GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

Size: px
Start display at page:

Download "GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER"

Transcription

1 INSTALLATION INSTRUCTIONS CH-K30 CH-K80 with G Series Control Package GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER This product is a gas-fired double-effect absorption unit which provides chilled water for cooling or hot water for heating in central plant-type air conditioning systems. These units are available with nominal refrigeration capacities of 30, 40, 50, 60, or 80 tons and are complete with operating and safety controls. These instructions are for use with CH-K Series units that employ the G Series control package. This control package utilizes a VFD solution pump and other enhancements to improve the overall efficiency of the K-Series units from the previous 1.02 COP. With the G Series control package, the new COP is 1.1. While many of the instructions contained within are the same for the CH-K units utilizing the older control package, there are significant differences between CH-K units in regard to these two different control packages. Therefore, verify that the instructions match the unit received. A simple visual difference is the presence or lack of a VFD controller in the control panel. If confusion remains, contact Yazaki Energy Systems, Inc. for further assistance. CONTENTS GENERAL Page Page GENERAL 2 MODEL DESIGNATION 2 STANDARD SPECIFICATIONS 3 FACTORY OPTIONS 5 ACCESSORIES 5 EQUIPMENT DIMENSIONS 6 TYPICAL SYSTEM DESIGN 7 WIRING DIAGRAMS 8 CAPACITY CONTROL 12 INSTALLATION RECEIVING 13 OVERHEAD RIGGING 13 CENTER OF GRAVITY 13 LOCATION 14 FOUNDATION 14 LEVELING 16 CHANGEOVER VALVE & FLOW SWITCH CONNECTION 17 COMBUSTION AIR SUPPLY 18 VENTING 19 PIPING 20 CHILLED/HOT WATER PIPING 21 COOLING WATER PIPING 21 FREEZE PROTECTION 22 GAS SUPPLY PIPING 23 ELECTRICAL 24 WATER QUALITY 26 INSTALLATION CHECK & REQUEST FOR STARTUP 26

2 GENERAL This equipment should only be installed by trained and qualified personnel who are familiar with absorption chillers. All precautions in these instructions, as well as on tags and labels attached to the unit, must be observed to ensure the safety of the personnel and maintain warranty validation. Each Yazaki absorption chillerheater has been evacuated, charged with lithium bromide and water solution, and run-tested prior to leaving the factory. Field wiring, water piping, and gas piping connections are located at the rear of the unit. After the equipment has been installed, a Yazaki Authorized Service Provider (ASP) must check the installation and supervise or conduct the initial startup and operation of the unit. Additionally, a copy of the startup sheet, the Installation Check & Request for Startup sheet, and the Warranty Card must be received by Yazaki Energy Systems, Inc., in order for warranty to be in force. Further, maintenance records should be kept with copies sent to Yazaki Energy Systems, Inc., in order to maintain warranty coverage. CAUTION THE YAZAKI WARRANTY WILL BE VOIDED IF THE FOLLOWING RESTRICTIONS ARE NOT OBSERVED: 1. DO NOT OPEN ANY VACUUM VALVES WITHOUT A PROPER EVACUATION ASSEMBLY ATTACHED TO THEM AS SUCH ACTION WILL RESULT IN LOSS OF VACUUM AND INTRODUCTION OF GASES TO THE INTERIOR OF THE MACHINE WHICH COULD CAUSE CORROSION. 2. ALWAYS HANDLE THE EQUIPMENT WITH CARE AND MAINTAIN IN A NEAR- VERTICAL POSITION DURING RIGGING. IF THE EQUIPMENT MUST BE TILTED, CAREFULLY FOLLOW INSTRUCTIONS PROVIDED WITHIN THIS DOCUMENT. 3. DISCONNECT GAS PIPING FROM EQUIPMENT WHEN PRESSURE TESTING AT 0.5 PSI OR GREATER IN ORDER TO AVOID DAMAGE TO THE GAS VALVES. 4. DO NOT ATTEMPT TO START THE SYSTEM WITHOUT SUPERVISION FROM A YAZAKI AUTHORIZED SERVICE PROVIDER (ASP). MODEL DESIGNATION Double-Effect Absorption Chiller-Heater (K Series) Cooling Capacity: 30 = 30 tons 40 = 40 tons 50 = 50 tons 60 = 60 tons 80 = 80 tons CH-K ### 2

3 STANDARD SPECIFICATIONS English Units Model Using G Controls CH-K High Fire MBTUh Cooling Low Fire MBTUh High Fire MBTUh Heating Low Fire MBTUh Capacity¹ Chilled / Hot Water² Cooling Water² Electrical³ Burner Construction⁴ Piping Capacity Control (High/ Low) 100% / 75% 100% / 63% 100% / 70% Inlet F 54.5 Cooling Outlet F 44.6 Inlet F Heating Outlet F Rated Water Flow GPM Evaporator Pressure Loss² PSI 9.2² 11.4² Maximum Operating Pressure PSI 85.3 (High pressure option available 142 PSI) Water Retention Volume Gal Total Heat Rejection MBTUh Inlet Temperature F 85.1 Outlet Temperature F Rated Water Flow GPM Condenser / Absorber Pressure Loss² PSI 9.9² 12.8² 9.2² Maximum Operating Pressure PSI 85.3 (High pressure option available 142 PSI) Water Retention Volume Gal Power Supply 208V or 230V / 60 Hz / 3-Phase Consumption³ Watts 900³ 1200³ 1250³ 1600³ 1800³ Minimum Circuit Amps Amps MOCP Max. Fuse Size Amps Burner High Fire¹ MBTUh 327¹ 436¹ 545¹ 655¹ 873¹ Input Low Fire¹ MBTUh 245¹ 327¹ 409¹ 413¹ 611¹ Supply Gas Pressure Inches W.C w.c w.c. Type Forced Draft with Category I Venting Gas Dedicated: Natural or Propane. Not convertible. Ignition Type Intermittent or Interrupted Spark Flame Detection Optical or UV Scanner Dimensions Weight Width Inches Depth⁵ Inches 60.6⁵ 70.1⁵ 74.8⁵ Height⁴ Inches 79.1⁴ 94.5⁴ Height with Vent Cap Installed⁴ Dry Lbs Inches 96.1⁴ 111.1⁴ Operating Lbs Cabinet UL50E Type 3R, Silver Metallic Pre-Painted Hot Dip Zinc-Coated Sheet Steel Noise Level db(a) Chilled / Hot Inches 2 NPT 2-1/2 NPT 3 NPT 4 Flanged Cooling Inches 2-1/2 NPT 3 NPT 5 Flanged Gas Inches 1-1/2 NPT 2 NPT 2-1/2 NPT Flue Diameter Inches NOTES: 1. Fuel Input is based on the high heat value of gas. 2. Pressure Loss ratings are +/- 10%. 3. Power Consumption does not include external pumps or cooling tower fan motors. 4. Height does not include level bolts. Height with Vent Cap includes both the cap and level bolts. 5. Depth does not include Junction Box. Junction box adds 3.9 to the Depth dimension. 3

4 STANDARD SPECIFICATIONS Metric Units Model Using G Controls CH-K High Fire kw Cooling Low Fire kw High Fire kw Heating Low Fire kw Capacity¹ Chilled / Hot Water² Cooling Water² Electrical³ Burner Construction⁴ Piping Capacity Control (High/ Low) 100% / 75% 100% / 63% 100% / 70% Inlet C 12.5 Cooling Outlet C 7.0 Inlet C Heating Outlet C 55.0 Rated Water Flow liters/sec Evaporator Pressure Loss² kpa 63.4² 78.6² Maximum Operating Pressure kpa 588 (High Pressure option available 980 kpa) Water Retention Volume liters Total Heat Rejection kw Inlet Temperature C 29.5 Outlet Temperature C Rated Water Flow liters/sec Condenser / Absorber kpa 68.3² 88.3² 63.4² Pressure Loss² Maximum Operating Pressure kpa 588 (High Pressure option available 980 kpa) Water Retention Volume liters Power Supply 208V or 230V / 60 Hz / 3-Phase Consumption³ Watts 900³ 1200³ 1250³ 1600³ 1800³ Minimum Circuit Amps Amps MOCP Max. Fuse Size Amps Burner Input High Fire¹ kw 96¹ 128¹ 160¹ 192¹ 256¹ Low Fire¹ kw 72¹ 96¹ 120¹ 121¹ 179¹ Supply Gas Pressure kpa kpa kpa Type Forced Draft with Category I Venting Gas Dedicated: Natural or Propane. Not convertible. Ignition Type Intermittent or Interrupted Spark Flame Detection Optical or UV Scanner Dimensions Weight Width mm Depth⁵ mm 1540⁵ 1780⁵ 1900⁵ Height⁴ mm 2010⁴ 2400⁴ Height with Vent Cap Installed⁴ mm 2440⁴ 2820⁴ Dry kg Operating kg Cabinet UL50E Type 3R, Silver Metallic Pre-Painted Hot Dip Zinc-Coated Sheet Steel Noise Level db(a) Chilled / Hot Inches 2 NPT 2-1/2 NPT 3 NPT 4 Flanged Cooling Inches 2-1/2 NPT 3 NPT 5 Flanged Gas Inches 1-1/2 NPT 2 NPT 2-1/2 NPT Flue Diameter mm NOTES: Metric units listed here are converted from English dimensions. 1. Fuel Input is based on the high heat value of gas. 2. Pressure Loss ratings are +/- 10%. 3. Power Consumption does not include external pumps or cooling tower fan motors. 4. Height does not include level bolts. Height with Vent Cap includes both the cap and level bolts. 5. Depth does not include Junction Box. Junction box adds 100mm to the Depth dimension. 4

5 FACTORY OPTIONS FS2 Cooling Water Circuit Flow Switch Maximum Operating Pressure in Chilled/Hot Water and Cooling Water PSI Reinforcement for Horizontal Rigging (No Horizontal Transport!) WTI Sensor ACCESSORIES Standard (UL Model Only) ACT5 Maintenance Checker (shipped in control box) Eye Bolts (4) Installation Instructions Leveling Bolts (4) Operating Instructions Spare Fuses (in control box) Vent Cap (in separate box) Changeover Valve Actuator (shipped in box with Vent Cap) Optional Accessories Gas Appliance Regulator Gas Meter LON Adapter Kit Metric Flare Adapters Remote Control Panel Water Pressure Tap English Conversion Kit (KITWPC4) WTI Sensor Gas Appliance Regulator Gas Meter KITWPC4 Remote Control Panel WTI Sensor LON Adapter 5

6 EQUIPMENT DIMENSIONS CH-K30, CH-K40 (Measurements in Inches. Drawings Not to Scale) CH-K50, CH-K60 6

7 CH-K80 TYPICAL SYSTEM DESIGN 7

8 WIRING DIAGRAMS 8

9 9

10 SYMBOL DESCRIPTION A thru I BMS and/or Remote Control Panel Connection Terminals REMARKS Field-Installed Optional Remote Control Panel Accessory AL# Alarm Contact Terminal ANOUT Analog Signal Output AX Auxiliary Gas Valve 120V Coil BM Burner Blower Motor 208/230V BN# Burner Wiring Circuit Located on Terminal Terminal Strip BNPW Burner Demand Relay On Circuit Board BON Burner Operation Demand Dry Contact 24V, 60va Max CAPS Combustion Air Proving Switch CHD Enable Signal Dry Contact 24V, 60va Max CHE Alarm Condition Dry Contact 24V, 60va Max CH No. For AroTrend Channel Number / Monitoring / Unit Address LON Adapter Use CHSTN Chiller Disabled Dry Contact 24V, 60va Max CIR Cool Mode Interrupt CM Cool Mode Dry Contact 24V, 60va Max CM1 Common for Pump & Field-Supplied Fan Dry Contact Relays Voltage CM2 Common for Safety 15V DC Unit- Interlocks Provided Signal CN# Molex Connector CND Condenser Thermister COM# Common for External 15V DC Unit- Signal Relays Provided Signal Changeover Valve Actuator CON Cool Position Confirmation CP Cooling Water Pump Dry Contact 24V, 60va Max CTF Cooling Tower Fan Dry Contact 24V, 60va Max CTI Entering Cooling Water Thermister CTO Leaving Cooling Water Thermister CVR Changeover Valve 24V DCL DC Reactor For VFD DCP# Digital Communication For AroTrend Protocol Interface Monitoring EDF Exhaust Damper/Fan Confirmation Signal EDM Enable LED EMG# Alarm Signal ESC1 External Signal for Cool Mode ESH1 External Signal for Heat Mode ESOFF External Signal to Disable ESON External Signal to Enable F Cooling Tower Fan FAN Control Box Cooling Fan SYMBOL DESCRIPTION REMARKS FD, FE Cooling Tower Fan Safety Interlock FS1 Chilled/Hot Water Flow Switch FS2 Cooling Water Flow Field-Installed Switch Option Fuji Model FGAO- FU11 200V Circuit Fuse 2; 250v, 2 Amp Fuji Model FGAO- FU12 200V Circuit Fuse 2; 250v, 2 Amp Fuji Model FGAO- FU2 24V Control Circuit Fuse 2; 250v, 2 Amp Fuji Model FGAO- FU31 32V Control Circuit Fuse 1; 250v, 1 Amp Fuji Model FGAO- FU32 32V Control Circuit Fuse 1; 250v, 1 Amp G Electrical Ground GBN Electrical Ground for Burner GLS Generator Level Switch GND Electrical Ground GP Generator Thermister GPJ Generator Over-Temp Detection Thermister GPSC Generator Thermal Limit Switch for Cooling Mode GPSH Generator Thermal Limit Switch for Heating Mode GV Main Gas Valve 120V Coil Controls High / Low HF# Burner Firing Rate Circuit Firing Rate Selection HIR Heat Mode Interrupt HM Heat Mode Dry Contact 24V, 60va Max Changeover Valve Actuator HON Heat Position Confirmation High/Low Fire Demand HU IN Control Relay On Circuit Board IF1 Chilled/Hot Water Freeze Protection Circuit IF2 Cooling Water Freeze Protection Circuit IGN Ignition Transformer 120V AC Pri. 6000V AC Sec. INV Inverter (VFD) Controller Hitachi WJ-200 INV SIG # Inverter Signal Line IRS Independent Remote Switch Not Used JP# Fuse on Circuit Board F1:6A ; F2:3A LCOM Common for LEDs LS Expansion Tank / Cistern Level Switch Not Used LT Evaporator Thermister LTPV Refrigerant Proportional Control Valve 32V; 0-400mA MB Burner Motor Contactor 120V Coil MBPW Blower Power Relay 24V Coil Maintenance Required MENTE Dry Contacts 24V, 60va Max MF Flame Failure Dry Contact Not Used 10

11 SYMBOL DESCRIPTION REMARKS MHU High Fire Demand Control Relay On Circuit Board MOP Burner Demand Relay On Circuit Board MRC GPSC Enable Relay On Circuit Board Field-Installed MS Seismic Sensor Terminals Option Solution Pump Enable MSP Control Relay On Circuit Board NFB Non-Fused Breaker OPa Unit Enabled Status Dry Contact 24V, 60va Max P Chilled/Hot Water Pump Dry Contact 24V, 60va Max P1 Chilled/Hot Water Pump P1D, P1E Chilled/Hot Water Pump Safety Interlock P2 Cooling Water Pump P2D, P2E Cooling Water Pump Safety Interlock PCH Palladium Cell Heater 200V; 30 Watts PD Dilution Mode Status Dry Contact 24V, 60va Max PV Pilot Valve 120V Coil R1 Burner Alarm Relay 120V Coil R2 Mod Motor Control Relay 120V Coil RC Cooling Control Relay RFAN Control Box Cooling Fan Control Relay RH Heating Control Relay RRBH Burner High/Low Control Relay 24V Coil RRBL Burner Start/Stop Control Relay 24V Coil Solution Pump RSP VFD Enable/Disable Relay On/Off Signal RSV9 SV91 & SV92 Control Relay 24V Coil SYMBOL DESCRIPTION REMARKS Control Board Relay to RYPW Engage MBPW Junction Box Unit Status S#, S## Terminals, Dry Contacts 24V, 60va Max S1, S2 Selector Switch SA# MOV Surge Protector SP Solution Pump Configurable for ST2 External Safety Interface NO or NC switches SV1 Evaporator Freeze Protection Valve 24V Coil SV91 Concentrated Solution Bypass Valve 200V Coil SV92 Concentrated Solution 200V Coil; Bypass Valve #2 CH-K80 Only TB# Terminal Block THR# Over-Current Relay / Safety Signal THW Set Point Set Back Signal Not Used TR# Transformer Circuit Wiring Terminal 24V AC Primary; TR04M- Power Transformer 18V, 15V, 14V, & UL 13V AC Secondary TR1- ULCE TR2- UL115V WFC- TRUL1 WTI WTO Power Transformer Power Transformer Power Transformer Entering Chilled/Hot Water Thermister Leaving Chilled/Hot Water Thermister 208V or 230V AC Primary; 200V, 24V, & 32V AC Secondary 208V or 230V AC Primary; 120V AC Secondary 208V or 230VAC Primary; 24VAC Secondary Field Wiring Diagram in Junction Box 11

12 Typical Field Wiring CAPACITY CONTROL COOLING HEATING Lo% Lo% NOTE: Lo% = 75% for (K30, K40, K50), 63% for K60, or 70% for K80. 12

13 RECEIVING INSTALLATION When the absorption chiller-heater is delivered, inspect it for transit damage. Should any damage have occurred, do not proceed with installation until the Yazaki distributor has been notified and any required remedial actions have been completed. Remember to properly plan the route to the installation site. Also, keep in mind when choosing the site, the unit will someday have to be replaced, so be mindful of permanent and semipermanent barriers. Dimension Drawing Not To Scale CH-K30, CH-K40 CH-K50, CH-K60 CH-K80 A 98 (2490) 113 (2870) B 78 (1980) 90 (2285) 95 (2415) C 80 (2030) 90 (2285) 95 (2415) Dimensions in Inches (mm) OVERHEAD RIGGING The Yazaki chiller-heater is designed for overhead rigging with four eye bolts installed in the top panel at the factory. Care should be taken at all times during rigging and handling to avoid damage to the panels and external connections. DO NOT DROP! Remove the crate from the unit. Install the level bolts screwing them in only until the threads reach all the way through the frame bolt. The leveling bolts can remain in place unless the additional height causes trouble getting it to the installation area. CENTER OF GRAVITY The Center of Gravity of all K- Series chiller-heaters is almost dead center of the machine, 40 (1m) up from the base. The Corner Weight of each unit is the same on all four corners. The chart shows corner weights for each size. Unit Corner Weight - lbs (kg) CH-K (650) CH-K (705) CH-K (870) CH-K (920) CH-K (1320) 13

14 LOCATION Particular care must be taken when placing the machine so as to provide adequate clearance for access to each side of the machine. Maintenance is mostly done through the front of the unit, but in repair scenario, any panel on any side may need to be removed to access components behind them. Finally, as with all mechanical devices, the unit will have to be replaced someday. Keep that in mind as well when choosing the final placement site. The minimum clearance space is shown on the chart and diagram below. Drawing Not To Scale Model Installation Area Maintenance Clearances A B C D E F CH-K30, (3580) 114 (2895) CH-K50, (3810) 126 (3200) 40 (1000) 40 (1000) 28 (700) 28 (700) CH-K (3935) 129 (3275) FOUNDATION All Dimensions in Inches (mm) All aspects of foundation and support computations must be in accordance with national and local codes. The chiller-heater must be mounted on a level, non-combustible foundation capable of supporting the weight of the machinery. This is particularly important for rooftop installations. Always make certain the structure can support not only the chiller-heater, but the pumps, piping, cooling towers, etc. as may be required. The rooftop area should be in a well-drained area and be at least 7 (2 m) from the edge of the roof. Antifall measures should always be taken if the chiller-heater is installed within 12 (4 m) of the edge of the roof. 14

15 Additionally, for protection of the roofing material, it is recommended a suitable platform or walkway be provided around all sides of the unit. If the chiller-heater is to be installed outside, but at ground level, make certain the concrete base and the soil beneath are sufficient for the task. Settling over time could cause the unit to become unlevel which could have a serious negative impact on the performance and lifespan of the unit. Concrete foundations are recommended to be sized so that at least 12 (300 mm) extends beyond the unit in all directions to accommodate potential mounting hardware. Yazaki chiller-heaters are designed to use L-anchor plates to secure them to their respective foundations. These anchor plates are included in the accessories box with each K-Series chiller-heater. There are holes in the base rail of the unit for use in bolting the L- anchor plate to the unit. Anchoring the L-anchor plate to the foundation should be done in accordance with the needs of the site and dictates of code. The details of the L-anchor plate follow. L-Anchor Plate Despite the chiller-heater s considerable mass, it is sometimes required that the unit be tied down or anchored in place, usually as part of an applicable seismic code. Follow code requirements in all such cases. CH-K Base Dimensions 15

16 LEVELING CH-K series units must be level in order for the fluids to be distributed properly over their respective tube bundles. There is a level bar mounted on the front of the machine. The unit must be level to both the longitudinal and transverse alignments. In cases of multiple units installed side-by-side, the units should all be level individually as well as in respect to each other. It is essential that all leveling be completed before any piping connections are attempted. 16

17 CHANGEOVER VALVE AND FLOW SWITCH CONNECTION Once the unit is in place and level, there are two additional items that need attending to. First is the installation of the Changeover Valve Actuator Motor. This valve actuator motor is shipped loose. It is wrapped in packing and shipped inside the vent cap. Be careful not to dispose of actuator motor inadvertently as it is absolutely required for the function of the chiller-heater. Replacement of lost actuator motors is not considered a warranty event. The Changeover Valve itself is located at the rear of the unit, just above the Junction Box. Examining the actuator motor assembly and the valve itself, it can be observed that the drive tang has a shallow and a deep end as does the tang receptor on the valve itself. These must be aligned properly before the mounting screws can be properly tightened. Dangling nearby will be a Molex plug which should be connected to the Molex plug on the Changeover Valve Actuator Motor. Next, locate the Chilled/Hot Water Flow Switch (FS1). It is located at the rear of the unit on the right side. The water tubes for it to sense pressure differential are not attached to the flow switch itself when shipped. Rather, the tubes are tied to other nearby tubes so that they do not break during shipping. It is necessary to remove the ties, attach the flare nuts to the flow switch, and tighten properly. 17

18 COMBUSTION AIR SUPPLY As with all gas-fired appliances, careful consideration must be given in regard to the provision of sufficient free air for combustion and venting. The rules for such are found in the National Fuel Gas Code, NFPA Standard 54. The code supersedes anything found in print here or in any other Yazaki documentation. Provided here are guidelines to help toward proper installation of the equipment. When installed outdoors, no special provisions are usually needed in regard to combustion air. However, if the unit is in a confined area outside, some issues could arise if external forces cause a negative pressure area around the unit. An example of such would be having the unit installed in an alcove, yet a strong, sustained wind blows by along the edge of the building. Such occurrences are rare, but should be considered. Of greater concern are indoor installations, especially in areas with more than one gas-fired appliance. Keep in mind that whatever combustion air supply is present, it must be capable of supporting every gas-fired appliance in the space while all of them operate at full capacity. Combustion air openings are also often the source for dilution air for Category I appliances, so it is recommended to consult the manuals on all appliances in the area in order to ensure all requirements are being considered. Never install a gas-fired appliance in an unventilated space. Air Openings for CH-K Series (Units With G Control Package Only) Direct to Outdoor Upper Opening Lower Opening CH-K30 82 (530) x FAM 82 (530) x FAM CH-K (704) x FAM 109 (704) x FAM CH-K (884) x FAM 137 (884) x FAM CH-K (1058) x FAM 164 (1058) x FAM CH-K (1413) x FAM 219 (1413) x FAM Ducted to Upper Opening Lower Opening Outdoor CH-K (1060) x FAM 164 (1060) x FAM CH-K (1408) x FAM 218 (1408) x FAM CH-K (1768) x FAM 274 (1768) x FAM CH-K (2116) x FAM 328 (2116) x FAM CH-K (2826) x FAM 438 (2826) x FAM One Opening Direct to Outdoor Upper Opening Lower Opening CH-K (704) x FAM Not Used CH-K (942) x FAM Not Used CH-K (1175) x FAM Not Used CH-K (1413) x FAM Not Used CH-K (1878) x FAM Not Used Free Area Modifier (FAM) Value of Louver. If unknown, use 2.0. (Consult Louver Manufacturer for FAM value.) Dimensions are Inches² (cm²) 18

19 VENTING Venting the flue products safely is a key concern when installing any gas-fired appliance including Yazaki chiller-heaters. Rules for the proper venting of gas-fired appliances are covered in the National Fuel Gas Code, NFPA Section 54. For chimney design purposes, the exhaust gas flow rates listed below reflect input fuel rate operating at high fire with proper combustion air supply, with CO at 8.5%, O2 at 5.5%, and no more than 40% excess air (32% is ideal). Venting gases will be approximately 392 F (200 C) at a density of lbs/ft³. Exhaust Gas Volume CFM (m³/hr) Unit Model CH-K30 (w/ G Control Package) 100 (170) CH-K40 (w/ G Control Package) 134 (228) CH-K50 (w/ G Control Package) 167 (284) CH-K60 (w/ G Control Package) 201 (342) CH-K80 (w/ G Control Package) 267 (454) Exhaust Gas Volume All CH-K series chiller-heaters are Category I appliances. When choosing vent material size, the chillers-heaters are classified as fan vent type since the fan on the burner assists in moving flue products through the unit. The fan does NOT provide enough force to do more than push the flue products a few feet down the vent, so it does not have enough force to qualify as Category III, side discharge venting. There are aftermarket kits that can provide Category III capability for Category I appliances should the need arise. Warranty may be void on the Yazaki chiller-heater if such a kit is used, but not installed or applied correctly. Carefully follow all instructions when applying these kits, and if necessary, contact Yazaki Energy Systems, Inc. for guidance on the integration of the kit into the unit control safeties. A number of quick rules can be listed in regard to venting: 1. Always use B-Type double wall vent material. 2. Vent should never run downhill. 3. Vent must terminate at least 7 above public walkways. 4. Vent must terminate at least 4 above vertically or 10 horizontally from openings into living areas or air intakes. 5. Vent must terminate no closer than 10 from an inside corner unless it terminates 2 above said inside corner. 6. Vent should terminate at least 2 above the highest point within Rise (Height) should be greater than the Run (Lateral). 8. It is recommended that each unit be vented separately if possible. If the vent is taller than 7, a barometric damper (also known as a draft regulator) may be required. The range of draft pressure allowed at the vent connection on the chiller-heater is 0.0 wc to wc. If the draft pressure is outside of this range, a barometric damper should be used to correct this in order to prevent sooting and possible damage to the HGE. In instances where multiple units are to be vented and individual venting is impractical or undesirable, combined venting (Common Venting) is permitted so long as it follows proper venting rules. It should be noted that there will be separate and special charts for sizing common venting applications. Follow the rules given by the vent material manufacturer. 19

20 Things that do not change by manufacturer: 1. Barometric dampers (draft regulators) are no longer an option. They are required so that vent conditions of one unit do not affect the operation/venting of the other(s). Use a separate damper for each chiller-heater with the damper located as close as possible to the unit (location A). If there is insufficient room for installation at location A, use location B as an alternative. 2. Size connecting Tees properly. 3. The maximum allowable lateral length (L) is equal to 1.5 x diameter of the pipe. 4. When the common pipe grows to become 7x greater in area than the interconnecting pipe, special rules will apply. Consult the pipe manufacturer for these details and/or special rules. PIPING After the chiller-heater has been leveled properly, the piping for the chilled/hot water and cooling water circuits may be installed. Piping arrangements should be made with care so that there is no interference with service access or panel removal. Piping should be adequately supported and braced independently of the unit so as to avoid undue strain on the unit piping connections. Maximum allowable pressure in any fluid circuit is 85.3 PSI (588 kpa) unless a high pressure option was purchased. CAUTION 1. Do not exceed 85.3 PSI (588 kpa) in either the chilled/hot water or the cooling water circuits of the Yazaki chiller-heater. 2. Do not install any valves in expansion pipe line. Thermo-wells, pressure gauges, Pete s Plugs, etc. may be installed at the inlet and/or outlet of each fluid circuit connection to facilitate startup, future service, and routine maintenance. Strainers in each circuit, particularly the cooling water circuit, are recommended as well. These should be placed before the inlet connection of the chiller-heater. Piping rules and conventions used with Yazaki chiller-heaters are exactly the same as used with any other type of chiller, therefore, this installation manual will not delve deeply into piping design. 20

21 CHILLED/HOT WATER PIPING A balance valve should be installed at the chilled/hot water outlet and a stop valve should be installed at the chilled/hot water inlet. Both valves should be placed in close proximity to the chiller-heater. After thoroughly testing for leaks, insulate the piping circuit, ensuring an adequate vapor barrier is obtained. Be sure to allow access to any valves, wells, and ports that may be present. Also, ensure the chiller-heater panels are not restricted by the insulation. COOLING WATER PIPING Cooling water should be supplied at 85 F (29.5 C) or less. The CH-K Series can typically accept cooling water down to 77 F (25 C) without use of a mixing valve. However, the inlet cooling water temperature must not be below 46.4 F (8 C) when the cooling cycle starts, nor may it drop to 46.4 F (8 C) and remain there for more than 3 minutes at any point in time. Such cases will result in the generation of error code E043. To prevent this, a mixing valve or a diverting valve should be installed so that when cooling water is too cold, the cooling water returning from the chiller-heater is diverted directly into the sump of the cooling tower in order to preserve and build up heat. Once the cooling water temperature rises to an acceptable temperature, the valve can allow the returning cooling water to flow through the tower medium once more. Temperatures above 85 F (29.5 C) can result in a loss of capacity. If cooling water exceeds 90 F (32 C), the refrigerant vapor may no longer condense properly which could lead to a loss of capacity as well. If the cooling water becomes consistently too hot, the unit may lock out, usually displaying error code E

22 If possible, the cooling tower should be installed at or above the level of the chiller-heater. If this is not possible, give careful consideration to the prevention of drain-back and loss of cooling water due to sump overflow. The design engineer must also take proper and appropriate steps to prevent damage to the cooling tower fill media as a result of mode change-over. When switching from heat to cool mode, for a short time the cooling water can return from the chiller-heater at temperatures in excess of 130 F (54 C). This hot slug of water must not be allowed to damage the fill media. Use of a mixing or diverting valve can help prevent this. If the cooling water remains in the lines during heat mode, ensure that any method of isolating the cooling water for heat mode operation does not cause a closed loop within the unit itself. Otherwise, heating of the closed fluid loop can cause water expansion pressure in the loop to quickly build well beyond the pressure limitations of the fluid circuit and can cause catastrophic failure of the fluid loop. Such an event results in immediate end-of-life condition for the unit. Such failure will not be considered a warranty event. As with the chilled/hot water connections, balance valve should be installed on the cooling water inlet and a stop valve installed on the cooling water outlet. Both valves should be in close proximity to the chiller-heater. After thoroughly testing for leaks, insulate the piping circuit, ensuring an adequate vapor barrier is obtained. Be sure to allow access to any valves, wells, and ports that may be present. Also, ensure the chiller-heater panels are not restricted by the insulation. Additionally, there should be flush and drain valves installed between the machine and the balance/stop valves so as to allow for chemical cleaning of the absorber-condenser coils should it ever become necessary. FREEZE PROTECTION When the chiller-heater and/or associated piping are installed in a location that is subject to freezing conditions, appropriate anti-freeze steps must be taken. Many anti-freeze methods are available including heat tape, but the most common method in the USA is the use of glycol in the fluid loop. Glycol may be permitted for use in Yazaki chiller-heaters with certain restrictions and observations. 1. In the chilled/hot water circuit, it should only be used during heating operation. It is not recommended for use in the chilled water circuit in cooling mode as the loss of heat transfer performance could result in tube failure under certain extreme conditions. 2. Glycol may be used in the cooling water circuit in any operating mode. 3. Do not use automotive glycol (Antifreeze) since it contains chemical additives that are inappropriate and potentially damaging to the Yazaki chiller-heater. Use only glycol appropriate for use with copper tubing. 4. Do not exceed a mixture of 50% by weight. 5. Be aware that loss of performance will result when glycol is used. In higher concentrations, the impact can be very significant. 6. Propylene Glycol is preferred wherever possible. It has very similar anti-freeze characteristics to Ethylene Glycol, but is nontoxic. It is also less viscous than Ethylene Glycol, which reduces the required pump power. Finally, it provides a heat transfer performance closer to that of water than EG. 7. Use of glycol can cause the unit to operate at a slightly higher internal temperature since heat transfer is dampened. This may result in depletion of inhibitor at a faster rate than what may be perceived as normal. 22

23 GAS SUPPLY PIPING Before connecting the gas supply pipe, check the UNIT NAMEPLATE to confirm that it is compatible with the gas type available. The gas piping must be selected and installed in accordance with local building codes and the National Fuel Gas Code (ANSI Z233.1, latest edition). Typically, the pipe size is selected at the maximum gas pressure input and with 0.5 inches water column maximum pressure loss between the gas meter and the equipment. CAUTION TO AVOID DAMAGE TO THE GAS VALVES IN THE CHILLER-HEATER, DISCONNECT THE GAS PIPE WHEN THE TEST PRESSURE EXCEEDS 0.5 PSI (3.4 kpa). Allowable supply gas pressure range: in. wc. ( in. wc. For K80) The maximum and rated gas pressures are measured when the burner is operating at 100% fire rate. Install a manual shut-off valve and a sediment trap within 6 feet of the equipment. A gas meter is recommended in order to facilitate burner setup when the primary gas meter is remote from the installation site, or when multiple gas-fired appliances exist on the supply lines. This optional gas meter Gas Piping Pressure Drop Data Mbtu/hr Capacity Equivalent Pipe Size Length of Straight 1-1/2" 2" 2-1/2" 3" Pipe in Feet allows for gas volume determination without the need to isolate other appliances during burner setup. Installation of an appliance regulator is also recommended, especially when multiple gas-fired appliances exist on the supply lines. This optional appliance regulator should be sized to handle the 100% fire rate gas supply and should be located as the last item in the gas supply line before it enters the chiller-heater. The minimum gas supply pressure is 5 inches water column at the burner gas valve (7 inches water column for K80 units). The maximum gas supply pressure is 10.5 inches water column at the burner gas valve. Combustion with supply gas pressure outside of this range could cause an incorrect flame shape in the High Temperature Generator (HGE) and could potentially cause damage to the HGE itself. The gas pipe connection on the chiller-heater does NOT mean that size is appropriate for bringing the gas supply to the unit. The gas supply piping must be capable of carrying the total MBtuh/hr capacity of all gas-fired appliances on the line when each is fired simultaneously at full firing rates. Reduce the required pipe size as close to the chiller-heater as is reasonably possible. Equivalent Lengths of Pipe Fittings in Feet 1-1/2" 2" 2-1/2" 3" Standard Ell Ell Tee Specific Gravity Correction Factors Natural Gas Multiplier Propane-Air Mix Propane Butane

24 ELECTRICAL Model CH-K Power Supply 208V or 230V / 60 Hz / 3-Phase Consumption³ Watts 900³ 1200³ 1250³ 1600³ 1800³ Minimum Circuit Amps Amps MOCP Max. Fuse Size Amps Power Consumption does not include external pumps or cooling tower fan motors. Electrical³ Each chiller-heater has a junction box located at the rear of the unit. This junction box is a single point where all electrical interface, be it high voltage or controls, is intended to enter the unit. High voltage connections should be made to L1, L2, L3, and G. If the voltage supply has a wild leg or high leg, that leg should attach to L2. Be aware that not all regions have high legs. A rotation test must be performed as well. Clockwise rotation is desired. If incorrect rotation is discovered, swap L1 and L3 wires to reverse the rotation. A rotation meter is the simplest method to determine rotation. The center section of the junction box has the pump controls. Supply voltage is provided from a field-supplied 24v transformer to terminal CM1. The unit will take that voltage and route it to terminal P when there is a chilled/hot water pump demand. It will take that same voltage and route it to terminal CP when there is a demand for the cooling water pump. It will use that same voltage to cycle the cooling tower fan, applying that voltage to CTF when the incoming cooling water is at 84.2 F (29 C) or greater, and taking it away when the incoming cooling water drops to 80.6 F (27 C). This logic function of cooling water temperature control is provided for convenience and is not intended to supersede more sophisticated controls such as VFD fan controls, etc. Terminals A through I in the lower right section of the junction box are intended for use with the optional Yazaki Remote Control Panel. However, these terminals can also be used to interface with Building Management Systems. 24

25 starter for the chilled/hot water pump, cooling water pump, and cooling tower fan motor should have a set of auxiliary contacts on their overloads. When interfacing with a BMS, it is recommended that two SPST relays be used and controlled by the BMS. Each relay should have the E terminal (the unit supplies a DC voltage signal) of the junction box connected to its common lead on the relay contacts. One of these relays will be used to determine whether the unit is in Heat or Cool mode. The other will Enable or Disable the unit. For the mode relay, designated ESC, the normally closed contact should be attached to the B terminal in the junction box. The normally open contact should be attached to the A terminal in the junction box. For the Enable/Disable relay, designated ESON, the normally closed contact should be attached to the D terminal in the junction box. The normally open contact should be attached to the C terminal in the junction box. In the upper right section of the junction box lies a terminal strip with terminals 1, 2, 3, 4, 5, and CM2 on the left end. Terminals 1 and 2 are for digital communication to the accessory LON Adapter. Terminal CM2 supplies a DC voltage signal that MUST return to terminals 3, 4, and 5. These are pump and motor overload interlocks. Each Each starter overload s auxiliary contacts should receive the DC voltage from terminal CM2 in the junction box and route it through normally closed contacts to return to the appropriate terminal. Terminal 3 should receive the return signal from the chilled/hot water pump overload auxiliary contacts. Terminal 4 should receive the return signal from the cooling water pump overload auxiliary contacts. Terminal 5 should receive the return signal from the cooling tower fan overload auxiliary contacts. If the return signal is not sensed, the unit will immediately generate an error code (E005, E006, and/or E007). Finally, in the upper right section of the junction box lies a terminal strip with terminals S5, S6, S7, S8, S11, S12, S13, and S14 on the right end. These terminals are used in pairs and provide sets of dry contacts for feedback of particular conditions. The use for each set of contacts is: S5 S6: Closes when unit is in Cool Mode S7 S8: Closes when unit is in Heat Mode S11 S12: Closes when the unit is Enabled S13 S14: Closes when unit is in Alarm 25

26 WATER QUALITY Water used in the chilled/hot water and cooling circuits may cause scaling and/or corrosion if not correctly analyzed and maintained within specified limits. In some areas, the water supply may contain minerals that cause scaling or may be extremely soft and corrosive. Where these conditions exist, a water treatment company should be consulted. If the absorption chiller-heater is damaged as a result of scaling, corrosion, or erosion caused by poor water quality control, the equipment warranty may be void. Water quality should not exceed the following limits: ITEM CHILLED/ HOT WATER COOLING WATER MAKE-UP WATER ph (at 77 F) Conductivity (µs/cm at 77 F) Standard Chloride ion (Cl - ppm) Sulfate ion (SO 2-4 ppm) M-alkalinity (CaCO 3 ppm) Total hardness (CaCO 3 ppm) * 70 Calcium hardness (CaCO 3 ppm) Ionic silica (SiO 2 ppm) Total iron (Fe ppm) Copper (Cu ppm) Reference Sulfide ion (S 2- ppm) ND ND ND Ammonium ion (NH 4 + ppm) Residual chlorine (Cl ppm) Free carbon dioxide (CO 2 ppm) Ryzner stability index NOTES: 1. ND (Not Detectable) 2. *Maximum total hardness of make-up water shall not exceed 70 ppm when bleed off is the only method used to control water quality INSTALLATION CHECK & REQUEST FOR STARTUP After the absorption chiller-heater has been installed, piped, and wired as described in these instructions, but before any attempt is made to start the unit, the Yazaki Authorized Service Provider should be advised so that the startup can be scheduled. Complete the REQUEST FOR STARTUP form and send it to the ASP or to Yazaki Energy Systems, Inc., at least 2 weeks prior to the required startup date. The contractor is expected to provide personnel to assist with final adjustments to the system controls and fluid flow rates as may be necessary. 26

27 YAZAKI CH-KG SERIES CHILLER-HEATER INSTALLATION CHECK AND REQUEST FOR START-UP Yazaki Service Provider: Address: Project Name: Project Address: Model No: Anticipated Startup Date: A. CHILLER-HEATER 1. Unit placed and leveled on foundation 2. Service clearance provided on all sides and top (40 in. front) 3. Chiller-heater anchored by L-Anchor plates to foundation (if required) 4. Changeover Valve Actuator Motor located and installed. 5. Flow Switch FS1 flare nuts released from shipping ties and tightened. B. WATER PIPING 1. Chilled/hot water piping installed between chiller-heater, pumps and air handling unit(s) 2. Cooling water piping installed between chiller-heater, pumps, and cooling tower 3. Flow switch piping attached 4. Water piping leak tested and flushed 5. System filled with water and glycol (if required) and trapped air vented 6. Flow setters installed in water piping 7. Test plugs (Pete s plugs) and/or thermowells installed in the inlet and outlet piping of each chiller-heater 8. Valves installed at each chiller-heater for flow balancing and isolation 9. Air vent valves installed on piping 10. Strainers present and clean 11. Expansion tank (properly charged) and water make-up piping installed to chilled/hot water system 12. Water make-up and fill lines installed to the cooling tower 13. Pressure relief valves, set at 85 psi (max.) installed on piping adjacent to each chiller-heater (if required) C. GAS PIPING 1. Natural Gas supply is available between 5 wc (7 wc for K80) and 10.5 wc 2. Gas piping installation completed 3. Gas cock and sediment trap installed 4. Gas meter and appliance regulator installed at each chiller-heater Serial No: 5. Gas pipe leak tested and purged D. VENTING 1. Factory-provided vent cap installed (outdoor installation) 2. Barometric damper and Type-B vent extension installed on each chillerheater outlet (indoor installation) E. POWER WIRING 1. Power supply, indicated on the UNIT NAMEPLATE, is connected 2. Wiring completed between the chillerheater, motor contactors and the following motors: Chilled/hot water pump, cooling water pump, and cooling tower fan 3. Rotation of each motor checked 4. Power supply wiring connected between a fused disconnect and each chiller-heater. (DO NOT operate the chiller-heater) vac power supply available near the chiller-heater for a vacuum pump F. CONTROL WIRING 1. Motor contactors and manual controls installed for all external motors 2. Control wiring installed between chiller-heater and pump/motor contactors 3. Interlock wiring installed between chiller-heater and thermal overloads on the following motors: Chilled/hot water pump, cooling water pump and cooling tower fan 4. Wiring installed between chiller-heater and auxiliary contact on the cooling tower fan motor contactor G. CONDITIONS 1. Personnel available to assist with start-up who are familiar with the system 2. Adequate vacuum pump available 27

28 YAZAKI AUTHORIZED SERVICE PROVIDER For information concerning service, operation or technical assistance, please contact your Yazaki Authorized Service Provider or the following: YAZAKI ENERGY SYSTEMS, INC. 701 E PLANO PKWY, SUITE 305 PLANO, TEXAS Phone: Fax: yazaki@yazakienergy.com Web: This symbol on the product s nameplate means it is listed by UNDERWRITERS LABORATORIES, INC. Yazaki reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations KGUL-II-1F1-0316

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

Gas-Fired Double-Effect Chiller-Heater

Gas-Fired Double-Effect Chiller-Heater Gas-Fired Double-Effect Chiller-Heater CH-K Series: 30, 40, 50, 60, 80, 100 RT Cooling with Standard Heating Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas-Fired Double-Effect Chiller-Heater

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 30 80 RT K-SERIES GAS-FIRED, DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K Gas-Fired, Double- Effect

More information

WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER

WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER OPERATING INSTRUCTIONS WFC-SC10, 20, 30 WFC-SH10, 20, 30 WATER FIRED SINGLE-EFFECT ABSORPTION CHILLER AND CHILLER-HEATER This product is a water fired absorption unit which provides chilled water for cooling

More information

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired Chiller/Chiller-Heater WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired SINGLE-EFFECT Chiller or Chiller-Heater Yazaki Water-Fired SINGLE-EFFECT chillers have cooling capacities of

More information

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 100 RT CH-K SERIES GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER 1. General Description The Contractor shall furnish and install (QTY) Yazaki model CH-K100 Gas-Fired, Double-Effect

More information

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER OPERATING INSTRUCTIONS CH-MG150 CH-MG200 GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER FOR YOUR SAFETY If you smell gas: 1. Open windows (only if installed indoors) 2. Don t touch electrical switches

More information

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER

GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER OPERATING INSTRUCTIONS CH-K30, 40, 50, 60, 80, 100 GAS-FIRED DOUBLE-EFFECT ABSORPTION CHILLER-HEATER This product is a gas-fired absorption unit which provides chilled water for cooling or hot water for

More information

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 Specifications CH-MG150CE CH-MG200CE Version 9.10 Contents Page 1. General Information 1.1 Chiller-heater... 2 1.1.1 Chiller-heater Specification. 2

More information

WFC-M Series Installation. WFC- M Series. Hot Water Fired single Effect Absorption Chiller. Installation WFC-M100 Version 1.0 (Original/Document)

WFC-M Series Installation. WFC- M Series. Hot Water Fired single Effect Absorption Chiller. Installation WFC-M100 Version 1.0 (Original/Document) WFC- M Series Hot Water Fired single Effect Absorption Chiller 2 Installation WFC-M100 Version 1.0 (Original/Document) - 0 - Contents 1. General Information 1.1 Precautions... 2 1.2 Receiving... 2 1.3

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER SYSTEM. Model: PVO-300, PVO-600 POWER VENTER SYSTEM Model: PVO-300, PVO-600 Included is one ETL and cetl listed Power Venter to be used primarily with a single 120VAC controlled oil fired furnace, boiler, or water heater. The PVO may

More information

M2 Series Startup Form

M2 Series Startup Form M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat SINGLE PACKAGE ROOFTOP, GAS HEATING/ELECTRIC COOLING UNIT WITH PURON R (R-410A) REFRIGERANT ONE STAGE COOLING CAPACITY CONTROL: SIZES 08-12 TWO STAGE COOLING CAPACITY CONTROL: SIZES 08, 12 & 14 Submittal

More information

WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP

WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP Receiving Do a quick visual inspection on the truck for any major damage prior to signing the paperwork. Damage should be noted

More information

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com MODEL HS115-3, HS115-4 & HS115-5 WIRING

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

WD7664 / WD7663 Maxon Burner. Ellis Whisper Dryer Installation & Start UP

WD7664 / WD7663 Maxon Burner. Ellis Whisper Dryer Installation & Start UP Title WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Procedure No. Installation & Start UP Procedure Author Chris Giordano Effective 1/23/17 Revision A Submitted By Chris Giordano Supersedes Date Revision

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED

More information

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M3RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 90+ AFUE Input 60,000 & 80,000 Btuh The high efficiency downflow gas furnace is especially

More information

Project Name: Location: Engineer: Contractor: I. GENERAL

Project Name: Location: Engineer: Contractor: I. GENERAL Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL I. PRODUCT Rep: Date: A. Supply and install modulating and condensing boiler(s) as specified

More information

Installation Instructions Dual Fuel Ranges

Installation Instructions Dual Fuel Ranges Installation Instructions Dual Fuel Ranges E30DF74EPS E36DF76EPS E48DF76EPS 5995447082 2 Safety IMPORTANT SAFETY INSTRUCTIONS Safety Precautions Do not attempt to install or operate your unit until you

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating The High Efficiency AYF60-119 units are 2 module appliances; each AYF is

More information

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507258-04 7/2018 Supersedes 10/2017 ZG 036, 048, 060, 072, 074 (3, 4, 5 and 6 Tons) ZG 092, 102, 120, 150 (7-1/2, 8-1/2, 10 and 12 Tons) ROOFTOP UNITS ZG

More information

Columbia Boiler Company

Columbia Boiler Company EMG Series Boilers Available in Natural Gas & Propane Rev 12012 Columbia Boiler Company PO Box 1070 Pottstown, PA 19464 Tel (610) 473-8457 Fax (610) 367-6800 Website www.columbiaboiler.com Email cbcsales@ptd.net

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

ENERVEX RSV CHIMNEY FAN

ENERVEX RSV CHIMNEY FAN ENERVEX RSV 200-450 CHIMNEY FAN 3000775 06.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731

More information

Bulletin (Jan 2011) And User s Guide

Bulletin (Jan 2011) And User s Guide Bulletin 30 32 (Jan 2011) Unichiller Installation And User s Guide Customer Service If you have questions about Installation, operation and Maintenance of the Unichiller or would like to order replacement

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

RSV Chimney Fan USA CAN. Start Up and Configuration. ... Chapter 5. Maintenance and Troubleshooting... Chapter 6. Job Name: Installer:

RSV Chimney Fan USA CAN. Start Up and Configuration. ... Chapter 5. Maintenance and Troubleshooting... Chapter 6. Job Name: Installer: Installation & Operating Manual RSV Chimney Fan USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

ELECTRONIC FIREPLACE DAMPER

ELECTRONIC FIREPLACE DAMPER ELECTRONIC FIREPLACE DAMPER Model: FSE Low Profile Series The Flue Sentinel Electronic Fireplace Damper is designed to increase the comfort and energy efficiency of residential homes with gas-fired fireplaces.

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2 3002239 RSIF 2014-04-04 Installation and operation manual RSIF power venter READ AND SAVE THESE INSTRUCTIONS! Product information Chapters 1 + 2 Mechanical installation Chapter 3 Electrical installation

More information

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: A. Supply and install modulating and condensing boiler(s) as specified herein. Date:

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

ELECTRONIC FIREPLACE DAMPER

ELECTRONIC FIREPLACE DAMPER ELECTRONIC FIREPLACE DAMPER Model: FSE Series The Flue Sentinel Electronic Fireplace Damper is designed to increase the comfort and energy efficiency of residential homes with gas-fired fireplaces. Consisting

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

M2 Series Startup Form

M2 Series Startup Form M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual EBC 10 Fan Control USA CAN Product Information... Chapter 1+2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova Solo Innova Models 30 and 50 Technical Datasheet Solo Innova Solo Innova is a patented, wood-fired gasification boiler available in two sizes with outputs from 102,500 to 170,700 Btu/hr. Benefits at a

More information

NMG NOZZLE MIX GAS BURNERS

NMG NOZZLE MIX GAS BURNERS INSTRUCTIONS NMG NOZZLE MIX GAS BURNERS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components, by

More information

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 507350-03 3/2016 Supersedes 9/2015 KG 024, 030, 036, 048, 060, 072, 074, 090 (2, 2-1/2, 3, 4, 5, 6 and 7-1/2 Tons) KG 092, 102, 120, 150 (7-1/2, 8 1/2,

More information

Jr. Tech (JT-1, 2, 3) Knowledge Areas

Jr. Tech (JT-1, 2, 3) Knowledge Areas Jr. Tech (JT-1, 2, 3) Knowledge Areas The Jr. Tech Level includes technicians that are just entering the business and are in the beginning stages of their HVAC-R training and development. Over this period

More information

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE:

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE: INSTALLATION INSTRUCTIONS DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System Model: DORGPT-1 NOTE: This guide provides the installer with instructions specific to the Bard Double O-Ring Geo-Prime

More information

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input Product Data 58EFA Horizontal Gas Furnace 50,000 125,000 Btuh Input GAS SUPPLY MANUAL SHUTOFF VALVE SEDIMENT TRAP UNION Carrier presents the 58EFA, a dedicated horizontal gas furnace that excels in the

More information

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED FUEL OIL DAY TANKS SST Series - Engineering Submittal SST Series - Advanced Line Day Tanks Construction: UL 142 aboveground steel tank all seam welded, square, atmospheric tank of heavy gauge steel with

More information

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH 33-44-50 CAH 49-54-70 CAH VARIABLE SPEED AIR HANDLERS DIMENSIONS... 3 TECHNICAL SPECS... 4 INSTALLATION DON TS... 5 INSTALLATION DO S... 6 FREEZE STAT REQUIRED

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M 2004 Lennox Industries Inc. Dallas, Texas KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04 Supersedes 503,249M Litho U.S.A. COMPRESSOR REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMPRESSOR

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING See unit nameplate for manufacturer and address. 506380 01 11/2009 KGA024, 030, 036, 048, 060, 072 (2, 2 1/2, 3, 4, 5, and 6 Tons) KGA092, 102, 120, 150 (7 1/2, 8-1/2, 10, and 12 Tons) KGA180, 210, 240,

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

Tjernlund Side Wall Venting Products

Tjernlund Side Wall Venting Products Tjernlund Side Wall Venting Products Any non-condensing gas or oil fired heater that can be vented by natural draft can be Side Wall Vented with a Tjernlund Power Venter. Power Venters are available in

More information

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC INSTALLATION INSTRUCTIONS GEO PRIME TANK (Patent Pending) GPC Table of Contents General Description 2 Installation 3 Flushing and Purging 5 Initial Start up 7 Adding or Checking Fluid 8 Replacing a Pump

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Service Manual For model N260 - a 2.4 cu. ft., 2-way refrigerator. For model N a 2.4 cu. ft., 3-way refrigerator.

Service Manual For model N260 - a 2.4 cu. ft., 2-way refrigerator. For model N a 2.4 cu. ft., 3-way refrigerator. Service Manual For model N260 - a 2.4 cu. ft., 2-way refrigerator. For model N260.3 - a 2.4 cu. ft., 3-way refrigerator. NORCOLD, Inc. P.O. Box 4248 Sidney, OH 45365-4248 Part No. 619260A (4-98) Table

More information

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA Navien America Inc. Specification Details for the Navien models: CR-210 CR-210A For Indoor Installation Only For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA,

More information

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE PFS APPROVED FOR NATURAL GAS OR PROPANE GAS Z21.50-2014 If your plans do not allow for the venting system as outlined previously in the installing chimney/vent

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL INDIRECT GAS-FIRED DUCT FURNACE

INSTALLATION, OPERATION & MAINTENANCE MANUAL INDIRECT GAS-FIRED DUCT FURNACE INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR COMMERCIAL APPLICATIONS IN-KI INDOOR SERIES RT-NO ROOFTOP SERIES WWW.RENEWAIRE.COM IMPORTANT SAFETY INFORMATION WARNING WARNING Risk of fire or explosion!

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL-

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL- SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 www.compu-aire.com Table of Contents

More information

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000

More information

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004 Engineering Bulletin Gas Heat for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-PRB010-EN Preface Gas heat can be a good heating option for any of the following applications: Climates

More information

Design Guide 111 9/25/2008. Eclipse Winnox Burners WX Series Version 1

Design Guide 111 9/25/2008. Eclipse Winnox Burners WX Series Version 1 Design Guide 111 9/25/2008 Eclipse Winnox Burners WX Series Version 1 Co p y r i g h t Disclaimer Notice Copyright 2005 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by

More information

Introduction Engineering and Design Manual

Introduction Engineering and Design Manual Genesis Engineering and Design Manual Introduction Engineering and Design Manual Dear A. O. Smith Customer, This Engineering and Design Manual has been written to aid in designing and specifying A. O.

More information

ELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b

ELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b PRODUCT SPECIFICATIONS OIL FURNACES El083b ELITE SERIES Lo-Boy Bulletin No. 20629 February 209 Supersedes July 202 MODEL NUMBER IDENTIFICATION el O 83 bf 0/4 p 60 AFUE - 83% Heating Input - 0,000 to 5,000

More information

Installation Instructions

Installation Instructions Installation Instructions Blower Packages For Gas Furnaces KCBBA00TG KCBBA00TG NOTE: Read the entire instruction manual before starting the installation. INTRODUCTION When upgrading a Coleman, Intertherm,

More information

TABLE OF CONTENTS. Site preparation 2 Placement. 2 Chimney and stove pipe connections. 2

TABLE OF CONTENTS. Site preparation 2 Placement. 2 Chimney and stove pipe connections. 2 TABLE OF CONTENTS SECTION TITLE PAGE 1. SITE PREPARATION AND INSTALLATION Site preparation 2 Placement. 2 Chimney and stove pipe connections. 2 Installation. 3 Water supply and return.. 3 Pressure/relief

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number: Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,

More information

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using

More information

PBG PACKAGED GAS BURNER

PBG PACKAGED GAS BURNER INSTRUCTIONS PBG PACKAGED GAS BURNER WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS FOR USE WITH ALL FORCED AIR SYSTEMS SEQUENCE OF OPERATION The AUTOFLO Model s 200P, 800BP and 97 Humidifiers use the evaporative by-pass principal to add moisture into the return air duct of your central

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) Installation Manual For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) N404M.3 (128 liter 3-way operation with LP gas, 240 volts AC, or 12

More information

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ... Installation & Operating Manual RSIF Power Venter USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter

More information

TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS)

TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS) See unit nameplate for manufacturer and address. 506003 01 5/2009 Supersedes 1/2008 TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS) TGA090, 102, 120, 150, TGA120 SHOWN (7

More information

RG7D 1-Stage Heat Series

RG7D 1-Stage Heat Series TECHNICAL SPECIFICATIONS RG7D 1-Stage Heat Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace

More information

MFC Series Boiler Vent and Combustion Air Guide

MFC Series Boiler Vent and Combustion Air Guide Pre-Installation Application Guide MFC Series Boiler Vent and Combustion Air Guide Applies to Models 3000 through 10000 Exhaust venting, combustion air and piping Requirements for MFC Series boilers Other

More information