for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

Size: px
Start display at page:

Download "for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe."

Transcription

1 Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 100 Type SD1 For applicability, see the last page VITOSOLIC 100 4/2009 Please keep safe.

2 Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Working on the system Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolator. Safeguard the system against unauthorised reconnection. Please note! Electronic modules can be damaged by electrostatic discharges. Touch earthed objects, such as heating or water pipes, to discharge static loads. Repair work! Please note Repairing components that fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. Observe the following when working on this system all legal instructions regarding the prevention of accidents, all legal instructions regarding environmental protection, the Code of Practice of relevant trade associations. all current safety regulations as defined by DIN, EN, DVGW, VDE and all locally applicable standards 2

3 Safety instructions Safety instructions (cont.) Ancillary components, spare and wearing parts Please note! Spare and wearing parts that have not been tested together with the heating system can compromise its function. Installing non-authorised components and non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only original spare parts supplied or approved by Viessmann. 3

4 Index Installation instructions Preparing for installation Installation information... 6 System example System example System example System example Installation sequence Fitting the solar control unit Overview of electrical connections Solar circuit pump Pump/valve at output R High limit safety cut-out Collector temperature sensor Cylinder temperature sensor Temperature sensor Power supply Service instructions Commissioning Switching the power ON Navigation through the menu Selecting the system scheme Setting system parameters Resetting system parameters Carrying out a relay test Service scans Scanning temperatures and operating conditions Troubleshooting Fault messages Checking sensors Changing the fuse Function description Parameter overview System scheme Collector limit temperature Collector cooling function Minimum collector temperature limit Index

5 Index Index (cont.) Frost protection function Reverse cooling function Interval function Heat statement Speed control Parts list Specification Appendix Certificates Declaration of conformity Keyword index

6 Preparing for installation Installation information Danger Subject to system configuration, DHW temperatures above 60 C can occur. DHW with temperatures in excess of 60 C can result in scalding. To limit the temperature to 60 C, install mixing equipment, e.g. a thermostatically controlled mixing valve (accessory). Install a mixer tap as anti-scalding device at the draw-off point. System example 1 DHW heating with dual-mode DHW cylinder Main components Viessmann solar collectors DHW cylinders Vitocell 100-B or Vitocell 300-B Vitosolic 100, type SD1 Solar-Divicon Wall mounted oil/gas boiler or oil/gas boiler Function description DHW heating with solar energy Solar circuit pump R1 ee starts and DHW cylinder qp is heated up if the temperature differential between collector temperature sensor S1 eq and cylinder temperature sensor S2 qq exceeds the starting temperature differential DT E. Solar circuit pump R1 ee is stopped in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT A. Exceeding the electronic temperature limit (max. 90 C) of control unit ez Reaching the temperature selected at high limit safety cut-out qw (if installed) Auxiliary function for DHW heating The requirements for the auxiliary function are achieved through circulation pump R2 qt. Suppression of DHW cylinder reheating by the boiler Coding address "67" in boiler control unit 2 defaults a third set DHW temperature (setting range 10 to 95 C). This value must be below the first set DHW temperature. DHW cylinder qp will only be heated by boiler 1 (solar circuit pump R1 ee runs) if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy The upper section of DHW cylinder qp is heated by boiler 1. The cylinder thermostat with cylinder temperature sensor 3 of boiler control unit 2 regulates cylinder heating. 6

7 Preparing for installation System example 1 (cont.) Required settings on the solar control unit Param eters Delivered condition Description Setting ANL 1 Without auxiliary function for DHW heating 1 With auxiliary function for DHW heating (see 4 page 56) DT E 8 K Start temperature differential for solar circuit pump at R1 DT A 4 K Stop temperature differential for solar circuit pump at R1 S SL 60 C Set cylinder temperature (see page 53) For further functions, see chapter "Functions" from page 49. Note "DT E" can be set at least 0.5 K higher than "DT A". "DT A" can be set up to 0.5 K below "DT E". Information regarding speed control of the solar circuit pump Observe chapter "Speed control" (see page 64). Installation 7

8 Preparing for installation System example 1 (cont.) Hydraulic installation diagram eq ew ee N ep qr qt ez qw qp qe 3 qq M 8

9 Preparing for installation System example 1 (cont.) Equipment required Pos. Description 1 Oil/gas boiler or wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit 3 Cylinder temperature sensor 4 Circulation pump for cylinder heating (integrated for wall mounted oil/gas boiler) qp Dual-mode DHW cylinder qq Cylinder temperature sensor S2 qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) (internal/external extension may be required for connecting a wall mounted oil/gas boiler) qr Thermostatic mixing valve (accessory) qt Circulation pump R2 (anti-stratification) (on site) ep Solar collectors eq Collector temperature sensor S1 ew Solar-Divicon (accessory) with ee Solar circuit pump R1 ez Vitosolic 100, type SD1 eu Junction box (on site) ei ON/OFF switch (on site) Installation 9

10 Preparing for installation System example 1 (cont.) Electrical installation diagram ez ei 230 V / 50 Hz? ? 14 eu 230 V / 50 Hz M 1~ R1 ee High limi qw 17 16? 13 M 1~ R2 qt KM BUS 2 Low voltage SOL qq 2 1 KOL eq 10

11 Preparing for installation System example 2 Vitodens DHW heating and central heating backup with a multimode heating water buffer cylinder Main components Viessmann solar collectors Vitocell 340-M or Vitocell 360-M multimode heating water buffer cylinder with integral DHW heating, with or without stratification system Vitosolic 100, type SD1 Solar-Divicon Wall mounted gas boiler from the year of manufacture 2008 Vitodens 200-W, type WB2B Vitodens 300-W, type WB3C Function description DHW heating with solar energy Solar circuit pump R1 ee starts and heating water buffer cylinder qp is heated up if the temperature differential between collector temperature sensor S1 eq and cylinder temperature sensor S2 qq exceeds the starting temperature differential DT E. Solar circuit pump R1 ee is stopped in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT A. Exceeding the electronic temperature limit (max. 90 C) of control unit ez Reaching the temperature selected at high limit safety cut-out qw (if installed) Entire heating water buffer cylinder qp is heated by the solar thermal system if the insolation is adequate. The upper part of heating water buffer cylinder qp will only be reheated by boiler 1 if the actual water temperature falls below the set temperature selected at boiler control unit 2. If the solar energy is inadequate to cover the entire heating demand, the DHW in the lower part of heating water buffer cylinder qp will be preheated by solar energy. The DHW in the upper part of the cylinder is heated to the required temperature by boiler 1. The burner is started and three-way diverter valve rz is switched to position "AB-A" via cylinder temperature sensor qz of the boiler control unit. When the set DHW temperature has been reached, the burner is stopped and three-way diverter valve rz is switched to position "AB-B". Suppression of DHW cylinder reheating by the boiler Coding address "67" in boiler control unit 2 defaults a third set DHW temperature (setting range 10 to 95 C). This value must be below the first set DHW temperature. Heating water buffer cylinder qp is only heated by boiler 1 (solar circuit pump R1 ee runs) if this set value cannot be achieved by the solar thermal system. 11 Installation

12 Preparing for installation System example 2 (cont.) DHW heating without solar energy The upper area of heating water buffer cylinderqp is heated by boiler 1. The integral instantaneous water heater/ standby section is heated by the surrounding buffer cylinder water. The cylinder thermostat with cylinder temperature sensor qz of boiler control unit 2 controls three-way diverter valve rz. Central heating with solar energy Central heating without solar energy If the temperature at sensor qt is inadequate, the burner and circulation pump in the Vitodens are started. The area between HV2/HR1 and HR2 in heating water buffer cylinder qp is heated up to the set temperature for the heating circuits in weather-compensated mode. When this set temperature is exceeded, the burner and, after a delay, the circulation pump in the Vitodens are stopped. The system provides central heating if the temperature at sensor qt is adequate. Required settings on the solar control unit Param eters Delivered condition Description Setting ANL 1 Without auxiliary function for DHW heating 1 DT E 8 K Start temperature differential for solar circuit pump at R1 DT A 4 K Stop temperature differential for solar circuit pump at R1 S SL 60 C Set cylinder temperature (see page 53) For further functions, see chapter "Functions" from page 49. Note "DT E" can be set at least 0.5 K higher than "DT A". "DT A" can be set up to 0.5 K below "DT E". Information regarding speed control of the solar circuit pump Observe chapter "Speed control" (see page 64). 12

13 Preparing for installation System example 2 (cont.) Codes required at the boiler and heating circuit control unit Code Function 51:1 The internal circulation pump is only switched on when the burner has been started (time delay off) 53:3 System without DHW circulation pump: Three-way diverter valve rz is connected to output sk of internal extension H1 or H2 5b:1 Internal diverter valve without function (DHW cylinder connected downstream of the low loss header) Installation 13

14 Preparing for installation System example 2 (cont.) Hydraulic installation diagram eq ew ee N ep qw qz qt qq ez qp qr HV1 ww HV2/HR1 HR2 HR3 qe 5/28 2 M rz 5/21 1 M 14

15 Preparing for installation System example 2 (cont.) Equipment required Pos. Description 1 Wall mounted gas boiler with 2 Boiler and heating circuit control unit 3 Internal extension H1 (standard delivery for the Vitodens 300-W) or 4 Internal extension H2 (accessory) or System with DHW circulation pump: 5 External extension H1 (accessory) 6 KM BUS distributor (accessory) qp Heating water buffer cylinder with ww Threaded DHW circulation pump (accessory) qt Temperature sensor (flow temperature sensor for low loss header; in this scheme with heating water buffer cylinder) (accessory) qz Cylinder temperature sensor (accessory) qq Cylinder temperature sensor S2 qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) qr Thermostatic mixing valve (accessory) ep Solar collectors eq Collector temperature sensor S1 ew Solar-Divicon (accessory) with ee Solar circuit pump R1 ez Vitosolic 100, type SD1 eu Junction box (on site) ei ON/OFF switch (on site) rz Three-way diverter valve (accessory) Installation 15

16 Preparing for installation System example 2 (cont.) Electrical installation diagram ez ei 230 V / 50 Hz? ? ? 13 eu 230 V / 50 Hz M 1~ R1 ee High limi qw A Low voltage SOL qq 2 1 KOL eq 16

17 Preparing for installation System example 2 (cont.) 2 fö L? 230 V / 50 Hz 3 4 lh lh V / 50 Hz lh? 1 gd sk? abj sk?? fö sö sa? sk? gö? M 1~ rz M 1~ ZP qe Installation avg 2 1 Low voltage % STS qz qt avg avg avg A 17

18 Preparing for installation System example 3 Vitodens DHW heating with freshwater module and central heating backup with heating water buffer cylinder Main components Viessmann solar collectors Freshwater module Heating water buffer cylinder Vitocell140-E or Vitocell 160-E Vitosolic 100, type SD1 Solar-Divicon Wall mounted gas boiler from the year of manufacture 2008 Vitodens 200-W, type WB2B Vitodens 300-W, type WB3C Function description Freshwater module qp heats DHW when hot water is drawn. The energy supply to freshwater module qp is provided via heating water buffer cylinder rp. DHW heating with solar energy Solar circuit pump R1 ee starts and heating water buffer cylinder rp is heated up if the temperature differential between collector temperature sensor S1 eq and cylinder temperature sensor S2 rq exceeds the start temperature differential DT E. Solar circuit pump R1 ee is stopped in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT A. Exceeding the electronic temperature limit (max. 90 C) of control unit ez Reaching the temperature selected at high limit safety cut-out rr (if installed) Entire heating water buffer cylinder rp is heated by the solar thermal system if the insolation is adequate. The upper part of heating water buffer cylinder rp will only be reheated by boiler 1 if the actual water temperature falls below the set temperature selected at boiler control unit 2. The burner is started and three-way diverter valve rz is switched to position "AB-A" via cylinder temperature sensor rw of the boiler control unit. When the set DHW temperature has been reached, the burner is stopped and three-way diverter valve rz is switched to position "AB-B". Suppression of DHW cylinder reheating by the boiler Coding address "67" in boiler control unit 2 defaults a third set DHW temperature (setting range 10 to 95 C). This value must be below the first set DHW temperature. Heating water buffer cylinder rp is only heated by the boiler (solar circuit pump R1 ee runs) if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy The upper area of heating water buffer cylinder rp is heated by boiler 1. The cylinder thermostat with cylinder temperature sensor rw of boiler control unit 2 controls three-way diverter valve rz. 18

19 Preparing for installation System example 3 (cont.) Central heating with solar energy Central heating without solar energy Central heating is provided via heating water buffer cylinder rp if the temperature at sensor re is adequate. Required settings on the solar control unit If the temperature at sensor re is inadequate, the burner and circulation pump in the Vitodens are started. The area between HV3/HR1 and HR3 in heating water buffer cylinder rp is heated up to the set temperature for the heating circuits in weather-compensated mode. When this set temperature is exceeded, the burner and, after a delay, the circulation pump in the Vitodens are stopped. Installation Param eters Delivered condition Description Setting ANL 1 Without auxiliary function for DHW heating 1 DT E 8 K Start temperature differential for solar circuit pump at R1 DT A 4 K Stop temperature differential for solar circuit pump at R1 S SL 60 C Set cylinder temperature (see page 53) For further functions, see chapter "Functions" from page 49. Note "DT E" can be set at least 0.5 K higher than "DT A". "DT A" can be set up to 0.5 K below "DT E". Information regarding speed control of the solar circuit pump Observe chapter "Speed control" (see page 64). Codes required at the boiler and heating circuit control unit Code Function 51:1 The internal circulation pump is only switched on when the burner has been started (time delay off) 53:3 System without DHW circulation pump: Three-way diverter valve rz is connected to output sk of internal extension H1 or H2 5b:1 Internal diverter valve without function (DHW cylinder connected downstream of the low loss header) 19

20 Preparing for installation System example 3 (cont.) Hydraulic installation diagram eq ew ee rr rw re rq qe N ep rp ez HV1 HV2 HV3/HR1 HR2 HR3 HR4 qq M qw qp rz M M

21 Preparing for installation System example 3 (cont.) Equipment required Pos. Description 1 Wall mounted gas boiler with 2 Boiler and heating circuit control unit rw Cylinder temperature sensor STS 3 Internal extension H1 (standard delivery for the Vitodens 300-W) or 4 Internal extension H2 (accessory) qp Freshwater module with qq Three-way diverter valve R3 and qw Temperature sensor S4 and qe Temperature sensor S3 qr ON/OFF switch (on site) rp Heating water buffer cylinder rq Cylinder temperature sensor S2 rr High limit safety cut-out (accessory) ep Solar collectors eq Collector temperature sensor S1 ew Solar-Divicon (accessory) with ee Solar circuit pump R1 ez Vitosolic 100, type SD1 eu Junction box (on site) ei ON/OFF switch (on site) re Temperature sensor (flow temperature sensor for low loss header) (accessory) rz Three-way diverter valve (accessory) Installation 21

22 Preparing for installation System example 3 (cont.) Electrical installation diagram ez ei 230 V / 50 Hz? ? ? 13 eu 230 V / 50 Hz M 1~ R1 ee High limi rr A Low voltage SOL rq 2 1 KOL eq 22

23 Preparing for installation System example 3 (cont.) 2 fö L? 230 V / 50 Hz 3 4 lh lh 230 V / 50 Hz lh? 1 gd sk? abj sk? M 1~ rz Installation Low voltage % STS rw A re 23

24 Preparing for installation System example 3 (cont.) Control unit, freshwater module qp qr 230 V / 50 Hz?? 230 V / 50 Hz M 1~ R3 qq Low voltage S4 S3 qw qe System example 4 DHW heating with solar retrofit system There are two control versions for this system example: Anti-stratification with sensor S3 in DHW cylinder 2 (existing) Anti-stratification with sensor S3 in DHW cylinder 1 (retrofit) Anti-stratification with sensor S3 in DHW cylinder 2 (existing) Main components Viessmann solar collectors Mono-mode DHW cylinder (existing) Solar retrofit system with the following components: Solar-Divicon Vitosolic 100, type SD1 DHW cylinder Vitocell 100-W, type CUG Wall mounted oil/gas boiler or oil/gas boiler (existing) 24

25 Preparing for installation System example 4 (cont.) Function description DHW heating with solar energy Solar circuit pump R1 qp starts and DHW cylinder qp is heated up if the temperature differential between collector temperature sensor S1 ee and cylinder temperature sensor S2 qq exceeds the start temperature differential DT E. Solar circuit pump R1 ee is stopped in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT A. Exceeding the electronic temperature limit (max. 90 C) of control unit ez Reaching the temperature selected at high limit safety cut-out qw (if installed) Anti-stratification pump R2 qt starts if the temperature differential between sensor S2 qq and sensor S3 qu exceeds the start temperature differential DT 3E. The water heated in DHW cylinder qp is transferred to DHW cylinder 2 qi. The anti-stratification pump R2 will also start if there is a demand for DHW heating issued by the auxiliary function. Anti-stratification pump R2 qt stops in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT 3A When the auxiliary function for DHW heating ends DHW circulation pump qe (if installed) for DHW cylinder 2 qi is controlled by boiler control unit 2. Suppression of DHW cylinder reheating by the boiler Coding address "67" in boiler control unit 2 defaults a third set DHW temperature (setting range 10 to 95 C). This value must be below the first set DHW temperature. DHW cylinder 2 qi will only be heated by boiler 1 (solar circuit pump R1 ee runs) if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy DHW cylinder 2 qi is heated by boiler 1. The cylinder thermostat with cylinder temperature sensor 3 of boiler control unit 2 regulates cylinder heating. Installation Required settings on the solar control unit Param eters Delivered condition Description ANL 1 With auxiliary function for DHW heating (see page 56) DT E 8 K Start temperature differential for solar circuit pump at R1 DT A 4 K Stop temperature differential for solar circuit pump at R1 Setting 8 25

26 Preparing for installation System example 4 (cont.) Param eters Delivered condition Description DT 3E 8 K Start temperature differential for anti-stratification pump at R2 DT 3A 4 K Stop temperature differential for anti-stratification pump at R2 S SL 60 C Set cylinder temperature (see page 53) For further functions, see chapter "Functions" from page 49. Setting Note "DT E/DT 3E" can be set to at least 0.5 K above "DT A/DT 3A". "DT A/DT 3A" can be set up to 0.5 K below "DT E/DT 3E". Information regarding speed control of the solar circuit pump Observe chapter "Speed control" (see page 64). 26

27 Preparing for installation System example 4 (cont.) Hydraulic installation diagram ez eq ep ew P qe 2 ee qr 1 qt qw 2 4 qu qq qp qi Installation 1 M 27

28 Preparing for installation System example 4 (cont.) Equipment required Pos. Description 1 Oil/gas boiler or wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit 3 Cylinder temperature sensor 4 Circulation pump for cylinder heating (integrated for wall mounted oil/gas boiler) qi DHW cylinder 2, mono-mode (existing) qp DHW cylinder 1, mono-mode (solar retrofit system) qq Cylinder temperature sensor S2 qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) (internal/external extension may be required for connecting a wall mounted oil/gas boiler) qr Thermostatic mixing valve (accessory) ep Solar collectors eq Collector temperature sensor S1 ew Solar-Divicon (solar retrofit system) with ee Solar circuit pump R1 and ez Vitosolic 100, type SD1 eu Junction box (on site) ei ON/OFF switch (on site) DHW circulation diversion qt Circulation pump R2 (anti-stratification) (accessory) qu Temperature sensor S3 (DHW cylinder 2) (accessory) 28

29 Preparing for installation System example 4 (cont.) Electrical installation diagram ez ei 230 V / 50 Hz? ? ? 13 eu 230 V / 50 Hz M 1~ R1 M 1~ ee High limi qw R2 qt Installation KM BUS 2 Low voltage SOL qu qq 2 1 KOL eq Anti-stratification with sensor S3 in DHW cylinder 1 (retrofit) Main components Viessmann solar collectors Mono-mode DHW cylinder (existing) Solar retrofit system with the following components: 29

30 Preparing for installation System example 4 (cont.) Solar-Divicon Vitosolic 100, type SD1 DHW cylinder Vitocell 100-W, type CUG Wall mounted oil/gas boiler or oil/gas boiler (existing) Function description DHW heating with solar energy Solar circuit pump R1eE starts and DHW cylinder qp is heated up if the temperature differential between collector temperature sensor S1 eq and cylinder temperature sensor S2 qq exceeds the start temperature differential DT E. Solar circuit pump R1 ee is stopped in accordance with the following criteria: The actual temperature falls below the shutdown temperature differential DT A. Exceeding the electronic temperature limit (max. 90 C) of control unit ez Reaching the temperature selected at high limit safety cut-out qw (if installed) Anti-stratification pump R2 qt starts if the temperature at sensor S3 qu exceeds the start temperature NH E. The water heated in DHW cylinder qp is transferred to DHW cylinder 2 qi. The anti-stratification pump R2 will also start if there is a demand for DHW heating issued by the auxiliary function. Anti-stratification pump R2 qt stops in accordance with the following criteria: The actual temperature falls below the stop temperature N HA When the auxiliary function for DHW heating ends DHW circulation pump qe (if installed) for DHW cylinder 2 qi is controlled by boiler control unit 2. Suppression of DHW cylinder reheating by the boiler Coding address "67" in boiler control unit 2 defaults a third set DHW temperature (setting range 10 to 95 C). This value must be below the first set DHW temperature. DHW cylinder 2 qi will only be heated by boiler 1 (solar circuit pump R1 ee runs) if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy DHW cylinder 2 qi is heated by boiler 1. The cylinder thermostat with cylinder temperature sensor 3 of boiler control unit 2 regulates cylinder heating. 30

31 Preparing for installation System example 4 (cont.) Required settings on the solar control unit Param eters Delivered condition Description ANL 1 With auxiliary function for DHW heating (see page 56) DT E 8 K Start temperature differential for solar circuit pump at R1 DT A 4 K Stop temperature differential for solar circuit pump at R1 N HE 40 C Start temperature for anti-stratification pump at R2 N HA 45 C Stop temperature for anti-stratification pump at R2 S Sl 60 C Set cylinder temperature (see page 53) For further functions, see chapter "Functions" from page 49. Setting 9 WW set + 4 K WW set + 2 K Installation Note "DT E" can be set at least 0.5 K higher than "DT A". "DT A" can be set up to 0.5 K below "DT E". WW set is the set DHW temperature of the DHW cylinder 2 (existing). Scan this value at the boiler control unit. When adjusting "N HE" observe the set cylinder temperature "S SL". If necessary, adjust the set DHW temperature of DHW cylinder 2 a little lower at the boiler control unit. Information regarding speed control of the solar circuit pump Observe chapter "Speed control" (see page 64). Installation and service instructions of the boiler control unit 31

32 Preparing for installation System example 4 (cont.) Hydraulic installation diagram ez eq ew ee qu qw 1 qp qq N ep qt qr qe 2 qi M 32

33 Preparing for installation System example 4 (cont.) Equipment required Pos. Description 1 Oil/gas boiler or wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit 3 Cylinder temperature sensor 4 Circulation pump for cylinder heating (integrated for wall mounted oil/gas boiler) qi DHW cylinder 2, mono-mode (existing) qp DHW cylinder 1, mono-mode (solar retrofit system) qq Cylinder temperature sensor S2 qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) (internal/external extension may be required for connecting a wall mounted oil/gas boiler) qr Thermostatic mixing valve (accessory) ep Solar collectors eq Collector temperature sensor S1 ew Solar-Divicon (solar retrofit system) with ee Solar circuit pump R1 and ez Vitosolic 100, type SD1 eu Junction box (on site) ei ON/OFF switch (on site) DHW circulation diversion qt Circulation pump R2 (anti-stratification) (accessory) qu Temperature sensor S3 (DHW cylinder 1) (accessory) Installation 33

34 Preparing for installation System example 4 (cont.) Electrical installation diagram ez ei 230 V / 50 Hz? ? 14 eu 230 V / 50 Hz M 1~ R1 ee High limi qw 17 16? 13 M 1~ R2 qt KM BUS 2 Low voltage SOL qu qq 2 1 KOL eq 34

35 Installation sequence Fitting the solar control unit Select an installation location near the DHW cylinder, considering the electrical connections and their cable lengths x Installation Before closing the solar control unit, make all electrical connections and apply a strain relief to all cables/leads. 35

36 Installation sequence Overview of electrical connections T 4 A 250 V E A R1 R2 P = 2 VA AC 250 V 0,8 A AC 250 V 4(2) A IP 20, l, T V 50 Hz S1 1 2 S2 3 4 S3 5 6 PWM GND ? N R2 N R1 N L B C D A Wiring chamber of the solar control unit B Sensor inputs C PWM signal for the solar circuit pump D KM BUS E Fuse, 4.0 A (slow) R1 Semiconductor relay (suitable for speed control) R2 Electromechanical relay Solar circuit pump Possible pumps Standard solar circuit pumps Without individual speed control (with integral auxiliary capacitor) With individual speed control High efficiency pumps Pumps with PWM input Note Use only solar pumps, not heating circuit pumps. "RPM" = 1 "RPM" = 0 "RPM" = 0 WILO pumps: "RPM" = 2 GRUNDFOS pumps: "RPM" = 3 36

37 Installation sequence Solar circuit pump (cont.) Installation The circulation pump with connecting cable is part of the Solar-Divicon pump station. Alternative pumps must be type-tested and installed in accordance with the manufacturer's details. Separate installation and service instructions Connection 3-core cable with a cross-section of 0.75 mm 2. Rated current: 0.8 A Standard pump Note Pumps that draw more than 190 W must be connected via an additional relay (coupler relay). Disable the speed control for this pump (see chapter "Speed control"). Installation A M 1~ A Wiring chamber of the solar control unit R1 Solar circuit pump 37

38 Installation sequence Solar circuit pump (cont.) Pump with PWM input A M 1~ A Wiring chamber of the solar control unit R1/PWM Solar circuit pump Pump/valve at output R2 Installation Pump and valve must be type-tested and installed in accordance with manufacturer's details. Connection 3-core cable with a cross-section of 0.75 mm 2. Rated current: max. 4(2) A 38

39 Installation sequence Pump/valve at output R2 (cont.) A M 1~ B A Wiring chamber of the solar control unit High limit safety cut-out A high limit safety cut-out in the consumer is required when less than 40 litres cylinder volume is available per m 2 absorber area. This installation safely prevents temperatures in excess of 90 C in the consumer. Installation Install the sensor of the high limit safety cut-out inside the cylinder cap (Vitocell 300 accessory). Connection 3-core cable with a cross-section of 1.5 mm 2. B Pump or valve Note For the Vitocell 100, observe the max. collector area that can be connected. Cylinder cap installation instructions Installation 39

40 Installation sequence High limit safety cut-out (cont.) A C Solar circuit pump D Junction box (on site) D M 1~ C B A Wiring chamber of the solar control unit B High limit safety cut-out Temperature setting Delivered condition: 120 C Requires adjustment to 95 C High limit safety cut-out installation instructions Collector temperature sensor Installation Collector installation instructions Connection Connect the sensor to S1 (terminals 1 and 2). Extension of the connecting lead: 2-core cable with a cross-section of 1.5 mm 2. Note Never route this lead immediately next to 230/400 V cables. 40

41 Installation sequence Cylinder temperature sensor Installation With the threaded elbow. DHW cylinder installation instructions Connection Connect the sensor to S2 (terminals 3 and 4). Extension of the connecting lead: 2-core cable with a cross-section of 1.5 mm 2. Temperature sensor Installation Note Never route this lead immediately next to 230/400 V cables. Installation

42 Installation sequence Temperature sensor (cont.) Note Never wrap insulating tape around the sensor. Seal in the sensor well. Connection Connect the sensor to S3 (terminals 5 and 6). Extension of the connecting lead: 2-core cable with a cross-section of 1.5 mm 2. Note Never route this lead immediately next to 230/400 V cables. Power supply Regulations Carry out the power supply connection and all earthing measures (i.e. RCD circuit) in accordance with IEC 364, the requirements of your local power supply utility, VDE or national regulations. Protect the power cable to the control unit with an appropriate fuse/mcb. 42

43 Installation sequence Power supply (cont.) A Provide the power supply connection (230 V~) via a two-pole mains isolator (on-site). Disconnect the system by means of a device which simultaneously separates all non-earthed conductors with at least 3 mm contact separation.? N C L B Danger Incorrect core termination can cause severe injuries and damage to the equipment. Never interchange cores "L" and "N": L Terminal 21 N Terminal 20 Installation A Solar control unit wiring chamber B ON/OFF switch (on site) C Mains voltage 230 V/50 Hz 43

44 Commissioning Switching the power ON 1. Check whether all electrical connections have been correctly made. 2. Check that the high limit safety cutout (if required) is connected. 4. Check the type of solar circuit pump that is connected and set parameter "RPM" accordingly (see pages 36 and 45). 3. Switch ON the power; the solar control unit then implements an initiation phase. The solar control unit is now in automatic mode. Navigation through the menu The display shows the collector temperature and the system scheme. Key Calling up the menu for setting the system parameters The symbol line on the display shows which keys to use to make adjustments and scans. Flashing "SET" Values can be changed Key Terminating an adjustment already begun in the menu (the value reverts to its previous setting) OK key Confirmation of the selection or value change made in the menu Note After approx. 4 min, the display changes to show the collector temperature, if no further adjustments are made. Selecting the system scheme Press the following keys: 1. "ANL 1" and the display will show the respective scheme OK "SET" flashes. 3. for the required scheme. 4. OK to confirm.

45 Commissioning Selecting the system scheme (cont.) System schemes, see from page 51. Setting system parameters Press the following keys: 1. "ANL" and the display will show the respective scheme. 2. until the required parameter is shown (see table on page 49). 3. OK "SET" flashes. 4. / for the selected value. 5. OK to confirm. Resetting system parameters If a different system scheme is selected, all parameters are returned to their original state. Carrying out a relay test Press the following keys: 1. "ANL" and the display will show the respective scheme. 2. Select "HND 1" or "HND 2". HND 1 Relay 1 HND 2 Relay 2 3. OK "SET" flashes. 4. / for the required setting. Auto Control mode On in (100%) "Æ" and "Â" or "Ã" are displayed and " " flashes. OFF OFF "Æ" is shown and " " flashes. 5. OK to confirm. Service 6. After the relay test has been completed, select "Auto". 45

46 Service scans Scanning temperatures and operating conditions Subject to system configuration and settings made, the following values can be scanned with keys / : Display Description KOL C Collector temperature TSPU C DHW temperature S3 C Temperature at a sensor S3 that may be connected n1 % Relative speed of the solar circuit pump n2 Status of relay R2: OFF: Relay off On: Relay on hp1 h Hours run of the device at output relay R1 (solar circuit pump) hp2 h Hours run of the device at output relay R2 kwh MWh Amount of heat if a heat meter is enabled Note Add the values for MWh and kwh together. Resetting the hours run and the energy volume 2. OK to confirm. Whilst this value is displayed, press the following keys: 1. OK "SET" flashes; value 0 is displayed. 46

47 Troubleshooting Fault messages Sensor faults: Display background light flashes The sensor symbol in the system scheme flashes quickly flashes Example - collector temperature sensor short circuit Possible displays: 88.8 Sensor short circuit Sensor break Note Further scans can be carried out with keys /. KOL C Checking sensors Resistance in kω 1 B A Temperature in C Service A Resistor 20 kω (sensor S1, collector temperature sensor) B Resistor 10 kω (sensors S2 and S3) 1. Disconnect the respective sensor and measure its resistance. 47

48 Troubleshooting Checking sensors (cont.) 2. Compare the measurement with the actual temperature (for scanning see page 46). Check the installation and, in case of severe deviation, replace the sensor. Specification Sensor NTC 10 kω at 25 C 20 kω at 25 C Protection IP 53 IP 53 Permissible ambient temperature during operation 20 to + 90 C 20 to C during storage and transport 20 to + 70 C 20 to + 70 C Changing the fuse A B A Solar control unit wiring chamber B Fuse, 4 A (slow) Open the solar control unit wiring chamber. A spare fuse is included in the fuse holder. 48

49 Function description Parameter overview The following parameters can be set subject to the actual system configuration: Display Parameters Delivered condition Setting range System scheme ANL System scheme DT E Start temperature differential for solar circuit pump R1 8 K K DT A Stop temperature differential for solar circuit 4 K K 1 to 9 pump R1 S SL Set cylinder temperature 60 C 4 90 C (see page 53) DT 1E Start temperature differential for solar circuit pump R1 (consumer 1) 8 K K DT 1A Stop temperature differential 4 K K for solar circuit pump R1 (consumer 1) S 1SL Set cylinder temperature (consumer 1) 60 C 4 90 C (see page 53) DT 2E Start temperature differential 8 K K 10 for solar circuit pump R1 and valve R2 (consumer 2) DT 2A Stop temperature differential 4 K K for solar circuit pump R1 and valve R2 (consumer 2) S 2SL Set cylinder temperature 60 C 4 90 C (consumer 2) (see page 53) NOT Collector limit temperature (see page 62) 130 C C OKX Collector cooling function OFF OFF/ON KMX (maximum collector temperature limit) 110 C C (see page 62) 1 to 10 OKN Minimum collector temperature OFF OFF/ON KMN limit 10 C C (see page 62) OKF Frost protection OFF OFF/ON KFR (see page 63) 4 C C Service 49

50 Function description Parameter overview (cont.) Display Parameters Delivered condition Setting range System scheme PRIO Sequence in which the consumers are heated up tsp Pump run break duration, 2 min 1 30 min 10 cycle pause time tumw Break intervals 15 min 1 30 min ORUE Return cooling function OFF OFF/ON (see page 63) ORK Interval function OFF OFF/ON 1 to 10 (see page 63) DT 3E Start temperature differential for anti-stratification pump R2 8 K 0 20 K DT 3A Stop temperature differential 4 K K for anti-stratification pump R2 7 MX3E Maximum limit S3 on 58 C C MX3A Maximum limit S3 off 60 C C MN3E Minimum limit S3 on 10 C C MN3A Minimum limit S3 off 5 C C NH E Starting temperature for the 40 C C 3, 5, 9 thermostat function NH A Switch-off temperature for 45 C C 3, 5, 9 the thermostat function OWMZ Heat statement OFF OFF/ON VMAX (see page 64) 5.0 l/min l/min at 100% pump speed MEDT to 10 MED% RPM Speed control (see page 64) n1mn *1 Minimum speed (see page 64) 30 % 30/ % *1 Only adjustable with setting RPM > 0. 50

51 Function description Parameter overview (cont.) Display Parameters Delivered condition Setting range System scheme DT S *1 Differential temperature for 10 K K the start of the speed regulation (see page 64) 1 to 9 ANS *1 Rise 2 K 1 20 K (see page 64) DT 1S *1 Differential temperature for the start of speed regulation (consumer 1) (see page 64) 10 K K ANS1 *1 Rise (consumer 1) 2 K 1 20 K (see page 64) DT 2S *1 Differential temperature for 10 K K 10 the start of speed regulation (consumer 2) (see page 64) ANS2 *1 Rise (consumer 2) 2 K 1 20 K (see page 64) HND1 Manual mode relay 1 AUTO OFF/ON (see page 45) HND2 Manual mode relay 2 AUTO OFF/ON 1 to 10 (see page 45) PROG Software version of the solar control unit VERS Hardware version System scheme 10 system schemes can be achieved with the solar control unit. Selection via parameter "ANL" (see page 44). All system schemes include the "ANL 1" functions (system scheme 1): Dual-mode DHW heating Suppression of reheating by the boiler in conjunction with control units with KM BUS Maximum DHW cylinder temperature limit Service *1 Only adjustable with setting RPM > 0. 51

52 Function description System scheme (cont.) Auxiliary functions can be enabled for every system scheme. Collector limit temperature (see page 62) Collector cooling function (see page 62) Collector minimum temperature limit (see page 62) Frost protection function (see page 63) Reverse cooling function (see page 63) Interval function (see page 63) Heat statement (see page 64) Speed control (see page 64) 52

53 Function description System scheme (cont.) "ANL" = 1 Standard scheme Dual-mode DHW heating with suppression of reheating by the boiler in conjunction with control units with KM BUS Display Temperature differential control Determination of the temperature differential between collector temperature sensor S1 and cylinder temperature sensor S2. Solar circuit pump R1 on: Exceeding "DT E" Solar circuit pump R1 off: The actual temperature falls below the switch-off temperature differential "DT A" Cylinder temperature limit Solar circuit pump R1 off: When reaching the set cylinder temperature "S SL". Symbol "È" is shown. Suppression of reheating by the boiler in conjunction with control units with KM BUS Function enabled: The DHW cylinder is heated by the solar thermal system. Connection of the KM BUS to terminals 11 and 12 in the solar control unit. In the boiler control unit, coding address "67" defaults a third set DHW temperature. (This value must be below the first set DHW temperature). See the installation and service instructions of the boiler control unit. The DHW cylinder will only be heated by the boiler, if this set value cannot be achieved by the solar thermal system. Service Note In some boiler control units, the PCB must be replaced (see page 68). 53

54 Function description System scheme (cont.) "ANL" = 2 Dual-mode DHW heating with suppression of reheating by the boiler in conjunction with control units without KM BUS and/or control of the secondary pump of an external heat exchanger Display Suppression of reheating by the boiler in conjunction with control units without KM BUS Function enabled: The DHW cylinder is heated by the solar thermal system. A resistor simulates an actual DHW temperature that is 10 K higher (for connections, see the following table). The DHW cylinder will only be heated by the boiler, if the set DHW temperature cannot be achieved by the solar thermal system. System with an external heat exchanger S1 R1 S2 R2 The secondary pump R2 is started in parallel with the solar circuit pump. 54

55 Function description System scheme (cont.) Cylinder temperature sensor as PTC A IP 20, l, T V 50 Hz? N R2 N R1 N L Cylinder temperature sensor as NTC A IP 20, l, T V 50 Hz? N R2 N R1 N L B B C C D E D E C Resistor 20 Ω, 0.25 W (on-site) C Resistor 10 kω, 0.25 W (on-site) A Solar control unit wiring chamber B Contactor relay E To the boiler control unit; connection for cylinder temperature sensor D Cylinder temperature sensor of the boiler control unit Service 55

56 Function description System scheme (cont.) "ANL" = 3 Dual-mode DHW heating and thermostat function Display Thermostat function Output R2 is used for this function. Relay R2 switches subject to the temperature at S3 (see the following table). Different effects can be achieved by determining the start and stop temperatures: "NH E" < "NH A" "NH E" > "NH A" e.g. for reheating e.g. for utilising excess heat Thoff Thon R2on R2off Thon Thoff R2on R2off "ANL" = 4 Dual-mode DHW heating and auxiliary function Display Auxiliary function for DHW heating Connection of the anti-stratification pump at R2. Signal for starting the anti-stratification pump R2 via the KM BUS of the boiler control unit. This also heats the lower area of the DHW cylinder to the required temperature. 56 Note In some boiler control units, the PCB must be replaced (see page 68).

57 Function description System scheme (cont.) 1. Connect the KM BUS at terminals 11 and 12 in the solar control unit. 2. Program the second set DHW temperature at the boiler control unit. Installation and service instructions; boiler control unit 3. Adjust the fourth DHW phase at the boiler control unit. Danger DHW with temperatures in excess of 60 C can cause scalding. To limit the temperature to 60 C, install mixing equipment, e.g. a thermostatically controlled mixing valve (accessory). Install a mixer tap as anti-scalding device at the draw-off point. "ANL" = 5 Operating instructions, boiler control unit Dual-mode DHW heating, thermostat function and auxiliary function Display Output R2 enables the thermostat function (see page 56) and the auxiliary function (see page 56) to be achieved. Service 57

58 Function description System scheme (cont.) "ANL" = 6 Dual-mode DHW heating and maximum cylinder temperature control Display When exceeding the set cylinder temperature "S SL" (see page 53) the anti-stratification pump R2 will start. Excess heat is transferred, e.g. to the pre-heating stage. "ANL" = 7 Dual-mode DHW heating and anti-stratification Display Determination of the temperature differential between collector temperature sensor S2 and cylinder temperature sensor S3. Anti-stratification pump R2 on: Exceeding "DT 3E" Anti-stratification pump R2 off: The actual temperature falls below the stop temperature differential "DT 3A" "ANL" = 8 Dual-mode DHW heating, auxiliary function and anti-stratification with sensor S3 in DHW cylinder 2 (existing) Display The anti-stratification pump R2 circulates the heating water to prevent stratification (see page 58) and implements the auxiliary function (see page 56). 58

59 Function description System scheme (cont.) "ANL" = 9 Dual-mode DHW heating, auxiliary function and anti-stratification with sensor S3 in DHW cylinder 1 (retrofit) Display The anti-stratification pump R2 circulates the heating water to prevent stratification (see page 58) and implements the auxiliary function (see page 56). Service 59

60 Function description System scheme (cont.) "ANL" = 10 Dual-mode DHW heating, heating of consumer 2 via the three-way diverter valve Display Temperature differential control Determination of the temperature differential between collector temperature sensor S1 and cylinder temperature sensor S2. Solar circuit pump R1 on: Exceeding "DT 1E" Consumer 1 is being heated. Solar circuit pump R1 off: The actual temperature falls below the stop temperature differential "DT 1A" Determination of the temperature differential between collector temperature sensor S1 and cylinder temperature sensor S3. Solar circuit pump R1 and three-way diverter valve R2 on: Exceeding "DT 2E" Consumer 2 is being heated. Solar circuit pump R1 and three-way diverter valve R2 off: The actual temperature falls below the stop temperature differential "DT 2A" Cyclical heating If the DHW cylinder cannot be heated with priority ("PRIO" 1), the next consumer in line will be heated for an adjustable cycle time "tumw". After expiry of this time, the solar control unit checks the temperature rise at the collector during the cycle pause time "tsp". As soon as the start conditions for the consumer with priority ("PRIO" 1) have been met, that consumer will be heated again. Otherwise, the consumer with lower ranking will continue to be heated. Once the consumer with priority has reached its set temperature "S SL", no cyclical heating will be implemented. 60

61 Function description System scheme (cont.) Consumer 1 Parameters Delivered condition Setting range DT 1E 8.0 K K DT 1A 4.0 K K S1 SL 60 C 4 90 C Note "DT 1E" can be set at least 0.5 K higher than "DT 1A". "DT 1A/" can be set at least 0.5 K lower than "DT 1E". Consumer 2 Parameters Delivered condition Setting range DT 2E 8.0 K K DT 2A 4.0 K K S2 SL 60 C 4 90 C Note "DT 2E" can be set at least 0.5 K higher than "DT 2A". "DT 2A" can be set at least 0.5 K lower than "DT 2E". Parameters Delivered condition Setting range PRIO tsp 2 min 1 30 min tumw min 0 Priority consumer 1, no cyclical heating 1 Priority consumer 1, with cyclical heating 2 Priority consumer 2, with cyclical heating Service 61

62 Function description Collector limit temperature The solar circuit pump is switched OFF to protect the system components if the "NOT" temperature has been exceeded; the symbol " " flashes. Set value for "NOT" (see page 45). Setting parameters Delivered condition Setting range NOT 130 C C Note This function is disabled at setting 200 C. Collector cooling function The solar circuit pump will be switched off when the set cylinder temperature "S SL" is reached. If the collector temperature rises to the set maximum collector temperature "KMX", the pump will be switched ON long enough to enable this temperature to fall 5 K lower (the symbol "È" flashes). The cylinder temperature can then rise again, but only up to 90 C; at that point, the solar circuit pump is switched off (the symbol " " flashes). 1. Set "OKX" to "ON" (see page 45). 2. Select the "KMX" value. Setting parameters Delivered condition Setting range KMX 110 C C Minimum collector temperature limit Minimum starting temperature "KMN" that must be exceeded before the solar circuit pump can start. This prevents the pump starting too frequently (cycling). The pump is switched OFF, if the actual temperature falls 5 K below this temperature; symbol "e" flashes. 1. Set "OKN" to "ON" (see page 45). 2. Select the "KMN" value. 62

63 Function description Minimum collector temperature limit (cont.) Setting parameters Delivered condition Setting range KMN 10 C C Frost protection function Enable this function only when using water as heat transfer medium. The solar circuit pump will be switched ON to avoid collector damage, if the collector temperature falls below the "KFR" value. The symbol "e" is displayed if this function is enabled and flashes if the solar circuit pump is running. 1. Set "OKF" to "ON" (see page 45). 2. Select the "KFR" value. Setting parameters Delivered condition Setting range KFR 4 C C Reverse cooling function Enable only in systems with flat-plate collectors. The "ORUE" function only makes sense if the collector cooling function has been enabled (see page 62). The collector cooling function enables the heating of the DHW cylinder to a higher temperature than "S SL" (see page 53). In the evening, the pump will continue to run (symbol "È" flashes) until the DHW cylinder has been cooled down via the collector and the pipework to the set cylinder temperature "S SL". Set "ORUE" to "ON" (see page 45). Service Interval function Activate the interval function in systems where the collector temperature sensor is not in an ideal location to prevent a time delay in capturing the collector temperature. For this, the solar circuit pump is started for 30 s when the collector temperature rises by 2 K. Set "ORK" to "ON" (see page 45). 63

64 Function description Heat statement The heat statement is calculated from the temperature differential between the collector and cylinder temperature as well as the selected throughput (see service instructions "Vitosol"). 1. Set "OWMZ" to "ON" (see page 45). 3. Adjusting the frost protection of the heat transfer medium "MEDT". 4. If necessary, adjust the mixing ratio of the heat transfer medium "MED %". 2. Check the throughput at the flow meter of the Solar-Divicon at 100 % speed and set that value as "VMAX". MEDT setting Heat transfer medium 0 Water 1 Propylene glycol 2 Ethylene glycol 3 Viessmann heat transfer medium Setting parameters Delivered condition Setting range VMAX 5.0 l/min l/min MEDT MED % 40 % % Speed control Speed control is disabled at the factory ("RPM" set to 0, see page 45). It can only be enabled for relay output R1 (solar circuit pump). The solar circuit pump should not have its own speed control. Set multi-stage pumps to the required stage. Note When using pumps with their own variable speed control, set "RPM" to 0. The solar circuit pump will be switched ON, if "DT E" has been exceeded. If the temperature differential rises to "DT S" (differential temperature for the start of the speed control), then the speed is increased by 10% with every rise by the value selected in "ANS" (rise). 64

65 Function description Speed control (cont.) Setting parameters Delivered condition Setting range n1mn 30 % % DT S 10 K K ANS 2 K 1 20 K Example Speed in % 60 DT E =8 K 50 DT S =10 K 40 ANS =2 K Temperature differential in K Enabling speed control Set the required value for "RPM" (see page 45). 1 Standard solar circuit pumps (with integral auxiliary capacitor) 2 WILO pump with PWM input 3 GRUNDFOS pump with PWM input Service 65

66 Parts list Parts list When ordering spare parts Quote the part and serial no. (see type plate) and the position no. of the required part (as per this parts list). Obtain standard parts from your local supplier. 030 Strain relief pack, capacitor and fuse 040 Fuse, 4 A (slow) 050 Installation and service instructions 060 Operating instructions Parts 010 Collector temperature sensor 020 Cylinder temperature sensor 66

67 Specification Specification Rated voltage 230 V~ Rated frequency 50 Hz Rated current 4 A Power consumption 2 W (in standby mode 0.7 W) Protection class II Protection IP 20 D to EN 60529, ensure through design/installation Function Type 1 B to EN Permiss. ambient temperature during operation 0 to +40 C Installation in living spaces or boiler rooms (standard ambient conditions) during storage and transport -20 to +65 C Rated breaking capacity of the relay outputs at 230 V~: R1 0.8 A R2 4 (2) A Service 67

68 Appendix Appendix Replace the PCB in the stated boiler control units in conjunction with the following functions: Suppression of reheating by the boiler Auxiliary function for DHW heating, achieved by the solar control unit Control unit Vitotronic 200, type KW1, part no , Vitotronic 200, type KW2, part no , Vitotronic 300, type KW3, part no , Vitotronic 200, type GW1, part no Vitotronic 300, type GW2, Part no Vitotronic 333, type MW1, Part no Electronics PCB Part no part no Part no

69 Certificates Declaration of conformity We, Viessmann Werke GmbH & Co KG, D Allendorf, confirm as sole responsible body that the product Vitosolic 100 complies with the following standards: EN EN This product is designated _ in accordance with the following Directives: 2004/108/EC 2006/95/EC Allendorf, 1 April 2009 Viessmann Werke GmbH&Co KG pp. Manfred Sommer Service 69

70 Keyword index Keyword index A Anti-scalding protection...6, 57 Anti-stratification...58 Applicability...72 Automatic mode...44, 45 Auxiliary function for DHW heating...56 C Changing settings...45 Changing the fuse...48 Changing values...45 Checking sensors...47 Collector cooling function...62 Collector limit temperature...62 Collector temperature sensor...40 Commissioning...44 Cyclical heating...60 Cylinder temperature limit...53 Cylinder temperature sensor...41 D Declaration of conformity...69 E External heat exchanger...54 F Fault messages...47 Fitting the solar control unit...35 Frost protection function...63 H Hardware version...51 Heat statement...64 High limit safety cut-out...39 I Interval function...63 M Manual mode...45 Manual operation...45 Maximum collector temperature limit. 62 Maximum cylinder temperature control...58 Minimum collector temperature limit..62 N Navigation through the menu...44 O Operating steps...44 Overview of electrical connections...36 P Parts list...66 Power supply...42 Pump at R Pumps...36 R Relay test...45 Restoring the delivered condition...45 Reverse cooling function...63 S Scanning temperatures...46 Selecting the system scheme...44 Setting system parameters...45 Software version of the solar control unit...51 Solar circuit pump...36 Spare fuse...48 Speed control...64 Starting the solar control unit...44 Suppressing reheating Control units with KM BUS...53 Control units without KM BUS...54 Switching the power ON...44 T Temperature differential control...53, 60 Temperature sensor...41 Thermostat function

71 Keyword index Keyword index (cont.) V Valve at R

72 Printed on environmentally friendly, chlorine-free bleached paper Applicability Applicable for the Vitosolic 100, type SD1 Part no Viessmann Werke GmbH&Co KG D Allendorf Telephone: Fax: Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: Fax: Subject to technical modifications.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe.

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe. Installation and service instructions for contractors VIESMANN Electronic temperature differential control unit Vitosolic 200 Type SD4 For applicability, see the last page VITOSOLIC 200 1/2012 Please keep

More information

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and Installation and service instructions for contractors VIESMANN Solar-Divicon SR Part no. 7419 520 and 7419 521 Safety instructions Please follow these safety instructions closely to prevent accidents and

More information

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer Installation instructions for contractors VIESMANN Mixer extension kit For one heating circuit with mixer Mixer extension kit 5/2017 Safety instructions Please follow these safety instructions closely

More information

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no Installation and service instructions for contractors VIESMANN Vitotrol 300A Remote control, part no. 7438 364 VITOTROL 300A 3/2010 Please keep safe. Safety instructions Safety instructions Please follow

More information

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-G Type BW/BWS 301.A06 to A17, 5.9 to 17.0 kw Type WW 301.A06 to A17, 7.9 to 23.0 kw Heat pump, single and two-stage Type BWC 301.A06

More information

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMANN Extension AM1 Part no. 7429 152 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors Installation instructions for contractors VIESMANN Vitodens 200-W Type WB2C, 45 and 60 kw Wall mounted gas condensing boiler Natural gas and LPG version VITODENS 200-W 1/2010 Dispose after installation.

More information

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA Installation and service instructions for contractors VIESMANN Vitocell 340-M/360-M Type SVKA Type SVSA Combi cylinder 750 and 950 litre capacity VITOCELL 340-M/360-M 4/2009 Please keep safe. Safety instructions

More information

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit Installation and service instructions for contractors VIESMANN Vitotrol 200 RF Wireless remote control for one heating circuit For applicability, see the last page VITOTROL 200 RF 3/2011 Please keep safe.

More information

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no Installation instructions for contractors VIESMNN Extension E1 Part no. 7429 151 Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions

More information

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B

More information

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l Installation instructions for contractors VIESMANN Vitocell 300-B Type EVBA-A Dual mode DHW cylinder, 300 and 500 l VITOCELL 300-B 1/2017 Dispose after installation. Safety instructions Please follow these

More information

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITODENS 200-W. for contractors Service instructions for contractors VIESMANN Vitodens 200-W Type WB2B, 4.8 to 35.0 kw Wall mounted gas fired condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation. Installation instructions for contractors PYROMAT ECO PYROMAT ECO 8/2012 Dispose after installation. Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors Installation and service instructions for contracrs VIESMANN Vitronic 00 Type KOB, KOB Weather-compensated, digital boiler control unit For applicability, see the last page VITOTRONIC 00 /0 Please keep

More information

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A Installation instructions for contractors VIESMNN Vitocell 300-V/W Type EVI- DHW cylinder with internal indirect coil 160 to 500 l VITOCELL 300-V/W 3/2017 Dispose after installation. Safety instructions

More information

VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors Installation and service instructions for contracrs VIESMANN Vitronic 00 Type GWB Vitronic 300 Type GWB Weather-compensated, digital boiler control units For applicability, see the last page VITOTRONIC

More information

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracrs Vitronic 100 Type GC1B Digital boiler control unit For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 100 Product may not be exactly

More information

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference.

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference. Installation and Service Instructions for use by heating contracr Vitronic 300 Type GW2B Weather-compensated, digital boiler control units For use with Boiler models VD2A, VD2 and CT3 VITOTRONIC r 300

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 6/2011 Dispose after installation. Safety instructions Please

More information

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw VIESMANN VITOCAL 00-G Brine/water and water/water heat pump Single and two-stage, from 21 kw Technical guide Heat pump with electric drive for DHW and central heating in mono-mode or dual mode heating

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 111-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 111-W 4/2012 Please keep safe. Safety instructions For

More information

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 100-W 1/2012 Please keep safe. Safety instructions For

More information

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

SD2. Differential Controller. Operating and Installation Instructions F2 72.3 SD2 Differential Controller Operating and Installation Instructions F2 72.3 i Please follow the safety information and read these Instructions carefully before putting the system into operation. Safety

More information

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service Service instructions Function module FM443 solar module For contractors Read carefully prior to commissioning or service 6 720 615 516-03/2008 GB/IE Contents 1 Safety........................................

More information

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors Installation and service instructions for contractors VIESMANN Vitocal 200-S Type AWB 201.B04 to B13, C10, C13 Air source heat pump, split version for heating operation Type AWB-AC 201.B04 to B13, C10,

More information

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner VITOCROSSAL 200 2/2007 Dispose after installation. Safety instructions

More information

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation Operating instructions for system users VIESMANN Heating system with control unit for constant temperature operation VITODENS 100 2/2005 Please keep safe Safety instructions For your safety Please follow

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contracrs VIESMANN Videns 200-W Type B2HA, 80 and 100 kw Wall mounted gas condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS

More information

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit Service instructions for contractors VIESMANN Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit VITOLADENS 300-T 1/2007 Please keep safe. Safety instructions Safety instructions

More information

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Service instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler For applicability, see the last page VITORONDENS 200-T 6/2011 Please keep safe. Safety

More information

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses. Installation and service instructions for contractors VIESMANN Solar-Divicon and solar pump assembly Safety instructions Please follow these safety instructions closely to prevent accidents and material

More information

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 200-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 200-W Type B2HA, B2KA, 3.2 to 35 kw Gas council no. System boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 Combi boilers: 47-819-28;

More information

Service Instructions for use by heating contractor

Service Instructions for use by heating contractor Service Instructions for use by heating contracr Please file in Service Binder Vitronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating

More information

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler Installation instructions for contractors VIESMANN Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler VITORONDENS 200-T 5/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 111-W Type B1LA, 6.5 to 35.0 kw Gas condensing storage combi boiler Natural gas and LPG version Gas Council no.: 47-819-23; 47-819-24;

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJC, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council no.: 47 819 31, 47 819 32

More information

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions Lago SD3 Differential Controller with Speed Control Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment.

More information

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

VIESMANN. Operating instructions VITOTRONIC 200. for the system user Operating instructions for the system user VIESMANN Heating system with weather-compensated control unit Vitotronic 200, type KO1B, KO2B or KW6B VITOTRONIC 200 12/2012 Please keep safe. Safety instructions

More information

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors Installation and service instructions for contractors VIESMANN Vitocal 300-A Type AWO-AC 301.B11 to B14 Air/water heat pump with electric drive, 400 V~ For applicability, see the last page VITOCAL 300-A

More information

TR 0603mc U Solar Controller

TR 0603mc U Solar Controller TR 0603mc U Solar Controller Part #8718572810 Engineering Submittal Sheet 178 mm [7.00 inch] 8 90 mm [3.54 inch] 170 mm [6.69 inch] 170 mm [6.69 inch] 134 mm [5.28 inch] 106 mm [4.17 inch] 32 1.26 0.31

More information

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors Installation instructions for contractors VIESMANN Vitomax 200-HW Type M238 Oil/gas fired high pressure hot water boiler Combustion output 4.0 to 18.2 MW VITOMAX 200-HW 6/2007 Dispose after installation.

More information

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors Installation and service instructions for contractors VIESMANN Vitodens 343-F Type WS4A Compact Energy Tower with a gas fired condensing boiler as compact model Natural gas and LPG version (GC no) 47-819-08

More information

Heating controller Lago

Heating controller Lago Heating controller Lago Product brochure GB 10 Edition 02.08 Wall-mounted (Lago Basic 0101/1001 and Lago 0321) Boiler or control panel attachment (Lago 0201R) Simple operation and programming Automatic

More information

Operating instructions

Operating instructions Operating instructions Room controller 6 720 618 477-00.1RS Logamatic EMS RC35 programming unit For users Read carefully before use. 6 720 642 272 (10/2009) GB Overview of controls Overview of controls

More information

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. Edition 06.14 GB Operating and installation instructions Lago FB digital remote control Translation from the German 2014 Elster GmbH Safety Please read and keep in a safe place Please read through these

More information

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater Installation and service instructions for contractors VIESMNN EHE immersion heater 6 kw and 12 kw For installation in HW cylinders For applicability, see the last page EHE immersion heater 9/2014 Please

More information

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner Installation instructions for contractors VIESMANN Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner VITOCROSSAL 300 2/2013 Dispose after installation. Safety instructions Please

More information

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user Operating instructions for the system user VIESMANN Heating system with the Vitotronic 200 control unit, type HO1B, for weathercompensated mode VITODENS VITOLADENS VITOPEND 10/2013 Please keep safe. Safety

More information

Operating instructions

Operating instructions Operating instructions Control unit - CGL Zone 0.0 C Friday 3/0/08 : 6 Wolf GmbH Postfach 380 D-84048 Mainburg Tel. +49 (0)875/74-0 Fax +49 (0)875/74600 Internet: www.wolf-heiztechnik.de Document no.:

More information

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO Great Britain en Installation, user and service manual Control panel HMI Gas 310/610 ECO PRO Dear Customer, Thank you very much for buying this appliance. Please read through the manual carefully before

More information

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser Vitocal 300-A, type AWC-I and AW-O.1 Product description A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser & High operational reliability,

More information

Installation and operating instructions

Installation and operating instructions Installation and operating instructions Cascade module KM Wolf GmbH Postfach 1380 84048 Mainburg Tel. 08751/74-0 Fax 08751/741600 Internet: www.wolf-heiztechnik.de Part no. 30 62 449 Subject to modifications

More information

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail) 74 319 0400 0 G2484 en Installation Instructions Solar Energy Manager RVP502 Installation Place of installation In a dry room, e.g. in the boiler room Installation choices: - Control panel (in the panel

More information

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE 780EN www.caleffi.com Recess Mounted Heat Interface Unit - SATK series SATK0-60 series INSTRUCTIS FOR INSTALLATI, COMMISSIING AND MAINTENANCE Function The SATK series HIU allows independent control of

More information

Operating instructions

Operating instructions Operating instructions Solar thermal controller 7747006071-00.1 SD Solar thermal system with Logamatic SC40 For the Owner Please read carefully before operation. 7 747 017 474 GB (2007/08) OSW Contents

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B Operating instructions for the system user VIESMANN Digital time switch for the Vitodens 100-W, type WB1B DIGITAL TIME SWITCH 5/2008 Please keep safe. Safety instructions For your safety Please follow

More information

BM Programming Module. For the heating engineer Installation instructions

BM Programming Module. For the heating engineer Installation instructions For the heating engineer Installation instructions BM Programming Module WOLF GmbH Postfach 1380 84048 Mainburg Tel. 08751/74-0 www.wolf-heiztechnik.de Document no.: 3062612_201509 Subject to modifications

More information

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

VIESMANN. VITOSOL Flat-plate collectors and vacuum tube collectors Flat and pitched roof installation, and wall mounting.

VIESMANN. VITOSOL Flat-plate collectors and vacuum tube collectors Flat and pitched roof installation, and wall mounting. VIESMNN VITOSOL Flat-plate collectors and vacuum tube collectors Flat and pitched roof installation, and wall mounting Technical guide VITOSOL 100-FM/-F Flat-plate collector, type SV and SH For installation

More information

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors Installation and service instructions for contractors VIESMANN Vitodens 050-W Type BPJD, 6.5 to 35.0 kw Wall mounted gas condensing boiler For natural gas and LPG Gas Council Number: 47 819 31, 47 819

More information

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT Operating Instructions for use by heating contractor Vitotronic 100, type GC1B Multi boiler system with control unit for constant temperature operation For use with Boiler models VD2A, VD2 and CT3 Vitotronic

More information

Boiler controller Lambdatronic S 3200

Boiler controller Lambdatronic S 3200 Operating Instructions Boiler controller Lambdatronic S 3200 Version 50.04 - Build 05.04 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

Engineers manual. Under counter machines

Engineers manual. Under counter machines Table of Contents 1. INTRODUCTION... 3 1.1 1.2 1.3 INSTALLATION AND COMMISSIONING... 3 SERVICE AND REPAIRS... 3 MODIFICATION... 3 2. EXPLANATION OF SYMBOLS USED... 3 3. WARNING AND SAFETY INFORMATION...

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVL471 Heating and Domestic Hot Water Controller Basic Documentation RVL471 Heating and Domestic Hot Water Controller Basic Documentation Edition: 2.2 Controller series: C CE1P2524E 23.10.2002 Siemens Building Technologies HVAC Products 2/118 HVAC Products 23.10.2002 Contents

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O VIESMANN VITOCAL Air/water heat pumps Technical guide VITOCAL 300-A Type AWC-I and AW-O Up to 60 C flow temperature Modulating output range 3 to 9 kw Reversible air source heat pump with electric drive

More information

O CRC100. Comfort Room Controller (2015/01) en

O CRC100. Comfort Room Controller (2015/01) en 6 720 906 767-00.1O Comfort Room Controller 100 6 720 806 769 (2015/01) en 2 Contents Contents 1 Explanation of symbols and safety instructions..................... 3 1.1 Explanation of symbols.....................................

More information

Installation and Service Instructions for use by heating contractor. VITOTRONIC r 200 VITOTRONIC r 300-K IMPORTANT

Installation and Service Instructions for use by heating contractor. VITOTRONIC r 200 VITOTRONIC r 300-K IMPORTANT Installation and Service Instructions for use by heating contracr Vitronic 200, Type KW6B/HO1B Digital boiler control unit Vitronic 300-K, Type MW2C Weather-compensated, digital cascade control unit VITOTRONIC

More information

DeltaTherm FK * * Solid fuel boiler controller Manual for the specialised craftsman

DeltaTherm FK * * Solid fuel boiler controller Manual for the specialised craftsman DeltaTherm FK Solid fuel boiler controller Manual for the specialised craftsman Mounting Electrical connection Application examples Operation Troubleshooting *11204753* 11204753 Your mobile remote display

More information

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 0 l capacity Datasheet Part no. and prices: see pricelist VITOCELL 300-V Type EVA and EVI Vertical DHW cylinder made from stainless steel 5/2012 Product

More information

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 01 CONTENTS Special information 2 General information 3 Safety 5 Appliance description, cleaning, care & maintenance 7 Appliance

More information

USERS GUIDE. LOGIC+ Combi 24, 30, 35

USERS GUIDE. LOGIC+ Combi 24, 30, 35 USERS GUIDE LOGIC+ Combi 24, 30, 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

Operation Manual of Solar controller SR1568 for split solar system

Operation Manual of Solar controller SR1568 for split solar system Operation Manual of Solar controller SR1568 for split solar system Read the instruction carefully please before operation! Contents 1. Safety information... 4 1.1 Installation and commissioning... 4 1.2

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Public. Altherma by Daikin. Altherma Commissioning Service Field Settings

Public. Altherma by Daikin. Altherma Commissioning Service Field Settings Public Altherma by Daikin Altherma Commissioning Service Field Settings Altherma Service Settings There are several service codes that can be altered to maximise the efficiency of the Altherma system.

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

Quick Reference. Air to Water Heat Pump Series 4 Lot 1 Standard & Powerful Types

Quick Reference. Air to Water Heat Pump Series 4 Lot 1 Standard & Powerful Types Quick Reference Air to Water Heat Pump Series 4 Lot Standard & Powerful Types Estia Series 4 Standard Type Models: Hydro unit HWS-804XWHM3-E HWS-804XWHT6-E HWS-804XWHT9-E HWS-404XWHM3-E HWS-404XWHT6-E

More information

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

- Data Brochure Steam Control 279

- Data Brochure Steam Control 279 - Data Brochure Steam Control 279 D 279 12/07 The tekmar Steam Control 279 can operate a single on-off steam boiler or an on-off steam valve using outdoor reset. The control determines the on time of the

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual SR868C6 System Regulator for Solar Thermal Systems Display Panel Illustration Pos. Button on display panel Button description 1 Green lamp Power indication lamp 2 On/Off

More information

Heating Controller SDC Remote Heating Controller DHC

Heating Controller SDC Remote Heating Controller DHC Heating Controller SDC Remote Heating Controller DHC PARAMETER LIST EN0B-0565GE51 R0313 EN0B-0565GE51 R0313 Contents Contents 1 Software version...5 2 Access to the technician / OEM area...5 3 "Hydraulics"

More information

GHP AWO 38 Technical overview

GHP AWO 38 Technical overview Gas absorption heat pump 9 Technical overview single unit G&' &(')*ption heat pump components. 1 7 2 8 9 3 4 10 8 5 6 1 +),-.&/012 &0* ')-*34 5&1 2 G414*&/)* 3 G&' (-*ner 4 6)1,41'4* 5 6)7(-'/0)1 38&7(4*

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

For the operator/for the heating engineer. Operating and Installation Manual VRC 430. Weather compensator VRC 430

For the operator/for the heating engineer. Operating and Installation Manual VRC 430. Weather compensator VRC 430 For the operator/for the heating engineer Operating and Installation Manual VRC 430 Weather compensator GB VRC 430 For the operator Operating Manual VRC 430 Weather compensator VRC 430 Contents Appliance

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service.

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service. Strategy module FM458/CMC 930 For contractors Read carefully prior to commissioning or service. 6 720 803 196 (2011/06) GB / IE / AU Service instructions 2 1 Safety........................................

More information

Operating instructions

Operating instructions SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE Operating instructions Temperature Differential Controller inputs, 1 output These operating instructions are part of the product. US Read

More information