Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC

Size: px
Start display at page:

Download "Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC"

Transcription

1 Cooling Unit for Producing Chilled Water Air handling with the focus on LCC

2 Address and telephone list for calling for service Supplier: IV Produkt Box 3103 SE VÄXJÖ, Sweden Street address: Sjöuddevägen 7 Phone: +46 (0) Telefax: +46 (0) Seller:... Service:... Post address:... Post address:... Telephone:... Telephone:... Other:... System Data Type of unit:... Order number:... Year manufactured:... Supply voltage:... Refrigerant:... SAQ approved HP:... Hydrostatic test:...

3 Air handling with the focus on LCC Page 3 Contents 1. The Cooling and Heat Pump System General How the Cooling Circuit Works How the Controller Works 4 2. Summary of Specific Rules in the Refrigerant Act One-piece Units containing less than 3 kg of Refrigerant One-piece Units containing more than 3 kg of Refrigerant One-piece Units containing a total of more than 10 kg of Refrigerant 6 3. Operating Instructions for Components and Assembled Equipment Regulations for Commissioning Checklist 8 4.Maintenance Instructions and Procedures General Requirements by Authorities according to the Refrigerant Act Periodic Inspection 9 5. Fault Tracing and Searching for Leakage Fault-tracing Schedule Searching for Leakage Flow Diagram for the Refrigerant System Technical Specification Appendices 8:1 Pressure and Tightness Tests - Refrigerant Circuit 8:2 Safety Equipment 8:3 Commissioning Report 8:4 Pressure and Tightness Tests - Liquid Circuits

4 Page Air handling with the focus on LCC 1. The Cooling and Heat Pump System 1.1 General All cooling and heat pump systems operate according to the same principle. The system moves the heat content in a medium, such as air, water, gas, etc. from one space where the heat isn t wanted or needed, to another place where it is possible to utilise the heat, or get rid of it. Your system has been designed and installed to meet given performance requirements. We ve selected and combined special components to meet these requirements with optimum safety and at lowest possible total cost. We ve designed the system according to specific fundamental prerequisites, which must exist for it to operate. These prerequisites should not be altered without first checking that the system can cope with this change. 1.2 How the Cooling Circuit Works See the flow diagram. The refrigerant in the cooling circuit absorbs heat from the component being chilled while it passes through the evaporator. As its pressure drops, the refrigerant evaporates and transforms from liquid to gas. The cold suction gas that now has absorbed heat from the cooled space/medium is sucked back into the compressor where it is compressed and heats up. In all fully hermetic compressors, the suction gas is also used to cool the electric motor that drives the compressor. The refrigerant now contains heat from the component being chilled, heat from the compressor motor and heat generated by compression. The refrigerant is in the form of hot gas when it leaves the compressor and circulates to the condenser where it gives off its heat. The refrigerant then condenses as it cools, transforming from gas to liquid. This occurs repeatedly in a totally closed system, until the temperature in the chilled/heated medium drops/rises to its set point. 1.3 How the Controller Works Interlocking EVC is interlocked across an external start signal Operation The selector switch S1 is used for initiating start-up (yellow LED is lit). When the temperature at the heating medium sensor drops below the preset value, a signal is transmitted across the stepping switch to start the compressors in a preset starting order so as to maintain the preset temperature. The in-operation condition of each compressor is indicated across the stepping switch. Output terminal blocks are provided for in-operation indication.

5 Air handling with the focus on LCC Page Compressor Protection If the safety circuit alarm trips the compressor will stop and a red LED will light up. A flow monitor supervises the water flow in the cooling medium circuit. On insufficient flow the monitor stops the compressors and initiates an alarm across a stepping switch. The flow monitor alarm can be reset by setting the selector switch S1 in the 0 position. The safety circuit alarm will trip if any of the following four conditions arises: High pressure in the system, HP Low pressure in the system, LP Tripped protective motor switch Q Tripped thermocouple in the compressor The group alarm safety circuit has output terminal blocks. If the safety circuit alarm trips repeatedly, get in touch with an authorised refrigeration service company Technical Description The compressor power cubicle of the EVC unit contains the following: Main switch Protective motor switch Contactors Auxiliary relays Controller Selector switch Flow monitor The cubicle is mounted inside the EVC unit and has been internally prewired and tested at the factory. Safety circuit alarm If a red LED is lit, the safety circuit of the relevant compressor has tripped. To reset the safety circuit Press the reset button on the high pressure switch or low pressure switch. Reset the protective motor switch. XC440C C1 C2 C3 C4 ((!)) 1 2 Flow monitor alarm If a buzzer sounds and a red LED is lit, the flow monitor alarm has tripped. AL prg SET EVC Selector switch O = EVC switched off I = EVC start mode To reset the flow monitor alarm Press the switch to O; then press it to I again. I O Size Rec. fuse Rec. cable section EVC-1610 EVC-2410 EVC-3110 EVC-4020 EVC-4820 EVC-6220 EVC-7830 EVC AT 25 AT 35 AT 50 AT 50 AT 63 AT 80 AT 100 AT 4 mm 2 6 mm 2 10 mm 2 16 mm 2 16 mm 2 25 mm 2 35 mm 2 50 mm 2 o C Dixell In-operation indication A red LED indicates that the compressors are running. Running period compressors Press and hold the clock button for at least 3 sec. Shows the running period of each compressor. Set point To show the set point: press the SET key. To change the set point: press the SET key for at least 2 sec. Alter the setting by pressing the arrow up or arrow down key. Then press the SET key to save your setting. Input cables LJ L1 L2 L3 N PE Power supply 3*x 400 V + N 50 Hz External start signal Potential-free, NO Group alarm Potential-free, NO In-operation indication C1, C2, C3 Potential-free, NO *) If the order of phases is wrong, the machine will run unusually loud.

6 Page Air handling with the focus on LCC 2. Summary of Specific Rules in the Refrigeration Act 2.1 One-piece Units containing less than 3 kg of Refrigerant The maintenance and service of these units should be carried out with good judgement and a certain degree of responsibility. This means, for example, that if you discover a leak, you must not charge the refrigeration circuit with additional refrigerant unit the leak has been sealed. Furthermore, you must always take care of refrigerant that you ve emptied from the unit either by reusing it or sending it to an appropriate facility for destruction. As far as service and maintenance are concerned, no qualifications stipulated by authorities are required of the technician who carries out this work. Although common sense and good judgement are important when servicing the unit. If servicing calls for a modification of the refrigerant circuit, only a certified refrigeration technician shall be permitted to carry out this work. No reporting to the authorities is required in conjunction with these cooling units. One-piece cooling units charged with 3 kg or less refrigerant are treated in system calculations as if they didn t contain any refrigerant at all. This means that you can add or include any number of one-piece cooling units of the type described above in a system, without being required to take increased refrigerant volume into consideration. 2.2 One-piece Units containing more than 3 kg of Refrigerant Besides complying with the above, the units and components of these systems shall be inspected in accordance with local standards and regulations at least once a year. The responsibility for seeing to it that this inspection is carried out rests on the owner of the system. A permit/authorisation for this is required for all permanent installations. 2.3 One-piece Units containing a total of more than 10 kg of Refrigerant Besides complying with the above, entries concerning the performance and maintenance of the units and components of these systems must be entered in a journal. The responsibility for seeing to it that such a journal is kept up-to-date rests on the owner. This journal must then be sent to an inspectorate for scrutiny once a year. If each circuit is charged with refrigerant in excess of 10 kg, special requirements are made on the equipment in the system.

7 Air handling with the focus on LCC Page 7 3. Operating Instructions for Components and Assembled Equipment 3.1 Regulations for Commissioning All wiring shall be completed prior to commissioning. The cooling medium and heating medium flows shall be adjusted according to specifications and these settings shall be entered in the Commissioning Report. Only qualified technicians shall be allowed to commission the system according to an accompanying checklist complete with commissioning record. A copy of the Commissioning Record shall first be signed by the technician who has commissioned the unit, then be signed by the seller and after that be sent in to IV Produkt. The validity of the product warrantee is conditional on the system having been correctly commissioned. No modifications in the machine are permissible during the warrantee period without the approval by IV Produkt. Follow the fault tracing directions in the fault tracing schedule before you contact a service representative for servicing the unit under warrantee. This will prevent any unnecessary service calls.

8 Page Air handling with the focus on LCC 3.2 Checklist 1. Check the power supply. Make sure that the phase leads are wired to the correct terminal. Make sure that the zero lead and the earth lead are wired. 2. Check that input cables from an external control cubicle are wired to the correct terminal and in the correct manner according to the wiring diagram, e.g: shielded cable wiring to correct terminal in motors terminal block screws are tightened 3. Switch off ALL protective motor switches 4. Switch in the power supply and fuses. 5. Feel the compressors to make sure that the crankcase heating is switched in. 6. Check that the water connections are complete and that there is water. 7. Switch in the pumps. Make sure that they discharge in the right direction. 8. A pump that won t start: check the wiring diagram. If it is interlocked: Temporarily cancel the interlock. 9. Check the pump data against the motor protection and the diagram. 10. Make sure that the water system has been carefully purged of air. 11. Check that water is flowing in the circuit. The measurement valves are on the EVC. See flow data in EVC specification. 12. When the flow is correctly set, lock the valves. 13. If you ve cancelled any interlock in order to start the pumps, restore it. 14. Check that the transducer is wired to the to the right measurement point. 15. Check that the sensor is at the correct location according to the diagram and that it works properly. 16. Check that the protective motor switch and the time relay are correctly set according to the Commissioning Report. 17. Now run through all the control functions according to their functional description in the wiring diagram. Both AHU and EVC WITHOUT STARTING THE COMPRESSORS. 18. It is important that the oil in the compressor crankcase is warm before the compressor is switched in. The crankcase heat should be switched in well in advance of commissioning (2 3 hours) to allow the oil to reach a temperature of at least 30 C ca.the temperature can be measured externally on the bottom of the compressor. 19. Connect the manometer mount on the service outlet; purge the air hoses. NOTE: Type of refrigerant 20. Start up the AHU and the EVC. Now test the compressors separately and follow the commissioning record. Let the compressors run for a while before you begin measuring, approx.10 minutes. Test the safety functions 21. After the compressors have been tested separately, test all of them at the same time. Review the commissioning record. 22. Now let the unit run until it stops as intended according to the preset control function. 23. Send one set of the commissioning records to: IV Produkt.

9 Air handling with the focus on LCC Page 9 4. Maintenance Instructions and Procedures 4.1 General This section of the instructions is intended for general use. We ve worded it in such a way so as to enable you to carry out simple periodical inspections of the system and to show you simple checks that you can carry out before having to call for qualified service help in the event of a malfunction. If more advanced troubleshooting in the system is necessary, you will find the information you need in the accompanying wiring diagrams and special instructions for the components of the system. 4.2 Requirements by Authorities according to the Refrigerant Act An inspector from an accredited company shall in accordance with Local Cooling Standards, inspect one-piece cooling units containing more than 3 kg of refrigerant. All service and modification of the cooling system and charged or emptied refrigerant shall be recorded in the journal. If the total volume of refrigerant exceeds 10 kg (Note! The total volume of all the units in the building), this must be reported to the local Environmental and Public Health Authorities and an annual report must be submitted to them. 4.3 Periodic Inspection 1. Appoint someone or qualified staff to be responsible for periodical inspections of the cooling system. Make sure that these technicians possess knowledge of how the system operates and where system components are located. 2. The system is designed to operate automatically.the Commissioning Record indicates the settings at which the system was set when it was commissioned. Make sure that the settings on the thermostats, controllers, pressure switches and other adjustable components have not been altered by someone who lacks knowledge about how the system operates. 3. See to it that the machine room or other component locations are kept clean. 4. Certain components in the system may require open space for contact with the surrounding air to operate properly. Make sure that this open space is not temporarily or permanently blocked in any way. If any of these components is equipped with an air filter or dirt filter, check these filters every third month. Replace filters whenever needed. 5. The cooling unit does not normally require any lubrication, oil changes or the like. In cases where special regulations pertain to any specific system component, this is explained in the instructions for that component. 6. The system and its components shall be inspected by qualified service technicians at least once a year. The inspection should include the following: Check the refrigerant system for tightness. Check that the system hasn t sustained any serious corrosion damage. Check that the safety equipment is in good condition. 7. Keeping a journal. Entries shall be made every time each system is charged or emptied of refrigerant, the results of searches for leakage and other measures in conjunction with inspecting and servicing the refrigerant circuit and its operation. 8. Are you uncertain about anything regarding your cooling system? If so, get in touch with your supplier! Sometimes it s better and cheaper to call once too often than too seldom.

10 Page Air handling with the focus on LCC 5. Fault Tracing and Searching for Leakage 5.1 Fault-tracing Schedule SYMPTOM POSSIBLE CAUSE REMEDIAL MEASURE Too high temperature in cooled component/medium The power supply has been interrupted. No flow or poor flow across the evaporator. The thermostat/control equipment is incorrectly set/faulty. The compressor doesn t work. Check the control/safety switches and fuses. Check that nothing is blocking the flow. Check that the system is well purged of air. Adjust the setting or replace the equipment. See under Compressor The compressor doesn t work. The power supply has been interrupted. The safety circuit has switched out the compressor. Pressure switches, temperature monitor, flow monitor, antifrosting protection or motor protection. Faulty compressor. Check the control/safety switches and fuses. Check and reset if required. Determine the fault. Replace the compressor. The low-pressure switch switches out the compressor. Too little refrigerant. No flow or poor flow across the evaporator. Too high glycol content. Faulty expansion valve. Faulty low-pressure switch. There is a leak in the system. Seal the leak and charge with refrigerant. Check the flow. Check the static pressure in the expansion vessel. Check the circulation pump. Check the glycol content. Check, replace. Check, replace. The high-pressure switch switches out the compressor. No flow or poor flow across the condenser. Too much refrigerant in the system. Faulty high-pressure switch. Check the flow across the condenser. Check the static pressure in the expansion vessel. Check the circulation pump. Reduce the refrigerant volume. Check, replace. Substantial frosting on the evaporator. The expansion valve is incorrectly set/ faulty. Too little refrigerant. The evaporator is fouled. Check, replace. Check in the sight glass. The system is leaking; seal the leakage; charge with refrigerant. Check the flow, filter if fitted, clean the evaporator if needed.

11 Air handling with the focus on LCC Page Searching for Leakage A search to detect leakage in the system should be made at least once per calendar year as a preventive measure. This leakage search should be recorded and entered in the journal. The cooling system can develop a leak. This becomes apparent first by impaired cooling performance or the system won t operate at all due to a momentary leakage. If you suspect refrigeration leakage, check the level of refrigerant in the sight glass of the system. The sight glass is located in the fluid pipe by the refrigerating machine. If you see bubbles continuously forming in the sight glass, and the cooling performance of the system is at the same time poor, the probable cause is that the system is leaking. If you see one or two or just a few bubbles in the sight glass when the machine starts up, and notice that it operates with reduced output or operates normally does not necessarily mean that the refrigerant volume is too low. IF BUBBLES APPEAR IN THE SIGHT GLASS AND THE PERFORMANCE OF THE SYSTEM IS NOTICEABLY BAD CALL AN AUTHORISED SERVICE REPRESEN- TATIVE FOR HELP. Keep in mind that refrigerant must not be released into the atmosphere and that escaping refrigerant can cause burns if it comes into contact with skin. If it becomes necessary to make modifications in the refrigerant circuit, the staff doing this work must wear the proper protective equipment. MODIFICATIONS IN THE REFRIGERANT SYSTEM MUST ONLY BE CARRIED OUT BY AN ACCREDITED INSPECTORATE A COMPANY WITH A REQUIRED PERMIT

12 Page Air handling with the focus on LCC 6. Flow Diagram for the Refrigerant System 1. KK Cooling compressor 2. VO Oil heater 3. GP High-pressure switch 4. MU Measurement tapping of Schrader valve 5. KD Liquid cooling condenser 6. SG Sight glass 7. FT Drying filter 8. MU Measurement tapping of Schrader valve 9. VS Thermostatic expansion valve with external pressure compensation 10. EV Liquid cooler 11. MU Measurement tapping of Schrader valve 12. GP Low pressure switch

13 Air handling with the focus on LCC Page Technical Specification Specification Cooling Unit for liquid Size 1610, 2410, 3110, 4020, 4820, 6220, 7830, 9330 EVC-a EVC: Cooling power (Pk) kw Condenser power (Pvv) kw Compressors (Qty) each Cooling circuits (Qty) each Cooling medium Water temp. +7/+12.5 C l/s Internal pressure in kpa connection point Connection diameter (dy) mm Rec. cooling medium volume (min) l Heating medium Water temp. +31/+39 C l/s Internal pressure in kpa connection point Connection diameter (dy) mm Refrigerant HFC 407C kg/circuit kg/circuit kg/circuit Total kg Electrical data Recommended fuse AT Casing Version size A A A B B B C C Weight kg

14 Page Air handling with the focus on LCC

15 Air handling with the focus on LCC Industriventilation Produkt AB, Box 3103, SE Växjö, Sweden Phone: +46 (0) E-D

Envistar Operation and Maintenance Instructions

Envistar Operation and Maintenance Instructions Air Handling Unit Envistar Instructions Project:... Air handling with the focus on LCC Address and Telephone Register for Service Supplier: IV Produkt AB Box 3103 SE-350 43 VÄXJÖ, Sweden Street address:

More information

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit!

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit! Safety Precautions IMPORTANT INFORMATION! The unit must NOT be used in any other way than as a cooling unit! Carefully read, study and understand the Operation and Maintenance Instructions before you commission

More information

USER MANUAL. Danfoss Heat Pump DHP-R VUIFK102

USER MANUAL. Danfoss Heat Pump DHP-R VUIFK102 USER MANUAL Danfoss Heat Pump DHP-R VUIFK102 Table of contents 1 Important information........................................................... 4 1.1 Safety precautions...4 1.2 Protection...4 2 About

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Technical instructions

Technical instructions Énergie Transfert Thermique Technical instructions A different climate Environmental control solutions Version IMPORTANT The warranty of ETT units depends on the respect of these technical instructions

More information

INSTRUCTIONS RHS 700. Recovery, Recycling, Evacuation and Charging Station RHS 700

INSTRUCTIONS RHS 700. Recovery, Recycling, Evacuation and Charging Station RHS 700 A GRAMKOW A/S Augustenborg Landevej 19 DK-6400 Sønderborg Denmark A/S Reg. No. 17 12 31 Telephone: 45 74 12 36 36 Telefax: 45 74 43 36 46 Telex: 5 23 18 Bank: Den Danske Bank, No. 32 27 INSTRUCTIONS Recovery,

More information

Instruction manual CCU 5-P. Table of contents

Instruction manual CCU 5-P. Table of contents Instruction manual Version: 1.0040.40 Updated: 09/02/2018 Replaces: CCU 5-P Table of contents Introduction... s. 2 Design / Construction... s. 3 Flammable gases and liquids... s. 4 Safety... s. 4 Service

More information

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual Ventilation and air conditioning QUALITY FOR LIFE GB Refrigerating systems and heat pumps Operating manual Refrigerating systems and heat pumps 3052967 I 07/2010 Refrigerating systems and heat pumps Table

More information

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

OPERATING MANUAL AIR CONDITIONER DUCT TYPE. ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N OPERATING MANUAL AIR CONDITIONER DUCT TYPE ART Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N9374379293-02 CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS... 2 PREPARATORY OPERATION...

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

REFRIGERANT ON-VEHICLE INSPECTION AC 14

REFRIGERANT ON-VEHICLE INSPECTION AC 14 14 REFRIGERANT ON-VEHICLE INSPECTION 1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET (a) This is a method to specify trouble areas by using a manifold gauge set. Read the manifold gauge pressure

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Instructions for installation

Instructions for installation Instructions for installation Read this notice carefully before installing, maintaining or repairing this appliance! The symbol indicates important information that you must take into account to avoid

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw

Technical Guide. Installation, Operation and Care. EP E series 7 step electric boilers 26 and 42 kw Technical Guide Installation, Operation and Care EP E series 7 step electric boilers 26 and 42 kw Arkelstorpsvägen 88, 291 94 KRISTIANSTAD Tel +46 44-22 63 20, Telefax +46 44-22 63 58 e-mail: info@varmebaronen.se

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

INSTALLATION AND OPERATING INSTRUCTIONS General operating instructions for sample gas conditioner Model: MAK 6

INSTALLATION AND OPERATING INSTRUCTIONS General operating instructions for sample gas conditioner Model: MAK 6 List of contents 1.0 Uses 2.0 Technical data 2.1 Operating data 2.2 Construction and installation 2.3 Climatic load 2.4 Power supply 3.0 Function and design 3.1 General comments 3.2 Design 3.3 Performance

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODEL: CFF-500 Operator s & Installation Manual Release Date: November 3, 1996 Publication Number: 90667 Revision Date: May 10, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP AXIAL HEATER TROUBLE SHOOTING GUIDE Page 1 July 2009 Table of Contents Frequently Asked Questions... 3 Axial Heater CONTROL (Siemens LME69) Troubleshooting Chart... 4 Axial Heater BURNER Troubleshooting

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

Technical instructions

Technical instructions Energie Transfert Thermique Technical instructions A different climate Environmental control solutions Version IMPORTANT The validity of our guarantee is conditional upon compliance with these technical

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

Mobile Air-Con Service Solution. AC7000 Operation Manual

Mobile Air-Con Service Solution. AC7000 Operation Manual Mobile Air-Con Service Solution AC7000 Operation Manual Cool-It Mobile HVAC Group Contents 1 About this operation manual.......................................... 2 1.1 Cool-It Hotline......................................................

More information

DOMESTIC STEAM GENERATOR Installation Instructions

DOMESTIC STEAM GENERATOR Installation Instructions DOMESTIC STEAM GENERATOR Installation Instructions Please read all of the instructions carefully before commencing installation or using the facility. Contents INTRODUCTION Page 2 TECHNICAL SPECIFICATION

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

HEAT & COOL MODEL (REVERSE CYCLE)

HEAT & COOL MODEL (REVERSE CYCLE) OPERATING MANUAL HEAT & COOL MODEL (REVERSE CYCLE) AIR CONDITIONER Duct Type Indoor Unit ARTG09LL ARTG12LL ARTG18LL KEEP THIS MANUAL FOR FUTURE REFERENCE P/N9374379439 CONTENTS SAFETY PRECAUTIONS... 1

More information

PAC12J. 12,000btu Cool & Heat Portable Air Conditioner. Please read this manual carefully prior to operating the product.

PAC12J. 12,000btu Cool & Heat Portable Air Conditioner. Please read this manual carefully prior to operating the product. USER MANUAL Portable Air Conditioner and Heater With Heat Pump Technology PAC12J 12,000btu Cool & Heat Portable Air Conditioner Please read this manual carefully prior to operating the product. Please

More information

SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT. DocID: 00G00019E

SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT. DocID: 00G00019E SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT DocID: 00G00019E 2008 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

Synergy3 Owner s Manual. Owner s Manual. Geothermal Heating Cooling Hot Water

Synergy3 Owner s Manual. Owner s Manual. Geothermal Heating Cooling Hot Water Owner s Manual Geothermal Heating Cooling Hot Water 13 Contents System Benefits 2 How GeoExchange Systems Work 3 GeoExchange System Types 4 WaterFurnace Quality Commitment 5 Warranty 5 Operating Procedures

More information

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1 Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,

More information

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

HYDROCIAT LW R407C. Water cooled chillers USE RANGE Screw compressors CIAT dry direct expansion shell and tubes evaporator HPS equipment (High Power System) cooling or heating Heat recovery ENVIRONMENTALLY HFC R407C PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information

Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology

Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology OWNER'S MANUAL Model # KY-34 3046364 Please read owner s manual carefully before operating unit. TABLE OF CONTENTS INTRODUCTION...3

More information

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions Model No. GB-PAC-08E4 8,000 BTU Portable Air Conditioner Operating Instructions Thank you for choosing a Soleus Air Powered by Gree Portable Air Conditioner. This owner s manual will provide you with valuable

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions. Model No. PE4-11R Soleus Air International

11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions. Model No. PE4-11R Soleus Air International 11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions Model No. PE4-11R-03 2006 Soleus Air International Thank you for choosing a Soleus Air Portable Air Conditioner.

More information

Trouble Shooting Guide RAA, 1-phase (D3627)

Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

Zehnder ComfoInline Heater

Zehnder ComfoInline Heater Zehnder ComfoInline Heater Specifications and Installation Guidelines This unit complies With CSA and UL SDHR5-1.5K120V1P-CIRO17-OTDD-OEMZ standards SDHR6-2.5K220V1P-CIRO17-OTDD-OEMZ SDHR7-3.5K220V1P-CIRO17-OTDD-OEMZ

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

Trouble Shooting Guide PAA, 1-phase (D3731)

Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user Operating instructions for the system user VIESMANN Heating system with control unit for constant temperature or weather-compensated mode VITODENS 100-W 1/2012 Please keep safe. Safety instructions For

More information

Electronically controlled instantaneous water heater. DEX: C models. Instructions for the user

Electronically controlled instantaneous water heater. DEX: C models. Instructions for the user Electronically controlled instantaneous water heater DEX: 27930-50 C models Instructions for the user For 50 ºC models, the appliance delivers water not exceeding 50 ºC in accordance with AS3498. MADE

More information

User manual AG-WT10. Indoor unit air/air heat pump UHB GB

User manual AG-WT10. Indoor unit air/air heat pump UHB GB User manual Indoor unit air/air heat pump UHB GB 1516-1 331557 Table of Contents 1 Important information Installation data Safety information Serial number an excellent choice Safety instructions Recovery

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

R410A. AIR CONDITIONER DUCT TYPE / ART Series OPERATING MANUAL. REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A.

R410A. AIR CONDITIONER DUCT TYPE / ART Series OPERATING MANUAL. REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A. AIR CONDITIONER DUCT TYPE / ART Series OPERATING MANUAL KEEP THIS OPERATION MANUAL FOR FUTURE REFERENCE R410A REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A. THIS PRODUCT

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

Settings and Maintenance of the CombinAir

Settings and Maintenance of the CombinAir Atmos CombinAir Settings and Maintenance of the CombinAir Issue 13.8.10 Operation and commissioning: The control unit on the front of the CombinAir is used to adjust the settings during commissioning.

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

Installation instructions Danfoss heat pump DHP-R

Installation instructions Danfoss heat pump DHP-R Installation instructions Danfoss heat pump DHP-R Table of contents DHP-R 1 Important information........................................................... 5 1.1 Refrigerant...5 1.2 Noise and vibrations...5

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

Electronically controlled instantaneous water heater CEX 9. CEX9: C models. Instructions for the user

Electronically controlled instantaneous water heater CEX 9. CEX9: C models. Instructions for the user Electronically controlled instantaneous water heater CEX 9 CEX9: 27900-50 C models Instructions for the user For 50 ºC models, the appliance delivers water not exceeding 50 ºC in accordance with AS3498.

More information

ph COOLING TOWER CONTROLLER

ph COOLING TOWER CONTROLLER LAKEWOOD INSTRUMENTS MODEL 350 ph COOLING TOWER CONTROLLER INSTRUCTION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI 53224 USA Phone (800) 228-0839 Fax (414) 355-3508 http://www.lakewoodinstruments.com

More information

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976H207 (10-06) PP TABLE OF CONTENTS I. General

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT. DocID: 00G00010EA

SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT. DocID: 00G00010EA SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT DocID: 00G00010EA 2008 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

- 1 - Updated on 18 March, 2010

- 1 - Updated on 18 March, 2010 - 1 - Updated on 18 March, 2010 TABLE OF CONTENTS 1. SPECIFICATION & PARTS IDENTIFICATION...3 2. OPERATION & FUNCTION OF PARTS...4, 5 A. Cooling Operation B. Heating Operation C. Function of Parts 3. LOCATION

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps Table of Contents From practical experience, for your practical needs...

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS Before using the heater, read and understand all instructions and follow them carefully. The manufacturer is not responsible for damages to goods

More information

12,000 BTU Evaporative Portable Air Conditioner

12,000 BTU Evaporative Portable Air Conditioner 12,000 BTU Evaporative Portable Air Conditioner Owner s Manual Model # KY-32E Please read owner s manual carefully before operating the unit. TABLE OF CONTENTS PAGE Table of Contents. 2 Introduction....3

More information

DANFOSS OPTYMA PLUS INVERTER UNITS

DANFOSS OPTYMA PLUS INVERTER UNITS Optyma Plus Inverter Condensing Units Danfoss Optyma Plus Inverter Units are designed with the unique benefits of stepless inverter scroll technology resulting in a 20-30% higher energy efficiency in a

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

User manual AG-WT10. Indoor unit air/air heat pump UHB GB LEK

User manual AG-WT10. Indoor unit air/air heat pump UHB GB LEK LEK User manual Indoor unit air/air heat pump UHB GB 1715-3 331557 Table of Contents 1 Important information Installation data Safety information Serial number an excellent choice Safety instructions

More information

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS TABLE OF CONTENTS I. General Information.................................................. 2 II. Standard Ceiling Plenum

More information

Rules for Safe Operation

Rules for Safe Operation Rules for Safe Operation Important: Do not attempt to operate the CleanStation until you have read thoroughly and understand all instructions and safety rules contained in this manual. Failure to comply

More information

Telephone Helpline: (Australia) Blast Chiller / Freezer. Instruction Manual. Model DN492-A DN494-A

Telephone Helpline: (Australia) Blast Chiller / Freezer. Instruction Manual. Model DN492-A DN494-A Blast Chiller / Freezer Instruction Manual Model DN492-A DN494-A 1 Safety Tips Position on a flat, stable surface. A service agent/qualified technician should carry out installation and any repairs if

More information

B 353 COFFEE BREWING MACHINES MACHINES A CAFE KAFFEEBRUEHMASCHINEN KOFFIEZETAPPARATEN

B 353 COFFEE BREWING MACHINES MACHINES A CAFE KAFFEEBRUEHMASCHINEN KOFFIEZETAPPARATEN Chiller A B C1 C2 C3 C4 C D E L H G F J M I K N Fig. 1 Principal components and Control organs E=154 W=78 115 572 755 200 35 482 415 245 E/W = 61 Fig. 2 Dimensions Bravilor Bonamat GB Operating instructions

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

Operating instructions Page 12

Operating instructions Page 12 Operating instructions Page 12 Refrigerator with explosion-proof interior container Read the operating instructions before switching on for the first time 7082 271-00 LKEXv 910 Disposal notes The appliance

More information

OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS:

OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS: OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS: 79202-00 79202-05 79202-30 79202-35 Approval Agency s Model 79202-00 & 79202-05 Model 79202-30 & 79202-35 Not recommended for pumping acid,

More information

VADA - Rain2Main Automatic Rainwater Controller

VADA - Rain2Main Automatic Rainwater Controller PRODUCT OVERVIEW / APPLICATION The Vada Rain2Main is designed to select between stored rainwater (when available) and mains supply water, and send this water to your toilet cistern, washing machine, garden

More information

SERVICE MANUAL CLASSIC PLUS 26 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT. DocID: 00G00025E

SERVICE MANUAL CLASSIC PLUS 26 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT. DocID: 00G00025E SERVICE MANUAL CLASSIC PLUS 26 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT DocID: 00G00025E 2009 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling CONTENTS 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling 6. Installation 6.1 Plates 6.2 Dimensions 6.3 Location 6.4 Free room 6.5 Installation

More information

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION Ecoline Geo RI HP INSTALLATION MANUAL The Ecoline GEO is an indirect unvented cylinder designed and approved for use with a heat pump. The

More information

OPERATING MANUAL. AIR CONDITIONER Duct Type. Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH PART NO KEEP THIS MANUAL FOR FUTURE REFERENCE

OPERATING MANUAL. AIR CONDITIONER Duct Type. Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH PART NO KEEP THIS MANUAL FOR FUTURE REFERENCE OPERATING MANUAL AIR CONDITIONER Duct Type Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH KEEP THIS MANUAL FOR FUTURE REFERENCE PART NO. 9374379583 CONTENTS SAFETY PRECAUTIONS... 2 FEATURES AND FUNCTIONS...

More information

OPERATION MANUAL. CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT

OPERATION MANUAL. CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT OPERATION MANUAL CLASSIC 10 and CLASSIC 18 SERIAL NUMBER FROM JANUARY 2009 (0109) TO PRESENT READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS SECCIÓN

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

USE, INSTALLATION AND

USE, INSTALLATION AND IDRA - RSC Air cooled water chillers and heat pumps with radial fans Capacities from 5 kw to 17 kw 0509-6180588-rev.0 USE, INSTALLATION AND MAINTENANCE MANUAL Summary GENERALITIES pg. 4 STANDARD VERSIONS

More information

CONTENTS SAFETY PRECAUTIONS. En-1 DANGER! CAUTION!

CONTENTS SAFETY PRECAUTIONS. En-1 DANGER! CAUTION! CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS... 2 PREPARATORY OPERATION... 3 OPERATION... 3 TIMER FUNCTIONS... 5 ON/OFF TIMER... 5 WEEKLY TIMER... 6 TEMPERATURE SET BACK TIMER... 8 FILTER DISPLAY RESET...

More information