1 International Journal of Automotive and Mechanical Engineering (IJAME) ISSN: (Print); ISSN: (Online); Volume 10, pp , July-December 2014 Universiti Malaysia Pahang DOI: EXPERIMENTAL ANALYSIS OF MICROCHANNEL CONDENSER USING R134a AND DROP IN SUBSTITUTE HYDROCARBON MIXTURE OF R290 AND R600a V.W. Bhatkar 1* V.M. Kriplani 2 and G.K. Awari 3 1* Department of Mechanical Engineering, G. H. Raisoni College of Engineering, R. T. M. Nagpur University, Maharashtra, India. * vijaybhatkar2009@gmail.com Phone: , Faculty of Mechanical Engineering, G. H. Raisoni College of Engineering, Nagpur, , Maharashtra, India. Phone: vilayatrai.kriplani@raisoni.net 3 Tulsiramji Gaikwad-Patil College of Engineering & Technology, Nagpur, India. ABSTRACT Microchannel condensers are widely used in automobile and household air conditioners with R134a as a refrigerant. In order to reduce the global warming potential as well as the refrigerant charge, hydrocarbon mixture of R290 and R600a (50:50 % by mass) was used as a drop in substitute to R134a in the vapour compression refrigeration system. Versatile vapour compression refrigeration system of 1 ton of refrigeration capacity was designed, developed and fabricated for testing different refrigerants. Various parameters such as ambient temperature in the condenser cabin, different condensation and evaporation temperatures, different mass flow rates of refrigerant and air can be controlled precisely in the test rig. Experiments were performed using R134a and hydrocarbon mixture of R290 and R600a (50:50 % by mass) for condensation temperature of 44 C and evaporation temperature ranging from -15 to 15 C. Refrigerant charge was reduced by 45 % with the hydrocarbon mixture of R290 and R600a (50:50 % by mass) over R134a. Performance parameters such as compressor power consumption increases by 13.3 %, coefficient of performance reduced by 43 %, refrigeration capacity increased by %, condenser capacity increased by % and the product of overall heat transfer coefficient and surface area of condenser was increased by % by using hydrocarbon mixture of R290 and R600a (50:50 % by mass) over R134a with the microchannel condenser at condensation temperature of 44 C and evaporation temperature of 0 C. It is suggested to use an environmental friendly refrigerant, hydrocarbon mixture of R290 and R600a (50:50 % by mass) as a drop in substitute to the conventional refrigerant R134a in the automobile, household air conditioning and refrigeration systems. Keywords: Coefficient of performance; hydrocarbon mixture; refrigerant; condenser capacity; compressor power consumption. 1993

2 Experimental analysis of microchannel condenser using R134a and drop in substitute hydrocarbon mixture of R290 and R600a INTRODUCTION Presently hydrofluorocarbon (HFC) 134a refrigerant is used in the automobile and household air conditioning systems in most of the countries. Thermodynamic properties of R134a are good but the global warming potential (GWP) is 1430 which is quite high considering the human health and environmental norms. Keeping in view the GWP of R134a, it is an urgent need to find the alternative refrigerants [1, 2]. As per latest European norms, the refrigerants which are having GWP more than 150 cannot be used in the automobile air conditioning systems [3]. Hydrocarbons (HCs) are natural refrigerants, having negligible GWP of 4, environmentally friendly, non-toxic, chemically stable, compatible with many materials and miscible with mineral oils. Major hydrocarbons under consideration are propane (R290), iso-butane (R600a), n- butane and mixture of propane and iso-butane in different proportions by mass. Besides this, the zeotropic refrigerant mixtures of hydrocarbon refrigerants have potential to enhance the performance and efficiency of a vapour compression refrigeration (VCR) system due to the temperature gliding effect [4, 5]. Latent heat of hydrocarbon refrigerant is nearly twice than that of HFC and hydrochlorofluorocarbon (HCFC) refrigerants. Performance of HC refrigerant is better than R134a but the problem with these refrigerants is that they are flammable. Density of hydrocarbon refrigerant is nearly 40 % of HFCs and HCFCs, thus the refrigerant required in the system reduces drastically [6]. In the household refrigerators, the possibility of explosion by flammability is negligible because half amount of HC s can be charged compared HFC s and HCFC s [7]. Some simple safety devices such as a ventilation system and a leakage detector can be installed to overcome the flammability problem in large size refrigeration and air conditioning systems [8]. The improvement in refrigeration cycle performance can be done by lowering the compressor power consumption, increasing the condenser heat rejection capacity or reducing the difference between condenser and evaporator pressures [9-12]. Microchannels are viewed as being responsible for reducing the ozone depletion potential by enabling the use of smaller amounts of environmentally harmful fluids, decreasing the green house gas emissions by improving component and system energy efficiencies [13-15]. The successful applications of microchannel heat exchangers in automotive industries also opens up a new frontier and creates a positive momentum for other industries such as residential and commercial heating, ventilating, air conditioning and refrigeration (HVACR) [3]. Several types of compact heat exchangers are employed in small refrigeration, air-conditioning and heat pump systems [16]. There are significant differences between large round tubes and the smaller noncircular tubes in the relative magnitudes of gravity, shear and surface tension forces, which determine the flow regime established at a given combination of liquid and vapor-phase velocities [17]. A microchannel tube with heat transfer enhancement characteristics is taken as one potential solution for system performance enhancement with reduction in the refrigerant charge. The pressure drop in flat tubes is expected to be less than circular tubes due to a smaller wake area. For the same reason, noise and vibration are less in flat tube heat exchangers as compared to circular tubes [18-21]. In recent years, new condenser design concept called sub-cooling parallel flow (SPF) is provided in the microchannel condenser which enhances the system performance in which the receiver-dryer is integrated with condenser core before the last one or two refrigerant passes. The performance of microchannel condenser is dependent on different parameters such as refrigerant charge, size of the receiver, sub-cooling area, 1994

3 Bhatkar et al. /International Journal of Automotive and Mechanical Engineering 10 (2014) pass structure, position of the receiver with respect to the condenser passes and liquidvapor separation in the receiver [22]. If the hydrocarbon refrigerant charge in the VCR system is below 150 g the chances of explosion are nil even though all the refrigerant comes out of the system, as the lower flammability limit dose not reach to the flammable level even though the room size is very small (4m 4m 4m) [23]. Pure propane has high pressure and pure iso-butane has low pressure at the working conditions so both are not perfect drop in substitute for R134a. In the experimental investigation of substituting R134a with R436A (a mixture of R290 and R600a with a mass ratio of 56/44) in a 238 L domestic refrigerator without any modification in a refrigeration cycle, results showed that in comparison to the base refrigerator working with R134a, the energy consumption per day was reduced by 5.3 % [24]. Design of Experiment EXPERIMENTAL SET UP Experimental set up was designed and fabricated for 1TR (ton of refrigeration) VCR system with the air cooled condenser as shown in Figure 1. Air heaters were provided in the condenser compartment for increasing the condensation temperature, ethylene glycol (25 % by mass in water) was used in evaporator with stirrer to get the desired evaporation temperature with the manual controlled expansion valve. Microchannel condenser was designed, developed and fabricated for heat rejection capacity of 4.86 kw with aluminium material for rectangular tubes and fins with the integral receiver and drier as shown in Figure 2. Each condenser tube was containing 10 microchannels with hydraulic diameter of mm. Four pressure gauges (range 0 to 2 MPa) were attached before and after the evaporator as well as condenser for measuring the pressure drop across the two heat exchangers with an accuracy of ± 0.007MPa. Voltmeter (range 0 to 400 Volts) was used for measuring voltage with an accuracy ±1 Volt. Ammeter (range 0 to 100 Ampere) was used for measuring the current with an accuracy of ±1 Amp. Rotameter (range Kg/hr) was used to measure the flow rate of refrigerant with an accuracy of ± 0.5 Kg/hr. Refrigerant temperatures were recorded at various points such as suction and discharge of compressor, sub-cooled liquid at the exit of condenser, glycol in the evaporator, ambient air flow and exhaust of air over the condensers with the help of PT-100 thermal sensors with an accuracy of ± C. Figure1. Experimental set up. 1995

4 Experimental analysis of microchannel condenser using R134a and drop in substitute hydrocarbon mixture of R290 and R600a Microchannels Receiver Inlet Outlet Figure 2. Microchannel condenser. Velocity of air across the condenser was measured with the help of anemometer with an accuracy of ± 0.1 m/s. Power consumption of compressor, air heaters, condenser fan, water heaters, stirrer were measured separately with the help of digital energy meters in kw with an accuracy of ± 0.01kW. Experimental Procedure The objective of the research was to study, analyze and compare the performance of the VCR system with R134a and HC mixture of R290/R600a (50:50 % by mass) with aluminium microchannel condenser in terms of actual compressor power consumption, coefficient of performance, refrigerating capacity, condenser capacity and the product of overall heat transfer coefficient (U) and surface area (A) of the condenser. In the experimentation, HC mixture of propane and isobutane (50:50 % by mass) was used as a drop in substitute to R134a and experiments were performed with microchannel condenser for condensation temperature of 44 0 C. For each condensation temperature, evaporator temperature was varied from C to 15 0 C. Desired condensation pressure corresponding to saturation temperature was obtained by controlling the air heater temperature and multi speed fan regulator. Evaporator temperature was controlled with the help of manually controlled expansion valve and setting the suction temperature of the refrigerant with the help of proportional, integral and derivative (PID) controller. Degree of sub-cooling at the exit of condenser was maintained at 7 0 C and degree of suction superheating to compressor was maintained 10 0 C throughout the experimentation for both the refrigerants. RESULTS AND DISCUSSION Experiments were performed on versatile VCR system using microchannel condenser at condensation temperature of 44 C while the evaporation temperature was varying from C to 15 0 C for R134a and HC mixture of R290/R600a (50:50 % by mass). It was observed that the performance of the VCR system enhanced by using HC mixture of R290/R600a (50:50 % by mass) as compared to R134a. As the density of hydrocarbon refrigerant is around 40 % of HFC refrigerants, refrigerant charge was reduced by 45 % for HC mixture of propane and isobutane (50:50 % by mass) over R134a. Performance parameters such as actual compressor power consumption, COP, refrigeration capacity, condenser capacity and the product of overall heat transfer coefficient and area of 1996

5 Bhatkar et al. /International Journal of Automotive and Mechanical Engineering 10 (2014) condenser for R134a and HC mixture of R290/R600a (50:50 % by mass) were analyzed and plotted for condensation temperature of 44 0 C and the evaporation temperature ranging from C to 15 0 C. Actual compressor power consumption Compressor is one of the most important component of VCR system. Actual compressor power consumption for microchannel condenser with R134a and HC mixture of R290/R600a (50:50 % by mass) at 44 0 C condensation temperature and evaporation temperature ranging from -15 to 15 0 C is shown in Figure 3. As the microchannel condenser has different geometrical structure and uniform air distribution over the condenser tubes than conventional condenser, the condensation temperature drops by 2 to 3 0 C for same ambient condition. Thus the microchannel condenser works efficient in the high ambient conditions. Actual compressor power consumption was more in HC mixture of R290/R600a (50:50 % by mass) than R134a. It was seen that the compressor power consumption increases as the evaporation temperature increases from C to 15 0 C for a condensation temperature of 44 0 C. It was observed that compressor power consumption is more by 13.3% for R134a than HC mixture of R290/R600a (50:50 % by mass) at condensation temperature of 44 0 C and evaporation temperature of 0 0 C. Figure 3. Actual compressor power consumption for microchannel condenser. Coefficient of performance Coefficient of performance of the VCR system is the ratio of desired refrigeration effect to the work supplied to the compressor. COP is one of the most important performance parameter of the VCR system. Figure 4 shows the values of COP for condensation temperature of 44 0 C and evaporation temperature were ranging from C to 15 0 C using microchannel condenser with R134a and HC mixture of R290/R600a (50:50 % by mass). It was observed that, COP increases for evaporation temperature ranging from C to 15 0 C for condensation temperatures of 44 0 C. It was seen that as the condensation temperature increases, COP decreases due to more compressor power consumption. It was also observed that COP values with the microchannel condenser were more for R134a than HC mixture of R290/R600a (50:50 % by mass) from C 1997

6 Experimental analysis of microchannel condenser using R134a and drop in substitute hydrocarbon mixture of R290 and R600a to 15 0 C. COP of HC mixture of R290/R600a (50:50 % by mass) at condensation temperature 44 0 C and evaporation temperature of 0 0 C was less by 43 % than R134a. Refrigerant capacity Figure 4. Coefficient of performance for microchannel condenser. Refrigerant capacity of any refrigerating system is the rate at which it will remove heat from the refrigerated space. Refrigeration capacity is the total refrigeration effect produced in the evaporator which is given as the product of mass flow rate of refrigerant in kg/s and the enthalpy difference (kj/kg) between the exit and inlet of evaporator. Refrigeration capacity of R134a and HC mixture of R290/R600a (50:50 % by mass) is shown in Figure 5 for condensation temperature of 44 0 C while the evaporator temperature ranges from C to 15 0 C. It was observed that the refrigerating capacity of HC mixture of R290/R600a (50:50 % by mass) was higher than R134a from evaporation temperature ranging from C to 15 0 C. As the latent heat of HC refrigerant is more than R134a, the cooling was fast for HC mixture of R290/R600a (50:50 % by mass) than R134a. It was seen that the refrigeration capacity increased by % for HC mixture of R290/R600a (50:50 % by mass) than R134a at condensation temperature of 44 0 C and evaporation temperature of 0 0 C. Figure 5. Refrigerating capacity for microchannel condenser. 1998

7 Bhatkar et al. /International Journal of Automotive and Mechanical Engineering 10 (2014) Condenser capacity Condenser capacity is the total heat rejected by the condenser which is equivalent to the addition of refrigeration effect in the evaporator and the heat generated by the mechanical compression. Thus condenser of VCR system is always larger than evaporator. Condenser capacity is given as the product of mass flow rate of refrigerant (kg/s) and the enthalpy of conversion from vapour to liquid (kj/kg) at that condensation temperature. Figure 6 shows the condenser capacity for microchannel condenser with R134a and HC mixture of R290/R600a (50:50% by mass) at condensation temperature of 44 0 C while evaporation temperature ranging from C to 15 0 C. Condenser size with the hydrocarbon refrigerants reduces for the same tonnage capacity of the refrigeration system as compared R134a due to large latent heat of hydrocarbons. This is beneficial for the automobile air conditioning systems as weight is reduced. It was observed that the condenser capacity of HC mixture of R290/R600a (50:50 % by mass) were more than R134a by % at condensation temperature of 44 0 C and evaporation temperature of 0 0 C. Figure 6. Condenser capacity for microchannel condenser Product of Overall Heat Transfer Coefficient and Surface Area of Condenser Product of overall heat transfer coefficient and surface area of condenser represents the heat exchanger capacity per degree of mean temperature difference. Product of overall heat transfer coefficient and surface area of condenser signifies the performance of the heat exchanger, higher the UA value, superior is the thermal performance of the heat exchanger. Figure 7 shows the product of overall heat transfer coefficient and the area of the condenser for microchannel condenser with R134a and HC mixture of R290/R600a (50:50 % by mass) at 44 0 C condensation temperature while evaporation temperatures ranging from C to 15 0 C. Experimental UA value was more by % for HC mixture of R290/R600a (50:50 % by mass) than R134a at condensation temperature of 44 0 C and evaporation temperature of 0 0 C. 1999

8 Experimental analysis of microchannel condenser using R134a and drop in substitute hydrocarbon mixture of R290 and R600a Figure 7. Product of overall heat transfer coefficient and surface area of condenser. CONCLUSIONS Performance analysis of VCR system was done using aluminium microchannel condenser tubes with aluminium fins using R134a and drop in substitute HC mixture of R290/R600a (50:50 % by mass) for condensation temperature of 44 0 C while the evaporator temperature ranges from C to 15 0 C. It was concluded that the performance parameters such as compressor power consumption increased by 13.3 %, coefficient of performance reduced by 43 %, refrigeration capacity increased by %, condenser capacity increased by % and the product of overall heat transfer coefficient and surface area of condenser was increased by % by using hydrocarbon mixture of R290 and R600a (50:50 % by mass) over R134a with the microchannel condenser for condensation temperature of 44 0 C and evaporation temperature of 0 0 C. As microchannel condensers are more compact in size, the refrigerant charge needed for HC refrigerants is around 42 to 45 % of R134a. Further the performance of the microchannel condenser can be enhanced by optimizing the passes in the condenser and number of tubes per pass, by providing proper position and size of inlet and outlet in the condenser. Thus it is concluded that microchannel condensers can be used in household refrigerators, air conditioners and in automobile air conditioning systems using HC mixture of R290/R600a (50:50 % by mass) as drop in substitute to R134a with proper care to prevent the leakage. ACKNOWLEDGEMENTS The authors acknowledge the financial support from the Board of Colleges and University Development (BCUD), University of Pune, India under Grant No 11ENG for fabrication and development of experimental set up. REFERENCES [1] Calm JM. The next generation of refrigerants Historical review, considerations, and outlook. international Journal of Refrigeration. 2008;31:

9 Bhatkar et al. /International Journal of Automotive and Mechanical Engineering 10 (2014) [2] Mohanraj M, Jayaraj S, Muraleedharan C, Chandrasekar P. Experimental investigation of R290/R600a mixture as an alternative to R134a in a domestic refrigerator. International Journal of Thermal Sciences. 2009;48: [3] Ohadi M, Choo K, Dessiatoun S, Cetegen E. Next Generation Microchannel Heat Exchangers: Springer; [4] Chang Y, Kim M, Ro S. Performance and heat transfer characteristics of hydrocarbon refrigerants in a heat pump system. International journal of refrigeration. 2000;23: [5] Dalkilic A, Wongwises S. A performance comparison of vapour-compression refrigeration system using various alternative refrigerants. International Communications in Heat and Mass Transfer. 2010;37: [6] Mani K, Selladurai V. Experimental analysis of a new refrigerant mixture as drop-in replacement for CFC12 and HFC134a. International journal of thermal sciences. 2008;47: [7] James R, Missenden J. The use of propane in domestic refrigerators. International journal of refrigeration. 1992;15: [8] ACRIB. Guidelines for the use of hydrocarbon refrigerants in static refrigeration and air conditioning systems. UK: Air Conditioning and Refrigeration Industry Board; p [9] Elsayed AO, Hariri AS. Effect of condenser air flow on the performance of split air conditioner. World renewable energy congress, Sweden2011. p [10] Vijaya Lakshmi B, Subrahmanyam T, Dharma Rao V, Sharma KV. Turbulent film condensation of pure vapors flowing normal to a horizontal condenser tube - constant heat flux at the tube wall. International Journal of Automotive and Mechanical Engineering. 2011;4: [11] Suryanarayana KV, Srinivasa Rao G, Reddy Prasad DM, Sharma KV, Sarma PK. Experimental analysis of heat and mass transfer in a packed bed. Journal of Mechanical Engineering and Sciences. 2011;1: [12] Tahseen TA, Ishak M, Rahman MM. A numerical study of forced convection heat transfer over a series of flat tubes between parallel plates. Journal of Mechanical Engineering and Sciences. 2012;3: [13] Kandlikar S, Garimella S, Li D, Colin S, King MR. Heat transfer and fluid flow in minichannels and microchannels: Elsevier; [14] Li W, Wu Z. A general criterion for evaporative heat transfer in micro/minichannels. International Journal of Heat and Mass Transfer. 2010;53: [15] Matkovic M, Cavallini A, Del Col D, Rossetto L. Experimental study on condensation heat transfer inside a single circular minichannel. International Journal of Heat and Mass Transfer. 2009;52: [16] Fernando P, Palm B, Ameel T, Lundqvist P, Granryd E. A minichannel aluminium tube heat exchanger Part II: Evaporator performance with propane. International journal of refrigeration. 2008;31: [17] Agarwal A, Bandhauer TM, Garimella S. Measurement and modeling of condensation heat transfer in non-circular microchannels. International Journal of Refrigeration. 2010;33: [18] Bhuiyan AA, Amin MR, Karim R, Sadrul Islam AKM. Plate fin and tube heat exchanger modeling: effects of performance parameters for turbulent flow regime. International Journal of Automotive and Mechanical Engineering. 2014;9:

10 Experimental analysis of microchannel condenser using R134a and drop in substitute hydrocarbon mixture of R290 and R600a [19] Tahseen TA, Ishak M, Rahman MM. Laminar forced convection heat transfer over staggered circular tube banks: A CFD approach. Journal of Mechanical Engineering and Sciences. 2013;4: [20] Tahseen TA, Rahman MM, Ishak M. An Experimental study of air flow and heat transfer over in line flat tube bank. International Journal of Automotive and Mechanical Engineering. 2014;9: [21] Ishak M, Tahseen TA, Rahman MM. Experimental investigation on heat transfer and pressure drop characteristics of air flow over a staggered flat tube bank in crossflow. International Journal of Automotive and Mechanical Engineering. 2013;7: [22] Qi Z, Zhao Y, Chen J. Performance enhancement study of mobile air conditioning system using microchannel heat exchangers. International Journal of refrigeration. 2010;33: [23] Poggi F, Macchi-Tejeda H, Leducq D, Bontemps A. Refrigerant charge in refrigerating systems and strategies of charge reduction. International Journal of Refrigeration. 2008;31: [24] Rasti M, Hatamipour M, Aghamiri S, Tavakoli M. Enhancement of domestic refrigerator s energy efficiency index using a hydrocarbon mixture refrigerant. Measurement. 2012;45:

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Effect of capillary diameter on the power consumption of VCRS using different refrigerants Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

Global Journal of Engineering Science and Research Management

Global Journal of Engineering Science and Research Management EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,

More information

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org Experimental Evaluation of

More information

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review

More information

DEEPAK PALIWAL, S.P.S.RAJPUT

DEEPAK PALIWAL, S.P.S.RAJPUT International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department

More information

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical

More information

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Mr. Subodh S. Deshpande Department of Mechanical Engineering M.G.M.s College of Engineering

More information

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Gaurav #1, Raj Kumar* 2 1# Research Scholar, Department of Mechanical Engineering,

More information

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical

More information

Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer

Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer 7 th International Chemical Engineering Congress & Exihibition Kish, Iran, 21-24 November, 2011 Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer M. Rasti 1,

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou

More information

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry Journal of Physics: Conference Series PAPER OPEN ACCESS Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry To cite this article: IM

More information

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser Issam Mohammed Ali Ahmed Qasim Mohammed Marwa Sallah Neama Mechanical Eng. Dept Air-

More information

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research

More information

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling ISSN 2395-1621 Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot #1 Student, Mechanical

More information

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser

More information

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Available online at   ScienceDirect. Energy Procedia 109 (2017 ) 56 63 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November

More information

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C drop analysis of evaporator using refrigerants R-22, R-404A and R-407C #1 Pallavi Sawkar, #2 Dr. Pradeep Patil #12 Department of Mechanical Engineering, JSPM s JSCOE, Savitribai Phule Pune University,

More information

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan

More information

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants 454 Journal of Scientific & Industrial Research Vol. 72, July 2013, pp. 454-460 Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants P. Thangavel 1* and

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties

More information

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator ISSN:1991-8178 Australian Journal of Basic and Applied Sciences Journal home page: www.ajbasweb.com Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator 1

More information

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XXI, NR. 1, 2014, ISSN 1453-7397 Feiza Memet A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

More information

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical

More information

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate International Journal of Research in Engineering and Innovation (IJREI) Vol-1, Issue-2, (2017), 49-53 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants [VOLUME 5 I ISSUE 3 I JULY SEPT 2018] e ISSN 2348 1269, Print ISSN 2349-5138 http://ijrar.com/ Cosmos Impact Factor 5.75 Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a

More information

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants

More information

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator Theoretical performance evaluation of R34a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator Chintankumar B. Lad, 2 Dr. Ragesh G. Kapadia M.E. Student, 2 Principal Thermal Engineering,

More information

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT Proceedings of the International Conference on Mechanical Engineering and Renewable Energy 217 (ICMERE217) 18 2 December, 217, Chittagong, Bangladesh ICMERE217-PI-48 IR-REVERSIBILITY ANALYSIS OF A SPLIT

More information

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Comparative assessment for drop in replacement of R134a in domestic refrigerator. Comparative assessment for drop in replacement of R134a in domestic refrigerator. Pravin K. Katare Research Scholar, Department of Mechanical Engineering, G.H.Raisoni College of Engineering Digdoh Hill,

More information

Department of MCE, Islamic University of Technology 2. Abstract

Department of MCE, Islamic University of Technology 2. Abstract Paper ID: TE-85 Study of power consumption characteristics of LPG and R134a in a vapor compression refrigeration system Md. Abu Shaid Sujon 1, Rakibul Hossain Ahmed 2, Dr. A.K.M. Sadrul Islam 3, Sk. Suzauddin

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

*Corresponding author;

*Corresponding author; PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU

More information

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,

More information

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION M.S.Bandgar 1, R. N. Kare 2 1,2 Assistant Professor, JSPM s Imperial College of Engineering & Research,

More information

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (www.rdmodernresearch.

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (www.rdmodernresearch. COMPARATIVE STUDY OF R600a AND BLENDS OF (R600a /R1270) AS DOMESTIC REFRIGERANTS M. Ramesh Kumar*, S. Siva Subramanian**, R. Arun Kumar*** & A. Sankara Narayana Murthy**** Department of Mechanical Engineering,

More information

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a. Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a. Raja Kumar Gond 1, Ravindra Pratap Chaudhary 2, Mohammad Amir Khan 3, Gaurav Jain 4 1Student,

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-772 Published BYAENSI Publication EISSN: 1998-19 http://www.aensiweb.com/anas 217 February 11(2): pages 77-84 Open Access Journal Certain Studies On

More information

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP Paul Maina and Zhongjie Huan mainap@tut.ac.za and huanz@tut.ac.za Department of Mechanical Engineering, Tshwane University of Technology P.O Box Private Bag X680

More information

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015 Page77 Page78 COMPARATIVE ANALYSIS OF PERFORMANCE OF OZONE-FRIENDLY AND LOW GWP HFC REFRIGERANT IN A VAPOUR COMPRESSION REFRIGERATION CYCLE Kashid Hari T. 1,Khatpe Akshay R 1,Khile Parshuram N 1,Ligade

More information

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study

More information

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT THERMAL SCIENCE, Year 2011, Vol. 15, Suppl. 2, pp. S391-S398 391 HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT by Thirupandiyur Selvanambi RAVIKUMAR a* and Dhasan MOHAN LAL b a Department

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Enhancement of COP using Nanoadditives in Domestic Refrigerator ISSN 2395-1621 Enhancement of COP using Nanoadditives in Domestic Refrigerator #1 Mr.Sajjan Kawade, #2 Prof P.T.Kharat 1 sajjankawade@gmail.com 2 pradip5872@gmail.com #1 P.G. Student, Mechanical Engineering

More information

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators Energy Conversion and Management 44 (2003) 381 388 www.elsevier.com/locate/enconman Assessment of LPG as a possible alternative to R-12 in domestic refrigerators Bilal A. Akash a, *, Salem A. Said b a

More information

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM 1 RONANKI SURESH, 2 Dr. K. KALYANI RADHA 1 M.Tech, Mechanical Engineering, JNTUA College of Engineering

More information

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar

More information

Waghmare Tushar Ramrao, D.S.Nakate

Waghmare Tushar Ramrao, D.S.Nakate International Engineering Research Journal Performance analysisof vapor compression system by using capillary tube suction line heat exchanger and helical condenser for R134a Waghmare Tushar Ramrao, D.S.Nakate

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn: Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Pawan Kumar Mishra #1, Amol Tripathi *2 # RIT Department of Mechanical Engineering Department,

More information

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation Methods for Improving Thermodynamic Energy and Exergy Performance of Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants in Primary Circuit and TIO 2 Nano Particles Mixed with

More information

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot 1 Stu dent - Mechanical Engineering,

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R29 as Substitution to & Mixture of Them in Vapour Compression System Pawan Kumar Mishra #1, Amol Tripathi *2 #RIT Department of Mechanical Engineering Department, RGPV,Bhopal

More information

JJMIE Jordan Journal of Mechanical and Industrial Engineering

JJMIE Jordan Journal of Mechanical and Industrial Engineering JJMIE Jordan Journal of Mechanical and Industrial Engineering Volume 9 Number 4, August.21 ISSN 199-666 Pages 289-296 Thermodynamic Analysis of R12a and Dimethylether Refrigerant Mixtures in Refrigeration

More information

International Journal of Advance Engineering and Research Development

International Journal of Advance Engineering and Research Development Scientific Journal of Impact Factor(SJIF): 3.134 e-issn(o): 2348-4470 p-issn(p): 2348-6406 International Journal of Advance Engineering and Research Development Volume 02,Issue 06, JUNE -2015 COMPARATIVE

More information

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical

More information

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of

More information

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY PERFORMANCE ANALYSIS OF AIR COOLED WATER COOLER BY USING ECO- FRIENDLY REFRIGERANTS AS A POSSIBLE SUBSTITUTE OF R134A Gaurav Gupta*,

More information

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression

More information

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.

More information

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation Volume 6, Issue 3(201)199-204 ISSN 2347-325 Comparative Performance Evaluation of Vapor Compression Refrigeration System for drop-in Replacement of R22 Vaibhav Jain *, Dhruva Gupta, Himank Gupta, Anirudh

More information

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Experimental Study on Performance of Condenser of Two Different Types Used in Window Air Conditioner Madhu Jhariya *1, P.K. Jhinge

More information

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 25 No. 2 Jul. 2016, pp. 637-645 2015 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/

More information

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 183-190 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1 HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil

More information

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE) October 217, Volume 4, Issue 1 EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R6A & HC MIXTURE) 1 NULAKA RAJESWARI, 2 Dr. B.OMPRAKASH, 3 Dr. R.GANAPATHI, 1

More information

Design and Analysis of Water Cooled Condenser

Design and Analysis of Water Cooled Condenser Design and Analysis of Water Cooled Sanjana V. Bharambe #1, Susmit A. Mulay #2, Suyash Jadhav #3 123 B ech Mechanical engineering, COEP Pune Abstract - he domestic refrigerator is one of the most commonly

More information

Performance investigation of Air-conditioning system using ejector as expansion device

Performance investigation of Air-conditioning system using ejector as expansion device International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance

More information

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger Chetan Papade Department of Mechanical Engineering N.K.Orchid college of Engg.& Tech., Solapur, Maharashtra,

More information

Chapter 2. Alternatives to HCFCs and their Characteristics

Chapter 2. Alternatives to HCFCs and their Characteristics Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid

More information

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation Methods for Improving First and Second Law Efficiencies of Vapour Compression Refrigeration Systems Using Flash-Intercooler with Ecofriendly Refrigerants Kapil Chopra *, V. Sahni, R. S. Mishra Department

More information

Design of LPG Refrigeration System

Design of LPG Refrigeration System Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1

More information

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System Available online at www.ijapie.org International Journal of Advanced Production and Industrial Engineering IJAPIE-SI-IDCM 606 (2017) 24 30 Special Issue on INNOVATIVE DESIGN & COMPUTATIONAL MODELLING Assessment

More information

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Prof. S.V.Rao 1, Hitesh Sharma 2, Pankaj Kumar Gound 3, Tukaram Walgude 4, Shekhar Gavas 5 1 Prof.

More information

Chapter 10. Refrigeration and Heat Pump Systems

Chapter 10. Refrigeration and Heat Pump Systems Chapter 10 Refrigeration and Heat Pump Systems Learning Outcomes Demonstrate understanding of basic vaporcompression refrigeration and heat pump systems. Develop and analyze thermodynamic models of vapor-compression

More information

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Shubham Rangari 1, Shubham Mahakalkar 2, Shubham Tiple 3, Praharsh Marathe 4, Sameer Bansod 5, Sunnyraj Katam 6, Suraj Nagrare

More information

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger "COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger" 1 Prof.Gaffar G.Momin, 2 Sagar B. Tupe, 2 Swapnil A. Parate 2 Omkar G. Yewale 2 Aakash P.

More information

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration 11.1 Introduction Preservation of foods is a vital processing step in food processing. There are

More information

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a Gaurav 1 and Raj Kumar 2 1,2Department of Mechanical Engineering, YMCA University of Science & Technology,

More information

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL K.Thejeswarudu 1, R. Meenakshi Reddy 2 and E. Siva Reddy 2 1 PG Student, Department of Mechanical Engineering, G. Pulla Reddy College

More information

Enhancement of COP in Vapour Compression Refrigeration System

Enhancement of COP in Vapour Compression Refrigeration System Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,

More information

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE PRESENTED BY J.SARAVANA PERUMAL 1 Saravananjsp005@gmail.com D.SATHEESH 2 Satheeshd123@gmail.com Contact no: 9789080381 DEPARTMENT

More information

Study of solar-thermal collector assisted hybrid split air conditioner

Study of solar-thermal collector assisted hybrid split air conditioner Study of solar-thermal collector assisted hybrid split air conditioner Chetan Brahmankar 1, Hrishikesh Bhushan 2, Akshay Ghule 3, Himanshu Ranjan 4 1,2,3,4 Dept. of mechanical engineering, Dr. D.Y Patil

More information

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators A Review on selecting an Eco-friendly Refrigerant alternate to in Domestic Refrigerators V. Manoj 1, V. Balamurugan 2, B. Senthil Kumar 3 1 PG Scholar (Thermal Engineering), 2, 3 Assistant Professor 1,

More information

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

CH2351 Chemical Engineering Thermodynamics II Unit V  Refrigeration.  Dr. M. Subramanian CH2351 Chemical Engineering Thermodynamics II Unit V www.msubbu.in Refrigeration www.msubbu.in Dr. M. Subramanian Associate Professor Department of Chemical Engineering Sri Sivasubramaniya Nadar College

More information

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Oyelami S., Bolaji B. O.

Oyelami S., Bolaji B. O. International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 1158 Experimental Investigation of the Performance of Liquefied Petroleum Gas (LPG) Refrigerant in A Vapour Compression

More information

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Main Anthropogenic Sources of Greenhouse Gases Refrigerants Main Anthropogenic Sources of Greenhouse Gases Refrigerants Content Refrigerant definition Refrigerants Refrigerants as a source of GHG Refrigerant Definition A refrigerant is a substance or mixture, usually

More information

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental

More information