview of controls Overview of controls

More information

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack. Technical Guide and Installation Instructions MKS / MUS Steel boiler 70-550 kw The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack. The control

More information

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO Great Britain en Installation, user and service manual Control panel HMI Gas 310/610 ECO PRO Dear Customer, Thank you very much for buying this appliance. Please read through the manual carefully before

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service.

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service. Strategy module FM458/CMC 930 For contractors Read carefully prior to commissioning or service. 6 720 803 196 (2011/06) GB / IE / AU Service instructions 2 1 Safety........................................

More information

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe. Service instructions for contractors VIESMANN Vitoplex 200 Type SX2A, 90 to 560 kw Oil/gas boiler For applicability, see the last page VITOPLEX 200 3/2013 Please keep safe. Safety instructions Safety instructions

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

VITOPLEX. Low temperature oil and gas fired boilers Rated output Vitoplex 100: 575 to 1750 kw Vitoplex 200: 90 to 560 kw Vitoplex 300: 80 to 1750 kw

VITOPLEX. Low temperature oil and gas fired boilers Rated output Vitoplex 100: 575 to 1750 kw Vitoplex 200: 90 to 560 kw Vitoplex 300: 80 to 1750 kw VITOPLEX Low temperature oil and gas fired boilers Rated output Vitoplex 100: 575 to 1750 kw Vitoplex 200: 90 to 560 kw Vitoplex 300: 80 to 1750 kw 2 Vitoplex low temperature boiler from 80 to 1750 kw

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

O CRC100. Comfort Room Controller (2015/01) en

O CRC100. Comfort Room Controller (2015/01) en 6 720 906 767-00.1O Comfort Room Controller 100 6 720 806 769 (2015/01) en 2 Contents Contents 1 Explanation of symbols and safety instructions..................... 3 1.1 Explanation of symbols.....................................

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

Installation instructions. Advanced Weather Compensation Controller. Sense II O UK/IE (2015/10)

Installation instructions. Advanced Weather Compensation Controller. Sense II O UK/IE (2015/10) Installation instructions Advanced Weather Compensation Controller Sense II 6 720 812 774-01.1O UK/IE 6 720 818 367 (2015/10) Contents Contents 1 Explanation of symbols and safety instructions.... 3 1.1

More information

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler. VIESMANN VITOROND 100 Cast iron low temperature oil and gas fired boiler 40 to 100 kw Datasheet Part numbers and prices: see pricelist File in: Vitotec folder, register 1 VITOROND 100 Type VR2B Cast iron

More information

Operating instructions Oil condensing boiler

Operating instructions Oil condensing boiler Operating instructions Oil condensing boiler COB COB-CS Boiler for heating Boiler with stratification cylinder Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49-8751/74-0 Fax +49-8751/741600 Internet:

More information

VIESMANN. Gas condensing boilers 87 to 1400 kw. Technical guide. VITOCROSSAL 200 Type CM2. VITOCROSSAL 300 Type CM3. VITOCROSSAL 300 Type CT3U

VIESMANN. Gas condensing boilers 87 to 1400 kw. Technical guide. VITOCROSSAL 200 Type CM2. VITOCROSSAL 300 Type CM3. VITOCROSSAL 300 Type CT3U VIESMNN Gas condensing boilers 87 to 1400 kw Technical guide VITOCROSSL 200 Type CM2 VITOCROSSL 300 Type CM3 VITOCROSSL 300 Type CT3U VITOCROSSL 300 Type CT3B VITOCROSSL 300 Type CR3B 5/2013 Index Index

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions ecotec plus Gas-fired wall-hung high-efficiency boiler GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Telefon

More information

Operating Instructions. VITODENS r 200 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT

Operating Instructions. VITODENS r 200 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT Operating Instructions Vitodens 200-W, B2HA Series and Vitodens 222-F B2TA Series Models 19 to 150 Wall-mounted, gas-fired condensing boiler For operation with natural gas and liquid propane gas Heating

More information

Installation and service instructions

Installation and service instructions Installation and service instructions Programming unit Logamatic EMS RC25 programming unit For contractors Read carefully before installation and servicing. 6 720 642 759 (05/2010) GB Contents Contents

More information

Multi Box HP 10. Accessories, split air to water heat pump PRINT APPROVAL 1 NOVEMBER Installation instructions (2012/11)

Multi Box HP 10. Accessories, split air to water heat pump PRINT APPROVAL 1 NOVEMBER Installation instructions (2012/11) Installation instructions Accessories, split air to water heat pump Multi Box HP 10 6 720 801 399-00.1I 6 720 804 408 (2012/11) Table of Contents Table of Contents 1 Key to symbols and safety instructions...................

More information

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1 Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1 Introduction Introduction The ROTEX THETA control unit is a simple to operate

More information

GRUNDFOS INSTRUCTIONS. Fire CONTROLLER SS EN12845 SS INSTA 900. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Fire CONTROLLER SS EN12845 SS INSTA 900. Installation and operating instructions INSTRUCTIONS Fire CONTROLLER Installation operating instructions SS EN12845 SS 883001 INSTA 900 Declaration of conmity Declaration of conmity Declaration of conmity GB: EC declaration of of conmity We,

More information

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE Installation instructions For the heating engineer Installation instructions timeswitch VTS 160 GB, IE Table of contents Table of contents 1 Notes on the installation instructions...4 1.1 Observing other

More information

VIESMANN. Installation and service instructions VITODENS 100. for heating engineers

VIESMANN. Installation and service instructions VITODENS 100. for heating engineers Installation and service instructions for heating engineers VIESMANN Vitodens 100 Type WB1A Gas fired wall mounted condensing boiler Natural gas version For applicability, see the last page VITODENS 100

More information