for MODEL KSU MAKE-UP AIR UNITS

Size: px
Start display at page:

Download "for MODEL KSU MAKE-UP AIR UNITS"

Transcription

1 Part # Installation, Operation and Maintenance Instructions for MODEL KSU MKE-UP IR UNITS Installation w/fan Pack Extension Down last Discharge Horizontal Discharge...6 Electrical Instructions...7 Table of Contents System Startup...8 Trouble Shooting...9 Maintenance...10 Dimensions and Weights...11 Documentation/Warranty...12 WRNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when you complete the job. This IOM is for installation, operation, and maintenance of a KSU unit. For information on installation and maintenance of heating or cooling options reference the following manuals: Direct Gas (Part # ) Evaporative Cooling (Part # ) Steam, Hot Water, DX and Chilled Water Coils, and Electric Heat (Part # ) GREENHECK P.O. OX 410 SCHOFIELD, WISCONSIN PH March 2000

2 Installation with Fan Package Extension efore beginning this installation: When locating this unit, make sure that there is room to access the unit from all sides. The inlet must be located at least 10 feet away from any exhaust vents. If this unit is direct fired gas without insulation, the clearance tolerance to combustibles is 6 on all sides, top, and bottom. D Exhaust Duct C Curb D Roof Opening Supply Duct E /2 Step 1 Roof Opening Determine the center of the exhaust and supply duct roof openings. The chart below shows the maximum recommended roof opening dimensions. These sizes can be smaller based on codes and ductwork sizes. Equipment Housing Size #1 #2 #3 - Max Roof Open. 25" 35" 47" - Max. Roof Open. 61" 83" 105" C - to of ducts 36" 48" 58" D - Duct to Edge of Open /2" 17 1 /2" 23 1 /2" Supply Duct to E - Equip /2" 81 1 /2" 88 1 /2" Roof Curb Metal Cover Step 2 Install Roof Curb and Equipment Center curb over roof openings and place on the roof. Level the curb and shim if necessary. ttach curb to roof and flash in place. To install equipment support, refer to the chart in step 1 for dimensional location based on KSU unit size. ttach to roof in the same manner as the curb, remove metal cover, flash to wooden nailer and reinstall cover. 1" Inside Flange Exhaust Supply Equipment Note: Equipment support height = Curb Height + 4. Step 3 Install Curb Extension Install curb extension over curb, use wood screws to lag in place. Prepunched holes are provided. Locate extension so the tall, louvered side is over the exhaust opening, as shown in illustration. Exhaust Ductwork by Others Supply Ductwork by Others Recommended Supply Ductwork Sizes Straight lower Duct Duct Size Size Length x x 13 37" x 14 47" x 16 54" x 20 68" x 24 81" x 26 96" Step 4 Install Ductwork Exhaust: Exhaust ductwork must be built in accordance with NFP 96 and any local codes. Ductwork terminating at the fan should be square in shape or of smooth transition so as not to to affect the fans performance. Supply: The chart at left shows the duct sizes and straight lengths recommended for optimal performance (MC Publication ). Using duct sizes less than the recommended lengths will affect fan performance. Good duct practices should be followed for the remaining ductwork. 2

3 Step 4 cont. The use of a duct adapter with the supply duct is strongly recommended to properly align the ductwork with the supply fan discharge. The duct adapter is only a guide and is not intended to be used as support for the ductwork. Exhaust Duct Installed Sealant Supply Duct with Duct dapter Installed Step 5 pply Sealant efore installing fans, apply a sealant around the perimeter of the exhaust and supply duct adapter to isolate the fan and minimize vibration. Model CUE Exhaust Fan Step 6 Install Exhaust Fan Install CUE exhaust fan on curb extension. Fasten with self-tapping sheet metal screws through existing holes in curb cap. NFP 96 requires the exhaust fan be hinged. Greenheck offers an optional hinge kit with restraining cables and a grease trap with drain connection. Install these options at this time. NOTE: Installing the exhaust fan prior to the supply unit will allow for easier installation of options. Lifting Lugs (4 places) Step 7 Install Supply Unit Use a crane and a spreader bar hooked to the factory lifting lugs (as shown in the diagram) to lift and center the KSU unit on the curb and equipment support. Use selftapping sheet metal screws to fasten unit to the curb and equipment support through holes provided. Electrical, coil, and/or gas connections can be made at this time. Use caution to avoid damaging exhaust fan when installing supply unit. Model KSU Supply Unit Exhaust Fan Electrical Cable Complete Installation Illustration shows the complete wired installation. Note that the electrical power cable for the exhaust fan is routed through the side breather tube. The cable should be of sufficient length to allow the fan to hinge open to the point where the restraining cables support the fan. 3

4 Installation with Down Discharge efore beginning this installation: When locating this unit, make sure that there is room to access the unit from all sides. The inlet must be located at least 10 feet away from any exhaust vents. If this unit is direct fired gas without insulation, it has a 6 clearance tolerance to combustibles on all sides, top, and bottom. For Installations using square curb and equipment support: Square Curb Roof Opening /2 Step 1 Roof Opening Determine the center of the supply duct roof opening. The chart below shows the maximum recommended roof opening dimensions. These sizes can be smaller based on codes and ductwork sizes. Housing Size #1 #2 #3 - Max Roof Open. Sq. 25" 35" 47" Supply Duct to - Equip /2" 81 1 /2" 88 1 /2" Rectangular Curb C* For Installations using rectangular curb: Roof Opening /2 /2 C* C- Determine equal dimension for these 3 locations (varies per curb size) Supply Ductwork by Others Ductwork with duct adapter installed Sealant /2 Equipment C* Recommended Supply Ductwork Sizes Straight lower Duct Duct Size Size Length x x 13 37" x 14 47" x 16 54" x 20 68" x 24 81" x 26 96" Step 2 Install Roof Curb and Equipment For square curbs, center curb over roof opening as shown in first installation diagram at left. For rectangular curbs, center curb on 3 sides of roof opening, as shown in second installation diagram, by determining C dimension (varies per unit/curb size). For either installation, level the curb and shim if necessary. ttach curb to roof and flash in place. If equipment support is needed, refer to chart in step 1 for dimensional location based on KSU unit size. ttach to roof in the same manner as the curb. Remove metal cover, flash to wooden nailer and reinstall cover (see pg. 2). Step 3 Install Ductwork The chart at left shows the duct sizes and straight lengths recommended for optimal performance (MC Publication ). Using duct sizes less than the recommended lengths will affect fan performance. Good duct practices should be followed for the remaining ductwork. The use of a duct adapter with the supply duct is strongly recommended to properly align the ductwork with the supply fan discharge. The duct adapter is only a guide and is not intended to be used as support for the ductwork. Step 4 pply Sealant efore installing fan, apply a sealant around the perimeter of the supply duct adapter to isolate the fan and minimize vibration. 4

5 Step 5 Install Supply Unit Use a crane and a spreader bar hooked to the factory lifting lugs (as shown in the diagram) to lift and center the KSU unit on the curb and equipment support. Use selftapping sheet metal screws to fasten unit to the curb and equipment support through holes provided. Electrical, coil, and/or gas connections can be made at this time. Lifting Lugs (4 places) Supply Unit Complete Installation Illustration shows the complete installation of a downblast KSU. 5

6 Installation with Horizontal Discharge efore beginning this installation: When locating this unit, make sure that there is room to access the unit from all sides. The inlet must be located at least 10 feet away from any exhaust vents. If this unit is direct fired gas without insulation, it has a 6 clearance tolerance to combustibles on all sides, top, and bottom. Step 1 Mounting the Unit Unit can be mounted on a curb with an equipment support (fig.1) or on two equipment supports (figs. 2&5). Unit can be mounted hanging (fig. 6), inline as part of an air handling system, or base mounted. Mounting hardware to be provided by others. (fig.1) Equipment (fig.2) Curb Housing Size #1 #2 #3 Curb to - Equip. CL 76 1 /2" 81 1 /2" 88 1 /2" Equipment Equipment Step 2 ttach Ductwork to Unit Discharge Chart and drawing (fig.3) below shows opening size (ID) and location for a discharge collar. lso included is the recommended straight duct lengths for optimal performance. Greenheck recommends attaching ductwork to collar using a rubber duct section at the unit to eliminate vibration. Step 3 ttach Ductwork to Unit Intake Chart and drawing (fig.4) below shows dimensions for supply opening (ID). ttach ductwork to perimeter flange using a rubber duct section at the unit to eliminate vibration. Design the remaining ductwork for minimal losses to allow the unit to operate properly. Duct Size/Location and Intake Dimensions: Housing lower Straight C D E F Size Size Duct Length* / / / / / / / *MC recommended minimum straight duct lengths for optimum performance Typical Installations D Discharge Collar Dimensions (fig.3) C Curb Height E Intake Opening Dimensions (fig.4) F Curb H DISCHRGE DISCHRGE INTKE INTKE (fig.5) Roof mounted with weatherhood, mounted on two equipment supports. Ductwork is attached to discharge collar with rubber boot transition. (fig.6) Shown as an indoor hanging installation with intake and discharge ductwork installed. (Hanging support structure for unit is by others). 6

7 Electrical Instructions efore connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached inside the door(s) of the unit. ll wiring should be done in accordance with the National Electrical Code NSI/NFP-70 latest edition and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code. The equipment must be properly grounded. Electrical Knockouts CUTION! For direct gas units: If any of the original wire must be replaced, the replacement wire must have a temperature rating of at least 105 C, except for energy cutoff or sensor lead wire which must be 150 C. DNGER! High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician. Unit Name Plate Control Center Door CUE Exhaust Fan Field Wiring to CUE NOTE: ny wiring running through the KSU unit in the airstream must be protected by flexible metal conduit, metal clad cable or raceways. Sequence for wiring KSU unit: For units without control centers: The motor nameplate is to be used for determining the voltage and amperage required by the unit. For units with control centers: 1. The units nameplate states the voltage and total amperage required. The main feeder supplying power to the unit should be sized for the labels voltage and amperage. 2. The main power line should be connected to the disconnect switch. Make sure that the disconnect lugs are securely tightened. 3. Connect control panel wiring to terminal strip in the control center. Greenheck s standard control voltage is 120/60/1. 4. Wire any remote temperature selectors (optional) at this time. These wires should be shielded cable if they are to be run with other power wires. 5. When an optional convenience outlet is provided, a separate power supply must be provided to the receptacle. This circuit must be on a ground fault breaker. 6. If an electric heater is supplied with the unit, a separate power source is required for the heater. CUTION ny wiring deviations may result in personal injury or property damage. Greenheck is not responsible for any damage to, or failure of the KSU unit caused by incorrect final wiring. 7

8 System Startup For proper unit function and safety, follow everything in this startup procedure in the order presented. This to be done after the electrical and gas connections are complete. Special Tools Required Voltage meter Incline manometer or equivalent (Direct Gas Units) Tachometer Thermometer (Direct Gas Units) mperage meter 1. Check Voltage efore starting the unit compare the supplied voltage with the units nameplate voltage and the motor voltage. 2. Check lower Rotation If the blower is rotating in the wrong direction, the unit will move some air but not perform properly. To check the rotation, open the blower access door and run the blower momentarily to determine the rotation. To reverse the rotation, turn the power off and use the following procedure: For single phase units, rewire the motor per the instructions on the motor. For three phase units, interchange any two power leads. This can be done at the motor starter. 3. ir Volume Check and Measurement long with the building balance, the units air volume (cfm) should be measured and compared with its rated air volume. This unit is flexible for varying air volume, but the actual air volume should be known for making final adjustments. The most accurate way to measure the air volume is by using the pitot traverse method in the ductwork away from the blower. Other methods can be used but should be proven and accurate. To adjust the air volume, change the fan rpm or the system losses. See Trouble Shooting section in this guide. 4. Measure Motor Voltage, mperage and Fan rpm ll access doors must be installed except the control center door and direct gas controls door. Measure and record the input voltage and motor amperage(s). To measure the fan rpm, the blower door will need to be removed. Minimize measurement time because the motor may over amp with the door removed. Compare measured amps to the motor nameplate full load amps and correct if over amping. See the Trouble Shooting section in this guide. 5. Settings for Optional Components Optional Freeze Protection: This shuts down the blower if the output temperature is below the set point. timer allows the blower to operate during startup. This will reset when turned off. Typical settings are: Discharge temperature = 45 F Timer = 5 minutes lower Housing Optional 2 Hour Time Delay: This allows the unit to operate for up to 2 hours after the control panel switch has been turned off. The timer is adjustable. Rotation 8

9 Trouble Shooting The following is a cause and correction list for common problems with these units. lso included in the unit owners packet are the Maxitrol (or Modusnap) Systems owner s manual plus the Flame Safeguard owner s manual. The sequence of operation should be used to help determine where the problems could be when trouble shooting the unit. lower Unit Symptom Possible Cause Corrective ction lower fails lown fuse or open circuit breaker Replace fuse or reset circuit breaker and to operate check amps roken fan belt Replace Defective motor or capacitor Replace Motor starter overloaded Reset starter and check amps Motor over amps Cfm too high Check cfm and adjust drives if needed Static pressures are higher or lower If higher, ductwork should be improved than design If lower, fan rpm should be lower lower rotation is incorrect Check rotation and correct Motor voltage incorrect Check motor nameplate and supplied voltage Motor horsepower too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Insufficient airflow Unit damper not fully open djust damper linkage or replace damper motor System static pressure too high Improve ductwork to eliminate losses using good duct practices lower speed too low Check for correct drives and rpm with catalog data Dampers or registers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Repair Elbows, or other obstructions may restrict fan outlet Correct or improve ductwork elt slippage djust belt tension Too much airflow lower fan speed too high Check for correct fan rpm Filter(s) not in place Install filters Insufficient static pressure (SP) Induce SP into system ductwork (airflow resistance) Excessive noise Wheel rubbing on housing Center wheel or vibration Loose wheel on shaft Tighten wheel setscrew Loose motor or blower sheave Tighten sheave setscrew elts too loose djust belt tension after 24 hours of operation elts too tight Loosen to maintain 3/8 deflection per ft. of span between sheaves Worn belt Replace Motor base or blower loose Tighten mountings bolts Worn bearings Replace earing and drive alignment Realign Motor out of balance Replace Wheel out of balance Replace or rebalance Sheaves eccentric or out of balance Replace or rebalance ccumulation of material on wheel Clean wheel and housing 9

10 Maintenance Greenheck recommends these procedures to insure trouble free operation of this unit. It is especially important to maintain gas heater units for clean and efficient operation. Most unit failures can be attributed to poor setup or poor maintenance. record of maintenance performed on this unit should be kept. This information will provide essential information if problems are encountered. section at the back of this manual is provided for recording the units maintenance history. CUTION: When performing any maintenance on this unit be sure that the power is disconnected and cannot be accidently turned on. The control center disconnect can be locked in the off position. 2 weeks after startup Check belt tension - elts tend to stretch after a period of time. They should be periodically checked for wear and tightness. pproximately 3 /8" of deflection per ft. of span between sheaves is standard for belt tightness. When replacing belts, use the same type as supplied with the unit. Matched belts should always be used on units with multigroove pulleys. Rotation lower Housing Too Tight Too Loose Motor elt Tension djustment Screw Replacement of belts should be accomplished by loosening the tensioning device to the point where the belts can be removed by hand. Do not force belts on or off as this may cause breakage of cords leading to premature belt failure. elts should be adjusted as above. NOTE: For motors of 1 HP or less a smaller bracket is used to attach to blower, Every 3 Months The filter in the unit should be inspected at least every 3 months. Depending on the environment, filters could require changing or cleaning more or less often. The filters can be slid out of either side of the unit. If washable filters are installed, they can be washed in warm soapy water. n adhesive spray can be applied to increase filter efficiency. If disposable filters are installed, check by holding up to a light source. If light cannot pass through the filter, it should be replaced. Replacement filters should be of the same manufacturer and size. When reinstalling filters be sure to install with the airflow in the correct direction indicated on the filter and with any factory spacers that came with the unit. Yearly ll bearings are factory lubricated and require no further lubrication under normal use. Normal use being considered -20 F to 180 F and in a relatively clean environment. Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to the exterior surfaces only. Removing dust and grease buildup on motor housing assures proper motor cooling. Greasing of motors is intended only when grease fittings are provided. Many fractional motors are permanently lubricated and require no further lubrication. Motors supplied with grease fittings should be greased in accordance with manufacturer's recommendations. When motor temperature does not exceed 104 F (40 C), the grease should be replaced after 2000 hours of running time as a general rule. Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe operation. Routinely check all fasteners for tightness. 10

11 ELECTRICL CONNECTION DISCONNECT SWITCH LIFTING LUGS E C Dimensions and Weights D ELEVTION VIEW CONTROL CENTER DOOR PLN VIEW Curb Height KSU SIZE C D E pprox Weight** Unit FPE FILTERS QTY 3 4* 10 SIZE 20x25 16x20 20x25 20x20 *Qty 4 of each size listed **Weight based on unit with direct fired gas unit weights will vary per heating options and blower motor combinations. C F G E D FPE Model CUE Sizes C D-Sq. E-Sq. F G ,100,120, , , , , , , Note: Dimensions are shown with an 8 Roof Curb. FPE Model: Last digit is housing size. See CUE literature for complete dimensions and weights of CUE fan. Curb Selection Chart Housing Size Rectangular Curb Square Curb Equip 1 30/ / / w/fpe 30/ W/FPE 40/ W/FPE 52/ FPE - Fan Pack Extension Curb Dimensional Chart Curb Size D W x L W x L 30/ /2 x 74 1 / /4 x 82 3 /4 40/ /2 x 84 1 / /4 x 92 3 /4 52/ /2 x 96 1 / /4 x / /2 x 28 1 / /4 x 36 3 / /2 x 38 1 / /4 x 46 3 / /2 x 50 1 / /4 x 58 3 /4 30/ /2 x 64 1 / /4 x 72 3 /4 40/ /2 x 86 1 / /4 x 94 3 /4 52/ /2 x / /4 x /4 GPNS Curbs Equipment 35 /8 D 11 /2 11 /2 3/4 3/4 Wood Nailer 8" or 12" Insulation 8" or 12" Wood Nailer 117/8 11

12 Maintenance Documentation Job Information Job Name: ddress: City: State: Zip: Phone: Fax: Contact Person: Service Organization: ddress: City: State: Zip: Phone: Fax: Work Done y: Name Plate Information Model: Volts: Hertz: Phase: mps: Mark: Supply Hp: Exhaust Hp: Serial Number: Field Start-Up Documentation ctual Voltage: Hertz: Phase: ctual mperage: lower Rotation Correct ir Volume Design CFM ctual CFM Maintenance Date Time Notes: Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. ny units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. The motor is warranted by the motor manufacturer for a period of one year. Should the motor prove defective during this period, it should be returned to an authorized motor service station. Greenheck will not be responsible for any installation or removal costs. Due to continuing research, Greenheck reserves the right to change specifications without notice. GREENHECK P.O. OX 410 SCHOFIELD, WISCONSIN PH KSU IOM FS Rev. 2 March 2000

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual MODEL DG Direct Fired Gas Make-Up Air Part #459335 Installation, Operation and Maintenance Manual Natural or LP gas ETL Listed R **IMPORTANT** ALL FACTORY PROVIDED LIFTING LUGS MUST BE USED WHEN LIFTING

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS PART # 538 Model BCF Belt Drive Centrifugal Cabinet Fans Installation, Operation, and Maintenance Manual Please read and save these instructions for future reference. Read

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 464496 Model LFC Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or

More information

Installation, Operation and Maintenance Manual **FOR YOUR SAFETY**

Installation, Operation and Maintenance Manual **FOR YOUR SAFETY** MODEL IGX Make-Up Air Unit Installation, Operation and Maintenance Manual Part # 462876 **FOR YOUR SAFETY** If you smell gas: 1. Open windows. 2. Don t touch electrical switches. 3. Extinguish any open

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Part #459023 Energy Recovery Ventilators Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL

HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL HMD Heated Makeup Direct: A Direct Fire Make-Up Air Unit INSTALLATION, OPERATION AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance procedures for standard units

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 462888 Model MSCF Modular Small Cabinet Fan Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

Installation, Operation and Maintenance Instructions. for MAKE-UP AIR UNITS

Installation, Operation and Maintenance Instructions. for MAKE-UP AIR UNITS Part # 456857 Installation, Operation and Maintenance Instructions for MAKE-UP AIR UNITS with Direct Fired Gas Heater Option (for natural or LP gas) R C ETL Listed R WARNING: Improper installation, adjustment,

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual Modular Electric Heater Electric Heat Module Electric Duct Insert RECEIVING AND INSPECTION Upon receiving

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 479677 Energy Recovery Ventilator Model Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual Modular Electric Heater Electric Heat Module Electric Duct Insert RECEIVING AND INSPECTION Upon receiving

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 479677 Model Energy Core Ventilator Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

14" - 24" CLASSIC Direct Drive Fans

14 - 24 CLASSIC Direct Drive Fans 14" - 24" CLSSIC Direct Drive Fans T14F T16F, G T18F, G T24F, G R R Ventilation Systems 14" - 24" Fiberglass Fans 16" - 24" Galvanized Fans Page 1 of 11 USER'S MNUL and INSTLLTION GUIDE TBLE OF CONTENTS

More information

MODEL PVF INDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITS Installation, Operation, and Maintenance Manual

MODEL PVF INDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITS Installation, Operation, and Maintenance Manual RETIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Part # 461006 MODEL PVF INDIRECT GS FIRED FURNCES FOR ENERGY RECOVERY UNITS Installation, Operation, and Maintenance Manual Model PVF, Indirect Gas Furnace,

More information

Modular Packaged Unit Installation, Operation and Maintenance Manual. Modular Packaged Cooling Unit

Modular Packaged Unit Installation, Operation and Maintenance Manual. Modular Packaged Cooling Unit Modular Packaged Unit Installation, Operation and Maintenance Manual Modular Packaged Cooling Unit FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 464664 Model AX Axial Fan Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate

More information

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual FAN POWERED TERMINALS Receiving Inspection Prior to removing the shipping material, visually inspect the packing materials. There

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 453284 Model BCF Centrifugal Cabinet Fans Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Part #461006 Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 453284 Centrifugal Cabinet Fans Model BCF Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

MODEL DG / DGX (Direct Spark)

MODEL DG / DGX (Direct Spark) MODEL DG / DGX (Direct Spark) Make-Up Air Unit Part # 464043 Installation, Operation and Maintenance Manual FOR YOUR SAFETY If you smell gas 1. Open windows 2. Don t touch electrical switches 3. Extinguish

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

B SERIES ELECTRIC FURNACE

B SERIES ELECTRIC FURNACE MISSISSAUGA, ONTARIO L5T 1H9 TEL.: 905-670-2500 FAX: 905-795-8311 CUSTOMER SERVICE TEL.: 1-888-882-7626 B SERIES ELECTRIC FURNACE! WARNING 1. The user MUST contact a specialized contractor when a failure

More information

User Manual Box Exhaust Fan Series (Belt Drive)

User Manual Box Exhaust Fan Series (Belt Drive) User Manual Box Exhaust Fan Series (Belt Drive) 36" Box Exhaust Fan with Three Wing Blade Box with Aluminum Shutter 54" Box with Cone 800-779-3267 sales@schaeferfan.com www.schaeferfan.com 2013 Schaefer

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

FOR YOUR SAFETY FOR YOUR SAFETY

FOR YOUR SAFETY FOR YOUR SAFETY Compact Direct Fired Heater Installation, Operation, and Maintenance Manual If you smell gas: 1. Open windows. 2. Don t touch electrical switches. 3. Extinguish any open flames. FOR YOUR SAFETY FOR YOUR

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 482886 Models DG, DGX, TSU, VSU Direct Gas Make-Up Air and Industrial Space Heat Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY.

KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters. Table of Contents FOR YOUR SAFETY. KEES, INC. Installation & Maintenance Manual DFG Series Direct Gas Fired Make-up Air Heaters Table of Contents FOR YOUR SAFETY Page # Topic If you smell gas: 1 Description of Operation 1 Receiving the

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER. IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. U.S.A. WARNING FOR YOUR

More information

Horizontal & Horizontal Quiet Blower Coils

Horizontal & Horizontal Quiet Blower Coils MANUAL INSTALLATION Horizontal & Horizontal Quiet Blower Coils BCH / BCHQ Series v200 Issue Date: 05/19/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety

More information

Installation Instructions

Installation Instructions Installation Instructions Safety Labeling & Rules Installation Requirements Location / Clearances Wiring Air Distribution Ductwork Connections Start-Up Maintenance Hoisting / Rigging PAS090H000 PAS090L000

More information

Air Storm Fans. Air Storm 54 Fiberglass Fan Installation and Operation Manual

Air Storm Fans. Air Storm 54 Fiberglass Fan Installation and Operation Manual Air Storm 54 Fiberglass Fan Installation and Operation Manual Table of Contents GrowerSELECT General Page... 3 Safety... 4 Warning Labels... 4 Installation... 5 Operation Safety... 5 Maintenance Safety...

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual MPA Modular Plenum Array Installation, Operation, and Maintenance Manual This publication contains the installation, operation and maintenance procedures for standard units of the MPA: Modular Plenum Array.

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

Installation Instructions Remote Blowers

Installation Instructions Remote Blowers Installation Instructions Remote Blowers Models: REMP3, REMP16 Suitable for use in a household cooking area. Suitable for use with solid state controls. To complete this blower, a Dacor hood assembly or

More information

ACT Cartridge Dust Collector

ACT Cartridge Dust Collector IOM-101-1 ACT Cartridge Dust Collector Installation and Operation Manual ACT Dust Collectors CAUTION! Accidents happen, be careful and always follow all local and federal regulations! Fires and explosions

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481153 Model IG/IGX Make-Up Air Unit Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL BC(E) SERIES INDOOR / OUTDOOR MANUFACTURED BY GENERAL INFORMATION PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: TELEPHONE: INSTALLATION

More information

Installation Instructions Part No , Part No Part No

Installation Instructions Part No , Part No Part No Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11

More information

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with

More information

Installation Instructions

Installation Instructions Installation Instructions Over the Range Microwave Oven BEFORE YOU BEGIN (Read these instructions completely and carefully.) IMPORTANT IMPORTANT Save these instructions for local inspector s use. Observe

More information

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4 Installation & Operating Manual BESF Box Ventilator USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

Drying Tumblers. Troubleshooting. 120 Pound Capacity 170 Pound Capacity. Refer to Page 5 for Model Numbers. Part No August 2007

Drying Tumblers. Troubleshooting. 120 Pound Capacity 170 Pound Capacity. Refer to Page 5 for Model Numbers. Part No August 2007 HIGH LOAD READY MEDIUM TEMPERATURE LOW LOW AIR FLOW NON REV REV PUSH TO START 10 5 15 0 50 40 60 0 30 10 20 Drying Tumblers 120 Pound Capacity 170 Pound Capacity Page 5 for Model Numbers Troubleshooting

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL AIR HANDLERS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL AIR HANDLERS INSTALLATION, OPERATION AND MAINTENANCE MANUAL IMAH-3 September 2001 AIR HANDLERS ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION ELECTRIC HEAT S THRU 05 5 THRU Supersedes: (9) (00) 0-5 FOR SINGLE PACKAGE CONDITIONERS THRU TON SINGLE PACKAGE HEAT PUMPS THRU 5 TON GENERAL This instruction contains all the

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4 Installation & Operating Manual BESB Box Ventilator USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

Installation and Maintenance Manual IM 1102

Installation and Maintenance Manual IM 1102 Installation and Maintenance Manual IM 1102 Parallel Fan Powered Variable Air Volume (VAV) Terminal Box Group: Applied Air Systems Part Number: IM 1102 Date: October 2010 Model MQFVI5 Table of Contents

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Axial Document 478529 Model RA Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions PRH Series Plenum Heaters Installation & Maintenance Instructions Dear Owner, Congratulations! Thank you for purchasing this new heater manufactured by Marley Engineered Products. You have made a wise

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

LC Series - Light Commercial Pump Station Installation and Operation Manual

LC Series - Light Commercial Pump Station Installation and Operation Manual LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump

More information

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater

Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual. Modular Electric Heater Standard and Modular Electric Heaters and Inserts Installation, Operation, and Maintenance Manual Modular Electric Heater Electric Heat Module Electric Duct Insert RECEIVING AND INSPECTION Upon receiving

More information

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual RSIF Power Venter USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

Installation and Maintenance Manual IM 782-8

Installation and Maintenance Manual IM 782-8 Installation and Maintenance Manual IM 782-8 Destiny Indoor Air Handler Group: Applied Air Systems Part Number: IM 782 Date: May 2015 Sizes 002 through 030 Horizontal Model Vertical Model Table of Contents

More information

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Please read and save these instructions. Read carefully before

More information

Installation Instructions

Installation Instructions Installation Instructions Above the Cooktop Microwave Oven JVM60 and JVM65 Questions? Call -800-56- or Visit our Website at: GEAppliances.ca BEFORE YOU BEGIN Read these instructions completely and carefully.

More information

XPS-ProDry User s Guide Dryer Base

XPS-ProDry User s Guide Dryer Base XPS-ProDry User s Guide XPS-ProDry User s Guide Dryer Base For Use with Inkjet Imaging Systems Manual Part#: M-3120 Revision: August 2005 XPS-ProDry User s Guide Written by Frank Mauri & John Brand Published

More information

Air Storm Fans. Air Storm 18 Fiberglass Fan Installation and Operation Manual

Air Storm Fans. Air Storm 18 Fiberglass Fan Installation and Operation Manual Air Storm 18 Fiberglass Fan Installation and Operation Manual Table of Contents GrowerSELECT General Page...3 Safety...4 Warning Labels...4 Installation...5 Operation Safety...5 Maintenance Safety...5

More information

Gas-Fired Indoor and Outdoor Duct Furnaces

Gas-Fired Indoor and Outdoor Duct Furnaces July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001 Bulletin No. HIMAH August 2002 Part Number 4346B001 (Replaces HIM71A, August 2002) Installation & Operations Manual Air Handler Unit Table of Contents Inspection...2 Shipment of Units Handling Suspended

More information

Installation Electric Dryers Instructions 01

Installation Electric Dryers Instructions 01 Installation Electric Dryers Instructions 01 Questions? Call 800.GE.CARES (800.432.2737) or visit our Web site at: GEAppliances.com This is the safety alert symbol. This symbol alerts you to potential

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

Understanding Fan System Effects

Understanding Fan System Effects Fan Application FA/101-99 A technical bulletin for engineers, contractors and students in the air movement and control industry. Understanding Fan System Effects The air moving industry uses a common term

More information

Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer

Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS Installation & Operating Manual 3001806 03.02 USA CAN BESF Box Ventilator READ AND SAVE THESE INSTRUCTIONS 1200 Northmeadow Parkway, STE 180 Roswell, GA 30076 (770) 587-3238 (800) 255-2923 Fax (770) 587-4731

More information

GALAXY FLOOR MACHINE

GALAXY FLOOR MACHINE OPERATION MANUAL GALAXY FLOOR MACHINE IMPORTANT SAFETY INSTRUCTIONS WARNING: Failure to observe these instructions can cause personal injury to machine operator or bystanders. WARNING: Shock or electrocution

More information

Operation Manual. Instructions for Installation, Operation & Maintenance. PortaPac 5-, 8 and 10-ton Portable Air Conditioners

Operation Manual. Instructions for Installation, Operation & Maintenance. PortaPac 5-, 8 and 10-ton Portable Air Conditioners Operation Manual PortaPac 5-, 8 and 10-ton Portable Air Conditioners A AirPac, Incorporated AirPac Technology Park 888 Shenandoah Shores Road Front Royal, Virginia 22630 U.S.A. Toll Free 888-324-7722 Web:

More information

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS R-410A - C MODELS COMFORT PACK PACKAGED THRU-THE-WALL AIR CONDITIONER WITH ELECTRIC HEAT INSTALLATION AND MAINTENANCE INSTRUCTIONS National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215)

More information