Carbon Dioxide based Heat Pump Dryer in Food Industry

Size: px
Start display at page:

Download "Carbon Dioxide based Heat Pump Dryer in Food Industry"

Transcription

1 1 Carbon Dioxide based Heat Pump Dryer in Food Industry J. Sarkar 1, S. Bhattacharyya, M. Ram Gopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur West Bengal, India Abstract Drying is one of the common phenomena in food industry. Heat pump assisted mechanical dryer is used in lot of processes such as fruit drying, milk powder production. In food industry, due to the problem of ozone layer depletion and global worming, most of the conventional refrigerants are required to be replaced by some eco-friendly refrigerants. Carbon dioxide is one of the natural refrigerant which can be used in heat pump dryers in food processing applications due to its eco-friendliness, higher volumetric capacity, good heat transfer properties, high temperature heating capability, etc. Modeling of heat pump dryer is complex due to both heat and mass transfer. Ambient conditions (temperature and humidity) influence the performance of heat pump dryer. In the present investigation, the simulation models of open and closed heat pump dryers have been developed to investigate the performance with carbon dioxide as a refrigerant. Finally performance based comparisons have been done with two other conventional refrigerants R22 and R134a, which are generally used in heat pump dryers. Comparison results show that the CO 2 based heat pumps can give comparable performance (slightly better) with respect to R22 and R134a based heat pumps (irreversibility in the expansion valve is higher whereas that in the gas cooler is lower). CO 2 can become a best alternative refrigerant for drying applications. Keywords: CO 2 heat pump, heat pump dryer, food processing, simulation, performance. 1. Introduction Large quantities of agricultural products are dried to extend shelf-life, improve taste, enhance appearance and reduce transportation cost. Drying of food is complex phenomenon, behavior of drying rate with time is depending on the drying materials, although in general the constant period followed by falling rate period is exhibit within total time in the heat drying. In the junction of two-period, the moisture content in the material is called critical moisture content 1 Corresponding author; jahar@mech.iitkgp.ernet.in (J. Sarkar); Tel

2 2 [1]. Better understanding of the effect of drying conditions on the product quality and energy consumption of the equipment has promoted the use of heat pump cycle for drying applications. A heat pump dryer (HPD) is simply an integration of a basic refrigeration cycle with a thermally designed drying chamber. HPD offers several key advantages over other drying systems. It enables close control of the drying conditions, namely, drying air temperature, humidity and flow rate, resulting in better product quality. It reduces energy consumption through efficient regeneration of the drying energy by recovering the latent heat from the drying air. Further, with HPD operations, stage-dryings comprising combinations of hot and cold drying conditions can be carried out. This mode of drying operation is extremely important for delicate products that are sensitive to thermal conditions. Also, HPD ensures a consistent output of hygienically dried products. Depending on the operating temperature, heat pump drying is two types: I) Low temperature drying: Medicinal herbs and spices (specialty crops) such as ginseng, echinacea, feverfew, mother-wort, etc. are heat sensitive and required to be dried at low temperatures (30-40oC) to reduce the risk of loss in nutrient content and damage to physical properties which are important aspects considering their high commercial value. II) High temperature drying required in forage processing for dehydrated alfalfa products (pellets and cubes). The optimum moisture content of forages for cubing and pelleting is less than 10%. High-temperature drying is typically done in rotary drum dryers, where air temperatures are maintained in the range from 200 o C to 800 o C at the inlet to 60oC to 95 o C at the outlet. Pneumatic drying/conveying in a rotary drum dryer does not closely control heat and residence time resulting in under-dried stems and overdried leaves. This results in loss of nutritious leaf fraction and increases the susceptibility of highmoisture cubes and pellets to spoilage during overseas transport. Lot of research is going on drying of agricultural material, product and fruits to optimize the systems and process improvements [2-4]. Choosing of refrigerant for HPD is became a very critical due to the duel prospects of performance and environmental effect. Due to high ODP, R12, which was using for HPD in the earlier days, was replaced by R22. But now-a-day, most of the HPDs are using R134a instead of R22 due lower zero ODP and lower GWP (Table 1), although the value is very higher. So, due to the problem of ozone layer depletion and global worming, most of the conventional refrigerants are required to be replaced by some eco-friendly refrigerants. Carbon dioxide is one of the natural refrigerant which have been gained very importance recently [5], can be used in heat pump dryers in food processing applications due to its eco-friendliness, higher volumetric capacity, good heat transfer properties, high temperature heating capability, etc. Schmidt and coworkers have done Thermodynamic and experimental analyses of CO2 heat pump dryer in laundry recently [6-8]. In the present study, performance comparisons of R22, R134a and R744 heat pump dryers based on both energy and exergy analyses. The design issues of the heat transfer

3 3 components for all R22, R134a and R744 based HPDs have been discussed. Although different types of configurations can be used for HPD (Fig. 1), the simple configuration of HPD (a) is used for this study. Fig. 1. Heat Pump Dryer Configurations (E: Evaporator, C: Condenser/Gas cooler, D: Dryer) Table 1. Comparison of R22, R134a and R744 as refrigerants Refrigerant NBP C. P. C. T. ODP GWP Flammability Toxicity ( o C) (bar) ( o C) R22 (CHClF 2 ) No Yes R134a (C 2 H 2 F 4 ) No Yes R744 (CO 2 ) No No R22: Chlorodifluoro Methane, R134a: Tetrafluoro Ethane, R744: Carbon dioxide 2. Performance analysis Thermodynamic cycle of air in the closed heat pump dryer is shown in psychometric chart (Fig. 2) contains following processes: (i) a1-a3: cooling and dehumidifying in evaporator, (ii) a3-a4: Sensible heating in condenser/gas cooler, (iii) a4-a1: Cooling & humidifying in dryer. T-s diagrams of heat pump dryer for R22 or R134a and that for R744 are shown in Figs 3 and 4

4 4 respectively. Main difference of R744 cycle with the conventional cycle is the gas cooler instead of condenser, where the refrigerant is in the supercritical state, so instead of condensation the R744 gas is cooled by gas cooler at constant pressure. The following assumptions have been made for the performance analysis: 1. Compression process is adiabatic but non-isentropic. 2. Refrigerant at evaporator outlet is considered as saturated vapor. 3. Refrigerant at condenser outlet is considered as saturated liquid. 4. Evaporation and compression processes are isobaric 5. Heat transfer with the ambient has been neglected 6. Air at the evaporator outlet or the gas cooler inlet is considered as saturated (relative humidity is 100 %). 7. Outlet air condition from the dryer is same as the inlet condition to the evaporator. 8. Temperature approach (AT) for both the evaporator and the condenser/gas cooler is taken as 5 o C Fig. 2. Thermodynamic cycle of air in closed HPD From the energy balance in the evaporator, the cooling load for cooling and dehumidification of air is given by: Qev = m r ( h1 h4) = m a ( ωa 3)( Ta1 Ta 3) ( ωa 1 ω a3) (1) and the heating load in sensible heating of air is given by: Q = m h h = m ω T T (2) ( ) ( )( ) gc r 2 3 a a3 a4 a3 Power input to the compressor:

5 5 cp = gc ev = r ( 2 1 W Q Q m h h ) (3) Cooling coefficient of performance is given by: COP = Q W = h h h h (4) c ev cp ( ) ( ) Fig. 3. T-s diagram R22 & R134a heat pump dryer Fig. 4. T-s diagram R744 heat pump dryer Moisture extraction rate (MER) and specific moisture extraction rate (SMER) are the important performance measures of heat pump dryer, which are given by: MER = m ω ω ) (5) a( a1 a4 SMER = MER W c (6)

6 6 3. Numerical calculation A computer code has been written based on energy and exergy balance equations incorporating the property codes CO2PROP (based on Span and Wagner correlations [9]) for R744 and REFPROP [10] for R22 and R134a. Although the AT is attained at point 4 in the evaporator (T T = ), In the condenser the AT may be attained at saturated vapor point or a3 4 AT point 2, so the temperature approach condition is mathematically written as for R22/R134a HPD: h2 h min ( t 3 2 ta4), t2 t a3+ ( ta4 ta3) = AT (7) h2 h3 For CO2 system, the entire temperature range is divided into elemental sub-ranges to find the minimum temperature between refrigerant (AT) and the gas cooler pressure is set as the optimum compressor discharge pressure (bar), given by [11], P = t 0.17t t (8) dopt, c e c 2 Valid for evaporation temperatures between 20 C and 20 C and cooler exit temperatures: between 30 C and 60 C. The detailed algorithm of computer code is given bellow: 1. Give all the input parameters: t a1, ω a1, t, T, m a4 R a. 2. Assume ω a3 and take corresponding saturated temperature t a3. 3. t 1 = t a3 -AT and ωa4 = ωa3. 4. Find the state points of refrigerant (1, 2,3, 4) by cycle simulation satisfying AT 5. Find cooling load and refrigerant mass flow rate using Eqn. (1): 6. Find heating load and new value of ω a3 using Eqn. (2). 7. If the new value of ω a3 is not matching with old one, find new t a3 corresponding to new value and repeat the steps Find performance parameters COP c, MER, SMER and irreversibilities. 4. Result and discussion Results are presented in Table 2 for unit mass flow rate of air (1 kg/s) and input parameters: ta1 = 30 o C, t 4 80 o a = C, inlet moisture content of evaporator ω a1 = 0.02 kg/kg of dry air and reference temperature T R. Evaporator outlet saturated air temperatures are 11.5 o C, 13.0 o C and 12.4 o C for R22, R134a and R744 respectively. Results clearly show that due to the high system pressure the volumetric capacity of R744 is very lager compared to others. Another advantage for R744 is the smaller pressure compared to others, although the high system pressure can make some difficulty in design of components. COP of R744 based heat pump dryer is 10 % higher than that of R134a, whereas 7 % lower than that of R22. In term of moisture extraction rate also R22 is best compared to others. SMER of R744 system is 11% higher than that of R134a

7 7 and 4% lower than that of R22 systems. For optimum evaporator inlet moisture content of kg/kg, system is giving maximum cooling COP as shown in Fig 5. This type of behavior is exhibit due to the nature of saturated line in psychometric chart. Table 2. Performance Comparison for R22, R134a and R744 HPD Refrigerant ω a1 ω a4 r p COP c V c 3 kj m MER kg/min SMER kg/kwh R R134a R Fig. 5. Variation of COP with evaporator inlet moisture content Table 3. Component irreversibilities Refrigerant I CP (%) I EXP (%) I EV (%) I GC (%) I R R134a R The irreversibility analysis of the components show that due to the gliding temperature in the gas cooler, irreversibility of the gas cooler for R744 heat pump dryer is much smaller than that for R22 and R134a heat pump dryers. Due to the huge pressure drop and near critical operation, irreversibility of expansion device for R744 HPD is much larger than that for R22 and R134a HPD. In the actual heat exchanger design temperature approach for R744 system can be lower compared to R22 and R134a due to better heat transfer properties [12].

8 8 5. Conclusion The performance-based comparison of R744 based heat pump dryer has been done with two other conventional refrigerants R22 and R134a based heat pump dryer in terms of both 1 st and 2 nd laws and the following conclusions can be drawn: 1. R744 based heat pump dryer gives better performance than that of R134a whereas poor performance than that of R22 2. Irreversibility of expansion device for R744 is higher whereas that of gas cooler is smaller that of R22 and R134a. 3. There is some optimum moisture content for which the system can give the maximum performance due to behavior of psychometric chart. 4. Use of expansion turbine instead of throttling device can improve the system performance of R744 HPD significantly. 5. Because of the superior environmental properties and favorable heat transfer properties of R744 compared to R22 and R134a, the use of R744 as refrigerant in heat pump dryer in near future is promising. References 1. Arora CP. Refrigeration and air-conditioning, 2 nd Ed. Tata McGraw Hill Prasertsan S, Saen-saby P. Heat pump drying of agricultural materials, Drying Tech 1998; 16(1,2); Oktay Z, Hepbasli A. Performance evaluation of a heat pump assisted mechanical open dryer, Energy Conv Magmt 2003; 44; Teeboonma U, Tiansuwan J, Soponronnarit S. Optimization of heat pump fruit dryers, J Food Engg 2003; 59; Kim MH, Pettersen J, Bullard CW. Fundamental process and system design issues in CO 2 vapor compression systems, Prog Energ Comb sc 2004; 30; Schmidt EL, Klocker K, Flacke N, Steimle L. Applying the transcritical CO2 process to a drying heat pump, Int J Refrig 1998; 21(3); Klocker K, Schmidt EL, Steimle L. Carbon dioxide as a working fluid in drying heat pumps, Int J Refrig 2001; 21(3); Neksa P. CO 2 heat pump systems, Int J Refrig 2002; 25; Span R, Wagner W. A new equations of state for Carbon dioxide covering the fluid region from triple point temperature to 1100 K at pressure up to 800 MPa, J Phys Chem Ref Data 1996; 25; NIST database REFPROP version 6.0, USA. 11. Sarkar J, Bhattacharyya S, Ramgopal M. Optimization of a transcritical CO 2 heat pump cycle for simultaneous cooling and heating applications, Int J Refrig 2004; 27(8); Sarkar J, Bhattacharyya S, Ramgopal M. Transcritical carbon dioxide based heat pumps: Process heat applications. Int Ref A/c conf, Purdue, USA.

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical

More information

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER THERMAL SCIENCE: Year 2016, Vol. 20, No. 1, pp. 267-277 267 PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER by Nurettin YAMANKARADENIZ a, K. Furkan SOKMEN d, Salih COSKUN a*, Omer KAYNAKLI b,

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP Paul Maina and Zhongjie Huan mainap@tut.ac.za and huanz@tut.ac.za Department of Mechanical Engineering, Tshwane University of Technology P.O Box Private Bag X680

More information

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.

More information

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Performance of a Transcritical CO 2 Heat Pump for Simultaneous Water Cooling and Heating

Performance of a Transcritical CO 2 Heat Pump for Simultaneous Water Cooling and Heating Performance of a Transcritical CO Heat Pump for Simultaneous Water Cooling and Heating J. Sarkar, Souvik Bhattacharyya, and M. Ramgopal Abstract This paper presents the experimental as well as the simulated

More information

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XXI, NR. 1, 2014, ISSN 1453-7397 Feiza Memet A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

More information

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170

More information

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou

More information

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Available online at   ScienceDirect. Energy Procedia 109 (2017 ) 56 63 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

η second law = Second law efficiency

η second law = Second law efficiency EXERGY ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION CYCLE BASED AUTOMOTIVE AIR CONDITIONER USING ECO FRIENDLY REFRIGERANTS Vijender Singh Saini 1, Balvinder 2, Pardeep Kumar 3 1 M.Tech Scholar, 2,3 Assistant

More information

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system archives of thermodynamics Vol. 37(2016), No. 4, 55 72 DOI: 10.1515/aoter-2016-0027 Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning Available online at www.sciencedirect.com Systems Engineering Procedia () 6 International Conference on Risk and Engineering Management (REM) Thermodynamic analysis of air cycle refrigeration system for

More information

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER Nurettin YAMANKARADENIZ 1, K. Furkan SOKMEN 2, Salih COSKUN 1,*, Omer KAYNAKLI 3, Bilsay PASTAKKAYA 4 1 Uludag University, Vocational School of

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

More information

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants 454 Journal of Scientific & Industrial Research Vol. 72, July 2013, pp. 454-460 Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants P. Thangavel 1* and

More information

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer GRD Journals- Global Research and Development Journal for Engineering Volume 2 Issue 6 May 2017 ISSN: 2455-5703 Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer Gokul G Nair Dr. Jeoju

More information

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation Thermodynamic Comparison Using HFO-1234yf and HFO-1234ze in the Refrigeration s and in Applications R. S. Mishra Department of Mechanical Engineering, Delhi Technological University, Delhi, India Article

More information

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution

More information

A Comparison Between Refrigerants Used In Air Conditioning

A Comparison Between Refrigerants Used In Air Conditioning A Comparison Between Refrigerants Used In Air Conditioning Derya Özkan, Özden Agra and Özlem Çetin University of Yildiz Technical University, Turkey Corresponding email: tumer@yildiz.edu.tr SUMMARY It

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,

More information

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Satish parmar 1, Ravindra Randa 2 1M.TECH. Scholar, Department Of Mechanical

More information

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation Use of Hydrocarbons in Low Temperature Circuit in Terms of First Law and Second Law of Four Stage Cascade Refrigeration of Semen Preservation R.S. Mishra Department of Mechanical Engineering, Delhi Technological

More information

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser

More information

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling ISSN 2395-1621 Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot #1 Student, Mechanical

More information

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM Suhail Ahmad Khan Department of Mechanical Engineering, Aligarh Muslim University, Aligarh (India) ABSTRACT Energy analysis

More information

Thermodynamics II Chapter 5 Refrigeration

Thermodynamics II Chapter 5 Refrigeration Thermodynamics II Chapter 5 Refrigeration Mohsin Mohd Sies Fakulti Kejuruteraan Mekanikal, Universiti Teknologi Malaysia Objectives Introduce the concepts of refrigerators and heat pumps and the measure

More information

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek Department of Flow, Heat and Combustion Mechanics, Ghent University UGent,

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER Alka Bani Agrawal* and A.C.Tiwari 1 Department of Mechanical Engineering, R.G.T.U., Bhopal M. P. (INDIA) *E-mail : alk_agr@yahoo.co.in

More information

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Lalit Narayan, Abhishek Arya 2,2 M. Tech. Scholar, Associate Professor,,2 Scope College of Engineering, Bhopal, India Abstract: The

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

Chapter 10. Refrigeration and Heat Pump Systems

Chapter 10. Refrigeration and Heat Pump Systems Chapter 10 Refrigeration and Heat Pump Systems Learning Outcomes Demonstrate understanding of basic vaporcompression refrigeration and heat pump systems. Develop and analyze thermodynamic models of vapor-compression

More information

Chapter 9. Refrigeration and Liquefaction

Chapter 9. Refrigeration and Liquefaction Chapter 9 Refrigeration and Liquefaction Refrigeration is best known for its use in the air conditioning of buildings and in the treatment, transportation, and preservation of foods and beverages. It also

More information

Brazed Plate Heat Exchanger for CO Applications

Brazed Plate Heat Exchanger for CO Applications Brazed Plate Heat Exchanger for CO Applications www.kaori-bphe.com CO 2 (R744) Due to global warming, climate change phenomenon, and rising restriction on the use of high GWP synthetic refrigerant; replacing

More information

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Comparative assessment for drop in replacement of R134a in domestic refrigerator. Comparative assessment for drop in replacement of R134a in domestic refrigerator. Pravin K. Katare Research Scholar, Department of Mechanical Engineering, G.H.Raisoni College of Engineering Digdoh Hill,

More information

Waste Heat Recovery Analysis of CO 2 Refrigeration Systems

Waste Heat Recovery Analysis of CO 2 Refrigeration Systems Poster P.3.2-1 - Waste Heat Recovery Analysis of CO 2 Refrigeration Systems Vishaldeep Sharma, Brian Fricke and Pradeep Bansal Oak Ridge National Laboratory, Oak Ridge, Tennessee, USA Abstract: This paper

More information

Chapter 11 REFRIGERATION CYCLES

Chapter 11 REFRIGERATION CYCLES Thermodynamics: An Engineering Approach Seventh Edition in SI Units Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011 Chapter 11 REFRIGERATION CYCLES Mehmet Kanoglu University of Gaziantep Copyright

More information

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Shubham Rangari 1, Shubham Mahakalkar 2, Shubham Tiple 3, Praharsh Marathe 4, Sameer Bansod 5, Sunnyraj Katam 6, Suraj Nagrare

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND

VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND Fongsaward S. Singharajwarapan 1 and Nattaporn Chaiyat 2 1 Groundwater Technology Service Center, Chiang

More information

Evaluation of HCFC Alternative Refrigerants

Evaluation of HCFC Alternative Refrigerants Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R29 as Substitution to & Mixture of Them in Vapour Compression System Pawan Kumar Mishra #1, Amol Tripathi *2 #RIT Department of Mechanical Engineering Department, RGPV,Bhopal

More information

Design & Fabrication of Hybrid Cooler

Design & Fabrication of Hybrid Cooler IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Design & Fabrication of Hybrid Cooler Shashank Chauragade Mukul Kshirsagar

More information

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of

More information

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Pawan Kumar Mishra #1, Amol Tripathi *2 # RIT Department of Mechanical Engineering Department,

More information

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle. Refrigeration Cycle Reading Problems 10-1 10-5, 10-7, 10-9 10-11, 10-14, 10-39 Definitions a refrigeration system removes thermal energy from a low-temperature region and transfers heat to a high-temperature

More information

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation Methods for Improving Thermodynamic Energy and Exergy Performance of Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants in Primary Circuit and TIO 2 Nano Particles Mixed with

More information

JJMIE Jordan Journal of Mechanical and Industrial Engineering

JJMIE Jordan Journal of Mechanical and Industrial Engineering JJMIE Jordan Journal of Mechanical and Industrial Engineering Volume 9 Number 4, August.21 ISSN 199-666 Pages 289-296 Thermodynamic Analysis of R12a and Dimethylether Refrigerant Mixtures in Refrigeration

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Mr. Subodh S. Deshpande Department of Mechanical Engineering M.G.M.s College of Engineering

More information

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With

More information

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties

More information

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression

More information

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant A.N. Korshetti 1, Dr.V.N.Raibhole 2, N.A. Kumbhar 3 KJ s Trinity C.O.E., Pune, Maharashtra, India 1 M.E.S.

More information

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type

More information

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm

More information

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION Kazimierz MACZEK Jaros aw MÜLLER Kazimierz WOJTAS TECHNICAL UNIVERSITY of CRACOW Institute of Thermal Engineering and Air Protection

More information

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Gaurav #1, Raj Kumar* 2 1# Research Scholar, Department of Mechanical Engineering,

More information

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn: Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,

More information

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant International Journal of Refrigeration 28 (2005) 1302 1307 www.elsevier.com/locate/ijrefrig Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant Tomoichiro

More information

Mathematical Simulation of Longan Fruit Drying

Mathematical Simulation of Longan Fruit Drying Mathematical Simulation of Longan Fruit Drying Aree Achariyaviriya, Somchart Soponronnarit and Jirawan Tiansuwan ABSTRACT The objectives of this study were to develop a mathematical model and to simulate

More information

Environment Protection Engineering

Environment Protection Engineering Environment Protection Engineering Vol. 38 212 No. 4 DOI: 1.5277/EPE1244 BUKOLA OLALEKAN BOLAJI*, ZHONGJIE HUAN* COMPUTATIONAL ANALYSIS OF THE PERFORMANCE OF OZONE-FRIENDLY ALTERNATIVE REFRIGERANTS IN

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

Heat Pump Fluidised Bed Dryer with CO 2 as Refrigerant Measurements of COP and SMER

Heat Pump Fluidised Bed Dryer with CO 2 as Refrigerant Measurements of COP and SMER Heat Pump Fluidised Bed Dryer with CO 2 as Refrigerant Measurements of COP and SMER Trygve M. Eikevik, Ingvald Strømmen, Odilio Alves-Filho Norwegian University of Science and Technology (NTNU) Department

More information

Thermodynamics I. Refrigeration and Heat Pump Cycles

Thermodynamics I. Refrigeration and Heat Pump Cycles Thermodynamics I Refrigeration and Heat Pump Cycles Dr.-Eng. Zayed Al-Hamamre 1 Content Introduction The Reversed Carnot Cycle The Ideal Compression Refrigeration Systems Deviation from the ICRS Selection

More information

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment

More information

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study

More information

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK

More information

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Experimental performance evaluation of heat pump by using CO 2 as a refrigerant To cite this article: V K Venkatesh et al 2016

More information

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration 11.1 Introduction Preservation of foods is a vital processing step in food processing. There are

More information

Homework Chapter2. Homework Chapter3

Homework Chapter2. Homework Chapter3 Homework Chapter2 2/1 A storage tank holds methane at 120 K, with a quality of 25 %, and it warms up by 5 C per hour due to a failure in the refrigeration system. How long time will it take before the

More information

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS International Journal of Scientific & Engineering Research Volume 3, Issue 7, July-2012 1 EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS Rahul ukey, Sharad chaudhary Abstract Electricity

More information

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible

More information

TRANSCRITICAL CO 2 SYSTEM

TRANSCRITICAL CO 2 SYSTEM STUDY OF CAPILLARY TUBE FOR TRANSCRITICAL CO 2 SYSTEM 1 JADHAV PRAVIN, 2 NEERAJ AGRAWAL 1 K. B. P. Collegee of Engineering Satara, Maharashtra, India 2 Dr.B.A.T..U.Lonere Raigad,Maharashtra,India ABSTRACT

More information

Transcritical Carbon Dioxide Microchannel Heat Pump Water Heaters: Part II - System Simulation and Optimization

Transcritical Carbon Dioxide Microchannel Heat Pump Water Heaters: Part II - System Simulation and Optimization Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 ranscritical Carbon Dioxide Microchannel Heat Pump Water Heaters: Part

More information

Analysis of Vapour Compression Refrigeration System with Refrigerants R134a, R143a, R152a, R290 and R32

Analysis of Vapour Compression Refrigeration System with Refrigerants R134a, R143a, R152a, R290 and R32 www.ijird.com June, 201 Vol Issue 6 ISSN 2278 0211 (Online) Analysis of Vapour Compression Refrigeration System with Refrigerants,,, and Ramesh P. Sah Assistant Professor, Department of Mechanical Engineering

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System Available online at www.ijapie.org International Journal of Advanced Production and Industrial Engineering IJAPIE-SI-IDCM 606 (2017) 24 30 Special Issue on INNOVATIVE DESIGN & COMPUTATIONAL MODELLING Assessment

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1222 1229 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Evaluation of COP in Refrigeration System by using Different Refrigerants

Evaluation of COP in Refrigeration System by using Different Refrigerants Evaluation of COP in Refrigeration System by using Different Refrigerants Jeetendra Kumar Patel 1, Yogesh Parkhi 2, Rajesh Soni 3 1 M. Tech (Thermal Engg.) 2, 3 Associate Professor, Dept. of ME, SORT,

More information