Hebei Datang International Wangtan Power Company, China

Size: px
Start display at page:

Download "Hebei Datang International Wangtan Power Company, China"

Transcription

1 Analysis of the Performance of Induced Draft (ID) Fans at a 600MW Thermal Power Unit before and after Installation of MV Variable Frequency Drives (VFD) Hebei Datang International Wangtan Power Company, China Authors: Gao Zhenhua; Lu Changhai Abstract: This article evaluates the results vis-à-vis energy savings, and enhancement of reliability after the installation of Variable Frequency Drives (VFD) at the Hebei Datang International Wangtan Power Company, China (WPCL) 1

2 1. Foreword 1.1 Introduction of parameter WPCL commissioned two thermal power units of 600 MW each (2x600MW). The boilers were all supplied by Harbin Boiler Company Limited and each boiler comprises of two rotary air pre-heaters and two AN37e6 (V19+4) type adjustable Axial Flow type Induced Draft (ID) Fans (IDF) manufactured by Chengdu Electric Power Equipment Co. The motors are made by Shanghai Electrical machinery plant. The primary parameters of the induced draft fan and motor are as follows: ID Fan Parameters Motor Parameters Particulars Unit Design Parameter Particulars Unit Design parameter Type Static-Blade Axial-flow Shanghai Electrical Manufacturer Fan Machinery Co. Specification AN37e6(V19+4 ) Specification YKK Manufacturer Chengdu Electric Power Equipment Co. Rated speed r/min 597 Control Mode Inlet Flow Adjustable Rated power kw 3,800 Max Air quantity m 3 /s Rated voltage kv 6 Air pressure Pa Rated current A 448 Shaft Power kw 2332 Power factor Max Permitted Medium Temp C Efficiency % 96.7 Bearing Medium kg/m Lubrication Density Method Forced Oil Cycle Rotation speed r/min 585 Fan Efficiency % 84 2

3 1.2 Analysis of energy consumption for induced draft fan Units #1 and #2 of WPGCL have been put into operation on December 7, 2005 and December 28, It was observed that the capacity of the boiler ID Fan was considerably higher than required. When the unit operated at full load, the ID Fan ran at 60% to 70% of its rated load. The actual current of the fan was only 60% of the rated current when the fan was operating at maximum power output. Data showed that the type of fan was not suitable and the induced draft fan operated within a low power output area over a long period of time, thereby increasing power consumption, raising coal consumption of unit and increasing costs of operating the unit. In order to improve the operating environment of the ID fan, and reducing the electricity consumption of the unit the North China Electric Power Academy of Science (NCEPAS) carried out a series of tests on the induced draft fan of 1# unit. Primary data of spot tests are as follows: Test table of the performance of the fan at typical working condition is as follows: 3

4 # Name Unit Operating condition1 Operating condition2 Operating condition 3 Operating Operating condition 4 condition 5 1 Unit load MW Volume flow of #1 fan M 3 /s Mass Flow Rate of #1 fan kg/s Pressure of #1fan Pa Pressure Energy of #1 fan N M/kg Interior input power of #1 fan kw Operating efficiency of #1 fan % Volume flow of #2 fan M 3 /s Mass Flow Rate kg/s Total press of #2fan Pa Pressure energy of #2 fan N M/kg Interior input power of #2 fan kw Operating efficiency of #2 fan % As per the test data, it was observed that the high capacity of the boiler IDF is resulting in the poor operating efficiency of the fan and substantially higher energy consumption. A considerable negative impact on energy conservation was noted. Furthermore, the operational performance of the two units was mismatched; the output of #1 fan is far higher that the output of the #2 fan. This poses a threat to the stable operation of the units. At the unit load 600MW: The current of #2 fan is 313A~317A The max actual current of each unit is not more than 340A The Max Actual Power of the fan is: 340A 6kV = 2986KW 4

5 Redundant capability is: 3800kW 2986kW = 814kW At a Unit Load of between 300MW to 350MW: The current of #2 fan is 205A~225A The max actual current of each unit is not more than 225A The Max Actual Power of the fan is: 225A 6kV = 1975kW Redundant capability is: 3800kW 1975kW = 1825kW With modification using a VFD it would be possible to: Fix the opening of the stable blade at total opening degree (100%) Minimize resistance to flue gas flow Decrease system throttle losses Raise the efficiency of the fan Upon changing throttling adjustment to shifting adjustment there could be: An effective avoidance of flue gas surges Increased stability of the fan Increased reliability of the fan As per the analysis above pertaining to the stability, reliability and operating costs of the fan, it was concluded that the fan would be suitable to be driven by a VFD 1.3 Operating stability analysis of the fan From the operating data of the fan it was observed that with a unit load 70% of the rated load, the fan usually operates in an unstable manner. When the unit operated at a variable load condition, the fan often stalled or surged - this situation was detrimental to the operational safety and life of the fan. 1.4 Selecting the appropriate VFD Considering the relationship between the stability of the fans and the economical operation 5

6 of the unit, earlier generation VFDs converted standard frequency (SF) to variable frequency (VF), or vice versa. In order to do this, one of the ID Fans needed to be stopped and therefore there was a 50% decrease in the unit s output. This situation negatively impacted the safety and economical operation of the unit. In view of this, when a VFD is selected, an important feature to consider is the ability of the VFD to switch operating conditions while the equipment is operational. In order to satisfy this condition we selected the DHVECTOL VFD provided by DHC. 2. Proposal to use the appropriate DHC VFD 2.1 The unit must operate stably after installation of VFD One VFD was installed per ID fan with control unit housed in a temperature-controlled environment located at a permitted distance of within 1,000 meters of the two fans. Entries and configurations for the operation of VFDs were made in the DCS system being used in the plant. Operating personnel can adjust the speed of the ID fan or put the VFD into operation by means of the DCS system. It can also send automatic controlled messages for the fan in case of indicated negative pressure in the boiler. This will result in controlling the speed of the fans and adjust boiler pressure. 6.0kV Main Breaker QF VFD Isolator QS1 Contactor KM1 Contactor KM2 Isolator QS2 M 6.0kV MOTOR Bypass Breaker QF2 6

7 Figure 1: Primary circuit figure of the fan VFD In order to avoid operational errors, interlocking is provided between the VFD contactor (KM2) and the bypass breaker (QF2) of the VFD, so that only one switch can be activated at a time. 2.2 VFD Logic Start Main breaker connected VFD fault Yes VFD running No Request runnig Reset Adjust speed DCS sends running instruction Continue Yes No Pre-charging Stop Finish pre-charging Yes Turn on main breaker No Main breaker is unconnected End Figure 2: the operating procedure to start and stop the VFD 2.3 Mode of fan operation after installation of VFD Existing interlocks and protection logic is maintained even after installation of the VFDs. For better control, a switch on the control panel in the control room is provided to change over 7

8 between standard frequency and variable frequency. The switch can be operated as per requirement even when the VFD is running. In order to ensure smooth operation, only one of the two permissible modes to control the ID fans this is, through VFD or through static blade is possible. This is done by providing appropriate interlocks. Operation to start the fan VFD: Before starting the VFD, QF2 is to be put into open position (off) and that QS1, QS2 are in closed position (on). When the self-diagnostic result of the VFD is indicated as normal, the local panel indicates that the VFD is ready for start Upon issuing the start command at the DCS the main breaker QF will close (on) When the VFD detects the switch has been closed, it sends a high-voltage ready message and request run message to DCS The VFD starts up with 10Hz (preset as the minimum start frequency) after 5 seconds If the fan is required to startup with standard frequency, the procedure is to: Switch-off the 6kV power source switch Put the switch to test position Switch-off the breakers QS1 and QS2 (disconnected position) Set the bypass switch QF2 to closed (on) position Close the Main breaker QF (On position) For the Operation to stop the ID Fan VFD normally: Using the DCS: o Gradually decrease the frequency of the VFD to 10Hz before stopping the VFD o Gradually close the stable blade open degree to 0 o Issue stop command at the DCS to stop VFD operation In case emergency shutdown of the VFD is required, the DCS will issue emergency 8

9 stop command The VFD controls the VF-SF/SF-VF switchovers during normal operation It is essential to test the ID Fans to know corresponding values between VFD Frequency (in Hz) and Static Blade opening degree (in ) In the event of VFD failure or bypass, the DCS uses the predetermined relationship curve between VFD Frequency and Static Blade opening degree to ensure boiler pressure remains stable by closing the Static Blade to a degree that corresponds to the frequency of the VFD at the point of failure FAN Fan 2 Figure 3: Relationship Curve between VFD Frequency (Hz) and Static Blade Opening Degree 9

10 3. Comparison of Parameters after installation of VFD 3.1 Safety and stability analysis of the fan after installation of VFD With direct-drive startup at standard frequency, the starting current exceeded 2600A and start time exceeded 8 seconds With startup through VFD, the electric motor startup was considerably smoother due to the gradual increase in current. There was also no surge on account of inrush current leading to overall system stability, reduced electro-mechanical stresses on the equipment and therefore an extended working life of the motor. After installation of the VFD: The control mode of the ID fan changed from throttling to frequency converting A decrease of loss of throttle was observed An Improvement in the performance curve of the fan due to variable speed adjustment was noted A head difference caused by the fixed pressure adjustment during working condition was removed The Pressure head of the fan and the pressure head of the system matched perfectly There was elimination of fan instability when the system resistance line was located above the stall line of the performance curve There was a decrease in the chances of blade-fatigue cracks developing during unstable fan operation The phenomenon of stall speed of the two fans was avoided which greatly enhanced the operating safety of the boiler In order to ensure the smooth operation of VFDs for use with ID Fans, the VF-SF switchover function was thoroughly examined and tested. 10

11 The momentary loss of power to the electric motor during switchover impacted the rotating speed of the fan. Thus, the negative pressure in the boiler did fluctuate, but well within permissible limits. The test results at 450MW load showed that a certain degree of positive pressure in the boiler during the SF-VF switchover process was found, but again within permissible levels. In the event that no human intervention occurs, the automatic system was able to control operations during the SF-VF switchover. The initial rotating speed was high therefore the impact on the negative pressure in the boiler was low. In order to test the disturbance to the boiler when the VFD switched automatically, we simulated a catastrophic fault and checked the operation of the fans and boiler. All operations continued in a stable manner and with minimal impact to the boiler. 3.2 Operating Cost Analysis The energy conservation effect is extremely notable through the modification of the fan VFD in our company, now we compare the test data which partial get before the modification and the other get after the modify of the fan VFD: 1. Operating Parameters at 600MW (100%) Load Parameter of #1 fan Parameter of #2 fan Current A Power consumption kw h Current A Power consumption kw h SF mode VF mode Operating parameter on 450MW load 11

12 Parameter of #1 fan Parameter of #2 fan Current A Power consumption kw h Current A Power consumption kw h SF mode VF mode Operating parameter on 300MW load Parameter of #1 fan Parameter of #2 fan Current A Power consumption kw h Current A Power consumption kw h IF mode VF mode t/h 800t/h 1000t/h power consumption on FF mode of #1 power consumption on VF mode of # t/h 800t/h 1000t/h power consumption on FF mode of #2 power consumption on VF mode of #2 Figure 4: Power consumption comparing of the fan on the same load 12

13 At a loading rate of 75% in a year, the electricity each boiler conserves every year after installation of the VFD is: ΔP= [( 3.I 1. V.cosø - 3.I 2. V.cosø) + ( 3.I 3. V.cosø - 3.I 4. V.cosø)] = 19,403,400 kw h In the equation above, I 1: Current of FAN-1 when unit is operating at 75% of rated load at Standard Frequency I 2 : Current of FAN-1 when unit is operating at 75% of rated load at Variable Frequency I 3: Current of FAN-2 when unit is operating at 75% of rated load at Standard Frequency I 4 : Current of FAN-2 when unit is operating at 75% of rated load at Variable Frequency V: Voltage; Cos : Power factor,

14 Coal consumption reduction was as follows: B g = (P 1 -P 2 ) f = 0.782g/ kw h In the equation above: P 1: Average power consumption before installing the VFD (at 75% loading rate) P 2 : Average power consumption after installing the VFD (at 75% loading rate) f: Coal consumption rate taken as 3.4g/kWh Each boiler conserves coal every year: B= F Δb g = 3, MT In the equation above, F: Generating capacity of the total year when (loading rate at 75%) Δb g : coal consumption difference between the VFD used before and after; 4. Related Testing Data after the fan installed the VFD 4.1 IF-VF switchover test of #1 fan VFD of #1 boiler(on July 18,2008) Operating parameter before Test Unit load: 500MW Parameter Name Value Boiler Pressure: -133Pa Fan-1 Current A FAN-2 Current of #2 fan 281.7A Boiler Oxygen Content 3.8%, 3.2% FAN-1 Opening degree of Static Blade 59.95% FAN-1 Opening degree of Static Blade 60.6% Steam temperature Automatic 14

15 Water level Coal Firing Automatic Automatic Test Procedure: 1. The output command of FAN-1 VFD was set at 50Hz 2. DCS SF-VF switchover command was given in the control room 3. After a programmed time-delay of 5 seconds, the VFD switched to VF mode 4. During the switchover, FAN-1 current decreased from 276.7A to 131A and then came back to 206A and operated stably at this level 5. Negative pressure in the boiler increased from -139Pa to 74Pa then returned to normal 6. No obvious impact to the other primary operating parameters was noted Curve of IF-VF switchover Test on July 18, 2008 Power Output of the Unit (in MW) IDF-1 Motor Current IDF-2 Motor Current Boiler Pressure IDF-1 Static Blade Position IDF-2 Static Blade Position VFD-1 Output Frequency 15

16 VFD-2 Output Frequency Tests proved that the VFD was able to meet operating demand the switchover from SF-VF or VF-SF was made with the fan running. 5. Summary The VFDs at our Wangtan Power Generation Co., Ltd operated stably. 1. The VFD system was delivered, installed and commissioned without posing any challenges or problems 2. The installations not only avoided the phenomenon of stall speed of the two fans, but also greatly enhanced the operating safety of the boiler 3. No change to the infrastructure or setup was required except the construction of an enclosure to house the VFDs at remote location within the site premises 4. Intensive training for maintenance staff for VFD operations was not required. The learning curve for operation and maintenance was not difficult 5. The ability of the Dongfang-Hitachi DHVECTOL VFD to switch from Standard Frequency to Variable Frequency (and vice versa) while the equipment is operational (as compared to other VFDs on the market) was very useful for increasing the Load Factor of the unit and also avoided tripping of the fan The results of installing VFDs at our plant were found to be excellent. Along with the benefit of extending the life of our equipment and lowering maintenance costs, we have found substantial saving in energy consumption and have been recognized for our efforts in reducing overall plant Auxiliary Power Consumption and meeting our commitments to the environment by reducing emissions. Address: Gao Zhenhua, Electricity Generation Department, Wangtan Power Generation Co. Ltd, Donghai Road, Harbor Development Area, Tangshan, Hebei province

17 For more details please contact: Epsilon Asia Group, X-29 Hauz Khas, New Delhi , India T: ; F: Epsilon Engineering (Thailand) Co. Ltd. Level 29, The Offices at Centralworld, 999/9 Rama-I Road Bangkok 10330, Thailand T: ; F: Neelesh@epsilonasia.com 17

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

E-16 Main Engine Remote Control System

E-16 Main Engine Remote Control System Guideline No.E-16 (201510) E-16 Main Engine Remote Control System Issued date: 20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

Service Instructions for use by heating contractor

Service Instructions for use by heating contractor Service Instructions for use by heating contracr Please file in Service Binder Vitronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating

More information

GPPS-2017-Put 4 digit paper number here

GPPS-2017-Put 4 digit paper number here Proceedings of Shanghai 2017 Global Power and Propulsion Forum 30 th October 1 st November, 2017 http://www.gpps.global GPPS-2017-Put 4 digit paper number here THE RESEARCH ABOUT INFLUENCE OF WET STEAM

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

E-17 Flammable Gas Detection and Alarm System

E-17 Flammable Gas Detection and Alarm System Guideline No.E-17 (201705) E-17 Flammable Gas Detection and Alarm System Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Microgrid Fault Protection Based on Symmetrical and Differential Current Components Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System White Paper Project: Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System Version 1, Revision 2, August 4, 2016 Jim Jenkins, William Goble The document was prepared using

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

FIL-SPL Flow-through heater for central heating USER MANUAL

FIL-SPL Flow-through heater for central heating USER MANUAL FIL-SPL Flow-through heater for central heating with 0-10 V EP 15-30 control unit USER MANUAL Kaukora LTD. D106159 r3.0 Contents 1. Important information... 5 Safety information... 5 General... 5 Marking...

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

PERFORMANCE EVALUATION AND RECURRING JAMMING PROBLEM ANALYSIS OF AIR PREHEATER IN COAL-FIRED POWER PLANTS

PERFORMANCE EVALUATION AND RECURRING JAMMING PROBLEM ANALYSIS OF AIR PREHEATER IN COAL-FIRED POWER PLANTS PERFORMANCE EVALUATION AND RECURRING JAMMING PROBLEM ANALYSIS OF AIR PREHEATER IN COAL-FIRED POWER PLANTS M.Srinivasa Rao M.Tech Student, Department of Mechanical Engineering, GMRIT, Srikakulam, AP, India.

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

APC APPLICATION NOTE #119

APC APPLICATION NOTE #119 #119 InRow RP-CW and InRow RP-DX Environmental Control By Henry Jespersen Abstract The primary function of the InRow RP product is to cool air from the hot aisle and deliver it to the cold aisle at the

More information

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans A look at two accepted technologies.. System Characteristics In general, the pressure developed by a fan is a function

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

WHAT IS A BOILER? BOILER IS AN EQUIPMENT WHICH PRODUCES STEAM AT THE REQUIRED PRESSURE AND TEMPERATURE. BOILER DESIGN, MANUFACTURE & INSTALLATION ARE

WHAT IS A BOILER? BOILER IS AN EQUIPMENT WHICH PRODUCES STEAM AT THE REQUIRED PRESSURE AND TEMPERATURE. BOILER DESIGN, MANUFACTURE & INSTALLATION ARE Your Logo Here TRAINING ON BOILERS PRESENTED AT M/S. MAGADI SODA COMPANY, MAGADI, KENYA LIMITED 1 WHAT IS A BOILER? BOILER IS AN EQUIPMENT WHICH PRODUCES STEAM AT THE REQUIRED PRESSURE AND TEMPERATURE.

More information

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b 6th International Conference on Information Engineering for Mechanics and Materials (ICIMM 2016) New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b 1 Department

More information

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans PARAG FANS & COOLING SYSTEMS LTD. Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans Registered Office & Works Plot No.1/2B & 1B/3A, Industrial Area No.1 A.B.Road, Dewas 455001 (M.P.)

More information

Boiler Technical Specifications (2013)

Boiler Technical Specifications (2013) ACT Bioenergy Boiler Dimensions 0.5-0.85 Million Btu/h (150-250kW) Model CP500 CP600 CP750 CP850 Heat Output in MBtu/h (kw) 510 (150) 610 (180) 750 (220) 850 (250) Height ft (mm) 6 1 (1855) 6 1 (1855)

More information

Application of Fuzzy Control in Central Air-conditioning Terminal Units Energy-saving

Application of Fuzzy Control in Central Air-conditioning Terminal Units Energy-saving www.ijcsi.org 123 Application of Fuzzy Control in Central Air-conditioning Terminal Units Energy-saving Yanqiu Zhao 1, Yingli Lv 1, Yong Gu 1, Shucheng Liu 2 1 Department of Electrical Engineer, Hebei

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

IQ-Sense. 2/2 Introduction. 2/3 IQ-Sense photoelectric sensors. 2/5 IQ-Sense ultrasonic sensors. 2/6 4 IQ-Sense sensor module for ET 200S

IQ-Sense. 2/2 Introduction. 2/3 IQ-Sense photoelectric sensors. 2/5 IQ-Sense ultrasonic sensors. 2/6 4 IQ-Sense sensor module for ET 200S / Introduction /3 photoelectric sensors /5 ultrasonic sensors /6 4 sensor module for ET 00S /6 8 sensor module for ET 00M/S7-300 Introduction Configuration/parameterization Uniform configuration tools

More information

SURGING AND BLOW OUT OF LOOP SEALS IN A CFBC BOILER. By K.K.Parthiban Venus energy audit system

SURGING AND BLOW OUT OF LOOP SEALS IN A CFBC BOILER. By K.K.Parthiban Venus energy audit system SURGING AND BLOW OUT OF LOOP SEALS IN A CFBC BOILER By K.K.Parthiban Venus energy audit system This is a very interesting case to us, wherein we had the opportunity to resolve the problem of surging and

More information

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants Govind Rengarajan, P.E.CEM, Dan Taylor CMI Energy, Erie PA 1651 Bernd Pankow P.E, Pankow Engineering Abstract Combined

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART)

C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART) C&I SYSTEM DIAGNOSTICS WITH SELF MONITORING AND REPORTING TECHNOLOGY (SMART) Suneel kumar P I Shravan Kumar Seema Deo Bhanu Kumar Raine Dy.General Manager, Dy.Manager Sr.Manager Manager NTPC RSTPS NTPC

More information

ANNEX A-1 GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES BOILER BALANCE OF PLANT STEAM TURBINE GENERATOR MISCELLANEOUS - GEOTHERMAL EXTERNAL

ANNEX A-1 GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES BOILER BALANCE OF PLANT STEAM TURBINE GENERATOR MISCELLANEOUS - GEOTHERMAL EXTERNAL ANNEX A-1 GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES Boiler Piping System 0500-0620 Condensing System 3110-3199 Circulating Water Systems 3210-3285 Waste Water (zero discharge) 3290-3299 Condensate

More information

PFS Single stage axial fan The axial fan for modern boiler plants

PFS Single stage axial fan The axial fan for modern boiler plants PFS Single stage axial fan The axial fan for modern boiler plants This large axial fan, type PFS- 400-236, was installed in 1987 at the Salmisaari coal-fired power station in Helsinki, Finland. The photo

More information

How to Cut Chiller Energy Costs by 30%

How to Cut Chiller Energy Costs by 30% How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation

More information

CLIMASTER ZCF AIR HANDLING UNITS

CLIMASTER ZCF AIR HANDLING UNITS CLIMASTER ZCF AIR HANDLING UNITS From 1 September 2013, EXHAUSTO has taken over Novenco s activities within sales and production of land-based climate control systems. Inquiries relating to the products

More information

ADC150 Automatic Draft Control

ADC150 Automatic Draft Control Installation & Operating Manual ADC150 Automatic Draft Control USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...

More information

Boiler Draft Equipment

Boiler Draft Equipment Boiler Draft Equipment Learning Outcome When you complete this module you will be able to: Discuss, sketch and describe the basic equipment used to supply combustion air to a boiler furnace. Learning Objectives

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices

Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices Cold Weather Preparedness RF Criteria For Plant Visits: Generating facilities that experienced repeated freezing or cold weather

More information

AXIAL FAN User s manual. Quiet-dMEV 100 DC.

AXIAL FAN User s manual. Quiet-dMEV 100 DC. AXIAL FAN User s manual Quiet-dMEV 100 DC www.ventilation-system.com CONTENTS Delivery set... 6 Brief description... 6 Operating guidelines... 6 Designation key... 7 Installation and set-up... 7 Fan options...

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660 Selectivity Adjustable by Means of - High Pass Frequency Filter - Gain - Threshold Different Adjustments for Different Conditions (e.g. According Fuel or Combustion Technology) Possible, to be Activated

More information

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option Description of options Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M 4189340401D SW 1.4X.X Description of option Functional description DEIF A/S Parameter list DEIF A/S,

More information

EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER

EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER Cinzia Buratti, Elisa Moretti and Michele Urbani Department of Industrial Engineering, University of Perugia, via G. Duranti 67, 06125 Perugia,

More information

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Abstract Axial flow fans, while incapable of developing high pressures, they are well suitable for handling large volumes of air at relatively

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Axial intelligent fan USER S MANUAL

Axial intelligent fan USER S MANUAL Axial intelligent fan USER S MANUAL CONTENTS Delivery set... 6 Technical data... 6 Installation and set-up... 9 Connection to power mains... 11 Operation guidelines... 11 Unit control... 12 Storage and

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

- Essay Control Functions and Benefits

- Essay Control Functions and Benefits - Essay Control Functions and Benefits E 005 07/01 A hydronic heating control system performs many complex and important functions. Each of these functions provide benefits that make the system comfortable,

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

Improved Dryer Control

Improved Dryer Control Improved Dryer Control Kenneth C. Hill President Kadant Johnson Systems Division David Vijh Senior Process Control Engineer Technical White Paper Series EXECUTIVE SUMMARY Significant improvements in dryer

More information

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc Important Considerations When Selecting a Fan for Forced Air Cooling By: Jeff Smoot, CUI Inc Designing an appropriate thermal management solution requires a systemic approach; each component on a circuit

More information

Axial flow fan AXICO ANTI-STALL

Axial flow fan AXICO ANTI-STALL Product data sheet: AXICO ANTI-STALL Axial flow fan AXICO ANTI-STALL Model FPAC and FPMC axial flow fans with controllable pitch blades. Air flow range: 3-110 m³/s (10.000 400.000 m³/h). Pressure rise:

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Application of ALPHA Inverter in the Transformation Plan of Central Air-Conditioning

Application of ALPHA Inverter in the Transformation Plan of Central Air-Conditioning Application of ALPHA Inverter in the Transformation Plan of Central Air-Conditioning I. Principle of the Energy-Conservation Transformation of the Central Air-Conditioning System 1. System Analysis In

More information

Boiler Venting. Definitions, Theory and Applications. Presented by: Jason Geagan, National Sales Manager US Draft Co Fort Worth, TX

Boiler Venting. Definitions, Theory and Applications. Presented by: Jason Geagan, National Sales Manager US Draft Co Fort Worth, TX Boiler Venting Definitions, Theory and Applications Presented by: Jason Geagan, National Sales Manager US Draft Co Fort Worth, TX Gas Appliance Listings ANSI Z21 - Categorized Appliances Gas fired low

More information

Flostop TS D7E and A8E. Operation Manual

Flostop TS D7E and A8E. Operation Manual Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

Electro-Sentry. Users Manual

Electro-Sentry. Users Manual Electro-Sentry Users Manual 2. To view an individual point, e.g. Speed just touch that point and it will display a graph showing the 45 min. of activity. Viewing a Leg: 1. Touch the desired leg, e.g. East

More information

Data Bulletin. Determining the Cause of AFCI Tripping Class 760

Data Bulletin. Determining the Cause of AFCI Tripping Class 760 Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

Variable Refrigerant Flow (VRF) Systems

Variable Refrigerant Flow (VRF) Systems Variable Refrigerant Flow (VRF) Systems Flexible Solutions for Comfort Carrier Corporation Syracuse, New York January 2013 TABLE OF CONTENTS INTRODUCTION... 2 VRF TECHNOLOGY... 2 ADVANTAGES OF A VRF SYSTEM...

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options Table 4 External Maintenance Switch Configuration Options External Maintenance Switch Options Installed with Interlock Option Option Auxiliary Contact Status open = On Test position or Maintenance position,

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

Table 1. Serie of Digital Room Thermostats.

Table 1. Serie of Digital Room Thermostats. Digital Room Thermostats INSTALLATION MANUAL APPLICATION DR is a serie of Digital Room Thermostats, provides a single stage, temperature control. Table 1 shows all the available models. All models can

More information

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants GRC Transactions, Vol. 40, 2016 Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants Jason Project Engineer, Vooner FloGard Corporation, Charlotte

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

Improving Boiler Stability Through Advanced Regulatory Control

Improving Boiler Stability Through Advanced Regulatory Control Improving Boiler Stability Through Advanced Regulatory Control Jacques Smuts, OptiControls, Inc., Houston, Texas KEYWORDS Boiler Control Systems, Advanced Regulatory Control ABSTRACT Coal-fired power plants

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override Date Code - Data rochure oiler Control 265 D 265 10/03 The tekmar oiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements.

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

Evaluation Report 509

Evaluation Report 509 Printed: June 1987 Tested at: Lethbridge ISSN 0383-3445 Group 5i Evaluation Report 509 Prairie Pride TR-36 Series Ventilation Fans A Co-operative Program Between ALBERTA FARM MACHINERY RESEARCH CENTRE

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Heating and D.h.w. Controller RVL482 Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International

More information

Air flow management tutorial session. ACC Users Group 8 th Annual Conference Dallas, 4 October 2016 Sander Venema Howden Netherlands

Air flow management tutorial session. ACC Users Group 8 th Annual Conference Dallas, 4 October 2016 Sander Venema Howden Netherlands tutorial session ACC Users Group 8 th Annual Conference Dallas, 4 October 2016 Sander Venema Howden Netherlands Howden Group 2016 Introduction Basic definitions Basics of fan performance Basics of fan

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls June 25, 2018 Touchscreen Description Plate Kit Enclosure TS series touchscreen kits provide a human machine interface (HMI) with a Siemens

More information

F Operating Manual. ESS0460-H119 PV Module Solar Soaking Chamber

F Operating Manual. ESS0460-H119 PV Module Solar Soaking Chamber F08-064 Operating Manual ESS0460-H119 PV Module Solar Soaking Chamber 12/19/2008 Thank you for your purchase. We are confident you will be completely satisfied with your new system. If for any reason you

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut Featuring Ozone-safe HFC134a Hitachi Centrifugal Chillers NEW GXG-S Series GSG-S Series Debut Centrifugal Chiller New GXG-S, GSG-S Series Debut High-efficiency New series Centrifugal Chillers that use

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

tech-info Continuous centrifugals of the K3000 series Fields of application: The BMA continuous centrifugals of the

tech-info Continuous centrifugals of the K3000 series Fields of application: The BMA continuous centrifugals of the tech-info Continuous centrifugals of the K3000 series Fields of application: The BMA continuous centrifugals of the new K3000 series are used in the cane and beet sugar industries, and also in sugar refineries.

More information

Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products. Product overview

Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products. Product overview Product overview 1 Company Profile Yantai Oceanair Refrigeration & Air-Conditioning Co.,Ltd. was established in 2004 and has been listed on the New OTCBB (Stock Code: 831870). We are mainly specialized

More information

Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode

Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode International Conference on Civil, Transportation and Environment (ICCTE 2016) Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode Guangyao Liu1,a, Xiewei Cheng2,b,

More information

6800 Design Envelope Booster. Technical overview

6800 Design Envelope Booster. Technical overview 6800 Design Envelope Technical File No: 100.30in Date: may 26, 2014 Supersedes: 100.30in Date: march 17, 2014 contents 1. Product introduction 4 Summary 4 Background 4 Benefits 4 2. Product data 5 Nomenclature

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Appendix B9 Geothermal Unit Cause Codes

Appendix B9 Geothermal Unit Cause Codes Appendix B9 Geothermal Unit Cause Codes GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES (Unit Codes 800 899) Cause Code BOILER Ranges Page No. Boiler Piping System 0500-0620 B-GE-2 BALANCE OF PLANT

More information

DC Inverter Smart VRF Products(R410A)

DC Inverter Smart VRF Products(R410A) DC Inverter Smart VRF Products(R410A) General Description What is DC Inverter Smart? Inverter Smart system is YDS system: 1. With DC inverter compressor; 2. Condensing unit and heat pump type; 3. It is

More information

Electric Coils. Blower Coils. Product Information

Electric Coils. Blower Coils. Product Information Product Information General Information Electric heat coils are an available accessory for use with Price blower coil units. The electric heating coils have been specific ally designed to suit Price blower

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information