GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

Size: px
Start display at page:

Download "GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER"

Transcription

1 OPERATING INSTRUCTIONS CH-MG150 CH-MG200 GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER FOR YOUR SAFETY If you smell gas: 1. Open windows (only if installed indoors) 2. Don t touch electrical switches 3. Extinguish any open flame 4. DO NOT SMOKE! 5. Immediately call your gas supplier FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other equipment. CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 3 HEATING OPERATION 4 CONTROLS GENERAL INFORMATION 5 CONTROL ADJUSTMENTS 8 CONTROL SEQUENCE 12 OPERATION COOLING 13 PRECAUTIONS 13 HEATING 13 REMOTE CONTROL 13 Page SAFETY CONTROLS 13 WINTER SHUTDOWN 14 MAINTENANCE GENERAL INFORMATION 14 MAINTENCE SCHEDULE 14 ROUTINE MAINTENANCE 15 EVACUATION OVERVIEW 15 CHEMICAL MAINTENANCE 17 WINTERIZING 17 TROUBLESHOOTING 17 WATER QUALITY 18 ERROR CODES 19

2 This product is a gas-fired absorption unit which provides chilled water for cooling or hot water for heating in central plant-type air conditioning systems. Units with nominal refrigeration capacities of 150 and 200 tons are complete with operating and safety controls. The chiller-heater is fitted with a low NOx burner, automatic spark ignition systems, power combustion blower and proportional firing control. When this equipment has been applied correctly, installed in accordance with Yazaki INSTALLATION INSTRUCTIONS (supplied with the chiller-heater), and with proper maintenance on the chiller-heater itself and accompanying support items such as pumps, cooling tower, etc., it can provide many years of trouble free operation. GENERAL These instructions are intended to acquaint the Owner/End User with the operation and general maintenance requirements of Yazaki Gas-Fired Double-Effect Absorption Chiller-Heater units. Please read ALL instructions carefully and observe precautions. Failure to operate and properly maintain this equipment in accordance with the OPERATING INSTRUCTIONS may affect the equipment performance and product Warranty. If the equipment does not operate as expected, check the Troubleshooting Guide in these instructions BEFORE calling your Yazaki Authorized Service Provider (ASP). This approach will not only save cost but also helps to avoid any unnecessary down time. THE ABSORPTION PRINCIPLE Yazaki absorption chiller-heaters use a solution of lithium bromide and water, under vacuum, as the working fluid. Water is the refrigerant and lithium bromide is the absorbent. During cooling operation, refrigerant liquid boils under the influence of a deep vacuum in the evaporator and creates a refrigerating effect which removes heat from the chilled water circuit. The double-effect absorption cycle has two generators one heated by a gas burner and another heated by superheated refrigerant vapor. The resulting refrigerant is passed through to the condenser, and is then metered into the evaporator. Lithium bromide solution leaving the generators flows into the absorber. Heat from the cycle is removed by cooling water flowing inside the condenser and absorber tubing bundles. Heat from the cooling water is rejected most typically to a cooling tower, but may also be rejected by alternative methods, including ground loops. 2

3 COOLING OPERATION High-Temperature Generator (HGE) The gas burner heats a dilute lithium bromide solution in the High- Temperature Generator resulting in a release of superheated refrigerant vapor. The dilute solution becomes more concentrated due to this release. Gravity, temperature, and pressure differences push the more concentrated solution through Heat Exchangers to recycle heat before the concentrated solution is sent to the Absorber (ABS). After release, the superheated refrigerant vapor flows through the Low- Temperature Generator (LGE) tubing bundle and is used as the heat source for the dilute solution that the LGE contains. Most, if not all, of the refrigerant vapor will condense into liquid refrigerant during this process. Ultimately, this tubing dumps the liquid refrigerant into the Condenser (COND). Low-Temperature Generator (LGE) After release, the superheated refrigerant vapor heats dilute lithium bromide solution in the Low-Temperature Generator. The refrigerant vapor liberated from this solution flows into the Condenser while the lithium bromide solution becomes more concentrated. Gravity, temperature, and pressure differences push this more concentrated solution through Heat Exchangers to recycle heat before the concentrated solution is sent to the Absorber. Condenser (COND) In the Condenser, refrigerant vapor is condensed on the outer surface of the condenser tubing bundle. Latent heat is removed by the cooling water that flows inside this tubing bundle. The heat absorbed by the cooling water is rejected to a cooling tower or alternative system. The liquid refrigerant that drips off the tubing bundle joins the liquid refrigerant that resulted from the operation of the LGE and accumulates in the condenser sump. Liquid refrigerant is routed from the condenser sump through an electronic expansion valve which meters the liquid refrigerant as required into the Evaporator (EVA). Evaporator (EVA) In the Evaporator, liquid refrigerant is exposed to a substantially deeper vacuum than in the Condenser due to the influence of the Absorber. As the liquid refrigerant flows over the surface of the Evaporator tubing bundle, it boils and removes heat from the chilled water flowing inside the Evaporator tubing bundle. The heat removed from the chilled water circuit is equal to the latent heat of the refrigerant, roughly 1000 BTU per pound of liquid refrigerant boiling into refrigerant vapor. Absorber (ABS) The Evaporator and the Absorber share the same space. A deep vacuum in the ABS is maintained by the affinity of the concentrated solution for refrigerant vapor. The concentrated solution flows over the outside of the Absorber tubing bundle where it is cooled by the cooling water flowing inside the Absorber tubing bundle. When the concentrated solution is cooled, it develops an even greater affinity for the refrigerant vapor. The heat absorbed by the cooling water is rejected to a cooling tower or alternative system. The deep level of vacuum in the ABS section is maintained by the action of the concentrated solution absorbing the refrigerant vapor that is being generated by the EVA during its normal operation. 3

4 This action dilutes the concentrated solution back to the same concentration level as it was when the cycle began. The dilute solution gathers in the Absorber sump before being pumped back into the Generators to start the cycle anew. Fig. 1 DOUBLE-EFFECT ABSORPTION CYCLE (COOLING) HEATING OPERATION High-Temperature Generator (HGE) Dilute lithium bromide solution is heated in the HGE by the gas burner in the same manner as in the cooling cycle. The solution boils vigorously, releasing superheated refrigerant vapor and leaving a more concentrated solution. The refrigerant vapor flows through a changeover valve into the Evaporator section. The concentrated solution flows through another changeover valve into the Absorber sump. Low-Temperature Generator (LGE) Although solution does flow through the LGE, since the superheated refrigerant vapor is not flowing in any meaningful amount through the LGE, the solution does not release any refrigerant vapor and the solution simply flows back into the Absorber sump in essentially a stilldiluted state. The lack of this generator operation in heating mode is why the heating capacity is lower than the cooling capacity in these chiller-heaters. 4

5 HEATING OPERATION Evaporator (EVA) Superheated refrigerant vapor condenses on the outer surface of the Evaporator tubing bundle. Heat equal to the latent heat of the refrigerant is transferred into the hot water circuit. The liquid refrigerant that condensed on the outer surface simply drips off into the Absorber sump, diluting the solution back to the same concentration level as when it started the cycle. Absorber (ABS) Liquid refrigerant that condensed on the outer surface of the Evaporator tubing bundle drips into the Absorber sump. Concentrated solution from the HGE and dilute solution cycled through the LGE also ends up in the Absorber sump. The joining of all the liquids results in diluting the solution back to the state at which it began the cycle. This diluted solution is then pumped to the Generators to begin the cycle anew. Fig. 2 DOUBLE-EFFECT ABSORPTION CYCLE (HEATING) 5

6 GENERAL INFORMATION CONTROLS A control panel, shown in Fig. 3, is built into each absorption chiller-heater and is located on the front of the control box. The control box is located behind the right-hand service door, as shown in Fig. 4. After inspecting the control panel or changing the mode of operation, make sure that the front panel is latched and locked in order to prevent rain from entering the cabinet and damaging the controls. This will also help to prevent unauthorized tampering with controls and settings. The chiller-heater may also be supervised and controlled in a limited manner by Building Automation Systems (BAS, BMS) when Remote Operation is engaged. Additional controls and interlocks may be required in some instances. These controls and their functions can be explained by your Yazaki Authorized Service Provider. Once COOLING or HEATING operation is selected and the unit has started, the chiller-heater will function automatically and remain in operation for as long as there is a demand for chilled or hot water. The burner modulates the Generator heat input in response to the leaving chilled/hot water temperature. When the chilled water temperature demand is satisfied, the solution pump automatically changes to Dilution Mode and the cooling water pump demand stops after a minimum of 4 minutes additional time. Fig. 3 Chiller-Heater Control Panel 6

7 GENERAL INFORMATION Evacuation Service Valves A and B are located behind this panel in this location. Control Panel located behind this panel in this location. Fig. 4 SOLUTION PUMP CONTROL The VFD Solution Pump is controlled by a Hitachi VFD Controller. This controller has been set up at the factory and SHOULD NOT BE ADJUSTED! Universal replacements are NOT recommended. Only use OEM parts for the solution pump and controller. Fig. 5 Hitachi VFD Controller 7

8 CONTROL ADJUSTMENTS The chiller-heater is normally operated from the control panel behind the right access door. If it is necessary to open the control box for troubleshooting, observe all safety warnings on the chillerheater and in these instructions. Only qualified and trained personnel should have access to the live electrical parts inside the chiller-heater. Failure to observe the safety warnings can result in personal injury, death, and/or damage to property. Fig. 6 Control Box (Opened) 8

9 CONTROL ADJUSTMENTS The ACT5 Maintenance Checker plugs into the Main CPU Board, shown in Fig. 8, and is used in many functions, including choosing the leaving chilled/hot water temperature set points. This board also has the Mode Setting Switch. This switch must be positioned to the left whenever the unit is to be in normal operating condition. Position this switch to the right when adjusting the burner. Position this switch to the middle when the unit is to sit dormant and unresponsive, but with power applied to it. The Unit Number Setting Dip Switch is only used in conjunction with the optional AroTrend Remote Monitoring or an optional LON Adapter. If not being monitored, this dial switch must be set to 0 or F. Fig. 8 Main CPU Board 9

10 CONTROL ADJUSTMENTS The leaving chilled water and hot water temperature controls are set at the factory to the Standard Specifications Set Points, which are a cooling set point of 44.6 F (7 C) and a heating set point of F (60 C). A Yazaki Authorized Service Provider can adjust these set points using the ACT5 Maintenance Checker. The cooling set point is adjustable from 41 F (5 C) to 53.6 F (12 C). The heating set point is adjustable from F (40 C) to F (63 C). The CH-MG Series has an Economy Mode feature as well that can be controlled by the Building Management System. Economy Mode functions in much the same way as night set-back. When engaged, the cooling set point will rise by 5.4 F (3 C) and the heating set point will fall by 9 F (5 C). Dis-engaging the Economy Mode will immediately restore the cooling and heating set points back to their original values. There is also an identical jack on the Sub-Control Board located in the top left corner of the control box. This board s jack is not functional and should not be used. To adjust the chilled and hot water set points: 1. On the ACT5, use the Λ and V buttons to move the cursor to the line 2. Unit data set and press ENTER. 2. Then use the Λ and V buttons to move the cursor to the line B2 CB Set and press ENTER. 3. Use the and buttons to reach the menu displaying data points Fig. 7 ACT5 Maintenance Checker Adjusting the chilled and hot water set points can only be done using the ACT5. Using a standard CAT5 cable (one was provided from the factory), connect the ACT5 to the Main CPU Board located in the upper right of the control box. There is a jack in the upper middle of the CPU Board (See Figure 8) that is for use with the ACT5. 4. Use the Λ, V, <, and > buttons to move the cursor to temperature numbers of data point 14 to change the cooling set point, or data point 15 to change the heating set point. 5. Once highlighting the block to be changed, use the + and - buttons to scroll through the available values until the desired value is displayed. 6. Press ENTER to save the new setting. 7. Press and hold the for longer than one full second to back out of the menu, or simply unplug the ACT5 if it is no longer needed for other functions. 10

11 CONTROL ADJUSTMENTS To enable the Economy Mode, locate terminals TB1-75 and TB1-76 (See Fig. 9) on the I/O Board, located at the middle left in the control box. The board sends voltage out on TB1-75, so no external or field-supplied power should be applied to the circuit or else damage to the board could result. To engage Economy Mode, close a circuit between TB1-75 and TB1-76. When that circuit is closed, the Main CPU Board logic will automatically apply a modifier to the temperature set point data in memory. When the circuit is open, no modifier will be applied. Most often, a relay with dry contacts that is controlled by the BMS is used to control Economy Mode. However, a timer, light sensor, or a simple toggle switch could also be used to make or break this circuit. Fig. 9 I/O Board 11

12 CONTROL SEQUENCE A built-in microprocessor in the chillerheater controls the external pump demand signals in response to the cooling and heating load. The operating sequence of each pump and the cooling tower fan after start-up, during normal operation, and after a normal stop or abnormal shut down is shown in Fig. 10. It is important that the chiller-heater have control over the pumps to allow for controlled shut down under normal and abnormal conditions. Running the chilled water pump at all times is discouraged as the chiller-heater logic will expect to see the flow switch open when the P dry contacts are opened. If it does not open, the chiller assumes the flow switch has failed and will generate error code E016. Fig. 10 General Control Sequence CP = Cooling Water Pump Demand Relay CTF = Cooling Tower Fan Demand Relay P = Chilled/Hot Water Pump Demand Relay 12

13 OPERATION COOLING 1. Select ON on the DIRECT OPERATION section of the control panel. 2. Select COOLING on the MODE SELECT section of the control panel. Cooling operation will commence after all self-check functions have completed. This can take as long as 5 minutes so do not be alarmed if the unit does not seem to respond immediately. If the unit is being switched over from HEATING mode, there is an enforced 30-minute delay period before COOLING mode will engage. HEATING 1. Select ON on the DIRECT OPERATION section of the control panel. 2. Select HEATING on the MODE SELECT section of the control panel. Heating operation will commence after all self-check functions have completed. This can take as long as 5 minutes so do not be alarmed if the unit does not seem to respond immediately. If the unit is being switched over from COOLING mode, there is an enforced 30-minute delay period before HEATING mode will engage. PRECAUTIONS 1. Ensure that all AUTO-OFF-MANUAL switches for external pumps and the cooling tower fan are set in the AUTO position during normal operation. The chiller-heater is designed to automatically control the chilled/hot water pump, cooling water pump, and cooling tower fan signals as it requires. 2. At the beginning of the cooling season, clean and refill the cooling tower with fresh water. Check strainers for debris and spray nozzles for proper operation. 3. During the heating season, the cooling tower and cooling water circuit should be drained in order to help prevent freezing and scaling in the Absorber and Condenser tubing bundles. 4. When two or more absorption chillerheaters are installed in parallel, set all units to the same operating mode. 13 REMOTE CONTROL In order to respond to BMS signals, the chiller-heater must be set to remote operation. Simply press the REMOTE button on the REMOTE OPERATION section of the control panel. The LED will illuminate on the REMOTE button to indicate remote operation has been engaged. SAFETY CONTROLS Safety and limit controls monitor critical operating conditions in the chillerheater and may shut down the unit when abnormal conditions occur. Not all abnormal conditions are harmful to the chiller-heater, therefore, the chillerheater may not always shut down when an error code is displayed. An Error Code will be displayed when an abnormal condition arises. This error

14 code will be displayed by LEDS located at the top left of the control panel. A list of error codes and their meanings is shown in Table 2 at the back of this manual. Some Error Codes will automatically reset themselves once the abnormal condition clears. Others may require a manual reset by pressing the RESET button on the control panel. Some manual reset codes will not clear until certain conditions are met, so if the Error Code does not clear or the chiller-heater does not restart, contact your Yazaki Authorized Service Provider (ASP). WINTER SHUT DOWN If a chiller-heater is only used in the cooling mode and is to be shut down for the winter, it is necessary to run the chiller-heater in Heat mode for a minimum of 30 minutes in order to properly return all fluids to the bottom of the unit and to prepare the unit for long term shutdown. Without running in Heat mode, some water will be trapped in upper portions of the chiller-heater and could potentially damage the unit should it freeze in the winter conditions. See the Service Manual for detailed information on proper Winter Shut Down. MAINTENANCE GENERAL INFORMATION ALL MAINTENANCE SHOULD BE PERFORMED BY SKILLED, EXPERIENCED PERSONNEL. Your Yazaki Authorized Service Provider (ASP) can help you establish a standard maintenance procedure. For your safety, keep the area around the equipment clear and free of combustible materials, gasoline, and other flammable substances. DO NOT obstruct service access to the equipment. MAINTENANCE SCHEDULE Every 6 months: Evacuation Inhibitor Check (if required) Combustion Analysis Gas Pressure Check Flow Rate Check Palladium Cell Heater Check Verify Flow Switch Operation Every 12 months: Flame Rod Replacement Igniter Rod Replacement Every 3 years: Generator Internal Inspection Average Cycle for Inhibitor Replenishment 14

15 ROUTINE MAINTENANCE Routine maintenance should be provided throughout the life of the equipment in order to ensure satisfactory operation and performance. During the warranty period, an ASP must be engaged to provide routine maintenance at the beginning of each cooling season (spring changeover) and heating season (fall changeover). When the chiller-heater is used for process cooling or heavy load operation, it may be necessary to schedule additional service visits to evacuate noncondensable gasses from the vacuum section. Be aware that during the first few months of operation, non-condensable gases may accumulate at a greater rate than expected as the inhibitor coating in the unit finishes forming. However, after approximately 3 months, the formation of non-condensable gases should decrease to the normal expected rates. Each routine maintenance item is covered in detail, many in step-by-step detail, in Section 5 of the Service Manual. What is provided here is a brief summary of what the Service Manual covers. EVACUATION OVERVIEW Arguably the most important aspect of maintenance for the chiller-heater is maintaining a proper level of vacuum. Evacuation is performed at the front of the machine. The evacuation service valves are referred to as Service Valve A (upper) and Service Valve B (lower). Refer to Fig. 4 for detail on where these valves are located at the front of the unit. The evacuation service valves are back-seating access valves similar to those used throughout the refrigeration industry. The stem has a 10mm square head. The stem secures a copper seal to a steel seat inside the valve. Do not over-torque this valve or else the seal can become damaged and compromise vacuum integrity. Yazaki offers a torque wrench (P/N N7510) specifically for use with this service valve. A number of precautions should be observed at all times during evacuation. Key points are: *** Great care must be taken to ensure that no oil enters the Yazaki chiller-heater! Permanent damage could result from even a small amount of oil being introduced into the vacuum section! *** Never leave a vacuum pump running unattended. Power loss could allow the chiller-heater vacuum section to suck oil out of the pump in a matter of minutes. Never have the Service Valve open unless the vacuum pump is running and the integrity of the vacuum lines between the valve and the pump has been verified as tight. Never have the vacuum pump discharge tube in the water bucket unless the vacuum pump is running. The vacuum pump could suck water from the bucket and contaminate the oil charge. Never pull a vacuum when the unit is running in Heat mode. Only pull a vacuum in Off or Cool modes.

16 Always start with a fresh oil charge in the vacuum pump. Always use a liquid trap or collection flask. Always use a vacuum gauge to verify the level of vacuum achieved. Run time has almost nothing to do with the level of vacuum achieved. Never pull a vacuum if the ACT5 Maintenance Checker indicates an LT temperature exceeding 90 F (32 C). Never pull an extended vacuum (exceeding a few hours). If such seems to be necessary, there is likely to be something wrong with the vacuum pump or the oil has been contaminated with moisture inherently found inside the chiller-heater vacuum section. Use only dual-stage, deep vacuum pumps. Typical refrigeration vacuum pumps may not perform well on a vessel as large as the chiller-heater vacuum section. Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate. A digital vacuum gauge MUST be used in order to determine the true level of vacuum achieved. The desired level of vacuum on a machine that is not running would be less than 2000 microns (<2mmHg), with less than 1000 microns (<1mmHg) preferred. On a machine actively running in Cool mode (burner engaged), the desired level of vacuum is 5000 microns (5mmHg), no less. Any lower than 5000 microns (5mmHg) on a running machine will cause the vacuum pump to remove an extraordinary amount of refrigerant vapor (water). A step-by-step, detailed evacuation method is provided in Section 5 of the Service Manual. The general evacuation assembly setup is displayed in Fig. 11. Fig. 11 General Evacuation Assembly Setup 16

17 CHEMICAL MAINTENANCE It is not necessary to perform regular chemical maintenance on the Yazaki chiller-heater itself. The chemical balance has been established in the factory during run testing. Normally, the only chemical that must be maintained is the inhibitor charge. By capturing noncondensable gases, as shown in Fig. 12, comparison can be made to determine if the normal hydrogen byproduct is being produced at anticipated rates. If more hydrogen is being produced than anticipated, a maintenance inhibitor charge may need to be introduced into the machine by the ASP. An inhibitor charge is typically needed every three years in Yazaki gas-fired chiller-heaters. Fig. 12 Capturing Gases WINTERIZING When equipment is located outdoors in climates subject to freezing, cooling water must be drained from the chillerheater, piping, and cooling tower at the end of the cooling season. Use of glycol may also be permissible. Consult the Service Manual for details concerning Anti-Freeze Strategies. When draining a fluid loop, make sure to blow through the emptied loop with compressed air (or similar). Blow in both directions through the loop so as to blow out as much of the residual fluid as possible. This is to help prevent potential tube damage during freezing conditions. TROUBLESHOOTING SYMPTOM: Chiller-Heater does not operate. Possible Cause REMEDY No High Voltage Check the LED for the Power indication on the Control Panel. If it is not illuminated, check the main power disconnect, fuses, and breakers. Solution Pump Not Running Check for illumination of the "FAILURE" LED in the row of indicator LEDs for the Solution Pump. If lit, check the VFD Controller. Manual Reset Device Tripped Check the error codes using the display on the front panel or the ACT5 Maintenance Checker to identify which device is tripped. Check combustion, gas pressure, and vent assembly for conditions that cause over-firing or Unit Overheated prevent proper venting. Check the VFD controller for the Solution Pump. Improper mass flow through the machine can cause overheating symptoms. SYMPTOM: Poor cooling capacity. Possible Cause Poor Vacuum High Inlet Cooling Water Temperature Low Cooling Water Flow Rate Condenser/Absorber Fouling, Scale Buildup REMEDY Evacuate the machine per normal maintenance procedure. Check the cooling tower fan. Check the cooling tower fluid level. Check the cooling tower sump and cooling water circuit strainers. Check the cooling water circuit strainers. It may be necessary to drain the cooling water circuit and open the inspection doors on the chiller-heater condenser and absorber for a visual confirmation. 17

18 WATER QUALITY It is the responsibility of the Owner or End User to have the cooling water analyzed and chemically treated as often as is necessary so that it conforms to the limits shown in Table 1. The water quality in the chilled/hot water and the cooling water circuits should not exceed the following limits: Note: 1. Items shown in the Trend column: An O mark indicates the potential issue should this line item go out of acceptable range. 2. When water temperature rises above 104 F (40 C), the tendency for corrosion rises remarkably. As such, there may arise a need for additional corrosion protection measures such as buffers and inhibitors. 3. For closed-loop cooling towers, use the Hot Water column data in the Circulating Water chart instead of the Cooling Water column data. For make-up water, use the Chilled Water column data instead of the Cooling Water column data. Table 1 Water Quality Charts 18

19 ERROR CODES Error Code Error Description Notes 1 DCP power error Remote monitoring package has lost power. 2 DCP communication line short Power available to the remote monitoring package but communication line is shorted. 3 DCP communication line noise Remote monitoring package cannot communicate with the chiller-heater. 4 Accessory error Optional fire safety shutdown has been enacted. 5 Chilled/hot water pump interlock Voltage signal from terminal CM2 in the junction box is not returning to terminal 3 in the error junction box. 6 Cooling water pump interlock Voltage signal from terminal CM2 in the junction box is not returning to terminal 4 in the error junction box. 7 Cooling tower fan interlock error Voltage signal from terminal CM2 in the junction box is not returning to terminal 5 in the junction box. 8 Solution pump error Solution pump VFD is reporting alarm status. 9 Generator (HGE) over heat error GP sensor indicates 325 F (163 C) or greater. Reset allowed when GP sensor reads below 302 F (150 C). 10 Generator (HGE) temp error GPSC or GPSH manual limit switch open when it should be closed. 12 Generator (HGE) solution level Generator level switch has opened when it should be closed. Ignored for first 10 minutes error of burner operation. 13 WTO sensor error WTO sensor reads below 14 F (-10 C) or above 212 F (100 C). 16 Flow switch error (FS1) FS1 did not open after "P" dry contacts opened. FS1 assumed stuck closed. 18 Seismic switch error Seismic switch is open when it should be closed. 19 Generator (HGE) over heat alarm The Generator temperature or HPS pressure reading has been unusually elevated for 30 consecutive minutes, but has not reached 325 F (163 C). 20 Cooling water scale alarm The temperature rise through the cooling water circuit is less than expected. 21 Cooling water scale error The temperature rise through the cooling water circuit is less than expected to the point of potentially damaging the chiller-heater. 24 Freeze protection error Freeze protection logic steps have been ineffective. 25 High cooling water temperature Cooling water above acceptable temperatures: CTI above 95 F (35 C) and/or CTO above 108 F (42 C) for 3 consecutive minutes. 26 Generator (HGE) over heat in heating mode GP sensor reads above 252 F (122 C) in heating mode. 27 Chilled water flow switch error Flow Switch FS1 is open when it should be closed. 28 Cooling water flow switch error Optional cooling water Flow Switch (FS2) is open when it should be closed. 29 CTO sensor error CTO sensor reads below 14 F (-10 C) or above 212 F (100 C). Ignored for first 10 minutes of P2 operation. 30 Exhaust gas temperature error EXH sensor reads above 446 F (230 C) 31 Generator (HGE) pressure error HPS indicates a pressure above 750 mmhg for 10 consecutive seconds. Reset allowed when pressure falls below 550 mmhg. 32 GP sensor error GP sensor reads above 446 F (230 C) 33 CTI sensor error CTI sensor reads below 14 F (-10 C) or above 212 F (100 C). Ignored for first 10 minutes of P2 operation. 35 Aspirator and exhaust fan error The small exhaust fan in the control box has failed or is unable to cool the box properly. 36 CND sensor error CND sensor reads below 14 F (-10 C) or above 212 F (100 C). 40 Loss of cooling capacity LT temperature reading has not fallen below 59 F (15 C) within 30 minutes. 43 Low cooling water temperature CTI sensor reads below 46.4 F (8 C) at start of operation, or has dropped below this limit for 2 consecutive minutes during operation. 44 Changeover valve error Changeover valve end switch has not closed within 22 seconds. 52 Combustion system error Burner control indicates alarm status. This incorporates all burner limits including air pressure switch, gas pressure switches, and flame safeties. 72 LT sensor error LT sensor reads below 14 F (-10 C) or above 212 F (100 C). 77 HPS output below 0.5vdc for 30 consecutive seconds, OR correlation of HPS pressure Generator (HGE) pressure sensor reading disagrees with GP senor reading after 10 minutes while GP sensor reads above error 212 F (100 C). 88 Corpus pressure error HPS pressure reads above typical atmospheric pressure. Chiller-heater requires tubing inspection to check for tubing breech. 93 Model setting error Configuration and options do not match the model selected in ACT5 Unit Data Set. 94 Check mode neglect Unit left in test mode without interaction longer than 30 minutes. 95 Data initial clear CPU board requires reboot or replacement. 96 Extended Error Code Alert An error code number beyond 99 exists. 101 WTI sensor error WTI sensor reads below 14 F (-10 C) or above 212 F (100 C). 105 Low chilled/hot water temp alert WTO sensor reads below 35.6 F (2 C). Table 2 Error Codes 19

20 YAZAKI AUTHORIZED SERVICE PROVIDER For information concerning service, operation or technical assistance, please contact your Yazaki Authorized Service Provider or the following: YAZAKI ENERGY SYSTEMS, INC. 701 E PLANO PKWY, SUITE 305 PLANO, TEXAS Phone: Fax: yazaki@yazakienergy.com Web: This symbol on the product s nameplate means it is listed by UNDERWRITERS LABORATORIES, INC. Yazaki reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. MGUL-OI-1C2-0813

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER OPERATING INSTRUCTIONS CH-K30, 40, 50, 60, 80, 100 GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER This product is a gas-fired absorption unit which provides chilled water for cooling or hot water for

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER

WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER OPERATING INSTRUCTIONS WFC-SC10, 20, 30 WFC-SH10, 20, 30 WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER This product is a water fired absorption unit which provides chilled water for cooling

More information

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 Specifications CH-MG150CE CH-MG200CE Version 9.10 Contents Page 1. General Information 1.1 Chiller-heater... 2 1.1.1 Chiller-heater Specification. 2

More information

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

Gas-Fired Double-Effect Chiller-Heater

Gas-Fired Double-Effect Chiller-Heater Gas-Fired Double-Effect Chiller-Heater CH-K Series: 30, 40, 50, 60, 80, 100 RT Cooling with Standard Heating Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas-Fired Double-Effect Chiller-Heater

More information

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired Chiller/Chiller-Heater WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired SINGLE-EFFECT Chiller or Chiller-Heater Yazaki Water-Fired SINGLE-EFFECT chillers have cooling capacities of

More information

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.

More information

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K100 Gas-Fired, Double-Effect

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water Aqua Balance WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water User s Information Manual * Low Lead Content If the information in this manual is not followed exactly, a fire

More information

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K Gas-Fired, Double- Effect

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

Universal Fire Tube Boiler Wall Mount Models

Universal Fire Tube Boiler Wall Mount Models Universal Fire Tube Boiler Wall Mount Models USER S INFORMATION MANUAL Models WBRU**80W / 100W / 120W / 140W / 175W / 199W **NG denotes Natural Gas Model, LP Denotes Propane Model Heat Exchanger Bears

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

User s Information Manual

User s Information Manual 48N2,N3,N4,N5,N6,N7,N8,N9 75-150 Ton Gas Heating/Electric Cooling Units with ComfortLink Controls User s Information Manual NOTE TO INSTALLER: This manual should be left with the equipment owner. : If

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

USER'S MANUAL PGE Single Package Rooftop

USER'S MANUAL PGE Single Package Rooftop USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........

More information

CH250 AND CH251 CHILLERS

CH250 AND CH251 CHILLERS CH250 AND CH251 CHILLERS Operator s & Installation Manual Release Date: April 19, 2004 Publication Number: 620914801 Revision Date: May 15, 2015 Revision: G Visit the Cornelius web site at www.cornelius.com

More information

User s Information Manual

User s Information Manual 48AJ,AK,AW,AY020-060 Single-Package Rooftop Gas Heating Units with COMFORTLINK Controls and Scroll Compressors User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use

More information

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing

More information

Owner s Manual Super-Slim Four-Way Cassette

Owner s Manual Super-Slim Four-Way Cassette CASSETTE- TYPE AIR CONDITIONER Owner s Manual Super-Slim Four-Way Cassette IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this

More information

USER S INFORMATION MANUAL (2,4)SG13B

USER S INFORMATION MANUAL (2,4)SG13B USER S INFORMATION MANUAL (2,4)SG13B Series Gas Heating/Electric Cooling Package Unit Congratulations......your outdoor heating/cooling package unit is a valuable piece of equipment, designed and manufactured

More information

Residential Gas Hybrid Water Heater

Residential Gas Hybrid Water Heater Residential Gas Hybrid Water Heater USER S INFORMATION MANUAL WGRGH20NG75F / WGRGH20NG76F / WGRGH20NG100F WGRGHNG75F / WGRGHNG76F / WGRGHNG100F Models* *A suffix of LP denotes propane gas NOTICE: Westinghouse

More information

IMPORTANT INSTRUCTIONS

IMPORTANT INSTRUCTIONS IMPORTANT INSTRUCTIONS W Fan Force Electric Space Heater DANGER ELECTRIC SHOCK OR FIRE HAZARD Figure 1 Covers all W Series models WARNING Read Carefully - These instructions are written in an effort to

More information

TO DO IF YOU SMELL GAS

TO DO IF YOU SMELL GAS User's Information Document 1125B User's Information Manual for Endurance EBP Series Modulating Combination Boiler (natural or propane gas) EDP Series Modulating Hydronic Boiler (natural or propane gas)

More information

Gas Fired Residential Combi Boiler Floor and Wall Mount Models

Gas Fired Residential Combi Boiler Floor and Wall Mount Models Gas Fired Residential Combi Boiler Floor and Wall Mount Models USER S INFORMATION MANUAL Models WBRC**140W WBRC**199W WBRC**140F WBRC**199F ** NG Refers to Natural Gas Operation LP Refers to Propane Gas

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

User s Information Manual

User s Information Manual User s Information Manual Gas-Fired Storage Water Heater, Tankless Water Heater, Heating Appliance, and Combination Appliance Models IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR

More information

Revision B Printed Fall Elston Manufacturing HC Heater Owners Manual

Revision B Printed Fall Elston Manufacturing HC Heater Owners Manual Revision B Printed Fall 2007 Elston Manufacturing HC Heater Owners Manual Table of Contents Important Safety Information... ii 1) Description of Heater... 1 General information about your heater including

More information

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions 16DF013-050 Hermetic Absorption Liquid Chillers/Heaters Start-Up, Operation, and Maintenance Instructions Absorption liquid chillers/heaters provide safe and reliable service when operated within design

More information

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER INSTALLATION INSTRUCTIONS CH-K30 CH-K80 with G Series Control Package GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER This product is a gas-fired double-effect absorption unit which provides chilled

More information

USERS INFORMATION MANUAL FOR GAS FIRED BOILERS

USERS INFORMATION MANUAL FOR GAS FIRED BOILERS USERS INFORMATION MANUAL FOR GAS FIRED BOILERS CATALOG NO.: 2000.52G Effective: 06-01-00 Replaces: 07-01-94 WARNING: If the information in this manual is not followed exactly, a fire or explosion may result

More information

CHILLER. Model CH3000. Operator s & Installation Manual

CHILLER. Model CH3000. Operator s & Installation Manual CHILLER Model CH3000 Operator s & Installation Manual Release Date: February 14, 2011 Publication Number: 620054173OPR Revision Date: May 08, 2014 Revision: B Visit the Cornelius web site at www.cornelius.com

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

ABSORPTION REFRIGERATION SYSTEMS

ABSORPTION REFRIGERATION SYSTEMS BELL SYSTEM PRACTICES AT&TCo Standard SECTION 770-250-303 Issue 1, July 1980 ABSORPTION REFRIGERATION SYSTEMS CONTENTS PAGE CONTENTS PAGE 1. GENERAL........... 3 11. COOLING TOWER BYPASS VALVE.. 9 12.

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

CH750, CH751 & CH951 CHILLERS

CH750, CH751 & CH951 CHILLERS CH750, CH751 & CH951 CHILLERS Operator s & Installation Manual Release Date: April 19, 2002 Publication Number: 91256 Revision Date: March 25, 2014 Revision: F Visit the Cornelius web site at www.cornelius.com

More information

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces P.O. Box 799900, Dallas, TX 75379-9900 USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals,

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

Packaged Gas/Electric

Packaged Gas/Electric Packaged Gas/Electric Units Owner's Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Failure to follow this warning can result in Disconnect power

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP) FGR Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM FGR-8 through FGR-22 (25 HP to 1000 HP) Gas, Light Oil or Combination MANUFACTURED BY JOHN ZINK COMPANY, LLC

More information

User s Information Manual

User s Information Manual 62DA,DB,DC,DD07-38 Vertical or Horizontal Dedicated 100% Outdoor Air Unit with Optional Gas Heat User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment owner. : If the

More information

USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater

USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater Contents Section Page Major Components... 2 1 About Our Manual... 2 2 Refractory Handling...

More information

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507258-04 7/2018 Supersedes 10/2017 ZG 036, 048, 060, 072, 074 (3, 4, 5 and 6 Tons) ZG 092, 102, 120, 150 (7-1/2, 8-1/2, 10 and 12 Tons) ROOFTOP UNITS ZG

More information

User s Information Manual

User s Information Manual User s Information Manual Gas-Fired Water Boilers With or without Aqua Logic (CWH) Now available Matching High Performance Companion Water Heater (Unit sold separately) If the information in this manual

More information

Tankless Water Heater

Tankless Water Heater Tankless Water Heater USER S INFORMATION MANUAL Models WGRT**150 / WGRT**199 / WGRTC**199 **A suffix of LP denotes propane gas **A suffix of NG denotes natural gas NOTICE: Westinghouse reserves the right

More information

Owner s Manual. Middle Static Pressure Duct Type MEU-18MPH2 MEU-24MPH2 MEU-36MPL2 MEU-48MPL2 MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER

Owner s Manual. Middle Static Pressure Duct Type MEU-18MPH2 MEU-24MPH2 MEU-36MPL2 MEU-48MPL2 MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER Owner s Manual Middle Static Pressure Duct Type MEU-18MPH2 MEU-24MPH2 MEU-36MPL2 MEU-48MPL2 IMPORTANT NOTE: Read this manual carefully before installing

More information

Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC

Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC Cooling Unit for Producing Chilled Water Air handling with the focus on LCC Address and telephone list for calling for service Supplier: IV Produkt Box 3103 SE-350 43 VÄXJÖ, Sweden Street address: Sjöuddevägen

More information

Bosch Split-Type Ductless Air Conditioner / Heat Pump

Bosch Split-Type Ductless Air Conditioner / Heat Pump Bosch Split-Type Ductless Air Conditioner / Heat Pump Climate 5000 AA Series User Manual 2 Bosch Split Type Ductless Air Conditioner / Heat Pump User Manual Data subject to change 01.2017 Bosch Thermotechnology

More information

40KMC KMQ

40KMC KMQ 40KMC------301 40KMQ------301 OWNER S MANUAL Split system Global cassette indoor unit IR Remote Control Room Controller Zone Manager The unit can be used with infrared Remote Control, with the Carrier

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL : If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline

More information

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507350-03 3/2016 Supersedes 9/2015 KG 024, 030, 036, 048, 060, 072, 074, 090 (2, 2-1/2, 3, 4, 5, 6 and 7-1/2 Tons) KG 092, 102, 120, 150 (7-1/2, 8 1/2,

More information

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions. User Manual for model FLOWMAX-90 Condensing water heater 85,000 BTU WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1 DUCTED AIR CONDITIONER Owner s Manual KD Series KD24 Kaden Owner s Manual 1 Table of Contents 1. Safety Precautions 4 2. Indoor Unit Parts and Major Functions 6 3. Care and Maintenance 8 4. Troubleshooting

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

User s Information Manual Models: ER152, ER202, ER252, ER302, and ER402

User s Information Manual Models: ER152, ER202, ER252, ER302, and ER402 ERP-USER_100161005_2000003726_Rev D User s Information Manual Models: ER152, ER202, ER252, ER302, and ER402 If the information in this manual is not followed exactly, a fire or explosion may result causing

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

Elite. User s Information Manual. Elite and Elite VWH* All Models

Elite. User s Information Manual. Elite and Elite VWH* All Models Elite User s Information Manual Elite and Elite VWH* All Models Heat Exchanger Bears the ASME H Stamp IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING

More information

Owner s Information Manual

Owner s Information Manual 48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

EL195UHE SERIES GAS FURNACE WARNING WARNING

EL195UHE SERIES GAS FURNACE WARNING WARNING 2012 Lennox Industries Inc. Dallas, Texas, USA 506737-01 12/2012 Supersedes 06/2011 EL195UHE SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com

More information

KSD-35 DR11 KUE-35 DVN11

KSD-35 DR11 KUE-35 DVN11 FLOOR-STANDING TYPE AIR CONDITIONER Owner s Manual Floor-Standing Type KSD-35 DR11 KUE-35 DVN11 IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit.

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

WHEN TROUBLESHOOTING, PERFORM THE STEPS IN ORDER.

WHEN TROUBLESHOOTING, PERFORM THE STEPS IN ORDER. WHEN, PERFORM THE STEPS IN ORDER. BURNER WON T LIGHT Control System 1. Is the main interlock in auto? The burner will not light if the dryer is in manual mode b. No: Switch the main interlock to auto 2.

More information

User s Information Manual

User s Information Manual Gas-fired Water boiler Series 2 NOTICE: Series 1/Series 2 identification Read the boiler rating plate to determine the series number. The rating plate is located on the right side of the boiler. User s

More information

EL195DFE SERIES GAS FURNACE WARNING

EL195DFE SERIES GAS FURNACE WARNING 2011 Lennox Industries Inc. Dallas, Texas, USA 506739 01 06/2011 EL195DFE SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G PGM-1 Cooktops For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G Install ation Instructions Part No. 65476 Rev. B Table of Contents Appliance Safety...1 Important Safety Instructions...2

More information

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only.

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only. 110 Cup (55 Cup Raw) Gas Rice Cooker Intertek 5010781 Conforms to ANSI STD Z83.11-2016 Model: 177GRCLP, 177GRCNAT 12/2018 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liquids

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

User s Information Manual

User s Information Manual User s Information Manual CONDENSING GAS BOILER 220/299/300/399 If the information in this manual is not followed exactly, a fire or explosion may result, causing property damage, personal injury or loss

More information

MC Series Gas-Fired Heating Appliance

MC Series Gas-Fired Heating Appliance MC Series Gas-Fired Heating Appliance USER S INFORMATION MANUAL MC Series Models MC50 / MC80 MC99 / MC120 NOTICE: HTP reserves the right to make product changes or updates without notice and will not be

More information

USER GUIDE VOGUE MAX SYSTEM

USER GUIDE VOGUE MAX SYSTEM USER GUIDE VOGUE MAX SYSTEM 15 18 26 32 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

PAC12J. 12,000btu Cool & Heat Portable Air Conditioner. Please read this manual carefully prior to operating the product.

PAC12J. 12,000btu Cool & Heat Portable Air Conditioner. Please read this manual carefully prior to operating the product. USER MANUAL Portable Air Conditioner and Heater With Heat Pump Technology PAC12J 12,000btu Cool & Heat Portable Air Conditioner Please read this manual carefully prior to operating the product. Please

More information

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N OPERATING MANUAL AIR CONDITIONER DUCT TYPE ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N9374379293-02 CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS... 2 PREPARATORY OPERATION...

More information

User s Information Manual

User s Information Manual TM User s Information Manual Commercial Condensing Gas-fired water boilers If the information in this manual is not followed exactly, a fire or explosion may result, causing property damage, personal injury

More information

Operating Instructions

Operating Instructions Operating Instructions BA-003 Read and understand this manual before use. Keep this manual for future reference. CONFORMS TO UL STD.No.1017 Certified to CSA STD C22.2 No.243-10 For questions or concerns

More information

Operating instructions

Operating instructions Operating instructions Gas condensing boiler WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

More information

EL195UH SERIES GAS FURNACE WARNING

EL195UH SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506597 01 11/2010 EL195UH SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

G61MPV SERIES GAS FURNACE WARNING

G61MPV SERIES GAS FURNACE WARNING 2003 Lennox Industries Inc. Dallas, Texas, USA 504,809M 03/2009 Supersedes 06/2003 G61MPV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result

More information

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Thank you for purchasing our fully-automatic gas-fired tankless water heater. Please completely read this Manual

More information

16TJ Single-Effect Steam-Fired Absorption Chillers

16TJ Single-Effect Steam-Fired Absorption Chillers 16TJ Single-Effect Steam-Fired Absorption Chillers Nominal cooling capacity 352-2461 kw 50 Hz Operation and maintenance instructions GB/T-19001-2000 to ISO9001/2000 NOTES TO USERS Thank you for purchasing

More information

WARNING FIRE OR EXPLOSION HAZARD.

WARNING FIRE OR EXPLOSION HAZARD. 2017 Lennox Industries Inc. Dallas, Texas, USA 506897-01 04/2017 Supersedes 10/2015 EL280DF SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

OWNER S MANUAL VMH 09/12/18/24

OWNER S MANUAL VMH 09/12/18/24 OWNER S MANUAL VMH 09/12/18/24 Version C Inverter Single Zone Ductless Mini-Split Heat Pump Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com VMH Inverter

More information

Utopian Split A/C. Thank you for purchasing this quality Split A/C system!

Utopian Split A/C. Thank you for purchasing this quality Split A/C system! Utopian Split A/C Thank you for purchasing this quality Split A/C system! Please read through this manual completely, and keep it in case you need to reference the information in the future. Any operation

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL 2005 Lennox Industries Inc. Dallas, Texas, USA USER S INFORMATION MANUAL 13GCSX SERIES UNITS GAS PACKAGED UNITS (2 5 TONS) Armstrong # 38152A068 505,058M 05/09 Supersedes 08/05 Table of Contents Litho

More information